Toshiba RAV-RM2801DTP-E, RAV-RM2241DTP-TR, RAV-RM2801DTP-TR, RAV-SM2244AT8-A1, RAV-SM2804AT8-A1 Service Manual

...
FILE NO. SVM-19066
SERVICE MANUAL
AIR-CONDITIONER
SPLIT TYPE
INDOOR UNIT <DIGITAL INVERTER>
Concealed Duct High Static Pressure Type
RAV-RM2241DTP Series RAV-RM2801DTP Series
R32 or R410A
CONTENTS
- 2 -
Definition of Qualified Installer or Qualified Service Person....................... 4
Warning Indications on the Air Conditioner Unit .......................................... 6
Precaution for Safety ....................................................................................... 7
Refrigerant (R32 or R410A) ............................................................................ 14
1.
SPECIFICATION ...................................................................................... 16
2.
FAN CHARACTERISTICS ......................................................................... 19
3.
CONSTRUCTION VIEWS (EXTERNAL VIEWS) ...................................... 20
WIRING DIAGRAM................................................................................... 22
4.
5. PARTS RATING ........................................................................................ 23
6.
CONTROL BLOCK DIAGRAM................................................................. 24
1. Indoor Controller Block Diagram .................................................................... 24
6-
2. Control Specifications ...................................................................................... 27
6-
6-3. Indoor Print Circuit Design Board ................................................................... 36
TROUBLESHOOTING .............................................................................. 40
7.
1. Summary of Troubleshooting ......................................................................... 40
7-
2. Check Code List (Indoor) ................................................................................. 45
7-
3. Diagnostic Procedure for Each Check Code (Indoor Unit) ........................... 50
7-
REPLACEMENT OF SERVICE P.C. BOARD .......................................... 63
8.
8-1. Indoor control P.C. Board ............................................................................... 63
8-
2. Fan IPDU P.C. Board (MMC-1610) ................................................................... 68
9.
SETUP AT LOCAL SITE AND OTHERS ................................................ 69
1. Indoor Unit......................................................................................................... 69
9-
2. Setup at Local Site / Others ............................................................................. 79
9-
3. How to Set up Central Control Address Number ........................................... 81
9-
10. ADDRESS SETUP.................................................................................... 83
10 - 1. Address Setup ................................................................................................ 83
10 - 2. Address Setup & Group Control.................................................................... 84
10 - 3. Address Setup (Manual Setting from Remote Controller)........................... 86
10 - 4. Confirmation of indoor unit No. position...................................................... 87
DETACHMENTS ..................................................................................... 88
11.
EXPLODED VIEWS AND PARTS LIST ....................................................100
- 3 -
12.
12 - 1. RAV-RM2241DTP-E(TR), RAV-RM2801DTP-E(TR) ....................................... 100
12 - 2. Drain pump kit (TCB-DP40DPE) .................................................................... 102
12 - 3. Electric Parts .................................................................................................. 103
Original instruction
- 4 -
Please read carefully through these instructions that contain important information which complies with the “Machinery Directive" (Directive 2006/42/EC), and ensure that you understand them.
Generic Denomination: Air Conditioner
Definition of Qualified Installer or Qualified Service Person
The air conditioner must be installed, maintained, repaired and removed by a qualified installer or qualified service person. When any of these jobs is to be done, ask a qualified installer or qualified service person to do them for you. A qualified installer or qualified service person is an agent who has the qualifications and knowledge described in the table below.
Agent Qualifications and knowledge which the agent must have
• The qualified installer is a person who installs, maintains, relocates and removes the air conditioners made by Toshiba Carrier Corporation. He or she has been trained to install, maintain, relocate and remove the air conditioners made by Toshiba Carrier Corporation or, alternatively, he or she has been instructed in such operations by an individual or individuals who have been trained and is thus thoroughly acquainted with the knowledge related to these operations.
• The qualified installer who is allowed to do the electrical work involved in installation, relocation and removal has the qualifications pertaining to this electrical work as stipulated by the local laws and regulations, and he or she is a person who has been trained in matters relating to electrical work on the air conditioners made by Toshiba Carrier Corporation or, alternatively, he
Qualified installer
or she has been instructed in such matters by an individual or individuals who have been trained and is thus thoroughly acquainted with the knowledge related to this work.
• The qualified installer who is allowed to do the refrigerant handling and piping work involved in installation, relocation and removal has the qualifications pertaining to this refrigerant handling and piping work as stipulated by the local laws and regulations, and he or she is a person who has been trained in matters relating to refrigerant handling and piping work on the air conditioners made by Toshiba Carrier Corporation or, alternatively, he or she has been instructed in such matters by an individual or individuals who have been trained and is thus thoroughly acquainted with the knowledge related to this work.
• The qualified installer who is allowed to work at heights has been trained in matters relating to working at heights with the air conditioners made by Toshiba Carrier Corporation or, alternatively, he or she has been instructed in such matters by an individual or individuals who have been trained and is thus thoroughly acquainted with the knowledge related to this work.
Qualified service person
• The qualified service person is a person who installs, repairs, maintains, relocates and removes the air conditioners made by Toshiba Carrier Corporation. He or she has been trained to install, repair, maintain, relocate and remove the air conditioners made by Toshiba Carrier Corporation or, alternatively, he or she has been instructed in such operations by an individual or individuals who have been trained and is thus thoroughly acquainted with the knowledge related to these operations.
• The qualified service person who is allowed to do the electrical work involved in installation, repair, relocation and removal has the qualifications pertaining to this electrical work as stipulated by the local laws and regulations, and he or she is a person who has been trained in matters relating to electrical work on the air conditioners made by Toshiba Carrier Corporation or, alternatively, he or she has been instructed in such matters by an individual or individuals who have been trained and is thus thoroughly acquainted with the knowledge related to this work.
• The qualified service person who is allowed to do the refrigerant handling and piping work involved in installation, repair, relocation and removal has the qualifications pertaining to this refrigerant handling and piping work as stipulated by the local laws and regulations, and he or she is a person who has been trained in matters relating to refrigerant handling and piping work on the air conditioners made by Toshiba Carrier Corporation or, alternatively, he or she has been instructed in such matters by an individual or individuals who have been trained and is thus thoroughly acquainted with the knowledge related to this work.
• The qualified service person who is allowed to work at heights has been trained in matters relating to working at heights with the air conditioners made by Toshiba Carrier Corporation or, alternatively, he or she has been instructed in such matters by an individual or individuals who have been trained and is thus thoroughly acquainted with the knowledge related to this work.
Definition of Protective Gear
- 5 -
When the air conditioner is to be transported, installed, maintained, repaired or removed, wear protective gloves and ‘safety’ work In addition to such normal protective gear, wear the protective gear described below when undertaking the special work detailed in the table below. Failure to wear the proper protective gear is dangerous because you will be more susceptible to injury, burns, electric shocks and other injuries.
Work undertaken
All types of work
Electrical-related work
Work done at heights (50 cm or more)
Transportation of heavy objects Repair of outdoor unit
The important contents concer ned to the safety are described on the product itself and on this Service Manual.
Please read this Service Manual after understanding the described items thoroughly in the following contents (Indications / Illustrated marks), and keep them.
[Explanation of indications]
clothing.
Protective gear worn
Protective gloves ‘Safety’ working clothing
Gloves to provide protection for electricians Insulating shoes Clothing to provide protection from electric shock
Helmets for use in industry Shoes with additional protective toe cap
Gloves to provide protection for electricians
noitanalpxEnoitacidnI
DANGER
WARNING
CAUTION
Indicates contents assumed that an imminent danger causing a death or serious injury of the repair engineers and the third parties when an incorrect work has been executed.
Indicates possibilities assumed that a danger causing a death or serious injury of the repair engineers, the third parties, and the users due to troubles of the product after work when an incorrect work has been executed.
Indicates contents assumed that an injury or property damage (*) may be caused on the repair engineers, the third parties, and the users due to troubles of the product after work when an incorrect work has been executed.
* Property damage: Enlarged damage concerned to property, furniture, and domestic animal / pet
[Explanation of illustrated marks]
noitanalpxEnoitacidnI
Indicates prohibited items (Forbidden items to do) The sentences near an illustrated mark describe the concrete prohibited contents.
Indicates mandatory items (Compulsory items to do) The sentences near an illustrated mark describe the concrete mandatory contents.
Indicates cautions (Including danger / warning) The sentences or illustration near or in an illustrated mark describe the concrete cautious contents.
MEANING OF SYMBOLS DISPLAYED ON THE UNIT
WARNING
(Risk of fire)
Read the OWNER'S MANUAL carefully before operation.
Service personnel are required to carefully read the OWNER'S MANUAL and INSTALLATION MANUAL
before operation.
Further information is available in the OWNER'S MANUAL, INSTALLATION MANUAL, and the like.
This mark is for In case that refrigerant type is R32, this unit uses a flammabl Ir refrigerant leaks and comes in contact with fire or heating there is risk of fire.
R32 refrigerant only. Refrigerant type is written on nameplate of outdoor unit.
e refrigerant.
par
t, it will create harmful gas and
Warning Indications on the Air Conditioner Unit
- 6 -
[Confirmation of warning label on the main unit]
Confirm that labels are indicated on the specified positions If removing the label during parts replace, stick it as the original.
Warning indication Description
WARNING
ELECTRICAL SHOCK HAZARD
Disconnect all remote electric power supplies before servicing.
WARNING
Moving parts. Do not operate unit with grille removed. Stop the unit before the servicing.
CAUTION
High temperature parts. You might get burned when removing this panel.
WARNING
ELECTRICAL SHOCK HAZARD
Disconnect all remote electric power supplies before servicing.
WARNING
Moving parts. Do not operate unit with grille removed. Stop the unit before the servicing.
CAUTION
High temperature parts. You might get burned when removing this panel.
CAUTION
Do not touch the aluminium fins of the unit. Doing so may result in injury.
CAUTION
BURST HAZARD
Open the service valves before the operation, otherwise there might be the burst.
CAUTION
Do not climb onto the fan guard.
Doing so may result in injury.
CAUTION
Do not touch the aluminium fins of the unit. Doing so may result in injury.
CAUTION
BURST HAZARD
Open the service valves before the operation, otherwise there might be the burst.
CAUTION
Do not climb onto the fan guard.
Doing so may result in injury.
PRECAUTIONS FOR SAFETY
- 7 -
The manufacturer shall not assume any liability for the damage caused by not observing the description of this manual.
DANGER
Before carrying out the installation, maintenance, repair or removal work, be sure to set the circuit
Turn off
breaker
Electric
shock hazard
Prohibition
Stay on
protection
breaker for both the indoor and outdoor units to the OFF position. Otherwise, electric shoc result.
Before opening the electrical box cover of the indoor unit or service panel of the outdoor unit, set the circuit breaker to the OFF position. Failure to set the circuit breaker to the OFF position may result in electric shocks through contact with the interior parts. Only a qualified installer (*1) or qualified service person (*1) is allowed to remove the intake grille of the indoor unit or service panel of the outdoor unit and do the work required.
Place a "Work in progress" sign near the circuit breaker while the installation, maintenance, repair or removal work is being carried out. There is a danger of electric shocks if the circuit breaker is set to ON by mistake.
Before opening the inspection opening, set the circuit breaker to the OFF position. Failure to set the circuit breaker to the OFF position may result in injury through contact with the rotation parts. Only a qualified installer (*1) or qualified service person(*1) is allowed to remove the inspection opening and do the work required.
When cleaning the filter (sold separately) or other parts of the indoor unit, set the circuit breaker to OFF without fail, and place a “Work in progress” sign near the circuit breaker before proceeding with the work.
When you have noticed that some kind of trouble (such as when check code display has appeared, there is a smell of burning, abnormal sounds are heard, the air conditioner fails to cool or heat or water is leaking) has occurred in the air conditioner, do not touc the circuit breaker to the OFF position, and contact a qualified service person. Take steps to ensure that the power will not be turned on (by marking “out of service” near the circuit breaker, for instance) until qualified service person arrives. Continuing to use the air conditioner in the trouble status may cause mechanical problems to escalate or result in electric shocks or other failure.
When you access inside of the service panel to repair electric parts, wait for about five minutes after turning off the breaker. Do not start repairing immediately.Otherwise you may get electric shock by touching terminals of high-voltage capacitors. Natur al discharge of the capacitor tak es about five minutes.
When checking the electric parts, removing the cover of the electric parts box of Indoor Unit and/or service panel of Outdoor Unit inevitably to determine the failure, use gloves to provide protection for electricians, insulating shoes, clothing to provide protection from electric shock and insulating tools. Be careful not to touch the live part. Electric shock may result. Only “Qualified service person” is allowed to do this work.
Before operating the air conditioner after having completed the work, check that the electrical partw box cover of the indoor unit and service panel of the outdoor unit are closed, and set the circuit breaker to the on position. You may receive on electric shock if the power is turned on without first conducting these checks.
Place a “Work in progress” sign near the circuit breaker while the installation, maintenance, repair or removal work is being carried out. There is a danger of electric shocks if the circuit breaker is set to ON by mistake.
When checking the electric parts, removing the cover of the electric parts box of Indoor Unit and/or front panel of Outdoor Unit inevitably to determine the failure, put a sign “Do not enter” around the site before the work. Failure to do this may result in third person getting electric shock.
Before operating the air conditioner after having completed the work, check that the electrical parts box cover of the indoor unit and service panel of the outdoor unit are closed, and set the circuit breaker to the ON position. You may receive an electric shock if the power is turned on without first conducting these checks.
If, in the course of carrying out repairs, it becomes absolutely necessary to check out the electrical parts with the electrical parts box cover of one or more of the indoor units and the service panel of the outdoor unit removed in order to find out exactly where the trouble lies, wear insulated heat-resistant gloves, insulated boots and insulated work overalls, and take care to avoid touching any live parts. You may receive an electric shock if you fail to heed this warning. Only qualified service person (*1) is allowed to do this kind of work.
h the air conditioner yourself but set
ks may
W ARNIG
- 8 -
General
Before starting to repair the air conditioner, read carefully through the Service Manual, and repair the air conditioner by following its instructions.
Only qualified service person (*1) is allowed to repair the air conditioner. Repair of the air conditioner by unqualified person may give rise to a fire, electric shocks, injury, water leaks and / or other problems.
Inside the air conditioner are high-voltage areas and rotating parts. Due to the danger of electric shocks or of your fingers or physical objects becoming trapped in the rotating part, do not remove the electrical control box cover of the indoor unit or service panel of the outdoor unit. When work involving the removal of these parts is required, contact a qualified installer or a qualified service person.
Only a qualified installer (*1) or qualified service person (*1) is allowed to carry out the electrical work of the air conditioner. Under no circumstances must this work be done by an unqualified individual since failure to carry out the work properly may result in electric shocks and / or electrical leaks.
When the air conditioner is to be transported, installed, maintained, repaired or removed, wear protective gloves and ‘safety’ wor k clothing.
To connect the electrical wires, repair the electrical par ts or undertake other electrical jobs, wear gloves to provide protection for electricians, insulating shoes and clothing to provide protection from electric shocks. Failure to wear this protective gear may result in electric shocks.
When checking the electric parts, removing the cover of the electric parts box of Indoor Unit and/or front panel of Outdoor Unit inevitably to determine the failure, put a sing "Do not enter" around the site before the work. Failure to do this may result in third person getting electric shock.
Electrical wiring work shall be conducted according to law and regulation in the community and installation manual. Failure to do so may result in electrocution or short circuit.
Use wiring that meets the specifications in the Installation Manual and the stipulations in the local regulations and laws. Use of wiring which does not meet the specifications may give rise to electric shocks, electrical leakage, smoking and/or a fire.
Only a qualified installer (*1) or qualified service person (*1) is allowed to undertake work at heights using a stand of 50 cm or more or to remove the intake grille of the indoor unit to undertake work.
When working at heights, use a ladder which complies with the ISO 14122 standard, and follow the procedure in the ladder’s instructions. Also wear a helmet for use in industry as protective gear to undertake the work.
Before working at heights, put a sign in place so that no-one will approach the work location, before proceeding with the work. Parts and other objects may fall from above, possibly injuring a person below. While carr ying out the work, wear a helmet for protection from falling objects.
When executing address setting, test run, or troubleshooting through the checking window on the electric parts box, put on insulated gloves to provide protection from electric shock. Otherwise you may receive an electric shock.
Do not touch the aluminum fin of the unit. You may injure yourself if you do so. If the fin must be touched for some reason, first put on protective gloves and safety work clothing, and then proceed.
Check earth
wires.
Use forklift to carry in the air conditioner units and use winch or hoist at installation of them. When transporting the air conditioner, wear shoes with protective toe caps, protective gloves and other
protective clothing. When transporting the air conditioner, do not take hold of the bands around the packing carton.
You may injure yourself if the bands should break. Before troubleshooting or repair work, check the earth wire is connected to the earth terminals of the main unit,
otherwise an electric shock is caused when a leak occurs.If the earth wire is not correctly connected, contact an electric engineer for rework.
After completing the repair or relocation work, check that the earth wires are connected properly. Be sure to connect earth wire. Incomplete earthing causes an electric shock. Do not connect earth
wires to gas pipes, water pipes, and lightning rods or
earth wires for telephone wires.
Prohibition of
- 9 -
modification.
Use specified
parts.
Do not bring
a child close
to the
equipment.
Do not modify the products.Do not also disassemble or modify the parts. It may cause a fire, electric shock or injury.
When any of the electrical parts are to be replaced, ensure that the replacement par ts satisfy the specifications given in the Service Manual (or use the parts contained on the parts list in the Service Manual). Use of any parts which do not satisfy the required specifications may give rise to electric shocks, smoking and / or a fire.
If, in the course of carrying out repairs, it becomes absolutely necessary to check out the electrical parts with the electrical parts box cover of one or more of the indoor units and the service panel of the outdoor unit removed in order to find out exactly where the trouble lies, put a sign in place so that no­one will approach the work location before proceeding with the work. Third-party individuals may enter the work site and receive electric shocks if this warning is not heeded.
Insulating measures
No fire
Refrigerant
Connect the cut-off lead wires with crimp contact, etc., put the closed end side upward and then apply a water cut method, otherwis
When performing repairs using a gas burner, replace the refrigerant with nitrogen gas because the oil that coats the pipes may otherwise burn. When repairing the refrigerating cycle, take the following measures.
1) Be attentive to fire around the cycle. When using a gas stove, etc., be sure to put out fire bef ore w ork; otherwise the oil mixed with refrigerant gas may catch fire.
2) Do not use a welder in the closed room. When using it without ventilation, carbon monoxide poisoning may be caused.
3) Do not bring inflammables close to the refrigerant cycle, otherwise fire of the welder may catch the inflammables.
The refrigerant used by this air conditioner is the R32 or R410A Check the used refrigerant name and use tools and materials of the parts which match with it.
For the produc on the outdoor unit where is easy to see. To prevent miss-charging, the route of the service port is changed from one of the former R22.
Do not use any refrigerant different from the one specified for complement or replacement. Otherwise, abnormally high pressure may be generated in the refrigeration cycle, which may result in a failure or explosion of the product or an injury to your body.
For
an air conditioner which uses R32 or R410A, never use other refrigerant than R32 or R410A. For an air conditioner which uses other refrigerant (R22, etc.), never use R32 or R410A. If different types of refrigerant are mixed, abnormal high pressure generates in the refrigerating cycle and an injury due to breakage may be caused.
When the air conditioner has been installed or relocated, follow the instructions in the Installation Manual and purge the air completely so that no gases other than the refrigerant will be mixed in the refrigerating cycle. Failure to purge the air completely may cause the air conditioner to malfunction.
Do not charge refrigerant additionally. If charging refrigerant additionally when refrigerant gas leaks, the refrigerant composition in the refrigerating cycle changes resulted in change of air conditioner characteristics or refrigerant over the specified standard amount is charged and an abnormal high pressure is applied to the inside of the refrigerating cycle resulted in cause of breakage or injury. Therefore if the refrigerant gas leaks, recover the refrigerant in the air conditioner, execute vacuuming, and then newly recharge the specified amount of liquid refrigerant. In this time, never charge the refrigerant over the specified amount.
When recharging the refrigerant in the r R32 or R410A into the specified refrigerant. If air or others is mixed with the refrigerant, abnormal high pressure generates in the refrigerating cycle resulted in cause of injury due to breakage.
After installation work, check the refrigerant gas does not leak. If the refrigerant gas leaks in the room, poisonous gas generates when gas touches to fire such as fan heater, stove or cocking stove though the refrigerant gas itself is innocuous.
Never recover the refrigerant into the outdoor unit. When the equipment is moved or repaired, be sure to recover the refrigerant with recovering device. The refrigerant cannot be recovered in the outdoor unit; otherwise a serious accident such as breakage or injury is caused.
ts which use R32 or R410A refrigerant, the refrigerant name is indicated at a position
e a leak or production of fire is caused at the users’ side.
efrigerating cycle, do not mix the refrigerant or air other than
Assembly /
- 10 -
Wiring
Insulator
check
Ventilation
Compulsion
Check after
repair
After repair work, surely assemble the disassembled parts, and connect and lead the removed wires as before . Perform the work so that the cabinet or panel does not catch the inner wires. If incorrect assembly or incorrect wire connection was done, a disaster such as a leak or fire is caused at user’s side.
After the work has finished, be sure to use an insulation tester set (500 V Megger) to check the resistance is 1 MΩ or more between the charge section and the non-charge metal section (Earth position). If the resistance value is low, a disaster such as a leak or electric shock is caused at user’s side.
When the refrigerant gas leaks during work, execute ventilation. If the refrigerant gas touches to a fire, poisonous gas generates. A case of leakage of the refrigerant and the closed room full with gas is dangerous because a shortage of oxygen occurs. Be sure to execute ventilation.
