7-1
7-2Description of Operation Circuit
7-3Hi POWER Mode
7-4High-Temperature Limit Control
7-5Low-Temperature Limit Control
7-6Defrosting Operation
7-7 A
7-8
7-9 Self-Cleaning function
7-10QUIET Mode
7-11COMFORT SLEEP mode
TION DESCRIPTION
Outline of Air Conditioner Control
uto Restar t Function
Filter Check Lamp
- 1 -
Page 3
8.INSTALLATION PROCEDURE
8-1Safety Cautions
8-2Installation Diagram of Indoor and Outdoor Units
8-3Installation
8-4Indoor Unit
8-5Outdoor Unit
8-6How to Set Remote Control Selector Switch
8-7Others
9.TROUBLESHOOTING CHART
9-1Troubleshooting Procedure
9-2Basic Check Items
9-3Primary Judgement
9-4Self-Diagnosis by Remote Control (Check Code)
9-5How to Diagnose Faulty Part
9-6Troubleshooting for Indoor Unit
9-7Troubleshooting for Wiring (Interconnect cable and Serial Signal
9-8Troubleshooting for P.C. Board
9-9Troubleshooting for Remote Control
FILE NO. SVM-06020
Wire)
10. PARTS REPLACEMENT
10-1 Indoor Unit
10-2 Outdoor Unit (RAS-24GAH-ES2, RAS-24GA-ES2)
10-3 Outdoor Unit (RAS-18GAH-ES2, RAS-18GA-ES2)
11. EXPLODED VIEWS AND PARTS LIST
11-1 Indoor Unit (E - Parts Assy)
11-2 Indoor Unit
11-3 Outdoor Unit
11-4 Outdoor Unit (RAS-18GAH-ES2)
11-5 Outdoor Unit (RAS-24GA-ES2)
11-6 Outdoor Unit (RAS-18GA-ES2)
(RAS-24GAH-ES2)
• This air conditioner is charged with
HFC (R410A) that doesn't deplete the
Ozone layer.
• This air conditioner requires special
installation for the refrigerant R410A.
- 2 -
Page 4
1. SPECIFICATIONS
FILE NO. SVM-06020
MODEL
ITEM
Capacity
Phase 1∅
Power source V 220 - 240
Power consumption W 243025102400 2480 2560 2690 1850 1900 1678 1748 1860 1960
Power factor % 9885998899 92 98 97 94 92 97 96
Running current A 0.3/ 0.3/
Indoor/Outdoor 11.0
Starting current A
Moisture removal lit/h 2.52.7 2.0 2.0
Noise
Refrigerant
Refrigerant control Capillary tube
Interconnection Connection type Flare connection
pipeMaximum length
INDOOR UNIT RAS-24GKHP-ES2RAS-24GKP-ES2RAS-18GKHP-ES2RAS-18GKP-ES2
DimensionsWidthmm998
Net weight kg 13
Evaporator typeFinned tube
Indoor fan typeCross flow fan
Air volume Medium fan m3/h 750 800 750 667 708 667
Fan motor output W 30
Air filterHoneycomb woven filter with PP frame
OUTDOOR UNIT RAS-24GAH-ES2RAS-24GA-ES2RAS-18GAH-ES2RAS-18GA-ES2
Dimensions Width mm 780780 780
Net weight kg 5652 44 39
Condenser typeFinned tube
Outdoor fan type Propeller fan
Airflow volume m3/h 2400 2550 2400 2550 2400 2550 2350 2450 2350 2450 2120 2200
Fan motor output W 42 42
Over 15m up to 25m (20g/m) Over 15m up to 20m (20g/m)
(DB)27°C20°C
(WB)19°C15°C
(DB) 35°C 7°C
(WB)24°C6°C
15m or less
JIS B8615-1
CoolingHeating
RAS-18GKHP-ES2 / RAS-18GAH-ES2
15m or less
- 4 -
Page 6
2-1. Indoor Unit
FILE NO. SVM-06020
2. CONSTRUCTION VIEWS
75
7
51
Knock out system
Back body
Front panel
Grille inlet
298
Air inlet
Air outlet
998
75
56
220
Knock out system
50
50
75
8
Connection pipe (0.39 m)
(Flare ∅15.88)
Outline of indoor unit
55 or more
Minimum distance
to ceiling
298
∅65
100
20
48
998
763.5
450
Installation
Plate outline
- 5 -
Drain hose (0.54 m)
Connection pipe (0.49 m)
(Flare ∅6.35)
20
10
100
57
Wireless remote control
(For stud bolt ∅6)
(For stud bolt ∅8 -∅10)
29
41
55
5555
∅6
40
5
160
18
48
Page 7
2.2 Outdoor Unit (24 Class)
28
600
50
36
R
15
FILE NO. SVM-06020
A
124109
6 hole
321
307
Ø
R
5.5
A Detail Drawing (Back leg)
HANDLE
290
321
Ø
Ø
715
86
25 Drain outlet
FAN-GUARD
436
275
906009069
2Ø11x14 Hole
(For
Ø8-Ø
10 anchor bolt)
B
307
321
Hole
6
Ø
11x14 Hole
Ø
36
50
B Detail Drawing (Front leg)
321
342
R
15
HANDLE
COVER-PV
Z
100 or more
321
100 or more
Z View
600
Air inlet
Air out
let
00 or more
6
Installation dimension
600 or more
4x
54
129
84
11 Long holes(For
Ø
Service port
10 anchor bolt)
Ø8-Ø
Electrical part cover
Liquid side
(Flare Ø6.35)
Gas-side
(Flare Ø15.88)
- 6 -
Page 8
2.3 Outdoor Unit (18 Class)
28
600
50
36
321
307
A detail Drawing (Back leg)
R5.5
R
Ø
15
6 hole
86
321
Ø
FAN-GUARD
436
Ø
A
25 Drain outlet
109124
2
-
Ø
11 x 14
(For 8 -
Ø
Ø
Hole
10 anchor bolt)
FILE NO. SVM-06020
307
321
Ø
6 hole
11x14 hole
Ø
B Detail Drawing (Front leg)
36
50
R
15
COVER-PV
Z
290
550
275
321
342
Electrical part cover
Liquid side
(Flare 6.35)
Ø
Gas side
(Flare 12.7)
Ø
5
4
Service port
Z View
9060090
69
129
84
100 or more
321
100 or more
600
Air intlel
Air outlel
600 or more
Installation dimension
- 7 -
600 or more
4x 11 Long holes(For 8- 10 anchor bolt)
Ø
Ø
Ø
Page 9
3. WIRING DIAGRAM
3-1. RAS-24GKHP-ES2 / RAS-24GAH-ES2
COLOR IDENTIFICATION
BRW : BROWN
RED : RED
WHI : WHITE
YEL : YELLOW
