Toshiba RAV-GP561ATP-E, RAV-GP561ATP-TR, RAV-GP561ATJP-E Service Manual

SERVICE MANUAL
OUTDOOR UNIT
<SUPER DIGITAL INVERTER>
RAV-GP561ATP-E
RAV-GP561ATP-TR
RAV-GP561ATJP-E
AIR-CONDITIONER
April, 2018
R32
FILE NO. SVM-18041
Original instruction
Adoption of New Refrigerant
This Air Conditioner is a new type which adopts a new refrigerant HFC (R32) instead of the conventional refrigerant R22 in order to prevent destruction of the ozone layer.
CONTENTS
SAFETY CAUTION ................................3
1. SPECIFICATIONS
...............................13
1-1. Outdoor Unit
...............................14
1-2. Operation Characteristic Curve
..............................15
..............................16
2. CONSTRUCTION VIEWS (EXTERNAL VIEWS)
2-1. RAV-GP561ATP
*
..............................16
3. SYSTEMATIC REFRIGERATING CYCLE DIAGRAM
..............................18
3-1. Indoor Unit
..............................20
4. WIRING DIAGRAM
4-1. RAV-GP561ATP
*
..............................20
..............................21
..............................22
5. SPECIFICATIONS OF ELECTRICAL PARTS
6. REFRIGERANT R32
6-1. Safety During Installation/Servicing
..............................22
6-2. Refrigerant Piping Installation
..............................22
6-3. Tools
..............................26
6-4. Recharging of Refrigerant
..............................27
6-5. Brazing of Pipes
..............................28
6-6. Instructions for Re-use Piping of R22 or R407C
..............................30
6-7. Replenishing refrigerant
..............................33
7. OUTDOOR CONTROL CIRCUIT
..............................34
7-1. Outdoor Controls
..............................34
7-2. Outdoor Print Circuit Board
..............................40
8. TROUBLESHOOTING
..............................41
8-1. Summary of Troubleshooting
..............................41
8-2. Troubleshooting
..............................43
8-3. Table Inspection of outdoor unit main parts
..............................63
9. OTHERS
..............................64
9-1. Refrigerant Recovery Control
..............................64
..............................66
9-2. Various Setting on Outdoor Unit
(Existing piping, Power save, Cooling-only, etc.)
..............................75
10. DETACHMENTS
10-
1. RAV-GP561
ATP
*
..............................75
..............................83
11. EXPLODED VIEWS AND PARTS LIST
..............................83
11-1. RAV-GP561ATP
*
FILE NO. SVM-18041
- 2 -
Please read carefully through these instructions that contain important information which complies with the “Machinery” Directive (Directive 2006/42/EC), and ensure that you understand them.
Generic Denomination: Air Conditioner
Definition of Qualified Installer or Qualified Service Person
The air conditioner must be installed, maintained, repaired and removed by a qualified installer or qualified service person.
When any of these jobs is to be done, ask a qualified installer or qualified service person to do them for you. A qualified installer or qualified service person is an agent who has the qualifications and knowledge
described in the table below.
Agent
Qualified installer (1)
Qualified service person (1)
Qualifications and knowledge which the agent must have
s The qualified installer is a person who installs, maintains, relocates and removes the air
conditioners made by Toshiba Carrier Corporation. He or she has been trained to install, maintain, relocate and remove the air conditioners made by
Toshiba Carrier Corporation or, alternatively, he or she has been instructed in such operations by an individual or individuals who have been trained and is thus thoroughly acquainted with the knowledge related to these operations.
s The qualified installer who is allowed to do the electrical work involved in installation, relocation
and removal has the qualifications pertaining to this electrical work as stipulated by the local laws and regulations, and he or she is a person who has been trained in matters relating to electrical work on the air conditioners made by Toshiba Carrier Corporation or, alternatively, he or she has been instructed in such matters by an individual or individuals who have been trained and is thus thoroughly acquainted with the knowledge related to this work.
s The qualified installer who is allowed to do the refrigerant handling and piping work involved in
installation, relocation and removal has the qualifications pertaining to this refrigerant handling and piping work as stipulated by the local laws and regulations, and he or she is a person who has been trained in matters relating to refrigerant handling and piping work on the air conditioners made by Toshiba Carrier Corporation or, alternatively, he or she has been instructed in such matters by an individual or individuals who have been trained and is thus thoroughly acquainted with the knowledge related to this work.
s The qualified installer who is allowed to work at heights has been trained in matters relating to
working at heights with the air conditioners made by Toshiba Carrier Corporation or, alternatively, he or she has been instructed in such matters by an individual or individuals who have been trained and is thus thoroughly acquainted with the knowledge related to this work.
s The qualified service person is a person who installs, repairs, maintains, relocates and removes
the air conditioners made by Toshiba Carrier Corporation. He or she has been trained to install, repair, maintain, relocate and remove the air conditioners made by Toshiba Carrier Corporation or, alternatively, he or she has been instructed in such operations by an individual or individuals who have been trained and is thus thoroughly acquainted with the knowledge related to these operations.
s The qualified service person who is allowed to do the electrical work involved in installation,
repair, relocation and removal has the qualifications pertaining to this electrical work as stipulated by the local laws and regulations, and he or she is a person who has been trained in matters relating to electrical work on the air conditioners made by Toshiba Carrier Corporation or, alternatively, he or she has been instructed in such matters by an individual or individuals who have been trained and is thus thoroughly acquainted with the knowledge related to this work.
s The qualified service person who is allowed to do the refrigerant handling and piping work
involved in installation, repair, relocation and removal has the qualifications pertaining to this refrigerant handling
and piping work as stipulated by the local laws and regulations, and he or she is a person who has been trained in matters relating to refrigerant handling and piping work on the air conditioners made by Toshiba Carrier Corporation or, alternatively, he or she has been instructed in such matters by an individual or individuals who have been trained and is thus thoroughly acquainted with the knowledge related to this work.
s The qualified service person who is allowed to work at heights has been trained in matters
relating to working at heights with the air conditioners made by Toshiba Carrier Corporation or, alternatively, he or she has been instructed in such matters by an individual or individuals who have been trained and is thus thoroughly acquainted with the knowledge related to this work.
SAFETY CAUTION
FILE NO. SVM-18041
- 3 -
Definition of Protective Gear
When the air conditioner is to be transported, installed, maintained, repaired or removed, wear protective gloves and “safety” work clothing.
In addition to such normal protective gear, wear the protective gear described below when undertaking the special work detailed in the table below.
Failure to wear the proper protective gear is dangerous because you will be more susceptible to injury, burns, electric shocks and other injuries.
