1 Fan motor (for indoor) ICF-340-30-2 DC 310-340V, 30W
2Thermo sensor (TA-sensor)———10 kΩ at 25°C
3 Switchins transformer (T01) SWT-77 Output DC 7V, 12Va and 12Vb
4 Microcontroller TMP87CM40ANG 6G60
5Heat exchanger sensor
(TC-sensor)
6Line filter (L01)SS11V-R0719019 mH, AC 0.7 A
7 Diode (DB01) D3SBA60 4 A, 600 V
8 Capacitor (C03) EKMH451VSN121MQ35S 120µF, 450 V
9Fuse (F01)TSCRT6.3 A, 250 V
10 Switching IC (IC01) MA8920 5 A, 900 V
11 Varistor (R09, R10) 15G561K 560 V
12 Resistor (R01) RF-5TK4R81.8 Ω, 5 W
13 Louver motor MP35EA12 Output (Rated) 2 W, 10 poles, 1 phase,
Cooling *High temperature 0.50 13.0 High 32/23 52/31*
Low temperature 0.25 1.0 Low 21/15 21/15
*SASO Standard’s condition
Note : Measure the heat exchanger temperature at the center of U-bend. (By means of TC sensor.)
– 11 –
5-2. RAS-30NKP-AR-1 / RAS-30N2A-AR
FILE NO. SVM-06017
(Connecting pipe)
0.39 m
∅15.88
15.88 mm O.D.:6.35 mm
O.D.:
Accumulator
Compressor
P
Packed valve
15.88)
(∅
NH56VNHT
Indoor unit
Evaporator
Cross flow fan
Condenser
Propeller fan
Outdoor unit
T
Bypass Capillary
∅1.0x1000 l
0.49 m
(Connecting pipe)
∅6.35
Packed valve
(∅6.35)
Capillary tube
∅2.4x800 s
Dryer
Refrigerant
2.00
R22
Mark ( ) means check points of Gas Leak
kg
Ambient temp.
50 Hz
Standard
pressure
(MPaG)
P
Surface temp. of heat
exchanger interchanging
pipe
T
(°C)
Fan speed
(indoor)
conditions DB/WB
(°C)
IndoorOutdoor
Standard 0.38 8.0 High 27/19 35/24
Cooling High temperature 0.52 13.0 High 32/23 52/31
Low temperature 0.30 2.0 Low 21/15 21/15
Note : Measure the heat exchanger temperature at the center of U-bend. (By means of TC sensor.)
– 12 –
Heat Exchanger Sensor
6. CONTROL BLOCK DIAGRAM
Indoor Unit Control Panel
M.C.U.
Functions
• Louver Control
FILE NO. SVM-06017
Operation
Display
Temperature Sensor
Infrared Rays Signal Receiver
Initiallizing Circuit
Infrared
Rays
Remote
Control
From Outdoor Unit
220 ~ 240 V AC 50 Hz
Clock Frequency
Oscillator Circuit
Power Supply
Circuit
Noise Filter
• 3-minute Delay at Restart for Compressor
• Motor Revolution Control
• Processing
(Temperature Processing)
• Timer
Outdoor unit
ON/OFF Signal
Relay Driver
Relay RY03
Outdoor Unit
Louver ON/OFF Signal
Louver Driver
Timer
Display
Filter Sign
Display
Fan Only
Sign Display
Hi Power
Sign Display
Indoor
Fan Motor
Louver Motor
REMOTE CONTROL
Remote Control
Operation ( )
Operation ()
Operation Mode Selection
AUTO, COOL, DRY, FAN ONLY
Temperature Setting
Fan Speed Selection
ON TIMER Setting
OFF TIMER Setting
Louver Auto Swing
Louver Direction Setting
ECO
Hi power
TIMER 1.3.5.9H
COMFORT SLEEP
QUIET
− 13 −
Infrared Rays
7. OPERATION DESCRIPTION
FILE NO. SVM-06017
7-1. Outline of Air Conditioner Control
This is a fixed capacity type air conditioner, which uses
a DC motor for an indoor fan. The DC motor drive
circuit is mounted in the indoor unit. And electrical
parts which operate the compressor and the outdoor
fan motor, are mounted in the outdoor unit.
The air conditioner is mainly controlled by the indoor
unit controller. The controller operates the indoor fan
motor based upon commands transmitted by the
remote control and transfers the operation commands
to the outdoor unit controller.
The outdoor unit controller receives operation
commands from the indoor unit, and operates the
outdoor fan motor and the compressor.
(1) Role of indoor unit controller
The indoor unit controller receives the operation
commands from the remote control and executes
them.
• Temperature measurement at the air inlet of the
indoor heat exchanger by the indoor
temperature sensor
• Temperature setting of the indoor heat
exchanger by the heat exchanger sensor
• Louver motor control
• Indoor fan motor operation control
• LED display control
• Transferring of operation commands to the
outdoor unit
• Receiving of information of the operation status
and judging of the information or indication of
error
(2) Role of indoor unit controller
The outdoor unit controller receives the operation
commands from the indoor controller and
executes them.
• Compressor operation
control
• Operation control of
outdoor fan motor
• Turning off the compressor and outdoor fan
when the outdoor unit receives the shutdown
command
Operations according
to the commands from
the indoor unit
Table 7-1-1
7-1-1. Louver control
(1)Vertical air flow louver
Position of veritcal air flow louver is automatically
controlled according to the operation mode.
Besides, position of vertical air flow louver can be
arbitrarily set by pressing [SET] button.
The louver position which is set by [SET] button
is stored in the microcomputer, and the louver is
automatically set at the stored position for the next
operation.
(2)Swing
If [SWING] button is pressed when the indoor unit is
in operation, the vertical air flow louver starts
swinging. When [SWING] button is pressed again, it
stops swinging.
7-1-2. Indoor fan control (DC Fan motor)
(1)The indoor fan is operated by the stepless speed
change DC motor.
(2)For air flow level, speed of the indoor fan motor is
controlled in five steps (LOW, LOW+, MED, MED
and HIGH). If AUTO mode is selected, the f an
motor speed is automatically controlled by the
difference between the preset temperature and the
room temperature.
LOW+ =
MED+=
LOW+MED
2
MED+HIGH
2
+
OPERATION
MODE
RAS-30NKP2B-1
Model
RAS-30NKP-AR-1
Cooling
Fan only
Dry
rpm
Air flow volume (m /h)
rpm
Air flow volume (m /h)
3
3
– 14 –
UH
UH
UH
1700
1200
1700
1200
H
H
H
1700
1200
1700
1200
M
M
M
1500
10501400
975
FAN TAP
L
L
L
1300
900
1050
650
LL-
L-
1200
800
900
500
UL
UL
UL
1100
700
800
400
SL
SL
1000
600
700
300
SL
900
500
700
300
FILE NO. SVM-06017
7-2. Description of Operation Circuit
(1) When turning on the breaker, the operation lamp
blinks. This means that the power is on (or the
power supply is cut off.)
(2) When pressing [ ] button on the
remote control, receiving beep sounds from the
indoor unit, and the next operation is performed
together with opening the vertical air flow louver.
(3) Once the operation mode is set, it is memorized in
the microcomputer so that the previous operation
can be effected thereafter simply by pressing
[ ] button.
7-2-1. Fan only operation
([MODE] button on the remote control is set
to the fan only operation.)
(1) When [FAN] b utton is set to AUTO, the indoor fan
motor operates as shown in Fig. 7-2-1. When
[FAN] button is set to LOW, LOW+, MED, MED+ or
HIGH, the motor operates with a constant air flow.
+3
+2.5
+2
+1.5
+1
+0.5
(Room temp.) – (Preset temp.)
Preset
temp.
0
(Preset temp.: 24°C
NOTE:
*1: The values marked with *1 are calculated and
controlled by the difference in motor speed
between M+ and L–.
M+
*1
*1
*1
L–
7-2-2. Cooling operation
([MODE] button on the remote control is set
to the cooling operation.)
(1) The compressor, outdoor fan and operation
display on the remote control are controlled as
shown in Fig. 7-2-2.
(Preset temp.)
−
(Room temp.)
Preset
temp.
0.5
ON
OFF OFF OFF ON
0
Compressor
ON
4-way valve
Outdoor fan
Fig. 7-2-2
(2) When [FAN] button is set to AUTO, the indoor fan
motor operates as shown in Fig. 7-2-3. When
[FAN] button is set to LOW, LOW+, MED, MED+ or
HIGH, the motor operates with a constant air flow.
(Room temp.) – (Preset temp.)
Preset
temp.
+3
+2.5
+2
+1.5
+1
+0.5
0
-0.5
M+
*1
*1
*1
L–
NOTE:
display
OPERATION
(2) The Hi POWER, ECO and COMFORT SLEEP
operation cannot be set.
Fig. 7-2-1 Setting of air flow [FAN:AUTO]
*1: The values marked with *1 are calculated and
controlled by the difference in motor speed
between M+ and L–.
Fig. 7-2-3 Setting of air flow [FAN:AUTO]
– 15 –
FILE NO. SVM-06017
7-2-3. Dry operation
([MODE] button on the remote control is set
to the dry operation.)
(1) The compressor, 4-way valve, outdoor fan and
operation display on the remote control are
controlled as shown in Fig. 7-2-4.
ON:6min.
ON:6min.
OFF:4min.
OFF:4min.
ON:5min.
OFF:5min.
ON:5min.
OFF:5min.
OFF
Outdoor fan
Compressor
ON
OPERATION
(Room temp.) – (Preset temp.)
Preset
temp.
+3
+2
+1
OFF
0
Fig. 7-2-4
(2) The microprocessor turns the compressor on and
off at the regular intervals (4 to 6 minutes). While
the compressor is turning off, the indoor fan motor
operates in the SUPER LOW position.