If refrigerant gas has leaked during the installation work, ventilate the room immediately. If the leaked refrigerant gas comes in contact with fire, noxious gas may generate.
After installation work, check the refrigerant gas does not leak. If the refrigerant gas leaks in the room, poisonous gas generates when gas touches to fire such as fan heater, stove or cocking stove though the refrigerant gas itself is innocuous.
When the refrigerant gas leaks, find up the leaked position and repair it surely. If the leaked position cannot be found up and the repair work is interrupted, pump-down and tighten the service valve, otherwise the refrigerant gas may leak into the room. The poisonous gas generates when gas touches to fire such as fan heater , stove or cocking stove though the refrigerant gas itself is innocuous. When installing equipment which includes a large amount of charged refrigerant such as a multi air conditioner in a sub-room, it is necessary that the density does not the limit even if the refrigerant leaks. If the refrigerant leaks and exceeds the limit density, an accident of shortage of oxygen is caused.
Tighten the flare nut with a torque wrench in the specified manner. Excessive tighten of the flare nut may cause a crack in the flare nut after a long period, which may result in refrigerant leakage.
Nitrogen gas must be used for the airtight test. The charge hose must be connected in such a way that it is not slack. For the installation / moving / reinstallation work, follow to the Installation Manual.
If an incorrect installation is done, a trouble of the refrigerating cycle, water leak, electric shoc k or fire is caused. Once the repair work has been completed, check for refrigerant leaks, and check the insulation
resistance and water drainage. Then perform a trial run to check that the air conditioner is running properly.
After repair work has finished, check there is no trouble. If check is not executed, a fire, electric shock or injury may be caused. For a check, turn off the power breaker.
After repair work (installation of front panel and cabinet) has finished, execute a test run to check there is no generation of smoke or abnormal sound. If check is not ex ecuted, a fire or an electric shock is caused. Bef ore test run, install the front panel and cabinet.
Be sure to fix the screws back which have been removed for installation or other purposes.
Do not
operate the
unit with the
valve closed.
Check after
reinstallation
Check the following matters before a test run after repairing piping.
• Connect the pipes surely and there is no leak of refrigerant.
• The valve is opened. Running the compressor under condition that the valve closes causes an abnormal high pressure resulted in damage of the parts of the compressor and etc. and moreover if there is leak of refrigerant at connecting section of pipes, the air is sucked and causes further abnormal high pressure resulted in burst or injury.
Only a qualified installer (*1) or qualified service person (*1) is allowed to relocate the air conditioner. It is dangerous for the air conditioner to be relocated by an unqualified individual since a fire, electric shocks, injury, water leakage, noise and / or vibration may result.
Check the following items after reinstallation.
1) The earth wire is correctly connected.
2) The power cord is not caught in the product.
3) There is no inclination or unsteadiness and the installation is stable. If check is not executed, a fire, an electric shock or an injury is caused.
When carrying out the pump-down work shut down the compressor before disconnecting the refrigerant pipe. Disconnecting the refrigerant pipe with the service valve left open and the compressor still operating will cause air, etc. to be sucked in, raising the pressure inside the refrigeration cycle to an abnormally high level, and possibly resulting in reputing, injury, etc.
Cooling check
- 11 -
Installation
When the service panel of the outdoor unit is to be opened in order for the compressor or the area around this part to be repaired immediately after the air conditioner has been shut down, set the circuit breaker to the OFF position, and then wait at least 10 minutes before opening the service panel. If you fail to heed this warning, you will run the risk of burning yourself because the compressor pipes and other parts will be very hot to the touch. In addition, before proceeding with the repair work, wear the kind of insulated heat-resistant gloves designed to protect electricians.
Take care not to get burned by compressor pipes or other parts when checking the cooling cycle while running the unit as they get heated while running. Be sure to put on gloves providing protection for heat.
When the service panel of the outdoor unit is to be opened in order for the fan motor, reactor, inverter or the areas around these parts to be repaired immediately after the air conditioner has been shut down, set the circuit breaker to the OFF position, and then wait at least 10 minutes before opening the service panel. If you fail to heed this warning, you will run the risk of burning yourself because the fan motor, reactor, inverter heat sink and other parts will be very hot to the touch. In addition, before proceeding with the repair work, wear the kind of insulated heat-resistant gloves designed to protect electricians.
Only a qualified installer or service person is allowed to do installation work. Inappropriate installation may result in water leakage, electric shock or fire.
Before starting to install the air conditioner, read carefully through the Installation Manual, and follow its instructions to install the air conditioner.
Be sure to use the company-specified products for the separately purchased parts. Use of non­specified products may result in fire, electric shock, water leakage or other failure. Have the installation performed by a qualified installer.
Do not install the air conditioner in a location that may be subject to a risk of expire to a combustible gas . If a combustible gas leaks and becomes concentrated around the unit, a fire may occur.
Install the indoor unit at least 2.5 m above the floor level since otherwise the users may injure themselves or receive electric shocks if they poke their fingers or other objects into the indoor unit while the air conditioner is running.
Install a circuit breaker that meets the specifications in the installation manual and the stipulations in the local regulations and laws.
Install the circuit breaker where it can be easily accessed by the agent. If you install the unit in a small room, take appropriate measures to prevent the refrigerant from
exceeding the limit concentration even if it leaks. Consult the dealer from whom you purchased the air conditioner when you implement the measures. Accumulation of highly concentrated refrigerant may cause an oxygen deficiency accident.
Do not place any combustion appliance in a place where it is directly exposed to the wind of air conditioner, otherwise it may cause imperfect combustion.
Explanations given to user
If you have discovered that the fan grille is damaged, do not approach the outdoor unit but set the circuit breaker to the OFF position, and contact a qualified service person to have the repairs done. Do not set the circuit breaker to the ON position until the repairs are completed.
Relocation
• Only a qualified installer (*1) or qualified service person (*1) is allowed to relocate the air conditioner. It is dangerous for the air conditioner to be relocated by an unqualified individual since a fire, electric shocks, injury, water leakage, noise and / or vibration may result.
• When carrying out the pump-down work shut down the compressor before disconnecting the refrigerant pipe. Disconnecting the refrigerant pipe with the service valve left open and the compressor still operating will cause air, etc. to be sucked in, raising the pressure inside the refrigeration cycle to an abnormally high level, and possibly resulting in reputing, injury, etc.
(*1) Refer to the “Definition of Qualified Installer or Qualified Service Person”
Declaration of Conformity
- 12 -
Manufacturer:
TCF holder: TOSHIBA CARRIER EUROPE S.A.S.
Hereby declares that the machinery described below: Generic Denomination: Air Conditioner Model / type:
TOSHIBA CARRIER (THAILAND) CO., LTD.
144 / 9 Moo 5, Bangkadi Industrial Park, Tivanon Road, Tambol Bangkadi, Amphur Muang, Pathumthani 12000, Thailand
Route de Thil 01120 Montluel FRANCE
RAV-RM2241DTP-E, RAV-RM2241DTP-TR RAV-RM2801DTP-E, RAV-RM2801DTP-TR
Commercial name:
plies with the provisions of the Machinery Directive (Directive 2006/42/EC) and the regulations
Com tra
nsposing into national la
“Declaration of incorporation of partly completed machinery”
Must not be put into service until the final machinery into which it is to be incorporated has been declared in conformity with the provisions of this Directive, where appropriate.
Digital Inverter Series Air Conditioner
w
NOTE
This declaration becomes invalid if technical or operational modifications are introduced without the manufacturer’s consent.
Specifications
- 13 -
Model
RAV-RM2241DTP-E
RAV-RM2801DTP-E
RAV-RM2241DTP-TR
RAV-RM2801DTP-TR
Sound pressure level (dBA)
Cooling Heating
44
46
44
46
44
46
44
46
Weight (kg)
Main unit
97
97
97
97
Refrigerant (R32 or R410A)
- 14 -
This air conditioner adopts
a HFC type refrigerant (R32 or R410A) which does not deplete the ozone layer.
1. Safety Caution Concerned to refrigerant (R32 or R410A)
The pressure of R32 or R410A is high 1.6 times of that of the former refrigerant (R22). Accompanied with change of refrigerant, the refrigerating oil has been also changed. Therefore, be sure that water, dust, the former refrigerant or the former refrigerating oil is not mixed into the refrigerating cycle of the air conditioner with refrigerant (R32 or R410A) during installation work or service work. If an incorrect work or incorrect service is performed, there is a possibility to cause a serious accident. Use the tools and materials exclusive to R32 or R410A to purpose a safe work.
2. Cautions on Installation/Service
1) Do not mix the other refrigerant or refrigerating oil. For the tools exclusive to R32 or R410A, shapes of all the joints including the service port differ from those of the former refrigerant in order to prevent mixture of them.
2) As the use pressure of the refrigerant (R32 or R410A) is high, use material thickness of the pipe and tools which are specified for R32 or R410A.
3) In the installation time, use clean pipe materials and work with great attention so that water and others do not mix in because pipes are affected by impurities such as water, oxide scales, oil, etc. Use the clean pipes. Be sure to brazing with flowing nitrogen gas. (Never use gas other than nitrogen gas.)
4) For the earth protection, use a vacuum pump for air purge.
5) R32 or R410A refrigerant is azeotropic mixture type refrigerant.
Therefore use liquid type to charge the refrigerant. (If using gas for charging, composition of the refrigerant changes and then characteristics of the air conditioner change.)
3. Pipe Materials
For the refrigerant pipes, copper pipe and joints are mainly used. It is necessary to select the most appropriate pipes to conform to the standard. Use clean material in which impurities adhere inside of pipe or joint to a minimum.
1) Copper pipe
<Piping>
The pipe thickness, flare finishing size, flare nut and others differ according to a refrigerant type. When using a long copper pipe for R32 or R410A, it is recommended to select “Copper or copper­base pipe without seam” and one with bonded oil amount 40mg/10m or less.
Also do not use crushed, deformed, discolored (especially inside) pipes. (Impurities cause clogging of expansion valves and capillary tubes.)
<Flare nut>
Use the flare nuts which are attached to the air conditioner unit.
2) Joint
The flare joint and socket joint are used for joints of the copper pipe. The joints are rarely used for installation of the air conditioner. However clear impur ities when using them.
4. Tools
- 15 -
1. Required Tools for R32 or R410A Mixing of different types of oil may cause a trouble such as generation of sludge, clogging of capillary, etc. Accordingly, the tools to be used are classified into the following three types.
1) Tools exclusive for R32 or R410A (Those which cannot be used for conventional refrigerant (R22))
2) Tools exclusive for R32 or R410A, but can be also used for conventional refrigerant (R22)
3) Tools commonly used for R32 or R410A and for conventional refrigerant (R22) The table below shows the tools exclusive for R32 or R410A and their interchangeability.
Tools exclusive for R32 or R410A (The following tools for R32 or R410A are required.)
Tools wh
No. Used tool
Flare tool Pipe aring Yes Yes
Copper pipe gauge for adjusting projection margin
Torque wrench Tightening of are nut Yes No No
Gauge manifold
Charge hose
Vacuum pump adapter Vacuum evacuating Yes No
Electronic balance for refrigerant charging
Refrigerant cylinder Refrigerant charge Yes No No
Leakage detector Gas leakage check Yes No Yes
ose specifications are changed for R32 or R410A and their interchangeability
R32 or R410A
air conditioner installation
Usage
Flaring by conventional are tool
Evacuating, refrigerant charge, run check, etc.
Refrigerant charge Yes Yes Yes
Existence of
new equipment
for R32 or R410A
Yes
Yes No No
Whether conventional
equipment can be used
* (Note)
* (Note)
Conventional air
conditioner installation
Whether
conventional equipment
can be used
* (Note)
Yes
(Note) When flaring is
carried out for R32 or R410A using the conventional flare tools, adjustment of projection
margin is necessary. For this adjustment, a copper pipe gauge, etc. are necessary.
General tools (Conventional tools can be used.)
In addition to the above exclusive tools, the following equipments which serve also for R22 are necessary as the general tools.
1) Vacuum pump. Use vacuum pump by attaching vacuum pump adapter. 7) Screwdriver (+, –)
2) Torque wrench 8) Spanner or Monkey wrench
3) Pipe cutter 9) Hole core drill
4) Reamer 10) Hexagon wrench (Opposite side 4mm)
5) Pipe bender 11) Tape measure
6) Level vial 12) Metal saw
Also prepare the following equipments for other installation method and run check.
1) Clamp meter 3) Insulation resistance tester (Megger)
2) Thermometer 4) Electroscope
1. SPECIFICATIONS
- 16 -
Concealed Duct Static Pressure Type
Model name
Cooling capacity …Note 1 (kW) 20.0 23.7 Heating capacity …Note 1 (kW) 22.4 27.0 Electrical Cooling Indoor Unit Power supply 1phase 50Hz 230V(220V-240V) characteristics Running current (220V-240V) (A) 2.80 (2.93-2.68) 3.75 (3.92-3.59) (factory setting) Power consumption (kW) 0.530 0.785
Heating Indoor Unit Power supply 1phase 50Hz 230V(220V-240V)
Maximum Indoor Unit starting current (A) 8.15 8.15
Current Outdoor Unit starting current (A) 18.0 20.0 Appearance Zinc hot dipping steel plate Dimension Height (mm) 448
Weight (kg) 97 Heat exchanger Finned tube Soundproof / Heat-insulating material Polyethylene foam Fan unit Fan Centrifugal fan
Controller Remote controller Air filter Sold separately (TCB-LK2801DP-E) Drain pump Sold separately (TCB-DP40DPE) Connecting Gas side (mm) Φ28.6 pipe Liquid side (mm) Φ12.7
Sound pressure level (High/Med./Low) …Note 3 (factory setting) Sound power level (High/Med./Low) (dB(A)) 79 / 75 / 71 81 / 77 / 73
Note 1 : The cooling capacities and electrical characteristics are measured under the conditions specified by JIS B 8615 based on the reference piping.
The reference piping consists of 7.5m piping connected with 0 meter height.
Note 2 : The EER and COP are measured under conditions specified by BS EN14511(2013)
External static pressure is different from factory setting.
Note 3 : The sound level are measured in an anechoic chamber in accordance with JIS B 8616.
Normally, the values measured in the actual operating environment become larger than the indicated valves
Note : Rated conditions Cooling: Indoor air temperature 27
Heating: Indoor air temperature 20℃ DB, Outdoor air temperature 7℃ DB/6℃ WB
Indoor Unit RAV- Outdoor Unit RAV-
Power factor (-) 0.82 0.91
Outdoor Unit Power supply 3-phase 4 wires 50Hz 380V-415V
Running current (380V-415V) (A) 10.31-9.44 13.82-12.66 Power consumption (kW) 5.89 8.14 Power factor (-) 0.87 0.89
Total Power consumption (min-max) (kW) 6.29 (2.63-7.60) 8.75 (2.68-12.20)
EER …Note 2 3.18 2.71
Running current (220V-240V) (A) 2.80 (2.93-2.68) 3.75 (3.92-3.59) Power consumption (kW) 0.530 0.785 Power factor (-) 0.82 0.91
Outdoor Unit Power supply 3-phase 4 wires 50Hz 380V-415V
Running current (380V-415V) (A) 9.29-8.51 11.22-10.27 Power consumption (kW) 5.51 6.51 Power factor (-) 0.90 0.88
Total Power consumption (min-max) (kW) 5.91 (2.32-7.02) 7.20 (2.55-9.32)
COP …Note 2 3.79 3.75
Width (mm) 1400 Depth (mm) 900
Standard air flow 3,800 4,800 (Med./Low) (3,200 / 2,500) (4,200 / 3,500) Motor output (kW) 1kW * 1pc External static pressure (factory setting) (Pa) 150 External static pressure range (Pa) 50-83-117-150-183-217-250 (7steps)
Drain port (mm) 25(Polyvinyl chloride tube)
DB/19℃ WB, Outdoor air temperature 35℃ DB
(m3/h)
(dB(A)) 44 / 40 / 36 46 / 42 / 38
RM2241DTP-E / -TR RM2801DTP-E / -TR
SM2244AT(Z)(ZG)8-E SM2804AT(Z)(ZG)8-E
due to the effects of external soun
d.
(50Hz)
Concealed Duct Static Pressure Type
- 17 -
Model name
Indoor Unit
Outdoor Unit Cooling capacity …Note 1 (kW) 20.0 23.7 Heating capacity …Note 1 (kW) 22.4 27.0 Electrical Cooling Indoor Unit Power supply 1phase 60Hz 220V characteristics Running current (A) 2.93 3.92 (factory setting) Power consumption (kW) 0.530 0.785
Power factor (-) 0.82 0.91
Outdoor Unit Power supply
Running current (A) 10.31 13.82 Power consumption (kW) 5.89 8.14 Power factor (-) 0.87 0.89
Total Power consumption (min-max) (kW) 6.29 (2.63-7.60) 8.75 (2.68-12.20)
EER …Note 2 3.18 2.71
Heating Indoor Unit Power supply 1phase 60Hz 220V
Running current (A) 2.93 3.92 Power consumption (kW) 0.530 0.785 Power factor (-) 0.82 0.91
Outdoor Unit Power supply
Running current (A) 9.29 11.22 Power consumption (kW) 5.51 6.51 Power factor (-) 0.90 0.88
Total Power consumption (min-max) (kW) 5.91 (2.32-7.02) 7.20 (2.55-9.32)
COP …Note 2 3.79 3.75 Maximum Indoor Unit starting current (A) 8.15 8.15 Current Outdoor Unit starting current (A) 18.0 20.0
Appearance Zinc hot dipping steel plate Dimension Height (mm) 448
Width (mm) 1400
Depth (mm) 900
Weight (kg) 97 Heat exchanger Finned tube Soundproof / Heat-insulating material Polyethylene foam Fan unit Fan Centrifugal fan
Standard air flow 3,800 4,800
(Med./Low) (3,200 / 2,500) (4,200 / 3,500)
Motor output (kW) 1kW * 1pc
External static pressure (factory setting) (Pa) 150
External static pressure range (Pa) 50-83-117-150-183-217-250 (7steps)
Controller Remote controller Air filter Drain pump Connecting Gas side (mm) Φ28.6 pipe Liquid side (mm) Φ12.7
Drain port (mm) 25(Polyvinyl chloride tube)
Sound pressure level (High/Med./Low) …Note 2 (factory setting) Sound power level (High/Med./Low) (dB(A)) 79 / 75 / 71 81 / 77 / 73
Note 1 : The cooling capacities and electrical characteristics are measured under the conditions specified by JIS B 8615 based on the reference piping.
The reference piping consists of 7.5m piping connected with 0 meter height.
Note 2 : The EER and COP are measured under conditions specified by BS EN14511(2013)
External static pressure is different from factory setting.
Note 3 : The sound level are measured in an anechoic cham ber in accordance with JIS B 8616.
Normally, the values measured in the actual operating environment become larger than the indicated valves due to the effects of external sound.
Note : Rated conditions Cooling: Indoor air temperature 27 DB/19 WB, Outdoor air temperature 35 DB
Heating: Indoor air temperature 20℃ DB, Outdoor air temperature 7℃ DB/6℃ WB
RAV- RM2241DTP-E RM2801DTP-E RAV- SM2244AT7 SM2804AT7
3-phase 4 wires 60Hz 380V
3-phase 4 wires 60Hz 380V
(m3/h)
Sold separately (TCB-LK2801DP-E)
Sold separately (TCB-DP40DPE)
(dB(A)) 44 / 40 / 36 46 / 42 / 38
(60Hz)
Concealed Duct Static Pressure Type for Australia, New zealand
- 18 -
Model name
Indoor Unit
Outdoor Unit Cooling capacity …Note 1 (kW) 16.8 20.0 Heating capacity …Note 1 (kW) 22.4 27.0 Electrical Cooling Indoor Unit Power supply 1phase 50Hz 230V-240V characteristics Running current (230V-240V) (A) 2.80-2.68 3.75-3.59 (factory setting) Power consumption (kW) 0.530 0.785
Power factor (-) 0.82 0.91
Outdoor Unit Power supply
Running current (400V-415V) (A) 7.86-7.58 9.16-8.83 Power consumption (kW) 4.71 5.62 Power factor (-) 0.86 0.89
Total Power consumption (min-max) (kW) 5.05 (2.63-7.60) 6.10 (2.68-12.20)
EER …Note 2 3.33 3.28
Heating Indoor Unit Power supply 1phase 50Hz 230V-240V
Running current (230V-240V) (A) 2.80-2.68 3.75-3.59 Power consumption (kW) 0.530 0.785 Power factor (-) 0.82 0.91
Outdoor Unit Power supply
Running current (400V-415V) (A) 8.83-8.51 10.66-10.27 Power consumption (kW) 5.51 6.51 Power factor (-) 0.90 0.88
Total Power consumption (min-max) (kW) 5.91 (2.32-7.02) 7.20 (2.55-9.32)
COP …Note 2 3.79 3.75 Maximum Indoor Unit starting current (A) 8.15 8.15 Current Outdoor Unit starting current (A) 18.0 20.0
Appearance Zinc hot dipping steel plate Dimension Height (mm) 448
Width (mm) 1400
Depth (mm) 900
Weight (kg) 97 Heat exchanger Finned tube Soundproof / Heat-insulating material Polyethylene foam Fan unit Fan Centrifugal fan
Standard air flow 3,800 4,800
(Med./Low) (3,200 / 2,500) (4,200 / 3,500)
Motor output (kW) 1kW * 1pc
External static pressure (factory setting) (Pa) 150
External static pressure range (Pa) 50-83-117-150-183-217-250 (7steps)
Controller Remote controller Air filter Drain pump Connecting Gas side (mm) Φ28.6 pipe Liquid side (mm) Φ12.7
Drain port (mm) 25(Polyvinyl chloride tube)
Sound pressure level (High/Med./Low) …Note 3 (factory setting) Sound power level (High/Med./Low) (dB(A)) 79 / 75 / 71 81 / 77 / 73
Note 1 : The cooling capacities and electrical characteristics are measured under the conditions specified by JIS B 8615 based on the reference piping.