Work undertaken
All types of work
Electrical-related work
Work done at heights (50 cm or more)
Transportation of heavy objects
Repair of outdoor unit
Protective gear worn
Protective gloves “Safety” working clothing
Gloves to provide protection for electricians and from heat Insulating shoes Clothing to provide protection from electric shock
Helmets for use in industry
Shoes with additional protective toe cap
Gloves to provide protection for electricians and from heat
The important contents concerned to the safety are described on the product itself and on this Service Manual. Please read this Service Manual after understanding the described items thoroughly in the following contents
(Indications/Illustrated marks), and keep them.
[Explanation of indications]
Indication
DANGER
WARNING
CAUTION
Explanation
Indicates contents assumed that an imminent danger causing a death or serious injury of the repair engineers and the third parties when an incorrect work has been executed.
Indicates possibilities assumed that a danger causing a death or serious injury of the repair engineers, the third parties, and the users due to troubles of the product after work when an incorrect work has been executed.
Indicates contents assumed that an injury or property damage () may be caused on the repair engineers, the third parties, and the users due to troubles of the product after work when an incorrect work has been executed.
Property damage : Enlarged damage concerned to property, furniture, and domestic animal/pet
[Explanation of illustrated marks]
Mark Explanation
Indicates prohibited items (Forbidden items to do)
The sentences near an illustrated mark describe the concrete prohibited contents.
Indicates mandatory items (Compulsory items to do)
The sentences near an illustrated mark describe the concrete mandatory contents.
Indicates cautions (Including danger/warning)
The sentences or illustration near or in an illustrated mark describe the concrete cautious contents.
FILE NO. SVM-18041
- 4 -
Warning Indications on the Air Conditioner Unit
[Confirmation of warning label on the main unit]
Confirm that labels are indicated on the specified positions If removing the label during parts replace, stick it as the original.
Warning indication
WARNING
ELECTRICAL SHOCK HAZARD
Disconnect all remote electric power supplies before servicing.
WARNING
Moving parts. Do not operate unit with grille removed. Stop the unit before the servicing.
CAUTION
High temperature parts. You might get burned when removing
this panel.
CAUTION
Do not touch the aluminum fins of the unit. Doing so may result in injury.
CAUTION
BURST HAZARD
Open the service valves before the operation, otherwise there might be the burst.
Description
WARNING
ELECTRICAL SHOCK HAZARD
Disconnect all remote electric power supplies before servicing.
WARNING
Moving parts. Do not operate unit with grille removed. Stop the unit before the servicing.
CAUTION
High temperature parts. You might get burned when removing this panel.
CAUTION
Do not touch the aluminum fins of the unit. Doing so may result in injury.
CAUTION
BURST HAZARD
Open the service valves before the operation, otherwise there might be the burst.
FILE NO. SVM-18041
- 5 -
Precaution for Safety
The appliance shall be installed in accordance with national wiring regulations. Capacity shortages of the power circuit or an incomplete installation may cause an electric shock or fire.
DANGER
Turn off
breaker.
Before carrying out the installation, maintenance, repair or removal work, be sure to set the circuit brea
ker to the OFF position. Otherwise, electric shocks may result.
Before opening the intake grille of the indoor unit or service panel of the outdoor unit, set the circuit breaker to the OFF position.
Failure to set the circuit breaker to the OFF position may result in electric shocks through contact with the interior parts.
Only a qualified installer (1) or qualified service person (1) is allowed to remove the intake grille of the indoor unit or service panel of the outdoor unit and do the work required.
Bef
Do not turn ON the circuit breaker under the condition of removing a cabinet, a panel, etc. Otherwise, it leads to an electric shock with a high voltage, resulting in loss of life.
ore starting to repair the outdoor unit fan or fan guard, be absolutely sure to set the circuit
breaker to the OFF position, and place a “Work in progress” sign on the circuit breaker.
When cleaning the filter or other parts of the indoor unit, set the circuit breaker to OFF without fail, and place a “Work in progress” sign near the circuit breaker before proceeding with the work.
Prohibition
FILE NO. SVM-18041
- 6 -
General
Before starting to repair the air conditioner, read care
fully through the Service Manual, and repair
the air conditioner by following its instructions.
Only qualified service person (1) is allowed to repair the air conditioner. Repair of the air conditioner by unqualified person may give rise to a fire, electric shocks, injury,
water leaks and/or other problems.
Only a qualified installer (1) or qualified service person (1) is allowed to carry out the electrical work of the air conditioner.
Under no circumstances must this work be done by an unqualified individual since failure to carry out the work properly may result in electric shocks and/or electrical leaks.
Wear protective gloves and safety work clothing during installation, servicing and removal.
When connecting the electrical wires, repairing the electrical parts or undertaking other electrical jobs, wear gloves to provide protection for electricians, insulating shoes and clothing to provide protection from electric shocks. Failure to wear this protective gear may result in electric shocks.
Use wiring that meets the specifications in the Installation Manual and the stipulations in the local regulations and laws.
Use of wiring which does not meet the specifications may give rise to electric shocks, electrical leakage, smoking and/or a fire.
Only a qualified installer (1) or qualified service person (1) is allowed to undertake work at heights using a stand of 50 cm or more.
When working at heights, use a ladder which complies with the ISO 14122 standard, and follow the procedure in the ladder’s instructions.
Also wear a helmet for use in industry as protective gear to undertake the work.
When working at heights, put a sign in place so that no-one will approach the work location, before proceeding with the work.
Parts and other objects may fall from above, possibly injuring a person below.
Do not touch the aluminum fin of the outdoor unit. You may injure yourself if you do so. If the fin must be touched for some reason, first put on
protective gloves and safety work clothing, and then proceed.
Do not climb onto or place objects on top of the outdoor unit. You may fall or the objects may fall off of the outdoor unit and result in injury.
When transpor ting the air conditioner, wear shoes with additional protective toe caps.
When transpor ting the air conditioner, do not take hold of the bands around the packing carton. You may injure yourself if the bands should break.
This air conditioner has passed the pressure test as specified in IEC 60335-2-40 Annex EE.
Electric
shock hazard
Prohibition
Stay on
protection
When you access inside of the electric cover to repair electric parts, wait for about five minutes after turning off the breaker. Do not start repairing immediately. Otherwise you may get electric shock by touching terminals of high-voltage capacitors. Natural discharge of the capacitor takes about five minutes.
Place a
When checking the electric parts, removing the cover of the electric parts box of Indoor Unit and/ or front panel of Outdoor Unit inevitably to determine the failure, put a sign “Do not enter” around the site before the work. Failure to do this may result in third person getting electric shock.
Before operating the air conditioner after having completed the work, check that the electrical parts box cover of the indoor unit and service panel of the outdoor unit are closed, and set the circuit breaker to the ON position. You may receive an electric shock if the power is turned on without first conducting these checks.