BLU : BLUE
BLK : BLACK
GRY : GRAY
PNK : PINK
ORN : ORANGE
GRN : GREEN
GRN&YEL : GREEN & YELLOW
CN30
CN31
P04BLK
DSA
Varistor
F01
250V6.3A
MAIN P.C. BOARD
(WP-003)
Louver
motor
BLU
PNK
6
5223311
5
6
FILE NO. SVM-06020
Infrared rays receive
and Indication parts
BLU
RED
YEL
BRW
ORN
4
CN07
4
BLU
1 2 3 4 6510
98 1071 2 3
4 65
4 6
5
BLU
BLU
BLU
BLU
5 64
321
CN25
10
9871 2 3
BLU
BLU
BLU
WHI
98
7
CN13
10
8 9
7
+12 VDC
+5 VDC
WP-003
OUTDOOR
TERMINAL
BLOCK
C
S
R
COMPRESSOR TERMINAL
POWER SUPPLY
220- 240 V ~ 50 Hz
L
BLK
RED
BLK
RED
WHI
PNK
COMPRESSOR
i
N
FERRITE CORE
RED
MAGNETIC
CONTACTOR
R
S
1
1
GRN&YEL
T
A1
CN23
2
2
3
3
GRN&YEL
i
CHASSIS
Serial Signal
OUTDOOR
UNIT
52C
BLK
A2
W
RED
WHI
RED
FAN MOTOR
U
V
CAPACITORCAPACITOR
S
C
R
GRY
BRW
BLK
BLK
RED
RED
BLK
BLK
WHI
RED
GRY
BLU
YEL
BLU
BLU
COIL FOR
4 WAY VALVE
YEL
1
2
1
2
145 C
TEMP FUSE
1
1
2
CN06
3
3
1
1
CN05
3
3
SG01
1
1
3
3
250VAC T6. 3A
5
5
CN01
7
7
9
9
1
CN11
313
11
CN02
33
circuit
TRANSFORMER
BLKBLK
4
3
66554
3
MAIN P.C. BOARD (MCC-890)
TNR
R74
F01
TNR
R73
RY07
CR11
RY05
CR12
CR13
CN03
1
1
RY06
3
CN07
CN08
DISCHARGE
PIPE
SENSOR (TD)
BLU
1
1
2
3
3
BLU
BLK
1
1
2
3
3
BLK
HEAT
EXCHANGER
SENSOR (TE)
- 8 -
Page 10
3-2. RAS-18GKHP-ES2 / RAS-18GAH-ES2
COLOR IDENTIFICATION
BRW : BROWN
RED : RED
WHI : WHITE
YEL : YELLOW
BLU : BLUE
BLK : BLACK
GRY : GRAY
PNK : PINK
ORN : ORANGE
GRN : GREEN
GRN&YEL : GREEN & YELLOW
CN30
CN31
P04BLK
DSA
Varistor
F01
250V6.3A
MAIN P.C. BOARD
(WP-003)
Louver
motor
BLU
PNK
6
5223311
5
6
FILE NO. SVM-06020
Infrared rays receive
and Indication parts
BLU
RED
YEL
ORN
BRW
4
CN07
4
BLU
1 2 3 4 6510
98 1071 2 3
4 65
4 6
5
BLU
BLU
BLU
BLU
5 64
321
CN25
10
9871 2 3
WHI
BLU
BLU
BLU
98
7
CN13
10
8 9
7
+12 VDC
+5 VDC
WP-003
OUTDOOR
TERMINAL
BLOCK
C
S
R
COMPRESSOR TERMINAL
POWER SUPPLY
220-240 V~ 50 Hz
L
BLK
RED
BLK
RED
WHI
PNK
COMPRESSOR
CN23
INDOOR
TERMINAL
BLOCK
i
N
FERRITE CORE
RED
MAGNETIC
CONTACTOR
R
S
1
1
GRN&YEL
T
A1
2
3
2
3
i
CHASSIS
INDOOR
UNIT
OUTDOOR
UNIT
GRN&YEL
52C
BLK
A2
W
RED
WHI
D
RE
FAN MOTOR
U
V
CAPACITORCAPACITOR
S
C
R
Serial Signal
circuit
TRANSFORMER
YEL
BLK
BLK
RED
RED
BLK
BLK
WHI
RED
GRY
BLU
YEL
BLU
BLU
COIL FOR
4 WAY VALVE
BLK
GRY
BRW
1
3
1
3
1
3
5
7
9
1
313
11
33
1
2
4
3
1
2
66554
3
145 C
TEMP FUSE
MAIN P.C. BOARD (MCC-890)
1
2
CN06
3
1
CN05
3
1
3
5
CN01
7
9
SG01
F01
250VAC T6. 3A
TNR
R74
CN11
CR11
CN02
CR12
CR13
CN03
1
1
BLK
RY07
RY05
3
TNR
R73
RY06
CN07
CN08
DISCHARGE
PIPE
SENSOR (TD)
BLU
1
1
2
3
3
BLU
BLK
1
1
2
3
3
BLK
HEA
T
EXCHANGER
SENSOR (TE)
- 9 -
Page 11
3-3. RAS-24GKP-ES2 / RAS-24GA-ES2
COLOR IDENTIFICATION
BLK
CN27
BRW : BROWN
RED : RED
WHI : WHITE
YEL : YELLOW
BLU : BLUE
BLK : BLACK
GRY : GRAY
PNK : PINK
ORN : ORANGE
GRN : GREEN
GRN&YEL : GREEN & YELLOW
P04
6.3A
CN30
CN31
DSA
F01
Varistor
250V
Varistor
Louver
motor
BLU
PNK
6
5223311
6
5
FILE NO. SVM-06020
Infrared rays receive
and Indication parts
1 2 3 4 610
BLU
BLU
BLU
YEL
RED
BRW
ORN
4
CN07
4
BLU
1 2 3 4 6510
321
Power supply
circuit
Control
Fan motor
circuit
7
598
7
BLU
BLU
7
5 64
7
105 64321
8 9
CN25
BLU
BLU
BLU
WHI
98
CN13
10
8 9
OUTDOOR
TERMINAL
BLOCK
INDOOR
TERMINAL
BLOCK
POWER SUPPLY
220 − 240 V ~ 50 Hz
L
N
BLK
RED
BLK
RED
RED
1
1
BLKBLK
SPARK KILLER
A2 A1
52C
1/L1 2/T1
3/L2 4/T2
6/T35/L3
GRN&YEL
2
2
GRN&YEL
RED
CAPACITOR
3
3
GRY
CHASSIS
RED
WHI
PNK
COMPRESSOR
MAIN P.C. BOARD
(WP-003)
INDOOR
UNIT
OUTDOOR
UNIT
CAPACITOR
S
C
R
WHI
RED
FAN MOTOR
BLK
C
S
COMPRESSOR TERMINAL
2
1
21
1
GRY
BRW
YEL
1
2
6
4
3
1
2
6
554
3
145 C
TEMP FUSE
BLK2BLK
Thermo.
sensor
(TA)
CN03
Heat exchanger
sensor
(TC)
CN01
2
1
BLK
BLK
BLK
R
MAGNETIC CONTACTOR
- 10 -
Page 12
3-4. RAS-18GKP-ES2 / RAS-184GA-ES2
COLOR IDENTIFICATION
BRW : BROWN
RED : RED
WHI : WHITE
YEL : YELLOW
BLK
GRN&YEL
BLU : BLUE
BLK : BLACK
GRY : GRAY
PNK : PINK
ORN : ORANGE
GRN : GREEN
GRN&YEL : GREEN & YELLOW
P04
CN30
CN31
CN27
6.3A
Varistor
DSA
F01
250V
MAIN P.C. BOARD
(WP-003)
Varistor
Louver
motor
BLU
YEL
PNK
6
5223311
4
6
5
4
FILE NO. SVM-06020
Infrared rays receive
and Indication parts
598
1 2 3 4 610
BLU
BLU
BLU
BLU
BLU
RED
BRW
ORN
CN07
Power supply
circuit
Control
Fan motor
circuit
GRY
BRW
YEL
BLU
1 2 3 4 6510
5 64
321
105 64321
8 9
7
7
BLU
7
7
8 9
CN25
BLU
BLU
WHI
98
CN13
10
2
1
21
1
BLK2BLK
CN03
CN01
2
1
BLK
BLK
OUTDOOR
TERMINAL
BLOCK
POWER SUPPLY
220 − 240 V ~ 50 Hz
L
BLK
MAGNETIC
CONTACTOR
BLK
RED
INDOOR
TERMINAL
BLOCK
N
RED
R
U
1
1
GRN&YEL
S
V
2
2
RED
SPARK KILLER
T
W
BLK
1
2
4
3
1
2
66554
3
145 C
TEMP FUSE
GRN&YEL
GRY
INDOOR
UNIT
OUTDOOR
UNIT
3
3
BLK
CHASSIS
(or A)
A1
(or B)
A2
Thermo.