The pattern of operation depending on the relation
between room temperature and preset
temperatures is shown in Fig. 7-2-5.
7-2-4. Automatic operation
([MODE] button on the remote control is set
to the automatic operation.)
(1) One of 2 operations (Cooling, Fan only) is
selected according to difference between the
preset temperature and the room temperature at
which the automatic operation has started, as
shown in Fig. 7-2-6. The Fan only operation
continues until the room temperature reaches a
level at which another mode is selected.
(2) Temporary Auto
When the TEMPORARY button on the indoor unit is
pushed, the preset temperature is fixed at 24°C and
the indoor unit is controlled as shown in Fig. 7-2-6.
°C
Cooling operation
The louver moves to the position
same as Hi Power operation.
display
+4
Cooling operation
0
Fan only operation
(Room temp.) – (Preset temp.)
RAS-30NKP2B-1
RAS-30NKP-AR-1
Room temp.
Preset temp.+1
Preset temp.
Compressor
Outdoor fan
Indoor fan
ONONONON
OFFOFFOFF
L.*S.L.S.L.L.L.S.L.L.
*
Super Low
Fig. 7-2-5
(3) [FAN] button on the remote control is set to AUTO
only.
(4) The ECO and Hi Power operations can not be set.
Fig. 7-2-6
– 16 –
FILE NO. SVM-06017
7-3. ECO Mode
([ECO] button on the remote control is
pressed.)
When [ECO] button is pressed while the indoor unit is
in Cooling, Heating or Auto operation, ECO mark is
indicated on the display of the remote control and the
unit operates quietly and mildly controlling air flow.
(1) Cooling operation
• The preset temperature is changed
automatically as shown in Fig. 7-3-1.
(The value of the preset temperature on the
remote control does not change.)
• Fan speed → LOW
(˚C)
Preset temp.
is changed
+2
+1
Preset temp.
ECO button
is pressed
Preset temp.
is changed
1H2HTIME0H
Fig. 7-3-1
7-4. Hi POWER Mode
([Hi POWER] button on the remote
control is pressed.)
When [Hi POWER] button is pressed while the indoor
unit is in Auto, Cooling or Heating operation, Hi
POWER mark is indicated on the display of the remote
control and the unit operates as follows.
(1) Automatic operation
• The indoor unit operates in according to the
current operation.
(2) Cooling operation
• The preset temperature drops 3°C.
(The value of the preset temperature on the
remote control does not change.)
• If the room temperature is higher than the
setting temperature by 3.5°C or more, the
horizontal louver moves to the Hi POWER
position automatically. Then when the room
temperature is °C less than the setting temperature
the horizontal louver returns automatically.
• FAN speed : [AUTO]
If the temperature is higher than the setting
temperature by 3.5°C or more, the air
conditioner operates at maximum airflow
level. If the temperature is higher than the setting
temperature by less than 3.5°C, the air
air conditioner operates at normal airflow level
FAN speed : One of 5 levels
•
If the temperature is higher than the setting
temperature by 3.5 °C or more, the air
conditioner operates at higher consecutive
airflow level. If the room temperature is higher
than the setting temperature by less than 3.5°C,
the air conditioner operates at normal airflow
level.
(3) The Hi POWER mode can not be set in Dry or
Fan only operation.
7-5. Low-Temperature Limit Control
The microprocessor detects the indoor heat exchanger
temperature to prevent the indoor heat exchanger from
freezing.
The compressor and outdoor fan motor are controlled
as shown in Fig. 7-6-1.
Heat exchanger
temperature
(˚C)
6
2
– 17 –
Compressor
ON
Less than 2°C continues for
5 minutes
OFF
Fig. 7-5-1
Outdoor fan
FILE NO. SVM-06017
7-6. Auto Restart Function
The indoor unit is equipped with an automatic
restarting function which allows the unit to restart
operating with the set operating conditions in the event
of power supply being accidentally shut down. The
operation will resume without warning three minutes
after power is restored.
This function is not set to work when shipped from the
factory. Therefore it is necessary to set it to work.
7-6-1. How to set auto restart function
To set the auto restart function, proceed as follows:
The power supply to the unit must be on; the function
will not set if the power is off.
Push the [TEMPORARY] button located in the center
of the front panel continuously for three seconds.
The unit receives the signal and beeps three times.
The unit then restarts operating automatically in the
event of power supply being accidentally shut down.
When the unit is on standby (Not operating)
OperationMotions
Push [TEMPORARY] button for moreThe unit is on standby.
than three seconds.
The unit starts to operate.The green lamp is on.
→
→
The unit beeps three timesThe lamp changes from
0
TEMPORARY button
and continues to operate.green to orange.
3S
If the unit is not required to operate at this time, push [TEMPORARY]
button once more or use the remote control to turn it off.
After approx. three seconds,
When the unit is in operation
OperationMotions
Push [TEMPORARY] button for moreThe unit is in operation.The green lamp is on.
than three seconds.
The unit stops operating.The green lamp is turned off.
→
→
After approx. three seconds,
0
TEMPORARY button
• While this function is being set, if the unit is in
operation, the orange lamp is on.
The unit beeps three times.
3S
If the unit is required to operate at this time, push [TEMPORARY]
button once more or use the remote control to turn it on.
• While the filter check lamp is on, the [TEMPORARY]
button has the function of filter reset button.
• This function can not be set if the timer operation
has been selected.
• When the unit is turned on by this function, the
louver will not swing even though it was swinging
automatically before shutting down.
– 18 –
7-6-2. How to cancel auto restart function
To cancel auto restart function, proceed as follows:
Repeat the setting prodedure: the unit receives the
signal and beeps three times.
The unit will be required to be turned on with the
remote control after the main power supply is turned
off.
When the unit is on standby (Not operating)
OperationMotions
Push [TEMPORARY] button for moreThe unit is on standby.
→
than three seconds.
The unit starts to operate.The orange lamp is on.
→
The unit beeps three timesThe lamp changes from
0
TEMPORARY button
and continues to operate.orange to g reen.
3S
If the unit is not required to operate at this time, push [TEMPORARY]
button once more or use the remote control to turn it off.
FILE NO. SVM-06017
After approx. three seconds,
When the unit is in operation
OperationMotions
Push [TEMPORARY] button for moreThe unit is in operation.The orange lamp is on.
→
than three seconds.
The unit stops operating.The orange lamp is turned off.
→
After approx. three seconds,
The unit beeps three times.
0
3S
If the unit is required to operate at this time,
TEMPORARY button
button once more or use the remote control to turn it on.
• While this function is being set, if the unit is in
operation, the orange lamp is on.
7-6-3. Power failure during timer operation
When the unit is in Timer operation, if it is turned off
because of power failure, the timer operation is
cancelled. Therefore, set the timer operation again.
7-7. Filter Check Lamp
When the elapsed time reaches 1000 hours, the filter
check lamp indicates. After cleaning the filters, turn off
the filter check lamp.
7-7-1. How to turn off filter check lamp
(1) Press [FILTER] button on the remote control.
(2) Push [TEMPORARY] button on the indoor unit.
push [TEMPORARY]
Note:
If [TEMPORARY] button is pushed while the filter
check lamp is not indicating, the indoor unit will start
the Automatic Operation.
– 19 –
y
g
g
play
(
(
p
)
g Op
g
p
g
(
(
)
g
FILE NO. SVM-06017
7-8. Self-Cleaning function.
Self-Cleaning function is designed to reduce humidity that causes mold to form inside the air conditioning unit.
This advanced, efficient system reduces moisture in the coil. When you turn off your air conditioner, the internal
fan activates and dries the moisture in the coil for 20 minutes, then turns off automaticall
.
Operation display
FCU fan
FCU louverOPENCLOSECLOSE
Timer display
Compressor
CDU fan
The Self-Cleaning function is set as default at ex-factory.
•
•
Self-Cleaning operation can stop manually by press [ ] botton of the remote
rpm is depend on preseting.rpm is SUL speed.
depend on preseting of timer function.depend on preseting of timer function.
depend on preseting per room temperature.
depend on preseting per room temperature.
Cool mode or dry modeSelf-Cleaning mode
operation more than 10 mins.operate 20 mins.
ONOFFOFF
ON ON
ON or OFF
ON or OFF
ON or OFF
Turn off by remote controller
or timer-off function.
ON
OFF OFF
OFFOFF
Automatically turn-off.
ON or OFF
control two more time.
7-8-1. How to cancel Self-Cleanin
To cancel the Self-Cleanin
function, proceed as follows:
function
• Press TEMPORARY button one time or use remote control to
turn on air conditioner. The OPERATION dis
orange color (When AUTO-RESTART is ON) or green color
When AUTO-RESTART is OFF).
•
Hold down the TEMPORARY button for more than 20 seconds.
The air conditioner will stop suddenly when the TEMPORARY is
ressed but keep holding it continue. Then will beep 3 times in
the first 3 seconds but it is not related to Self-Cleaning function
After holding about 20 seconds, the air conditioner will beep 5
•
times without any blinking of display.
The Self-Cleanin
•
eration had been cancelled.
OFF
Operation time
will show in
TEMPORARY button
Remarks
Per settin
•
of Self-Cleaning function above, AUTO-RESTART
function had been cancelled. To set AUTO-RESTART again,
lease follow item 7-6-1.
7-8-2. How to set Self-Cleaning function.
To set the Self-Cleaning function, proceed as follows.
•
Press TEMPORARY button one time or use remote control to
turn on air conditioner. The OPERATION display will show in
e color (When AUTO-RESTART is ON) or green color
oran
When AUTO-RESTART is OFF).
