Toshiba RAS-18GKHP-ES2, RAS-18GAH-ES2, RAS-18GA-ES2, RAS-24GKHP-ES2, RAS-24GKP-ES2 SERVICE MANUAL

Page 1
SERVICE MANUAL
AIR CONDITIONER
SPLIT WALL TYPE
RAS-24GKHP-ES2 / RAS-24GAH-ES2
RAS-18GKHP-ES2 / RAS-18GAH-ES2
FILE NO. SVM-06020
RAS-24GKP-ES2 / RAS-24GA-ES2 RAS-18GKP-ES2 / RAS-18GA-ES2
May, 2006
Page 2
CONTENTS
1. SPECIFICATIONS
2.
CONSTR
2-1 2-2 2-3
3. WIRING DIAGRAM
3-1 3-2 3-3
3-3
4. SPECIFICATION OF ELECTRICAL PARTS
4-1 Indoor Unit (RAS-24GKHP-ES2, RAS-18GKHP-ES2) 4-2 Outdoor Unit (RAS-24GAH-ES2) 4-3 Outdoor Unit (RAS-18GAH-ES2)
4-4 Indoor Unit (RAS-24GKP-ES2, RAS-18GKP-ES2)
4-5 Outdoor Unit (RAS-24GA-ES2) 4-5 Outdoor Unit (RAS-18GA-ES2)
UCTION VIEWS
Indoor Unit Outdoor Unit Outdoor Unit
RAS-24GKHP-ES2 / RAS-24GAH-ES2 RAS-18GKHP-ES2 / RAS-18GAH-ES2
RAS-24GKP-ES2 / RAS-24GA-ES2 RAS-18GKP-ES2 / RAS-18GA-ES2
(24 Class) (18 Class)
FILE NO. SVM-06020
5. REFRIGERATION CYCLE DIAGRAM
5-1
RAS-24GKHP-ES2 / RAS-24GAH-ES2 RAS-18GKHP-ES2 / RAS-18GAH-ES2
5-2
5-3 RAS-24GKP-ES2 / RAS-24GA-ES2 5-4
RAS-18GKP-ES2 / RAS-18GA-ES2
RAS-B18NKPX / RAS-18N2AX
5-4
6. CONTROL BLOCK DIAGRAM
6-1 RAS-24GKHP-ES2, RAS-18GKHP-ES2 6-2 RAS-24GKP-ES2, RAS-18GKP-ES2
7.
OPERA
7-1 7-2 Description of Operation Circuit 7-3 Hi POWER Mode 7-4 High-Temperature Limit Control 7-5 Low-Temperature Limit Control 7-6 Defrosting Operation 7-7 A 7-8 7-9 Self-Cleaning function 7-10 QUIET Mode 7-11 COMFORT SLEEP mode
TION DESCRIPTION
Outline of Air Conditioner Control
uto Restar t Function
Filter Check Lamp
- 1 -
Page 3
8. INSTALLATION PROCEDURE
8-1 Safety Cautions 8-2 Installation Diagram of Indoor and Outdoor Units 8-3 Installation 8-4 Indoor Unit 8-5 Outdoor Unit 8-6 How to Set Remote Control Selector Switch
8-7 Others
9. TROUBLESHOOTING CHART
9-1 Troubleshooting Procedure 9-2 Basic Check Items 9-3 Primary Judgement 9-4 Self-Diagnosis by Remote Control (Check Code) 9-5 How to Diagnose Faulty Part 9-6 Troubleshooting for Indoor Unit 9-7 Troubleshooting for Wiring (Interconnect cable and Serial Signal 9-8 Troubleshooting for P.C. Board 9-9 Troubleshooting for Remote Control
FILE NO. SVM-06020
Wire)
10. PARTS REPLACEMENT
10-1 Indoor Unit 10-2 Outdoor Unit (RAS-24GAH-ES2, RAS-24GA-ES2) 10-3 Outdoor Unit (RAS-18GAH-ES2, RAS-18GA-ES2)
11. EXPLODED VIEWS AND PARTS LIST
11-1 Indoor Unit (E - Parts Assy) 11-2 Indoor Unit 11-3 Outdoor Unit 11-4 Outdoor Unit (RAS-18GAH-ES2) 11-5 Outdoor Unit (RAS-24GA-ES2) 11-6 Outdoor Unit (RAS-18GA-ES2)
(RAS-24GAH-ES2)
This air conditioner is charged with HFC (R410A) that doesn't deplete the Ozone layer.
This air conditioner requires special installation for the refrigerant R410A.
- 2 -
Page 4

1. SPECIFICATIONS

FILE NO. SVM-06020
MODEL
ITEM
Capacity
Phase 1
Power source V 220 - 240
Power consumption W 2430 2510 2400 2480 2560 2690 1850 1900 1678 1748 1860 1960 Power factor % 98 85 99 88 99 92 98 97 94 92 97 96
Running current A 0.3/ 0.3/
Indoor/Outdoor 11.0 Starting current A Moisture removal lit/h 2.5 2.7 2.0 2.0
Noise
Refrigerant
Refrigerant control Capillary tube
Interconnection Connection type Flare connection pipe Maximum length
INDOOR UNIT RAS-24GKHP-ES2 RAS-24GKP-ES2 RAS-18GKHP-ES2 RAS-18GKP-ES2
Dimensions Width mm 998
Net weight kg 13 Evaporator type Finned tube Indoor fan type Cross flow fan
Air volume Medium fan m3/h 750 800 750 667 708 667
Fan motor output W 30 Air filter Honeycomb woven filter with PP frame OUTDOOR UNIT RAS-24GAH-ES2 RAS-24GA-ES2 RAS-18GAH-ES2 RAS-18GA-ES2
Dimensions Width mm 780 780 780
Net weight kg 56 52 44 39 Condenser type Finned tube Outdoor fan type Propeller fan Airflow volume m3/h 2400 2550 2400 2550 2400 2550 2350 2450 2350 2450 2120 2200 Fan motor output W 42 42
Compressor
Safety device IOL, Td Sensor IOL IOL, Td Sensor IOL Louver type Automatic louver Usable outdoor temperature range °C 15 ~ 43 -10 ~ 24 21 ~ 43 15 ~ 43 -10 ~ 24 21 ~ 43
Note *1 Chargeless pipe
*2 Maximum pipe
Indoor (H/M/L) dB Outdoor (220-240V) dB 56-57 57-58 56-57 52-53 53-54 51-52 Name of refrigerant R410A Rated amount
Gas side size mm ∅12.7 Connection type Flare connection Liquid side size mm ∅6.35
(One way) 25* Maximum height
difference
Height mm 298
Depth mm 220
High fan m3/h 900 900 900 900 900 900
Low fan m3/h 625 667 625 543 584 543
Height mm
Depth mm 290
Model
PA290X3CS-4MU1
Output W 2160 1500
45/43/41/39/37
RAS-24GKHP-ES2 RAS-24GKP-ES2 RAS-18GKHP-ES2 RAS-18GKP-ES2
RAS-24GAH-ES2 RAS-24GA-ES2 RAS-18GAH-ES2 RAS-18GA-ES2
Cooling Heating Cooling Cooling Heating Cooling
220V 240V 220V 240V 220V 240V 220V 240V 220V 240V 220V 240V
kW 6.30 6.30 6.80 6.90 6.80
Hz
220V 240V 220V 240V 220V 240V 220V 240V 220V 240V 220V 240V
0.3/
0.3/
11.23
10.7
54
kg
m
m 8
1.90
0.3/11.75 0.3/12.20
11.45
2
10
715
6.85
54
1.70
PA225X2CS-4KU1
5.00 5.05 5.45
50
0.3/ 0.3/ 0.3/ 0.3/
8.3 7.9 7.8 7.6
1
15*
5.55
5.30
0.3/8.4 0.3/8.2
36
44/42/39/37/35
1.15
2
20*
550
290
5.35
33
1.26
550
290
- 3 -
Page 5
Note : 1
· Capacity is based on the following temperature conditions.
FILE NO. SVM-06020
Condition
Temperature
Indoor unit inlet air temperature
Outdoor unit inlet air temperature
Note : 2
· Charge refrigerant according to the table below.
Refrigerant
*1
No need to charge extra refrigerant
*2 Need to charge
extra refrigerant
RAS-24GKHP-ES2 / RAS-24GAH-ES2
RAS-24GKP-ES2 / RAS-24GA-ES2 RAS-18GKP-ES2 / RAS-18GA-ES2
Over 15m up to 25m (20g/m) Over 15m up to 20m (20g/m)
(DB) 27°C 20°C
(WB) 19°C 15°C
(DB) 35°C 7°C
(WB) 24°C 6°C
15m or less
JIS B8615-1
Cooling Heating
RAS-18GKHP-ES2 / RAS-18GAH-ES2
15m or less
- 4 -
Page 6
2-1. Indoor Unit
FILE NO. SVM-06020

2. CONSTRUCTION VIEWS

75
7
51
Knock out system
Back body Front panel
Grille inlet
298
Air inlet
Air outlet
998
75
56
220
Knock out system
50
50
75
8
Connection pipe (0.39 m) (Flare ∅15.88)
Outline of indoor unit
55 or more
Minimum distance
to ceiling
298
65
100
20
48
998
763.5 450
Installation Plate outline
- 5 -
Drain hose (0.54 m)
Connection pipe (0.49 m) (Flare ∅6.35)
20
10
100
57
Wireless remote control
(For stud bolt ∅6) (For stud bolt 8 -10)
29
41 55 5555
6
40
5
160
18
48
Page 7
2.2 Outdoor Unit (24 Class)
28
600
50 36
R
15
FILE NO. SVM-06020
A
124109
6 hole
321
307
Ø
R
5.5
A Detail Drawing (Back leg)
HANDLE
290
321
Ø
Ø
715
86
25 Drain outlet
FAN-GUARD
436
275
90 600 90 69
2Ø11x14 Hole (For
Ø8-Ø
10 anchor bolt)
B
307
321
Hole
6
Ø
11x14 Hole
Ø
36 50
B Detail Drawing (Front leg)
321 342
R
15
HANDLE
COVER-PV
Z
100 or more
321
100 or more
Z View
600
Air inlet
Air out
let
00 or more
6
Installation dimension
600 or more
4x
54
129
84
11 Long holes(For
Ø
Service port
10 anchor bolt)
Ø8-Ø
Electrical part cover
Liquid side (Flare Ø6.35)
Gas-side (Flare Ø15.88)
- 6 -
Page 8
2.3 Outdoor Unit (18 Class)
28
600
50
36
321
307
A detail Drawing (Back leg)
R5.5
R
Ø
15
6 hole
86
321
Ø
FAN-GUARD
436
Ø
A
25 Drain outlet
109 124
2
-
Ø
11 x 14
(For 8 -
Ø
Ø
Hole
10 anchor bolt)
FILE NO. SVM-06020
307
321
Ø
6 hole
11x14 hole
Ø
B Detail Drawing (Front leg)
36 50
R
15
COVER-PV
Z
290
550
275
321 342
Electrical part cover
Liquid side (Flare 6.35)
Ø
Gas side (Flare 12.7)
Ø
5
4
Service port
Z View
9060090
69
129
84
100 or more
321
100 or more
600
Air intlel
Air outlel
600 or more
Installation dimension
- 7 -
600 or more
4x 11 Long holes(For 8- 10 anchor bolt)
Ø
Ø
Ø
Page 9

3. WIRING DIAGRAM

3-1. RAS-24GKHP-ES2 / RAS-24GAH-ES2
COLOR IDENTIFICATION
BRW : BROWN RED : RED WHI : WHITE YEL : YELLOW BLU : BLUE BLK : BLACK GRY : GRAY
PNK : PINK ORN : ORANGE GRN : GREEN GRN&YEL : GREEN & YELLOW
CN30 CN31
P04BLK
DSA
Varistor
F01
250V6.3A
MAIN P.C. BOARD (WP-003)
Louver motor
BLU
PNK
6
5 223311 5
6
FILE NO. SVM-06020
Infrared rays receive
and Indication parts
BLU
RED
YEL
BRW
ORN
4
CN07
4
BLU
1 2 3 4 65 10
98 1071 2 3
4 65 4 6
5
BLU
BLU
BLU
BLU
5 64
321
CN25
10
9871 2 3
BLU
BLU
BLU
WHI
98
7
CN13
10
8 9
7
+12 VDC
+5 VDC
WP-003
OUTDOOR TERMINAL BLOCK
C
S
R
COMPRESSOR TERMINAL
POWER SUPPLY 220- 240 V ~ 50 Hz
L
BLK
RED
BLK
RED
WHI PNK
COMPRESSOR
i
N
FERRITE CORE
RED
MAGNETIC
CONTACTOR
R
S
1
1
GRN&YEL
T
A1
CN23
2
2
3
3
GRN&YEL
i
CHASSIS
Serial Signal
OUTDOOR UNIT
52C
BLK
A2
W
RED
WHI RED
FAN MOTOR
U
V
CAPACITOR CAPACITOR
S
C
R
GRY
BRW
BLK BLK
RED RED
BLK BLK WHI RED GRY
BLU
YEL
BLU
BLU COIL FOR 4 WAY VALVE
YEL
1
2
1
2
145 C
TEMP FUSE
1
1 2
CN06
3
3
1
1
CN05
3
3
SG01
1
1
3
3
250VAC T6. 3A
5
5
CN01
7
7
9
9
1
CN11
313
11
CN02
33
circuit
TRANSFORMER
BLK BLK
4
3
66554
3
MAIN P.C. BOARD (MCC-890)
TNR R74
F01
TNR R73
RY07
CR11
RY05
CR12
CR13
CN03
1 1
RY06
3
CN07
CN08
DISCHARGE PIPE SENSOR (TD)
BLU
1
1 2 3
3
BLU
BLK
1
1 2 3
3
BLK
HEAT EXCHANGER SENSOR (TE)
- 8 -
Page 10
3-2. RAS-18GKHP-ES2 / RAS-18GAH-ES2
COLOR IDENTIFICATION
BRW : BROWN RED : RED WHI : WHITE YEL : YELLOW BLU : BLUE BLK : BLACK GRY : GRAY
PNK : PINK ORN : ORANGE GRN : GREEN GRN&YEL : GREEN & YELLOW
CN30 CN31
P04BLK
DSA
Varistor
F01
250V6.3A
MAIN P.C. BOARD (WP-003)
Louver motor
BLU
PNK
6
5 223311 5
6
FILE NO. SVM-06020
Infrared rays receive
and Indication parts
BLU
RED
YEL
ORN
BRW
4
CN07
4
BLU
1 2 3 4 65 10
98 1071 2 3
4 65 4 6
5
BLU
BLU
BLU
BLU
5 64
321
CN25
10
9871 2 3
WHI
BLU
BLU
BLU
98
7
CN13
10
8 9
7
+12 VDC
+5 VDC
WP-003
OUTDOOR TERMINAL BLOCK
C
S
R
COMPRESSOR TERMINAL
POWER SUPPLY 220-240 V~ 50 Hz
L
BLK
RED
BLK
RED
WHI PNK
COMPRESSOR
CN23
INDOOR TERMINAL BLOCK
i
N
FERRITE CORE
RED
MAGNETIC
CONTACTOR
R
S
1
1
GRN&YEL
T
A1
2
3
2
3
i
CHASSIS
INDOOR UNIT
OUTDOOR UNIT
GRN&YEL
52C
BLK
A2
W
RED
WHI
D
RE
FAN MOTOR
U
V
CAPACITOR CAPACITOR
S
C
R
Serial Signal
circuit
TRANSFORMER
YEL
BLK
BLK
RED
RED
BLK
BLK
WHI
RED
GRY
BLU
YEL
BLU
BLU COIL FOR 4 WAY VALVE
BLK
GRY
BRW
1
3
1
3
1
3
5
7
9
1
313
11
33
1
2
4
3
1
2
66554
3
145 C
TEMP FUSE
MAIN P.C. BOARD (MCC-890)
1 2
CN06
3
1
CN05
3
1
3
5
CN01
7
9
SG01
F01
250VAC T6. 3A
TNR R74
CN11
CR11
CN02
CR12
CR13
CN03
1 1
BLK
RY07
RY05
3
TNR R73
RY06
CN07
CN08
DISCHARGE PIPE SENSOR (TD)
BLU
1
1 2 3
3
BLU
BLK
1
1
2 3
3
BLK
HEA
T
EXCHANGER SENSOR (TE)
- 9 -
Page 11
3-3. RAS-24GKP-ES2 / RAS-24GA-ES2
COLOR IDENTIFICATION
BLK
CN27
BRW : BROWN RED : RED WHI : WHITE YEL : YELLOW BLU : BLUE BLK : BLACK GRY : GRAY
PNK : PINK ORN : ORANGE GRN : GREEN GRN&YEL : GREEN & YELLOW
P04
6.3A
CN30 CN31
DSA F01
Varistor
250V
Varistor
Louver motor
BLU
PNK
6
5 223311
6
5
FILE NO. SVM-06020
Infrared rays receive
and Indication parts
1 2 3 4 6 10
BLU
BLU
BLU
YEL
RED
BRW
ORN
4
CN07
4
BLU
1 2 3 4 65 10
321
Power supply circuit
Control Fan motor circuit
7
5 98
7
BLU
BLU
7
5 64
7
105 64321
8 9
CN25
BLU
BLU
BLU
WHI
98
CN13
10
8 9
OUTDOOR TERMINAL BLOCK
INDOOR TERMINAL BLOCK
POWER SUPPLY 220 240 V ~ 50 Hz
L
N
BLK
RED
BLK
RED
RED
1
1
BLK BLK
SPARK KILLER
A2 A1
52C
1/L1 2/T1
3/L2 4/T2
6/T35/L3
GRN&YEL
2
2
GRN&YEL
RED
CAPACITOR
3
3
GRY
CHASSIS
RED
WHI PNK
COMPRESSOR
MAIN P.C. BOARD (WP-003)
INDOOR UNIT
OUTDOOR UNIT
CAPACITOR
S
C
R
WHI RED
FAN MOTOR
BLK
C
S
COMPRESSOR TERMINAL
2
1
21
1
GRY
BRW
YEL
1
2
6
4
3
1
2
6
554
3
145 C
TEMP FUSE
BLK2BLK
Thermo. sensor
(TA)
CN03
Heat exchanger sensor
(TC)
CN01
2
1
BLK
BLK
BLK
R
MAGNETIC CONTACTOR
- 10 -
Page 12
3-4. RAS-18GKP-ES2 / RAS-184GA-ES2
COLOR IDENTIFICATION
BRW : BROWN RED : RED WHI : WHITE YEL : YELLOW
BLK
GRN&YEL
BLU : BLUE BLK : BLACK GRY : GRAY PNK : PINK ORN : ORANGE GRN : GREEN GRN&YEL : GREEN & YELLOW
P04
CN30 CN31
CN27
6.3A
Varistor
DSA F01
250V
MAIN P.C. BOARD (WP-003)
Varistor
Louver motor
BLU
YEL
PNK
6
5 223311
4
6
5
4
FILE NO. SVM-06020
Infrared rays receive
and Indication parts
5 98
1 2 3 4 6 10
BLU
BLU
BLU
BLU
BLU
RED
BRW
ORN
CN07
Power supply
circuit
Control Fan motor circuit
GRY
BRW
YEL
BLU
1 2 3 4 65 10
5 64
321
105 64321
8 9
7 7
BLU
7 7
8 9
CN25
BLU
BLU
WHI
98
CN13
10
2
1
21
1
BLK2BLK
CN03
CN01
2
1
BLK
BLK
OUTDOOR TERMINAL BLOCK
POWER SUPPLY 220 240 V ~ 50 Hz
L
BLK
MAGNETIC
CONTACTOR
BLK
RED
INDOOR
TERMINAL
BLOCK
N
RED
R
U
1
1
GRN&YEL
S
V
2
2
RED
SPARK KILLER
T
W
BLK
1
2
4
3
1
2
66554
3
145 C
TEMP FUSE
GRN&YEL
GRY
INDOOR UNIT
OUTDOOR UNIT
3
3
BLK
CHASSIS
(or A)
A1
(or B)
A2
Thermo. sensor
(TA)
Heat exchanger sensor
(TC)
CAPACITOR
RED
S
WHI PNK
R
COMPRESSOR
S
COMPRESSOR TERMINAL
CAPACITOR
RED
C
BLK
WHI
RED
BLK
FAN MOTOR
C
R
- 11 -
Page 13
FILE NO. SVM-06020