sensor
(TA)
Heat exchanger
sensor
(TC)
CAPACITOR
RED
S
WHI
PNK
R
COMPRESSOR
S
COMPRESSOR TERMINAL
CAPACITOR
RED
C
BLK
WHI
RED
BLK
FAN MOTOR
C
R
- 11 -
Page 13
FILE NO. SVM-06020
4. SPECIFICATION OF ELECTRICAL PARTS
4-1. Indoor Unit (RAS-24GKHP-ES2, RAS-18GKHP-ES2)
No.Parts nameTypeSpecifications
1 Fan motor (for indoor) AFS-220-31-4A AC 200 − 240V, 31W
2Thermo sensor (TA-sensor)———10 kΩ at 25°C
3 Micro Power Module (M01) µRM1260V DC 390 V, Secondary DC 12 V
4MicrocontrollerTMP87CM40AN
5Heat exchanger sensor
(TC-sensor)
6 Line filter (L01) LC*SS11V-06270 27mH, 600mA
7Diode (DB01)D3SBA604 A, 600 V
8 Capacitor (C63) EKMH401VSN470MP20S 4.7µF, 400 V
9 Fuse (F01) BET6.3A T6.3 A, 250 V
10 Varistor (R21, R22) TND15G561K 560 V
11 Resistor (R319) RF-2TK5R65.6Ω , 2 W
12 Louver motor 35BYJ46Output (Rated) 2 W, 10 poles, 1 phase,
1 Fan motor (for indoor) AFS-220-31-4A AC 200 − 240V, 31W
2Thermo sensor (TA-sensor)———10 kΩ at 25°C
3 Micro Power Module (M01) µRM1260V DC 390 V, Secondary DC 12 V
4MicrocontrollerTMP87CM40AN
5Heat exchanger sensor
(TC-sensor)
6 Line filter (L01) LC*SS11V-06270 27mH, 600mA
7Diode (DB01)D3SBA604 A, 600 V
8 Capacitor (C63) KMH400VSSN47M22S4.7µF, 400 V
9 Fuse (F01) BET6.3A T6.3 A, 250 V
10 Varistor (R21, R22) TND15G561K 560 V
11 Resistor (R319) RF-2TK5R6 5.6Ω, 2 W
12 Louver motor
13Relay : (RY04) G5NB-1A Coil DC 12V, 16.7mA, Contact AC 250V, 1A
Low temperature 2.0 32.0 High 20/––10/–10
Standard 0.9 9.5 High 27/19 35/24
Cooling Overload 1.1 12.6 High 32/23 43/26
Low temperature 0.7 2.4 Low 21/15 21/15
Note :
• Measure the heat exchanger temperature at the center of U-bend. (By means of TC sensor)
*1 • During heating overload operation, a value for the high temperature limit control operation is included.
- 16 -
Page 18
5-3. RAS-24GKP-ES2 / RAS-24GA-ES2
FILE NO. SVM-06020
0.39m
(Connecting pipe)
12.7
∅
O.D.:12.7mm
Cooling
Compressor
Indoor unit
Cooling
P
Packed valve
(∅
12.7)
Gas container connection (Reinstall etc.)
Accumulator
PA290X3CS-4MU1
Heat exchanger
Cross flow fan
T1
Packed valve
∅
6.35)
(
Capillary tube
2.0x900
∅
s
0.49m
(Connecting pipe)
∅
6.35
O.D.:6.35mm
Condenser
Refrigerant
R410A 1.70kg
)means check points of Gas Leak.
Cooling
Propeller fan
Outdoor unit
Mark(
Ambient temp.
50Hz
Standard
pressure
(MPaG)
P
Surface temp. of heat
exchanger interchanging
pipe
T1
(° C)
Fan speed
(indoor)
conditions DB/WB
(° C)
Indoor Outdoor
Standard 3.183 7.0 High 27/19 35/24
Cooling Overload 4.040 11.7 High 32/23 43/26
Low temperature 1.651 -0.4 Low 21/15 21/15
Note :
• Measure the heat exchanger temperature at the center of U-bend. (By means of TC sensor)
- 17 -
Page 19
5-4. RAS-18GKP-ES2 / RAS-18GA-ES2
FILE NO. SVM-06020
0.39m
(Connecting pipe)
∅
12.7
O.D.:12.7mm
Cooling
Compressor
Indoor unit
Cooling
P
Packed valve
(
∅
12.7)
PA225X2CS-4KU1
Evaporator
Cross flow fan
T1
Packed valve
∅
6.35)
(
Capillary tube
1.7x400
∅
s
0.49m
(Connecting pipe)
∅
6.35
O.D.:6.35mm
Condenser
Cooling
Propeller fan
Outdoor unit
Mark(
Refrigerant
R410A 1.
)means check points of Gas Leak.
26 kg
Ambient temp.
50Hz
Standard
pressure
(MPaG)
P
Surface temp. of heat
exchanger interchanging
pipe
T1
(°C)
Fan speed
(indoor)
conditions DB/WB
(°C)
IndoorOutdoor
Standard 1.1 10.0 High 27/19 35/24
Cooling Overload 1.2 13.0 High 32/23 43/26
Low temperature 0.6 2.0 Low 21/15 21/15
Note :
• Measure the heat exchanger temperature at the center of U-bend. (By means of TC sensor)
- 18 -
Page 20
6. CONTROL BLOCK DIAGRAM
6-1. RAS-24GKHP-ES2, RAS-18GKHP-ES2
Indoor Unit Control Panel
Heat Exchanger Sensor
Functions
• Louver Control
FILE NO. SVM-06020
M.C.U.
Operation
Display
Temperature Sensor
Infrared Rays Signal Receiver
Infrared
Rays
Remote
Control
From Outdoor Unit
220 ~ 240 V AC 50 Hz
Initiallizing Circuit
Clock Frequency
Oscillator Circuit
Power Supply
Circuit
Noise Filter
• 3-minute Delay at Restart for Compressor
• Motor Revolution Control
• Processing
(Temperature Processing)
• Timer
• Serial Signal Communication
Louver ON/OFF Signal
Louver Driver
Serial Signal Transmitter/Receiver
Serial Signal Communication
Timer
Display
Filter Sign
Display
PRE DEF.
Sign Display
Hi Power
Sign Display
Indoor
Fan Motor
Louver Motor
REMOTE CONTROL
Infrared Rays
Remote Control
Operation ()Operation ( )
Operation Mode Selection
AUTO, COOL, DRY, HEAT, FAN ONLY
Temperature Setting
Fan Speed Selection
ON TIMER Setting
OFF TIMER Setting
Louver Auto Swing
Louver Direction Setting
ECO
Hi power
TIMER 1.3.5.9H
COMFORT SLEEP
QUIET
- 19 -
Page 21
6-2. RAS-24GKP-ES2, RAS-18GKP-ES2
Indoor Unit Control Panel
Heat Exchanger Sensor
Functions
Louver Control
FILE NO. SVM-06020
M.C.U.
Operation
Display
Temperature Sensor
Infrared Rays Signal Receiver
Infrared
Rays
Remote
Control
From Outdoor Unit
220 ~ 240V AC 50Hz
Initiallizing Circuit
Clock Frequency
Oscillator Circuit
Power Supply
Circuit
Noise Filter
3-minute Delay at Restart for Compressor
Motor Revolution Control
Processing
(Temperature Processing)
Timer
Outdoor unit
ON/OFF Signal
Relay Driver
Relay RY04
Outdoor Unit
Louver ON/OFF Signal
Louver Driver
Timer
Display
Filter Sign
Display
Fan Only
Sign Display
Hi Power
Sign Display
Indoor
Fan Motor
Louver Motor
REMOTE CONTROL
Infrared Rays
Remote Control
Operation ()Operation ( )
Operation Mode Selection
AUTO, COOL, DRY, FAN ONLY
Temperature Setting
Fan Speed Selection
ON TIMER Setting
OFF TIMER Setting
Louver Auto Swing
Louver Direction Setting
ECO
Hi power
TIMER 1.3.5.9H
COMFORT SLEEP
QUIET
- 36 -
Page 22
7. OPERATION DESCRIPTION
7-1.Outline of Air Conditioner Control
This is a fixed capacity type air conditioner, which uses
a AC motor for an indoor fan. The AC motor drive
circuit is mounted in the indoor unit. And electrical
parts which operate the compressor and the outdoor
fan motor, are mounted in the outdoor unit.
The air conditioner is mainly controlled by the indoor
unit controller. The controller operates the indoor fan
motor based upon commands transmitted by the
remote control and transfers the operation commands
to the outdoor unit controller.
The outdoor unit controller receives operation
commands from the indoor unit, and operates the
outdoor fan motor and the compressor.
(1) Role of indoor unit controller
The indoor unit controller receives the operation
commands from the remote control and executes
them.
·Temperature measurement at the air inlet of the
indoor heat exchanger by the indoor
temperature sensor
· Temperature setting of the indoor heat
exchanger by the heat exchanger sensor
· Louver motor control
· Indoor fan motor operation control
· LED display control
· T ransferring of operation commands to the
outdoor unit
· Receiving of information of the operation status
and judging of the information or indication of
error
(2) Role of outdoor unit controller
The outdoor unit controller receives the operation
commands from the indoor controller and
executes them.
FILE NO. SVM-06020
· Compressor operation
control
· Operation control of
outdoor fan motorf
Turning off the compressor and outdoor fan
·
when the outdoor unit receives the shutdown
command
· Defrost control in heating operation
(Temperature measurement by the outdoor heat
exchanger and control for the four-way valve
and the outdoor fan motor) *Heat pump Model
only
7-1-1. Louver contr
ol
(1) Vertical air flow louver
Position of veritcal air flow louver is automatically
controlled according to the operation mode.