The reference piping consists of 7.5m piping connected with 0 meter height.
Note 2 : The EER and COP are measured under conditions specified by BS EN14511(2013)
External static pressure is different from factory setting.
Note 3 : The sound level are measured in an anechoic cham ber in accordance with JIS B 8616.
Normally, the values measured in the actual operating environment become larger than the indicated valves due to the effects of external sound.
Note: Rated conditions Cooling: Indoor air temperature 27 DB/19 WB, Outdoor air temperature 35 DB
Heating: Indoor air temperature 20℃ DB, Outdoor air temperature 7℃ DB/6℃ WB
RAV- RM2241DTP-E RM2801DTP-E RAV- SM2244AT8-A1 SM2804AT8-A1
3-phase 4 wires 50Hz 400-415V
3-phase 4 wires 50Hz 400-415V
(m3/h)
Sold separately (TCB-LK2801DP-E)
Sold separately (TCB-DP40DPE)
(dB(A)) 44 / 40 / 36 46 / 42 / 38
(50Hz)
2. FAN CHARACTERISTICS
- 19 -
RM224 type RM280 type
350 325 300 275 250
Mid(150Pa,117Pa)
Mid(250Pa)
Mid(217Pa)
Mid(183Pa)
225
Low
200 175 150 125 100
External Static Pressure (Pa)Fan Speed (rpm)
75 50 25
0
Mid(83Pa)
Mid(50Pa)
1800 2200 2600 3000 3400 3800 4200 4600
Standard Air Flow : 3800 (m³/h)
Air Flow (m³/h)
High(250Pa)
High(217Pa)
High(183Pa)
High(150Pa)
High(117Pa)
High(83Pa)
High(50Pa)
350 325 300
Mid(150Pa,117Pa)
275 250 225 200 175 150 125 100
External Static Pressure (Pa)Fan Speed (rpm)
75 50 25
0
2800 3200 3600 4000 4400 4800 5200 5600 6000
Mid(183Pa)
Low
Mid(83Pa)
Mid(250Pa)
Mid(217Pa)
Mid(50Pa)
Standard Air Flow : 4800 (m³/h)
Air Flow (m³/h)
High(250Pa)
High(217Pa)
High(183Pa)
High(150Pa)
High(117Pa)
High(83Pa)
High(50Pa)
1500
1400
1300
1200
1100
Mid(250Pa)
Mid(217Pa)
Mid(183Pa)
Low
Standard Air Flow : 3800 (m³/h)
High(250Pa)
High(217Pa)
High(183Pa)
1000
900
800
700
Mid(150Pa,117Pa)
600
500
Mid(83Pa)
Mid(50Pa)
High(83Pa)
High(50Pa)
1800 2200 2600 3000 3400 3800 4200 4600
Air Flow (m³/h)
High(150Pa)
High(117Pa)
1500
1400
1300
1200
Mid(217Pa)
Mid(183Pa)
Low
Mid(250Pa)
Standard Air Flow : 4800 (m³/h)
High(250Pa)
High(217Pa)
High(183Pa)
High(150Pa)
1100
1000
900
800
Mid(150Pa,117Pa)
700
Mid(83Pa)
Mid(50Pa)
High(83Pa)
High(50Pa)
2800 3200 3600 4000 4400 4800 5200 5600 6000
Air Flow (m³/h)
High(117Pa)
3. CONSTRUCTION VIEWS (EXTERNAL VIEWS)
- 20 -
500 or less
or less
190
(310)
Unit : mm
Refrigerant pipe
connecting port (Liquid side)
Drain pump kit
(sold separately)
connecting port
Drain pipe
Refrigerant pipe
221
connecting port (Gas side)
(Brazing connection)
O 28.6
(Flare nut connection)
O 12.7
321
510
300 or less
(sold separately)
When attached the drain pump kit
Drain-up piping
1/100 or more downward
310
(Accessory)
Flexible drain hose
(Accessory)
Flexible drain hose
1/100 or more downward
At the time of natural drainage
510
778
448
84
(Outside)
324
95
Drain pipe connecting port
(Gravitiational drainage)
45
1296(Outside)
Unit external dimension 1400 101
74
27
90
90
90
900 21
810
Hanging bolt mounting pitch
45
Air inlet
25
(Suction duct)
850 or more
950
Service door (Ceiling opening)
25
Ceiling
1465 34
448
more
5 or
more 70 or
Air inlet
25
300 or more
950
Service door (Ceiling opening)
25
< When attached the long life filter kit (sold separately)>
Ceiling
the service door(Ceiling opening) is not necessary.
If there are enough space under the unit (more than 1000mm)
Hanging bolt mounting pitch
200
600
1000
or more
25
1450
Air outlet
25
more
200 or
Ceiling
or more
Check port
Floor surface
Service door (Ceiling opening)
Air outlet
or more
2500
1000 or more
Service space
100
control box
Electrical
Space required for installation and servicing
Hole for hanging bolt
(4-Φ12×30)
Duct arrangement
- 21 -
<Air outlet>
1296(Outside)
98 100100100100100 100100 100100100100 98
Unit : mm
324
(Outside)
84
8
17
8
27 27
90 90 90
32
384
20
343
44
106 44
106
44
<Air inlet>
1316
58 200 200 200 200 200 200 58
1297
200 200 200 200 200 200
361
Electrical control box
41
41
58
4. WIRING DIAGRAMS
- 22 -
Color
Indication
RED : Red WHI : White YEL : Yellow BLU : Blue BLK : Black BRW : Brown
DM
M
RY02
8
5
RB
Sold Separately
0
6
4
1
RY01
WHI
RED
3
Drain Pump Kit
BRW
BRW
Symbol
CN**
F01,F500
FM
L-FM
RB
RY01,02
TA
TB01,02
TC,TCJ
DM
FS
7
(Option)
MCC-1610
CN504
(BLU)
Fan Control P.C. Board
F500
CN500
15A
(WHI)
250V
1 3
5 4 3 2 1
CN505
(RED)
2
1
CN602
(BLK)
+
U V W
Noise Filter
P.C. Board
MCC-1551
CN04
CN03
3
CN08
1
Parts Name
Connector
Fuse
Fan Motor
Reactor
Rush Current
Protect Resistor
Relay
Indoor Temp Sensor
Terminal Block
Temp Sensor
Drain Pump Motor
Float Switch
1 2 3 4 5
+
+
CN705
CN704
WHI
RED
MS 3
P01
CN02
CN01
4
-
CN703
BLK
FM
CN511
CN510
-
WHI
RED
Indoor Unit
Earth Screw
Drain Pump
Kit Attached
(Option)
FS
L-FM
TB01
Power Supply
220-240V 50Hz
Outdoor Unit
CN34
(RED)
3
1
CN210
L
220V 60Hz
TA
2
2
1
1
CN104
(YEL)
3
CN34
1
(RED)
2
CN504
(WHI)
1
20 19 18 17 1615
14 13 1211
CN510
10
(WHI)
9 8 7
6 5 4 3
2 1
7 6
5 4 3 2 1
(WHI)
F01
T6.3A
250V
RED
N
Power Supply
380-415V 3N 50Hz
380V 3N 60Hz
CN101
CN102
(BLK)
(RED)
(External Static Pressure Set Up)
Control P.C. Board
for Indoor Unit
CN67
3
5
1
(BLK)
WHI
BLK
3
21
3
21
L3
L2L1
TCTCJ
2
1
SW501
CN71 (CHK)
CN72 (DISP)
MCC-1643
Indoor Unit
Earth Screw
Outdoor
Unit
N
Earth
Screw
ON
1 2
CN22 (BLK)
Power Supply Circuit
+
DC15V
DC20V
+
CN521
(RED)
CN20 (BLU)
CN32
DC 7V
DC12V
(WHI)
CN61
(YEL)
CN50 (WHI)
-
BLK
Wired Remote
Field Wiring
Protective Earth
Terminal Block
Terminal
Connector
P.C.Board
Accessory
1 2 3 4 5
1 2 3 4 5
2 3 4 5 6 1 2 1
1 2 3 4 5
CN309
(YEL)
1 3
CN41 (BLU)
2
1
BLK
BA
A B
Controller
4
UART
5
1
CN51
CN40
U3
Connection
TB02
Wireless Remote
5
3 4
2
(RED)
(BLU)
21
MCC-1440
U4
"1:1
Model"
Interface
(Option)
WHI
1
Adapter for
Controller
BLK
2
5. PARTS RATING
- 23 -
Model RAV- RM224* RM280*
Fan motor
TA sensor
TC sensor
TCJ sensor
Drain pump (option)
Float switch (option)
SWF-340W1000-1
Lead wire length:218mm
6 size lead wire length:1000mm Vinyl tube (Black)
6 size lead wire length:1000mm Vinyl tube (Red)
PCD-4N230TF-4
FS-1A-31-3
6. CONTROL BLOCK DIAGRAM
- 24 -
6-1. Indoor Controller Block Diagram
6-1-1. In Case of Connection of Wired (Simple) Remote Controller
Wired (Simple) header remote controller
(Up to 2 units) Schedule timer
Indoor unit
#1 (Header)
Indoor
fan
motor
Reactor
Drain
pump
*Option
PMV
Fan IPDU
(MCC-1610)
Fan motor
control
circuit
DC15V
Power
circuit
Noise filter
P.C. Board
(MCC-1551)
Display LCD
Display LED
EEPROM
Indoor control P.C. Board (MCC-1643)
DC20V
DC5V
DC12V
Outside output
Start/Alarm/Ready
Power
circuit
MCU
DC5V
CPU
DC5V
Remote controller
communication circuit
AB
Remote controller
communication circuit
MCU
Driver
L
Power supply 1Φ 220-240V, 50Hz 1Φ 220V, 60Hz
Up to 8 units are connectable. *1
1 However, if "1:1 model connection interface" is
*
connected when 2 wired (simple) remote controllers are connected, Max. 7 units are connectable.
*
2 Connect "1:1 model connection interface" to only 1 unit and connect 1 "1:1 model connection interface" to the header unit. 3 It is unavailable to connect the Schedule remote
*
controller to the simple wired remote controll
Function setup
Key switch
Powe r
circuit
N
CN2
EEPROM
TA sensor
TC sensor
TCJ sensor
Float input
HA
Serial
communication
circuit
2
3
1
Outdoor unit
Display
CN1
1
*
Indoor/Outdoor communication
LCD
DC5V
LCD
driver
CPU
Powe r circuit
#2
(Follower)#3(Follower)
L N
Powe r
supply
Function setup
Secondary
AB
Same as left
1 2 3
Outdoor
unit
Key switch
battery
AB
Same as left
L N
1 2 3
Powe r
supply
Outdoor
unit
6-1-2. In Case of Connection of Wireless Remote Controller
- 25 -
Indoor unit
#1 (Header)
Indoor control P.C. Board
(MCC-1643)
DC20V
A B
Remote controller
communication circuit
Remote controller
communication circuit
Wireless remote
controller kit
Receiving P.C. Board
#2 #3
(Follower)(Follower)
BA
AB
Indoor
fan
motor
Drain
pump
*Option
PMV
Reactor
Fan IPDU (MCC-1610)
Fan motor
control
circuit
Power circuit
Noise filter P.C. Board
(MCC-1551)
DC15V
Power
circuit
MCU
DC5V
DC5V
DC12V
output
Outside
Start/Alarm/Ready
EEPROM
TA sensor
MCU
Driver
L
N
Power supply
1Φ 220-240V, 50Hz
1Φ 220V, 60Hz
Up to 8 units are connectable. *1
1 However, if "1:1 model connection interface" is
*
connected when 2 wired (simple) remote controllers are connected, Max. 7 units are connectable.
*
2 Connect "1:1 model connection interface" to only 1 unit and connect 1 "1:1 model connection interface" to the header unit. 3 It is unavailable to connect the Schedule remote
*
controller to the simple wired remote controll
TC sensor
TCJ sensor
Float input
HA
Serial
communication
circuit
2
3
1
Outdoor unit
Indoor/Outdoor communication
Power
circuit
DC5V
Buzzer
Receiving
circuit
CPU
Emergent operation
SW
Function
setup SW
Display
LED
L N
Powe r supply
Same as left
1 2 3
Outdoor
unit
L N
Powe r
supply
Same as left
1
Outdoor
2 3
unit
6-1-3. Connection of Both Wired (Simple) Remote Controller and Wireless Remote Controller
- 26 -
Indoor unit
#1 (Header)
PMV
Wired (Simple) header remote controller
Display LCD
Display LED
Indoor control P.C. Board
(MCC-1643)
DC20V
DC5V
DC12V
Outside output
Start/Alarm/Ready
Power
circuit
EEPROM
communication circuit
Driver
CPU
DC5V
Remote controller
A B
Remote controller
communication circuit
MCU
Function setup
Key switch
Powe r
circuit
EEPROM
TA sensor
TC sensor
TCJ sensor
Float input
HA
Serial
communication
circuit
CN2
1
*
communication circuit
Power
circuit
Buzzer
Receiving
circuit
Schedule timer
Display
CN1
Powe r
circuit
Remote controller
DC5V
CPU
LCD
DC5V
Wireless remote
controller kit
Receiving P.C. Board
Emergent operation
SW
Function
setup SW
Display
LED
LCD
driver
CPU
Secondary
battery
#2 #3
Function setup
Key switch
BA
Same as left
(Follower)(Follower)
BA
Same as left
Indoor
fan
motor
Drain
pump
*Option
Reactor
Fan IPDU (MCC-1610)
Fan motor
control
circuit
Power circuit
Noise filter P.C. Board
(MCC-1551)
MCU
DC5V
DC15V
L
N
Power supply
1Φ 220-240V, 50Hz
1Φ 220V, 60Hz
Up to 8 units are connectable. *1
1 However, if "1:1 model connection interface" is
*
connected when 2 wired (simple) remote controllers are connected, Max. 7 units are connectable.
*
2 Connect "1:1 model connection interface" to only 1 unit and connect 1 "1:1 model connection interface" to the header unit. 3 It is unavailable to connect the Schedule remote
*
controller to the simple wired remote controll
Max. 8 units are connectable. *1 The schedule timer cannot be connected to the simple wired remote controller.
2
3
1
Outdoor unit
Indoor/Outdoor communication
L N
Power supply
1 2 3
Outdoor
unit
L N
Power
supply
1 2 3
Outdoor
unit
6-2. Control Specifications
- 27 -
No.
1
When power supply is reset
2
Operation mode selection
Item
Outline of specifications
1) Distinction of outdoor unit When the power supply is reset, the outdoors are distin-
guished and the control is selected according to the distinguished result.
2) Setting of indoor fan speed and existence of air direction adjustment
Based on EEPROM data, select setting of the indoor fan speed.
1) Based on the operation mode selecting command from the remote controller, the operation mode is selected.
Remote controller
command
STOP
FAN
COOL
DRY
HEAT
AUTO
• COOL/HEAT operation mode is automatically selected by TA, TS and TO for operation.
• The operation is performed as shown in the following figure according to Ta value at the first time only. (In the range of TS +
Control outline
Air conditioner stops.
Fan operation
Cooling operation
Dry operation
Heating operation
α –1 < TA < TS + α + 1, Cooling
thermostat
volume operation continues.)
. OFF (Fan)/Setup air
Remarks
Fan speed (rpm)
TA: Room temp.
TS: Setup temp. TO: Outside temp.
3
Room temp. control
Cooling
1.0
TA˚C TS + α
–1.0
α is corrected according to the outside temperature.
Outside temp.
No TO
TO 24°C
24°C > TO 18°C
TO < 18°C
TO trouble
operation
Cooling thermostat. OFF (Fan)
• Setup air volume
Heating operation
Correction value (
0K
–1K
0K
+1K
0K
αα
α)
αα
1) Adjustment range: Remote controller setup temperature ( °C )
Wired type
Wireless type
COOL/DRY
18°C to 29°C 17°C to 30°C
HEAT
18°C to 29°C 17°C to 30°C
K = deg
AUTO
18°C to 29°C 17°C to 30°C
No.
- 28 -
3
Room temp. control (Continued)
4
Automatic capacity control
(GA control)
Item
Outline of specifications
2) Using the CODE No. 06, the setup temper ature in heating operation can be corrected.
SET DA TA
Setup temp.
correction
0246
+0°C +2°C +4°C +6°C
Setting at shipment
SET DA TA 2
1) Based on the difference between TA and TS, the operation frequency is instructed to the outdoor unit.
2) Cooling operation Every 90 seconds, GA calculates TA-TS, the fluctuation,
and the correction amount of compressor frequency
TA (n) – TS (n) : Room temp. difference
n
TA (n-1) – TS (n) : Room temp.fluctuation
n – 1
: Detecting counts :
Detecting counts of 90 seconds before
3) Heating operation Every 1 minute (60 sec.), GA calculates TA-TS, the
fluctuation, and the correction amount of compressor frequency.
TS (n) – TA (n)
n
TA (n) – TA (n – 1): Room temp.fluctuation
n – 1
: Room temp. difference : Detecting counts
: Detecting counts of 1 minute before
4) Dry operation The frequency correction control is same as those of the
cooling operation. However the maximum frequency is limited to approxi-
mately “S6”.
Note) When LOW is set up, the maximum frequency is
limited to approximately “SB”.
Remarks
Shift of suction temperature in heating operation
Maximum frequency code: S0-SF (16 steps)
5
Automatic cooling/heating control
1) The judgment of selecting Cooling/Heating mode is
carried out as shown belows
When TA exceeds Tsh+1.5°C after 10 minutes at thermostat off, the operation mode
TSC: Setup temp. in
cooling operation
TSH: Setup temp. in
heating operation + temp. correction of room temp. control
+1.5
–1.5
Cooling
(Cooling ON)
(Cooling OFF)
Heating
TA ˚C
TSC or TSH
When TA is lower Tsc-1.5°C after 10 minutes at thermostat off, the operation mode
changes COOL to HEAT mode.
2) For the automatic capacity control after judgment of cooling/heating, see Item 4.
3) For temperature correction of room temp. control at automatic heating, see Item 3.
No.
- 29 -
6
Fan speed control
Item
Outline of specifications
1) Operation with (HH), (H), (L) or [AUTO] mode is carried
out by the command from the remote controller.
2) When the fan speed mode [AUTO] is selected, the fan
speed varies by the difference between TA and TS.
<COOL>
Remarks
HH > H+ > H > L+ > L > UL
A B C
D
E
F G
TA-TSC ˚C
+3.0 +2.5 +2.0 +1.5 +1.0 +0.5
0
–0.5
HH (HH)
H+ (HH) H (HH) L+ (H+) L (H) L (H) L (L+)
• Controlling work using thermostat of remote controller is
same as the case of using body thermostat.
• If the fan s
c
hanged
exchanged,
• When cooling operation s
selected along a down arrow in figure
When "TA-TSC" is just on boundary
change
( ) indicated the fan speed at automatic cooling operation.
peed has changed automatically, it is not
for 3 minutes. However when the air volume is
the fan s
peed changes.
tarted,
the fan speed will be
.
the fan speed won't
.
<HEAT>
L (L+) L+ (H) H (H+)
H+ (HH)
HH (HH)
E
D
C B A
TSH-TA ˚C
[-0.5] –1.0
[ 0 ] 0
[+0.5] +1.0
[+0.1] +2.0 [+1.5] +3.0 [+2.0] +4.0
the value with [ ] indicates the temperature at using remote
ontroller thermostat.
c the value without [ ] indicates the
temperature
at using body
thermostat of indoor unit.
• If the fan speed has changed automatically, it is not
changed for 1 minute.
When heating operation starts, the fan speed will be
selected along an up arrow in figure.
When 'TSH-TA' is just on boundary, the fan speed won't
change.
( ) indicates the fan speed at automatic heating operation.
• In TC 60°C, the fan speed increases by 1 step.
TC: Indoor heat
exchanger sensor temperature
No.
- 30 -
6
Fan speed control (Continued)
Item
Outline of specifications
CODE No.
DN : [ 5d ]
SW501 (1)-(2)
TAP HEAT COOL HEAT COOL HEAT COOL HEAT COOL HEAT COOL HEAT COOL HEAT COOL
F1 HH HH F2 HH HH H+ H+ F3 HH HH H+ H+ F4 HH HH HH H+ H+ F5 HH HH H+ H+ H H F6 HH H+ H+ H H L+ L+ F7 HH HH H+ H+ H H F8 H+ H+ H H H H L+ L+ L+ L+
F9 H H L+ L+ L+ L+ L L FA H H L+ L+ L L L L FB L+ L+ L L L L FC L L L L FD LL LL LL LL LL LL LL LL LL LL LL LL LL LL
50Pa 83Pa 117Pa 150Pa 183Pa 217Pa
0001 0002 0004 0000 0005 0003 0006
3) In heating operation, the fan speed changes to [UL] if thermostat is turned off.
4) If TA 25°C when heating operation has started or defrost operation has been cleared, the air conditioner operates with (H) mode or higher mode for 1 minute after Tc entered in E zone of cold air draft preventive control (No. 7).
Remarks
250Pa
ON-ONON-OFF - - OFF-OFF - OFF-ON
7
Cold air draft preventive control
1) In heating operation, the indoor fan is controlled based on the detected temperature of TC sensor or TCJ sensor. As shown below, the upper limit of the fan speed is restricted in
spite of the fan speed set on remote control.
However B zone is assumed as C zone for 6 minutes after the compressor has started.
In defrost operation, the control value of TC is shifted +6°C.
TC, TCJ
˚C
HH
32
H
30 28 26
20 16
L
UL
OFF
E zone D zone
C zone B zone
A zone
In A zone while thermostat is ON, [PRE-HEAT (Heating ready)] is displayed.
No.