4. SPECIFICATION OF ELECTRICAL PARTS

4-1. Indoor Unit (RAS-24GKHP-ES2, RAS-18GKHP-ES2)
No. Parts name Type Specifications
1 Fan motor (for indoor) AFS-220-31-4A AC 200 240V, 31W 2 Thermo sensor (TA-sensor) ——— 10 k at 25°C 3 Micro Power Module (M01) µRM1260V DC 390 V, Secondary DC 12 V 4 Microcontroller TMP87CM40AN 5 Heat exchanger sensor
(TC-sensor) 6 Line filter (L01) LC*SS11V-06270 27mH, 600mA 7 Diode (DB01) D3SBA60 4 A, 600 V 8 Capacitor (C63) EKMH401VSN470MP20S 4.7µF, 400 V 9 Fuse (F01) BET6.3A T6.3 A, 250 V
10 Varistor (R21, R22) TND15G561K 560 V
11 Resistor (R319) RF-2TK5R6 5.6 , 2 W 12 Louver motor 35BYJ46 Output (Rated) 2 W, 10 poles, 1 phase,
——— 10 k at 25°C
DC 12 V
4-2. Outdoor Unit (RAS-24GAH-ES2)
No. Parts name Type Specifications
Output (Rated) 2200W, 2poles, 1 phase, 220 − 240V, 50Hz
1 Compressor PA290X3CS-4MU1 Winding resistance (Ω) Red-Black White-Black
(at 20°C) 1.13 2.10 Output (Rated) 42W, 4poles, 1 phase, 220 – 240V, 50Hz
2 Fan motor (for outdoor) FG-240-42A-1 Winding resistance (Ω) Red-Black White-Black
(at 20°C) 128 126
Running capacitor 3
(for fan motor)
Running capacitor 4
(for compressor)
Solenoid coil 5
(for 4-way valve) 6 Thermo sensor TE / TD 10k at 25°C / 50k at 25°C 7 Magnetic contactor CLK-35J 220 ~ 240V, 50Hz 8 Transformer TT-05 220 ~ 240V 9 Microcontroller TMP47C840N
10 Varistor (R73, R74) 15G471K 470V 11 Fuse (F01) TSCR T6.3A, 250V
451305L AC 450V, 3.0µF
RS44B506U0218S AC 440V, 50µF
VHV (STF) AC 220 ~ 240V
- 12 -
Page 14
FILE NO. SVM-06020
4-3. Outdoor Unit (RAS-18GAH-ES2)
No. Parts name Type Specifications
Output (Rated) 1500W, 2poles, 1 phase, 220 − 240V, 50Hz
1 Compressor PA225X2CS-4KU1 Winding resistance (Ω) Red-Black White-Black
(at 20°C) 1.54 2.48 Output (Rated) 42W, 4poles, 1 phase, 220 – 240V, 50Hz
2 Fan motor (for outdoor) FG-240-42A-1 Winding resistance (Ω) Red-Black White-Black
(at 20°C) 128 126
Running capacitor 3
(for fan motor)
Running capacitor 4
(for compressor)
Solenoid coil 5
(for 4-way valve) 6 Thermo sensor TE / TD 10k at 25°C / 50k at 25°C 7 Magnetic contactor CLK-26J 220 − 240V, 50Hz 8 Transformer TT-05 220 − 240V 9 Microcomputer TMP47C840N
10 Varistor (R73, R74) 15G471K 470V 11 Fuse (F01) TSCR T6.3A, 250V
451305L AC 450V, 3.0 µF
RS44B506U0218S AC 440V, 50µF
VHV (STF) AC 220 − 240V
4-4. Indoor Unit (RAS-24GKP-ES2, RAS-18GKP-ES2)
No. Parts name Type Specifications
1 Fan motor (for indoor) AFS-220-31-4A AC 200 240V, 31W 2 Thermo sensor (TA-sensor) ——— 10 k at 25°C 3 Micro Power Module (M01) µRM1260V DC 390 V, Secondary DC 12 V 4 Microcontroller TMP87CM40AN 5 Heat exchanger sensor
(TC-sensor) 6 Line filter (L01) LC*SS11V-06270 27mH, 600mA 7 Diode (DB01) D3SBA60 4 A, 600 V 8 Capacitor (C63) KMH400VSSN47M22S 4.7µF, 400 V 9 Fuse (F01) BET6.3A T6.3 A, 250 V
10 Varistor (R21, R22) TND15G561K 560 V
11 Resistor (R319) RF-2TK5R6 5.6, 2 W 12 Louver motor
13 Relay : (RY04) G5NB-1A Coil DC 12V, 16.7mA, Contact AC 250V, 1A
35BYJ46 Output (Rated) 2 W, 10 poles, 1 phase,
——— 10 k at 25°C
DC 12 V
- 13 -
Page 15
FILE NO. SVM-06020
4-5. Outdoor Unit (RAS-24GA-ES2)
No. Parts name Type Specifications
Output (Rated) 2200W, 2poles, 1 phase, 220 − 240V, 50Hz
1 Compressor PA290X3CS-4MU1 Winding resistance (Ω  ) Red-Black White-Black
(at 20°C) 1.13 2.10 Output (Rated) 42W, 4poles, 1 phase, 220 − 240V, 50Hz
2 Fan motor (for outdoor) FG-240-42A Winding resistance (Ω) Red-Black White-Black
(at 20° C) 128 126
Running capacitor
3
(for fan motor) Running capacitor
4
(for compressor)
5
Magnetic contactor
CLK-35J
451305L AC 450V, 3.0µ F
RS44B506U0218S
AC 440V, 50µ F
220 240V, 50Hz
4-6. Outdoor Unit (RAS-18GA-ES2)
No. Parts name Type Specifications
Output (Rated) 1500W, 2poles, 1 phase, 220 − 240V, 50Hz
1 Compressor PA225X2CS-4KU1 Winding resistance (Ω) Red-Black White-Black
(at 20°C ) 1.54 2.48
Output (Rated) 42W, 6poles, 1 phase, 220 240V, 50Hz
2 Fan motor (for outdoor) WLF-240-42A-1 Winding resistance (Ω) Red-Black White-Black
(at 20°C) 188 289
Running capacitor
3
(for fan motor) Running capacitor
4
(for compressor)
5
Magnetic contactor
451205L AC 450V, 2.0µF
RS44B506U0218S AC 440V, 50µF
CLK-26J
220 240V, 50Hz
- 14 -
Page 16

5. REFRIGERATION CYCLE DIAGRAM

5-1. RAS-24GKHP-ES2 / RAS-24GAH-ES2
FILE NO. SVM-06020
0.39m (Connecting pipe)
12.7
O.D.:12.7mm
Cooling
Heating
Tank
Indoor unit
Cooling
Heating
P
Packed valve
(
12.7)
Gas container connection (Reinstall etc.)
Heating
4-way valve
Cooling
Compressor
PA290X3CS-4MU1
Heat exchanger
Cross flow fan
T1
Packed valve
(
6.35)
Main
2.0x1500
s
0.
49m
(Connecting pipe)
6.35
O.D.:6.35mm
Condenser
Cooling Heating
Propeller fan
Outdoor unit
Mark(
Refrigerant R410A 1.
)means check points of Gas Leak.
90 kg
Ambient temp.
50Hz
Standard
pressure
(MPaG)
P
Surface temp. of heat
exchanger interchanging
pipe
T1
(°C)
Fan speed
(indoor)
conditions DB/WB
(°C)
Indoor Outdoor
Standard 3.0 48.2 High 20/– 7/6
Heating Overload*1 3.93 56.4 Low 27/– 24/18
Low temperature 2.17 38.4 High 20/– –10/–10 Standard 3.03 8.7 High 27/19 35/24
Cooling Overload 4.02 12.1 High 32/23 43/26
Low temperature 2.1 0.3 Low 21/15 21/15
Note :
Measure the heat exchanger temperature at the center of U-bend. (By means of TC sensor)
*1 During heating overload operation, a value for the high temperature limit control operation is included.
- 15 -
Page 17
5-2. RAS-18GKHP-ES2 / RAS-18GAH-ES2
FILE NO. SVM-06020
0.39m (Connecting pipe)
12.7
O.D.:12.7mm
Cooling
Heating
Indoor unit
Cooling
Heating
P
Packed valve
(
Heating
4-way valve
Cooling
Compressor
12.7)
PA225X2CS-4KU1
Accumulator
Evaporator
Cross flow fan
T1
Packed valve
6.35)
(
Capillary tube
2.0x1200
s
0.49m (Connecting pipe)
6.35
O.D.:6.35mm
Condenser
Cooling Heating
Propeller fan Outdoor unit
Mark(
Refrigerant R410A 1.
)means check points of Gas Leak.
15 kg
Ambient temp.
50Hz
Standard
pressure
(MPaG)
P
Surface temp. of heat
exchanger interchanging
pipe
T1
(°C)
Fan speed
(indoor)
conditions DB/WB
(°C)
Indoor Outdoor
Standard 2.6 44.7 High 20/– 7/6
Heating Overload*1 3.0 ~ 3.6 49.0 ~ 56.0 Low 27/– 24/18
Low temperature 2.0 32.0 High 20/––10/–10 Standard 0.9 9.5 High 27/19 35/24
Cooling Overload 1.1 12.6 High 32/23 43/26
Low temperature 0.7 2.4 Low 21/15 21/15
Note :
Measure the heat exchanger temperature at the center of U-bend. (By means of TC sensor)
*1 During heating overload operation, a value for the high temperature limit control operation is included.
- 16 -
Page 18
5-3. RAS-24GKP-ES2 / RAS-24GA-ES2
FILE NO. SVM-06020
0.39m (Connecting pipe)
12.7
O.D.:12.7mm
Cooling
Compressor
Indoor unit
Cooling
P
Packed valve
(
12.7)
Gas container connection (Reinstall etc.)
Accumulator
PA290X3CS-4MU1
Heat exchanger
Cross flow fan
T1
Packed valve
6.35)
(
Capillary tube
2.0x900
s
0.49m (Connecting pipe)
6.35
O.D.:6.35mm
Condenser
Refrigerant R410A 1.70kg
)means check points of Gas Leak.
Cooling
Propeller fan Outdoor unit
Mark(
Ambient temp.
50Hz
Standard
pressure
(MPaG)
P
Surface temp. of heat
exchanger interchanging
pipe
T1
(° C)
Fan speed
(indoor)
conditions DB/WB
(° C)
Indoor Outdoor
Standard 3.183 7.0 High 27/19 35/24
Cooling Overload 4.040 11.7 High 32/23 43/26
Low temperature 1.651 -0.4 Low 21/15 21/15
Note :
Measure the heat exchanger temperature at the center of U-bend. (By means of TC sensor)
- 17 -
Page 19
5-4. RAS-18GKP-ES2 / RAS-18GA-ES2
FILE NO. SVM-06020
0.39m (Connecting pipe)
12.7
O.D.:12.7mm
Cooling
Compressor
Indoor unit
Cooling
P
Packed valve
(
12.7)
PA225X2CS-4KU1
Evaporator
Cross flow fan
T1
Packed valve
6.35)
(
Capillary tube
1.7x400
s
0.49m (Connecting pipe)
6.35
O.D.:6.35mm
Condenser
Cooling
Propeller fan Outdoor unit
Mark(
Refrigerant R410A 1.
)means check points of Gas Leak.
26 kg
Ambient temp.
50Hz
Standard
pressure
(MPaG)
P
Surface temp. of heat
exchanger interchanging
pipe
T1
(°C)
Fan speed
(indoor)
conditions DB/WB
(°C)
Indoor Outdoor
Standard 1.1 10.0 High 27/19 35/24
Cooling Overload 1.2 13.0 High 32/23 43/26
Low temperature 0.6 2.0 Low 21/15 21/15
Note :
Measure the heat exchanger temperature at the center of U-bend. (By means of TC sensor)
- 18 -
Page 20

6. CONTROL BLOCK DIAGRAM

6-1. RAS-24GKHP-ES2, RAS-18GKHP-ES2
Indoor Unit Control Panel
Heat Exchanger Sensor
Functions
Louver Control
FILE NO. SVM-06020
M.C.U.
Operation
Display
Temperature Sensor
Infrared Rays Signal Receiver
Infrared
Rays
Remote
Control
From Outdoor Unit
220 ~ 240 V AC 50 Hz
Initiallizing Circuit
Clock Frequency
Oscillator Circuit
Power Supply
Circuit
Noise Filter
3-minute Delay at Restart for Compressor
Motor Revolution Control
Processing
(Temperature Processing)
Timer
Serial Signal Communication
Louver ON/OFF Signal
Louver Driver
Serial Signal Transmitter/Receiver
Serial Signal Communication
Timer
Display
Filter Sign
Display
PRE DEF.
Sign Display
Hi Power
Sign Display
Indoor
Fan Motor
Louver Motor
REMOTE CONTROL
Infrared Rays
Remote Control
Operation ( )Operation ( )
Operation Mode Selection
AUTO, COOL, DRY, HEAT, FAN ONLY
Temperature Setting Fan Speed Selection
ON TIMER Setting
OFF TIMER Setting
Louver Auto Swing
Louver Direction Setting
ECO
Hi power
TIMER 1.3.5.9H
COMFORT SLEEP
QUIET
- 19 -
Page 21
6-2. RAS-24GKP-ES2, RAS-18GKP-ES2
Indoor Unit Control Panel
Heat Exchanger Sensor
Functions  Louver Control
FILE NO. SVM-06020
M.C.U.
Operation
Display
Temperature Sensor
Infrared Rays Signal Receiver
Infrared
Rays
Remote
Control
From Outdoor Unit
220 ~ 240V AC 50Hz
Initiallizing Circuit
Clock Frequency Oscillator Circuit
Power Supply
Circuit
Noise Filter
 3-minute Delay at Restart for Compressor
 Motor Revolution Control
 Processing
(Temperature Processing)
 Timer
Outdoor unit
ON/OFF Signal
Relay Driver
Relay RY04
Outdoor Unit
Louver ON/OFF Signal
Louver Driver
Timer
Display
Filter Sign
Display
Fan Only
Sign Display
Hi Power
Sign Display
Indoor
Fan Motor
Louver Motor
REMOTE CONTROL
Infrared Rays
Remote Control
Operation ( )Operation ( )
Operation Mode Selection
AUTO, COOL, DRY, FAN ONLY
Temperature Setting Fan Speed Selection
ON TIMER Setting
OFF TIMER Setting
Louver Auto Swing
Louver Direction Setting
ECO
Hi power
TIMER 1.3.5.9H
COMFORT SLEEP
QUIET
- 36 -
Page 22