Besides, position of vertical air flow louver can be
arbitrarily set by pressing [FIX] button.
The louver position which is set by [FIX] button is
stored in the microcomputer, and the louver is
automatically set at the stored position for the next
operation.
(2) Swing
If [SWING] button is pressed when the indoor unit
is in operation, the vertical air flow louver starts
swinging. When [FIX] button is pressed, it stops
swinging.
7-1-2. Indoor fan control (AC Fan motor)
(1) The indoor fan is operated by the stepless speed
change AC motor
.
(2) For air flow level, speed of the indoor fan motor is
controlled in five steps (LOW, LOW
and HIGH). If AUTO mode is selected, the fan
motor speed is automatically controlled by the
difference between the preset temperature and
the room temperature.
Operations according
to the commands
from the indoor unit
+
, MED, MED
+
Table 7-1-1
FAN TAP
OPERATION
MODE
RAS-24GKHP Series
RAS-18GKH Series
Model
RAS-24GKP Series
RAS-18GKP Series
Cooling
Heat
Fan Only
Dry
rpm
Air Flow volume(m /h)
rpm
Air Flow volume(m /h)
rpm
Air Flow volume(m /h)
rpm
Air Flow volume(m /h)
3
3
3
3
900
−
−
−
−
1300
900
UHH
HM+M
13001300
900
1300
900
1300
900
M+
M+M
1250 1200
830
1150
750
1250
830
1150
750
ML+
MUHH
115010501000 900 800700
790
750
1100
1050
667
708
1150
−
−
750
1050
−
667
−
Note : Under some function of setting. The fan motor is controlled automatically.
Then LOW+ = LOW + MED and MED
2
+
= MED + HIGH
2
- 20 -
LL-UL SUL/SL-
380
600
300
700
380
600
300
SUL/SL-
600
300
500
220
−
−
−
−
LLLL-
625
900
543
1000
625
900
543
UL
ULSUL
461
543
700
800
380
461
800
900
461
543
700
800
380
461
L-LL+
L+
L+
667
950
584
1050
−
−
667
950
−
584
−
Page 23
FILE NO. SVM-06020
7-2. Description of Operation Circuit
(1) When turning on the breaker, the operation lamp
blinks. This means that the power is on (or the
power supply is cut off.)
(2) When pressing [ ] button on the
remote control, receiving beep sounds from the
indoor unit, and the next operation is performed
together with opening the vertical air flow louver.
(3) Once the operation mode is set, it is memorized in
the microcomputer so that the previous operation
can be effected thereafter simply by pressing
[ ] button.
7-2-1. Fan only operation
([MODE] button on the remote control is set
to the fan only operation.)
(1) When [FAN] button is set to AUTO, the indoor fan
motor operates as shown in Fig. 7-2-1. When
[FAN] button is set to LOW, LOW
HIGH, the motor operates with a constant air flow.
+
, MED, MED+ or
7-2-2. Cooling operation
([MODE] button on the remote control is set
to the cooling operation.)
(1) The compressor, 4-way valve, outdoor fan and
operation display lamp are controlled as shown in
Fig. 7-2-2.
ON
4-way valve
Compressor
Outdoor fan
(Heat pump model)
Preset
temp.
0.5
ON
OFF OFF OFF ON
0
Fig. 7-2-2
display lamp
OPERATION
+3
+2.5
(Preset temp.)
-
+2
+1.5
+1
+0.5
(Room temp.)
Preset
temp.
0
(Preset temp.: 24°C)
NOTE :
*1: The values marked with *1 are calculated and
controlled by the difference in motor speed
between M+ and L-.
(2)
The Hi Power, ECO and COMFORT SLEEP
operation cannot be set.
Fig. 7-2-1 Setting of air flow [FAN:AUTO]
M+
*1
*1
*1
(2) When [FAN] button is set to AUTO, the indoor fan
motor operates as shown in Fig. 7-2-3. When
[FAN] button is set to LOW, LOW
+
, MED, MED+ or
HIGH, the motor operates with a constant air flow.
(Preset temp.)
-
(Room temp.)
Preset
temp.
+3
+2.5
+2
+1.5
+1
+0.5
0
-0.5
M+
*1
*1
*1
NOTE :
*1: The values marked with *1 are calculated and
controlled by the difference in motor speed
between M+ and L-.
Fig. 7-2-3 Setting of air flow [FAN:AUTO]
- 21 -
Page 24
FILE NO. SVM-06020
7-2-3. Dry operation
([MODE] button on the remote control is set
to the dry operation.)
(1) The compressor, 4-way valve, outdoor fan and
operation display lamp are controlled as shown in
Fig. 7-2-4.
ON:6min.
OFF:4min.
ON:5min.
OFF:5min.
OFF
4-way valve
Outdoor fan
Preset
temp.
+3
+2
+1
ON:6min.
OFF:4min.
OFF
ON:5min.
OFF:5min.
OFF
0
Compressor
Fig. 7-2-4
ON
display lamp
OPERATION
7-2-4. Heating operation *Heat pump model only
([MODE] button on the remote control is set
to the heating operation.)
(1) The compressor, 4-way valve, outdoor fan and
operation display lamp are controlled as shown in
Fig. 7-2-6.
Preset
temp.
OFF
ON
ON
Compressor
ON
OFF
ON
4-way valve
Outdoor fan
OPERATION
Fig. 7-2-6
display lamp
(2) The microprocessor turns the compressor on and
off at the regular intervals (4 to 6 minutes). While
the compressor is turning off, the indoor fan motor
operates in the SUPER LOW position.
The pattern of operation depending on the relation
between room temperature and preset
temperatures is shown in Fig. 7-2-5.
Room temp.
Preset temp.+1
Preset temp.
Compressor
Outdoor fan
Indoor fan
ONONONON
OFFOFFOFF
L. *S.L.S.L.L.L.S.L.L.
*Super Low
Fig. 7-2-5
(3) [FAN] button on the remote control is set to AUTO
only.
(2) When [FAN] button is set to AUTO, the indoor fan
motor operates as shown in Fig. 7-2-7. When
[FAN] button is set to LOW, LOW
+
, MED, MED+ or
HIGH, the motor operates with a constant air flow.
Preset
temp.
0
-0.5
-1
-1.5
-2
-5.0
-5.5
[FAN AUTO]
L
*1
*2
+
M
H
*1, *2 : The values marked with *1 and *2 are
calculated and controlled by the difference in
motor speed between M+ and L.
Fig. 7-2-7 Setting of air flo w [FAN:AUTO]
(4) The ECO and Hi Power operations can not be set.
- 22 -
Page 25
FILE NO. SVM-06020
(3) The indoor heat exchanger restricts revolving
speed of the fan motor to prevent a cold draft. The
upper limit of the revolving speed is shown in
Fig. 7-2-8 and Table 7-2-1.
Manual
(One of
AUTO
*4
SUL*
SUL*1
Stop
5 speed)
L-H
(Up to
setting
3
speed)
*2
A+4 A+4
464534
33
3321
3220
A-8 A-8
*6*5
NOTES :
*1: The fan stops for 2 minutes after thermostat-OFF.
*2: A is 24°C when the preset temperature is 24°C or
more and A is the preset temperature when it is
under 24°C.
*3: SUL means Super Ultra Low.
*4: Calculated from difference in motor speed
between SUL and HIGH.
7-2-5. Automatic operation
([MODE] button on the remote control is set
to the automatic operation.)
(1) One of 3 operations (Cooling, Fan only or Heating)
is selected according to difference between the
preset temperature and the room temperature at
which the automatic operation has started, as
shown in Fig. 7-2-9. The Fan only operation
continues until the room temperature reaches a
level at which another mode is selected.
(2) Temporary Auto
When the TEMPORARY button on the indoor unit
is pushed, the preset temperature is fixed at 24°C
and the indoor unit is controlled as shown in
Fig. 7-2-9.
C
Cooling operation
The louver moves to the position same
as Hi POWER operation.
+4
Cooling operation
0
Fan only operation
Fig. 7-2-8 Cold draft preventing control
*5 and *6:
Table 7-2-1
Fan*5*6
speedStarting periodStabilized period
AUTO • Up until 12 minutes
passed after starting
the unit
• From 12 to 25 minutes
passed after starting
the unit and room
temperature is 3°C
lower than preset
temperature
Manual • Room temperature
(L - H)< Preset temperature
• From 12 to 25 minutes
passed after starting
the unit and room
temperature is
between preset
temperature and 3°C
lower than preset
temperature
• 25 minutes or more
passed after starting
the unit
• Room temperature
Preset temperature
-4°C
-3.5°C
Heating operation
(Room temp.) - (Preset temp.)