- 31 -
Item
Outline of specifications
Remarks
8
Freeze preventive control (Low temperature release)
1) The cooling operation (including Dry operation) is performed as follows based on the detected temperature of TC sensor or TCJ sensor. When [J] zone is detected for 6 minutes (Following figure), the commanded frequency of compressor is decreased. After then the commanded frequency changes every 30 seconds while operation is performed in [J] zone.
In [K] zone, time c
ation is held.
oper When [ I ] z
and the operation retur If the c
ommanded frequency becomes S0 because the oper return temperature A is raised from 5°C to 12°C until [ I ] zone is detected and the indoor fan speed is operated with L tap.
ounting is interrupted and the
one is detected, the timer is cleared
ns to the nor
ation contin
mal oper
ues in [J] zone, the
ation.
TC,TCJ˚C
5
I
A
K
2
J
TCJ:
Indoor heat exchanger sensor temperature
In heating operation, the freeze-preventive control works if 4-way valve is not exchanged and the following conditions are satisfied. (However the temperature for J zone dashing control is changed from 2°C to –5°C.)
<Conditions>
• When c or d is established 5 minutes af ter activation.
TCn TC (n – 1) – 5
c
TCn < TC (n – 1) – 1 and TCn TA
d
< 5°C
TCn:
TC temperature when 5 minutes elapsed after activation
TC (n – 1):
TC temperature at start time
No.
- 32 -
9
High-temp. release control
Item
Outline of specifications
1) The heating operation is performed as follows based on the detected temperature of TC sensor or TCJ sensor.
• When [M] zone is detected, the commanded frequency is
decreased. After then the commanded frequency changes every 30 seconds while operation is performed in [M] zone.
• In [N] zone, the commanded frequency is held.
• When [L] zone is detected, the commanded frequency is
returned to the original value by approx. 6Hz every 60 seconds.
Remarks
However this control is ignored in case of the follower unit of the twin.
10
Drain pump control
Setup at shipment
Control temp. °C
AB
56 (54) 52 (52)
TC, TCJ
˚C
A
B
M N
L
NOTE:
When the operation has started or when TC or TCJ < 30°C after operation start, the release temperature is controlled between values in parentheses of A and B.
1) In cooling operation (including Dry operation), the drain pump is usually operated.
2) If the float switch works while drain pump drives, the compressor stops, the drain pump continues the operation, and a check code is output.
3) If the float switch works while drain pump stops, the compressor stops and the drain pump operates. If the float switch keeps operating for approx. 4 minutes, a check code is output.
Same status as that when “thermostat-OFF” (status that the air conditioner enters in the room temp. monitor mode when the temperature reached the setup temperature on the remote controller)
Check code [P10]
Drain pump kit
TCB-DP40DE (Sold separately)
11
After-heat elimination
When heating operation stops, in some cases, the indoor fan operates with (L) for approx. 30 seconds.
No.
- 33 -
12
Frequency fixed operation (Test run)
Item
Outline of specifications
<In case of wired remote controller>
1) When pus displayed on the display screen and the mode enters in T run mode.
2) Push [ON/OFF] button.
3) Using [MODE] button, set the mode to [COOL] or [HEAT].
Do not use other mode than [COOL]/[HEAT] mode.
• During test run operation, the temperature cannot be ad-
justed.
Trouble is detected as usual.
• A frequency fixed operation is performed.
4) After the test run, push [ON/OFF] button to stop the operation. (Display in the display part is same as the procedure in Item 1.)
5) Push [CHK] button to clear the test run mode. ([TEST] display in the display part disappears and the status returns to the normal stop status.)
<In case of wireless remote controller>
1) When TEMPORARY button is pushed for 10 seconds or more, “Pi!” sound is heard and the operation changes to test run. After approx. 3 minutes, a cooling operation starts forcedly.
Check cool air starts blowing. If the operation does not start, check wiring again.
2) To stop a test operation, push TEMPORARY button once again (Approx. 1 second).
Check wiring / piping of the indoor and outdoor units in test run.
hing [CHK] button for 4 seconds or more, [TEST] is
est
Remarks Command frequency is
approximately [S7]
TEMPORARY button
13 1) The operation time of the indoor fan is calculated, the filter
(Except wireless type)
reset signal is sent to the remote controller when the speci­fied time (2500H) has passed, and it is displayed on LCD.
2) When the filter reset signal has been received from the remote controller, time of the calculation timer is cleared.
In this case, the measurement time is reset if the specified time has passed, and display on LCD disappears.
[FILTER ] goes on.Filter sign display
No.
- 34 -
14
Central control mode selection
Item
Outline of specifications
1) Setting at the central controller side enables to select the contents which can be operated on the wired remote controller.
2) Setup contents
• In case of TCC-LINK Central remote controller
(TCB-SC642TLE2) [Individual]: Operated by wired remote controller ([After-push precedence]) [Central 1]: START / STOP operation by wired remote controller is unavailable. [Central 2]: START / STOP, MODE change and TEMP. setting by wired remote controller are unavailable. [Central 3]: MODE change and TEMP. setting by wired remote controller are unavailable. [Central 4]: MODE change by wired remote controller is unavailable.
• In case of the wireless remote controller, the con-
tents to be operated are same though the display lamp does not change. If an item prohibited by the central control mode is operated from the remote controller, it is notified with receiving sound Pi, Pi, Pi, Pi (5 times)
Remarks
Display at wired remote controller side (No display)
] goes on.
[
] goes on.
[
] goes on.
[
] goes on.
[
15
Saving operation
16
Max. frequency cut control
1) Selecting [AUTO] mode enables an saving mode to be operated.
2) The setup temperature is shifted (corrected) in the range not to lose the comfort ability according to input values of various sensors.
3) Data (Input value room temp. Ta, Outside temp. To, Air volume, Indoor heat exchanger sensor temp. Tc) for 20 minutes are taken the average to calculate correc­tion value of the setup temperature.
4) The setup temperature is shifted every 20 minutes, and the shifted range is as follows.
In cooling time: +1.5 to – 1.0K In heating time: –1.5 to +1.0K.
1) This control is operated by selecting [AUTO] operation mode.
2) COOL operation mode: It is controlled according to the following figure if To < 28°C.
Ta ˚C
Normal control
+4 +3
3) HEAT operation mode: It is controlled according to the following figure if To > 15°C.
Max. frequency is
Ta ˚C
Tsh
–3
restricted to approximately the rated heating frequency
Tsc
Max. frequency is restricted to approximately the rated cooling frequency
–4
Normal control
No.
- 35 -
17
DC motor
Energy saving
18
operation
Item
Outline of specifications
Remarks
1) When the fan operation has started, positioning of the stator and the rotor are performed. (Moves slightly with tap sound)
2) The motor operates according to the command from the indoor controller.
Notes)
• When a fan lock is found, the air conditioner stops, and
trouble is displayed.
• If static pressure of the used duct does not match with
the setup value of static pressure, which was decided
Check code [P12]
in the static pressure setting code No. [5D], the air conditioner may stop or a check code may be displayed.
1) Tur n on
2) During operation of save operation, wired remote controller.
3) During save operation, the current release control is performed with the restriction ratio set in EEPROM on the outdoor unit.
4) The restriction ratio can be set by keeping pushed for 4 seconds or more on the remote controller.
5) When validating the save operation, the next operation starts with save operation valid because contents are
SAVE
button on the remote controller.
lights on the
SAVE
button
Carry out setting operation during stop of the unit; otherwise the unit stops operation.
For the setup operation, refer to “How to set contents of save operation” in Section
9. SETUP AT LOCAL SITE AND OTHERS”.
held even when operation stops, operation mode changes or power supply is reset.
6) The restriction ratio can be set by changing the setup data of CODE No. (DN) [C2] in the range of 50 to 100% (every 1%, Setting at shipment: 75%).
8°C heating/Frost
19
protective operation
1) This function is intended for the cold latitudes and performs objective heating operation (8°C heating operation).
2)
Using the indoor CODE No. [D1] (1 bit), Valid/Invalid of this function is set up at the customer’s side.
The setup by CODE No. is Invalid [0]/Valid [1] and
Invalid [0] has been set at the shipment.
This function starts operation by pushing temperature
3)
button during heating operation for 4 seconds or more after temperature reached the minimum set temperature.
4) To stop/release this operation, select and execute one from the following operations.
Push button:
c
Heating operation 18°C setting) continues.
Push [START/STOP] button:
d
Air conditioner stops. (Heating 18°C operation at the next start)
Push :
e
MODE
Other operation mode is selected and the operation continues.
5) The indoor fan stops to protect the compressor for 2 minutes after start of heating operation (thermostat-ON) by this function.
In a group connection, if there is even one combination with other unit, “This function is not provided.” is display ed.
The setup temperature jumps from [18] to [8].
6-3. Indoor Print Circuit Design Board
- 36 -
<MCC-1643>
Indoor/Outdoor
inter-unit cable
CN67
Optional power supply
(CN309)
Ventilation output CN32
Power supply LED of remote controller
D403 (Red)
EEPROM
IC503
“1:1 model”
Connection
inter CN50
HA
CN61
UART
(Fan - IPDU, Application Control Kit)
CN521 (Red) DC12V
DISP(CN72)
CHK(CN71)
Remote
controller
External static pressure select SW
SW501
CN41
Float SW
CN34
TC sensor
TCJ sensor
CN102
CN101
TA sensor
CN104
Signal for Drain Pump Kit
CN504 (WHI) DC12V
6-3-1. Optional connector specifications of Indoor Circuit Design Board
- 37 -
controller (DN [31] = 0000 0001)
Setting at shipment: Interlock of ON by indoor unit operation, with OFF by stop operation
The single operation setting by FAN button on the remote controller is performed on the remote
DC12V
Output (Open collector)
1
2
Permission/Prohibition of remote controller operation stop is performed by input.
Operation ON (Answer back of HA)
Warning output ON
This check is used to check indoor operation. (Performs operation of indoor fan “H”
and Drain pump ON without communication with outdoor and remote controller)
Communication is available by indoor unit and remote controller only.
ON/OFF input
0V
Remote controller prohibited input
Operation output (Open collector)
DC12V
Warning output (Open collector)
1 HA ON/OFF input (J01: YES/NO=Pulse (At shipment from factory) /Static input selection)
234
5
6
1
20V
1
20V
CN71
CN72
Connected FAN-IPDU (MCC-1610)
Connected Application control kit (TCB-PCUC1E)
1 12V
25V
3 Transmission
4 Receive
50V
CN521
Function Connector No. Pin No. Specifications Remarks
Ventilation output CN32
HA CN61
CHK
Operation check
DISP
Exhibition mode
UART
(FAN-IPDU,
Option control
kit)
6-3-2. Fan IPDU P.C. Board (MCC-1610)
- 38 -
Power relay output
CN602
UART communication between
CDB
CN504
UART communication
between Application control kit
(TCB-PCUC1E)
CN505
CN504
CN505
CN702
CN705
CN704
CN703
CN602
Fan motor output U-phase
CN705
Fan motor output V-phase
CN704
Fan motor output W-phase
CN703
CN502
CN500
Power supply input
CN500
CN511
CN510
Reactor connecting terminal
Reactor connecting terminal
CN510
CN511
6-3-3. Noise filter (MCC-1551)
- 39 -
CN04 (White) Power supply output (
Neutral)
L01
Line Filter
CN04 (White)
ower supply input
P (Neutral)
CN03 (Red) Power supply output (Live)
CN08 (Blue) Power supply output for drain pump kit *option
CN01 (Red) Power supply input (Live)
7. TROUBLESHOOTING
- 40 -
7-1. Summary of Troubleshooting
<Wired remote controller type>
1. Before troubleshooting
1) Required tools/instruments
+
and – screwdrivers, spanners, radio cutting pliers, nippers, push pins for reset switch
• Tester, thermometer, pressure gauge, etc.
2) Confirmation points before check a) The following operations are normal.
1. Compressor does not operate.
• Is not 3-minutes delay (3 minutes after compressor OFF)?
• Is not the outdoor unit in standby status though the remote controller reached the setup temperature?
• Does not timer operate during fan operation?
• Is not an overflow trouble detected on the indoor unit?
• Is not outside high-temperature operation controlled in heating operation?
2. Indoor fan does not rotate.
• Does not cool air discharge preventive control work in heating operation?
3. Outdoor fan does not rotate or air volume changes.
• Does not high-temperature release operation control work in heating operation?
• Does not outside low-temperature operation control work in cooling operation?
• Is not defrost operation performed?
4. ON/OFF operation cannot be performed from remote controller.
• Is not automatic address being set up? (When the power is turned on at the first time or when indoor unit address setting is changed, the operation cannot be performed for maximum approx. 5 minutes after power-ON.)
• Is not being carried out a test run by operation of the outdoor P.C. board?
b) Did you return the cabling to the initial positions? c) Are connecting cables of indoor unit and remote controller correct?
2. Troubleshooting procedure
When a trouble occurred, check the parts along with the following procedure.
Trouble Confirmation of check code display Check defective parts.
NOTE
For cause of a trouble, power conditions or malfunction/erroneous diagnosis of microcomputer due to outer noise is considered except the items to be checked. If there is any noise source, change the cables of the remote controller to shield cables.
<Wireless remote controller type>
- 41 -
1. Before troubleshooting
1) Required tools/instruments
+
and – screwdrivers, spanners, radio cutting pliers, nippers, etc.
• Tester, thermometer, pressure gauge, etc.
2) Confirmation points before check a) The following operations are normal.
1. Compressor does not operate.
• Is not 3-minutes delay (3 minutes after compressor OFF)?
• Is not the outdoor unit in standby status though the remote controller reached the setup temperature?
• Does not timer operate during fan operation?
• Is not an overflow trouble detected on the indoor unit?
• Is not outside high-temperature operation controlled in heating operation?
2. Indoor fan does not rotate.
• Does not cool air discharge preventive control work in heating operation?
3. Outdoor fan does not rotate or air volume changes.
• Does not high-temperature release operation control work in heating operation?
• Does not outside low-temperature operation control work in cooling operation?
• Is not defrost operation performed?
4. ON/OFF operation cannot be performed from remote controller.
• Is not forced operation performed?
• Is not the control operation performed from outside/remote side?
• Is not automatic address being set up?
• Is not being carried out a test run by operation of the outdoor controller?
b) Did you return the cabling to the initial positions? c) Are connecting cables between indoor unit and receiving unit correct?
2. Troubleshooting procedure
(When the power is turned on at the first time or when indoor unit address setting is changed, the operation cannot be performed for maximum approx. 5 minutes after power-ON.) When a trouble occurred, check the parts along with the following procedure.
Trouble
Confirmation of lamp display
→→
(When wireless remote controller is connected)
Check defective position and parts.
Outline of judgment
- 42 -
The primary judgment to check whether a trouble occurred in the indoor unit or outdoor unit is carried out with the following method.
Method to judge the erroneous position by display panel of the indoor unit (lamp display of the wireless receiving part)
The indoor unit monitors the operating status of the air conditioner, and the blocked contents of self-diagnosis are displayed restricted to the following cases if a protective circuit works.
: Go off, : Go on, : Flash (0.5 sec.)
Lamp indication
Operation
No indication at all
Operation
Flash
Operation
Operation
Timer Ready
Timer Ready
Timer Ready
Flash
Timer Ready
Alternate flash
Check code
E01 E02 E03 E08 E09 E10
E18
E04
P10
P12
Cause of trouble occurrence
Pow er supply OFF or mis wiring between lamp indication unit and indoor unit
Receiving trouble
Sending trouble
Communication stop
Duplicated indoor unit No. Duplicated master units of remote controller
⎫ ⎬
Receiving unit
⎫ ⎪
Miswiring or wire connection trouble
between receiving unit and indoor unit
⎪ ⎭
Setup trouble
⎬ ⎭
UART communication trouble
Wire connection trouble between indoor units, Indoor power OFF (Communication stop between indoor header and follower)
Miswiring between indoor unit and outdoor unit or connection trouble (Communication stop between indoor and outdoor units)
Overflow was detected.
Indoor DC fan trouble
⎫ ⎪ ⎬
Protective device of indoor unit worked.
⎪ ⎭
Outdoor unit discharge temp. trouble Outdoor high pressure system trouble Negative phase detection trouble Heat sink overheat trouble Gas leak detection trouble
Protective device of
outdoor unit worked.
⎫ ⎪ ⎬
Outdoor unit trouble
⎪ ⎭
4-way valve system trouble (Indoor or outdoor unit judged.) Outdoor unit high pressure protection
Outdoor unit: Outdoor unit trouble Outdoor unit: Inverter Idc operation Outdoor unit: Position detection trouble
⎫ ⎪
Protective device of
outdoor unit worked.
⎪ ⎭
Stopped because trouble of other indoor unit in a group (Check codes of E03/L03/L07/L08)
1
1
Operation
Timer Ready
Alternate flash
P03 P04 P05 P07 P15 P19 P20 P22 P26 P29
P31
1: These are representative examples and the check code differs according to the outdoor unit to be combined.
Lamp indication
- 43 -
Operation
Alternate flash
Operation
Alternate flash
Operation
Timer Ready
Timer Ready
Timer Ready
Check code
F01 F02 F10 F04 F06 F07 F08 F12 F13 F15
Cause of trouble occurrence
Heat exchanger sensor (TCJ) trouble
Heat exchanger sensor (TC) trouble
Heat exchanger sensor (TA) trouble
Discharge temp. sensor (TD) trouble
Temp. sensor (TE) trouble Temp. sensor (TL) trouble Temp. sensor (TO) trouble Temp. sensor (TS) trouble Temp. sensor (TH) trouble
Temp. Sensor mis wiring (TE, TS)
⎫ ⎪
Indoor unit sensor trouble
⎬ ⎪ ⎭
⎫ ⎪ ⎪ ⎪ ⎪ ⎪ ⎪ ⎬
Sensor trouble of outdoor unit 1
⎪ ⎪ ⎪ ⎪ ⎪ ⎪ ⎭
Simultaneous flash
Operation
Timer Ready
Simultaneous flash
Operation
Timer Ready
Flash
Operation
Timer Ready
Simultaneous flash
Operation
Timer Ready
Simultaneous flash
F29
F31
H01 H02 H03 H04 H06 L03
L07
L08
L09
L10 L20 L29 L30 L31
Indoor EEPROM trouble
Outdoor EEPROM trouble
Compressor break down Compressor lock Current detection circuit trouble Case thermostat worked.
⎫ ⎪ ⎪ ⎬
Outdoor compressor system trouble ∗1
⎪ ⎪ ⎭
Outdoor unit low pressure system trouble
Duplicated header indoor units There is indoor unit of group connection AUTO address
in individual indoor unit. Unsetting of group address
Missed setting (Unset indoor capacity)
Unset model type (Service board) Duplicated indoor central addresses Outdoor unit and other trouble Outside interlock trouble Negative phase trouble
⎫ ⎪ ⎪ ⎬ ⎪
If group construction and
address are not normal
when power supply turned on, automatically goes to address setup mode.
⎫ ⎪ ⎪ ⎪ ⎪
Others
⎬ ⎪ ⎪ ⎪ ⎪ ⎭
1: These are representative examples and the check code differs according to the outdoor unit to be combined.
Others (Other than Check Code)
- 44 -
Lamp indication
Operation Timer Ready
Simultaneous flash
Operation Timer Ready
Alternate flash
Check code
Cause of trouble occurrence
During test run
Disagreement cool/heat (Automatic cool/heat setting to automatic cool/heat prohibited mode)
continuation
- 45 -
{×{×{×{×{×{×{×{
reset
Automatic Operation
Air conditioner operation
×
××
××
××
×
××
××
{
×
××
××
××
××
{×{
continuation
——
——
reset
Automatic Operation
Air conditioner operation
×
continuation
——
——
——
reset
Automatic Operation
Air conditioner operation
——
Explanation of trouble contents
No communication from remote controller and network adapter
(Also no communication from central control system)
There is trouble on serial communication between indoor and outdoor units
Representative defective position
Same address as yours was detected.
Communication trouble between CDB(MCC-1643) and FAN-IPDU(MCC-1610)
Regular communication between indoor master and follower units is impossible.
Open/short was detected on heat exchanger (TCJ).
Open/short was detected on heat exchanger (TC).
Open/short was detected on room temp. sensor (TA).
EEPROM trouble (Other trouble may be detected. If no trouble, automatic address is repeated.
There are multiple master units in a group.
When even one group connection indoor unit exists in individual indoor unit.
Indoor group address is unset.
Capacity of indoor unit is unset.
Duplicated setting of central control system address
Abnormal stop by outside trouble (CN80) input
Trouble of indoor AC fan was detected. (Fan motor thermal relay worked.)
Float switch worked.
Indoor DC fan trouble (Over-current/Lock, etc.) was detected. Static pressure trouble set
In heating operation, trouble was detected by temp. down of indoor heat exchanger sensor.
Follower unit in group cannot operate by warning from [E03/L03/L07/L08] of master unit.
When this warning was detected before group construction/address check finish at power supply was turned on, the mode shifts automatically to AUTO address setup mode.
Explanation of trouble contents
Signal cannot be received from indoor unit. Master remote controller was not set. (including 2 remote controllers)
Signal cannot be sent to indoor unit.
In 2-remote controller control, both were set as master.
(Indoor master unit stops warning and follower unit continues operation.)
Representative defective position
Explanation of trouble contents
Signal sending operation of central control system is impo ssible. There a re multipl e same cen tral devic es.
Signal receiving operation of central control system is impossible.
Representative defective position
Trouble on device connected to general-purpose device control interface of exclusive to TCC-LINK
Group follower unit is defective. (For remote controller, above-mentioned [∗∗∗] details are displayed with unit No.)