“Work in progress” sign near the circuit breaker while the installation, maintenance, repair
or removal work is being carried out. There is a danger of electric shocks if the circuit breaker is set to ON by mistake.
If, in the course of carrying out repairs, it becomes absolutely necessary to check out the electrical parts with the electrical parts box cover of one or more of the indoor units and the service panel of the outdoor unit removed in order to find out exactly where the trouble lies, wear insulated heat-resistant gloves, insulated boots and insulated work overalls, and take care to avoid touching any live parts.
You may receive an electric shock if you fail to heed this warning. Only qualified service person (1) is allowed to do this kind of work.
WARNING
FILE NO. SVM-18041
- 7 -
WARNING
Check earth
wires.
Prohibition of
modification.
Use specified
parts.
Do not bring a child close to the equipment.
Insulating measures
Before troubleshooting or repair work, check the earth w
ire is connected to the earth terminals of the main unit, otherwise an electric shock is caused when a leak occurs.If the earth wire is not correctly connected, contact an electric engineer for rework.
After completing the repair or relocation work, check that the earth wires are connected properly.
Be sure to connect earth wire. (Grounding work) Incomplete earthing causes an electric shock. Do not connect earth wires to gas pipes, water pipes, and lightning rods or earth wires for
telephone wires.
Do not modify the products.Do not also disassemble or modify the parts. It may cause a fire, electric shock or injury.
When any of the electrical parts are to be replaced, ensure that the replacement parts satisfy the specifications given in the Service Manual (or use the parts contained on the parts list in the Service Manual).
Use of any parts which do not satisfy the required specifications may give rise to electric shocks, smoking and/or a fire.
If, in the course of carrying out repairs, it becomes absolutely necessary to check out the electrical parts with the electrical parts box cover of one or more of the indoor units and the service panel of the outdoor unit removed in order to find out exactly where the trouble lies, place "Keep out" signs around the work site before proceeding.
Third-party individuals may enter the work site and receive electric shocks if this warning is not heeded.
Connect the cut-off lead wires with cr
Replace components only with parts specified by the manufacturer. Other parts may result in the ignition of refrigerant in the atmosphere from a leak.
imp contact, etc, put the closed end side upward and then
apply a water-cut method, otherwise a leak or production of fire is caused at the users’ side.
No fire
When performing repairs using a gas burner, replace the refrigerant with nitrogen gas because the oil that coats the pipes may otherwise burn.
When repairing the refrigerating cycle, take the following measures.
1) Be attentive to fire around the cycle.
When using a gas stove, etc, be sure to put out fire before work; otherwise the oil mixed with refrigerant gas may catch fire.
2) Do not use a welder in the closed room.
When using it without ventilation, carbon monoxide poisoning may be caused.
3) Do not bring inflammables close to the refrigerant cycle, otherwise fire of the welder may catch
the inflammables.
FILE NO. SVM-18041
- 8 -
Refrigerant
Assembly/
Cabling
Insulator
check
Ventilation
The refrigerant used by this air conditioner is the R32.
C
heck the used refrigerant name and use tools and materials of the parts which match with it.
For the products which use R32 refrigerant, the refrigerant name is indicated at a position on the outdoor unit where is easy to see.
T Be careful for miss-charging since a charging port of R32 is the same diameter as that of R410A.
o prevent miss-charging, the route of the service port is changed from one of the former R22.
For an air conditioner which uses R32, never use other refrigerant than R32. For an air conditioner which uses other refrigerant (R22, R410A etc.), never use R32. If different types of refrigerant are mixed, abnormal high pressure generates in the refrigerating
cycle and an injur If the different type of refrigerants are mixed in, be sure to recharge the refrigerant
y due to breakage may be caused.
Do not charge refrigerant additionally. If charging refrigerant additionally when refrigerant gas leaks, the refrigerant composition in the
refrigerating cycle changes resulted in change of air conditioner characteristics or refrigerant over the specified standard amount is charged and an abnormal high pressure is applied to the inside of the refrigerating cycle resulted in cause of breakage or injury.
Therefore if the refrigerant gas leaks, recover the refrigerant in the air conditioner, execute vacuuming, and then newly recharge the specified amount of liquid refrigerant.
In this time, never charge the refrigerant over the specified amount.
When recharging the refrigerant in the refrigerating cycle, do not mix the refrigerant or air other than R32 into the specified refrigerant.
If air or others is mixed with the refrigerant, abnormal high pressure generates in the refrigerating cycle resulted in cause of injury due to breakage.
After the installation work, confirm that refrigerant gas does not leak. If refrigerant gas leaks into the room and flows near a fire source, such as a cooking range, it may generate noxious gases, causing a fire.
Never recover the refrigerant into the outdoor unit. When the equipment is moved or repaired, be sure to recover the refrigerant with recovering device. The refrigerant cannot be recovered in the outdoor unit; otherwise a serious accident such as
breakage or injury is caused.
Do not use any refrigerant different from the one specified for complement or replacement. Otherwise, abnormally high pressure may be generated in the refrigeration cycle, which may result in a failure or explosion of the product or an injury to your body.
After repair work, surely assemble the disassembled parts, and connect and lead the removed wires as before.
Perform the work so that the cabinet or panel does not catch the inner wires. If incorrect assembly or incorrect wire connection was done, a disaster such as a leak or fire is
caused at user’s side.
After the work has finished, be sure to use an insulation tester set (500V Megger) to check the resistance is 1MΩ or more between the charge section and the non-charge metal section (Earth position).
If the resistance value is low, a disaster such as a leak or electric shock is caused at user’s side.
When the refr
If refrigerant gas has leaked during the installation work, ventilate the room immediately. If the leaked refrigerant gas comes in contact with fire, it may generate noxious gases, causing a fire.
igerant gas leaks during work, execute ventilation.
If the refrigerant gas touches to a fire, it may generate noxious gases, causing a fire.
A case of leakage of the refrigerant and the closed room full with gas is dangerous because a shortage of oxygen occurs. Be sure to execute ventilation.
FILE NO. SVM-18041
- 9 -
Check after
repair
Do not
operate the
unit with the
valve closed.
Check after
reinstallation
Cooling check
Once the repair work has been completed, check for refrigerant leaks, and check the insulation resi
stance and water drainage.
Then perform a trial run to check that the air conditioner is running properly.
After repair work has finished, check there is no trouble. If check is not executed, a fire, electric shock or injury may be caused. For a check, turn off the power breaker.
Install the outdoor unit properly in a location that is durable enough to support the weight of the outdoor unit. Insufficient durability may cause the outdoor unit to fall, which may result in injury.
After repair work (installation of front panel and cabinet) has finished, execute a test run to check there is no generation of smoke or abnormal sound.