•
Hold down the TEMPORARY button for more than 20 seconds.
The air conditioner will stop suddenly when the TEMPORARY is
pressed but keep holding it continue. Then will beep 3 times is
the first 3 seconds but it is not related to Self-Cleaning function
•
After holding about 20 seconds, the air conditioner will beep
5 times and OPERATION display blinks 5 times.
•
The Self-Cleaning function had been set.
Remarks
•
Per settin
of Self-Cleaning function above, AUTO-RESTART
function had been cancelled. To set AUTO-RESTART again,
please follow item 7-6-1.
− 20 −
FILE NO. SVM-06017
7-9. QUIET Mode
Quiet mode is the system which, control the
revolving speed of indoor fan to work constantly
at lower than speed L. In addition, noise level of
indoor unit is less than usual.
When the [QUIET] button is pressed, the fan of the
indoor unit will be restricted the revolving speed at
speed L
again (cancel Quiet mode).
Remarks :
1. Quiet mode is unable to work in dry mode.
2. Quiet mode is appropriate to work with less
-
until the [QUIET] button is pressed once
cooling load and less heating load condition.
Because of the fan speed L- may cause not
enough the cooling capacity or heating capacity.
7-10. COMFORT SLEEP mode
The principles of comfort sleep mode are:
• Quietness for more comfortable.
• Save energy by changing room temperature
automatically.
• The air condition can shut down by itself
automatically.
7-10-1. Cooling mode
• The fan speed of indoor unit operates automatically,
it relates with the compressor's operation.
Compressor’s Operation Fan Speed
-
ONL
OFF SL
• The preset temperature will increase 1°C after the
Comfort sleep mode has operated for 1 hour and
the temperature will increase another 1°C after the
comfort sleep mode has operated for 2 hour. (The
value of the preset temperature on the remote control
does not change.)
• Press the [COMFORT SLEEP] button to choose the
operating hours. Repeat pressing to select the hours.
(1hr, 3hr, 5hr or 9hr)
• If the [COMFORT SLEEP] button is pressed again
means cancel comfort sleep mode.
Remarks:
1. Comfort sleep mode will not operate in dry mode
and fan only mode.
2. Comfort sleep mode is appropriate to work with less
cooling load and less heating load condition.
Because of the fan speed L- may cause not enough
the cooling capacity or heating capacity.
-
21
-
FILE NO. SVM-06017
8. INSTALLATION PROCEDURE
8-1. Safety Cautions
For general public use
Power supply cord of Outdoor unit shall be more than 4 mm2 (H07RN-F or 245 IEC66 : polychloroprene
sheathed flexible cord) or 3.5 mm2 (AWG-12).
CAUTION
This appliance must be connected to the main power supply by means of a circuit breaker or a switch with a
contact separation of at least 3 mm.
If this is not possible, a power supply plug with earth must be used. This plug must be easily accessible after
installation. The plug must be disconnected from the power supply socket in order to disconnect the
appliance completely from the mains.
To Disconnect the Appliance from the Main Power Supply
DANGER
• FOR USE BY QUALIFIED PERSONS ONLY.
• TURN OFF MAIN POWER SUPPLY BEFORE ATTEMPTING ANY ELECTRICAL WORK. MAKE SURE
ALL POWER SWITCHES ARE OFF. FAILURE TO DO SO MAY CAUSE ELECTRIC SHOCK.
• CONNECT THE CONNECTING CABLE CORRECTLY. IF THE CONNECTING CABLE IS CONNECTED
WRONGLY, ELECTRIC PARTS MAY BE DAMAGED.
• CHECK THE EARTH WIRE THAT IT IS NOT BROKEN OR DISCONNECTED BEFORE INSTALLATION.
• DO NOT INSTALL NEAR CONCENTRATIONS OF COMBUSTIBLE GAS OR GAS VAPORS.
FAILURE TO FOLLOW THIS INSTRUCTION CAN RESULT IN FIRE OR EXPLOSION.
• TO PREVENT OVERHEATING THE INDOOR UNIT AND CAUSING A FIRE HAZARD, PLACE THE UNIT
WELL AWAY (MORE THAN 2 M) FROM HEAT SOURCES SUCH AS RADIATORS, HEATORS,
FURNACE, STOVES, ETC.
• WHEN MOVING THE AIR-CONDITIONER FOR INSTALLING IT IN ANOTHER PLACE AGAIN, BE VERY
CAREFUL NOT TO GET THE SPECIFIED REFRIGERANT WITH ANY OTHER GASEOUS BODY INTO
THE REFRIGERATION CYCLE. IF AIR OR ANY OTHER GAS IS MIXED IN THE REFRIGERANT, THE
GAS PRESSURE IN THE REFRIGERATION CYCLE BECOMES ABNORMALLY HIGH AND IT
RESULTINGLY CAUSES BURST OF THE PIPE AND INJURIES ON PERSONS.
• IN THE EVENT THAT THE REFRIGERANT GAS LEAKS OUT OF THE PIPE DURING THE
INSTALLATION WORK, IMMEDIATELY LET FRESH AIR INTO THE ROOM. IF THE REFRIGERANT GAS
IS HEATED BY FIRE OR SOMETHING ELSE, IT CAUSES GENERATION OF POISONOUS GAS.
WARNING
• Never modify this unit by removing any of the safety guards or bypassing any of the safety interlock
switches.
• Do not install in a place which cannot bear the weight of the unit.
Personal injury and property damage can result if the unit falls.
• Before doing the electrical work, attach an approved plug to the power supply cord.
Also, make sure the equipment is properly earthed.
• Appliance shall be installed in accordance with national wiring regulations.
If you detect any damage, do not install the unit. Contact your TOSHIBA dealer immediately.
CAUTION
• Exposure of unit to water or other moisture before installation could result in electric shock.
Do not store it in a wet basement or expose to rain or water.
• After unpacking the unit, examine it carefully for possible damage.
• Do not install in a place that can increase the vibration of the unit. Do not install in a place that can amplify
the noise level of the unit or where noise and discharged air might disturb neighbors.
• To avoid personal injury, be careful when handling parts with sharp edges.
• Please read this installation manual carefully before installing the unit. It contains further important
instructions for proper installation.
– 22–
FILE NO. SVM-06017
REQUIREMENT OF REPORT TO THE LOCAL POWER SUPPLIER
Please make absolutely sure that the installation of this appliance is reported to the local power supplier
before installation. If you experience any problems, or if the installation is not accepted by the supplier, the
service agency will take adequate countermeasures.
Remark per EMC Directive 89/336/EEC
To prevent flicker impressions during the start of the compressor (technical process) following installation
conditions do apply.
1. The power connection for the air conditioner has to be done at the main power distribution. This distribution
has to be of an impedance.
Normally the required impedance is reached at a 32A fusing point. Air conditioner fuse has to be 16A max.!
2. No other equipment should be connected to this power line.
3. For detailed installation acceptance, please contact your power supplier whether its restriction does apply
for products like washing machines, air conditioners or electrical ovens.
4. For power details of the air conditioner, refer to the rating plate of the product.
– 23 –
8-2. Installation Diagram of Indoor and Outdoor Units
Hook
65 mm or more
(A
tta
c
h
to
th
5 Sasa-Zeolite Vitamin C filter
1
7
0
m
o
r m
m
o
re
A
ir filte
e
fr
o
n
t p
a
n
e
l) (A
tta
c
h
to
th
e
a
ir filte
6 Bio-enzyme & Gingko filter
Hook
r
r)
1
Installation
plate
1
7
0
o
r m
Shield
pipe
FILE NO. SVM-06017
For the rear left and left
piping
m
m
o
re
Insert the cushion between
the indoor unit and wall,
and tilt the indoor unit for
better operation.
Do not allow the drain hose
to get slack.
Wall
ore installing the
Bef
wireless remote control
• With the remote control cover
open, load the batteries supplied
correctly, observing their polarity.
2 Wireless remote control
Cover
3 Batteries
2 Wireless remote
control
100 mm or more
m
600 m
8 Pan head wood screw
4
Remote control holder
Vinyl tape
Apply after
carrying out a
drainage test.
Saddle
100 mm
600 mm or more
ore
r m
o
or more
Extension
drain hose
(Not available,
provided by
installer)
600 mm or more
Cut the piping hole
sloped slightly
Make sure to run the drain
hose sloped downward.
The auxiliary piping can be
connected the left, rear left,
rear right or bottom.
Right
Rear
Rear left
Bottom
Insulate the refrigerant
pipes separately with
insulation, not together.
Left
Electric parts cover
Loop the connective cable
(about 100 mm in diameter
and 300 – 350 mm long).
Fig. 8-2-1
– 24 –
6 mm thick heat resisting
polyethylene foam
8-3. Installation
8-3-1. Optional installation parts
FILE NO. SVM-06017
Part
Code
Parts name
Refrigerant piping
Liquid side : ∅6.35 mm
A
Gas side : ∅15.88 mm
Pipe insulating material
B
(polyethylene foam, 6 mm thick)
Putty, PVC tapes
C
< Fixing bolt arrangement of outdoor unit >
600 mm
Air inlet
64 mm
340 mm
120 mm
Q'ty
One
each
1
One
each
Air outlet
Fig. 8-3-1
• Secure the outdoor unit with fixing bolts and nuts if the unit is likely to be exposed to a strong wind.
• Use ∅ 8 mm or ∅ 10 mm anchor bolts and nuts.
– 25 –
8-3-2. Accessory and installation parts
FILE NO. SVM-06017
Part
No.
Part name (Q'ty)
1
Installation plate x 1
2
Wireless remote control x 1
3
Battery x 2
Others
Owner’s manual
Installation manual
Name
Part
No.