7. OPERATION DESCRIPTION

7-1.Outline of Air Conditioner Control
This is a fixed capacity type air conditioner, which uses a AC motor for an indoor fan. The AC motor drive circuit is mounted in the indoor unit. And electrical parts which operate the compressor and the outdoor fan motor, are mounted in the outdoor unit. The air conditioner is mainly controlled by the indoor unit controller. The controller operates the indoor fan motor based upon commands transmitted by the remote control and transfers the operation commands to the outdoor unit controller. The outdoor unit controller receives operation commands from the indoor unit, and operates the outdoor fan motor and the compressor.
(1) Role of indoor unit controller
The indoor unit controller receives the operation commands from the remote control and executes them.
· Temperature measurement at the air inlet of the indoor heat exchanger by the indoor temperature sensor
· Temperature setting of the indoor heat exchanger by the heat exchanger sensor
· Louver motor control
· Indoor fan motor operation control
· LED display control
· T ransferring of operation commands to the
outdoor unit
· Receiving of information of the operation status and judging of the information or indication of error
(2) Role of outdoor unit controller
The outdoor unit controller receives the operation commands from the indoor controller and executes them.
FILE NO. SVM-06020
· Compressor operation
control
· Operation control of outdoor fan motorf Turning off the compressor and outdoor fan
· when the outdoor unit receives the shutdown command
· Defrost control in heating operation (Temperature measurement by the outdoor heat exchanger and control for the four-way valve and the outdoor fan motor) *Heat pump Model only
7-1-1. Louver contr
ol
(1) Vertical air flow louver
Position of veritcal air flow louver is automatically controlled according to the operation mode. Besides, position of vertical air flow louver can be arbitrarily set by pressing [FIX] button. The louver position which is set by [FIX] button is stored in the microcomputer, and the louver is automatically set at the stored position for the next operation.
(2) Swing
If [SWING] button is pressed when the indoor unit is in operation, the vertical air flow louver starts swinging. When [FIX] button is pressed, it stops swinging.
7-1-2. Indoor fan control (AC Fan motor)
(1) The indoor fan is operated by the stepless speed
change AC motor
.
(2) For air flow level, speed of the indoor fan motor is
controlled in five steps (LOW, LOW and HIGH). If AUTO mode is selected, the fan motor speed is automatically controlled by the difference between the preset temperature and
the room temperature.
Operations according to the commands from the indoor unit
+
, MED, MED
+
Table 7-1-1
FAN TAP
OPERATION MODE
RAS-24GKHP Series
RAS-18GKH Series
Model
RAS-24GKP Series
RAS-18GKP Series
Cooling Heat Fan Only Dry
rpm Air Flow volume(m /h) rpm Air Flow volume(m /h) rpm Air Flow volume(m /h) rpm
Air Flow volume(m /h)
3
3
3
3
900
1300
900
UH H
H M+ M
13001300
900
1300
900
1300
900
M+
M+ M
1250 1200
830
1150
750
1250
830
1150
750
M L+
MUH H
1150 1050 1000 900 800 700
790
750
1100
1050
667
708
1150
750
1050
667
Note : Under some function of setting. The fan motor is controlled automatically.
Then LOW+ = LOW + MED and MED
2
+
= MED + HIGH
2
- 20 -
L L- UL SUL/SL-
380 600
300
700 380 600
300
SUL/SL-
600 300 500
220
L L­L L-
625 900 543
1000
625
900 543
UL
UL SUL
461
543
700
800
380
461
800
900
461
543
700
800
380
461
L-LL+ L+ L+
667 950 584
1050
667 950
584
Page 23
FILE NO. SVM-06020
7-2. Description of Operation Circuit
(1) When turning on the breaker, the operation lamp
blinks. This means that the power is on (or the power supply is cut off.)
(2) When pressing [ ] button on the
remote control, receiving beep sounds from the indoor unit, and the next operation is performed together with opening the vertical air flow louver.
(3) Once the operation mode is set, it is memorized in
the microcomputer so that the previous operation can be effected thereafter simply by pressing [ ] button.
7-2-1. Fan only operation
([MODE] button on the remote control is set to the fan only operation.)
(1) When [FAN] button is set to AUTO, the indoor fan
motor operates as shown in Fig. 7-2-1. When [FAN] button is set to LOW, LOW HIGH, the motor operates with a constant air flow.
+
, MED, MED+ or
7-2-2. Cooling operation
([MODE] button on the remote control is set to the cooling operation.)
(1) The compressor, 4-way valve, outdoor fan and
operation display lamp are controlled as shown in Fig. 7-2-2.
ON
4-way valve
Compressor
Outdoor fan
(Heat pump model)
Preset temp.
0.5
ON
OFF OFF OFF ON
0
Fig. 7-2-2
display lamp
OPERATION
+3 +2.5
(Preset temp.)
-
+2 +1.5 +1 +0.5
(Room temp.)
Preset temp.
0
(Preset temp.: 24°C)
NOTE : *1: The values marked with *1 are calculated and
controlled by the difference in motor speed between M+ and L-.
(2)
The Hi Power, ECO and COMFORT SLEEP operation cannot be set.
Fig. 7-2-1 Setting of air flow [FAN:AUTO]
M+
*1 *1
*1
(2) When [FAN] button is set to AUTO, the indoor fan
motor operates as shown in Fig. 7-2-3. When [FAN] button is set to LOW, LOW
+
, MED, MED+ or
HIGH, the motor operates with a constant air flow.
(Preset temp.)
-
(Room temp.)
Preset temp.
+3 +2.5 +2 +1.5 +1 +0.5
0
-0.5
M+
*1 *1 *1
NOTE : *1: The values marked with *1 are calculated and
controlled by the difference in motor speed between M+ and L-.
Fig. 7-2-3 Setting of air flow [FAN:AUTO]
- 21 -
Page 24
FILE NO. SVM-06020
7-2-3. Dry operation
([MODE] button on the remote control is set to the dry operation.)
(1) The compressor, 4-way valve, outdoor fan and
operation display lamp are controlled as shown in Fig. 7-2-4.
ON:6min.
OFF:4min.
ON:5min.
OFF:5min.
OFF
4-way valve
Outdoor fan
Preset temp.
+3
+2
+1
ON:6min.
OFF:4min.
OFF
ON:5min.
OFF:5min.
OFF
0
Compressor
Fig. 7-2-4
ON
display lamp
OPERATION
7-2-4. Heating operation *Heat pump model only
([MODE] button on the remote control is set to the heating operation.)
(1) The compressor, 4-way valve, outdoor fan and
operation display lamp are controlled as shown in Fig. 7-2-6.
Preset temp.
OFF
ON
ON
Compressor
ON
OFF
ON
4-way valve
Outdoor fan
OPERATION
Fig. 7-2-6
display lamp
(2) The microprocessor turns the compressor on and
off at the regular intervals (4 to 6 minutes). While the compressor is turning off, the indoor fan motor operates in the SUPER LOW position. The pattern of operation depending on the relation between room temperature and preset temperatures is shown in Fig. 7-2-5.
Room temp.
Preset temp.+1
Preset temp.
Compressor
Outdoor fan
Indoor fan
ON ON ON ON
OFF OFF OFF
L. *S.L. S.L.L. L. S.L. L.
*Super Low
Fig. 7-2-5
(3) [FAN] button on the remote control is set to AUTO
only.
(2) When [FAN] button is set to AUTO, the indoor fan
motor operates as shown in Fig. 7-2-7. When [FAN] button is set to LOW, LOW
+
, MED, MED+ or
HIGH, the motor operates with a constant air flow.
Preset temp.
0
-0.5
-1
-1.5
-2
-5.0
-5.5
[FAN AUTO]
L
*1 *2
+
M
H
*1, *2 : The values marked with *1 and *2 are
calculated and controlled by the difference in motor speed between M+ and L.
Fig. 7-2-7 Setting of air flo w [FAN:AUTO]
(4) The ECO and Hi Power operations can not be set.
- 22 -
Page 25
FILE NO. SVM-06020
(3) The indoor heat exchanger restricts revolving
speed of the fan motor to prevent a cold draft. The upper limit of the revolving speed is shown in Fig. 7-2-8 and Table 7-2-1.
Manual (One of
AUTO
*4
SUL* SUL*1
Stop
5 speed)
L-H (Up to setting
3
speed)
*2
A+4 A+4
464534
33
33 21 32 20
A-8 A-8
*6 *5
NOTES :
*1: The fan stops for 2 minutes after thermostat-OFF. *2: A is 24°C when the preset temperature is 24°C or
more and A is the preset temperature when it is
under 24°C. *3: SUL means Super Ultra Low. *4: Calculated from difference in motor speed
between SUL and HIGH.
7-2-5. Automatic operation
([MODE] button on the remote control is set to the automatic operation.)
(1) One of 3 operations (Cooling, Fan only or Heating)
is selected according to difference between the preset temperature and the room temperature at which the automatic operation has started, as shown in Fig. 7-2-9. The Fan only operation continues until the room temperature reaches a level at which another mode is selected.
(2) Temporary Auto
When the TEMPORARY button on the indoor unit is pushed, the preset temperature is fixed at 24°C and the indoor unit is controlled as shown in Fig. 7-2-9.
C
Cooling operation
The louver moves to the position same as Hi POWER operation.
+4
Cooling operation
0
Fan only operation
Fig. 7-2-8 Cold draft preventing control
*5 and *6:
Table 7-2-1
Fan *5 *6 speed Starting period Stabilized period
AUTO Up until 12 minutes
passed after starting the unit
From 12 to 25 minutes passed after starting the unit and room temperature is 3°C lower than preset temperature
Manual Room temperature (L - H) < Preset temperature
From 12 to 25 minutes passed after starting the unit and room temperature is between preset temperature and 3°C lower than preset temperature
25 minutes or more passed after starting the unit
Room temperature
Preset temperature
-4°C
-3.5°C
Heating operation
(Room temp.) - (Preset temp.)
RAS-24GKHP-ES2 RAS-18GKHP-ES2
RAS-24GKP-ES2 RAS-18GKP-ES2
Fig. 7-2-9
- 23 -
Page 26
FILE NO. SVM-06020
62
55 54
Compressor
Outdoor fan
OFF
OFF
ON
ON
OFF
ON
Heat exchanger temp.
7-3.Hi POWER Mode
([Hi POWER] button on the remote control is pressed.)
When [Hi POWER] button is pressed while the indoor unit is in Auto, Cooling or Heating operation, Hi POWER mark is indicated on the display of the remote control and the unit operates as follows.
(1) Automatic operation
· The indoor unit operates in according to the current operation.
(2) Cooling operation
· The preset temperature drops 3°C. (The value of the preset temperature on the remote control does not change.)
·
 If the room temperature is higher than the
setting temperature by 3.5 °C or more, the
horizontal louver moves to the Hi POWER position automatically. Then when the room
temperature is °C less than the setting temperature the horizontal louver returns
automatically.
·
 FAN speed : [AUTO]
If the temperature is higher than the setting temperature by 3.5°C or mor, the air conditioner operates at maxim airflow
level. If the temperature is higher than the
setting temperature by less than 3.5°C, the air conditioner operates at normal airflow level.
·
 FAN speed : One of 5 levels
If the temperature is higher than the
setting temperature by 3.5°C or more, the air conditioner operates at higher consecutive airflow level. If the room temperature is higher
than the setting temperature by less than 3.5°C, the air conditioner operates at normal airflow level.
7-4.High-Temperature Limit Control
*Heat pump model only
The microcontroller detects the indoor heat exchanger temperature to prevent pressure of a refrigerating cycle from increasing excessively. The compressor and outdoor fan motor are controlled as shown in Fig. 7-4-1.
Fig. 7-4-1
7-5.Low-Temperature Limit Control
The microcontroller detects the indoor heat exchanger temperature to prevent the indoor heat exchanger from freezing.
· The compressor and outdoor fan motor are controlled as shown in Fig. 7-5-1.
Heat exchanger temperature
6
2
Compressor Outdoor fan
ON
Less than continues
for 5 minutes
OFF
Fig. 7-5-1
7-6.Defrost Operation *Heat pump model only
(3) Heating operation (UKH Series only)
·
 The preset temperature increases 2°C,
(The value of the preset temperature on the remote control does not change.)
 The indoor unit operates in normal heating
·
mode except the preset temperature is higher (+2°C).
(4) The Hi POWER mode can not be set in Dry or
Fan only operation.
When the indoor unit is in heating operation, if the refrigerant evaporation temperature detected by the outdoor heat exchanger sensor is under the specified temperature, the outdoor unit starts the defrosting operation. At this time, the 4-way valve relay and the outdoor fan motor are turned off. The indoor fan motor is also turned off by the cold draft preventing control of the indoor microcomputer. Then, [PRE. DEF.] lamp on the indoor unit comes on. The defrosting operation stops and the 4-way valve relay, outdoor fan motor and the indoor fan motor are turned on automatically when the refrigerant evaporation increases to the specified temperature, or when the defrosting time is over 12 minutes.
- 24 -
Page 27
FILE NO. SVM-06020
7-6-1. Defrost starting condition
A-Zone : If -10°C > Teo ≥ − 18°C, defrost will
start when. Teo - Te 2.5°C at teat 20 sec or
~ 30 min after operation.
B-Zone : If Te ≤ −18°C, defrost start instantaneously
(Suddenly) 00 ~ 25 min ofter operation
C-Zone : If -2ºC Teo ≥ −10°C defrost will start when
Teo - Te ≤ −3°C at least 20 sec or ~ 60 min after operation.
7-6-2. Defrost finish condition.
1) If Te 3°C at least 60 sec -->4 way value on.
2) If Te 8°C --> 4 way value on.
Timing
Operation time (4 Loops = Tt)
Td1
Td2
Td3 Td4
Finish time recordStart time record
Defrost time rate : (Td/Tt) x 100 Heating time rate : (Tt - Td) x Tt
Fig. 7-6-2
- 25 -
Page 28
FILE NO. SVM-06020
7-7. Auto Restart Function
The indoor unit is equipped with an automatic restarting function which allows the unit to restart operating with the set operating conditions in the event of power supply being accidentally shut down. The operation will resume without warning three minutes after power is restored. This function is not set to work when shipped from the factory. Therefore it is necessary to set it to work.
7-7-1. How to set auto restart function
To set the auto restart function, proceed as follows: The power supply to the unit must be on; the function will not set if the power is off. Push the [TEMPORARY] button located in the center of the front panel continuously for three seconds. The unit receives the signal and beeps three times. The unit then restarts operating automatically in the event of power supply being accidentally shut down.
When the unit is on standby (Not operating)
Operation Motions
Push [TEMPORARY] button for more The unit is on standby. than three seconds.
The unit starts to operate. The green lamp is on.
→ →
After approx. three seconds,
The unit beeps three times The lamp changes from and continues to operate. green to orange.
If the unit is not required to operate at this time, push [TEMPORARY]
TEMPORARY button
TEMPORARY button
0
0
3S
3S
button once more or use the remote control to turn it off.
When the unit is in operation
Operation Motions
Push [TEMPORARY] button for more The unit is in operation. The green lamp is on. than three seconds.
The unit stops operating. The green lamp is turned off.
→ →
After approx. three seconds,
0
TEMPORARY button
TEMPORARY button
0
3S
3S
The unit beeps three times.
If the unit is required to operate at this time, push [TEMPORARY] button once more or use the remote control to turn it on.
While this function is being set, if the unit is in
operation, the orange lamp is on.
This function can not be set if the timer operation
While the filter check lamp is on, the
[TEMPORARY] button has the function of filter reset button.
has been selected.
When the unit is turned on by this function, the
louver will not swing even though it was swinging automatically before shutting down.
- 26 -
Page 29
7-7-2. How to cancel auto restart function
To cancel auto restart function, proceed as follows: Repeat the setting prodedure: the unit receives the signal and beeps three times. The unit will be required to be turned on with the remote control after the main power supply is turned off.
When the unit is on standby (Not operating)
Operation Motions
Push [TEMPORARY] button for more The unit is on standby. than three seconds.
FILE NO. SVM-06020
The unit starts to operate. The orange lamp is on.
After approx. three seconds,
The unit beeps three times The lamp changes from and continues to operate. orange to green.
If the unit is not required to operate at this time, push [TEMPORARY]
TEMPORARY button
TEMPORARY button
0
0
3S
3S
button once more or use the remote control to turn it off.
When the unit is in operation
Operation Motions
Push [TEMPORARY] button for more The unit is in operation. The orange lamp is on. than three seconds.
The unit stops operating. The orange lamp is turned off.
→ →
After approx. three seconds,
0
0
3S
3S
TEMPORARY button
TEMPORARY button
While this function is being set, if the unit is in
The unit beeps three times.
If the unit is required to operate at this time, push [TEMPORARY] button once more or use the remote control to turn it on.
7-8. Filter Check Lamp
operation, the orange lamp is on.
When the elapsed time reaches 1000 hours, the filter
7-7-3. Power failure during timer operation
check lamp indicates. After cleaning the filters, turn off the filter check lamp.
When the unit is in Timer operation, if it is turned off because of power failure, the timer operation is
7-8-1. How to turn off filter check lamp
cancelled. Therefore, set the timer operation again.
Press [FILTER] button on the remote control. OR push [TEMPORARY] button on the indoor unit.
Note:
If [TEMPORARY] button is pushed while the filter check lamp is not indicating, the indoor unit will start the Automatic Operation.
- 27 -
Page 30
y
y
g
g
play
g
(
(
y
p
g
)
y
g Op
g
g
p
g
g
y
g
(
(
y
g
g
)
y
g
g
g
p
FILE NO. SVM-06020
7-9. Self-Cleaning function.
Self-Cleaning function is designed to reduce humidity that causes mold to form inside the air conditioning unit. This advanced, efficient s fan activates and dries the moisture in the coil for 20 minutes, then turns off automaticall
stem reduces moisture in the coil. When you turn off your air conditioner, the internal
.
Operation display
FCU fan
FCU louver OPEN CLOSE CLOSE
Timer display
Compressor
CDU fan
rpm is depend on preseting. rpm is SUL speed.
depend on preseting of timer function. depend on preseting of timer function.
depend on preseting per room temperature.
depend on preseting per room temperature.
Cool mode or dry mode Self-Cleaning mode
operation more than 10 mins. operate 20 mins.
ON OFF OFF
ON ON
ON or OFF
ON or OFF
ON or OFF
Turn off by remote controller
or timer-off function.
ON
OFF OFF
OFF OFF
Automatically turn-off.
ON or OFF
The Self-Cleaning function is set as default at ex-factory.
Self-Cleaning operation can stop manually by press [ ] botton of the remote control two more time.
7-9-1. How to cancel Self-Cleanin
To cancel the Self-Cleanin
Press [TEMPORARY] button one time or use remote control to
function, proceed as follows:
function
turn on air conditioner. The OPERATION dis oran
e color (When AUTO-RESTART is ON) or green color
When AUTO-RESTART is OFF).
Hold down the [TEMPORARY] button for more than 20 seconds.
The air conditioner will stop suddenl
when the [TEMPORARY] is
ressed but keep holding it continue. Then will beep 3 times in
the first 3 seconds but it is not related to Self-Cleanin
After holding about 20 seconds, the air conditioner will beep 5
times without an
The Self-Cleanin
blinking of display.
eration had been concelled.
OFF
Operation time
will show in
function
TE MPO R AR Y buttonTE MPO R AR Y button
Remarks
Per settin
of Self-Cleaning function above, AUTO-RESTART
function had been cancelled. To set AUTO-RESTART a
lease follow item 7-7-1.
7-9-2. How to set Self-Cleanin
To set the Self-Cleanin
Press [TEMPORARY] button one time or use remote control to
function, proceed as follows.
turn on air conditioner. The OPERATION displa
e color (When AUTO-RESTART is ON) or green color
oran
function.
will show in
When AUTO-RESTART is OFF).
Hold down the [TEMPORARY] button for more than 20 seconds.
The air conditioner will stop suddenl
pressed but keep holdin
it continue. Then will beep 3 times is
the first 3 seconds but it is not related to Self-Cleanin After holding about 20 seconds, the air conditioner will beep
5 times and OPERATION displa
The Self-Cleanin
function had been set.
when the [TEMPORARY] is
function
blinks 5 times.
Remarks
Per settin
of Self-Cleaning function above, AUTO-RESTART
function had been cancelled. To set AUTO-RESTART a
lease follow item 7-7-1.
- 28 -
ain,
ain,
Page 31
FILE NO. SVM-06020
7-10. QUIET Mode
Quiet mode is the system which, control the revolving speed of indoor fan to work constantly
at lower than speed L. In addition, noise level of indoor unit is less than usual.
When the [QUIET] button is pressed, the fan of the indoor unit will be restricted the revolving speed at
speed L
again (cancel Quiet mode).
Remarks :
1. Quiet mode is unable to work in dry mode.
2. Quiet mode is appropriate to work with less
-
until the [QUIET] button is pressed once
cooling load and less heating load condition. Because of the fan speed L- may cause not
enough the cooling capacity or heating capacity.
7-11. COMFORT SLEEP mode
The principles of comfort sleep mode are:
Quietness for more comfortable.
Save energy by changing room temperature
automatically.
The air condition can shut down by itself
automatically.
7-11-1. Cooling mode
The fan speed of indoor unit operates automatically,
it relates with the compressor's operation.
Compressor’s Operation Fan Speed
-
ON L
OFF SL
The preset temperature will increase 1°C after the
Comfort sleep mode has operated for 1 hour and the temperature will increase another 1°C after the comfort sleep mode has operated for 2 hour. (The value of the preset temperature on the remote control
does not change.)
Press the [COMFORT SLEEP] button to choose the
operating hours. Repeat pressing to select the hours. (1hr, 3hr, 5hr or 9hr)
If the [COMFORT SLEEP] button is pressed again
means cancel comfort sleep mode.
7-11-2. Heating mode
The fan speed of indoor unit operates automatically,
it relates with the compressor's operation.
Compressor’s Operation Fan Speed
ON L
OFF SL
-
Remarks:
1. Comfort sleep mode will not operate in dry mode
and fan only mode.
2. Comfort sleep mode is appropriate to work with less
cooling load and less heating load condition.
Because of the fan speed L- may cause not enough the cooling capacity or heating capacity.
The preset temperature will drop down 1°C after the
comfort sleep mode has operated for 1 hour and the temperature will decrease another 1°C after the comfort sleep mode has operated for 2 hour. (The
value of the preset temperature on the remote control. dose not change.)
Press the [COMFORT SLEEP] button to choose the
operating hours. Repeat pressing to select the hours. (1hr, 3hr, 5hr or 9 hr)
If the [COMFORT SLEEP] button is pressed again
means cancel comfort sleep mode.
- 29 -
Page 32
FILE NO. SVM-06020
8-3-3. Installation/Servicing tools <Changes in the product and components>
In the case of an air conditioner using R410A, in order to prevent any other refrigerant from being charged accidentally, the service port diameter of the outdoor unit control valve (3 way valve) has been changed. (1/2 UNF 20 threads per inch)
In order to increase the pressure withstand strength of the refrigerant piping, flare processing diameter and size of opposite side of flare nuts have been changed. (for copper pipes with nominal dimensions 1/2 and 5/8)
New tools for R410A
New tools for R410A Applicable to R22 model Changes
Gauge manifold As pressure is high, it is impossible to measure by
means of conventional gauge. In order to prevent any other refrigerant from being charged, each port diameter has been changed.
Charge hose In order to increase pressure withstand strength,
hose materials and port size have been changed (to 1/2 UNF 20 threads per inch). When purchasing a charge hose, be sure to confirm the port size.
Electronic balance As pressure is high and gasification speed is fast, for refrigerant charging it is difficult to read the indicated value by means
of a charging cylinder, as air bubbles occur.
Torque wrench The size of opposing side of flare nuts have been (nominal dia. 1/2, 5/8) increased.
Incidentally, a common wrench is used for nominal diameters 1/4 and 3/8.
Flare tool By increasing the clamp bar’s receiving hole, (clutch type) strength of spring in the tool has been improved.
Gauge for projection Used when flare is made by using conventional flare adjustment tool.
Vacuum pump adapter Connected to conventional vacuum pump. It is
Gas leakage detector Exclusive for HFC refrigerant.
necessary to use an adapter to prevent vacuum pump oil from flowing back to the charge hose. The charge hose connecting part has two ports­one for conventional refrigerant (7/16 UNF 20 threads per inch) and one for R410A. If the vacuum pump oil (mineral) mixes with R410A, a sludge may occur and damage the equipment.
Incidentally, the “refrigerant cylinder” comes with the refrigerant designation (R410A) and protector coating in
the U. S’s ARI specified rose color (ARI color code: PMS 507).
Also, the “charge port and packing for refrigerant cylinder” require 1/2 UNF 20 threads per inch
corresponding to the charge hose’s port size.
- 35 -
Page 33