If check is not executed, a fire or an electric shock is caused. Before test run, install the front panel and cabinet.
Check the following matters before a test run after repairing piping.
• Connect the pipes surely and there is no leak of refrigerant.
• The valve is opened.
Running the compressor under condition that the valve closes causes an abnormal high pressure resulted in damage of the par ts of the compressor and etc. and moreover if there is leak of refrigerant at connecting section of pipes, the air is suctioned and causes further abnormal high pressure resulted in burst or injury.
Only a qualified installer (1) or qualified service person (1) is allowed to relocate the air conditioner. It is dangerous for the air conditioner to be relocated by an unqualified individual since a fire, electric shocks, injury, water leakage, noise and/or vibration may result.
Check the following items after reinstallation.
1) The earth wire is correctly connected.
2) The power cord is not caught in the product.
3) There is no inclination or unsteadiness and the installation is stable. If check is not executed, a fire, an electric shock or an injury is caused.
When the service panel of the outdoor unit is to be opened in order for the compressor or the area around this part to be repaired immediately after the air conditioner has been shut down, set the circuit breaker to the OFF position, and then wait at least 10 minutes before opening the service panel.
If you fail to heed this warning, you will run the risk of burning yourself because the compressor pipes and other parts will be very hot to the touch. In addition, before proceeding with the repair work, wear the kind of insulated heat-resistant gloves designed to protect electricians.
When the service panel of the outdoor unit is to be opened in order for the fan motor, reactor, inverter or the areas around these parts to be repaired immediately after the air conditioner has been shut down, set the circuit breaker to the OFF position, and then wait at least 10 minutes before opening the service panel.
If you fail to heed this warning, you will run the risk of burning yourself because the fan motor, reactor, inverter heat sink and other parts will be very hot to the touch.
In addition, before proceeding with the repair work, wear the kind of insulated heat-resistant gloves designed to protect electricians.
Compulsion
When the refrigerant gas leaks, find up the leaked position and repair it surely. If t
he leaked position cannot be found up and the repair work is interrupted, pump-down and
tighten the service valve, otherwise the refrigerant gas may leak into the room. When gas touches to fire such as fan heater, stove or cocking stove, it may generate noxious gases, causing a fire though the refrigerant gas itself is innocuous. When installing equipment which includes a large amount of charged refrigerant such as a multi
air conditioner in a sub-room, it is necessary that the density does not the limit even if the refrigerant leaks.
If the refrigerant leaks and exceeds the limit density, an accident of shortage of oxygen is caused.
Tighten the flare nut with a torque wrench in the specified manner. Excessive tighten of the flare nut may cause a crack in the flare nut after a long period, which
may result in refrigerant leakage.
Nitrogen gas must be used for the airtight test.
The charge hose must be connected in such a way that it is not slack.
For the installation/moving/reinstallation work, follow to the Installation Manual. If an incorrect installation is done, a trouble of the refrigerating cycle, water leak, electric shock or fire is caused.
FILE NO. SVM-18041
- 10 -
Installation
Compulsion
Only a qualified installer (1) o
r qualified service person (1) is allowed to install the air conditioner. If the air conditioner is installed by an unqualified individual, a fire, electric shocks, injury, water leakage, noise and/or vibration may result.
Before starting to install the air conditioner, read carefully through the Installation Manual, and follow its instructions to install the air conditioner.
Do not install the air conditioner in a location that may be subject to a risk of expire to a combustible gas.
If a combustible gas leaks and becomes concentrated around the unit, a fire may occur.
When transporting the air conditioner, use a forklift and when moving the air conditioner by hand, move the unit with 4 people.
Install a circuit break
When carrying out the pump-down work shut down the compressor before disconnecting the refrigerant pipe. Disconnecting the refrigerant pipe with the service valve left open and the compressor still operating will cause air, etc. to be sucked in, raising the pressure inside the refrigeration cycle to an abnormally high level, and possibly resulting in reputing, injury, etc.
When removing the welding parts of suction and discharge pipe for the compressor, remove them at the place ventilated well after recovering the refrigerant. Improper recovering may cause the spurt of the refrigerant and the refrigeration oil, causing an injury.
Do not vent gases to the atmosphere. Venting gases to the atmosphere is prohibited by the law.
er that meets the specifications in the installation manual and the stipulations
in the local regulations and laws.
Install the circuit breaker where it can be easily accessed by the agent.
Do not place any combustion appliance in a place where it is directly exposed to the wind of air conditioner, otherwise it may cause imperfect combustion.
Prohibition
CAUTION
Wearing of
gloves
Ensure wearing of gloves when performing any work in order to avoid injury from parts, etc. Failure to wear the proper protective gloves cause an injury due to the parts, etc.
Confirm
When performing the welding work, check whether refrigerant leaks or remains. If the leakage refrigerant gas touches a fire source, it may generate noxious gases, causing a fire.
FILE NO. SVM-18041
- 11 -
Explanations given to user
s If you have discovered that the fan grille is damaged, do not approach the outdoor unit but set the circuit breaker
to the OFF position, and contact a qualified service person to have the repairs done. Do not set the circuit breaker to the ON position until the repairs are completed.
Relocation
s Only a qualified installer (1) or qualified service person (1) is allowed to relocate the air conditioner.
It is dangerous for the air conditioner to be relocated by an unqualified individual since a fire, electric shocks, injury, water leakage, noise and/or vibration may result.
s When carrying out the pump-down work shut down the compressor before disconnecting the refrigerant pipe.
Disconnecting the refrigerant pipe with the service valve left open and the compressor still operating will cause air, etc. to be sucked in, raising the pressure inside the refrigeration cycle to an abnormally high level, and possibly resulting in reputing, injury, etc.
(
1) Refer to the “Definition of Qualified Installer or Qualified Service Person.”
Declaration of Conformity
TOSHIBA CARRIER (THAILAND) CO., LTD. 144 / 9 Moo 5, Bangkadi Industrial Park, Tivanon Road, Amphur Muang, Pathumthani 12000, Thailand
Manufacturer:
Nick Ball
Representative/TCF holder: Toshiba EMEA Engineering Director
Toshiba Carrier UK Ltd. Porsham Close, Belliver Industrial Estate, PLYMOUTH, Devon, PL6 7DB. United Kingdom
Authorized
Hereby declares that the machinery described below: Generic Denomination: Model/type:
Commercial name:
Air Conditioner
RAV-GP561ATP-E RAV-GP561ATP-TR RAV-GP561ATJP-E
Super Digital Inverter Series Air Conditioner
Complies with the provisions of the “Machinery” Directive (Directive 2006/42/EC) and the regulations transposing into national law.