Part name (Q'ty)
4
Remote control holder x 1
5
Sasa-Zeolite Vitamin C filter x 2
6
Bio-enzyme & Gingko filter x 2
Part
No.
Part name (Q'ty)
7
Mounting screw ∅ 4 x 25 x 8
8
Pan head wood screw∅ 3.1 x 16 x 2
l
l
– 26 –
FILE NO. SVM-06017
8-4. Indoor Unit
8-4-1. Installation place
• A place which provides the spaces around the
indoor unit as shown in the above diagram.
• A place where there is no obstacle near the air inlet
and outlet.
• A place that allows easy installation of the piping to
the outdoor unit.
• A place which allows the Front panel to be opened.
CAUTION
• Direct sunlight to the indoor unit's wireless
receiver should be avoided.
• The microprocessor in the indoor unit should not
be too close to RF noise sources.
(For details, see the owner's manual.)
<Remote control>
• A place where there are no obstacles such as a
curtain that may block the signal from the indoor
unit.
• Do not install the remote control in a place exposed
to direct sunlight or close to a heating source, such
as a stove.
• Keep the remote control at least 1 m apart from the
nearest TV set or stereo equipment. (This is
necessary to prevent image disturbances or noise
interference.)
• The location of the remote control should be
determined as shown below.
8-4-2. Cutting a hole and mounting installation
plate
<Cutting a hole>
When installing the refrigerant pipes from the rear.
Pipe
hole
m
∅65 m
The center of the pipe
hole is above the arrow.
100 mm
Fig. 8-4-2
1. After determining the pipe hole position on the
mounting plate (100 mm A), drill the pipe hole
(∅65 mm) at a slight downward slant to the outdoor
side.
NOTE
• When drilling a wall that contains a metal lath, wire
lath or metal plate, be sure to use a pipe hole brim
ring sold separately.
<Mounting the installation plate>
Indoor unit
(Side view)
7 m
°
5
7
Reception
range
Remote
control
(Top view)
Indoor unit
Reception
range
* : Axial distance
Fig. 8-4-1
45
°
5 m
°
Remote control
* 7 m
170
120
Pipe hole
Hook
Indoor unit
Hook
Thread
Weight
55
Hook
Pipe hole
7Mounting screw
65
1
Installation
plate
m
5
45
Fig. 8-4-3
– 27 –
FILE NO. SVM-06017
<When the installation plate is directly mounted on
the wall>
1. Securely fit the installation plate onto the wall by
screwing it in the upper and lower parts to hook up
the indoor unit.
2. To mount the installation plate on a concrete wall
with anchor bolts, utilize the anchor bolt holes as
illustrated in the above figure.
3. Install the installation plate horizontally in the wall.
CAUTION
When installing the installation plate with a
mounting screw, do not use the anchor bolt hole.
Otherwise the unit may fall down and result in
personal injury and property damage.
Installation plate
<Keep horizontal direction>
Anchor
bolt
Projection
5 mm dia. hole
15 mm or less
8-4-3. Electrical work
1. The supply voltage must be the same as the rated
voltage of the air conditioner.
2. Prepare the power source for exclusive use with the
air conditioner.
NOTE
• Wire type: More than 1.5 mm2 (H07RN-F or 245
IEC66) or 1.3 mm2 (AWG-16)
CAUTION
• Use power specified above table.
• This appliance can be connected to the mains in
the following way.
Connection to fixed wiring:
A switch or circuit breaker which disconnects all
poles and has a contact separation of at least
3 mm must be incorporate in the fixed wiring. An
approved circuit breaker or switches must used.
NOTE
• Perform wiring works so as to allow a generous
wiring capacity.
7 Mounting
screw
ss
∅4 x 25
s
ss
Clip anchor
(local parts)
Fig. 8-4-4
CAUTION
Failure to firmly install the unit may result in
personal injury and property damage if the unit falls.
• In case of block, brick, concrete or similar type
walls, make 5 mm dia. holes in the wall.
• Insert clip anchors for appropriate 7 mounting
screws.
NOTE
• Secure four corners and lower parts of the
installation plate with 6 to 7 mounting screws to
install it.
– 28 –
8-4-4. Wiring connection
Air inlet grille
FILE NO. SVM-06017
Connecting cable
Front panel
2
1
Terminal
cover
Screw
Terminal block
Cord clamp
Screw
Connecting cable
Earth
line
Fig. 8-4-5
<How to connect the connecting cable>
Wiring of the connecting cable can be carried out
without removing the front panel.
about 15 cm
Fig. 8-4-6
<Stripping length of connecting cable>
10 mm
10 mm
50 mm
40 mm
Earth line
Fig. 8-4-7
NOTE
Use stranded wire only.
• Wire type : More than 1.5 mm2 (H07RN-F or 245
IEC66) or 1.3 mm2 (AWG-16)
1. Remove the air inlet grille.
Open the air inlet grille upward and pull it toward
you.
2. Remove the terminal cover and cord clamp.
3. Insert the connecting cable (according to the local
cords) into the pipe hole on the wall.
4. Take out the connecting cable through the cable
slot on the rear panel so that it protrudes about
15 cm from the front.
5. Insert the connecting cable fully into the terminal
block and secure it tightly with screws.
6. Tightening torque : 1.2 N·m (0.12 kgf·m)
7. Secure the connecting cable with the cord clamp.
8. Fix the terminal cover, rear plate bushing and air
inlet grille on the indoor unit.
CAUTION
• Be sure to refer to the wiring system diagram
labeled inside the front panel.
• Check local electrical cords and also any specific
wiring instructions or limitations.
Fig. 8-4-8
NOTE
Connect the earth line to the metallic part (i mark)
located at the side of 3P terminal.
<How to install the air inlet grille on the indoor unit>
• When attaching the air inlet grille, the contrary of
the removed operation is performed.
– 29 –
Fig. 8-4-9
FILE NO. SVM-06017
8-4-5. Piping and drain hose installation
<In case of rightward piping>
• After scribing slits of the body-right by a knife or a
making-off pin, cut them by a pair of nippers or the
like.
Slit (Body-right)
Fig. 8-4-10
<In case of downward piping>
• After scribing slits of the body-right by a knife or a
making-off pin, cut them by a pair of nippers or the
like.
To connect pipe after installation of unit (figure)
(To the forefront of flare)
400 mm
300 mm
R 30 mm (Use polisin (polyethylene
core or the like for bending pipe.)
43 mm
Liquid side
Gas side
Outward form of indoor unit
Use the handle of screwdriver, etc.
Fig. 8-4-12
NOTE
If the pipe is bent incorrectly, the indoor unit may
unstably be set on the wall.
After passing the connecting pipe through the pipe
hole, connect the connecting pipe to the auxillary pipes
and wrap the facing tape around them.
Slit (Body-right)
Fig. 8-4-10
<Left-hand connection with piping>
Bend the connecting pipe so that it is laid within 43 mm
above the wall surface. If the connecting pipe is laid
exceeding 43 mm above the wall surface, the indoor
unit may unstably be set on the wall. When bending the
connecting pipe, make sure to use spring bender so as
not to crush the pipe.
Bend the connection pipe within a radius of 30 mm.
CAUTION
• Bind the auxiliary pipes (two) and connecting
cable with facing tape tightly. In case of leftward
piping and rear-leftward piping, bind the auxiliary
pipes (two) only with facing tape.
Indoor unit
Auxiliary pipes
Installation plate
• Carefully arrange pipes so that any pipe does
not stick out of the rear plate of the indoor unit.
• Carefully connect the auxiliary pipes and
connecting pipes to each other and cut off the
insulating tape wound on the connecting pipe to
avoid double-taping at the joint, moreover, seal
the joint with the vinyl tape, etc.
• Since dewing results in a machine trouble, make
sure to insulate both the connecting pipes.
(Use polyethylene foam as insulating material.)
• When bending a pipe, carefully do it not to crush
it.
Connecting
cable
Drain hose
– 30 –
FILE NO. SVM-06017
8-4-6. Indoor unit fixing
1. Pass the pipe through the hole in the wall, and hook
the indoor unit on the installation plate at the upper
hooks.
2. Swing the indoor unit to right and left to confirm that
it is firmly hooked up on the installation plate.
3. While pressing the indoor unit onto the wall, hook it
at the lower part on the installation plate. Pull the
indoor unit toward you to confirm that it is firmly
hooked up on the installation plate.
1
2
Hook
Hook here
1 Installation
plate
Press
(unhook)
Fig. 8-4-13
• For detaching the indoor unit from the installation
plate, pull the indoor unit toward you while pushing
its bottom up at the specified parts.
8-4-7. Drainage
1. Run the drain hose sloped downwards.
NOTE
• Hole should be made at a slight downward slant on
the outdoor side.
Do not form the drain hose
Do not rise the drain hose.
50 mm
or more
Do not put the
drain hose end
into water.
into a wavy shape.
Do not put the
drain hose end
in the drainage
ditch.
Fig. 8-4-15
2. Put water in the drain pan and make sure that the
water is drained out of doors.
3. When connecting extension drain hose, insulate the
connecting part of extension drain hose with shield
pipe.
Fig. 8-4-14
Shield pipe
Drain hose
Inside the
room
Extension drain hose
Fig. 8-4-16
PushPush
CAUTION
Arrange the drain pipe for proper drainage from the
unit.
Improper drainage can result in dew-dropping.
This air conditioner has the structure designed to drain
water collected from dew, which forms on the back of
the indoor unit, to the drain pan.
Therefore, do not store the power cord and other parts
at a height above the drain guide.
Wall
Drain guide
Space for pipes
– 31 –
Fig. 8-4-17
FILE NO. SVM-06017
8-5. Outdoor Unit
8-5-1. Installation place
• A place which provides the spaces around the
outdoor unit as shown in the left diagram.