8. INSTALLATION PROCEDURE

8-1. Safety Cautions
For general public use
Power supply cord of Outdoor unit shall be more than 4 mm sheathed flexible cord) or 3.5 mm2 (AWG-12).
FILE NO. SVM-06020
2
(H07RN-F or 245 IEC66 : polychloroprene
CAUTION
THIS AIR CONDITIONER USES THE NEW HFC REFRGERANT (R410A), WHICH DOES NOT DESTROY THE OZONE LAYER.
R410A refrigerant is apt to be affected by impurity such as water, oxidizing membranes, and oils because the pressure of R410A refrigerant is approx. 1.6 times of refrigerant R22. As well as the adoption of this new refrigerant, refrigerating machine oil has also been changed. Therefore, during installation work, be sure that water, dust, former refrigerant, or refrigerating machine oil does not enter into the refrigerating cycle of a new-refrigerant air conditioner. To avoid mixing refrigerant and refrigerating machine oil, the sizes of charging port connecting sections on the main unit are different from those for the conventional refrigerant, and different size tools are also required. Accordingly, special tools are required for the new refrigerant (R410A) as shown below. For connecting pipes, use new and clean piping materials with high-pressure withstand capabilities, designed for R410A only, and ensure that water or dust does not enter. Moreover, do not use any existing piping as its pressure withstand may be insufficient, and may contain impurities.
CAUTION
This appliance must be connected to the main power supply by means of a circuit breaker or a switch with a contact separation of at least 3 mm. If this is not possible, a power supply plug with earth must be used. This plug must be easily accessible after installation. The pl appliance completely from the mains.
New Refrigerant Air conditioner Installation
To Disconnect the Appliance from the Main Power Supply.
ug must be disconnected from the power supply socket in order to disconnect the
- 30 -
Page 34
FILE NO. SVM-06020
DANGER
FOR USE BY QUALIFIED PERSONS ONLY.
TURN OFF MAIN POWER SUPPLY BEFORE ATTEMPTING ANY ELECTRICAL WORK. MAKE SURE
ALL POWER SWITCHES ARE OFF. FAILURE TO DO SO MAY CAUSE ELECTRIC SHOCK.
CONNECT THE CONNECTING CABLE CORRECTLY. IF THE CONNECTING CABLE IS CONNECTED
WRONGLY, ELECTRIC PARTS MAY BE DAMAGED.
CHECK THE EARTH WIRE THAT IT IS NOT BROKEN OR DISCONNECTED BEFORE INSTALLATION.
DO NOT INSTALL NEAR CONCENTRATIONS OF COMBUSTIBLE GAS OR GAS VAPORS.
FAILURE TO FOLLOW THIS INSTRUCTION CAN RESULT IN FIRE OR EXPLOSION.
TO PREVENT OVERHEATING THE INDOOR UNIT AND CAUSING A FIRE HAZARD, PLACE THE UNIT
WELL AWAY (MORE THAN 2 M) FROM HEAT SOURCES SUCH AS RADIATORS, HEATORS, FURNACE, STOVES, ETC.
WHEN MOVING THE AIR-CONDITIONER FOR INSTALLING IT IN ANOTHER PLACE AGAIN, BE VERY
CAREFUL NOT TO GET THE SPECIFIED REFRIGERANT (R410A) WITH ANY OTHER GASEOUS BODY INTO THE REFRIGERATION CYCLE. IF AIR OR ANY OTHER GAS IS MIXED IN THE REFRIGERANT, THE GAS PRESSURE IN THE REFRIGERATION CYCLE BECOMES ABNORMALLY HIGH AND IT RESULTINGLY CAUSES BURST OF THE PIPE AND INJURIES ON PERSONS.
IN THE EVENT THAT THE REFRIGERANT GAS LEAKS OUT OF THE PIPE DURING THE
INSTALLATION WORK, IMMEDIATELY LET FRESH AIR INTO THE ROOM. IF THE REFRIGERANT GAS IS HEATED BY FIRE OR SOMETHING ELSE, IT CAUSES GENERATION OF POISONOUS GAS.
WARNING
Never modify this unit by removing any of the safety guards or bypassing any of the safety interlock
switches.
Do not install in a place which cannot bear the weight of the unit.
Personal injury and property damage can result if the unit falls.
Before doing the electrical work, attach an approved plug to the power supply cord.
Also, make sure the equipment is properly earthed.
Appliance shall be installed in accordance with national wiring regulations.
If you detect any damage, do not install the unit. Contact your TOSHIBA dealer immediately.
CAUTION
Exposure of unit to water or other moisture before installation could result in electric shock.
Do not store it in a wet basement or expose to rain or water.
After unpacking the unit, examine it carefully for possible damage.
Do not install in a place that can increase the vibration of the unit. Do not install in a place that can amplify
the noise level of the unit or where noise and discharged air might disturb neighbors.
To avoid personal injury, be careful when handling parts with sharp edges.
Please read this installation manual carefully before installing the unit. It contains further important instruc-
tions for proper installation.
REQUIREMENT OF REPORT TO THE LOCAL POWER SUPPLIER
Please make absolutely sure that the installation of this appliance is reported to the local power supplier before installation. If you experience any problems, or if the installation is not accepted by the supplier, the service agency will take adequate countermeasures.
Remark per EMC Directive 89/336/EEC
To prevent flicker impressions during the start of the compressor (technical process) following installation conditions do apply.
1. The power connection for the air conditioner has to be done at the main power distribution. This distribution has to be of an impedance. Normally the required impedance is reached at a 32A fusing point. Air conditioner fuse has to be 16A max.!
2. No other equipment should be connected to this power line.
3. For detailed installation acceptance, please contact your power supplier whether its restriction does apply for products like washing machines, air conditioners or electrical ovens.
4. For power details of the air conditioner, refer to the rating plate of the product.
- 31 -
Page 35
FILE NO. SVM-06020
8-2. Installation Diagram of Indoor and Outdoor Units
Hook
65 mm or more
(Atta
c
h to th
e f
r
on
t panel) (A
ttac
6 Bio enzyme & Gingko filter 5 Sasa Zeolite Vitamin C filter
170 mm
or more
A
h to
ir
filter
the air filter)
1 Installation
plate
170 mm
or more
Shield
pipe
For the rear left and left piping
Wall
Insert the cushion between the indoor unit and wall, and lift the indoor unit for better operation.
Do not allow the drain hose to get slack.
Cut the piping hole sloped slightly
Make sure to run the drain hose sloped downward.
Before installing the wireless remote control
With the remote control cover open, load the batteries supplied correctly, observing their polarity.
2 Wireless remote control
Cover
3 Batteries
1
0
0
m
m
o
r
m
o
r
e
600 mm or more
8 Pan head wood screw
The auxiliary piping can be connected the left, rear left, rear, right or bottom.
Right
4 Remote control holder
Rear
Bottom
Rear
left
Left
2 Wireless remote control
Insulate the refrigerant pipes separately with insulation, not together.
Vinyl tape Apply after carrying out a drainage test.
Saddle
Extension
e
r
Extension drain hose
(Not available,
e
provided by installer)
mor
or
m
m
100
1
0
0
m
m
o
r
m
o
r
e
o
or m
m
m
0
10
600 mm or more
drain hose
(Not available, provided by installer)
6 mm thick heat resisting polyethylene foam
ore
m
or
m
m
0
0
6
600
m
m
or
m
o
r
e
18 Class 24 Class
ore
or m
m
m
0
0
6
6
0
0
m
m
o
r
m
o
r
e
- 32 -
Page 36
8-3. Installation
8-3-1. Optional installation parts
FILE NO. SVM-06020
Part
Code
Parts name
Refrigerant piping Liquid side :
A
Gas side : Pipe insulating material
B
(polyethylene foam, 6 mm thick)
C
Putty, PVC tapes
6.35 mm
12.7 mm
<Fixing bolt arrangement of outdoor unit>
124 mm109 mm
321 mm
28 mm
86 mm
Air outlet
25
Æ
600 mm
Air inlet
Q'ty
One
each
1
One
each
116 mm
90 mm
Drain outlet
Fig. 8-3-1.
Secure the outdoor unit with fixing bolts and nuts if the unit is likely to be exposed to a strong wind.
Use 
8 mm or ∅ 10 mm anchor bolts and nuts.
If it is necessary to drain the defrost water, attach drain nipple 10 to the bottom plate of the outdoor unit
before installing it.
- 33 -
Page 37
8-3-2. Accessory and installation parts
FILE NO. SVM-06020
Part
No.
Part name (Q'ty)
1
Installation plate x 1
2
Wireless remote control x 1
3
Battery x 2
Others
Owner’s manual
Installation manual
Name
Part
No.
Part name (Q'ty)
4
Remote control holder x 1
5
Sasa Zeolite Vitamin C filter x 2
6
Bio enzyme & Gingko filter x 2
Part
No.
Part name (Q'ty)
7
Mounting screw 4 x 25 x 8
l
8
Pan head wood screw 3.1 x 16 x 2
l
9
Drain nipple* x 1
10
Cap water proof* x 2
(For Heat pump model only)
The part marked with asterisk (*) is packaged with the outdoor unit.
(For Heat pump model only)
- 34 -
Page 38
FILE NO. SVM-06020
8-4. Indoor Unit
8-4-1. Installation place
A place which provides the spaces around the
indoor unit (See Fug 8-2).
A place where there is no obstacle near the air inlet
and outlet.
A place that allows easy installation of the piping to
the outdoor unit.
A place which allows the front panel to be opened.
CAUTION
Direct sunlight to the indoor unit’s wireless
receiver should be avoided.
The microprocessor in the indoor unit should not
be too close to RF noise sources. (For details, see the owner’s manual.)
<Remote control>
A place where there are no obstacles such as a
curtain that may block the signal from the indoor unit.
Do not install the remote control in a place exposed
to direct sunlight or close to a heating source, such as a stove.
Keep the remote control at least 1 m apart from the
nearest TV set or stereo equipment. (This is necessary to prevent image disturbances or noise interference.)
The location of the remote control should be
determined as shown below.
8-4-2. Cutting a hole and mounting installation
plate
<Cutting a hole>
When installing the refrigerant pipes from the rear.
Pipe hole
65 mm
The center of the pipe hole is above the arrow.
100 mm
Fig. 8-4-2
1. After determining the pipe hole position on the
mounting plate (A), drill the pipe hole (65 mm) at a slight downward slant to the outdoor side.
NOTE
When drilling a wall that contains a metal lath, wire
lath or metal plate, be sure to use a pipe hole brim ring sold separately.
<Mounting the installation plate>
ndoor unit
I
(Side view)
7 m
°
5
7
Reception range
Remote control
(Top view)
Indoor unit
Reception range
* : Axial distance
Fig. 8-4-1
5 m
5 m
55
Hook
45
°
45
°
Remote control
* 7 m
170
120
Pipe hole
Indoor unit
Hook
Thread
Weight
Hook
Pipe hole
7 Mounting screw
65
1
Installation plate
Fig. 8-4-3
- 37 -
Page 39
FILE NO. SVM-06020
<When the installation plate is directly mounted on the wall>
1. Securely fit the installation plate onto the wall by
screwing it in the upper and lower parts to hook up the indoor unit.
2. To mount the installation plate on a concrete wall with anchor bolts, utilize the anchor bolt holes as illustrated in the above figure.
3. Install the installation plate horizontally in the wall.
CAUTION
When installing the installation plate with a mounting screw, do not use the anchor bolt hole. Otherwise the unit may fall down and result in personal injury and property damage.
Installation plate <Keep horizontal direction>
Anchor bolt
Projection
5 mm dia. hole
15 mm or less
8-4-3. Electrical work
1. The supply voltage must be the same as the rated
voltage of the air conditioner.
2. Prepare the power source for exclusive use with the
air conditioner.
NOTE
2
Wire type : More than 1.5 mm
245 IEC66) or 1.3 mm
(H07RN-F or
2
(AWG-16)
CAUTION
This appliance can be connected to the mains in
the following way. Connection to fixed wiring: A switch or circuit breaker which disconnects all poles and has a contact separation of at least 3 mm must be incorporate in the fixed wiring. An approved circuit breaker or switches must used.
NOTE
Perform wiring works so as to allow a generous
wiring capacity.
7 Mounting
screw
ss
4 x 25
s
ss
Clip anchor (local parts)
Fig. 8-4-4
CAUTION
Failure to firmly install the unit may result in personal injury and property damage if the unit falls.
In case of block, brick, concrete or similar type walls, make 5 mm dia. holes in the wall.
Insert clip anchors for appropriate mounting screws
7 .
NOTE
Secure four corners and lower parts of the installation plate with 6 to 7 mounting screws to install it.
- 38 -
Page 40
FILE NO. SVM-06020
8-4-4. Wiring connection
Air inlet grille
Terminal cover
Screw
2
1
Terminal block
Cord clamp
Screw
Front panel
Earth line
CAUTION
Be sure to refer to the wiring system diagram
labeled inside the front panel.
Check local electrical cords and also any specific
wiring instructions or limitations.
Connecting cable
about 15 cm
Fig. 8-4-6
<Stripping length of connecting cable>
10
10
40
50
Connecting cable
Fig. 8-4-5
<How to connect the connecting cable> Wiring of the connecting cable can be carried out
without removing of the front panel.
1. Remove the air inlet grille. Open the air inlet grille upward and pull it toward you.
2. Remove the terminal cover and cord clamp.
3. Insert the connecting cable (according to local cords) into pipe hole on the wall.
4. Take out the connecting cable through the cable slot on the rear panel so that it protrudes about 15 cm from the front.
5. Insert the connecting cable fully into the terminal block and secure it tightly with screws.
6. Tightening torque : 1.2 N·m (0.12 kgf·m).
7. Secure the connecting cable with the cord clamp.
8. Fix the terminal cover, rear plate bushing and air inlet grille on the indoor unit.
Earth line
Fig. 8-4-7
NOTE
Use stranded wire only.
Wire type : More than 1.5 mm 2 (H07RN-F or
245 IEC66) or 1.3 mm
2
(AWG-16)
Fig. 8-4-8
NOTE
Connect the earth line to the metallic part (i mark) located at the side of 3P terminal.
<How to install the air inlet grille on the indoor unit>
When attaching the air inlet grille, the contrary of
the removed operation is performed.
Fig. 8-4-9
- 39 -
Page 41
FILE NO. SVM-06020
8-4-5. Piping and Drain Hose Installation <In case of rightward piping>
After scribing slits of the body-right by a knife or a making-off pin, cut them by a pair of nippers or the like.