Complies with the provisions of the following harmonized standard:
EN 378-2: 2008 + A2:2012
Note: This declaration becomes invalid if technical or operational modifications are introduced without the
manufacturer’s consent.
Disposal
How to dispose of air conditioners with a rating of 12 kW and below in accordance with the 2002/96/EC Directive WEEE (Waste Electrical and Electronic Equipment) is provided in the Installation Manual supplied with your product. For disposal of the product above 12 kW in rating you should use a registered company in accordance with any national or EU legislation.
<Model names with a rating of 12 kW and below (outdoor units)>
SDI series
RAV-GP561ATP-E RAV-GP561ATP-TR RAV-GP561ATJP-E
FILE NO. SVM-18041
- 12 -
Specifications
Model
Sound power level (dBA)
Cooling Heating
Weight (kg)
RAV-GP561ATP-E
RAV-GP561ATP-TR
RAV-GP561ATJP-E
  
  
45
45
45
Under 70 dBA
FILE NO. SVM-18041
- 13 -
1. SPECIFICATIONS
1-1. Outdoor Unit
<Super Digital Inverter>
Model name Outdoor unit
RAV-
GP561ATP
*
Power supply
1 phase 220-240V 50Hz
(Power exclusive to outdoor is required.)
Compressor
Type Hermetic compressor
Motor (kW) 1.1
Pole 4
Refrigerant charged (kg)
1.35
Refrigerant control Pulse motor valve
Inter connecting pipe
Standard length (m) 7.5
Min. length (m) 5
Max. total length (m)
50
Additional refrigerant charge under long piping connector
20g/m
(21m to 50m)
Height difference
Outdoor lower (m) 30
Outdoor higher (m) 30
Outer dimension
Height (mm)
630
Width (mm)
799
Depth (mm)
29
9
Appearance Silky shade (Muncel 1Y8.5/0.5)
Total weight (kg)
45
Heat exchanger Finned tube
Fan unit
Fan Propeller fan
Standard air flow high (m
3
/min.) 40
Motor (W) 43
Connecting pipe
Gas side (mm) 12.7
Liquid side (mm) 6.4
Sound pressure level Cooling/Heating (dB
·A)
46/48
Sound power level Cooling/Heating (dB
·A)
63/65
Outside air temperature, Cooling (°C)
52 to -15
Outside air temperature, Heating (°C)
15 to -27
FILE NO. SVM-18041
- 14 -
>gnitaeH<
RAV-GP561ATP
<Cooling>
1-2. Operation Characteristic Curve
<Heating><Cooling>
s Capacity variation ratio according to temperature
RAV-G
P561ATP
0
1
2
3
4
5
6
7
8
9
10
0 01 02 30 04 05 60 07 08 90100
Current(A)
Comoressorspeed(rps)
Conditions Indoor:DB27Ԩ/WB19Ԩ outdoor:DB35Ԩ Indoor airflow:High Pipelength:7.5m
0
2
4
6
8
10
12
14
Current(A)
0 102030405060708090100101
Comoressorspeed(rps)
Conditions Indoor:DB20Ԩ Outdoor:DB7Ԩ/WB6Ԩ Indoor airflow:High Pipelength:7.5m
40%
45%
50%
55%
60%
65%
70%
75%
80%
85%
90%
95%
100%
105%
110%
32 34 36 38 40 42 44 46 48 50 52
Current(A)
outdoortemperatureԨ
Conditions Indoor:DB27Ԩ/WB19Ԩ Indoor airflow:High
20%
30%
40%
50%
60%
70%
80%
90%
100%
110%
120%
Current(A)
27 24 21 18 15 12 9 6 30 3 6 912
outdoortemperatureԨ
Conditions Indoor:DB20Ԩ Indoor airflow:High
FILE NO. SVM-18041
- 15 -
2. CONSTRUCTION VIEWS (EXTERNAL VIEWS)
2-1. RAV-GP561ATP
*
(Discharge guide
(For dia.8-dia.10 anchor bolts)
Details of A legs
250mm or more
200mm or more
100mm or more
50mm
Air inlet
Air inlet port
Air outlet
Space required for service
Minimum
distance up to wall
2-dia.11×14 long hole
(For dia.8-dia.10 anchor bolt)
2-dia.11×14 U-shape hole
(For dia.8-dia.10 anchor bolt)
Earth terminal
Charge port
2-dia.11×14 U-shape hole
2-dia.11×14 long hole
Discharge guard
4-dia.4.5
embossing
Drain hole(dia.25)
Refrigerant pipe
connecting port
(Piping dia.6.35 )
Refrigerant pipe
connecting port
(Piping dia.12.7)
299
630
26
15
600
316
330
244
528
150
178
300
108
178 176
600
330
25
22
5
4
20
78
167
135
13231
351
92
137
88
20
233
274
55
29
20
88
161
29
58130
53
113650
18
26
Details of B legs
6
14
8
15
R
1
5
157
69
528
20
8
300
178 178
176
150
29
799 69
26
17
501136
6
8
16
330
600
R
1
5
dia.6×8
long hole
dia.6 hole
dia.6 hole
dia.6×8
long hole
dia.11×14
long hole
32
600
330
A legs
(For dia.8-dia.10 anchor bolt)
B legs
C
L
or more
mounting hole)
port
6-dia.4.5
embossing
(Protection against snow hood
Drain hole
(2-dia.20×88 long hole)
port
external liexternal linnee
ProducProductt
mounting hole)
Packed valve cover
FILE NO. SVM-18041
- 16 -
RAV-TWP30E2, RAV-TWP50E2 (Simultaneous Twin)
Inner diameter Ø C
Inner
diameter Ø D
Inner
diameter Ø D
A
B
Model (RBC-)
TWP30E2
Liquid side
Gas side
TWP50E2
Liquid side
Gas side
ABCD
36 14 Ø9.5 Ø6.4
43 23 Ø15.9 Ø12.7
34 14 Ø9.5 Ø9.5
44 21 Ø15.9 Ø15.9
FILE NO. SVM-18041
- 17 -
(Indoor unit)
Refrigerant pipe at liquid side (Outer dia : ØB)
Refrigerant pipe at gas side (Outer dia : ØA)
Distributor (Strainer incorporated)
Strainer
Heating Cooling
TCJ sensor
TC sensor
Air heat
exchanger
To outdoor unit
To outdoor unit
s Single type (Combination of 1 indoor unit and 1 outdoor unit)
Dimension table
Indoor unit
GP56 type
Outer diameter of refrigerant pipe
Gas side ØA Liquid side ØB
12.7 6.4
3. SYSTEMATIC REFRIGERATING CYCLE DIAGRAM
3-1. Indoor Unit
FILE NO. SVM-18041
- 18 -
RAV-GP561ATP
R32 1.35 kg