Regular communication trouble between indoor and remote controller
Indoor/Outdoor serial trouble
Duplicated indoor addresses
E03
E04
E08
Remote controller
TCC-LINK central &
7-2. Check Code List
Check code indication
(Indoor)(Indoor unit detected)
UART communication trouble
Regular communication trouble between indoor master and follower units
Indoor unit, Heat exchanger (TCJ) trouble
Indoor unit, Heat exchanger (TC) trouble
Indoor unit, Room temp. sensor (TA) trouble
Indoor unit, other indoor P.C. board trouble
Duplicated setting of indoor group master unit
There is group cable in individual indoor unit.
Unset indoor group address
Unset indoor capacity
L03
L07
L08
E10
E18
F01
F02
F10
F29
L09
Duplicated central control system address
Outside trouble input to indoor unit (Interlock)
Indoor unit, AC fan trouble
Indoor unit, overflow detection
Indoor unit, DC fan trouble
4-way valve system trouble
Other indoor unit trouble
L20
L30
P01
P10
P12
P19
P31
No master remote controller, Remote controller communication (Receive) trouble
Remote controller communication (Send) trouble
E01
E02
Remote controller
Check code indication
(Remote controller detected)
Central control system communication (send) trouble
Duplicated master remote controller
E09
Check code indication
(Central control devices detected)
Central control system communication (receive) trouble
C05
C06
TCC-LINK central
General-purpose device control interface batched warning
C12
Group follower unit is defective.
P30
When remote controller or central controller detects trouble, it is not necessarily related to operation of the air conditioner. In this list, the check codes that outdoor unit detects are not described.
NOTE: Even for the same contents of trouble such as communication trouble, the display of check code may differ according to detection device.
Check Code List
- 46 -
Trouble detected by indoor unit
Operation of diagnostic function
Check
code
No communication from remote
E03
controller (including wireless) and communication adapter
The serial signal is not output from outdoor unit to indoor unit.
• Miswiring of inter-unit wire
E04
• Defective serial sending circuit on
• Defective serial receiving circuit on
E08
Duplicated indoor unit address
L03
Duplicated indoor header unit There is group wire in individual indoor
L07
unit.
L08
Unset indoor group address
L09
Unset indoor capacity
L30
Abnormal input of outside interlock
Float switch operation
P10
• Float circuit, Disconnection, Coming-
Cause of operation
outdoor P.C. board
indoor P.C. board
off, Float switch contact trouble
Status of
air conditioner
Stop
(Automatic reset)
Stop
(Automatic reset)
Stop
Stop
Stop
Stop
Condition
Displayed when check code is detected
Displayed when check code is detected
Displayed when check code is detected
Displayed when
heck
ode is
c
c
detected Displayed when
check code is detected
Displayed when check code is detected
Judgment and measures
1. Check cables of remote controller and communication adapters.
• Remote controller LCD display OFF (Disconnection)
• Central remote controller [97] check code
1. Outdoor unit does not completely operate.
• Inter-unit wire check, correction of miswiring
• Check outdoor P.C. board. Correct wiring of P.C. board.
2. When outdoor unit normally operates Check P.C. board (Indoor receiving / Outdoor sending).
1. Check whether remote controller connection (Group/Individual) was changed or not after power supply turned on (Finish of group construction/Address check).
* If group construction and address are not normal when the
power has been turned on, the mode automatically shifts to address setup mode. (Resetting of address)
1. Set indoor capacity (DN=11)
1. Check outside devices.
2. Check indoor P.C. board.
1. Trouble of drain pump
2. Clogging of drain pump
3. Check float switch.
4. Check indoor P.C. board.
P12
Indoor DC fan trouble
4-way valve system trouble
P19
• After heating operation has started, indoor heat exchangers temp. is down.
Own unit stops while warning is output
P31
to other indoor units.
Coming-off, disconnection or short of
F01
indoor heat exchanger temp. sensor (TCJ)
Coming-off, disconnection or short of
F02
indoor heat exchanger temp. sensor (TC)
Coming-off, disconnection or short of
F10
indoor heat exchanger temp. sensor (TA)
Indoor EEPROM trouble
F29
• EEPROM access trouble
E10
UART communication trouble
Stop
Stop
(Automatic reset)
Stop
(Follower unit)
(Automatic reset)
Stop
(Automatic reset)
Stop
(Automatic reset)
Stop
(Automatic reset)
Stop
(Automatic reset)
Stop
(Automatic reset)
Displayed when check code is detected
Displayed when check code is detected
Displayed when check code is detected
Displayed when check code is detected
Displayed when
check code is detected
Displayed when check code is detected
Displayed when
check code is detected
Displayed when check code is detected
1. Position detection trouble
2. Indoor fan driving part over-current protective circuit operation
3. Indoor fan lock
4. Indoor P.C. board check
1. Check 4-way valv e.
2. Check 2-way valv e and check valve.
3. Check indoor heat exchanger (TC/TCJ).
4. Check indoor P.C. board.
1. Judge follower unit while master unit is [E03], [L03], [L07] or [L08].
2. Check indoor P.C. board.
1. Check indoor heat exchanger temp. sensor (TCJ).
2. Check indoor P.C. board.
1. Check indoor heat exchanger temp. sensor (TC).
2. Check indoor P.C. board.
1. Check indoor heat exchanger temp. sensor (TA).
2. Check indoor P.C. board.
1. Check indoor EEPROM. (including socket insertion)
2. Check indoor P.C. board.
1.
Check for defect in indoor P.C. board
(MCC-1643 and MCC-1610)
5. Static pressure trouble set
Regular communication trouble between indoor header and follower
E18
units
Stop
(Automatic reset)
Displayed when check code is detected
1. Check remote controller wiring.
2. Check indoor power supply wiring.
3. Check indoor P.C. board.
Trouble detected by outdoor unit
- 47 -
Operation of diagnostic function
Check
code
Indoor
unit
F04
F06
F07
F12
F15
F08
F13
F31
L10
L29
P07
P15
P19
H01
H02
Cause of operation
Disconnection, short of discharge temp. sensor (TD)
Disconnection, short of outdoor temp. sensor (TE)
Disconnection, short of outdoor temp. sensor (TL)
Disconnection, short of suction temp. sensor (TS)
Miss-mounting of outdoor temp. sensor (TE, TS)
Disconnection, short of outside temp. sensor (TO)
Disconnection, short of heat sink temp. sensor (TH)
Outdoor P.C. EEPROM trouble
Unset jumper of service P.C. board
Communication trouble between outdoor P.C. board MCU
Heat sink Heat sink temp. sensor detected over specified
temperature.
Detection of gas leak Discharge temp. sensor (TD), Suction temp.
sensor (TS) detected temperature over specified temp.
4-way valve inverse trouble After heating operation has started, indoor
heat exchanger temp. lowers under the specified temp.
After heating operation has started, outdoor
heat exchanger / suction temp. rises over the specified temp.
Compressor break down Although operation has started, operation
frequency decreases and operation stops.
Compressor lock Over-current detection after compressor
start-up
erheat trouble
ov
Status of
air conditioner
Continue
Stop
Stop
Stop
Stop
Stop
Stop
Stop
Stop
Stop
Stop
Stop
Stop
Stop
Stop
Condition
Displayed when check code is detected
Displayed when check code is detected
Displayed when check code is detected
Displayed when check code is detected
Displayed when check code is detected
Displayed when
check code is detected
Displayed when check code is detected
Displayed when check code is detected
Displayed when check code is detected
Displayed when check code is detected
Displayed when check code is detected
Displayed when check code is detected
Displayed when check code is detected
Displayed when check code is detected
Displayed when check code is detected
Judgment and measures
1. Check discharge temp. sensor (TD).
2. Check outdoor P.C. board.
1. Check temp. sensor (TE).
2. Check outdoor P.C. board.
1. Check temp. sensor (TL).
2. Check outdoor P.C. board.
1. Check suction temp. sensor (TS).
2. Check outdoor P.C. board.
1. Check temp. sensor (TE, TS).
2. Check outdoor P.C. board.
1. Check outside temp. sensor (TO).
2. Check outdoor P.C. board.
1. Check outdoor P.C. board. (Q201 is incorporated in TH sensor.)
1. Check outdoor P.C. board.
1. Outdoor service P.C. board Check model type setting jumper wire.
1. Check outdoor P.C. board
2. Connection check for each P.C. board.
1. Check screw tightening between PC. Board and heat sink and check radiator grease.
2. Check heat sink blast path.
1. Check gas leak, recharge
2. Check full open of service valve.
3. Check PMV (Pulse Motor Valve).
4. Check broken pipe.
5. Check discharge temp. sensor (TD), suction temp. sensor (TS).
1. Check operation of 4-way valve.
2. Check outdoor heat exchanger (TE), suction temp. sensor (TS).
3. Check indoor heat exchanger sensor (TC).
4. Check 4-way valv e coil.
5. Check PMV (Pulse Motor Valve).
1. Check power supply voltage.
2. Overload operation of refrigerating cycle
1. Trouble of c c
ompressor.
2. Wiring
trouble
ompressor (Lock
of compressor (Open phas
, etc.): Replace
e)
Check
- 48 -
code
Indoor
unit
H03
P05
F23
H06
P03
H04
P04
P05
P20
P22
P26
P29
Operation of diagnostic function
Cause of operation
Current detection circuit trouble
Open phase of 3-phase power supply
Ps sensor trouble
Low pressure protective operation
Discharge temp. trouble Discharge temp. (TD) over specified v alue
was detected.(1.6)
Case thermostat operation Abnormal overheat of compressor
High pressure SW system trouble
Power supply voltage trouble
High pressure protective operation
• During cooling operation, outdoor temp . sensor (TL) detected temperature over specified temp.
• During heating operation, indoor temp. sensor (TC, TCJ) detected temperature over specified temp.
Outdoor fan system trouble
Short-circuit trouble of compressor driving element
Position detection circuit trouble
Status of
air conditioner
Stop
Stop
Stop
Stop
Stop
Stop
Stop
Stop
Stop
Stop
Stop
Stop
Condition
Displayed when check code is detected
Displayed when
c
c
heck
ode is
detected
Displayed when check code is detected
Displayed when check code is detected
Displayed when check code is detected
Displayed when check code is detected
Displayed when check code is detected
Displayed when check code is detected
Displayed when check code is detected
Displayed when check code is detected
Displayed when check code is detected
Displayed when
heck
ode is
c
c
detected
Judgment and measures
1. Check outdoor P.C. board. (AC current detection circuit)
1. Check open phase of 3-phase power supply.
2. Black lead wire to be connected to CN03 of outdoor P. C. board does not pass through T611.
1. Check connection of Ps sensor connector.
2. Check failure of Ps sensor.
3. Check compressing power trouble of compressor.
4. Check 4-way valve trouble.
5. Check outdoor P.C. board
1. Check service valves are fully opened.
(Gas side, Liquid side)
2. Check clogging of outdoor PMV. (PMV1, 2)
3. Check SV2 circuit.
4. Check Ps sensor trouble.
5. Check clogging of indoor filter.
6. Check clogging of refrigerant pipe.
7. Check of outdoor fan operation. (In heating mode)
8. Check short of refrigerant.
1. Check refrigerating cycle (Gas leak)
2. T rouble of electronic expansion valve
3. Check discharge temp. sensor (TD).
1. Check case thermostat and connector.
2. Check gas leak, recharge
3. Check full open of service valve.
4. Check PMV (Pulse Motor Valve).
5. Check broken pipe.
1. Check service valves are fully opened. (Gas side, Liquid side)
2. Check of outdoor fan operation.
3. Check motor trouble of outdoor fan.
4. Check clogging of outdoor PMV. (PMV1, 2)
5. Check clogging of heat exchanger in indoor/outdoor units.
6. Short-circuit status of suction/discharge air in outdoor unit.
7. Check outdoor P.C. board trouble.
8. Check fan system trouble (Cause of air volume drop) at
indoor side.
9. Check PMV opening status in indoor unit.
1. Check power supply voltage.
1. Check outdoor heat exchanger sensor (TL).
2. Check indoor heat exchanger sensor (TC, TCJ).
3. Check full open of service valve.
4. Check indoor/outdoor fan.
5. Check PMV (Pulse Motor Valve).
6. Check clogging and short circuit of indoor/outdoor heat exchanger.
7. Overcharge of refrigerant. Recharge
1. Check lock of fan motor.
2. Check power supply voltage between L2 and N.
3. Check outdoor P.C. board.
1. When performing operation while taking-off compressor wire, P26 trouble occurs. Check control P.C. board.
2. When performing operation while taking-off compressor wire, trouble does not occur. (Compressor rare short)
1. Check control P.C. board.
trouble.
Trouble detected by remote controller or central controller (TCC-LINK)
- 49 -
Operation of diagnostic function
Check code
Not displayed at all (Operation on remote controller is impossible.)
Cause of operation
No communication with master indoor unit
• Remote controller wiring is not correct.
• Power of indoor unit is not turned on.
• Automatic address cannot be completed.
Status of
air conditioner
Stop
Condition
Power supply trouble of remote controller, Indoor EEPROM trouble
1. Check remote controller inter-unit wiring.
2. Check remote controller.
3. Check indoor power wiring.
4. Check indoor P.C. board.
5. Check indoor EEPROM. (including socket insertion)
Automatic address repeating phenom-
Judgment and measures
enon generates.
E01
2
E02
E09
L20
Central controller
L20
3
Central controller
(Send)
C05
(Receive)
C06
Central controller
P30
No communication with master indoor unit
• Disconnection of inter-unit wire between remote controller and master indoor unit (Detected by remote controller side)
Signal send trouble to indoor unit (Detected by remote controller side)
There are multiple main remote controllers. (Detected by remote controller side)
Duplicated indoor central addresses on communication of central control system (Detected by indoor/central controller side)
Communication circuit trouble of central control system (Detected by central controller side)
Indoor Gr sub unit trouble (Detected by central controller side)
Stop
(Automatic reset)
If center exists,
operation continues.
Stop
(Automatic reset)
If center exists,
operation continues.
Stop
(Sub unit
continues operation.)
Stop
(Automatic reset)
Continues
(By remote controller)
Continuation/Stop
(According
to each case)
Displayed when check code is detected
Displayed when check code is detected
Displayed when check code is detected
Displayed when check code is detected
Displayed when check code is detected
Displayed when check code is detected
Receiving trouble from remote controller
1. Check remote controller inter-unit wiring.
2. Check remote controller.
3. Check indoor power wiring.
4. Check indoor P.C. board.
Sending trouble of remote controller
1. Check sending circuit inside of remote controller.
Replace remote controller.
1. In 2-remote controllers (including wireless), there are multiple main units.
Check that there are 1 main remote controller and other sub remote controllers.
1. Check setting of central control system network address. (Network adapter SW01)
2. Check network adapter P.C. board.
1. Check communication wire / miswiring
2. Check communication (U3, U4 terminals)
3. Check network adapter P.C. board.
4. Check central controller (such as central control remote controller, etc.)
5. Check terminal resistance. (TCC-LINK)
Check the check code of the corresponding unit from remote controller.
2 The check code cannot be displayed by the wired remote controller.
(Usual operation of air conditioner becomes unavailable.) For the wireless models, trouble is notified with indication lamp.
3 This trouble is related to communication of remote controller (A, B), central system (TCC-LINK U3, U4),
and [E01], [E02], [E03], [E09] or [E18] is displayed or no check display on the remote controller according to the contents.
7-3. Diagnostic Procedure for Each Check Code (Indoor Unit)
- 50 -
Check code [E01]
NO
Is inter-unit cable of A and B normal?
YES
Is there no disconnection or
contact trouble of connector on harness
from terminal block of indoor unit?
NO
Is group control operation?
YES
Is power of all indoor units turned on?
YES
Is power supplied to remote controller?
AB terminal: Approx. DC18V
YES
NO
YES
NO
NO
Correct inter-unit cable
of remote controller
Correct connection of connector.
Check circuit wiring.
Check power connection of indoor unit.
(Turn on power again.)
Check indoor P.C. board (MCC-1643).
Defect Replace
[E09]
Are 2 remote controllers set
without header unit?
NO
Are 2 header units set in
2 remote controllers?
NO
YES
YES
Correct a header unit/a follower unit.
(Remote controller address connector)
Check remote controller P.C. board.
Defect Replace
Correct as a header unit
and a follower unit.
Check remote controller P.C. board.
Defect Replace
[E04]
- 51 -
Does outdoor operate?
YES
NO
Is group address setup of remote controller correct?
YES
Are wiring in indoor unit and
1, 2, 3 inter-unit cables correct?
YES
Are wirings of terminal blocks
(1, 2, 3) wired to CN67 normal?
YES
Does the voltage
between 2 and 3 of the indoor unit
inter-unit terminal blocks
(1, 2, 3) vary?
NO
NO
NO
NO
As shown in the following figure,
carry out measurement within 20 seconds after the power was turned on.
Black White
Terminal block
Check CODE No. [14].
Correct wiring and
inter-unit cables.
Correct wiring of connector
and terminal blocks.
Check indoor P.C. board
(MCC-1643).
Defect Replace
S5277G
3 2 1
Check indoor P.C. board.
Defect Replace
Check outdoor P.C. board.
Defect Replace
[E10]
- 52 -
Is the
connection for the
UART communication
connector (MMC-1643
CN521, MCC-1610
CN505) abnormal?
No
Yes
Repair of connector
connection.
Is connector
lead wire for the UART
communication
cut?
No
Red LED (D640)
of MCC-1610 not
illuminated.
No
Fault with the MCC-1643
Replace
Yes
Yes
Replacement of the
connector’s lead wire.
Check the power
supply of MCC-1610
[E11]
- 53 -
Is the
connection for the UART communication connector (MCC-1643
CN521, MCC-1610
CN505) normal?
No
Yes
Repair of connector
connection.
Is connector
lead wire for the UART
communication
cut?
No
Red LED (LD1)
of Optional board
not illuminated.
No
Red LED (LD1)
light on the Optional
board flashes
on and off.
No
Red LED (LD1)
of Optional
blinks.board
No
Yes
Yes
Yes Fault with the external
Yes
Replacement of the
connector’s lead wire.
Lead wire is cut or fault
of input/output board.
input/output board
Replace
Fault with the internal
board (MCC-1643)
Replace
Check the operating status.
[E18]
- 54 -
NO
Is inter-unit cable
of A and B normal?
YES
Is there no disconnection
or contact trouble of connector
on harness from terminal block
of indoor unit?
NO
Is group control operation?
YES
Is power of all indoor units turned on?
YES
Is there no contact trouble
of indoor/outdoor inter-unit wire
NO
YES
NO
YES
Correct inter-unit cable
of remote controller
Correct connection of connector.
Check circuit wiring.
Check power
connection status of indoor unit
(Connect again).
Correct indoor/outdoor inter-unit wire
(Serial signal line).
.
NO
Check indoor P.C. board
(MCC-1643).
Defect Replace
[E08, L03, L07, L08]
E08: Duplicated indoor unit No. L03: There are 2 or more header units in a group control. L07: There is 1 or more group address [Individual] in a group control. L08: The indoor group address is unset. (99)
If the above trouble is detected when power supply turned on, the mode enters automatically in the automatic address set mode. (Check code is not output.) However, if the above trouble is detected during the automatic address set mode, a check code may be output.
[L09]
Is not yet capacity setting
of indoor unit set up?
YES
Set capacity data of indoor unit.
(Setup CODE No. (DN)=11)
NO
Check indoor P.C. board (MCC-1643).
Defect Replace
[L20]
- 55 -
Are wiring connections
to communication lines
U3 and U4 normal?
YES
Is not the multiple same central
control system addresses connected?
NO
Check central controller
(including 1:1 model connection interface)
and indoor P.C. board (MCC-1643).
Defect Replace
[L30]
Do outside devices normally work?
Outside devices connected with Application control kit input terminal TB2 : IN1
NO
YES
NO
Correct wiring connection.
Correct central control system address.
Check outside devices.
Defect Replace
YES
Check cause of operation.
[P30] (Central controller)
Is group operation carried out?
YES
Is there check code on remote controller in the follower remote controller?
YES
Check corresponding
indoor unit/outdoor unit.
NO
NO
Check indoor P.C. board (MCC-1643).
Defect Replace
[P10] Drain pump kitnTCB-DP40DE (Sold separately)
- 56 -
Is connection of
float switch connector
(Indoor control board CN34)
normal?
YES
Does float switch work?
YES
Does drain pump work?
YES
Check the drain pipe, etc.
NO
NO
NO
Is power of
drain pump turned on?
YES
Check and correct wiring
Is circuit wiring normal?
NO
and wire circuit.
NO NO
Is voltage 7-8 pin on
Replace drain pump.
YES
RY02 12V?
YES
Correct connection
of connector.
Replace drain pump.
Check wiring.
Check indoor P.C. board
(MCC-1643).
Defect Replace
Check that voltage of 1 - 3 pin of CN08 on the MCC-1551 is 200-240V and check that voltage of 3-5 pin
on RY02 is 0 v.
[F10]
Is connection of TA sensor connector
(indoor P.C. board CN104) normal?
YES
Are characteristics of TA sensor resistance value normal? Replace TA sensor.
YES
Refer to Characteristics-1.
NO
NO
Connect connector
of connector.
Check indoor P.C. board (MCC-1643).
Defective Replace
[P12]
- 57 -
[P12]
Check code nameCheck code
Indoor fan motor trouble
Power supply ON
Cause
1. Installation environment trouble
2. Electric parts trouble
3. Wiring trouble of fan motor connector
4. Fan motor trouble
5.. Indoor P.C. board trouble
Measure the power supply voltage
and if the voltage is normal or not.
220-240VAC(50Hz) or
220VAC(60Hz)
YES
If the power relay operates
normally or not.
(the voltage between power relay
4pin-GND and 6pin-GND are
198-264V? *1)
YES
Power supply OFF
The ambient temperature is
normal or not.
