Toshiba RAV-362B-PE, RAV-462B-PE, RAV-363A8-PE, RAV-463A8-PE, RAV-362C-PE Service Manual

...
SERVICE MANUAL
FILE NO. A90-9608
AIR-CONDITIONER
RAV-362B-PE/RAV-363A8-PE RAV-462B-PE/RAV-463A8-PE
SPLIT BUILT-IN DUCT TYPE
SPLIT CEILING TYPE
RAV-362C-PE/RAV-363A8-PE RAV-462C-PE/RAV-463A8-PE
SPLIT CASSETTE TYPE
PRINTED IN U.K. Apr. 1996
Heronhill - for all your Toshiba requirements
Tel: 01823 665660
www.heronhill.co.uk
Fax: 01823 665807
• The units referred to within this manual conform with the protection requirements of Directives 89/336/EEC Electromagnetic Compatibility and 73/23/EEC Low Voltage.
• Operating conditions of units are as follows:
OUTDOOR TEMPERATURE -2 TO 43°C ROOM TEMPERATURE 18 TO 32°C ROOM HUMIDITY LESS THAN 80%
NOTE 1: Cooling Capacity is based on the following temperature conditions
Indoor air inlet temperature 27°C DB, 19°C WB Outdoor air inlet temperature 35°C DB
NOTE 2: Specifications are subject to change without notice.
SUMMARY
CONTENTS
1. IMPORTANT NOTES ........................................................................................................................ 3
2. SPECIFICATIONS ............................................................................................................................ 4
3. CONSTRUCTION VIEWS ................................................................................................................. 7
4. WIRING DIAGRAM .......................................................................................................................... 8
5. SPECIFICATIONS OF ELECTRICAL PARTS .................................................................................... 9
6. REFRIGERANT PIPING DIAGRAM ................................................................................................ 10
7. PERFORMANCE CHARACTERISTICS ...........................................................................................11
8. EXPLODED VIEWS AND PARTS LISTS ......................................................................................... 13
Heronhill - for all your Toshiba requirements
Tel: 01823 665660
www.heronhill.co.uk
Fax: 01823 665807
1. IMPORTANT NOTES
a. Refer to Service Manual, File No. A90-9504 for details of indoor units and control circuits.
b. Reverse Phase Protector
The Scroll Compressor used in this unit can only rotate in one direction. For this reason a protective
device ( Reverse Phase Protector ) is fitted to prevent incorrect wiring of electrical phases. If the red LED on the remote controller does not flash when the system is switch on, then the wiring to the outdoor unit should be checked to ensure that the three phases are wired in the correct sequence.
c. Inner Overload Relay
If the Inner Overload Relay operates, the Magnetic contactor will remain energised, but the compressor
will stop. In this event fault Code '09' will appear on the Remote Controller.
d. Delivery Temperature Thermostat.
In the unlikely event of a gas leak a bi-metal thermostat is fitted to this unit to prevent the compressor from
overheating. During such abnormal conditions, the thermostat operates and power to the indoor unit and remote controller is disconnected.
e. Special Refrigerant Reclaim Procedure for Scroll Compressors
When the refrigerant charge is reclaimed only from the discharge side of the Scroll Compressor, it is
possible that the suction side of the compressor remains pressurised. If a brazing torch is applied to the suction side the pressurised refrigerant and oil mixture could ignite.
THIS COULD RESULT IN A FIRE AND / OR SEVERE PERSONAL INJURY.
The refrigerant gas MUST
be reclaimed simultaneously from the discharge and the suction sides of the
outdoor unit to avoid this potential problem.