Slit (Body-right)
Fig. 8-4-10
<In case of downward piping>
After scribing slits of the body-right by a knife or a making-off pin, cut them by a pair of nippers or the like.
To connect the pipe after installation of the unit (figure)
(To the forefront of flare)
400 mm
300 mm
R 30 mm (Use polisin (polyethylene) core or the like for bending pipe.)
43 mm
80
Liquid side
Gas side
Outward form of indoor unit
Use the handle of screwdriver, etc.
Fig. 8-4-12
NOTE
If the pipe is bent incorrectly, the indoor unit may unstably be set on the wall. After passing the connecting pipe through the pipe hole, connect the connecting pipe to the auxiliary pipes and wrap the facing tape around them.
Slit (Body-right)
Fig. 8-4-11
<Left-hand connection with piping>
Bend the connecting pipe so that it is laid within 43 mm above the wall surface. If the connecting pipe is laid exceeding 43 mm above the wall surface, the indoor unit may unstably be set on the wall. When bending the connecting pipe, make sure to use a spring bender so as not to crush the pipe.
Bend the connection pipe within a radius of 30 mm.
CAUTION
Bind the auxiliary pipes (two) and connecting
cable with facing tape tightly. In case of leftward piping and rear-leftward piping, bind the auxiliary pipes (two) only with facing tape.
Indoor unit
Auxiliary pipes
Installation plate
Carefully arrange pipes so that any pipe does not
stick out of the rear plate of the indoor unit.
Carefully connect the auxiliary pipes and
connecting pipes to each other and cut off the insulating tape wound on the connecting pipe to avoid double-taping at the joint, moreover, seal the joint with the vinyl tape, etc.
Since dewing results in a machine trouble, make
sure to insulate both the connecting pipes. (Use polyethylene foam as insulating material.)
When bending a pipe, carefully do it not to crush
it.
Connecting cable
Drain hose
- 40 -
Page 42
FILE NO. SVM-06020
8-4-6. Indoor unit fixing
1. Pass the pipe through the hole in the wall, and hook the indoor unit on the installation plate at the upper hooks.
2. Swing the indoor unit to right and left to confirm that it is firmly hooked up on the installation plate.
3. While pressing the indoor unit onto the wall, hook it at the lower part on the installation plate. Pull the indoor unit toward you to confirm that it is firmly hooked up on the installation plate.
1
2
Hook
Hook here
1 Installation
plate
Fig. 8-4-13
For detaching the indoor unit from the installation plate, pull the indoor unit toward you while
pressing
its bottom up at the specified parts.
8-4-7. Drainage
1. Run the drain hose sloped downwards.
NOTE
Hole should be made at a slight downward slant on
the outdoor side.
Do not form the Do not rise the drain hose.
50 mm or more
Do not put the drain hose end into water.
drain hose into
a wavy shape.
Do not put the drain hose end in the drainage ditch.
Fig. 8-4-15
2. Put water in the drain pan and make sure that the
water is drained out of doors.
3. When connecting extension drain hose, insulate the
connecting part of extension drain hose with shield pipe.
PressPress
Fig. 8-4-14
Press
(unhook)
Shield pipe
Drain hose
Inside the room
Extension drain hose
Fig. 8-4-16
CAUTION
Arrange the drain pipe for proper drainage from the unit. Improper drainage can result in dew-dropping.
This air conditioner has the structure designed to drain water collected from dew, which forms on the back of the indoor unit, to the drain pan. Therefore, do not store the power cord and other parts at a height above the drain guide.
Wall
Drain guide
Space for pipes
- 41 -
Fig. 8-4-17
Page 43
8-5. Outdoor Unit
8-5-1. Installation place
A place which provides the spaces around the
outdoor unit as shown in the installation diagram
of indoor and outdoor unit.
A place which can bear the weight of the outdoor
unit and does not allow an increase in noise level and vibration.
A place where the operation noise and discharged
air do not disturb your neighbors.
A place which is not exposed to a strong wind.
A place free of a leakage of combustible gases.
A place which does not block a passage.
When the outdoor unit is to be installed in an
elevated position, be sure to secure its feet.
An allowable length of the connecting pipe is up 15 m. (Refer to the table of TO CHARGE REFRIGERANT for detail.)
An allowable height level is up to 8 m.
A place where the drain water does not raise any
problem.
FILE NO. SVM-06020
8-5-2. Refrigerant piping connection
1. Cut the pipe with a pipe cutter.
90°
Obliquity
Fig. 8-5-2
2. Insert a flare nut into the pipe, and flare the pipe.
Projection margin in flaring : A (Unit : mm)
Die
Pipe
Fig. 8-5-3
Rigid (Clutch type)
Roughness Warp
A
CAUTION
1. Install the outdoor unit without anything blocking
the air discharging.
2. When the outdoor unit is installed in a place
exposed always exposed to strong wind like a coast or on a high storey of a building, secure the normal fan operation using a duct or a wind shield.
3. In particularly windy areas, install the unit such
as to avoid admission of wind.
4. Installation in the following places may result in
trouble. Do not install the unit in such places.
A place full of machine oil.
A saline-place such as the coast.
A place full of sulfide gas.
A place where high-frequency waves are likely
to be generated as from audio equipment, welders, and medical equipment.
Strong
wind
Fig. 8-5-1
Outer dia. R410A Conventional
of copper pipe tool used tool used
6.35 0 to 0.5 1.0 to 1.5
12.70 0 to 0.5 1.0 to 1.5
Imperial (wing nut type, conventional tool)
Outer dia.
of copper pipe
R410A
6.35 1.5 to 2.0
12.70 2.0 to 2.5
<Tightening connection>
Align the centers of the connecting pipes and tighten the flare nut as far as possible with your fingers. Then tighten the nut with a spanner and torque wrench as shown in the figure.
CAUTION
Do not apply excess torque.
Otherwise, the nut may crack depending on the
conditions.
- 42 -
Page 44
FILE NO. SVM-06020
(Unit : N·m)
Outer dia.
of copper pipe
Tightening torque
6.35 mm 16 to 18 (1.6 to 1.8 kgf·m)9.52 mm 30 to 42 (3.0 to 4.2 kgf·m)
12.70 mm 50 to 62 (5.0 to 6.2 kgf·m)
Tightening torque of flare pipe connections
The operating pressure of R410A is higher than that of R22. (Approx. 1.6 times). It is therefore necessary to firmly tighten the flare pipe connecting sections (which connect the indoor and outdoor units) up to the specified tightening torque. Incorrect connections may cause not only a gas leakage, but also damage to the refrigerant cycle.
Flare at indoor unit side
Flare at outdoor unit side
Fig. 8-5-4
Flare nutHalf union
Externally threaded side
Use a wrench to secure.
Use a torque wrench to tighten.
Internally threaded side
Fig. 8-5-5
8-5-3. Evacuating
After the piping has been connected to the indoor unit, you can perform the air purge together at once.
AIR PURGE
Evacuate the air in the connecting pipes and in the indoor unit using a vacuum pump. Do not use the refrigerant in the outdoor unit. For details, see the manual of the vacuum pump.
<Using a vacuum pump>
Be sure to use a vacuum pump with counter-flow prevention function so that inside oil of the pump does not flow backward into pipes of the air conditioner when the pump stops. (If oil inside of the vacuum pump enters into the air conditioner, which use R410A, refrigeration cycle trouble may result.)
1. Connect the charge hose from the manifold valve to
the service port of the gas side packed valve.
2. Connect the charge hose to the port of the vacuum
pump.
3. Open fully the low pressure side handle of the
gauge manifold valve.
4. Operate the vacuum pump to start evacuating.
Perform evacuating for about 15 minutes if the piping length is 20 meters. (15 minutes for 20 meters) (assuming a pump capacity of 27 liters per minute. Then confirm that the compound pressure gauge reading is –101 kPa (–76 cmHg).
5. Close the low pressure side valve handle of gauge
manifold.
6. Open fully the valve stem of the packed valves
(both side of Gas and Liquid).
7. Remove the charging hose from the service port.
8. Securely tighten the caps on the packed valves.
CAUTION
KEEP IMPORTANT 4 POINTS FOR PIPING WORK
(1) Take away dust and moisture (Inside of the
connecting pipes.)
(2) Tight connection (between pipes and unit) (3) Evacuate the air in the connecting pipes using
VACUUM PUMP.
(4) Check gas leak (connected points)
- 43 -
Compound pressure gauge
–101 kPa (–76 cmHg)
Handle Lo
Charge hose (For R410A only)
Connecting pipe
Packed valve at liquid side
Pressure gauge
Manifold valve
Handle Hi (Keep full closed)
Charge hose (For R410A only)
Vacuum pump adapter for counter-flow prevention (For R410A only)
Vacuum
pump
Packed valve at gas side
Service port (Valve core (Setting pin))
Fig. 8-5-6
Page 45
FILE NO. SVM-06020
TO CHARGE REFRIGERANT
Refrigerant
No need to charge refrigerant
Need to charge Over 15 m up to Over 15 m up to refrigerant 25 m (20g/m) 20 m (20g/m)
24 Class
15 m or less 15 m or less
18 Class
<Packed valve handling precautions>
Open the valve stem all the way out; but do not try to open it beyond the stopper.
Securely tighten the valve stem cap with torque in the following table:
Gas side 50 to 62 N·m (∅12.70 mm) (5.0 to 6.2 kgf·m)
Liquid side 16 to 18 N·m (∅6.35 mm) (1.6 to 1.8 kgf·m)
Service port
9 to 10 N·m (0.9 to 1.0 kgf·m)
Hexagonal wrench is required.
4 mm
8-5-4. Wiring connection
1. Remove the valve cover from the outdoor unit.
2. Connect the connecting cable to the terminal as
identified with their respective matched numbers on the terminal block of indoor and outdoor unit.
3. When connecting the connecting cable to the
outdoor unit terminal, make a loop as shown in the
installation diagram of indoor and outdoor unit, to
prevent water coming in the outdoor unit.
4. Insulate the unused cords (conductors) from any
water coming in the outdoor unit. Proceed them so that they do not touch any electrical or metal parts.
<Stripping length of connecting cable>
Terminal block
LN 1 32
Terminal screw
Cord clamp
Power supply cord
10
60
N
L
10
70
70
Earth line
Screw
Cord clamp
Connecting cable
123
10
10
80
Fig. 8-5-7
Earth line
Power supply cord
Connecting cable
Fig. 8-5-8
Model
Power source 50 Hz, 220 240 V Single phase Maximum running current 18A 16A Plug socket & fuse rating
Power cord
24 Class
20A 20A
2
(H07R N-F or 245 IE C 66)
4 mm or 3.5 mm2 (AWG -12)
CAUTION
Wrong wiring connection may cause some
electrical parts burn out.
Be sure to comply with local codes on running
the wire from indoor unit to outdoor unit (size of wire and wiring method etc).
Every wire must be connected firmly.
NOTE: Connecting cable
Wire type: More than 1.5 mm
245 IEC66) or 1.3 mm
- 44 -
2
(H07RN-F or
2 (AWG-16)
18 Class
Page 46
FILE NO. SVM-06020
8-6. How to Set Remote Control Selector
Switch
When two indoor units as installed in seperated rooms, there is no need to change the selector switch.
<Remote control selector switch>
When two indoor units are installed in the same room or the adjacent two rooms, they may be controlled simultaneously with a single remote control. To prevent this, set either unit and its remote control to B setting. (Both units are set to A setting before shipment.)
The remote control signal is not recived when the indoor unit setting is different from the remote control one.
1. Set the remote control selectors witch with the indoor unit.
1) Turn the circuit breaker of the main power switch off before setting the selector switch.
2) Remove the Air inlet grille and Front panel. (Refer to Chapter 10-1, procedure 1 )
3) Open the Electrical part cover (Refer to chapter 10-1, procedure 2 ), then cut the jumper (J90) with only the nippers.
2. Set the remote control selector switch with the remote control
[B] is indicated on the liquid crystal display when setting remote control selector switch to B. [A] is not indicated on the display even if the selector switch is set to A.
1) Load the remote control with the batteries.
2) Press the [CHECK] button using something with sharp point. (The preset temperature on the remote control changes to [00].)
3) Press the [MODE] button while pressing the [CHECK] button, [B] is indicted at the right of the present temperature display.
To reset the switch to the [A] setting, press the [MODE] button again while pressing the [CHECK] button.
CAUTION
Do not use any other sharp tools (such as cutters, pliers, or the like). Such tools
may cause breakage or damage.
See Fig. 8-6-1
Fig. 8-6-1
[MODE] button
[CHK] button
Fig. 8-6-2
3. Confirm that the indoor unit can operate with the new setting.
- 45 -
Page 47
FILE NO. SVM-06020
8-7. Others
8-7-1. Gas leak test
Flare nut connections (Indoor unit)
Flare nut connections (Outdoor unit)
B
A
Valve stem cap connection
Service port cap connection
Valve stem cap connection
Fig. 8-7-1
Check the flare nut connections, valve stem cap
connections and service port cap connections for gas leak with a leak detector or soap water.
8-7-2. Test operation
8-7-3. Auto restart setting
This product is designed so that, after a power failure, it can restart automatically in the same operating mode as before the power failure.
Information
The product was shipped with Auto Restart function in the off position. Turn it on as required.
<How to set the auto restart>
Press and hold the TEMPORARY button for about 3 seconds. After 3 seconds, the electronic beeper makes three short beeps to tell you the Auto Restart has been selected.
To cancel the Auto Restart, follow the steps described in the section Auto Restart Function of the Owner’s Manual.
To switch the TEST RUN (COOL) mode, press TEMPORARY button for 10 sec. (The beeper will make a shaort beep.)
TE MPO R AR Y button
Fig. 8-7-2
- 46 -
Page 48