• A place which can bear the weight of the outdoor
unit and does not allow an increase in noise level
and vibration.
• A place where the operation noise and discharged
air do not disturb your neighbors.
• A place which is not exposed to a strong wind.
• A place free of a leakage of combustible gases.
• A place which does not block a passage .
• When the outdoor unit is to be installed in an
elevated position, be sure to secure its feet.
• An allowable length of the connecting pipe is up 15 m.
(Refer to the table of T O CHARGE REFRIGERANT
for detail.)
• An allowable height level is up to 10 m.
• A place where the drain water does not raise any
problem.
CAUTION
8-5-2. Refrigerant piping connection
1. Cut the pipe with a pipe cutter.
90°
Obliquity
Roughness
Fig. 8-5-2
2. Insert a flare nut into the pipe, and flare the pipe.
• Projection margin in flaring : A (Unit : mm)
A
Die
Pipe
Fig. 8-5-3
Outer dia.
of copper pipe
∅6.35
RigidImperial
1.0 to 1.5
A
1.5 to 2.0
Warp
1. Install the outdoor unit without anything blocking
the air discharging.
2. When the outdoor unit is installed in a place
exposed always exposed to strong wind like a
coast or on a high storey of a building, secure
the normal fan operation using a duct or a wind
shield.
3. In particularly windy areas, install the unit such
as to avoid admission of wind.
4. Installation in the following places may result in
trouble.
Do not install the unit in such places.
• A place full of machine oil.
• A saline-place such as the coast.
• A place full of sulfide gas.
• A place where high-frequency waves are likely
to be generated as from audio equipment,
welders, and medical equipment.
Strong
wind
15.88
∅
1.0 to 1.5
2.0 to 2.5
<Tightening connection>
Align the centers of the connecting pipes and tighten
the flare nut as far as possible with your fingers. Then
tighten the nut with a spanner and torque wrench as
shown in the figure.
CAUTION
• Do not apply excess torque.
• Otherwise, the nut may crack depending on the
conditions.
Fig. 8-5-1
– 32 –
FILE NO. SVM-06017
(Unit : N·m)
Outer dia.
of copper pipe
∅ 6.35 mm
∅15.88 mm
Tightening torque
16 to 18 (1.6 to 1.8 kgf·m)
65 to 80 (6.5 to 8.0 kgf·m)
• Tightening torque of flare pipe connections
Flare at
indoor unit side
Flare at
outdoor unit side
Fig. 8-5-4
Flare nutHalf union
Externally
threaded side
Use a wrench to secure.
Use a torque wrench to tighten.
Internally
threaded side
Fig. 8-5-5
CAUTION
8-5-3. Evacuating
After the piping has been connected to the indoor unit,
you can perform the air purge together at once.
AIR PURGE
Evacuate the air in the connecting pipes and in the
indoor unit using a vacuum pump. Do not use the
refrigerant in the outdoor unit. For details, see the
manual of the vacuum pump.
<Using a vacuum pump>
Be sure to use a vacuum pump with counter-flow
prevention function so that inside oil of the pump does
not flow backward into pipes of the air conditioner
when the pump stops.
1. Connect the charge hose from the manifold valve to
the service port of the gas side packed valve.
2. Connect the charge hose to the port of the vacuum
pump.
3. Open fully the low pressure side handle of the
gauge manifold valve.
4. Operate the v acuum pump to start evacuating.
Perform evacuating for about 15 minutes if the
piping length is 20 meters. (15 minutes for 20
meters) (assuming a pump capacity of 27 liters per
minute.) Then confirm that the compound pressure
gauge reading is –101 kPa (–76 cmHg).
5. Close the low pressure side valve handle of gauge
manifold.
6. Open fully the valve stem of the packed valves
(both sides of Gas and Liquid).
7. Remove the charging hose from the service port.
8. Securely tighten the caps on the packed valves.
• KEEP IMPORTANT 4 POINTS FOR PIPING
WORK
(1) Take away dust and moisture (Inside of the
connecting pipes.)
(2) Tight connection (between pipes and unit)
(3) Evacuate the air in the connecting pipes using
VACUUM PUMP.
(4) Check gas leak (connected points)
Compound pressure gauge
-101kPa (-76cmHg)
Handle Lo
Charge hose
Connecting pipe
Packed valve at liquid side
Packed valve at gas side
Service port
(Valve core (Setting pin))
Fig. 8-5-6
Pressure gauge
Manifold valve
Handle Hi
(Keep full closed)
Charge hose
Vacuum pump
adapter for
counter-flow
prevention
Vacuum
pump
– 33 –
FILE NO. SVM-06017
TOCHARGE REFRIGERANT
Refrigerant
No need to charge
refrigerant
Need to charge Over 15 m up to
refrigerant 25 m (40g/m)
30 Class
15 m or less
<Packed valve handling precautions>
• Open the valve stem all the way out; but do not try
to open it beyond the stopper.
• Securely tighten the valve stem cap with torque in
the following table:
Gas side Tightening torque A
Gas side65 to 80 N·m
(∅15.88 mm.)(6.5 to 8.0 kgf·m)
4 mm
Liquid side16 to 18 N·mSame as
(∅6.35 mm.)(1.6 to 1.8 kgf·m)Gas side
Service port
9 to 10 N·m
(0.9 to 1.0 kgf·m)
8-5-4. Wiring connection
1. Remove the electric parts cover from the outdoor unit.
2. Connect the connecting cable to the terminal as
identified with their respective matched numbers on
the terminal block of indoor and outdoor unit.
3. When connecting the connecting cable to the
outdoor unit terminal, make a loop as shown
installation diagram of indoor and outdoor unit, to
prevent water coming in the outdoor unit.
4. Insulate the unused cords (conductors) with water
coming in the outdoor unit. Process them so that
they do not touch any electrical or metal parts.
<Stripping length of connection cable>
Terminal block
LN132
Terminal screw
Earth line
Cord clamp
Power supply cord
Screw
Cord clamp
Connecting cable
• Hexagonel wrench: A (unit : mm)
Hexagonal wrench
is required.
Fig. 8-5-7
N
L
10
10
60
A
70
Earth line
123
10
10
70
Connecting cablePower supply cord
80
Fig. 8-5-8
Model
Power source
Maximum running
current
Plug socket &
fuse rating
Power cord
4 mm2 (H07RN-F or 245 IEC 66) or
3.5 mm
60 Hz, 220 ~ 230V Single phase
30 Class
18A
20A
2
(AWG-12)
CAUTION
• Wrong wiring connection may cause some
electrical parts burn out.
• Be sure to comply with local codes on running the
wire from outdoor unit to indoor unit (size of wire
and wiring method etc.)
• Every wire must be connected firmly.
NOTE: Connecting cable
• Wire type : More than 1.5 mm2 (H07RN-F or 245
IEC66) or 1.3 mm2 (AWG-16)
– 34 –
FILE NO. SVM-06017
8-6.How to Set Remote Control Selector
Switch
When two indoor units as installed in seperated rooms,
there is no need to change the selector switch.
<Remote control selector switch>
• When two indoor units are installed in the same
room or the adjacent two rooms, they may be
controlled simultaneously with a single remote
control. To prevent this, set either unit and its
remote control to B setting. (Both units are set to A
setting before shipment.)
• The remote control signal is not recived when the
indoor unit setting is different from the remote
control one.
1. Set the remote control selector switch with the
indoor unit.
1) Turn the circuit breaker of the main power switch off
before setting the selector switch.
2) Remove the Air inlet grille and Front panel. (Refer to
page 52, 10-1)
2. Set the remote control selector switch with the
remote control
[B] is indicated on the liquid crystal display when
setting remote control selector switch to B. [A] is
not indicated on the display even if the selector
switch is set to A.
1) Load the remote control with the batteries.
2) Press the [CHK] button using something with
sharp point. (The preset temperature on the remote
control changes to [00].)
3) Press the [MODE] button while pressing the
[CHK] button, [B] is indicted at the right of the
present temperature display.
• To reset the switch to the [A] setting, press the
[MODE] button again while pressing the [CHK]
button.
3) Select the terminal of selector switch from
[A position] to [B position].
A
B
Fig. 8-6-1
Slector
switch
[MODE] button
[CHK] button
Fig. 8-6-2
3. Confirm that the indoor unit can operate with
the new setting.
– 35 –
FILE NO. SVM-06017
8-7. Others
8-7-1. Gas leak test
Electric parts cover
Flare nut connections
(Outdoor unit)
D
B
Valve stem cap connection
Fig. 8-7-1
• Check the flare nut connections, valve stem cap
connections and service port cap connections for
gas leak with a leak detector or soap water.
8-7-2. Test operation
C
Flare nut connections
(indoor unit)
Valve stem cap
connection
A
Service cap
connection
8-7-3. Auto restart setting
This product is designed so that, after a power failure,
it can restart automatically in the same operating mode
as before the power failure.
Information
The product was shipped with Auto Restart function
in the off position. Turn it on as required.
<How to set the auto restart>
• Press and hold down the TEMPORARY button for
about 3 seconds. After 3 seconds, the electronic
beeper makes three short beeps to tell you the Auto
Restart has been selected.
• To cancel the Auto Restart, follow the steps
described in the section Auto Restart Function of
the Owner’s Manual.
To switch the TEST RUN (COOL) mode, press
TEMPORARY b utton for 10 sec.
(The beeper will make a short beep.)
TEMPORARY button
Fig. 8-7-2
– 36 –
9. TROUBLESHOOTING CHART
FILE NO. SVM-06017
9-1. Troubleshooting Procedure :
9-2-2. Incorrect cable connection between Indoor
and outdoor units
Follow the details of 9-2. Basic Check Items.