RAS-24GKHP-ES2
RAS-18GKHP-ES2
RAS-24GKP-ES2
RAS-18GKP-ES2
Fig. 7-2-9
- 23 -
Page 26
FILE NO. SVM-06020
62
55
54
Compressor
Outdoor fan
OFF
OFF
ON
ON
OFF
ON
Heat exchanger
temp.
7-3.Hi POWER Mode
([Hi POWER] button on the remote
control is pressed.)
When [Hi POWER] button is pressed while the indoor
unit is in Auto, Cooling or Heating operation,
Hi POWER mark is indicated on the display of the
remote control and the unit operates as follows.
(1) Automatic operation
· The indoor unit operates in according to the
current operation.
(2) Cooling operation
· The preset temperature drops 3°C.
(The value of the preset temperature on the
remote control does not change.)
·
If the room temperature is higher than the
setting temperature by 3.5 °C or more, the
horizontal louver moves to the Hi POWER
position automatically. Then when the room
temperature is °C less than the setting
temperature the horizontal louver returns
automatically.
·
FAN speed : [AUTO]
If the temperature is higher than thesetting temperature by 3.5°C or mor, the
air conditioner operates at maxim airflow
level. If the temperature is higher than the
setting temperature by less than 3.5°C, the air
conditioner operates at normal airflow level.
·
FAN speed : One of 5 levels
If the temperature is higher than the
setting temperature by 3.5°C or more, the
air conditioner operates at higher consecutive
airflow level. If the room temperature is higher
than the setting temperature by less than 3.5°C,
the air conditioner operates at normal airflow
level.
7-4.High-Temperature Limit Control
*Heat pump model only
The microcontroller detects the indoor heat exchanger
temperature to prevent pressure of a refrigerating cycle
from increasing excessively.
The compressor and outdoor fan motor are controlled
as shown in Fig. 7-4-1.
Fig. 7-4-1
7-5.Low-Temperature Limit Control
The microcontroller detects the indoor heat exchanger
temperature to prevent the indoor heat exchanger from
freezing.
·
The compressor and outdoor fan motor are controlled
as shown in Fig. 7-5-1.
Heat exchanger
temperature
6
2
Compressor Outdoor fan
ON
Less than continues
for 5 minutes
OFF
Fig. 7-5-1
7-6.Defrost Operation *Heat pump model only
(3) Heating operation (UKH Series only)
·
The preset temperature increases 2°C,
(The value of the preset temperature on the
remote control does not change.)
The indoor unit operates in normal heating
·
mode except the preset temperature is higher
(+2°C).
(4) The Hi POWER mode can not be set in Dry or
Fan only operation.
When the indoor unit is in heating operation, if the
refrigerant evaporation temperature detected by the
outdoor heat exchanger sensor is under the specified
temperature, the outdoor unit starts the defrosting
operation. At this time, the 4-way valve relay and the
outdoor fan motor are turned off. The indoor fan motor
is also turned off by the cold draft preventing control of
the indoor microcomputer. Then, [PRE. DEF.] lamp on
the indoor unit comes on.
The defrosting operation stops and the 4-way valve
relay, outdoor fan motor and the indoor fan motor are
turned on automatically when the refrigerant
evaporation increases to the specified temperature, or
when the defrosting time is over 12 minutes.
- 24 -
Page 27
FILE NO. SVM-06020
7-6-1. Defrost starting condition
A-Zone : If -10°C > Teo ≥ − 18°C, defrost will
start when.
Teo - Te ≥ 2.5°C at teat 20 sec or
~ 30 min after operation.
B-Zone : If Te ≤ −18°C, defrost start instantaneously
(Suddenly) 00 ~ 25 min ofter operation
C-Zone : If -2ºC ≥ Teo ≥ −10°C defrost will start when
Teo - Te ≤ −3°C at least 20 sec or ~ 60 min
after operation.
7-6-2. Defrost finish condition.
1) If Te ≥ 3°C at least 60 sec -->4 way value on.
2) If Te ≥ 8°C --> 4 way value on.
Timing
Operation time (4 Loops = Tt)
Td1
Td2
Td3 Td4
Finish time recordStart time record
Defrost time rate : (Td/Tt) x 100
Heating time rate : (Tt - Td) x Tt
Fig. 7-6-2
- 25 -
Page 28
FILE NO. SVM-06020
7-7. Auto Restart Function
The indoor unit is equipped with an automatic
restarting function which allows the unit to restart
operating with the set operating conditions in the event
of power supply being accidentally shut down. The
operation will resume without warning three minutes
after power is restored.
This function is not set to work when shipped from the
factory. Therefore it is necessary to set it to work.
7-7-1. How to set auto restart function
To set the auto restart function, proceed as follows:
The power supply to the unit must be on; the function
will not set if the power is off.
Push the [TEMPORARY] button located in the center
of the front panel continuously for three seconds.
The unit receives the signal and beeps three times.
The unit then restarts operating automatically in the
event of power supply being accidentally shut down.
When the unit is on standby (Not operating)
Operation Motions
Push [TEMPORARY] button for more The unit is on standby.
than three seconds.
The unit starts to operate. The green lamp is on.
→
→
After approx. three seconds,
The unit beeps three times The lamp changes from
and continues to operate. green to orange.
If the unit is not required to operate at this time, push [TEMPORARY]
TEMPORARY button
TEMPORARY button
0
0
3S
3S
button once more or use the remote control to turn it off.
When the unit is in operation
Operation Motions
Push [TEMPORARY] button for more The unit is in operation. The green lamp is on.
than three seconds.
The unit stops operating. The green lamp is turned off.
→
→
After approx. three seconds,
0
TEMPORARY button
TEMPORARY button
0
3S
3S
The unit beeps three times.
If the unit is required to operate at this time, push [TEMPORARY]
button once more or use the remote control to turn it on.
• While this function is being set, if the unit is in
operation, the orange lamp is on.
• This function can not be set if the timer operation
• While the filter check lamp is on, the
[TEMPORARY] button has the function of filter
reset button.
has been selected.
• When the unit is turned on by this function, the
louver will not swing even though it was swinging
automatically before shutting down.
- 26 -
Page 29
7-7-2. How to cancel auto restart function
To cancel auto restart function, proceed as follows:
Repeat the setting prodedure: the unit receives the
signal and beeps three times.
The unit will be required to be turned on with the
remote control after the main power supply is turned
off.
When the unit is on standby (Not operating)
Operation Motions
Push [TEMPORARY] button for more The unit is on standby.
than three seconds.
→
FILE NO. SVM-06020
The unit starts to operate. The orange lamp is on.
→
After approx. three seconds,
The unit beeps three times The lamp changes from
and continues to operate. orange to green.
If the unit is not required to operate at this time, push [TEMPORARY]
TEMPORARY button
TEMPORARY button
0
0
3S
3S
button once more or use the remote control to turn it off.
When the unit is in operation
Operation Motions
Push [TEMPORARY] button for more The unit is in operation. The orange lamp is on.
than three seconds.
The unit stops operating. The orange lamp is turned off.
→
→
After approx. three seconds,
0
0
3S
3S
TEMPORARY button
TEMPORARY button
• While this function is being set, if the unit is in
The unit beeps three times.
If the unit is required to operate at this time, push [TEMPORARY]
button once more or use the remote control to turn it on.
7-8. Filter Check Lamp
operation, the orange lamp is on.
When the elapsed time reaches 1000 hours, the filter
7-7-3. Power failure during timer operation
check lamp indicates. After cleaning the filters, turn off
the filter check lamp.
When the unit is in Timer operation, if it is turned off
because of power failure, the timer operation is
7-8-1. How to turn off filter check lamp
cancelled. Therefore, set the timer operation again.
Press [FILTER] button on the remote control.
OR push [TEMPORARY] button on the indoor unit.
Note:
If [TEMPORARY] button is pushed while the filter
check lamp is not indicating, the indoor unit will start
the Automatic Operation.
- 27 -
Page 30
y
y
g
g
play
g
(
(
y
p
g
)
y
g Op
g
g
p
g
g
y
g
(
(
y
g
g
)
y
g
g
g
p
FILE NO. SVM-06020
7-9. Self-Cleaning function.