9. TROUBLESHOOTING CHART

FILE NO. SVM-06020
9-1. T r oub leshooting Pr ocedure :
9-2-2. Incorrect cable connection between Indoor
and outdoor units
Follow the details of 9-2. Basic Check Items. If there is no trouble corresponding to 9-2, check whether or not there are faulty parts following
9-4. Self-Diagnosis by Remote Control.
9-2. Basic Check Items
The indoor unit is connected to the outdoor unit with 4 cables. Check that the indoor and outdoor units have been properly connected with terminals assigned the same numbers. If the connectors are not properly connected, the outdoor unit will not operate normally, or OPERATION lamp and TIMER lamp will blink (5 Hz).
9-2-1. Power supply voltage
The line voltage must be AC 220 – 240 V. If it is not within this range, the air conditioner may not operate normally.
9-2-3. Program control
The microcontroller operates as shown in Table 9-2-1 to control the air conditioner. If there are any opera­tional problems, check whether or not the problems correspond to Table 9-2-1. If they correspond to the Table, they are not problems with the air conditioner, but they are indispensable operations to control and maintain the air conditioner properly.
Table 9-2-1
No. Operation of air conditioner Descriptions
1 When the main power supply is turned
on, the OPERATION lamp on the indoor unit blinks.
2 The indoor fan motor speed does not
change in the Dry operation.
3 The compressor is not turned off even
though the room temperature is in the range that the compressor is turned off.
4 The compressor is not turned on and
off even though the thermo control is operated in the Dry operation.
*5 The PRE-DEF. lamp is indicated when
the Heating operation starts.
The OPERATION lamp blinks to indicate that power is turned on. If the [ ] button is pressed, the lamp stops blinking.
The indoor fan motor speed is automatically controlled in the Dry operation.
The compressor has a function that it is not turned off for 3 minutes after it is turned on even though the room temperature is in the range that the compressor is turned off.
In the Dry operation, the compressor is turned on and off automatically at the regular intervals, independent of the thermo control.
The PRE-DEF. lamp is indicated during the Defrosting operation or if the indoor heat exchanger temperature is low when the Heating operation starts. At this time, the indoor fan motor stops to prevent cold air from blowing in the room.
*6 The outdoor fan motor stops in the
Heating operation.
7 The compressor is not turned on even
though the room temperature is in the range that the compressor is turned on.
8 The operation mode changes in the
Automatic operation.
9 The Fan only operation continues in the
Automatic operation.
10 The ECO operation or Hi-POWER
operation does not work.
11 When [Hi POWER] button is pressed,
the display on the remote control does not change at all.
Note *5 and *6 are for Heat pump model :
When the indoor heat exchanger temperature is high, the outdoor fan motor is stopped by the high-temperature limit control operation.
The compressor is not turned on in the restart delay timer (3-minutes timer) operation. It is also not turned on after the power supply is turned on because of this timer operation.
In Automatic operation, the room temperature is detected all time for control fan speed and the operation mode is changed every 15 minutes according to difference between the room temperature and the preset temperature.
When the room temperature is in the range (Preset temperature ± 1°C), the Fan only operation is selected.
These operations do not work when the unit is in the Dry operation or Fan only operation.
The display on the remote control does not change when [Hi POWER] button is pressed. However the microcontroller gives commands to change the preset temperature and air flow level.
- 47 -
Page 49
FILE NO. SVM-06020

9-3. Primary Judgement

9-3-1. Role of indoor unit controller
The indoor unit controller receives the operation commands from the remote control and executes them.  Temperature measurement at the air outlet of the
·
indoor heat exchanger by the indoor temperature sensor
 Temperature setting of the indoor heat exchanger by
·
the heat exchanger sensor
 Louver motor control
·
 Indoor fan motor operation control
·
 LED display control
·
 Transferring of operation commands to the outdoor
·
unit
Table 9-3-1
Lamps Self-diagnosis
A OPERATION lamp is blinking. (1Hz) B OPERATION lamp is blinking. (5Hz) C OPERATION lamp is blinking. (5Hz) D OPERATION lamp is blinking. (5Hz) E OPERATION lamp is blinking. (5Hz) F OPERATION and TIMER lamps are blinking.
(5Hz)
9-3-2. Failure diagnosis
The indoor unit diagnoses the operation condition and indicates the information of the self-diagnosis with the lamps on the display panel of the indoor unit.
Power failure (when the power supply is turning on) Thermo sensor (TA) short or break Heat exchanger sensor (TC) short or break Indoor fan motor lock or failure Indoor P.C. board failure Wrong wiring of connecting cable
G OPERATION, TIMER and PRE-DEF.
(or FAN ONLY for cooling only model) lamps are blinking.
Table 9-3-2 Diagnosis by detective operation
Symptom Check Primary judgement
The remote control does not work.
The outdoor fan does not rotate.
Turn off the power supply once, then turn it on. Try to operate the remote control.
The compressor operates.
The compressor does not operate.
Cycle failure  Gas shortage or other refrigerant cycle trouble
·
 Heat exchanger sensor open, break or short
·
·
 Overload relay or thermostat trouble of compressor
The remote control still does not work.
The remote control works.
The indoor unit (and/or remote control) is/are defective .
OK.
The outdoor unit (Outdoor fan motor) is defective.
An internal part of the compressor or P.C. board is defective.
- 48 -
Page 50
9-4. Self-Diagnosis by Remote Control
(Check Code)
(1) If the lamps are indicated as shown B to G in Table
9-3-1, exchanger the self-diagnosis by the remote control.
(2) When the remote control is set to the service
mode, the indoor controller diagnoses the operation condition and indicate the information of the self-diagnosis on the display of the remote control with the check codes. If a fault is detected, all lamps on the indoor unit will blink at 5Hz and it
will beep for 10 seconds (Pi, Pi, Pi....). The timer
lamp usually blinks (5Hz) during the self-diagnosis.
9-4-1. How to use remote control in service mode
FILE NO. SVM-06020
(1) Press [CHK] button with a tip of pencil to set the
remote control to the service mode.
“00” is indicated on the display of the remote
control.
The timer lamp on the indoor unit blinks
continuously. (5 times per 1 sec.)
(2) Press [TIMER 8] button.
If there is no fault with a code, the indoor unit will beep once (Pi) and the display of the remote control will change as follows:
00
01
Check the unit with all 35 check codes (00 to 22). as shown in Table 9-4-1.
Press [TIMER 9] button to change the check
code backwards.
If there is a fault, the indoor unit will beep for 10 seconds (Pi, Pi, Pi...). Note the check code on the display of the remote control.
2-digits alphanumeric will be indicated on the
display.
All lamps on the indoor unit will blink. (5 times
per 1 sec.)
(3) Press [CLR] button. After service finish for clear
service code in memory.
“7F” is indicated on the display of the remote
control.
1d
02
1E
22
Alphanumeric characters are used for the check code.
is 5. is 6. is A. is B. is C. is D.
* This illustration in only for Heat pump model.
For Cooling only model, there is not the ( ) symbol.
(4) Press [ ] button to release the service
mode.
The display of the remote control returns to as it
was before service mode was engaged.
- 49 -
Page 51
Table 9-4-1
Block level Diagnosis function
Check
code code status
Block
Indoor P.C. board
Cable connection
Outdoor P.C. board
Other parts (including compressor)
Check
Symptom
The indoor thermo sensor (TA) is defective. Disconnection or short-circuit
The indoor heat exchanger sensor (TC) is defective. Disconnection or short-circuit
The indoor fan motor or its circuit is defective.
The part other than the above parts on the indoor P.C. board is defective. EEPROM access error
IOL operation
The serial signals can not be transmitted and received between indoor and outdoor units.
The crossover wire is connected wrongly.
The serial signal transmitting circuit on the outdoor P.C. board is defective.
The serial signal receiving circuit on the indoor P.C. board is defective.
The operation command signals are not transmitted from the indoor unit to the outdoor unit.
The outdoor thermo sensor (TE) is defective. Disconnection or short-circuit
The outdoor heat exchanger (TD) sensor is defective. Disconnection or short-circuit
The reply serial signal has been transmitted when starting the unit, but stops being transmitted shortly after.
1. Compressor thermo operation
Gas shortage
Gas leak
2. Instantaneous power failure
The discharge temperature is over 120°C.
The IOL operation is defective.
Unit
Operation continues.
Operation continues.
All off
Operation continues.
All off
Operation continues.
Operation continues.
All off
All off
Operation continues.
All off
All off
Condition
The lamp on the indoor unit blinks when error is defected.
The lamp on the indoor unit blinks when error is defected.
The lamp on the indoor unit blinks when error is defected.
The lamp on the indoor unit blinks when error is defected.
The lamp on the indoor unit blinks when error is
.
defected The lamp on the
indoor unit blinks when error is defected.
The lamp on the indoor unit blinks when error is defected. And it returns to the normal condition when recovering from errors.
The lamp on the indoor unit blinks when error is defected.
The lamp on the indoor unit blinks when error is defected.
The lamp on the indoor unit blinks when error is defected. And it returns to the normal condition when recovering from errors.
The lamp on the indoor unit blinks when error is defected.
The lamp on the indoor unit blinks when error is detected.
FILE NO. SVM-06020
Judgement and action
1. Check the indoor thermo sensor (TA).
2. Check the indoor P.C. board.
1. Check the indoor heat exchanger sensor (TC).
2. Check the indoor P.C. board.
1. Check the connector circuit of the indoor fan motor (CN10).
2. Check the indoor fan motor.
3. Check the indoor P.C. board.
1. Check the indoor P.C. board. (EEPROM and peripheral circuits)
Overload operation of refrigerating cycle
1. In the case of the outdoor unit not operating at all;
Check the crossover cable and
connect it properly.
Check the outdoor P.C. board.
2. In the case of the outdoor unit operating normally;
Check whether or not both of serial
LED (Green) and serial LED (Orange) is blinking. If the serial LED (Green) is not blinking, check the outdoor P.C. board. If the serial LED (Orange) is not blinking, check the indoor P.C. board.
If the operation command signals continue to be transmitted between 2 and 3 of the indoor terminal block, replace the outdoor P.C. board.
1. Check the outdoor thermo sensor (TE).
2. Check the outdoor P.C. board.
1. Check the outdoor heat exchanger sensor (TD).
2. Check the outdoor P.C. board.
1. Repeatedly turn the indoor unit on and off with the interval of approx. 10 to 40 minutes. (The check code is not indicated during operation.) And supply gas. (Check gas leak.)
2. The indoor unit operates normally during the check. If the reply serial signal continues to be transmitted between 2 and 3 of the indoor terminal block, replace the outdoor P.C. board. If the signal stops between them, replace the indoor P.C. board.
1. Check the heat exchanger sensor (TD).
2. Gas purging
When turning on the unit, the normal phase (RST) is detected but T-R waveform has not been detected for 120 seconds or more.
- 50 -
Page 52