In cooling operation In heating operation
Standard
Cooling Overload
Low load
Standard
Heating Overload
Low load
Pressure
(MPa) (kg/cm²g)
Pd Ps Pd Ps
2.84 1.04 29.0 10.6
3.48 1.50 35.5 15.3
2.41 0.80 24.6
8.2
2.43 0.70 24.8
7.1
3.37 1.15 34.4 11.7
1.63 0.12 16.6 1.2
Pipe surface temperature (°C)
Discharge Suction
Indoor heat Outdoor heat
exchanger exchanger
(TD) (TS) (TC) (TE)
81 14
13
36
75 24 23 55
53
6
7
23
80
2
38
4
85 16 52 17
26 –29 25 –23
Compressor
drive revolution
frequency
(rps)
50
25
34
62
44
106
Indoor
fan
HIGH
HIGH
LOW
HIGH
LOW
HIGH
Indoor/Outdoor
temp. conditions
(DB/WB) (°C)
Indoor Outdoor
27 / 19 35 / –
32 / 24
52 / –
18 / 15.5
15 / –
20 / – 7 / 6
30 / – 24 / 18
15 / –
27 / –
Rotarycompressor
Accumulator
(1L)
2stepMuffler
(φ25×200L)
Muffler
(φ19×160L)
TD
sensor
TS
sensor
TE
sensor
Highpressure switch
OFF:4.15MPa
ON:3.2MPa
4wayvalve
Capillarytube
(φ1.2×80L)
Distributor
Refrigerantpipe atliquidsideΦ6.4 Packedvalve
Refrigerantpipe atliquidsideΦ12.7 Packedvalve
Strainer
Pulsemotor
valve
Heat exchanger
Φ7,2rows, 28stages
Strainer
Fanmotor
M
Fan
TL
sensor
TO
sensor
FILE NO. SVM-18041
- 19 -
4.WIRING DIAGRAM
4-1. RAV-*PATP
*
FM
49C
PMV
TS
TD
TE
TO
TB01
Parts name
Fan Motor
Thermostat for Compressor
Pulse Motor Valve
Pipe temp. sensor (Suction)
Pipe temp. sensor (Discharge)
Heat exchange temp. sensor
Air temp. sensor
Terminal block
Field wiring
Protective
Terminal
Terminal
Connector
P.C.board
Fuse 25A 250V
Compressor
High pressure switch
***
CM
F01
63H
20SF 4-way valve coil
CN Connector
Fuse T6.3A 250V F-IU
TL Liquid temp. sensor
1.For D800 D805 and SW01 SW02,
refer to the installation manual.
SW01 SW02
+
-
-
+
+ +
CM
FM
L-1
20SF
To INDOOR UNIT POWER SUPPLY
TB01
12
3
L
N
OPTION
PMV
65
MCC-1713
Outdoor Control P.C. Board
Symbol
Parts name
TLTSTDTETO
(WHI)
CN604
(WHI)
CN603
(WHI)
CN601
(WHI)
CN600CN602
(YEL)
211221
12
CN500
(BLU)
213
21321
CN704
(WHI)
63H
P>
t >
49C
123456
CN700
(WHI) (GRN)
CN501
(BLU)
CN806
1 2 3 4 5
3
MS
MSMS
3
WHI
RED
BLK
RED
WHI
BLK
WHI
WHI
ORN
WHI
BLK
BLK
-
+
Reactor
Symbol
(WHI)
CN807
1 2 3 4 5 6 78910
D803
(YEL) (YEL)
D804
(YEL)
D802
(YEL)
D801
(YEL)
D800 D805
(GRN)
10
MCC-1646
Display P.C. Board
block
earth
GRY : GRAY
RED : RED
BLU : BLUE
BLK : BLACK
Color Indication
234567 8 9110
CN01(WHI)
P07
P01
P02
P03
CN300
(WHI)
P05
P06
P04
P16
P17
123
L-1
220-240V 50Hz
123
GRN : GREEN
WHI : WHITE
YEL : YELLOW
ORN : ORANGE
BLK
BLK
WHI
F-IU
T6.3A
250V
F01
FILE NO. SVM-18041
- 20 -
5. SPECIFICATIONS OF ELECTRICAL PARTS
RAV-GP561ATP
*
No. Parts name Type Specifications
1 Compressor
DX150A1T-21F
3 phase, 4P, 1100 W
2 Fan motor
ICF-140-A43-1
Output 43 W
3 4-way valve coil
STF-H01AZ1724A1
-
4 PMV coil
PQ-M10012-000313
-
5 P.C. board
MCC-1713
-
6 Reactor
CH-102-Z-T 18mH, 16A 7 Fuse (Switching power (Protect)) - T3.15A, AC 250V 8 Fuse (Inverter, input (Current protect)) - AC240V 9 Outdoor temp. sensor (To sensor) - 10 kΩ at 25°C
10 Heat exchanger sensor (Te sensor) - 10 kΩ at 25°C 11 Suction temp. sensor (Ts sensor) - 10 kΩ at 25°C 12 Discharge temp. sensor (Td sensor) - 50 kΩ at 25°C 13 Compressor thermo. (Protection) CS-12AL OFF: 125 ± 4°C, ON: 90 ± 5°C
FILE NO. SVM-18041
- 21 -
6. REFRIGERANT R32
This air conditioner adopts the new refrigerant HFC (R32) which does not damage the ozone layer.
The next section describes the precautions for air conditioner using the new refrigerant. Conforming to contents of the next section together with the general cautions included in this manual, perform the correct and safe work.
6-1. Safety During Installation/Servicing
The basic installation servicing work procedures are the same as conventional R410A models. As R32’s pressure is about 1.6 times higher than that of R22, improper installation/servicing may cause a serious trouble. By using tools and materi-als exclusive for R32, it is necessary to carry out installation/ servicing safely while taking the following precautions into consideration.
1. Never use refrigerant other than R32 in an air conditioner which is designed to operate with R32. If other refrigerant than R32 is mixed, pressure in the refrigeration cycle becomes abnormally high, and it may cause personal injury, etc. by a rupture.
2. Confirm the used refrigerant name, and use tools and materials exclusive for the refrigerant. The refrigerant name R32 is indicated on the visible place of the outdoor unit of the air conditioner using R32 as refrigerant. To prevent mischarging, the diameter of the service port differs from that of R22. R32 and other HFCs are heavier than air, and therefore they are inclined to settle near the floor surface. If the gas fills up the room or the bottom part of a room, it may also cause oxygen deficiency and may reach its combustion concentration.
In order to prevent oxygen deficiency and R32 combustion, keep the room well-ventilated for a healthy work environment.