YES
NO
Power supply voltage is less than 198V
Power supply voltage is more than 264V
NO YES
*1 : Power relay pin No,
NO
more than 80
The voltage between
the terminals of CN602
of MCC-1610 is 12V
NO
Replacement of the power relay
Replacement of the MCC-1610
Adjustment of the main power supply on the equipment side
Improves the installation
environment
If there is any poor connection of
the connector of MCC-1610, or
disconnection of the motor lead.
NO
Remove the motor lead from
CN703,704,705 of MCC-1610
If the fan motor is locked or not.
(Unable to rotate it by hand)
NO
If the winding resistance of the
motor is correct or not. *2
YES
Replacement of the MCC-1610
YES
YES
NO
Correction of the connection
of the connector
Replacement of the motor
*1 : Measure the resistance value of each winding by using the tester
SWF-340W1000-1
Red
White
Black
Position Resistance value
Red - White 2.6 ± 0.3 Ω
White - Black 2. 6 ± 0.3 Ω
Black - Red 2.6 ± 0.3 Ω
at 20°C
Fan motor inside wiring diagram
[P19]
- 58 -
Is operation of 4-way valve normal?
(Check the pipe temp., etc.
during cooling/heating operation.
YES
Check temperature sensors.
TE sensor TS sensor
Indoor TC sensor
Defective Correct, replace
NO
Are 1.3 to 1.6kΩ applied to
resistance value of 4-way valve coil ?
YES
Check outdoor P.C. board operation.
(See the following description.)
OK
Check 4-way valve.
Defective Replace
NO
Replace 4-way valve coil.
Defective
Check outdoor P.C. board.
Defective Replace
Operation check direction of the outdoor P.C. board (In case of self-preservation valve)
1) Set the Dip switch SW804 as same as the following table and push SW801 for approx. 1 second. It enables you to check the exchange operation to cooling cycle or heating cycle.
• Only for approx. 10 seconds, the power is turned on.
• As the heat value of part (coil: resistance R700) is large, when checking the operation continuously, wait 1
minute or more until the next check. (There is no problem if a coil is not connected.)
2) After check, turn off all the Dip switches SW804.
Exchange to cooling cycle Exchange to heating cycle
SW804 SW8011CN701
4321
Push
ON
4
DC180V or more
SW804 SW801 CN701
4321
ON
Push
1
4
DC180V or more
Check by tester
Analog tester: Good article if over DC180V Digital tester: Although in some cases, the value varied and indicated. If the maximum value is DC180V or
more, it is good article.
[F02]
- 59 -
[F01]
Is connection of TC sensor connector
(CN101 on Indoor P.C. board) correct?
YES
Are characteristics of
TC sensor resistance value normal?
YES
Refer to Charqacteristics-2.
Check indoor P.C. board (MCC-1643).
Defect Replace
Is connection of TCJ sensor connector (CN102 on Indoor P.C. board) correct?
NO
Correct connection of connector.
NO
Replace TC sensor.
NO
Correct connection of connector.
YES
Are characteristics of
TCJ sensor resistance value normal?
YES
Refer to Charqacteristics-2.
Check indoor P.C. board (MCC-1643).
Defect Replace
NO
Replace TCJ sensor.
[C06] (1:1 model connection interface)
- 60 -
Are U3 and U4 communication lines normal? Correct communication line.
YES
1
Is connection of connector normal?
YES
Are A and B communication lines normal?
YES
Is there no connection trouble of power supply cable?
NO
Is not the source power supply turned on?
1
In case of 1:1 model connection interface 1:1 model connection interface (MCC-1440) CN51 and indoor P.C. board CN050.
NO
NO
NO
YES
NO
Correct connection of connector.
Check connection of A and B terminal blocks.
Correct communication line of remote controller.
Correct power wiring.
Turn on the source power supply.
YES
Did a power failure occur?
NO
Is the network address changed
from the wired remote controller?
NO
Is there no noise source?
NO
Can the other indoor units
be normally controlled from the central controller?
Or is the operation status of indoor unit reflected?
YES
Can the indoor unit be normally controlled
from the wired remote controller?
YES
YES
YES
Uncontrolled
(Same to others)
Uncontrolled
Clear the check code.
Eliminate noise, etc.
Check central controller.
Defect Replace
Check indoor P.C. board (MCC-1643).
Defect Replace
YES
Check the power supply transformer of
1:1 model connection interface (MCC-1440).
Defective Replace
[E03] (Master indoor unit)
- 61 -
[E03] is detected when the indoor unit cannot receive a signal from the wired remote controller (also central controller). Check A and B remote controllers and communication lines of the central control system U3 and U4. As communication is impossible, this check code [E03] is not displayed on the wired remote controller and the central controller. [E01] is displayed on the wired remote controller and [C06] is displayed on the central controller. If these check codes generate during operation, the air conditioner stops.
[F29]
This check code indicates a detection trouble of IC503 non-volatile memory (EEPROM) on the indoor unit P.C. board, which generated during operation of the air conditioner. Replace the service P.C. board.
When EEPROM was not inserted when power supply turned on or when the EEPROM data read/write
operation is impossible at all, the automatic address mode is repeated. In this time, [97] is displayed on the central controller.
(Power ON)
(Approx.
3 minutes)
[SET] is displayed on
wired remote controller.
(Approx.
1 minute)
[SETTING]
goes off.
(Repetition)
LED (D501) on indoor unit
P.C. board flashes with
1Hz for approx. 10 seconds.
Reboot (Reset)
[P31] (Follower indoor unit)
When the master unit of a group operation detected [E03], [L03], [L07] or [L08] check code, the follower unit of the group operation detects [P31] and then the unit stops.
There is no display of the check code or alarm history of the wired remote controller. (In this model, the mode enters in automatic address set mode when the header unit detected [L03], [L07] or [L08] check code.)
Temperature – Resistance value characteristic table
- 62 -
TA, TC, TCJ sensor
Representative value
40
Temperature
(°C)
0 10 20 25 30 40 50 60 70 80 90 100
Resistance value (k
(Minimum (Standard (Maximum
value) value) value)
32.33 33.80 35.30
19.63 20.35 21.09
12.23 12.59 12.95
9.75 10.00 10.25
7.764 7.990 8.218
5.013 5.192 5.375
3.312 3.451 3.594
2.236 2.343 2.454
1.540 1.623 1.709
1.082 1.146 1.213
0.7740 0.8237 0.8761
0.5634 0.6023 0.6434
ΩΩ
Ω)
ΩΩ
TA, TC, TCJ sensor
30
20
Resistance (kΩ)
10
0
10 20 30 40 50 60 70 80 90 100
0
Temperature (˚C)
8. REPLACEMENT OF SERVICE P.C. BOARD
- 63 -
8-1. Indoor control P.C. Board
CAUTION
< Model : RAV-RM****DTP*> For the above
models, set the CODE no. to " " and the setting data 0000 (initial) to "0001"
<Note: when replacing the P.C. board for indoor unit servicing>
The nonvolatile memory (hereafter called EEPROM, IC503) on the indoor unit P.C. board before replacement includes the model specific type information and capacity codes as the factory-set value and the important setting data which have been automatically or manually set when the indoor unit is installed, such as system/ indoor/group addresses, external static pressure select setting, etc.
When replacing the P.C. board for indoor unit servicing, follow the procedures below. After replacement completes, confirm whether the settings are correct by checking the indoor unit No., Group
header unit/follower unit settings and perform the cooling cycle confirmation through the trial operation.
<Replacement procedures>
CASE 1
Before replacement, the indoor unit can be turned on and the setting data can be read out by wired remote control operation.
EEPROM data read out [1]
Ø
Replacement of P.C. board for Indoor unit servicing and power on [2]
Ø
Writing the read out EEPROM data [3]
Ø
Power reset
(for all indoor units connected to the remote control when the group operation control is perfor med.)
CASE 2
The EEPROM before replacement is defective and the setting data cannot be read out.
EEPROM data read out [2]
Ø
Writing the setting data to EEPROM, such as high ceiling installation setting and
optional connection setting, etc., based on the customer information. [3]
Ø
Power reset
(for all indoor units connected to the remote control when the group operation control is performed.)
[1] Setting data read out from EEPROM
- 64 -
The setting data modified on the site, other than factory-set value, stored in the EEPR OM shall be read out.
Step 1 Push
SET,CL
When the group operation control is performed, the unit No . displayed f or the first time is the header unit No.
At this time, the CODE No. (DN) shows “ ”. Also, the fan of the indoor unit selected starts its operation.
Step 2 Every time when the
is displayed in order. Specify the indoor unit No. to be replaced.
1. Change the CODE No. (DN) to setting. (this is the setting for the filter sign lighting time.)
At this time, be sure to write down the setting data displayed.
2. Change the CODE No. (DN) by pushing Similarly, be sure to write down the setting data displayed.
3. Repeat the step 2-2 to set the other settings in the same way and write down the setting data as shown in the table 1 (example).
The CODE No. (DN) are ranged from “ ” to “ ”. The CODE No. (DN) may skip.
Step 3 After writing down all setting data, push
(It takes approx. 1 min until the remote controller operation is available again.)
CODE No. required at least
DN Contents
10 11 12 13 14
Type
Indoor unit capacity
System address
Indoor unit address
Group address
and
TEST
button on the remote controller simultaneously for more than 4 seconds.
UNIT LOUVER
(left side button) button is pushed, the indoor unit No. under the group control
by pushing / buttons for the temperature
/ buttons for the temperature setting.
TEST
button to return to the normal stop status.
1. The CODE No. for the Indoor unit type and Indoor unit capacity are required to set the rotation number setting of the fan.
2. If the system/indoor/group addresses are different from those before replacement, the auto-address setting mode starts and the manual resetting may be required again. (when the multiple units group operation including twin system.)
[2] P.C. Board for indoor unit servicing replacement procedures
Step 1 Replace the P.C. board to the P.C. board for indoor unit servicing.
At this time, perform the same setting of the jumper wire (J01, J08, J09) setting (cut), switch SW501, (short-circuit) connector CN34 as the setting of the P.C. board before replacement.
If the plug for short-circuit is attached on the P.C. board before replacement, attach it on the P.C. board replaced.
Connector (CN504) for drain pump
Step 2 According to the system configuration, turn on the indoor unit following to the either methods shown below.
a) Single operation (Indoor unit is used as standalone.)
Turn on the indoor unit.
1. After completion of the auto-address setting mode (required time: approx. 5 min.), proceed to [3]. (System address = 1, Indoor unit address = 1, Group address = 0 (standalone) are automatically set.)
Push
SET,CL
2. setting mode, and proceed to [3]. (The unit No. “ ” is displayed.)
and
TEST
buttons simultaneously for more than 4 seconds to interrupt the auto-address
b)
- 65 -
Group operation Turn on the indoor unit(s) with its P
.C. board replaced to the P.C. board for indoor unit servicing, accord-
ing to either methods 1 or 2 shown below.
1. Turn on only the indoor unit with its P.C. board replaced. (Be sure to confirm the remote controller is surely connected. If not, the operation [3] cannot be performed.)
Perform either methods 1 or 2 described in item a) above.
2. Turn on the multiple indoor units including the indoor unit with its P.C. board replaced.
• All group connections
After completion of the auto-address setting mode (required time: approx. 5 min.), proceed to [3]. The header unit of the group may be changed by performing the auto-address setting.
Also, the system address/Indoor unit address of the indoor unit with its P.C. board replaced may be assigned to the addresses (not used) other than those of the indoor units without its P.C. board replaced. It is recommended to keep the information in advance, which cooling system the indoor unit belongs to or whether the indoor unit works as the header unit or the follower unit in the group control operation.
[3] Writing the setting data to EEPROM
The settings stored in the EEPROM of the P.C. board for indoor unit servicing are the factory-set values.
Step 1 Push
SET,CL
and
TEST
buttons on the remote controller simultaneously for more than 4 seconds.
In the group control operation, the unit No. displayed for the first time is the header unit No.
At this time, the CODE No. (DN) shows “ ”. Also, the fan of the indoor unit selected starts its operation. (The unit No. “ ”
Step 2 Every time when
is displayed if the auto-address setting mode is interrupted in [2] step 2 a))
UNIT LOUVER
(left side button) button is pushed, the indoor unit No. in the group control operation are displayed in order. (The settings stored in the EEPROM of the P.C. board for indoor unit servicing are the factory-set values.)
Specify the indoor unit No. with its P.C. board replaced to the P.C. board for indoor unit servicing. (You cannot perform this operation if “ ” is displayed.)
Step 3 Select the CODE No. (DN) can be selected by pushing the
/ button for the temperature setting.
• Set the indoor unit type and capacity.
The factory-set values shall be written to the EEPROM by changing
<Fig. 1 RBC-AMT32E>
the type and capacity.
Set the CODE No. (DN) to “ ”. (without change)
1.
2. Select the type by pushing
/ buttons for the timer setting. (For example, 4-way Cassette Type is set to “0001”. Refer to table 2)
3.
Push
button.
SET
(The operation completes if the setting data is displayed.) Change the CODE No. (DN) to “ ” by pushing
4.
/
buttons for the temperature setting. Select the capacity by pushing /
5.
buttons for the timer setting.
(For example, 280 Type is set to “0023”. Refer to table 3)
6.
Push
button.
SET
(The setting completes if the setting data are displayed.)
3651 42
Setting Concealed Duct High Static Pressure Type
7. Using the set temperature
” to the CODE No. (DN).
8. Using the timer time / buttons, set the dat. (0001)
SET
9. Push
10.Push the
button (The setting completes if the setting data are displayed.)
TEST
button to return to the normal stop status
(It takes approx. 1 min until the remote control operation is available again.)
/
buttons, set “
Step 4 Write the on-site setting data to the EEPROM, such as address setting, etc. Perform the steps 1 and 2
- 66 -
above again.
Step 5 Change the CODE No. (DN) to “ ” by pushing / buttons for the temperature setting.
(this is the setting for the filter sign lighting time.)
Step 6 Check the setting data displayed at this time with the setting data put down in [1].
1.
/ buttons for the timer setting toIf the setting data is different, modify the setting data by pushing
the data put down in [1]. The operation completes if the setting data is displayed.
2. If the data is the same, proceed to next step.
Step 7 Change the CODE No. (DN) by pushing
/ buttons for the temperature setting.
As described above, check the setting data and modify to the data put down in [1].
Step 8 Repeat the steps 6 and 7. Step 9 After the setting completes, push
TEST
button to return to the normal stop status.
(It takes approx. 1 min until the remote control operation is available again.) The CODE No. (DN) are ranged from “ ” to “ ”. The CODE No. (DN) is not limited to be serial No.
Even after modifying the data wrongly and pushing modification by pushing
CL
button if the CODE No. (DN) is not changed.
SET
button, it is possible to return to the data before
<Fig. 2 EEPROM layout diagram>
The EEPROM (IC503) is attached to the IC sock et. When detaching the EEPROM, use a tw eezers, etc. Be sure to attach the EEPROM by fitting its direction as shown in the figure. Do not bend the IC lead when replacing.
EEPROM
Cut out
EEPROM
Cut out
IC socket
CODE No. list (Example)
- 67 -
CODE No. (DN)
01 02 03 06 0d 0F
10 11 12 13 14
1E
28 31 32 5d 60
d0
d1
F6
Filter sign lighting time Filter pollution level Central control address Heating suction temperature shift Existence of automatic COOL/HEAT mode Cooling only
Type Indoor unit capacity System address Indoor unit address Group address Temperature range of cooling / heating automatic SW control point Power failure automatic recovery Vent Fan (Single operation) Sensor SW (Selection of static pressure)
Static pressure selection
Timer setting (wired remote controller) Power save operation
Frost protection function
Presence of Application control kit
Item
Setting data Factory-set value
Depending on Type 0000: standard 0099: Not determined 0002: +2°C (Floor standing type: 0) 0001: No auto mode cooling / heating 0000: Heat pump
Depending on model type Depending on capacity type 0099: Not determined 0099: Not determined 0099: Not determined 0003: 3 deg (TS ± 1.5)
0000: None 0000: Not possible 0000: Body sensor 0000: Standard 0000: Available 0001: Standard
0000: None 0000: None
* Automatically selection
by connected outdoor unit
Type Code No. [10]
Setting data Type Model abb. name
0006
Concealed Duct High Static Pressure Type
RAV-RM∗∗∗DTP-E (TR)
Indoor unit capacity CODE No. [11]
Setting data Type
0000
0021
0023
Disable
224
280
8-2. Fan IPDU P.C. Board (MCC-1610)
- 68 -
Replacement steps:
[Remove PCB]
(1) Turn off the power supply of the indoor unit and allow at least one minute for the capacitor to discharge.
Confirm that the light of the LED (D640) fades away.
(2) Remove all the connectors which are connected to the FAN IPDU. (Remove the connectors by pulling
the connector body. Do not pull the wire, because there are some rocks in connector).
(3) Remove all the five screws (a) which secures the FAN IPDU to the Heat sink.(These screws are to be
re-used after procedure.)
(4) Remove the Fan IPDU from four PCB spacer (b).
Connection points
LED(D640)
(a)Screw
PCB(MCC1610)
Black White Red
leads from motor
Figure1 PCB outline
(b)Spacer
Figure2 After removing PCB
[Set PCB]
(5) Confirm that no dirt or damage is on the sub heat sink. And don’t forget to set sub heat sink. As it can
reduce the heat transfer efficiency, and cause a breakdown.
(6) Screw the FAN IPDU to the heat sink using the five screws that were removed in step (3). If the screws
are loose, the effected component will generate heat, and cause in to breakdown. Do not use an electric
driver or an air driver, as it can cause component damage. The torque of 5 screws (IC701, DB509,
DB510 and Q590) is “0.55Nm”.
(7) Re-connect the connectors. Be sure that all the connectors are connected correctly and securely
inserted.
Sub-Heat sink
(8)Install the cover, then turn on the supply. Check the operation.
10-3. N/F P.C. Board (MCC-1551) Replacement Procedure
(1) Turn off the power supply of the indoor unit
(2) Remove all the connectors and remove earth lead from metals. (Remove the connectors by pulling the
connector body. Do not pull the wire, because there are some rocks in connector).
(3) Remove the Fan IPDU from four PCB spacer (a).
(4) After changing PCB, re-connect the connectors. Be sure that all the connectors are connected correctly
and securely inserted. And Screw to earth lead.
(5) Install the cover, then turn on the supply. Check the operation.
Connection points
Power terminal side
FAN IPDU side
Earth lead
(a)Spacer
SETUP AT LOCAL SITE AND OTHERS
- 69 -
9.
9-1. Indoor Unit
9-1-1. Test Run Setup on Remote Controller
<Wired remote controller>
1. When pushing Then push button.
• “TEST” is displayed on LC display during operation of Test Run.
• During Test Run, temperature cannot be adjusted but air volume can be selected.
• In heating and cooling operation, a command to fix the Test Run frequency is output.
Detection of check code is performed as usual. However, do not use this function except case of Test Run because it applies load on the unit.
2. Use either heating or cooling operation mode for [TEST]. NOTE : The outdoor unit does not operate after power has been turned on or for approx. 3 minutes after
3.
After a Test Run has finished, push button again and check that [TEST] on LC display has gone off. (To prevent a continuous test run operation, 60-minutes timer release function is provided to this remote controller.)
TEST
button on the remote controller for 4 seconds or more, “TEST” is displayed on LC display.
ON / OFF
operation has stopped.
TEST
<Wiress remote controller>
1 When TEMPORARY button is pushed for 10 seconds or more, “Pi!” sound is heard and the
operation changes to test run. After approx. 3 minutes, a cooling operation starts forcedly.
Check cool air starts blowing. If the operation does not start, check wiring again.
2 To stop a test operation, push TEMPORARY button once again (Approx. 1 second).
Check wiring / piping of the indoor and outdoor units in test run.
TEMPORARY button
9-1-2. Forced Defrost Setup of Remote Controller (For wired remote controller only)
- 70 -
(Preparation in advance)
TEST
1 Push
SET
+
+ CL buttons simultaneously for 4 seconds or more on the remote controller.
(Push buttons while the air conditioner stops.)
The first displayed unit No. is the master indoor unit address in the group control.
2 Every pushing
UNIT
button, the indoor unit No. in the group control is displayed one after the
other.
Select a main indoor unit (outdoor unit is connected) which is to be defrosted. In this time, fan of the selected indoor unit operate.
3 Using the set temperature 4 Using the timer time 5 Push 6 Pushing
SET
button. (OK if indication lights)
TEST
button returns the status to the normal stop status.
TIME
TEMP.
buttons, specify the CODE No. (DN) 8C.
buttons, set time to data 0001. (0000 at shipment)
(Practical operation)
• Push ON/OFF
• Select the HEAT mode.
After a while, the forced defrost signal is sent to the outdoor unit and then the outdoor unit starts defrost operation. (The forced defrost operation is performed for Max. 12 minutes.)
• After defrost operation finished, the operation returns to the heating operation.
ON / OFF
Key.
To execute the defrost operation again, start procedure from above item 1 .
(If the forced defrost operation was executed once, setting of the above forced defrost operation is cleared.)
9-1-3. LED Display on Indoor P.C. Board
1. D501 (Red)
• Goes on at the same time when power was turned on (Main microcomputer operates and goes on.)
Flashes with 1-second interval (every 500ms): When EEPROM is not provided or writing was trouble.
• Flashes with 10-seconds interval (every 5S): When the mode is DISP
2. D403 (Red)
• Goes on when power is supplied to remote controller (Lights on the hardware)
3
SET
T
T
CL
FA
N
SA
X
E
F
UNIT
LOUVER
9-1-4. Function Selection Setup
ST
- 71 -
<Procedure> Perform setting while the air conditioner stops.
TE
1 Push
The first displayed unit No. is the master indoor unit address in the group control. In this time, fan of the selected indoor unit operate.
SET
+
+ CL buttons simultaneously for 4 seconds or more.
2
Every pushing displayed one after the other. In this time, fan of the selected indoor unit only operate.