9-5. How To Diagnose Faulty Parts

[04 Serial signal error] (Heat pump model)
FILE NO. SVM-06020
Operation
Check item
Conceivable principle cause
Measure
Does outdoor
unit operate?
YES
NO
Are 1, 2 and 3 crossover
wires connected properly?
YES
Is connector
connected properly?
YES
Does LED (Orange) on
outdoor P.C. board blink?
YES
Does LED (Green) on
outdoor P.C. board blink?
YES
NO
NO
NO
NO
Outdoor P.C. board
is defective.
Indoor P.C. board
is defective.
Item by symptoms
Connect crossover
wires properly.
Connect connector
properly.
Replace
P.C. board.
Replace
P.C. board.
[08 Four-way valve error] (Heat pump model)
Does four-way valve
operate properly?
YES
Is TC sensor
resistance value
(10kat 25°C) normal?
NO
NO
YES
Does coil terminal
have 220 − 240 V
in heating operation?
YES
Are circuit
wires normal?
YES
Is outdoor P.C. board
normal?
YES
YES
NO
NO
Four-way valve
is defective.
Outdoor P.C. board
is defective.
(CN11 220 240V)
Indoor P.C. board
is defective.
Replace
Four-way valve
Circuit check/modification
Replace
P.C. board.
Replace
P.C. board.
Replace TC sensor.
- 51 -
Page 53
[09 Other cycle error] (1) (Heat pump model)
FILE NO. SVM-06020
NO
Replace TC
sensor.
YES
Connect TC
sensor properly.
Does compressor operate?
YES
Is compressor
turned off shortly?
NO
Is TC sensor
resistance value
(10kΩ at 25°C) normal?
YES
Is TC sensor
disconnected from
the sensing element?
NO
NO
YES
Does inner
overload relay
(in compressor)
operate?
NO
Is circuit wiring
normal?
YES
Is outdoor P.C.
board normal?
YES
YES
NO
NO
Check charged amount of refrigerant.
Check defective overload.
Check compressor.
Failure
compressor.
Wiring check/modification
Outdoor P.C. board
is defective.
Indoor P.C. board
is defective.
Replace
Replace
P.C. board.
Replace
P.C. board.
[09 Other cycle error] (2)
NO
Connect
connector
properly.
NO
Replace
condenser.
NO
Replace
fan motor.
Is connector
connected properly?
Is condenser normal?
Is indoor fan
motor normal?
YES
YES
YES
NO
Does indoor fan operate?
Are filters clogged?
Is TC sensor
resistance value
(10kΩ at 25°C) normal?
Is charged amount
of refrigerant normal?
Is outside air
low load?
YES
NO
YES
YES
NO
YES
NO
NO
YES
Anti-freezing operation
Anti-freezing operation
Clean filters.
Replace
TC sensor.
Charge
refrigerant.
Indoor P.C. board
is defective.
- 52 -
Replacd
P.C. board.
Page 54
[0C Indoor TA sensor error]
FILE NO. SVM-06020
Is CN04 (TA sensor connector)
connected properly?
YES
Is TA sensor resistance value
(10 kΩ at 25
°C)
YES
normal?
[0d Indoor TC sensor error]
Is CN05 (TC sensor connector)
connected properly?
YES
NO
NO
NO
Indoor P.C. board is defective.
Connect CN04 properly.
Replace TA sensor.
Replace P.C. board.
Connect CN05 properly.
Is TC sensor resistance value
(10 k
at 25°C) normal?
YES
NO
Indoor P.C. board is defective.
[18 outdoor TE sensor error] (Heat pump model)
Is TE sensor connector
connected properly?
YES
Is TE sensor resistance value
(10 k
at 25°C) normal?
YES
NO
NO
Replace TC sensor.
Replace P.C. board.
Connect connector
properly.
Replace TE sensor.
Indoor P.C. board is defective.
- 53 -
Replace P.C. board.
Page 55
[19 outdoor TD sensor error] (Heat pump model)
FILE NO. SVM-06020
Is TD sensor
connected properly?
YES
Is TD sensor resistance value
(50 k
at 25°C) normal?
YES
NO
NO
Outdoor P.C. board is defective.
[1E Discharge temp. error] (Heat pump model)
Connect connector
properly.
Replace TD sensor.
Replace P.C. board.
Is protective
controller such as discharge
thermostat normal?
YES
Is charged amount
of refrigerant normal?
YES
Is overload relay normal?
NO
Is TD sensor resistance value
(50 k at 25°C) normal?
YES
NO NO
NO
YES
NO
Are wires connected
to connector properly?
Outdoor P.C. board is defective.
Connect wires to
connector properly.
Check and modify charged
amount of refrigerant.
Unit operates normally.
Replace TD sensor.
Replace P.C. board.
- 54 -
Page 56
FILE NO. SVM-06020
Operation
Measure
Item by symptoms
Check item
Conceivable principle
cause
9-6.
Troubleshooting for Indoor unit
9-6-1. Power can not be turned on. (The unit does not operate at all.)
<Primar check>
(1) Is the supply voltage normal? (2)Is the connection to the AC output OK? (3) Is the fuse (F01) blown?
Turn off power supply once, and 5 second later, turn it
on again.
NO
Is OPERATION
lamp blinking?
YES
Does
Is it possible to
turn on power
supply by
pressing
[START/STOP]
button on remote
control?
YES
NO
transmission
mark on
remote
control flash
normally, and
is its signal
transmitted
properly?
YES
NO
Remote control is
defective.
Refer to 9-9
ÒTroubleshooting for
Remote Control.Ó
Is DC 310 -
340V across
C63?
Are DC 12V,
across C66?
YES
YES
NO
NO
Is fuse (F01)
control board
Is voltage (DC
12V or 5V)
NO
indicated on rear of indoor control board
Turn off breaker
once and turn it
on again after
removing motor.
of indoor
blown?
normal?
NO
YES
YES
Parts (R21, R22, SG01,
C01, DB01,
C02,
M01 and IC04)
are defective.
Are DC 12V,
across C66?
YES
- 55 -
NO
Does the fan
motor
connector
between 1
and 2 short-
circuit?
NO
Microcomputer is
defective.
M01 is
def
ec
tive.
Unit operates
normally.
YES
Replace main P.C.
board.
Replace motor.
Page 57
FILE NO. SVM-06020
9-6-2. Only the indoor fan does not operate
<Primary chec k>
(1) Is it possible to detect the power supply voltage (200 − 240V) between 1 and 2 on the terminal block? (2) Does the indoor fan motor operate in cooling operation?
(In heating operation, the indoor fan motor does not operate for approximately 5 minutes after it is turned on, to prevent a cold air from blowing in.)
Shut off the
power supply once.
Turn the power supply.
Does the fan stop in
no operating status?
YES
Start the operation
with low fan setting
in cool operation.
Does the fan rotate?
YES
Change the setting of
cooling to high fan.
Does the fan speed
become higher?
YES
NO
NO
NO
Control P.C. board is defective.
Does AC 120V
or higher voltage apply
to between red and black
lead of fan motor?
YES
Shut off the power supply.
Does the cross flow fan rotate normally?
YES
Turn on the power supply.
Operation
stops
NO
NO
Replace the P.C. board.
Does connecting
terminal, connecting
cable or power supply
cord completely?
Does not found the short
wire about connecting
cable and power cord?
YES
Repair the bearing of
the fan.
Motor control circuit failure
(IC30, IC03, D38, R25, R26, Q17)
or 12V power circuit failure.
Replace the P.C. board.
of incompleted connecting.
NO
Thermal fuse operated
due to prevent
temperature rising cause
Normal
Is the rotation signal (DC+5V-0V)
output between 2 (gray lead wire)
and 3 (brown lead wire) of the motor
connector (CN11) when rotating
the cross flow fan by hand in no
operating status? (1 pulse/one turn)
YES
Replace the control
P.C. board.
- 56 -
NO
Replace the fan motor
Replace connecting
the cable (or power cord),
thermal fuse and
terminal block.
Page 58
FILE NO. SVM-06020
9-6-3. Compressor does not operate. <Primary check>
(1) Is the preset temperature higher than the room temperature in cooling operation? (2) Is the crossover cable connected properly?
<Inspection procedure>
Turn on power supply.
Does OPERATION
lamp blink?
YES
Does miniature relay RY04
switch on and off due to
temperature changes?
YES
Is it possible to detect AC
220 – 240V between 2
and 3 on terminal block?
YES
Are all of compressor cords normal?
YES
Is compressor motor winding
normal?
(Check winding resistor.)
YES
Is capacitor for compressor normal?
NO
NO
NO
Is resistance value of thermo
sensor (TA) and heat ex-
changer sensor (TC) normal?
Microcomputer is defective.
Miniature relay RY04 is
defective.
NO
NO
NO
NO
YES
Compressor is defective.
Capacitor is defective.
Refer to 9-6-1 “Power
can not be turned on”.
Thermo sensor or
heat exchanger
sensor is defective.
Replace thermo sensor
or heat exchanger
sensor.
Replace P.C. board.
Rewire or replace
defective cords.
Replace compressor.
Replace capacitor.
YES
Is overload relay normal?
YES
Does compressor start?
YES
Does compressor stop after a while?
YES
Is gas quantity normal?
(Check gas pressure.)
YES
Compressor is defective.
YES
Replace P.C. board.
NO
NO
NO
Overload relay is
defective.
Compressor is defective.
Gas shortage (Gas leak)
- 57 -
Replace overload relay.
Replace compressor.
Supply gas.
Page 59
<Inspection procedure>
- Cooling model -
Turn on power supply.
FILE NO. SVM-06020
Does OPERATION
lamp blink?
YES
Is it possible to start
unit by remote control?
YES
Is it possible to detect AC 200V
between 2 and 3 on terminal block?
YES
Is crossover cable normal?
YES
Are all of compressor cords normal?
YES
Is compressor motor winding normal?
(Check winding resistor.)
YES
Is capacitor for compressor normal?
YES
NO
NO
NO
NO
NO
NO
NO
Compressor is defective.
Capacitor is defective.
Refer to item Power
can not be turned on .
Refer to 9-9 Troubleshooting
for Remote Control .
Replace P.C. Board
Connect crossover
cable properly.
Rewire or replace
defective cords.
Replace compressor.
Replace compressor.
Is overload relay normal?
YES
Does compressor start?
YES
Does compressor stop after a while?
YES
Is gas quantity normal?
(Check gas pressure.)
YES
Compressor is defective.
YES
Replace P.C. borad
NO
NO
NO
Overload relay is defective.
Compressor is defective.
Gas shortage (Gas leak)
Replace overload relay.
Replace compressor.
Supply gas.
- 58 -
Page 60
<Inspection procedure)
- Heating model -
AC 70-100V
FILE NO. SVM-06020
Replace transformer
outdoor
P.C. board.
- 59 -
Page 61
YES
FILE NO. SVM-06020
Are all of compressor cords normal?
YES
Is compressor motor winding normal?
(Check winding resistor.)
YES
Is capacitor for compressor normal?
YES
Is overload relay normal?
YES
Does compressor start?
YES
Does compressor stop after a while?
YES
Is gas quantity normal?
(Check gas pressure.)
YES
NO
NO
NO
NO
NO
NO
Compressor is defective.
Capacitor is defective.
Overload relay is defective.
Compressor is defective.
Gas shortage (Gas leak)
Rewire or replace
defective cords.
Replace compressor.
Replace capacitor.
Replace overload relay.
Replace compressor.
Supply gas.
Compressor is defective.
YES
Replace compressor.
- 60 -
Page 62
FILE NO. SVM-06020
9-7. Troubleshooting for Wiring (Interconnect cable and Serial Signal Wire)
9-7-1. Outdoor unit does not operate. <Inspection procedure>
(1) Is the voltage between and of the indoor terminal block varied?
1
(2) Are signals from the indoor unit to the outdoor unit transmitted correctly based upon the following diagram?
NOTE:
 Measure the voltage for 2 minutes and 30 seconds after starting the unit. 
Heatpump model
Terminal block on indoor side
Red
2
3
White
2
1
Terminal block
Tester
Normal condition : Voltage varied between AC70 ~ 100V Abnormal condition : Voltage does not vary.
Cooling model
Terminal block on indoor side
Red
White
3
2
1
Terminal block
Tester
Fig. 9-7-1
Normal condition : After start operated about 2 minutes and 30 seconds. Voltage between 2 and 3 of the
of the indoor's Terminal block should be equal AC 220 ~ 240V (For Asia model), AC 220V (For Thai model).
Abnormal condition : Don't found voltage AC 220 ~ 240V (For Asia model), AC 220V (For Thai model) from
terminal block (0V)
9-7-2. Outdoor unit stops a while after starting the unit.
<Confirmation procedure> Select one of 3 cases below and follow the procedure.
(1) The outdoor unit stops between 10 and 20 minutes passed after starting and it takes 10 minutes or more to
restart the unit.
Gas has a low circulation.
Measure gas pressure.
Compressor is turned off and on automatically by thermo sensor
(Heat pump Model) or thermostat (Cooling only Model).
Gas shortage Gas leak Pipe clogging
(2) The outdoor unit stops once, it would not operate until the power is turned on again.
Refer to 9-6-4 "Compressor does not operate"
(3) The outdoor unit stops between 10 minutes to 1 hour after starting and a check code is indicated on the
remote control. (Check code 03-1E : Refer to Table 9-4-1.)
- 61 -
Page 63
FILE NO. SVM-06020
9-8. Troubleshooting for P.C. board
9-8-1. How to check indoor P.C. board <Cautions for handling P.C. board>
(1) When removing the front panel and the P.C. board,
be sure to turn off the power supply.
(2) When removing the P.C. board, hold the edge of
the P.C. board and do not apply force to the parts.
(3) When connecting or disconnecting the connectors
on the P.C. board, hold the housing. Do not pull at lead wires.
<Inspection procedure>
(1) If the P.C. board is detective, check for disconnec-
tion, burn or discoloration of the copper foil pattern of the P.C. board.
(2) The P.C. board consists of the following 2 parts:
a. Main P.C. board parts.
Power relay, indoor fan motor drive circuit and control circuit, C.P.U. and peripheral circuits, buzzer drive circuit and buzzer.
b. Infrared rays parts:
Infrared rays receiving circuit
Check the defects of the P.C. board with Table 9-8-1.
Table 9-8-1 Inspection pr ocedure
No. Procedure Check points Causes
1 Turn off the power supply and
remove the P.C. board assembly from electric parts base. Remove the connecting cables from the terminal block.
2 Remove the connector of the motor
and turn on the power supply. If OPERATION lamp blinks (once per second), it is not neccessary to check steps (1 to 3) in the right next column.
Check whenther or not the fuse (F01) is blown.
Check power supply voltage;
1. Between CN30 and CN31 (220 240 V AC) : Except
2. Between + and of C63 (DC310 340 V)
3. Between 12 V and GND
4. Between 5 V and GND
Impluse voltage was applied or the indoor fan motor short-circuited.
1. The terminal block or the crossover cable is connected wrongly.
2. The capacitor (C01 and C02 ) line filter (L01), resistor (R319), or the diode (DB01) is defective.
3. C65, C66 and M01 are defective.
4. IC04, C05, C06 and C07 are defective.
3 Press [ ] button once
to start the unit. (Do not set the mode to Fan Only or On-Timer operation).
4 Shorten the line of the restart delay
timer and start unit.
Check power supply voltage; <Heat pump model>
1. Between CN31 and CN23 (DC15 60 V)
<Cooling only model>
1. Between connector of Q24 and GND (for relay coil (DC12 V))
2. Between 1 and 2 of terminal block for connecting cable
Check whether or not all lamps (OPERA TION, TIMER, PRE.-DEF. (or FAN ONLY), FILTER.and Hi Power) are indicated for 3 seconds and they return to normal 3 seconds later.
<Heat pump model> IC32 and IC33 are defectice.
<Cooling only model>
1. The wire of the relay coil (RY04) comes down or the relay drive (Q24) is defective.
2. CN27 or RY04 is connected wrongly.
The lamps are defective or the housing assembly (CN13) is defective.
- 62 -
Page 64
FILE NO. SVM-06020
No. Procedure Check points Causes
5 Press [ ] button once
to start the unit.
Shorten the time of the restart delay timer.
Set the operation mode to COOL.
Set the fan speed level to AUTO.
Set the preset temperature much
lower than the room temperature. (The unit (compressor) operates continuously in the above condition.)
1. Check whether or not the compressor operates.
2. Check whether or not the OPERATION lamp blinks.
1. The temperature of the indoor heat exchanger is extremely low.
2. The connection of the heat exchanger sensor is loose. (The connector is disconnected.) (CN01)
3. The heat exchanger sensor and the P.C. board are defective. (Refer to Table 9-8-2.)
4. The main P.C. board is defective.
6 If the above condition (No. 6) still
continues, start the unit in the following condition.
Set the operation mode to HEAT.
Set the preset temperature much
higher than room temperature.
7 Connect the motor connector to the
motor and turn on the power supply. Start the unit in the following condition.
Set the operation mode to FAN.
Set the fan speed level to HIGH.
(The unit (compressor) operates continuously in the above codition.)
1. Check whether or not the compressor operates.
2. Check whether or not the OPERATION lamp blinks.
1. Check it is impossible to detect the voltage (DC 12 V) between and1
3 of the motor terminals.
2. The motor does not operate. (But it is possible to receive the signal from the remote control.)
3. The motor rotates but vibrates strongly.
1. The temperature of the indoor heat exchanger is extremely high.
2. The connector of the heat exchanger sensor short-circuited. (CN01)
3. The heat exchanger sensor and the P.C. board are defective. (Refer to T ab le 9-8-2.)
4. The main P.C. board is defective.
1. The indoor fan motor is defective . (Protected operation of P.C. board)
2. The connection of the motor connector is loose.
3. The P.C. board is defective.
Table 9-8-2 Approximate resistance value of thermo sensor
Temperature 0°C10°C20°C25°C30°C
Resistance value 33.8 20.35 12.59 10.0 7.99
(kΩ)
9-8-2. How to Shorten Time of Restart Delay Timer
1 Press [CLR] button while pressing [CHK] button
with a tip of a pencil.
2 Then press [ ] button to transmit the
signal to the indoor unit.
9-8-3. How to use self cleaning function
The self cleaning function is set from a factory. To cancel this function, should keep press the temporary switch for 20 secounds till can hear the long combination sound and repeat the
same procedure when need to set.
2
1
- 63 -
Page 65
9-9. Troubleshooting for Remote Control
FILE NO. SVM-06020
Is receiver on
indoor unit exposed
to direct sunlight?
YES
NO
Is there any
thyristor fluorescent
light nearby?
YES
YES
NO NO
Press START/STOP
button.
Is transmission
mark indicated?
Does indoor unit
operate when
moving remote control
near receiver or
indoor unit?
YES
Batteries are
exhausted.
The unit does not beep at all. OPERATION lamp on indoor unit is not indicated.
NO
Press RESET button
on remote control
with tip of pencil.
Press START/STOP
button.
Avoid direct
sunlight.
Keep indoor unit
away from
thyristor
fluorescent light.
Does indoor unit
NO
start to operate by
automatic restart
function?
YES
Does radio sound
is affected by
remote control when
a signal is transmitted
at distance of 5 cm
from radio?
P.C. board is
defective.
Replace
P.C. board.
YES
NO
NO
Replace
batteries.
Note : After replacing batteries,
press the RESET button with a tip of a pencil.
- 64 -
Is transmission mark
indicated?
YES
Does indoor unit
beep and operate?
YES
Normal
operation
NO
Remote control
is defective.
Replace
remote control.
Page 66
FILE NO. SVM-06020