If there is no trouble corresponding to 9-2, check
whether or not there are faulty parts following
9-4. Self-Diagnosis by Remote Control.
9-2. Basic Check Items
The indoor unit is connected to the outdoor unit with
4 cables. Check that the indoor and outdoor units have
been properly connected with terminals assigned the
same numbers. If the connectors are not properly
connected, the outdoor unit will not operate normally,
or OPERATION lamp and TIMER lamp will blink (5 Hz).
9-2-1. Power supply voltage
The line voltage must be AC 220 – 240 V. If it is not
within this range, the air conditioner may not operate
normally.
9-2-3. Program control
The microcontroller operates as shown in Table 9-2-1
to control the air conditioner. If there are any operational problems, check whether or not the problems
correspond to Table 9-2-1. If they correspond to the
Table, they are not problems with the air conditioner,
but they are indispensable operations to control and
maintain the air conditioner properly.
Table 9-2-1
No.Operation of air conditionerDescriptions
1When the main power supply is turned
on, the OPERATION lamp on the
indoor unit blinks.
2The indoor fan motor speed does not
change in the Dry operation.
3The compressor is not turned off even
though the room temperature is in the
range that the compressor is turned off.
The OPERATION lamp blinks to indicate that power is turned on. If the
[ ] button is pressed, the lamp stops blinking.
The indoor fan motor speed is automatically controlled in the Dry
operation.
The compressor has a function that it is not turned off for 3 minutes
after it is turned on even though the room temperature is in the range
that the compressor is turned off.
4The compressor is not turned on and
off even though the thermo control is
operated in the Dry operation.
5The compressor is not turned on even
though the room temperature is in the
range that the compressor is turned on.
6The operation mode changes in the
Automatic operation.
7The Fan only operation continues in the
Automatic operation.
8The ECO operation or Hi-POWER
operation does not work.
9When [Hi POWER] button is pressed,
the display on the remote control does
not change at all.
In the Dry operation, the compressor is turned on and off automatically
at the regular intervals, independent of the thermo control.
The compressor is not turned on in the restart delay timer (3-minutes
timer) operation. It is also not turned on after the power supply is
turned on because of this timer operation.
In Automatic operation, the room temperature is detected all time
for control fan speed and the operation mode is changed every
15 minutes according to difference between the room temperature
and the preset temperature.
When the room temperature is in the range
(Preset temperature ± 1°C), the Fan only operation is selected.
These operations do not work when the unit is in the Dry
operation or Fan only operation.
The display on the remote control does not change when
[Hi POWER] button is pressed. However the microcontroller gives
commands to change the preset temperature and air flow level.
– 37 –
FILE NO. SVM-06017
9-3. Primary Judgement
9-3-1. Role of indoor unit controller
The indoor unit controller receives the operation
commands from the remote control and executes
them.
• Temperature measurement at the air outlet of the
indoor heat exchanger by the indoor temperature
sensor
• Temperature setting of the indoor heat exchanger by
the heat exchanger sensor
• Louver motor control
• Indoor fan motor operation control
• LED display control
• Transferring of operation commands to the outdoor
unit
Table 9-3-1
LampsSelf-diagnosis
AOPERATION lamp is blinking. (1 Hz)
BOPERATION lamp is blinking. (5 Hz)
COPERATION lamp is blinking. (5 Hz)
DOPERATION lamp is blinking. (5 Hz)
EOPERATION lamp is blinking. (5 Hz)
FOPERATION and TIMER lamps are blinking.
(5 Hz)
9-3-2. Failure diagnosis
The indoor unit diagnoses the operation condition and
indicates the information of the self-diagnosis with the
lamps on the display panel of the indoor unit.
Power failure (when the power supply is turning on)
Thermo sensor (TA) short or break
Heat exchanger sensor (TC) short or break
Indoor fan motor lock or failure
Indoor P.C. board failure
Wrong wiring of connecting cable
GOPERATION, TIMER and PRE-DEF.
(or FAN ONLY for cooling only model) lamps
are blinking.
Table 9-3-2 Diagnosis by detective operation
SymptomCheckPrimary judgement
The remote control
does not work.
The outdoor fan
does not rotate.
Turn off the power supply once,
then turn it on. Try to operate
the remote control.
The compressor operates.
The compressor does not operate.
Cycle failure
• Gas shortage or other refrigerant cycle trouble
• Heat exchanger sensor open, break or short
• Overload relay or thermostat trouble of compressor
The remote control
still does not work.
The remote control
works.
The indoor unit (and/or remote
control) is/are defective .
OK.
The outdoor unit (Outdoor fan
motor) is defective .
An internal part of the
compressor or P.C. board is
defective.
– 38 –
9-4. Self-Diagnosis by Remote Control
(Check Code)
(1) If the lamps are indicated as shown B to G in Table
9-3-1, exchanger the self-diagnosis by the remote
control.
(2) When the remote control is set to the service
mode, the indoor controller diagnoses the
operation condition and indicate the information of
the self-diagnosis on the display of the remote
control with the check codes. If a fault is detected,
all lamps on the indoor unit will blink at 5 Hz and it
will beep for 10 seconds (Pi, Pi, Pi....). The timer
lamp usually blinks (5 Hz) during the self-diagnosis.
9-4-1. How to use remote control in service mode
FILE NO. SVM-06017
(1) Press [CHK] button with a tip of pencil to set the
remote control to the service mode.
• “00” is indicated on the display of the remote
control.
• The timer lamp on the indoor unit blinks
continuously. (5 times per 1 sec.)
(2) Press [TIMER 8] button.
If there is no fault with a code, the indoor unit will
beep once (Pi) and the display of the remote
control will change as follows:
00
01
• Check the unit with all 35 check codes (00 to 22).
as shown in Table 9-4-1.
• Press [TIMER 9] button to change the check
code backwards.
If there is a fault, the indoor unit will beep f or 10
seconds (Pi, Pi, Pi...).
Note the check code on the display of the remote
control.
• 2-digits alphanumeric will be indicated on the
display.
• All lamps on the indoor unit will blink. (5 times
per 1 sec.)
(3) Press [CLR] button. After service finish for clear
service code in memory.
• “7F” is indicated on the display of the remote
control.
1d
1E0222
• Alphanumeric characters are used for the check code.
is 5.is 6.
is A.is B.
is C.is D.
* This illustration is only for Heat pump model.
For Cooling only model, there is not the ( ) symbol.
– 39 –
(4) Press [ ] button to release the service
mode.
• The display of the remote control returns to as it
was before service mode was engaged.
Table 9-4-1
Block levelDiagnosis function
Check
codecodestatus
Block
Indoor
P.C. board
Cable
connection
Outdoor
P.C. board
Other parts
(including
compressor)
Check
Symptom
The indoor thermo sensor (TA) is
defective.
Disconnection or short-circuit
The indoor heat exchanger
sensor (TC) is defective.
Disconnection or short-circuit
The indoor fan motor or its circuit
is defective.
The part other than the above
parts on the indoor P.C. board is
defective.
EEPROM access error
IOL operation
The serial signals can not be
transmitted and received between
indoor and outdoor units.
The crossover wire is
•
connected wrongly.
The serial signal transmitting
•
circuit on the outdoor P.C. board
is defective.
The serial signal receiving
•
circuit on the indoor P.C. board
is defective.
The operation command signals
are not transmitted from the
indoor unit to the outdoor unit.
The outdoor thermo sensor (TE)
is defective.
Disconnection or short-circuit
The outdoor heat exchanger (TD)
sensor is defective.
Disconnection or short-circuit
The reply serial signal has been
transmitted when starting the
unit, but stops being transmitted
shortly after.
1. Compressor ther mo operation
•
Gas shortage
• Gas leak
2. Instantaneous power failure
The discharge temperature is
over 120°C.
The IOL operation is defective.
Unit
Operation
continues.
Operation
continues.
All off
Operation
continues.
All off
Operation
continues.
Operation
continues.
All off
All off
Operation
continues.
All off
All off
Condition
The lamp on the
indoor unit blinks
when error is
defected.
The lamp on the
indoor unit blinks
when error is
defected.
The lamp on the
indoor unit blinks
when error is
defected.
The lamp on the
indoor unit blinks
when error is
defected.
The lamp on the
indoor unit blinks
when error is
defected.
The lamp on the
indoor unit blinks
when error is
defected.
The lamp on the
indoor unit blinks
when error is
defected. And it
returns to the
normal condition
when recovering
from errors.
The lamp on the
indoor unit blinks
when error is
defected.
The lamp on the
indoor unit blinks
when error is
defected.
The lamp on the
indoor unit blinks
when error is
defected. And it
returns to the
normal condition
when recovering
from errors.
The lamp on the
indoor unit blinks
when error is
defected.
The lamp on the
indoor unit blinks
when error is
detected.
FILE NO. SVM-06017
Judgement and action
1. Check the indoor thermo sensor (TA).
2. Check the indoor P.C. board.
1. Check the indoor heat exchanger
sensor (TC).
2. Check the indoor P.C. board.
1. Check the connector circuit of the
indoor fan motor (CN10).
2. Check the indoor fan motor.
3. Check the indoor P.C. board.
1. Check the indoor P.C. board.
(EEPROM and peripheral circuits)
Overload operation of refrigerating cycle
1. In the case of the outdoor unit not
operating at all;
•
Check the crossover cable and
connect it properly.
•
Check the outdoor P.C. board.
2. In the case of the outdoor unit operating
normally;
•
Check whether or not both of serial
LED (Green) and serial LED (Orange)
is blinking.
If the serial LED (Green) is not
blinking, check the outdoor P.C. board.
If the serial LED (Orange) is not
blinking, check the indoor P.C. board.