Heronhill - for all your Toshiba requirements
Tel: 01823 665660
www.heronhill.co.uk
Fax: 01823 665807
- 4 -
Cooling capacity kW 10.0 12.5
Phase 3 3
Power source V 380 – 415 380 – 415
Hz 50 50
COOLING COOLING Power consumption kW 3.9 5.0 Power Factor % 87 86 Running current A 6.5 8.4 Starting current A 42 50
Operating
Indoor unit
(High/Med./Low) dB(A) 45/42/39 46/43/40
noise (SPL)
Outdoor unit dB(A) 55 59 Name of refrigerant R-22 R-22
Refrigerant Charge volume kg 2.7 3.7
Add. volume (20-50m) g/m 50 50
Refrigerant control Capillary tube Capillary tube
Large side size *1 mm ø 19 (ø 22) ø 19 (ø 22) Coupler style Flare Flare Smaller side size mm ø 9.5 ø 9.5
I
nter- Coupler style Flare Flare connection Standard length m 7.5 7.5 pipe Maximum pipe lengths m 50 50
Max. height difference
m 20 20
if indoor unit higher Outdoor unit higher m 50 50
Condensate drain pipe diameter mm ø 32 (OD) ø 32 (OD) INDOOR UNIT RAV-362B-PE RAV-462B-PE
Model Appearance colour Black (Zinc galvanized steel + Thermal insulation)
Height mm 345 345
Dimensions Width mm 1350 1350
Depth mm 800 800 Net weight kg 53 62 Heat exchanger type Finned tube Finned tube Indoor fan type Multi-blade fan Multi-blade fan Air flow volume m3/h 1820 2100 Fan motor output W 120 140 External Static STANDARD mmAq 4 4 Pressure MAX. MOTOR mmAq 10 10 OUTDOOR UNIT RAV-363A8-PE RAV-463A8-PE
Model Appearance colour Bronze white (Munsell 6Y7.5/1) Bronze white (Munsell 6Y7.5/1)
Height mm 1240 1240 Dimensions Width mm 930 930
Depth mm 385 385 Net Weight kg 103 111 Heat exchange type Finned tube Finned tube Outdoor fan type Propeller fan Propeller fan Air flow volume m3/h 6000 6000 Fan motor output 39 + 63 39 + 63 Compressor Model ZR49K3-TFD ZR61K3-TFD
Output kW 3.0 3.75
Fuse, Crankcase heater, Reverse Fuse, Crankcase heater, Reverse
Protective device Phase Protector, Inner overload relay Phase Protector, Inner overload relay
Bi-metal thermostat Bi-metal thermostat Built-in duct filter kit RBC-RK462BE-PE Air filter Washable
RAV-462B-PERAV-362B-PE
ITEM
MODEL
2. SPECIFICATIONS
Note 1: (ø22) should be used when the length of pipe exceeds 30m.
Diameter (mm) 6.4 9.5 12.7 15.9 19 22 Nominal Diameter (inch) 1/4 3/8 1/2 5/8 3/4 7/8
Metric/Imperial Pipe Comparisons
Heronhill - for all your Toshiba requirements
Tel: 01823 665660
www.heronhill.co.uk
Fax: 01823 665807
- 5 -
Cooling capacity kW 10.0 12.5
Phase 3 3
Power source V 380 – 415 380 – 415
Hz 50 50
COOLING COOLING Power consumption kW 3.9 5.0 Power Factor % 87 86 Running current A 6.5 8.4 Starting current A 42 50
Operating
Indoor unit
(High/Med./Low) dB(A) 47/43/40 49/45/41
noise (SPL)
Outdoor unit dB(A) 55 59 Name of refrigerant R-22 R-22
Refrigerant Charge volume kg 2.7 3.7
Add. volume (20-50m) g/m 50 50
Refrigerant control Capillary tube Capillary tube
Large side size *1 mm ø 19 (ø 22) ø 19 (ø 22) Coupler style Flare Flare Smaller side size mm ø 9.5 ø 9.5
Inter- Coupler style Flare Flare connection
Standard length m 7.5 7.5
pipe
Maximum pipe lengths m 50 50 Max. height difference
m 20 20
if indoor unit higher
Outdoor unit higher m 50 50 Condensate drain pipe diameter mm ø 20 (ID) ø 20 (ID) INDOOR UNIT
RAV-362C-PE RAV-462C-PE
Model Appearance colour Silky mist Silky mist
Height mm 240 240 Dimensions Width mm 1430 1630
Depth mm 640 640 Net weight kg 39 44 Heat exchanger type Finned tube Finned tube Indoor fan type Multi-blade fan Multi-blade fan Air flow volume m3/h 1680 2100 Fan motor output W 75 75 Air filter Washable Washable OUTDOOR UNIT
RAV-363A8-PE RAV-463A8-PE
Model Appearance colour Bronze white (Munsell 6Y7.5/1) Bronze white (Munsell 6Y7.5/1)
Height mm 1240 1240 Dimensions Width mm 930 930
Depth mm 385 385 Net Weight kg 103 111 Heat exchange type Finned tube Finned tube Outdoor fan type Propeller fan Propeller fan Air flow volume m3/h 6000 6000 Fan motor output 39 + 63 39 + 63
Compressor
Model ZR49K3-TFD ZR61K3-TFD
Output kW 3.0 3.75
Fuse, Crankcase heater, Reverse Fuse, Crankcase heater, Reverse
Protective device Phase Protector, Inner overload relay Phase Protector, Inner overload relay
Bi-metal thermostat Bimetal thermostat
RAV-462C-PERAV-362C-PE
ITEM
MODEL
Note 1: (ø22) should be used when the length of pipe exceeds 30m.