10. PART REPLACEMENT

10-1. Indoor Unit
No. Part name Procedures Remarks
1 Front panel
How to remove the front panel
1) Stop the operation of the air conditioner and turn off
its main power supply.
2) Pull the inlet grille toward you to open it and remove
4 screws fixing the front panel.
3) Remove upper 3 hooks of the front panel from the
back body.
4) Open the horizontal grille right below by hand.
5) Pull the lower side of the front panel toward you
until it touches the horizontal grille to remove it.
(2)
(2)
4-screws
(2)
2 Electrical part
assembly
How to mount the front panel
1) Mount the front panel with the inverse procedure of
“How to remove the front panel”.
2) Push 3 places (right, left and center) of the air
outlet.
3) Check the gap between the front panel and the
back body. If you operate the air conditioner in cooling or dry operation without pushing the 3 places, the surface of the front panel may be covered with frost and have dewdrops.
1) Remove the front panel with the procedure 1.
2) Remove the screw fixing the electrical part box.
3) Remove the drain guide.
4) Remove the connector (
and the connector (6P) for the louver motor from the microcomputer assembly.
5) Remove the screw for the earth, and pull the
electrical part base toward you to remove it from the main unit.
6) Pull out the TC sensor from the sensor holder.
3P x 2) for the fan motor
(3) Drain guide
(3)
(4)
(5) screws
(3P X 2) 6P
(2) screws
- 65 -
(6) TC sensor
When assembling the electrical parts assembly, make the connecting cable U-shaped and put it in the drain pan.
Page 67
FILE NO. SVM-06020
No. Part name Procedures Remarks
3 Horizontal louver
4 Heat exchanger
1) Remove center 2 shafts of the horizontal grille from
the back body.
2) Remove left shaft of the horizontal
louver from the
back body.
3) Remove the horizontal
louver from the back body.
1) Remove the front panel, electrical parts assembly
and the horizontal louver with procedure 2 and 3.
2) Remove the screw on the rear side of the main unit to remove the pipe holder.
3) Remove 2 screws fixing the heat exchanger and the bearing base.
4) Remove 2 screws fixing the heat exchanger fixtures (upper and lower) and the back body then pull out the upper side of the heat exchanger slowly.
(1) Center shafts
(2) Left shafts
(3) 2 screws
(2) Screw
Bearing base
(3)
Pipe holder
(4) 2 screws
5 Cross flow fan
6 Bearing base
1) Remove the front panel, electrical parts assembly, horizontal
louver and the heat exchanger with
procedure 4.
2) Loosen the set screw of the cross flow fan.
3) Remove 2 screws fixing the bearing base and the back body.
4) Pull the cross flow fan toward you.
1) Remove the front panel, electrical parts assembly, horizontal
louver, heat exchanger and the cross flow
fan with procedure 5.
2) Remove the bearing from the bearing base. If the housing protrudes from the base bearing, put the housing in position and assemble the bearing to the bearing base.
(3) Screws
(2) Set screw
When assembling the cross flow fan, fix it with the set screw at the position where the gap between the back body and the right surface of the cross flow fan is 4 mm.
Bearing base
Bearing
7 Fan motor
1) Remove the front panel, electrical parts assembly, horizontal louver, and the heat exchanger with procedure 4.
2) Loosen the set screw of the cross flow fan.
3) Remove 2 screws of the motor fixture.
4) Remove the lower side of the body (R) and move it right to remove it.
5) Remove the motor from the motor fixture.
- 66 -
(3) 2 screws
(4) BODY (R)
(5)
Motor fixture
Page 68
FILE NO. SVM-06020
10-2. Outdoor Unit (RAS-24GAH-ES2, RAS-24GA-ES2)
No. Part name Procedures Remarks
Top cabinet
1 Common
procedure
1) Stop the operation of the air conditioner and turn off its main power supply or remove the power supply cord.
2) Remove the packed valve cover and the electrical parts cover (2 screws4 x 10L)
3) Remove 2 cord clamps (4 screws 4 x 16L) and disconnect the power supply cord and connecting cable after removing 6 screwson on the terminal block and 1 ground screw on the electrical parts base.
4) Remove the top cabinet. (7 screws 4 x 10L) (Pulling out upward)
5) Remove the top cabinet. (2 screws 4 x 10L) (Pull the front right portion toward you, and remove it pulling out upward)
Front cabinet
2 screws
4 x 10L
Packed valve cover
2 Cord clamps
Side cabinet
4 screws 4 x 16L
7 screws 4 x 10L
Front
cabinet
- 67 -
Page 69
FILE NO. SVM-06020
No.
2 Running
3 Running
4 Magnetic
5 Spark killer
Part name
capacitor for compressor
capacitor for fan motor
contactor
(Cooling only model)
Procedures
1) Perform the common procedure 1
2) Remove the capacitor band. (1 screw ∅4 x 10L)
3) Disconnect the lead wires from the capacitor terminal.
1) Perform the common procedure 1
2) Remove the fixing screw. (1 screw ∅4 x 10L)
3) Disconnect the lead wires from the capacitor terminal.
1) Perform the common procedure 1
2) Remove the fixing screw. (2 screws 4 x 16L)
3) Disconnect the lead wires from the terminal.
1) Perform the common procedure 1
2) Remove the fixing screw. (1 screws 4 x 10L)
3) Disconnect the lead wires from the terminal.
Remarks
Running capacitor for compressor
Running capacitor for fan motor
Cooling only model
Spark killer
Magnetic contactor
- 68 -
Page 70
FILE NO. SVM-06020
10-3 Outdoor Unit (RAS-18GAH-ES2, RAS-18GA-ES2)
No. Part name Procedures Remarks
1 Common
procedure
1) Stop the operation of the air conditioner and turn off its main power supply or remove the power supply cord.
2) Remove the packed valved cover and the electrical
Parts cover
(2 screws 4 x 10L)
3) Remove 2 cord clamps (4 screws 4 x 16L) and disconnect the power supply cord and connecting cable after removing 6 screws on the terminal block and 1 ground screw on the electrical parts base.
4) Remove the upper cabinet. (4 scerws ∅ 4 x 10L) (Pulling out upward)
5) Remove the front cabinet. (3 screws∅ 4 x 10L) (Pull the front right protion toward you, and remove
it pulling out upward.)
Packed valve cover
2 screws 4 x 10L
Upper cabinet
2 Cord clamps
4 screws 4 x 16L
Running
2
capacitor for compressor
Running
3
capacitor
for fan motor
4
Magnetic contactor
Transformer
5
(Heat pump model)
P.C. Board
6
(Heat pump model)
7
Spark killer
(Cooling only model)
1) Perform the common procedure 1
2) Remove the capacitor band. (1 screw ∅4 x 10L)
3) Disconnect the lead wires from the capacitor terminal.
1) Perform the common procedure 1
2) Remove the fixing screw. (1 screw ∅4 x 10L)
3) Disconnect the lead wires from the capacitor
terminal.
form the common procedure 1
1) Per
2) Remove the fixing screw. (2 screws 4 x 10L)
3) Disconnect the lead wires from the terminal.
1) Perform the common procedure 1
2) Remove the fixing screw. (2 screws 4 x 10L)
3) Disconnect the housing from the P.C. Board.
1) Perform the common procedure 1
2) Disconnect the lead wires from the P.C. Board.
3) Remove P.C.Board after unhooking 4 clams.
1) Perform the common procedure 1
2) Remove the fixing screw. (1 screw ∅ 4 x 10L)
3) Disconnect the lead wires from the terminal.
Running capacitor
for fan motor
Running capacitor
for compressor
Running capacitor
Running capacitor for compressor
Front
cabinet
Heat pump model
for fan motor
Cooling only model
P.C. Board
Transformer
Magnetic contactor
Spark killer
Magnetic contactor
- 69 -
Page 71

11. EXPLODED VIEWS AND PARTS LIST

11-1. Indoor Unit (E-Parts Assy)
413
FILE NO. SVM-06020
411
407
Location Part Location Part
No. No. No. No.
402 43T60002 TERMINAL BLOCK; 3P 411 43T69527 PC BOARD (RAS-24GKHP) 403 43T50004 SENSOR; HEAT EXCHANGER 411 43T69528 PC BOARD (RAS-24GKP) 404 43T50314 SENSOR;THERMOSTAT 411 43T69529 PC BOARD (RAS-18GKHP) 405 43T69559 PC BOARD ASSY ; WRS-LED 411 43T69530 PC BOARD (RAS-18GKP) 407 43T62003 CORD CLAMP 413 43T63310 SENSOR HOLDER
Description Description
- 70 -
Page 72
11-2. Indoor Unit
HP)
P)
FILE NO. SVM-06020
202
203
201
227
229
230
221
208
217
228
213
222
219
210
220
215
232214
218
216
211
209
231
226
224
212
223
207
234
204
236
235
233
Location Part Location Part
No. No. No. No.
201 43T00409 FRONT PANEL ASSY 219 43T49324 PLATE; EVA-SEAL 202 43T09386 GRILLE ASSY (18,24GKHP) 220 43T49039 HOLDER; PLATE EVA-SEAL 202 43T09388 GRILLE ASSY (18,24GKP) 221 43T49038 PLATE; EVA-SEAL 203 43T80306 AIR FILTER (L) 222 43T49037 HOLDER; PLATE EVA-SEAL 204 43T80312 AIR FILTER (R) 223 43T79007 GUIDE DRAIN 207 43T03010 BODY; RIGHT 224 43T39306 FIX FOR MOTOR 208 43T03011 BODY; LEFT 226 43T21370 MOTOR FAN 209 43T03012 HIDE; CLAW 227 43T20316 FAN; CROSS FLOW 210 43T09345 LOUVER-H 228 43T22309 ASM-M-BEARING 211 43T70309 HOSE ASSY; DRAIN 229 43T39015 BASE; BEARING 212 43T21373 STEPPING MOTOR 230 43T03344 BACK BODY ASSY 213 43T44376 REFRIGERATION ASSEMBLY 231 43T07022 HOLDER; PIPE 214 43T47349 PIPE; DELIVERY 232 43T82306 INSTALLATION PLATE 215 43T47350 PIPE; SUCTION 234 43T69421 WIRELESS-REMOCO (RAS-18,24GK 216 43T49021 PIPE; SHIELD 234 43T69422 WIRELESS-REMOCO (RAS-18,24GK 217 43T19322 FIX-P-SENSOR 235 43T83003 HOLDER; REMOTE CONTROLLER 218 43T49325 SPRING 236 43T62029 COVER; TERMINAL
Description Description
- 71 -
Page 73
11-3. Outdoor Unit (RAS-24GAH-ES2)
FILE NO. SVM-06020
Location Part Location Part
No. No. No. No.
1 43T42324 BASE PLATE ASSEMBLY 24 43T19330 PACKED VALVE COVER 2 43T41397 COMPRESSOR;PA290X3CS-4MU 25 43T00455 UPPER CABINET 3 43T49011 SPRING BASE(UPPER) 26 43T96305 BUSHING 4 43T49012 SPRING BASE (LOWER) 27 43T62325 ELECTRIC PART COVER 5 43T49019 SPRING; BUFFER 28 43T61306 ELECTRIC PARTS BASE 6 43T97307 COMPRESSOR BOLT (M6) 29 43T52301 SWITCH;MAGNET; CLK-35J 7 43T43391 CONDENSER ASSEMBLY 30 43T55340 MF CAPACITOR 8 43T00448 FIXING PLATE VALVE 31 43T55341 CAPACITOR;PLASTIC-FILM
9 43T46332 VALVE;PACKED 6.35 DIA 32 43T60352 TERMINAL BLOCK; 6P 10 43T46335 VALVE;PACKED 12.7 DIA (H4) 35 43T19331 FIN GUARD 11 43T47331 BONNET, 6.35 DIA 36 43T00456 UPPER FRONT CABINET; A 12 43T47333 BONNET, 12.70 DIA 37 43T00457 UPPER FRONT CABINET; B 13 43T47013 CAPILLARY TUBE; 2.0 DIA 38 43T 71301 HANDLE 14 43T00468 FRONT CABINET 39 43T46337 4 WAY VALVE 15 43T00474 LEFT CABINET 40 43T46339 COIL;V-4WAY;AC220-240V 50Hz 16 43T00454 RIGHT CABINET 41 43T69059 SENSOR; TE 17 43T21378 FAN MOTOR;AC220-240V 50Hz 42 43T69060 SENSOR; TD 18 43T20319 PROPELLER FAN 43 43T79305 DRAIN NIPPLE 19 43T47001 NUT FLANGE 44 43T58301 TRANSFORMER; TT-05 20 43T19329 FAN GUARD 45 43T69580 PC BOARD 21 43T04302 PARTITION 46 43T60325 FILTER;CLAMP 22 43 23 43T39318 MOTOR BASE
T39317 MOTOR BASE CONNECTION PLATE 47 43T47308 CAPILLARY TUBE; 1.0 DIA
Description Description
- 72 -
Page 74
11-4. Outdoor Unit (RAS-18GAH-ES2)
FILE NO. SVM-06020
Location Part Location Part
No. No. No. No.
1 43T42324 BASE PLATE ASSEMBLY 22 43T39317 MOTOR BASE CONNECTION PLATE 2 43T41396 COMPRESSOR;PA225X2C-4KU1 23 43T39318 MOTOR BASE 3 43T49011 SPRING BASE(UPPER) 24 43T19330 PACKED VALVE COVER 4 43T49012 SPRING BASE (LOWER) 25 43T00460 UPPER CABINER ASSEMBLY 5 43T49019 SPRING; BUFFER 26 43T96305 BUSHING 6 43T97307 COMPRESSOR BOLT (M6) 27 43T62325 ELECTRIC PART COVER 7 43T43392 CONDENSER ASSEMBLY 28 43T61307 ELECTRIC PARTS BASE 8 43T00448 FIXING PLATE VALVE 29 43T52302 MAGNETIC CONTACTOR; AC220-240V 50Hz
9 43T46332 VALVE;PACKED 6.35 DIA 30 43T55340 MF CAPACITOR 10 43T46335 VALVE;PACKED 12.7 DIA (H4) 31 43T55341 CAPACITOR;PLASTIC-FILM 11 43T47331 BONNET, 6.35 DIA 32 43T60352 TERMINAL BLOCK; 6P 12 43T47333 BONNET, 12.70 DIA 34 43T61305 MAGNETIC RELAY BASE 13 43T47013 CAPILLARY TUBE; 2.0 DIA 35 43T19331 FIN GUARD 14 43T00468 FRONT CABINET 39 43T46337 4 WAY VALVE 15 43T00473 LEFT CABINET 40 43T46339 COIL;V-4WAY;AC220-240V 50Hz 16 43T00451 RIGHT CABINET ASSEMBLY 41 43T69059 SENSOR; TE 17 43T21378 FAN MOTOR;AC220-240V 50Hz 42 43T69060 SENSOR; TD 18 43T20319 PROPELLER FAN 43 43T79305 DRAIN NIPPLE 19 43T47001 NUT FLANGE 44 43T58301 TRANSFORMER; TT-05 20 43T19329 FAN GUARD 45 43T 69580 PC BOARD 21 43T04301 PARTITION 46 43T60325 FILTER;CLAMP
Description Description
- 73 -
Page 75
FILE NO. SVM-06020
11-5.
Outdoor Unit (RAS-24GA-ES2)
Location Part Location Part
No. No. No. No.
1 43T42324 BASE PLATE ASSEMBLY 20 43T19329 FAN GUARD
2 43T41397 COMPRESSOR;PA290X3CS-4MU 21 43T04302 PARTITION
3 43T49011 SPRING BASE(UPPER) 22 43T39317 MOTOR BASE CONNECTION PLATE
4 43T49012 SPRING BASE (LOWER) 23 43T39318 MOTOR BASE
5 43T49019 SPRING; BUFFER 24 43T19330 PACKED VALVE COVER
6 43T97307 COMPRESSOR BOLT (M6) 25 43T00455 UPPER CABINET
7 43T43390 CONDENSER ASSEMBLY 26 43T96305 BUSHING
8 43T00448 FIXING PLATE VALVE 27 43T62325 ELECTRIC PART COVER
9 43T46332 VALVE;PACKED 6.35 DIA 28 43T61306 ELECTRIC PARTS BASE
10 43T46335 VALVE;PACKED 12.7 DIA (H4) 29 43T52301 SWITCH;MAGNET; CLK-35J 11 43T47331 BONNET, 6.35 DIA 30 43T55340 MF CAPACITOR 12 43T47333 BONNET, 12.70 DIA 31 43T55341 CAPACITOR;PLASTIC-FILM 13 43T47013 CAPILLARY TUBE; 2.0 DIA 32 43T60352 TERMINAL BLOCK; 6P 14 43T00468 FRONT CABINET 33 43T33002 SPARK-KILLER 15 43T00474 LEFT CABINET 35 43T19331 FIN GUARD 16 43T00454 RIGHT CABINET 36 43T00456 UPPER FRONT CABINET; A 17 43T21377 FAN MOTOR;AC220-240V 50Hz 37 43T00457 UPPER FRONT CABINET; B 18 43T20319 PROPELLER FAN 38 43T71301 HANDLE 19 43T47001 NUT FLANGE
Description Description
- 74 -
Page 76
11-6. Outdoor Unit (RAS-18GA-ES2)
FILE NO. SVM-06020
Location Part Location Part
No. No. No. No.
1 43T42324 BASE PLATE ASSEMBLY 19 43T47001 NUT FLANGE 2 43T41396 COMPRESSOR;PA225X2C-4KU1 20 43T19329 FAN GUARD 3 43T49011 SPRING BASE(UPPER) 21 43T04301 PARTITION 4 43T49012 SPRING BASE (LOWER) 22 43T39317 MOTOR BASE CONNECTION PLATE 5 43T49019 SPRING; BUFFER 23 43T39318 MOTOR BASE 6 43T97307 COMPRESSOR BOLT (M6) 24 43T19330 PACKED VALVE COVER 7 43T43389 CONDENSER ASSEMBLY 25 43T00460 UPPER CABINER ASSEMBLY 8 43T00448 FIXING PLATE VALVE 26 43T96305 BUSHING
9 43T46332 VALVE;PACKED 6.35 DIA 27 43T62325 ELECTRIC PART COVER 10 43T46335 VALVE;PACKED 12.7 DIA (H4) 28 43T61304 ELECTRIC PART BASE 11 43T47331 BONNET, 6.35 DIA 29 43T52302 MAGNETIC CONTACTOR; AC220-240V 50Hz 12 43T47333 BONNET, 12.70 DIA 30 43T55340 MF CAPACITOR 13 43T47014 CAPILLARY TUBE; 1.7DIA 31 43T55324 CAPACITOR; PLASTIC-FILM 14 43T00468 FRONT CABINET 32 43T60352 TERMINAL BLOCK; 6P 15 43T00459 LEFT CABINET 33 43T33002 SPARK-KILLER 16 43T00451 RIGHT CABINET ASSEMBLY 34 43T61305 MAGNETIC RELAY BASE 17 43T21345 FAN-MOTOR(Made in China) 35 43T19331 FIN GUARD 18 43T20319 PROPELLER FAN
Description Description
- 75 -
Page 77
FILE NO. SVM-03009(1)
TOSHIBA CARRIER (THAILAND) CO.,LTD.
144/9 MOO 5, BANGKADI INDUSTRIAL PARK, TIVANON ROAD, TAMBOL BANGKADI,
AMPHUR MUANG, PATHUMTHANI 12000,THAILAND.
75
Loading...