Self-Cleaning function is designed to reduce humidity that causes mold to form inside the air conditioning unit.
This advanced, efficient s
fan activates and dries the moisture in the coil for 20 minutes, then turns off automaticall
stem reduces moisture in the coil. When you turn off your air conditioner, the internal
.
Operation display
FCU fan
FCU louverOPENCLOSECLOSE
Timer display
Compressor
CDU fan
rpm is depend on preseting.rpm is SUL speed.
depend on preseting of timer function.depend on preseting of timer function.
depend on preseting per room temperature.
depend on preseting per room temperature.
Cool mode or dry modeSelf-Cleaning mode
operation more than 10 mins.operate 20 mins.
ONOFFOFF
ONON
ON or OFF
ON or OFF
ON or OFF
Turn off by remote controller
or timer-off function.
ON
OFFOFF
OFFOFF
Automatically turn-off.
ON or OFF
• The Self-Cleaning function is set as default at ex-factory.
• Self-Cleaning operation can stop manually by press [ ] botton of the remotecontrol two more time.
7-9-1. How to cancel Self-Cleanin
To cancel the Self-Cleanin
Press [TEMPORARY] button one time or use remote control to
•
function, proceed as follows:
function
turn on air conditioner. The OPERATION dis
oran
e color (When AUTO-RESTART is ON) or green color
When AUTO-RESTART is OFF).
Hold down the [TEMPORARY] button for more than 20 seconds.
•
The air conditioner will stop suddenl
when the [TEMPORARY] is
ressed but keep holding it continue. Then will beep 3 times in
the first 3 seconds but it is not related to Self-Cleanin
After holding about 20 seconds, the air conditioner will beep 5
•
times without an
The Self-Cleanin
•
blinking of display.
eration had been concelled.
OFF
Operation time
will show in
function
TE MPO R AR Y buttonTE MPO R AR Y button
Remarks
Per settin
•
of Self-Cleaning function above, AUTO-RESTART
function had been cancelled. To set AUTO-RESTART a
lease follow item 7-7-1.
7-9-2. How to set Self-Cleanin
To set the Self-Cleanin
Press [TEMPORARY] button one time or use remote control to
•
function, proceed as follows.
turn on air conditioner. The OPERATION displa
e color (When AUTO-RESTART is ON) or green color
oran
function.
will show in
When AUTO-RESTART is OFF).
Hold down the [TEMPORARY] button for more than 20 seconds.
•
The air conditioner will stop suddenl
pressed but keep holdin
it continue. Then will beep 3 times is
the first 3 seconds but it is not related to Self-Cleanin
After holding about 20 seconds, the air conditioner will beep
•
5 times and OPERATION displa
The Self-Cleanin
•
function had been set.
when the [TEMPORARY] is
function
blinks 5 times.
Remarks
Per settin
•
of Self-Cleaning function above, AUTO-RESTART
function had been cancelled. To set AUTO-RESTART a
lease follow item 7-7-1.
- 28 -
ain,
ain,
Page 31
FILE NO. SVM-06020
7-10. QUIET Mode
Quiet mode is the system which, control the
revolving speed of indoor fan to work constantly
at lower than speed L. In addition, noise level of
indoor unit is less than usual.
When the [QUIET] button is pressed, the fan of the
indoor unit will be restricted the revolving speed at
speed L
again (cancel Quiet mode).
Remarks :
1. Quiet mode is unable to work in dry mode.
2. Quiet mode is appropriate to work with less
-
until the [QUIET] button is pressed once
cooling load and less heating load condition.
Because of the fan speed L- may cause not
enough the cooling capacity or heating capacity.
7-11. COMFORT SLEEP mode
The principles of comfort sleep mode are:
• Quietness for more comfortable.
• Save energy by changing room temperature
automatically.
• The air condition can shut down by itself
automatically.
7-11-1. Cooling mode
• The fan speed of indoor unit operates automatically,
it relates with the compressor's operation.
Compressor’s Operation Fan Speed
-
ONL
OFF SL
• The preset temperature will increase 1°C after the
Comfort sleep mode has operated for 1 hour and
the temperature will increase another 1°C after the
comfort sleep mode has operated for 2 hour. (The
value of the preset temperature on the remote control
does not change.)
• Press the [COMFORT SLEEP] button to choose the
operating hours. Repeat pressing to select the hours.
(1hr, 3hr, 5hr or 9hr)
• If the [COMFORT SLEEP] button is pressed again
means cancel comfort sleep mode.
7-11-2. Heating mode
• The fan speed of indoor unit operates automatically,
it relates with the compressor's operation.
Compressor’s Operation Fan Speed
ON L
OFF SL
-
Remarks:
1. Comfort sleep mode will not operate in dry mode
and fan only mode.
2. Comfort sleep mode is appropriate to work with less
cooling load and less heating load condition.
Because of the fan speed L- may cause not enough
the cooling capacity or heating capacity.
• The preset temperature will drop down 1°C after the
comfort sleep mode has operated for 1 hour and the
temperature will decrease another 1°C after the
comfort sleep mode has operated for 2 hour. (The
value of the preset temperature on the remote control.
dose not change.)
• Press the [COMFORT SLEEP] button to choose the
operating hours. Repeat pressing to select the hours.
(1hr, 3hr, 5hr or 9 hr)
• If the [COMFORT SLEEP] button is pressed again
means cancel comfort sleep mode.
- 29 -
Page 32
FILE NO. SVM-06020
8-3-3. Installation/Servicing tools
<Changes in the product and components>
In the case of an air conditioner using R410A, in order to prevent any other refrigerant from being charged
accidentally, the service port diameter of the outdoor unit control valve (3 way valve) has been changed. (1/2
UNF 20 threads per inch)
•
In order to increase the pressure withstand strength of the refrigerant piping, flare processing diameter and
size of opposite side of flare nuts have been changed. (for copper pipes with nominal dimensions 1/2 and 5/8)
New tools for R410A
New tools for R410A Applicable to R22 model Changes
Gauge manifold As pressure is high, it is impossible to measure by
means of conventional gauge. In order to prevent
any other refrigerant from being charged, each
port diameter has been changed.
Charge hose In order to increase pressure withstand strength,
hose materials and port size have been changed
(to 1/2 UNF 20 threads per inch).
When purchasing a charge hose, be sure to
confirm the port size.
Electronic balance As pressure is high and gasification speed is fast,
for refrigerant charging it is difficult to read the indicated value by means
of a charging cylinder, as air bubbles occur.
Torque wrench The size of opposing side of flare nuts have been
(nominal dia. 1/2, 5/8) increased.
Incidentally, a common wrench is used for nominal
diameters 1/4 and 3/8.
Flare tool By increasing the clamp bar’s receiving hole,
(clutch type) strength of spring in the tool has been improved.
Gauge for projection Used when flare is made by using conventional
flare adjustment tool.
Vacuum pump adapter Connected to conventional vacuum pump. It is
Gas leakage detector Exclusive for HFC refrigerant.
—
necessary to use an adapter to prevent vacuum
pump oil from flowing back to the charge hose.
The charge hose connecting part has two portsone for conventional refrigerant (7/16 UNF 20
threads per inch) and one for R410A. If the
vacuum pump oil (mineral) mixes with R410A,
a sludge may occur and damage the equipment.
• Incidentally, the “refrigerant cylinder” comes with the refrigerant designation (R410A) and protector coating in
the U. S’s ARI specified rose color (ARI color code: PMS 507).
• Also, the “charge port and packing for refrigerant cylinder” require 1/2 UNF 20 threads per inch
corresponding to the charge hose’s port size.
- 35 -
Page 33
8. INSTALLATION PROCEDURE
8-1. Safety Cautions
For general public use
Power supply cord of Outdoor unit shall be more than 4 mm
sheathed flexible cord) or 3.5 mm2 (AWG-12).
FILE NO. SVM-06020
2
(H07RN-F or 245 IEC66 : polychloroprene
CAUTION
•
THIS AIR CONDITIONER USES THE NEW HFC REFRGERANT (R410A), WHICH DOES NOT DESTROY
THE OZONE LAYER.
R410A refrigerant is apt to be affected by impurity such as water, oxidizing membranes, and oils because the
pressure of R410A refrigerant is approx. 1.6 times of refrigerant R22. As well as the adoption of this new
refrigerant, refrigerating machine oil has also been changed. Therefore, during installation work, be sure that
water, dust, former refrigerant, or refrigerating machine oil does not enter into the refrigerating cycle of a
new-refrigerant air conditioner.