In particular, using HFCs in a basement r
oom or confined area creates a higher risk; be sure to furnish the room with local exhaust ventilation. If a refrigerant leak is confirmed in a room an inadequately ventilated location, do not use a flame until the area has been ventilated appropriately and the work environment has been improved. The same applies in case of brazing, ensure appropriate ventilation to prevent oxygen deficiency and R32 combustion. Check that there are no dangerous or combustible items nearby, and ensure a fire extinguisher is close at hand. Keep a sufficient distance away from causes of fire (ignition sources) such as gas-burning equipment and electric heaters in places where installation, repairs, or similar work on air-conditioning equipment is performed.
3. If a refrigeration gas leakage occurs during installation/servicing, be sure to ventilate fully. If the refrigerant gas comes into contact with fire, a poisonous gas may occur.
4. When installing or removing an air conditioner, do not allow air moisture dust or oil to remain in the refrigeration cycle. Otherwise, pressure in the refrigeration cycle may become abnormally high so that a rupture or personal injury may be caused.
5. After completion of installation work, check to make sure that there is no refrigeration gas leakage. If the refrigerant gas leaks into the room, coming into contact with fire in the fan-driven heater, space heater, etc., a poisonous gas may occur
6. When an air conditioning system charged with a large volume of refrigerant is installed in a small room, it is necessary to exercise care so that, even when refrigerant leaks, its concentration does not exceed the marginal level. If the refrigerant gas leakage occurs and its concentration exceeds the marginal level, an oxygen starvation accident may result.
7. Be sure to carry out installation or removal according to the installation manual. Improper installation may cause refrigeration trouble, water leakage, electric shock, fire, etc.
8. Unauthorized modifications to the air conditioner may be dangerous. If a breakdown occurs please call a qualified air conditioner technician or electrician. Improper repair's may result in water leakage, electric shock and fire, etc.
6-2. Refrigerant Piping Installation
6-2-1. Piping Materials and Joints Used
For the refrigerant piping installation, copper pipes and joints are mainly used. Copper pipes and joints suitable for the refrigerant must be chosen and installed. Furthermore, it is necessary to use clean copper pipes and joints whose interior surfaces are less affected by contaminants.
1. Copper Pipes
It is necessary to use seamless copper pipes which are made of either copper or copper alloy and it is desirable that the amount of residual oil is less than 40 mg/10 m. Do not use copper pipes having a collapsed, deformed or discolored portion (especially on the interior surface).
Otherwise, the expansion valve or capillary tube may become blocked with contaminants.
As an air conditioner using R32 incurs pres-sure higher than when using R22, it is necessary to choose adequate materials.
Thicknesses of copper pipes used with R32 are as shown in Table 3-2-1. Never use copper pipes thinner than 0.8 mm even when it is available on the market.
FILE NO. SVM-18041
- 22 -
Table 6-2-1 Thicknesses of annealed copper pipes
Nominal diameter
1/4
3/8
1/2
5/8
Outer diameter (mm)
6.35
9.52
12.70
15.88
Thickness (mm)
R32(R410A) R22
0.80 0.80
0.80 0.80
0.80 0.80
1.00 1.00
2. Joints
For copper pipes, flare joints or socket joints are used. Prior to use, be sure to remove all contaminants.
a) Flare Joints
Flare joints used to connect the copper pipes cannot be used for pipings whose outer diameter exceeds 20 mm. In such a case, socket joints can be used. Sizes of flare pipe ends, flare joint ends and flare nuts are as shown in Tables 3-2-3 to 3-2-6 below.
b) Socket Joints
Socket joints are such that they are brazed for connections, and used mainly for thick pipings whose diameter is larger than 20 mm. Thicknesses of socket joints are as shown in Table 6-2-2.
Table 6-2-2 Minimum thicknesses of socket joints
Nominal diameter
1/4
3/8
1/2
5/8
Reference outer diameter of
copper pipe jointed (mm)
6.35
9.52
12.70
15.88
Minimum joint thickness
(mm)
0.50
0.60
0.70
0.80
6-2-2. Processing of Piping Materials
When performing the refrigerant piping installation, care should be taken to ensure that water or dust does not enter the pipe interior, that no other oil than lubricating oils used in the installed air-water heat pump is used, and that refrigerant does not leak. When using lubricating oils in the piping processing, use such lubricating oils whose water content has been removed. When stored, be sure to seal the container with an airtight cap or any other cover.
1. Flare processing procedures and precautions
a) Cutting the Pipe
By means of a pipe cutter, slowly cut the pipe so that it is not deformed.
b) Removing Burrs and Chips
If the flared section has chips or burrs, refrigerant leakage may occur. Carefully remove all burrs and clean the cut surface before installation.
c) Insertion of Flare Nut
FILE NO. SVM-18041
- 23 -
A
ØD
d) Flare Processing
Make certain that a clamp bar and copper pipe have been cleaned.
By means of the clamp bar, perform the flare processing correctly.
Use either a flare tool for R32 or conven­tional flare tool.
Flare processing dimensions differ according to the type of flare tool. When using a con­ventional flare tool, be sure to secure “dimen­sion A” by using a gauge for size adjustment.
Fig. 6-2-1 Flare processing dimensions
Table 6-2-3 Dimensions related to flare processing for R32(R410A)
Nominal
diameter
1/4
3/8
1/2
5/8
Outer
diameter
(mm)
6.35
9.52
12.70
15.88
Thickness
(mm)
0.8
0.8
0.8
1.0
A (mm)
Flare tool for R32
clutch type
0 to 0.5
0 to 0.5
0 to 0.5
0 to 0.5
Conventional flare tool
Clutch type Wing nut type
1.0 to 1.5 1.5 to 2.0
1.0 to 1.5 1.5 to 2.0
1.0 to 1.5 2.0 to 2.5
1.0 to 1.5 2.0 to 2.5
Table 6-2-4 Dimensions related to flare processing for R22
Nominal
diameter
1/4
3/8
1/2
5/8
Outer
diameter
(mm)
6.35
9.52
12.70
15.88
Thickness
(mm)
0.8
0.8
0.8
1.0
A (mm)
Flare tool for R22
clutch type
0 to 0.5
0 to 0.5
0 to 0.5
0 to 0.5
Conventional flare tool
Clutch type Wing nut type
0.5 to 1.0 1.0 to 1.5
0.5 to 1.0 1.0 to 1.5
0.5 to 1.0 1.5 to 2.0
0.5 to 1.0 1.5 to 2.0
Table 6-2-5 Flare and flare nut dimensions for R32(R410A)
Nominal
diameter
1/4
3/8
1/2
5/8
Outer diameter
(mm)
6.35
9.52
12.70
15.88
Thickness
(mm)
0.8
0.8
0.8
1.0
Dimension (mm)
ABCD
9.1 9.2 6.5 13
13.2 13.5 9.7 20
16.6 16.0 12.9 23
19.7 19.0 16.0 25
Flare nut width
(mm)
17
22
26
29
FILE NO. SVM-18041
- 24 -
43° to 45°
45° to 46°
B A
C
D
Table 6-2-6 Flare and flare nut dimensions for R22
Nominal
diameter
1/4
3/8
1/2
5/8
3/4
Outer diameter
(mm)
6.35
9.52
12.70
15.88
19.05
Thickness
(mm)
0.8
0.8
0.8
1.0
1.0
Dimension (mm)
ABCD
9.0 9.2 6.5 13
13.0 13.5 9.7 20
16.2 16.0 12.9 20
19.7 19.0 16.0 23
23.3 24.0 19.2 34
Flare nut width
(mm)
17
22
24
27
36
Fig. 6-2-2 Relations between flare nut and flare seal surface
2. Flare Connecting Procedures and Precautions
a) Make sure that the flare and union portions do not have any scar or dust, etc.