UNIT LOUVER
button (button at left side), the indoor unit No. in the group control is
Ø
Ø
3 Using the set temperature
TEMP.
buttons, specify the CODE No. (DN).
Ø
4
Using the timer time
5
Push
• To change the selected indoor unit, proceed to Procedure 2 .
• To change item to be set up, proceed to Procedure 3 .
6 Pushing
SET
button. (OK if indication lights)
TEST
button returns the status to the normal stop status.
TIME
buttons, select the set data.
Ø
Ø
6
1
<Operation procedure>
1 2 3 4 5 6
ON / OF
TIMER SE
MOD
4
TESTRESE
SWING/FI
5
2
END
Item No. (DN) table (Selection of function)
- 72 -
DN
01
Filter sign lighting time}
02
Dirty state of filter
03
Central control address
06
Heating suction temp shift
0F
Cooling only
10
Type
11
Indoor unit capacity
12
Line address
13
Indoor unit address
14
Group address
Item
Description
0000 :None 0002 :2500H (4-Way/Duct/Ceiling Type)
0000 :Standard 0001 : High degree of dirt
(Half of standard time)
0001 :No.1 unit to 0064 : No.64 unit 0099 :Unfixed
0000 :No shift 0001 : +1°C 0002 :+2°C to 0010 : –10°C
(Up to recommendation + 6)
0000 :Heat pump 0001 : Cooling only
(No display of [AUTO] [HEAT])
0004 :Concealed duct type 0007 : Ceiling type 0014 :Compact 4-way cassette type
0000 : Unfixed 0009 : 56 type 0012 : 80 type 0015 : 110 type 0017 : 140 type
0001 :No.1 unit to 0030 : No.30 unit 0001 :No.1 unit to 0064 : No.64 unit 0000 :Individual 0001 : Master of group
0002 :Follower of group
At shipment
0002 :2500H
0000 : Standard
0099 : Unfixed
0002 : +2°C
0000 : Heat pump
According to model type
According to capacity type
0099 :Unfixed 0099 :Unfixed 0099 :Unfixed
19
Louver type (Air direction adjustment) None for concealed duct
1E
Temp difference of automatic cooling/heating mode selection COOL HEAT, HEAT →COOL
28
Auto restart after power failure
2A
Option Thermostat output
2b
selection (T10 e)
2E
Option
30
Option
31
Option
32
Sensor selection
33
Temperature indication
40 Option 0003 :Default
42 Self clean time 0000: None
0000 :No louver 0001 : Swing only 0002 :1-way 0003 : 2-way 0004 :4-way
0000 :0 deg to 0010 : 10 deg (For setup temperature, reversal of COOL/HEAT by ± (Data value)/2)
0000 :None 0001 : Auto restart
0000 : Indoor thermostat ON 0001 : Output of outdoor comp-ON receiving
0000 :Body TA sensor 0001 : Remote controller sensor 0000 :°C (celsius) 0001 : °F (Fahrenheit)
0001: 0.5h to 0.012: 6.0h The case that compressor-ON time is 10 to 60 minutes is set up. When ON time is over 60 minutes, the operating time becomes two times of it.
According to model type
0003 :3 deg (Ts±1.5)
0000 :None
0002 :Default 0000: Thermostat ON
0000 :Default 0000 :Default 0000 :Default 0000 :Body sensor 0000 :°C
0002: 60 minutes
DN
- 73 -
Item
Description
At shipment
High ceiling selection
5d
(External static pressure selection)
60
Timer set (Wired remote controller)
77 Dual set point
B3 Soft cooling 0000: Unavailable
8b
Correction of high heat feeling
C2
Power sa ving (Current demand × % to outdoor unit)
CC
Forced stop setting for self clean Self clean stop function when [START/
C
d
STOP] operation was prohibited
<Concealed Duct type>
Set data
0000
150Pa
External static
pressure
The list above is when SW501-1 and SW501-2 is OFF.
(Factory default)
0000 :Available (Operable) 0001 :Unavailable (Operation prohibited)
0000: Unavailable 0002: Available
0001: Available
0000 :None 0001 : Correction 0050: 50% to 0100: 100%
0000: None 0001: Set When stopping the air conditioner (including “Fire alarm”
of the control system, etc.) while [START/STOP] operation is prohibited (Central 1, 2) from the central controller side, 0000: Valid (No self cleaning) 0001: Invalid (Self cleaning)
0001
50Pa
According to capacity type
0002
83Pa
0003
217Pa
0004
117Pa
0005
183Pa
0000 :Available
0000: Unavailable
0001: Available
0000 :None 0075: 75%
0000: None 0000: Valid
0006
250Pa
Existence of Power save operation
d0
Existence of 8°C heating operation
d1
function Revolution count of self clean
d3
Display/ No display of [SELF CLEANING]
d4
during self clean operation
F6 Presence of Application control kit
Restriction ratio setting for save operation (DN code No. [C2]) can be set/changed from the normal DN setup
(Detail DN setup).
0000: Invalid (Unavailable) 0001: Valid (Available)
0000: Invalid (Unavailable)} 0001: Valid (Available)
0000: Invalid (Self cleaning is not performed.) 0011: Valid (Self cleaning is performed at 310 rpm.)
0000: Displayed, 0001: Not displayed
0000: None 0001: Exist
0001: Valid (Available)
0000: Invalid (Unavailable)
0000: Invalid
0000: Displayed
0000: None
9-1-4. Cabling and Setting of Remote Controller Control
DIP-Switch [SW30]
4 ON=Follower OFF=Header 3 ON=B OFF=A 2 Not used 1 Not used
SW30
SW30
Bit3 : OFF ON
ON
1ON234
- 74 -
2-remote controller control (Controlled by 2 remote controllers)
This control is to operate 1 or multiple indoor units are controlled by 2 remote controllers. (Max. 2 remote controllers are connectable.)
• When connected 2 remote controllers operate an indoor unit
Remote controller
switch (Master)
Sold
separately
BABA
BA
Indoor unit
3
21
21 3
Outdoor unit
Remote controller
switch (Sub)
Sold
separately
Remote controller cables (Procured locally)
Terminal block for remote controller cables
(Setup method)
One or multiple indoor units are controlled by two remote controllers. (Max. 2 remote controllers are connectable.)
<Wired remote controller>
How to set wired remote controller as sub remote controller
Change DIP switch inside of the rear side of the remote controller switch from remote controller master to sub. (In case of RBC-AMT32E)
Remote controller (Inside of the rear side)
Sub remote
controller
Master remote
controller
1 2
12
1 2
DIP switch
<Wireless remote controller>
Remote controller address (A-B selection) setting
• When two or more signal receiving units are installed in a room, a unique address can be set for each signal receiving unit to prevent interference.
• Address (A-B selection) must be changed on both signal receiving unit and wireless remote controller.
• For the details of address change (A-B selection) on wireless remote controller, refer to the owner’s manual.
Turn off the indoor unit power supply. Tur n on the bit 3 of DIP switch SW30 on the signal receiving unit P.C. board.
The setting change is shown below.
Wireless remote controller (A-B selection)
- 75 -
Using 2 wireless remote controllers for the respec­tive air conditioners, when the 2 air conditioners are closely installed.
Wireless remote controller B setup
1. Start the air conditioner.
2. Point the wireless remote controller at the indoor unit.
3. Push and hold
button on the wireless
CHK
remote controller by the tip of the pencil. “00” will be shown on the display.
4. Push MODE
MODE
button during
CHK
pushing .
“B” will be shown on the display and “00” will be disappear and the air conditioner will turn OFF. The wireless remote controller B is memorized.
"B" Display
"00" Display
PRESET FAN
NOTE
• Repeat above step to reset wireless remote controller to be A.
• The wireless remote controllers do not display “A”.
• The factory default of the wireless remote controllers is “A”.
• A-B selection can be set with signal receiving unit. For the further details, refer to the installation manual.
9-1-5. Monitor Function of Remote Controller
ST
U
R
ST
SET
T
T
CLSAS
X
E
ON / OFF
UNIT
LOUVER
- 76 -

Calling of sensor temperature display

<Contents>
Each sensor temperature of the remote controller, indoor unit, and outdoor unit can become known by calling the service monitor mode from the remote controller.
<Procedure>
1 Push
TE
+ CL buttons simultaneously for 4 seconds to
call the service monitor mode.
The service monitor goes on, the master indoor unit No. is displayed, at first and then the temperature of CODE No.
0000
00
0000
is
displayed.
2 Push temperature set
TEMP.
buttons and then change
the CODE No. of data to be monitored.
The item code list is shown below:
TIMER SE
TESTRESE
WING/FI
241 3
MOD
CODE No.
01
02 03
04
07
Indoor unit data
F2 F3
Data name
Room temperature (Remote controller)
Indoor suction temperature (TA) Indoor heat exchanger (Coil)
temperature (TCJ) Indoor heat exchanger (Coil)
temperature (TC) Indoor fan revolution frequency Indoor fan calculated operation time Filter sign time
Unit
°C
°C °C
°C
rpm
×100h
×1h
CODE No.
60
Outdoor heat exchanger (Coil) temperature (TE)
61
Outside temperature (TO)
62
Compressor discharge temperature (TD)
63
Compressor suction temperature (TS)
65
Heat sink temperature (THS)
6A
Operation current (× 1/10)
6D
Outdoor unit data
Outdoor heat exchanger (Coil) temperature (TL)
70
Compressor operation frequency
72
Outdoor fan revolution frequency (Lower)
73
Outdoor fan revolution frequency (Upper)
F1
Compressor calculated operation time
<Operation procedure>
1 2 3 4
Returned to usual display
Data name
Unit
°C °C °C °C °C
A
°C
rps rpm rpm
×100h
3
Push Each data of the indoor unit and its outdoor units can be monitored.
4
Pushing
• The data value of each item is not the real time, but value delayed by a few seconds to ten-odd seconds.
• If the combined outdoor unit is one before 2 or 3 series, the outdoor unit data [6D], [70], [72] and [73] are
NIT LOUVE
button to select the indoor unit to be monitored.
TE
button returns the status to the usual display.
not displayed.
Ø
Ø
ST
ST
SET
T
T
CLSAS
X
E
ON / OFF
UNIT
LOUVER
s
- 77 -
Calling of trouble history
<Contents>
The trouble contents in the past can be called.
<Procedure>
TE
1 Push
CL
+
buttons simultaneously for 4 seconds or
more to call the service check mode.
01
Service Check goes on, the CODE No. then the content of the latest alarm is displayed.
The number and trouble contents of the indoor unit in which trouble occurred are displayed.
01
01
is displayed, and
01
01
TIMER SE
MOD
2 In order to monitor another trouble history, push the set
TESTRESE
WING/FI
temperature / buttons to change the trouble
history No. (CODE No.)
01
01
01
CODE No. NOTE : 4 trouble histories are stored in memory.
3 Pushing
(Latest) CODE No.
01
01
TE
button returns the display to usual display.
REQUIREMENT
Do not push deleted by pushing CL button, turn off the power supply once and then turn on the power supply again. When the trouble which is same as one occurred at the last before deletion continuously occurs again, it may not be stored in memory.
CL
button, otherwise all the trouble histories of the indoor unit are deleted. If the trouble histories are
04
04
04
04
04
(Old)
<Operation procedure>
231
1 2 3
Returned to usual display
(Group control operation)
In a group control, operation of maximum 8 indoor units can be controlled by a remote controller. The indoor unit connected with outdoor unit (Individual/Header) controls room temperature according to setting on the remote controller.
<System example>
OUT
IN
1-1 2-1
OUT
IN
Header
OUT
IN
3-1 4-1 8-1
OUT
IN
OUT
IN
Max. 8 unit
Remote controller
1. Display range on remote controller The setup range (Operation mode/Air volume select/Setup temp) of the indoor unit which was set to the header unit is reflected on the remote controller.
1) Concealed duct high static pressure type (RAV-SMXXX) is not set up on the header unit.
• If the Concealed duct high static pressure type is the header unit: Operation mode: [Cooling/Heating AUTO] [HEAT] [COOL] [FAN] and no [DRY] Air volume select: [HIGH]
• When the operation mode is [DRY], [FAN] stops in concealed duct high static pressure models.
2. Address setup If there is no serial communication between indoor and outdoor when the power is turned on, it is judged as follower unit of the twin. (Every time when the power is turned on)
• The judgment of header (wired) / follower (simple) of twin is carried out every time. It is not stored in non-
volatile memory.
Turn on power of the indoor unit to be controlled in a group within 3 minutes after setting of automatic address. If power of the indoor unit is not turned on within 3 minutes (completion of automatic address setting), the system is rebooted and the automatic address setting will be judged again.
1) Connect indoor/outdoor connecting wire surely.
2) Check line address/indoor address/group address of the unit one by one.
3) The unit No. (line/indoor gout address) which have been set once keep the present status as a rule if the unit
No.
is not duplicated with one of another unit.

- 78 -
Indoor unit power-ON sequence

Power ON
<By indoor unit which receives power feed from outdoor unit>
<Automatic address judgment>
Gr construction check
• The unit without power feed waits entirely Waiting status is released by system start
• Reboot when power is fed on the way
Not normal NO
3 minutes elapse
Normal Gr normal
1) There is no duplicated indoor unit address.
2) There is no invalid indoor unit address.
3) Individual unit and header / follower units are not intermingled.
4) Only a unit for individual.
5)
Header indoor unit and 1 or more follower units for Gr.
System start
<Initial communication>
Outdoor model distinction (10 seconds) (Indoor unit) Gr construction, (Remote controller)
Remote controller operation is available.
YES
Automatic address starts.
(Approx. 1 minute up to finish)
<Cautions at test run>
• Power supply/Indoor/Outdoor serial and Gr wiring: OK
• Powers of all indoor units are turned on within 3 minutes.
• Reception time for remote controller operation (After power supply was turned on)
1) When address is OK : Approx. 50 seconds
2) In AUTO address : Approx. 4 to 5 minutes
(Approx. 50 seconds after power-ON)
<Usual regular communication>
Regular communication between indoor units (Every 30 seconds) (Header / Follower) (When the above status changes, immediately communicates.)
(Repetition)
• In a group operation, if the indoor unit which was fed power after judgment of automatic address cannot receive regular communication from the header unit and regular communication on identical pipe within 120 seconds after power was turned on, it reboots (system reset).
The operation starts from judgment of automatic address (Gr construction check) again.
(If the address of the header unit was determined in the previous time, the power fed to the header unit and reboot works, the header unit may change though the indoor unit line address is not changed.)
9-2. Setup at Local Site / Others
- 79 -
Model name: TCB-PCNT30TLE2
9-2-1. 1:1 Model Connection Interface
1. Function
This model is an optional P.C. board to connect the indoor unit to 1:1 model connection interface.
2. Microprocessor block diagram
Indoor unit
CN050
Indoor control
P.C. board
CN041
Terminal block (A, B)
Remote controller
1:1 model connection interface P.C. board
CN51
1:1 model
connection interface
communication circuit
CN40
Terminal
resistance
SW01
MCC-1440
Communication units : Total 64 units Communication distance : 2000 m
Central controller
1:1 model connection interface
3. 1:1 model connection interface wiring connection
CAUTION
1) When controlling customized setup collectively, 1:1 model connection interface (This option) is required.
2) In case of group operation, the 1:1 model connection interface is necessary to be connected to the main unit.
3) Connect the central control devices to the central control system wiring.
4) When controlling DI, SDI series only, turn on only Bit 1 of SW01 of the least line of the system address No. (OFF when shipped from the factory)
In case of DI, SDI series, the address is necessary to be set up again from the wired remote
controller after automatic addressing.
Central control device
U2
U1
U4
U3
Outdoor unit
Caution 3
Indoor unit
Central control device
Refrigerant line 1
123
U4
U3
123
U1 U3
U2 U4
Central control devices: Max. 10 units
Refrigerant line 2
3
12
Header unit
123
U4 1 2 3
U3
Refrigerant line 3
12
3
Follower unit
1:1 model connection interface
This product
( )
sold separately
A
B
A
Caution 1
[If mixed with SMMS series (Link wiring), multi indoor units are included.]
* However group follower units of SDI, DI series are not included in number of the units.
Indoor units in all refrigerant lines: Max.64 units
Caution 2
Group operation (Max. 8 units)
B
Remote controller
Remote controller Remote controllerRemote controller
wiring
A
B
4. Wiring specifications
- 80 -
• Use 2-core with no polar wire.
• Match the length of wire to wire length of the central
control system. If mixed in the SMMS system, the wire length is lengthened
with all indoor/outdoor inter-unit wire length at side.
No. of wires
2
Up to 1000m: twisted wire 1.25mm Up to 2000m: twisted wire 2.0mm
Size
• To prevent noise trouble, use 2-core shield wire.
• Connect the shield wire by closed-end connection and apply open process (insulating process) to the last
terminal. Ground the earth wire to 1 point at indoor unit side. (In case of central controlling of digital inverter (DI, SDI) unit setup)
CAUTION
1) Closed-end connection of shield wire (Connect all the connecting par ts of each indoor unit)
2) Apply open process to the last terminal (insulating process).
Central control device
U2
U1
Outdoor unit
3) Ground ear th wire to 1 point at indoor unit side.
Caution 2
123
Caution 1
12
3
Central control
system wiring
12
3
2
2
Indoor unit
U3
123
U4
Remote controller
Header unit
U3
U4
123
B
A
Remote controller
B
A
(Group operation)
Follower unit
U3
123
U4
Remote controller
: 1:1 model connection interface
B
A
(This option)
5. P.C. board switch (SW01) setup
When performing collective control by DI or SDI only, the setup of terminator is necessary.
• Using SW01, set up the terminator.
• Set up the terminator to only the adapter connected to the indoor unit of least line address No.
Central control device
U2
U1
U4
U3
Refrigerant line 1
Outdoor unit
Indoor unit
U3
U4
Central control device
U1
U2
U3
U4
123
123
Central control system wiring
Central control devices: Max. 10 units
Refrigerant line 2
3
12
Header unit
123
U4
U3
Refrigerant line 3
12
Follower unit
123
3
Indoor/outdoor inter-unit wire (AC230V serial)
A
1:1 model
connection interface
This product
( )
sold separately
Line address
SW01 Bit 1 SW01 Bit 2
Remarks
Remote controller Remote controller Remote controller
Turn SW01 Bit 1 to ON.
B
1
ON
OFF
(Reference) Setup contents of switch
SW01
Bit 1 OFF
ON
OFF
ON
Bit 1 OFF OFF
ON ON
As status shipped from factory
Terminator
None 100Ω
75Ω 43Ω
Mixed with multi (Link wiring) at shipment from factory Central control by digital inverter only Spare Spare
A
B
Group operation (Max. 8 units)
2
OF
OFF
(OFF at shipment from factory) (OFF at shipment from factory)
Remarks
A
B
Remote controller wiring
SET
T
T
CLSAS
X
E
ON / OFF
UNIT
LOUVER
6. External view of P.C. board assembly
- 81 -
Terminator (SW01)
52
85
7. Address setup
In addition to set up the central control address, it is necessary to change the indoor unit number. (Line/Indoor/Group address). For details, refer to 1:1 model connection interface Installation Manual.
9-3. How to Set up Central Control Address Number
When connecting the indoor unit to the central control remote controller using 1:1 model connection interface, it is necessary to set up the central control address number.
• The central control address number is displayed as the line No. of the central control remote controller.
<Procedure> Perform setup while the unit stops.
1 Push
TEST
When group control is executed, first the unit No. is displayed and all the indoor units in the group control are selected. In this time, fans of all the selected indoor units are turned on. (Fig. 1) (Keep displayed status without pushing
In case of individual remote controller which is not group-controlled, Line address and Indoor unit address are displayed.
2 Using temperature setup 3 Using timer time
The setup data is shown in the table below (Table 1).
4 Push 5 Push
SET
• To change the item to be set up, return to Procedure 2.
TEST
The status returns to usual stop status.
VENT
+
buttons for 4 seconds or more.
TEMP.
buttons, specify CODE No. !.
TIME
buttons, select the setup data.
button. (OK if display goes on.)
button.
UNIT LOUVER
button.)
(Fig.1)
(Table 1)
Setup data
0001 0002 0003
:
0064 0099
Central control address No.
1 2 3
:
64
Unset (Setup at shipment from factory)
2 1
5
TIMER SE
MOD
3
TESTRESE
WING/FI
1 4
How to confirm the central control address (New function for AMT32E remote controller)
- 82 -
<Procedure> It can be confirmed even during operation or stopping.
1 Push UNIT of
UNIT LOUVER
button for 4 seconds or more.
ò
2
In the frame at left side of the remote controller screen, the lighting set contents are displayed.
During unset time, '' (At shipment from factory) is displayed.
ò
3
After lighting display for 3 seconds, the display automatically disappears.
If any button is pushed during display, immediately the display disappears and then the pushed button is displayed.
10. ADDRESS SETUP
- 83 -
10-1. Address Setup Procedure
When an outdoor unit and an indoor unit are connected, or when an outdoor unit is connected to each indoor unit respectively in the group operation even if multiple refrigerant lines are provided, the automatic address setup completes with power-ON of the outdoor unit.
The operation of the remote controller is not accepted while automatic address works. (Approx. 4 to 5 minutes)
Setup of line address of outdoor unit, indoor unit address, and group address
Completion of cabling work
Do you arbitrarily set the
indoor unit address?
YES
Connect one remote controller with one indoor unit (1 : 1) tentatively with communication cable.
Turn on power of outdoor unit.
Set to all indoor units one by one.
(MANUAL)
NO
Is group control performed?
YES
Do you change setting after
automatic setting at the first time?
YES
Turn on power of outdoor unit.
After completion of address setup, change is to arbitral
( )
address/group manually.
NO
NO
(To AUTO address mode)
Setup of automatic address finishes within
( )
4 to 5 minutes.
Is refrigerant line 1 line?
Turn on power of outdoor unit.