To avoid mixing refrigerant and refrigerating machine oil, the sizes of charging port connecting sections on
the main unit are different from those for the conventional refrigerant, and different size tools are also
required. Accordingly, special tools are required for the new refrigerant (R410A) as shown below. For
connecting pipes, use new and clean piping materials with high-pressure withstand capabilities, designed for
R410A only, and ensure that water or dust does not enter. Moreover, do not use any existing piping as its
pressure withstand may be insufficient, and may contain impurities.
CAUTION
This appliance must be connected to the main power supply by means of a circuit breaker or a switch with a
contact separation of at least 3 mm.
If this is not possible, a power supply plug with earth must be used. This plug must be easily accessible after
installation. The pl
appliance completely from the mains.
New Refrigerant Air conditioner Installation
To Disconnect the Appliance from the Main Power Supply.
ug must be disconnected from the power supply socket in order to disconnect the
- 30 -
Page 34
FILE NO. SVM-06020
DANGER
• FOR USE BY QUALIFIED PERSONS ONLY.
• TURN OFF MAIN POWER SUPPLY BEFORE ATTEMPTING ANY ELECTRICAL WORK. MAKE SURE
ALL POWER SWITCHES ARE OFF. FAILURE TO DO SO MAY CAUSE ELECTRIC SHOCK.
• CONNECT THE CONNECTING CABLE CORRECTLY. IF THE CONNECTING CABLE IS CONNECTED
WRONGLY, ELECTRIC PARTS MAY BE DAMAGED.
• CHECK THE EARTH WIRE THAT IT IS NOT BROKEN OR DISCONNECTED BEFORE INSTALLATION.
• DO NOT INSTALL NEAR CONCENTRATIONS OF COMBUSTIBLE GAS OR GAS VAPORS.
FAILURE TO FOLLOW THIS INSTRUCTION CAN RESULT IN FIRE OR EXPLOSION.
• TO PREVENT OVERHEATING THE INDOOR UNIT AND CAUSING A FIRE HAZARD, PLACE THE UNIT
WELL AWAY (MORE THAN 2 M) FROM HEAT SOURCES SUCH AS RADIATORS, HEATORS,
FURNACE, STOVES, ETC.
• WHEN MOVING THE AIR-CONDITIONER FOR INSTALLING IT IN ANOTHER PLACE AGAIN, BE VERY
CAREFUL NOT TO GET THE SPECIFIED REFRIGERANT (R410A) WITH ANY OTHER GASEOUS
BODY INTO THE REFRIGERATION CYCLE. IF AIR OR ANY OTHER GAS IS MIXED IN THE
REFRIGERANT, THE GAS PRESSURE IN THE REFRIGERATION CYCLE BECOMES ABNORMALLY
HIGH AND IT RESULTINGLY CAUSES BURST OF THE PIPE AND INJURIES ON PERSONS.
• IN THE EVENT THAT THE REFRIGERANT GAS LEAKS OUT OF THE PIPE DURING THE
INSTALLATION WORK, IMMEDIATELY LET FRESH AIR INTO THE ROOM. IF THE REFRIGERANT GAS
IS HEATED BY FIRE OR SOMETHING ELSE, IT CAUSES GENERATION OF POISONOUS GAS.
WARNING
• Never modify this unit by removing any of the safety guards or bypassing any of the safety interlock
switches.
• Do not install in a place which cannot bear the weight of the unit.
Personal injury and property damage can result if the unit falls.
• Before doing the electrical work, attach an approved plug to the power supply cord.
Also, make sure the equipment is properly earthed.
• Appliance shall be installed in accordance with national wiring regulations.
If you detect any damage, do not install the unit. Contact your TOSHIBA dealer immediately.
CAUTION
• Exposure of unit to water or other moisture before installation could result in electric shock.
Do not store it in a wet basement or expose to rain or water.
• After unpacking the unit, examine it carefully for possible damage.
• Do not install in a place that can increase the vibration of the unit. Do not install in a place that can amplify
the noise level of the unit or where noise and discharged air might disturb neighbors.
• To avoid personal injury, be careful when handling parts with sharp edges.
• Please read this installation manual carefully before installing the unit. It contains further important instruc-
tions for proper installation.
REQUIREMENT OF REPORT TO THE LOCAL POWER SUPPLIER
Please make absolutely sure that the installation of this appliance is reported to the local power supplier
before installation. If you experience any problems, or if the installation is not accepted by the supplier, the
service agency will take adequate countermeasures.
Remark per EMC Directive 89/336/EEC
To prevent flicker impressions during the start of the compressor (technical process) following installation
conditions do apply.
1. The power connection for the air conditioner has to be done at the main power distribution. This distribution
has to be of an impedance.
Normally the required impedance is reached at a 32A fusing point. Air conditioner fuse has to be 16A max.!
2. No other equipment should be connected to this power line.
3. For detailed installation acceptance, please contact your power supplier whether its restriction does apply
for products like washing machines, air conditioners or electrical ovens.
4. For power details of the air conditioner, refer to the rating plate of the product.
- 31 -
Page 35
FILE NO. SVM-06020
8-2. Installation Diagram of Indoor and Outdoor Units
Hook
65 mm or more
(Atta
c
h to th
e f
r
on
t panel) (A
ttac
6 Bio enzyme & Gingko filter
5 Sasa Zeolite Vitamin C filter
170 mm
or more
A
h to
ir
filter
the air filter)
1 Installation
plate
170 mm
or more
Shield
pipe
For the rear left and left
piping
Wall
Insert the cushion between
the indoor unit and wall,
and lift the indoor unit for
better operation.
Do not allow the drain
hose to get slack.
Cut the piping
hole sloped
slightly
Make sure to run the drain
hose sloped downward.
Before installing the
wireless remote control
• With the remote control cover
open, load the batteries supplied
correctly, observing their polarity.
2 Wireless remote control
Cover
3 Batteries
1
0
0
m
m
o
r
m
o
r
e
600 mm or more
8 Pan head wood screw
The auxiliary piping can
be connected the left, rear
left, rear, right or bottom.
Right
4 Remote control holder
Rear
Bottom
Rear
left
Left
2 Wireless remote control
Insulate the refrigerant
pipes separately with
insulation, not together.
Vinyl tape
Apply after carrying
out a drainage test.
Saddle
Extension
e
r
Extension drain hose
(Not available,
e
provided by installer)
mor
or
m
m
100
1
0
0
m
m
o
r
m
o
r
e
o
or m
m
m
0
10
600 mm or more
drain hose
(Not available,
provided by
installer)
6 mm thick heat resisting
polyethylene foam
ore
m
or
m
m
0
0
6
600
m
m
or
m
o
r
e
18 Class24 Class
ore
or m
m
m
0
0
6
6
0
0
m
m
o
r
m
o
r
e
- 32 -
Page 36
8-3. Installation
8-3-1. Optional installation parts
FILE NO. SVM-06020
Part
Code
Parts name
Refrigerant piping
Liquid side :
A
Gas side :
Pipe insulating material
B
(polyethylene foam, 6 mm thick)
C
Putty, PVC tapes
∅
6.35 mm
∅
12.7 mm
<Fixing bolt arrangement of outdoor unit>
124 mm109 mm
321 mm
28 mm
86 mm
Air outlet
25
Æ
600 mm
Air inlet
Q'ty
One
each
1
One
each
116 mm
90 mm
Drain outlet
Fig. 8-3-1.
• Secure the outdoor unit with fixing bolts and nuts if the unit is likely to be exposed to a strong wind.
• Use
∅ 8 mm or ∅ 10 mm anchor bolts and nuts.
• If it is necessary to drain the defrost water, attach drain nipple 10 to the bottom plate of the outdoor unit
before installing it.
- 33 -
Page 37
8-3-2. Accessory and installation parts
FILE NO. SVM-06020
Part
No.
Part name (Q'ty)
1
Installation plate x 1
2
Wireless remote control x 1
3
Battery x 2
Others
Owner’s manual
Installation manual
Name
Part
No.
Part name (Q'ty)
4
Remote control holder x 1
5
Sasa Zeolite Vitamin C filter x 2
6
Bio enzyme & Gingko filter x 2
Part
No.
Part name (Q'ty)
7
Mounting screw ∅ 4 x 25 x 8
l
8
Pan head wood screw
∅ 3.1 x 16 x 2
l
9
Drain nipple* x 1
10
Cap water proof* x 2
(For Heat pump model only)
The part marked with asterisk (*) is packaged with the
outdoor unit.