If the operation command signals continue
to be transmitted between 2 and 3 of the
indoor terminal block, replace the outdoor
P.C. board.
1. Check the outdoor thermo sensor (TE).
2. Check the outdoor P.C. board.
1. Check the outdoor heat exchanger
sensor (TD).
2. Check the outdoor P.C. board.
1. Repeatedly tur n the indoor unit on and
off with the interval of approx. 10 to 40
minutes. (The check code is not
indicated during operation.) And supply
gas. (Check gas leak.)
2. The indoor unit operates nor mally
during the check.
If the reply serial signal continues to be
transmitted between 2 and 3 of the
indoor terminal block, replace the
outdoor P.C. board.
If the signal stops between them,
replace the indoor P.C. board.
1. Check the heat exchanger sensor (TD).
2. Gas purging
When turning on the unit, the normal
phase (RST) is detected but T-R waveform
has not been detected for 120 seconds or
more.
−40−
9-5. How To Diagnose Faulty Parts
[09 Other cycle error]
FILE NO. SVM-06017
Connect
connector
properly.
Replace
condenser.
Replace
fan motor.
NO
NO
NO
Is connector
connected properly?
Is condenser normal?
Is indoor fan
motor normal?
YES
YES
YES
NO
Does indoor
fan operate?
Are filters clogged?
Is TC sensor
resistance value
(10 kΩ at 25°C) normal?
Is charged amount
of refrigerant normal?
Is outside air
low load?
Indoor P.C. board
is defective.
YES
NO
YES
YES
NO
YES
NO
NO
YES
Clean filters.
Replace
TC sensor.
Anti-freezing operation
Charge
refrigerant.
Anti-freezing operation
Replacd
P.C. board.
[0C Indoor TA sensor error]
Is CN04 (TA sensor connector)
connected properly?
YES
Is TA sensor resistance value
(10 kΩ at 25°C) normal?
YES
NO
NO
Indoor P.C. board is defective.
Connect CN04 properly.
Replace T A sensor.
Replace P.C. board.
– 41 –
[0d Indoor TC sensor error]
FILE NO. SVM-06017
Is CN05 (TC sensor connector)
connected properly?
YES
Is TC sensor resistance value
(10 kΩ at 25°C) normal?
YES
NO
NO
Indoor P.C. board is defective.
Connect CN05 properly.
Replace TC sensor.
Replace P.C. board.
– 42 –
9-6. Troubleshooting for Indoor unit
Operation
Measure
Item by symptoms
Check item
Conceivable principle
cause
9-6-1. Power can not be turned on. (The unit does not operate at all.)
<Primar check>
(1) Is the supply voltage normal?
(2)Is the connection to the AC output OK?
(3) Is the fuse (F01) blown?
Turn off power
supply once, and 5
second later, turn it
on again.
NO
Is OPERATION
lamp blinking?
YES
Does
Is it possible to
turn on power
supply by
pressing
[ ]
button on remote
control?
YES
NO
transmission
mark on
remote
control flash
normally, and
is its signal
transmitted
properly?
YES
NO
FILE NO. SVM-06017
Remote control is
defective.
Refer to 9-9
"Troubleshooting for
Remote Control."
Is DC 310 -
340V across
C03?
Are DC 12V,
across C27?
YES
YES
NO
NO
Is fuse (F01)
control board
Is voltage (DC
NO
indicated on
rear of indoor
control board
Turn off breaker
once and turn it
on again after
removing motor.
of indoor
blown?
NO
12V or 5V)
normal?
YES
YES
Parts (R10,
C01, DB01,
or C02, C03
IC01)
are defective.
Are DC 12V,
across C27?
YES
– 43−
NO
Does the fan
motor
connector
between 1
and
short-
3
circuit?
NO
Microconlroler
defective.
T01 or IC01 is
def
ec
tive.
YES
Unit operates
normally.
Replace main P.C.
board.
Replace motor.
FILE NO. SVM-06017
9-6-2. Only indoor fan motor does not operate.
<Primary check>
(1) Is it possible to detect the power supply voltage (200 – 240 V) between 1 and 2 on the terminal block?
(2) Does the indoor fan motor operate in cooling operation?
[ ]
– 44 –
FILE NO. SVM-06017
9-6-3. Indoor fan motor automatically starts to rotate by turning on power supply.
<Cause>
The IC is built in the indoor fan motor. Therefore the P.C. board is also mounted to the inside of the motor.
If the P.C. board is soldered imperfectly or the IC is defective, the fan motor may automatically rotate by turning
on power supply.
<Inspection procedure>
(1) Remove the front panel. (Remove 4 screws.)
(2) Remove the cover of the fan motor lead wires.
(3) Check DC voltage with CN10 connector while the fan motor is rotating.
NOTE:
• Do not disconnect the connector while the fan motor is rotating.
• Use a thin test rod.
Indoor fan starts rotating when power supply is turned on.
(Check output DC voltage of fan motor on P.C. board.)
Measure voltage between 3 (GND:BLACK)
and 5 (V line:YELLOW) of motor connector
(CN10) while indoor fan motor is rotating.
DC 1.0 V or more
P.C. board is defective.
Replace P.C. board.
Under DC 1.0 V
Motor is defective.
Replace motor.
DC
Yellow
Black
P.C. board
CN10
6 (Blue)
5 (Yellow)
4 (White)
3 (Black)
2
1 (Red)
– 45 –
9-6-4. Compressor does not operate.
<Primary check>
(1) Is the preset temperature higher than the room temperature in cooling operation?
(2) Is the crossover cable connected properly?
<Inspection procedure>
-Cooling only model-
FILE NO. SVM-06017
– 46 –
<Inspection procedure>
- Colling model -
Turn on power supply.
FILE NO. SVM-06017
Does OPERATION
lamp blink?
YES
Is it possible to start
unit by remote control?
YES
Is it possible to detect AC 200V
between 2 and 3 on terminal block?
YES
Is crossover cable normal?
YES
Are all of compressor cords normal?
YES
Is compressor motor winding normal?
(Check winding resistor.)
YES
Is capacitor for compressor normal?
YES
NO
NO
NO
NO
NO
NO
NO
Compressor is defective.
Capacitor is defective.
Refer to item Power
can not be turned on .
Refer to 9-9 Troubleshooting
for Remote Control .
Replace P.C. Board
and TC sensors.
Connect crossover
cable properly.
Rewire or replace
defective cords.
Replace compressor.
Replace compressor.
Is overload relay normal?
YES
Does compressor start?
YES
Does compressor stop after a while?
YES
Is gas quantity normal?
(Check gas pressure.)
YES
Compressor is defective.
YES
Replace P.C. borad
NO
NO
NO
Overload relay is defective.
Compressor is defective.
Gas shortage (Gas leak)
Replace overload relay.
Replace compressor.
Supply gas.
− 47−
FILE NO. SVM-06017
9-7. Troubleshooting for Wiring (Interconnect cable)
9-7-1. Outdoor unit does not operate.
<Inspection procedure>
(1) Is the voltage between and of the indoor terminal block varied?
1
(2) Are signals from the indoor unit to the outdoor unit transmitted correctly based upon the following diagram?
NOTE:
Measure the voltage for 2 minutes and 30 seconds after starting the unit.
Terminal block on indoor side
Red
2
3
~
White
2
1
Terminal block
~
Tester
Fig. 9-7-1
Normal condition : After start operated about 2 minutes and 30 seconds. Voltage between 2 and 3 of the
of the indoor's Terminal block should be equal AC 220 ~ 240V (For Asia model), AC 220V
Abnormal condition : Don't found voltage AC 220 ~ 240V from terminal block (0V)
9-7-2. Outdoor unit stops a while after starting the unit.
<Confirmation procedure> Select one of 3 cases below and follow the procedure.
(1) The outdoor unit stops between 10 and 20 minutes passed after starting and it takes 10 minutes or more to
restart the unit.
Gas has a low circulation.
Measure gas pressure.
Compressor is turned off and on automatically by
or thermostat (Cooling only Model).
Gas shortage
Gas leak
Pipe clogging
(2) The outdoor unit stops once, it would not operate until the power is turned on again.
Refer to 9-6-4 "Compressor does not operate"
(3) The outdoor unit stops between 10 minutes to 1 hour after starting and a check code is indicated on the
remote control. (Check code 03-1E : Refer to Table 9-4-1.)
−48−
9-8. Troubleshooting for Air Purifier and Minus Ion
9-8-1. How to Check Whether the Air Purifier is Good or Not
Turn off the power breaker once,
and turn on again after 10 seconds.
FILE NO. SVM-06017
Does the OPERATION lamp blink?
YES
Turn off the power breaker and
remove CN34 (Micro switch connector).
Short-circuit between 1 and 2 pin
of CN34 at PC side, and turn on the
power breaker after 10 seconds.
Is DC12V applied
1
between
(Brown/GND) of CN1 of the
micro-switch connector under
OFF status of the micro-switch
micro-switch connector under
ON status of the micro-switch
1) Check operation while short-circuiting CN34 of the main P.C. board.
2) Perform air purifying operation by the remote control.
• In this time, check that the remote control is in status which is shortened by time on
• While the air purifier operates, check that the fan speed [AUTO] is not displayed.
3) Be sure not to touch the dust collector, ionizer, or ionized wire unit with the human body.
(Red/DC12V) and
high-voltage unit?
YES
Is there conduction of
(Front panel opened)?
NO
Is there conduction of
(Front panel closed)?
YES
the reactivation preventive timer and all display lamps go on for approx. 3 seconds
when a signal is received.
If time on the reactivation preventive timer is not shortened,
( )
the high-voltage is not applied to electrode of the air purifier for approx. 1 hour.