YES
END
• When the following addresses are not stored in the neutral memory (IC503) on the indoor P.C. board, a test
run operation cannot be performed. (Unfixed data at shipment from factory)
Line address Indoor unit
address
Group address
CODE No.
12
13
14
Data at shipment
0099
0099
0099
Setup data range
0001 (No. 1 unit) to 0030 (No. 30 unit) 0001 (No. 1 unit) to 0064 (No. 64 unit)
Max. value of indoor units in the identical refrigerant line 0000 : Individual (Indoor units which are not controlled in a group)
0001 : Header unit (1 indoor unit in group control) 0002 : Follower unit (Indoor units other than master unit in group control)
10-2. Address Setup & Group Control
- 84 -
<Terminology>
Indoor unit No. : N - n = Outdoor unit line address N (Max. 30) - Indoor unit address n (Max. 64)
Group address : 0 = Single (Not group control)
1 = Header unit in group control 2 = Follower unit in g roup control
Header unit (= 1) : The representative of multiple indoor units in g roup oper ation sends/receives signals
to/from the remote controllers and follower indoor units . ( It has no relation with an indoor unit which communicates serially with the outdoor units.) The operation mode and setup temperature range are displayed on the remote controller LCD.
Follow er unit (= 2) : Indoor units other than header unit in group operation
Basically, follower units do not send/receive signals to/from the remote controllers. (Except troubles and response to demand of service data)
10-2-1. System Configuration
1. Single
Outdoor
Indoor
Remote controller
2. Single group operation
• Each indoor unit controls the outdoor unit individually.
2-1
Header/Sub
1-1
Header/Sub
4-1
Header/Master
1-1
Individual
(Header/Master)
3-1
Header/Sub
8-1
Header/Sub
10-2-2. Automatic Address Example from Unset Address (No miswiring)
- 85 -
1. Standard (One outdoor unit)
1) Single
1-1
Individual
(Header/Master)
Only turning on source power supply (Automatic completion)
2. Group operation (Multiple outdoor units = Multiple indoor units with serial communication only, without twin)
2-1
Header/Sub
1-1
Header/Sub
3-1
Header/Master
8-1
Header/Sub
(Max. : 8 units)
Only turning on source power supply (Automatic completion)
SET
E
T
T
CL
SA
VE
S
X
T
E
ON / OFF
UNIT
LOUVER
10-3. Address Setup (Manual Setting from Remote Controller)
- 86 -
In case that addresses of the indoor units will be determined prior to piping work after cabling work
• Set an indoor unit per a remote controller.
• Turn on power supply.
(Example of 2-lines cabling) (Real line: Cabling, Broken line: Refrigerant pipe)
Outdoor
1 23
Outdoor
1 2 3
Line address 1
Indoor unit address 1
Group address 1
1 Push
SET
+ CL +
TEST
buttons simultaneously
for 4 seconds or more.
2 (
Line address)
Using the temperature setup
12 to the CODE No.
set
/ buttons,
3 Using timer time / buttons, set the line address. 4 Push 5 (
SET
button. (OK when display goes on.)
Indoor unit address)
Using the temperature setup
/ buttons, set 13 to the CODE No.
6 Using timer time / buttons, set 1 to the line address. 7 Push 8 (
SET
button. (OK when display goes on.)
Group address)
Using the temperature setup
/ buttons, set 14 to the CODE No.
1 2 3
Indoor
A B
A B
Remote controller
For the above example, perform setting by connecting singly the wired remote controller without remote controller inter-unit cable.
Group address Individual : 0000
Header unit : 0001 Follower unit : 0002
1 2 3
Indoor
A B
2 1 2
In case of group control
9 Using timer time / buttons, set 0000 to Individual, 0001 to Master unit, and 0002 to sub unit. 10 Push 11 Push
SET
button. (OK when display goes on.)
TEST
button.
Setup completes. (The status returns to the usual stop status.)
2, 5, 8
END 11
TIMER SE
TIM
TESTRESE
MOD
VEN
WING/FI
3, 6, 9 4, 7, 10
1
<Operation procedure>
1 2 3 4 5 6 7 8 9 10 11 END
SET
T
T
CLSAS
X
E
ON / OFF
UNIT
LOUVER
SET
T
T
CLSAS
X
E
ON / OFF
UNIT
LOUVER
10-4. Confirmation of indoor unit No. position
- 87 -
1. To know the indoor unit addresses though position of the indoor unit body is recognized
• In case of individual operation (Wired remote controller : indoor unit = 1 : 1) (Follow to the procedure during operation)
<Procedure>
1 Push 2 Push UNIT of
Unit No. 1-1 is displayed on LCD. (It disappears after seve ral seconds.) The displayed unit No. indicate line address and
indoor unit address. (When other indoor units are connected to the
identical remote controller (Group control unit), other unit numbers are also display ed every pushing
UNIT LOUVER
ON / OFF
button.
button if the unit stops.
UNIT LOUVER
button.
TESTRESE
<Operation procedure>
TIMER SE
MOD
WING/FI
1
Operation
2
2. To know the position of indoor unit body by address
• To confirm the unit No. in the group control (Follow to the procedure during operation) (in this procedure, the indoor units in group control stop.)
<Procedure>
The indoor unit numbers in the group control are successively displayed, and fan, and drain pump of the corresponding indoor unit are turned on. (Follow to the procedure during operation)
1 Push
VENT
and
TEST
buttons simultaneously for
4 seconds or more.
• Unit No. is displayed.
• Fans of all the indoor units in the group control operate.
2 Every pushing UNIT of
UNIT LOUVER
button, the unit numbers
in the group control are successivel y displayed.
• The unit No. displayed at the first time indicates the master unit address.
• Fan of the selected indoor unit only operate.
3 Push
TEST
button to finish the procedure.
All the indoor units in the group control stop.
1 2
END
1
TESTRESE
3
<Operation procedure>
1 2 3
TIMER SE
END
MOD
WING/FI
2
11. DETACHMENTS
- 88 -
WARNING
Be sure to stop operation of the air conditioner before
work and then turn off switch of the breaker.
No.
Electrical parts box cover
1. Detachment
1) Remove the fixing screws A fixing the electrical parts box cover. Loosen the fixing screws B.
2) Slide the electrical parts box cover to the arrow direction
and remove the electrical parts box cover.
2. Attachment
1) Hang the electrical parts box cover to the screws B and tighten the screws.
2) Attach the removed screws A to the original positions.
CAUTION
Be sure to put on gloves during working time; otherwise an injury will be caused by a part, etc.
RemarksProcedurePart name
Electrical parts box cover
Screw A
Fan cotrol P.C. board MCC-1610
Screw B
Cotrol P.C. board MCC-1643
Control
P.C. board MCC-1643
1. Detachment
1) Perform 1 of t o remove the electrical parts box
cover.
2) Remove the connector of the below No. from the P.C.
board.
3) Unlock the locking card spacers (4 positions) in the
electrical parts box to remove the control P.C. board. CN41 : A,B terminal block (2P, Blue) CN67 : Power supply terminal block (5P: Black) CN101 : TC sensor (2P, Black) CN102 : TCJ sensor (2P, Red) CN104 : TA sensor (2P, Yellow) CN521 : UART(5P,Red) CN22 : Ground (Faston terminal) CN34 : Float switch (3P, Red) *Option
NOTE
First unlock the housing and then remove the connectors.
TA Sensor
CN104
Card spacer (4 positions)
Noise filter P.C. board MCC-1551
TC Sensor
CN101
TCJ Sensor
CN102
A,B terminal CN41
Float switch
CN34
UART CN521
Ground CN22
Power supply CN67
Part name Procedure Remarks
- 89 -
No.
Control
P.C. board MCC-1643
2. Attachment
1) Mount the control P.C. board in the electrical parts
box as before.
2) Be sure to wire in the electric parts box as before.
NOTE 1
Check if there is no missing or contact failure of the connectors.
NOTE 2
Be sure to wire as before.
3) Attach the electrical parts box cover as before.
Fan control
P.C. board MCC-1610
1. Detachment
1) Perform 1 of to remove the electrical parts box cover.
2) Remove the connector of the below No. from the P.C . board.
CN504 : UART (5P, Blue) CN500 : Power supply terminal block (3P: White) CN510 : Reactor (Faston terminal) CN511 : Reactor (Faston terminal) CN602 : Relay (2P, Black) CN703 : Fan motor (Black wire) W CN704 : Fan motor (White wire) V CN705 : Fan motor (Red wire) U
NOTE
First unlock the housing and then remove the
connectors.
3) Remove the screws A.
4) Unlock the card edge spacers (4 positions) in the electrical parts box to remove the fan control P.C. board.
2 . Attachment
1) Mount the fan control P.C. board in the electrical parts
box as before.
2) Be sure to wire in the electrical parts
box as before.
NOTE 1
Check if there is no missing or contact failure
of the connectors.
Power supply CN500
Reactor CN510,511
Uart
CN504
Fan motor CN703,704,705
Relay CN602
NOTE 2
Be sure to wire as before.
4) Attach the electrical parts box cover as before.
Screw A
Part name Procedure Remarks
- 90 -
No.
Noise filter
P.C. board MCC-1551
1. Detachment
1) Perform 1 of to remove the electrical parts box cover.
2) Remove the connector of the below No. from the P.C .
board.
CN01 : Power supply (Red wire)
CN02 : Power supply (White wire)
CN03 : Power supply (Red wire)
CN04 : Power supply (White wire)
3) Remove the screw of the earth wire.
4) Unlock the card edge spacers (4 positions) in the
electrical parts box to remove the noise filter P.C. board.
NOTE
First unlock the housing and then remove the
connectors.
2. Attachment
1) Mount the noise filter P.C. board in the electrical parts
box as before.
2) Be sure to wire in
the electric parts box as before.
NOTE 1
Check if there is no missing or contact failure of the connectors.
CN04
CN03
Earth screws
CN02
CN01
Power supply
Bottom plate
(fan side)
NOTE 2
Be sure to wire as before.
3) Attach the electrical parts box cover as before.
1. Detachment
Remove the screw A fixing the bottom plate
1)
(fan side). Loosen the screw B.
2) Slide the bottom plate (fan side) to the arrow direction and remove the bottom plate (fan side).
2. Attachment
1) Hang the bottom plate (fan side) to the screw B.
2) Attach the removed screw A to the original positions.
3) Attach the bottom plate (fan side) as before.
Screw A
Bottom plate (fan side)
Screw B
Part name Procedure Remarks
- 91 -
No.
Fan motor,
Fan
1. Detachment
1) Perform 1 of to remove the electrical parts box
Wires of the fan motor CN703 CN704 CN705
cover.
2) Remove the connectors of the wires of the fan motor
from the fan control P.C. board.
CN703 : Fan motor (Black wire)
CN704 : Fan motor (White wire)
CN705 : Fan motor (Red wire)
3)
Remove the ferrite core from wire of the fan motor.
Ferrite core
4) Perform 1 of to remove the bottom plate(fan side).
5)
Remove the screw A (M8 x 20, 8 pcs) . and loosen the screw B (M8 x 20, 2 pcs) . (The fan motor is in the temporary hanging state by the fixing plate.)
6)
Remove the fan assembly.
Ferrite core
Screw A
Fan assembly
CAUTION
Weight of the fan assembly is about 30kg. Handle it by 2 workers.
7) Remove the screw C (M8 x 20, 8 pcs) .
8) Loosen the hexagonal bolt of the fan and
pull out the fan from the shaft.
9) Remove the screw D (4 pcs) from the fan case
and remove the nose plate and then take out the fan.
10) Remove the earth screw of fan motor.
11) Remove the screw E (M8 x 20, 2 pcs) and
remove the motor fixing plate and fan motor.
Earth screw
Screw B
Screw C
hexagonal bolt
Screw D
Nose plate
Part name Procedure Remarks
- 92 -
No.
Fan motor,
Fan,
2. Attachment
1) Screw the fan motor with the motor fixing plate. (M8 x 20, 2 pcs).
NOTE
Fix the wiring of the motor on the electrical parts box side as right figure.
2) Attach the earth screw.
3) Put the fan in the fan case.
Attach the nose plate to the original position on the fan case.
NOTE
Adjust the direction of the fan blade.
4) Insert the fan to the shaft.
5) Tighten the Screw C. (M8 x 20, 8 pcs)
6) Insert the fan to where the shaft of the fan motor stops,
and adjust the flat portion(2 places) ,
then tighten the hexagon head bolt.
NOTE
Check that if the fan rotate smoothly without touching the fan case.
Electrical parts box
Fan blade
shaft
Wiring of the motor
flat portion
Ground screw
NOTE
Be sure to use a torque wench for fixing and tighten with 10.0Nm
7) Hook the fan assembly on the looser screw B.
8) Tighten the screw A and B.(M8 x 20, 10 pcs)
9) A ferrite core is attached to the wire of a fan motor as before within an electric part box. Connect the wires of the fan motor as before, and close and fix the electrical parts box cover. Be sure to wire in the electrical parts box as before.
10) Attach the bottom plate(fan side) to the original position.
NOTE
When the ferrite core is attached to the earth wire of a fan motor as below photo, please repairing work indicated to P96 ~ 99.
Ferrite core attached in earth lead of motor
Wires of the fan motor CN703 CN704 CN705
Ferrite core
flat portion
Hexagonal bolt
Ferrite core
Part name Procedure Remarks
- 93 -
No.
Drain pan
1. Detachment
1) Remove the drain hose or drain cap and then extract the drain water accumulated in the drain pan.
NOTE
When removing the drain hose or drain cap, be sure
to take the drain water with a bucket, etc.
2) Remove the screw A fixing the bottom plate. (9 positions) Loosen the screw B. (4 positions)
3) Slide the bottom plate (drain side) to the arrow direction and then remove the panel.
4) Loosen the screw of the drain pan supporter, and turn the drain pan supporter.
5) Lower the drain pan of the drain socket side, and remove it to the arrow direction slowly.
CAUTION
When removing the drain pan, do not hold the drain socket. (Water leakage may occur.)
2. Attachment
1) Put back the drain pan, and turn back the drain pan supporter and fix it with the screws.
2) Attach the bottom plate (drain side) to the original position.
Bottom plate (Drain side)
Screw A
Drain pan supporter
Drain pan pull-out
direction.
Drain pan
Screw B
Drain socket
Sensor
TC, TCJ
1. Detachment
1)
Perform 1 of to remove the electrical parts box cover.
Loosen the fixing screws of the inspection cover and
2)
remove the inspection cover.
3)
Remove the connectors of the wires of TC sensor and TCJ sensor from the control P.C. board.
CN101 : TC sensor (2P, Black) CN102 : TCJ sensor (2P, Red)
4)
Remove the sensor from the
TC Sensor
CN101
TCJ Sensor
sensor holder.
sensor clip
sensor holder
Control P.C.board
MCC-1643
2. Attachment
1)
Attach the TC sensor and TCJ sensor to the original position.
2)
Attach the inspection cover as before.
Attach the wires of TC sensor, and TCJ sensor as
3)
before.
Attach the electrical parts box cover as before.
4)
Screw
CN102
Inspection cover
TCJ sensor
(Red)
TC sensor
(Black)
Part name Procedure Remarks
- 94 -
No.
Heat
exchanger
1. Detachment
1) Recover the refrigerant gas and then remove the refrigerant pipe of the indoor unit.
2) Perform 1 of ⑦ to remove the drain pan.
3) Remove the screw A (M4 x 0.4" (10mm), 7 pcs)
and remove the Left side panel.
4) After performing 1) and 3) of 1 of ⑧ , withdraw the wire of the sensor from the bushing to the heat exchanger side.
5) Remove the screw B (M4 x 0.4" (10mm), 3 pcs) and remove the evaporator partition (back).
Left side panel
6) Remove the screw C (M4 x 0.4" (10mm), 4 pcs) and remove the evaporator partition (down).
7) Remove the screw D (M4 x 0.4" (10mm), 5 pcs)
Screw A
of the right side panel.
8) While holding the heat exchanger, remove the screw E (M4 x 0.4" (10mm), 2 pcs) and then take out the heat exchanger slowly.
Right side panel
Heat exchanger
Screw E
Screw C
Evaporator partition (down)
2. Attachment
1) Attach the heat exchanger to the original position.
Screw E (M4 x 0.4" (10mm), 2 pcs)
2) Fix the screw D on the right side panel as before.
Screw D (M4 x 0.4" (10mm), 5 pcs)
3) Attach the evaporator partition (down) as before.
Screw C (M4 x0.4" (10mm), 4 pcs)
4) Attach the evaporator partition (back) as before.
Screw B (M4 x 0.4" (10mm), 3 pcs)
5) Perform 1) , 3) and 4) of 2 of ⑧ to attach the
sensor conector and electrical parts box cover .
6) Attach the Left side panel as before.
Screw A (M4 x 0.4" (10mm), 7 pcs)
7) Perform 2 of ⑦ to attach the drain pan and
bottom plate (drain side).
screw D
Screw E
Bushing
Screw B
Evaporator partition (back
Part name Procedure Remarks
- 95 -
No.
Sensor TA
1. Detachment
1)
Perform 1 of and 1 of .
2) Remove the connector of the wires of TA sensor from the control P.C. board.
3) Pinch the lock of the TA sensor holder from the outside
of the electrical parts box and push it into the inside of the electrical parts box.
2. Attachment
1)
Attach the TA sensor to the original position.
Attach the wires of TA sensor in the holder as before.
2)
3) Attach the electronical parts box as before.
TA sensor CN104
Electrical parts
box
TA sensor holder
Reactor
NOTE
After assembling, check if that there is no abnormal sound, vibration, or puncture.
Check the exchange point when you have a problem.
1. Detachment
1)
Perform 1 of and 1 of .
2) Remove the connector of the wires of the reactor from the fan control P.C. board.
3)
Remove the screw fixing the reactor cover. Slide the reactor cover to the arrow direction and remove.
4) Remove the screw fixing the reactor.
Remove the reactor from the reactor cover.
2. Attachment
1) Attach the reactor to the reactor cover.
2) Attach the reactor cover as before.
3)
Attach the
wires of the reactor in the
CN511 CN510
Screw
holder as before.
Reactor
Reactor cover
Screw
Reactor assembly
[The way of repairing high static duct 8/10HP according t
- 96 -
o
specification change]
1. Contents
(1) Target production (3) Remove ferrite core which is set in earth lead of fan motor (2) Replacing noise filter PCB (4) Add ferrite core to motor lead
2
. Req
(1) New noise filter PCB(MCC1551) (2) Tie band
3
. Target production
3-1 Target model name .
RAV-RM2241DTP-E/-TR High static duct 8HP LC RAV-RM2801DTP-E/-TR High static duct 10HP LC
3-2 Target products .
uired part
Model name Type System
The target is a
uct which is installed ferrite core in motor earth lead.
prod
Ferrite core attached
in earth lead of motor
The production year March, 2019 or before
4. The contents
4-1 Summary of modification points
Photo of control BOX inside before repairing
of o
PCB for motor
MCC1610
Clamp filter Ferrite core
ther
pairing except motor exchanging
re
Replace noise filter
PCB to he new one
Noise filter PCB
MCC1551
Photo of control BOX inside after repairing
1. Remove the clamp filter
2. Install the ferrite core
which is set in earth lead of
fan motor
4-2 Replace to new noise filter PCB
Photo of motor earth lead before repairing Photo of motor earth lead after repairing
1. Remove the ferrite core
2.Tie the extra length of earth
lead by tie band
Step1
Step2
Step3
Step3
Old PCB : 1117878001 Alternate new PCB : 1117878002
- 97 -
[Step1]
Remove the earth screw from metal plate.
[Step2]
Remove four wiring (red and white) which are connected in PCB.
Notice : These wiring have lock mechanism. So when remove the wiring, it need to push the lock which
is set side of connector.
[Step3]
Unlock the four PCB spacers and remove.
[Step4]
Replace the new noise filter PCB to PCB spacer and connect wiring and tighten screw same as step 1 to 3.
Notice : Before replace the new noise filter PCB, check the number which is described in label on PCB
Old PCB : 1117878001 Alternate new PCB: 1117878002
4-3 Remove ferrite core which is set in earth lead of fan motor and bundle extra length
- 98 -
Step1
[Step1]
Remove the earth screw from metal plate.
[Step2]
Cut the tie band attached in ferrite core and remove a screw which is fixed the ferrite core.
[Step3]
Unwind the earth lead from ferrite core and take off ferrite core.
Notice : Keep the ferrite core. Because the ferrite core is used in motor lead later
[Step4]
Tighten the earth screw.
[Step5]
Bundle up the extra earth lead by folding in half at four times.
[Step6]
Tie the extra earth lead by tie band.
Step2
Step2
Step3
Step4
Step5
Step6
4-4 Install the ferrite core of motor earth lead to motor lead
Step1
PCB for motor
MCC1610
Step2
Step3 Reactor lead
Power lead
Step4
CN705(RED)
CN704(WHI)
CN703(BLK)
Step5
- 99 -
[Step1]
Remove the cramp filter from motor lead.
[Step2] Only motor lead has connect to PCB(MCC1610)
Remove the motor lead from PCB(MCC1610)
[Step3]
Through the motor lead in a hole of ferrite core at twice.
[Step4]
Connect the motor lead to PCB(MCC1610).
Notice : Check the connection between motor lead and connector on PCB invariably
Red motor lead = CN705(RED) White motor lead = CN704(WHI) Black lead = CN703(BLK)
[Step5]
Fix the ferrite core to motor lead and reactor lead and white lead of power lead by using tie band.
12. EXPLODED VIEWS AND PARTS LIST
- 100 -
12-1. RAV-RM2241DTP-E, RAV-RM2801DTP-E
RAV-RM2241DTP-TR, RAV-RM2801DTP-TR
210
'
207
208 209
211
204
202
'
213
205
211
214
218
201
203
217
206
212
216
219
215
217
220
Loading...