b) Correctly align the processed flare surface with the union axis. c) Tighten the flare with designated torque by means of a torque wrench. The tightening torque for R32 is
the same as that for conventional R22. Incidentally, when the torque is weak, the gas leakage may occur. When it is strong, the flare nut may crack and may be made non-removable. When choosing the tighten­ing torque, comply with values designated by manufacturers. Table 3-2-7 shows reference values.
NOTE :
When applying oil to the flare surface, be sure to use oil designated by the manufacturer. If any other oil is used, the lubricating oils may deteriorate and cause the compressor to burn out.
Table 6-2-7 Tightening torque of flare for R32(R410A) [Reference values]
Nominal
diameter
1/4
3/8
1/2
5/8
Outer diameter
(mm)
6.35
9.52
12.70
15.88
Tightening torque
N•m (kgf•cm)
14 to 18 (140 to 180)
33 to 42 (330 to 420)
50 to 62 (500 to 620)
63 to 77 (630 to 770)
Tightening torque of torque
wrenches available on the market
N•m (kgf•cm)
16 (160), 18 (180)
42 (420)
55 (550)
65 (650)
FILE NO. SVM-18041
- 25 -
6-3. Tools
6-3-1. Required Tools
The service port diameter of packed valve of the outdoor unit in the air-water heat pump using R32 is changed to prevent mixing of other refrigerant. To reinforce the pressure-resisting strength, flare processing dimensions and opposite side dimension of flare nut (For Ø12.7 copper pipe) of the refrigerant piping are lengthened.
The used refrigerating oil is changed, and mixing of oil may cause a trouble such as generation of sludge, clogging of capillary, etc. Accordingly, the tools to be used are classified into the following three types.
1. Tools exclusive for R32 (Those which cannot be used for conventional refrigerant (R22))
2. Tools exclusive for R32, but can be also used for conventional refrigerant (R22)
3. Tools commonly used for R32 and for conventional refrigerant (R22) The table below shows the tools exclusive for R32 and their interchangeability.
Tools exclusive for R32 (The following tools for R410A are required.)
Tools whose specifications are changed for R32 and their interchangeability
No.
1
2
3
4
5
6
7
8
Used tool
Flare tool
Copper pipe gauge for adjusting projection margin
Torque wrench (For Ø12.7)
Gauge manifold
Charge hose
Vacuum pump adapter
Electronic balance for refrigerant charging
Leakage detector
Usage
Pipe flaring
Flaring by conventional flare tool
Connection of flare nut
Evacuating, refrigerant charge, run check, etc.
Vacuum evacuating
Refrigerant charge
Gas leakage check
R32(R410A)
air-water heat pump installation
Existence of new equipment for R32
Ye s
Ye s
Ye s
Ye s
Ye s
Ye s
Ye s
Whether conven­tional equipment can be used
*(Note 1)
*(Note 1)
×
×
× ×
×
Conventional air-water heat pump installation
Whether new equipment can be used with conventional refrigerant
¡
*(Note 1)
×
×
¡
¡
¡
(Note 1) When flaring is carried out for R32(R410A) using the conventional flare tools, adjustment of projection
margin is necessary. For this adjustment, a copper pipe gauge, etc. are necessary.
In addition to the above exclusive tools, the following equipments which serve also for R22 are necessary as the general tools.
1. Vacuum pump Use vacuum pump by attaching vacuum pump adapter.
2. Torque wrench (For Ø6.35, Ø9.52)
3. Pipe cutter
4. Reamer
5. Pipe bender
6. Level vial
7. Screwdriver (+, –)
8. Spanner or Monkey wrench
9. Hole core drill (Ø65)
10. Hexagon wrench (Opposite side 4mm)
11. Tape measure
12. Metal saw
Also prepare the following equipments for other installation method and run check.
1. Clamp meter
2. Thermometer
3. Insulation resistance tester
4. Electroscope
General tools (Conventional tools can be used.)
FILE NO. SVM-18041
- 26 -
Connect the charge hose to packed valve service port at the outdoor unit’s gas side.
Recover the refrigerant, and check no refrigerant remains in the equipment.
(For refrigerant charging, see the figure below.)
Connect the charge hose to the vacuum pump adapter.
Open fully both packed valves at liquid and gas sides.
Place the handle of the gauge manifold Low in the fully opened position, and turn on the vacuum pump’s power switch. Then, evacuating the refrigerant in the cycle.
When the compound gauge’s pointer has indicated –0.1 Mpa (–76 cmHg), place the handle Low in the fully closed position, and turn off the vacuum pump’s power switch.
Keep the status as it is for 1 to 2 minutes, and ensure that the compound gauge’s pointer does not return.
Set the refrigerant cylinder to the electronic balance, connect the connecting hose to the cylinder and the connecting port of the electronic balance, and charge liquid refrigerant.
(Indoor unit)
(Outdoor unit)
Opened
Opened
Refrigerant cylinder
(with siphon)
Check valve
Open/close valve for charging
Electronic balance for refrigerant charging
Opened
Closed
Service port
6-4. Recharging of Refrigerant
When it is necessary to recharge refrigerant, charge the specified amount of new refrigerant according to the following steps.
1. Never charge refrigerant exceeding the specified amount.
2. If the specified amount of refrigerant cannot be charged, charge refrigerant bit by bit in COOL mode.
3. Do not carry out additional charging.
When additional charging is carried out if refrigerant leaks, the refrigerant composition changes in the refrigeration cycle, that is characteristics of the air conditioner changes, refrigerant exceeding the specified amount is charged, and working pressure in the refrigeration cycle becomes abnormally high pressure, and may cause a rupture or personal injury.
Fig. 6-4-1 Configuration of refrigerant charging
FILE NO. SVM-18041
- 27 -
Loading...
+ 60 hidden pages