(Because the power ON/OFF is controlled on the program)
NO
NO
YES
NO
Is DC12V applied
1
between
P.C. board (WP-008)?
Micro-switch malfunction
(+) and 2 (−)
of CN33 of the main
YES
Micro-switch is stuck
NO
To item Power supply is not turned on
Replace the main P.C. board (WP-008)
Replace micro-switch.
• Conduction check of micro-switch
Push the switch
ON
Tester
ON
Releaes the switch
OFF
Does the indoor fan rotate?
Does the plasma lamp (Blue) or
the filter lamp (Orange) go on?
Does the plasma lamp
go off within 2 seconds after
it was ON, and does the
filter lamp (Orange) go on?
Are the dust collector
Operation checkPrimary check
and ionizer dried?
(Electrode check)
Refer to items, cleaning and check
for the dust collector/ionizer/ionized
wire units.
When the ionized wire is
disconnected or when dirt is
not cleaned even cleaned,
( )
replace each unit.
YES
YES
YES
YES
NO
NO
NO
YES
Is DC-5V to DC-10V
applied between
4 (Brown/Negative voltage)
and 2 (Brown/GND)
of CN33 of the main
P.C. board?
YES
Dry the dust
collector and
ionizer.
Referring to the right figure, check the
high-output voltage of the air filter unit.
(NOTE)
Use an exclusive high voltage tester;
otherwise the tester may be broken.
YES
Is output of the ionizer
approx. 3.9kV to 4.7kV?
Is output of the collector
approx. 2.9kV to 3.7kV?
YES
Are the dust
collector/ionizer/ionized
wire units dirty?
Is an abnormal sound
(cracking noise) heard
from the electrode?
To item Only indoor fan does not operate
Replace the main P.C. board (WP-008).
• How to check output of the air purifier
NO
GND
Be sure not to come to
contact to the silver part
or not to touch the
[ ]
ionized cables.
NO
NO
<Caution on High Voltage!!>
Ionizer
Output
Replace the high-voltage unit.
No trouble
Collector
output
High-voltage tester
– 49 –
FILE NO. SVM-06017
No.ProcedureCheck pointsCauses
5 Press [ ] button once
to start the unit.
• Shorten the time of the restart
delay timer.
• Set the operation mode to COOL.
• Set the fan speed level to AUTO.
• Set the preset temperature much
lower than the room temperature.
(The unit (compressor) operates
continuously in the above
condition.)
1. Check whether or not the
compressor operates.
2. Check whether or not the
OPERATION lamp blinks.
1. The temperature of the indoor
heat exchanger is extremely low.
2. The connection of the heat
exchanger sensor is loose.
(The connector is disconnected.)
(CN01)
3. The heat exchanger sensor and
the P.C. board are defective.
(Refer to Table 9-8-2.)
4. The main P.C. board is defective.
6If the above condition (No. 6) still
continues, start the unit in the
following condition.
• Set the operation mode to COOL.
• Set the preset temperature much
lower than room temperature.
7Connect the motor connector to the
motor and turn on the power supply.
Start the unit in the following
condition.
• Set the operation mode to FAN.
• Set the fan speed level to HIGH.
(The unit (compressor) operates
continuously in the above codition.)
1. Check whether or not the
compressor operates.
2. Check whether or not the
OPERATION lamp blinks.
1. Check it is impossible to detect the
voltage (DC 15 V) between 3 and4 of the motor terminals.
2. The motor does not operate.
(But it is possible to receive the
signal from the remote control.)
3. The motor rotates but vibrates
strongly.
1. The temperature of the indoor
heat exchanger is extremely low.
2. The connector of the heat
exchanger sensor short-circuited.
(CN01)
3. The heat exchanger sensor and
the P.C. board are defective. (Refer
to T ab le 9-8-2.)
4. The main P.C. board is defective.
1. The indoor fan motor is defective.
(Protected operation of P.C. board)
2. The connection of the motor
connector is loose.
3. The P.C. board is defective.
Table 9-8-2 Approximate resistance value of thermo sensor
Temperature0°C10°C20°C25°C30°C
Resistance value 35.8 20.35 12.59 10.0 7.99
(kΩ)
9-8-2. How to Shorten Time of Restart Delay Timer
1 Press [CLR] button while pressing [CHK] button
with a tip of a pencil.
2 Then press [ ] button to transmit the
signal to the indoor unit.
9-8-3. How to use self cleaning function
The self cleaning function is set from a factory.
To cancel this function, should keep press the
temporary switch for 20 secounds till can hear
the long combination sound and repeat the
same procedure when need to set.
2
1
– 50 –
9-9. Troubleshooting for Remote Control
FILE NO. SVM-06017
Is receiver on
indoor unit exposed
to direct sunlight?
YES
NO
Is there any
thyristor fluorescent
light nearby?
YES
YES
NONO
Press [ ]
button.
Is transmission
mark indicated?
Does indoor unit
operate when
moving remote control
near receiver or
indoor unit?
YES
Batteries are
exhausted.
The unit does not beep at all.
OPERATION lamp on
indoor unit is not indicated.
NO
Press RESET button
on remote control
with tip of pencil.
Press [ ]
button.
Avoid direct
sunlight.
Keep indoor unit
away from
thyristor
fluorescent light.
Does indoor unit
NO
start to operate by
automatic restart
function?
YES
Does radio sound
is affected by
remote control when
a signal is transmitted
at distance of 5 cm
from radio?
P.C. board is
defective.
Replace
P.C. board.
YES
NO
NO
Replace
batteries.
Note :After replacing batteries,
press the RESET button
with a tip of a pencil.
– 51 –
Is transmission mark
indicated?
YES
Does indoor unit
beep and operate?
YES
Normal
operation
NO
Remote control
is defective.
Replace
remote control.
FILE NO. SVM-06017
10. PART REPLACEMENT
10-1. Indoor Unit
No.Part nameProceduresRemarks
1Front panel
How to remove the front panel
1) Stop the operation of the air conditioner
and turn off its main power supply.
2) Pull the inlet grille toward you to open it
and remove 4 screws fixing the front panel.
3) Remove upper 3 hooks of the front panel
from the back body.
4) Open the horizontal grille right below by
hand.
5) Pull the lower side of the front panel toward
you until it touches the horizontal grille to
remove it.
How to mount the front panel
1) Mount the front panel with the inverse
procedure of “How to remove the front
panel”.
2) Push 3 places (right, left and center) of the
air outlet.
3) Check the gap between the front panel and
the back body.
If you operate the air conditioner in cooling
or dry operation without pushing the 3
places, the surface of the front panel may
be covered with frost and have dewdrops.
(2)
4-screws
(2)
(2)
(3)
(4)
2Electrical part
assembly
1) Remove the front panel with the procedure 1.
2) Remove the screw fixing the electrical part
box.
3) Remove the drain guide.
4) Remove the connector (5P) for the fan
motor and the connector (6P) for the louver
motor from the microcomputer assembly.
5) Remove the screw for the earth, and pull
the electrical part base toward you to
remove it from the main unit.
6) Pull out the TC sensor from the sensor
holder.
(3) Drain Guide
When assembling the electrical parts
assembly, make the connecting cable
U-shaped and put it in the drain pan.
(5) Screw
(2) Screw
(6) TC sensor
5P
6P
– 52 –
FILE NO. SVM-06017
No.Part nameProceduresRemarks
3Horizontal grille
4Heat exchanger
5Cross flow fan
1) Remove center 2 shafts of the horizontal
grille from the back body.
2) Remove left shaft of the horizontal grille
from the back body.
3) Remove the horizontal grille from the back
body.
1) Remove the front panel, electrical parts
assembly and the horizontal grille with
procedure 2 and 3.
2) Remove the screw on the rear side of the
main unit to remove the pipe holder.
3) Remove 2 screws fixing the heat
exchanger and the bearing base.
4) Remove 2 screws fixing the heat
exchanger fixtures (upper and lower) and
the back body then pull out the upper side
of the heat exchanger slowly.
1) Remove the front panel, electrical parts
assembly, horizontal grille and the heat
exchanger with procedure 4.
2) Loosen the set screw of the cross flow fan.
3) Remove 2 screws fixing the bearing base
and the back body.
4) Pull the cross flow fan toward you.
(1) Center shafts
(2) Left shafts
Pipe holder
(3) 2 screws
(2) Screw
Bearing base
(4) 2 screws
(3) Screws
(2) Set screw
6Bearing base
7Fan motor
1) Remove the front panel, electrical parts
assembly, horizontal grille, heat exchanger
and the cross flow fan with procedure 5.
2) Remove the bearing from the bearing base.
If the housing protrudes from the base
bearing, put the housing in position and
assemble the bearing to the bearing base.
1) Remove the front panel, electrical parts
assembly, horizontal grille, and the heat
exchanger with procedure 4.
2) Loosen the set screw of the cross flow fan.
3) Remove 2 screws of the motor fixture.
4) Remove the lower side of the body (R) and
move it right to remove it.
5) Remove the motor from the motor fixture.
– 53 –
When assembling the cross flow fan, fix it
with the set screw at the position where the
gap between the back body and the right
surface of the cross flow fan is 4 mm.
Bearing base
Bearing
(4)
(3) 2 screws
(4) BODY (R)
Motor fixture
FILE NO. SVM-06017
10-2. Outdoor Unit
No.Part nameProceduresRemarks
1 Common
procedure
1) Stop the operation of the air conditioner and turn off
its main power supply or remove the power supply
cord.
2) Remove the electrical parts cover .
(4 screws ∅4 x 10L)
3) Remove 2 cord clamps (4 screws ∅4 x 22L) and
disconnect the power supply cord and connecting
cable after removing 6 screwson on the terminal
block and 1 ground screw on the electrical parts
base.