(For Heat pump model only)
- 34 -
Page 38
FILE NO. SVM-06020
8-4. Indoor Unit
8-4-1. Installation place
• A place which provides the spaces around the
indoor unit (See Fug 8-2).
• A place where there is no obstacle near the air inlet
and outlet.
• A place that allows easy installation of the piping to
the outdoor unit.
• A place which allows the front panel to be opened.
CAUTION
• Direct sunlight to the indoor unit’s wireless
receiver should be avoided.
• The microprocessor in the indoor unit should not
be too close to RF noise sources.
(For details, see the owner’s manual.)
<Remote control>
• A place where there are no obstacles such as a
curtain that may block the signal from the indoor
unit.
• Do not install the remote control in a place exposed
to direct sunlight or close to a heating source, such
as a stove.
• Keep the remote control at least 1 m apart from the
nearest TV set or stereo equipment. (This is
necessary to prevent image disturbances or noise
interference.)
• The location of the remote control should be
determined as shown below.
8-4-2. Cutting a hole and mounting installation
plate
<Cutting a hole>
When installing the refrigerant pipes from the rear.
Pipe
hole
65 mm
The center of the pipe
hole is above the arrow.
100 mm
Fig. 8-4-2
1. After determining the pipe hole position on the
mounting plate (A), drill the pipe hole (∅65 mm) at
a slight downward slant to the outdoor side.
NOTE
• When drilling a wall that contains a metal lath, wire
lath or metal plate, be sure to use a pipe hole brim
ring sold separately.
<Mounting the installation plate>
ndoor unit
I
(Side view)
7 m
°
5
7
Reception
range
Remote
control
(Top view)
Indoor unit
Reception
range
* : Axial distance
Fig. 8-4-1
5 m
5 m
55
Hook
45
°
45
°
Remote control
* 7 m
170
120
Pipe hole
Indoor unit
Hook
Thread
Weight
Hook
Pipe hole
7 Mounting screw
65
1
Installation
plate
Fig. 8-4-3
- 37 -
Page 39
FILE NO. SVM-06020
<When the installation plate is directly mounted on
the wall>
1. Securely fit the installation plate onto the wall by
screwing it in the upper and lower parts to hook up
the indoor unit.
2. To mount the installation plate on a concrete wall
with anchor bolts, utilize the anchor bolt holes as
illustrated in the above figure.
3. Install the installation plate horizontally in the wall.
CAUTION
When installing the installation plate with a
mounting screw, do not use the anchor bolt hole.
Otherwise the unit may fall down and result in
personal injury and property damage.
Installation plate
<Keep horizontal direction>
Anchor
bolt
Projection
5 mm dia. hole
15 mm or less
8-4-3. Electrical work
1. The supply voltage must be the same as the rated
voltage of the air conditioner.
2. Prepare the power source for exclusive use with the
air conditioner.
NOTE
2
• Wire type : More than 1.5 mm
245 IEC66) or 1.3 mm
(H07RN-F or
2
(AWG-16)
CAUTION
• This appliance can be connected to the mains in
the following way.
Connection to fixed wiring:
A switch or circuit breaker which disconnects all
poles and has a contact separation of at least
3 mm must be incorporate in the fixed wiring. An
approved circuit breaker or switches must used.
NOTE
• Perform wiring works so as to allow a generous
wiring capacity.
7 Mounting
screw
ss
∅4 x 25
s
ss
Clip anchor
(local parts)
Fig. 8-4-4
CAUTION
Failure to firmly install the unit may result in
personal injury and property damage if the unit falls.
• In case of block, brick, concrete or similar type
walls, make 5 mm dia. holes in the wall.
• Insert clip anchors for appropriate mounting screws
7 .
NOTE
• Secure four corners and lower parts of the
installation plate with 6 to 7 mounting screws to
install it.
- 38 -
Page 40
FILE NO. SVM-06020
8-4-4. Wiring connection
Air inlet grille
Terminal
cover
Screw
2
1
Terminal block
Cord clamp
Screw
Front panel
Earth
line
CAUTION
• Be sure to refer to the wiring system diagram
labeled inside the front panel.
• Check local electrical cords and also any specific
wiring instructions or limitations.
Connecting cable
about 15 cm
Fig. 8-4-6
<Stripping length of connecting cable>
10
10
40
50
Connecting cable
Fig. 8-4-5
<How to connect the connecting cable>
Wiring of the connecting cable can be carried out
without removing of the front panel.
1. Remove the air inlet grille.
Open the air inlet grille upward and pull it toward
you.
2. Remove the terminal cover and cord clamp.
3. Insert the connecting cable (according to local
cords) into pipe hole on the wall.
4. Take out the connecting cable through the cable
slot on the rear panel so that it protrudes about
15 cm from the front.
5. Insert the connecting cable fully into the terminal
block and secure it tightly with screws.
6. Tightening torque : 1.2 N·m (0.12 kgf·m).
7. Secure the connecting cable with the cord clamp.
8. Fix the terminal cover, rear plate bushing and air
inlet grille on the indoor unit.
Earth line
Fig. 8-4-7
NOTE
Use stranded wire only.
• Wire type : More than 1.5 mm2 (H07RN-F or
245 IEC66) or 1.3 mm
2
(AWG-16)
Fig. 8-4-8
NOTE
Connect the earth line to the metallic part (i mark)
located at the side of 3P terminal.
<How to install the air inlet grille on the indoor unit>
• When attaching the air inlet grille, the contrary of
the removed operation is performed.
Fig. 8-4-9
- 39 -
Page 41
FILE NO. SVM-06020
8-4-5. Piping and Drain Hose Installation
<In case of rightward piping>
• After scribing slits of the body-right by a knife or a
making-off pin, cut them by a pair of nippers or the
like.
Slit (Body-right)
Fig. 8-4-10
<In case of downward piping>
• After scribing slits of the body-right by a knife or a
making-off pin, cut them by a pair of nippers or the
like.
To connect the pipe after installation of the unit (figure)
(To the forefront of flare)
400 mm
300 mm
R 30 mm (Use polisin (polyethylene)
core or the like for bending pipe.)
43 mm
80
Liquid side
Gas side
Outward form of indoor unit
Use the handle of screwdriver, etc.
Fig. 8-4-12
NOTE
If the pipe is bent incorrectly, the indoor unit may
unstably be set on the wall.
After passing the connecting pipe through the pipe
hole, connect the connecting pipe to the auxiliary pipes
and wrap the facing tape around them.
Slit (Body-right)
Fig. 8-4-11
<Left-hand connection with piping>
Bend the connecting pipe so that it is laid within 43 mm
above the wall surface. If the connecting pipe is laid
exceeding 43 mm above the wall surface, the indoor
unit may unstably be set on the wall. When bending the
connecting pipe, make sure to use a spring bender so
as not to crush the pipe.
Bend the connection pipe within a radius of 30 mm.
CAUTION
• Bind the auxiliary pipes (two) and connecting
cable with facing tape tightly. In case of leftward
piping and rear-leftward piping, bind the auxiliary
pipes (two) only with facing tape.
Indoor unit
Auxiliary pipes
Installation plate
• Carefully arrange pipes so that any pipe does not
stick out of the rear plate of the indoor unit.
• Carefully connect the auxiliary pipes and
connecting pipes to each other and cut off the
insulating tape wound on the connecting pipe to
avoid double-taping at the joint, moreover, seal
the joint with the vinyl tape, etc.
• Since dewing results in a machine trouble, make
sure to insulate both the connecting pipes. (Use
polyethylene foam as insulating material.)
• When bending a pipe, carefully do it not to crush
it.
Connecting cable
Drain hose
- 40 -
Page 42
FILE NO. SVM-06020
8-4-6. Indoor unit fixing
1. Pass the pipe through the hole in the wall, and hook
the indoor unit on the installation plate at the upper
hooks.
2. Swing the indoor unit to right and left to confirm that
it is firmly hooked up on the installation plate.
3. While pressing the indoor unit onto the wall, hook it
at the lower part on the installation plate. Pull the
indoor unit toward you to confirm that it is firmly
hooked up on the installation plate.
1
2
Hook
Hook here
1 Installation
plate
Fig. 8-4-13
• For detaching the indoor unit from the installation
plate, pull the indoor unit toward you while
pressing
its bottom up at the specified parts.
8-4-7. Drainage
1. Run the drain hose sloped downwards.
NOTE
• Hole should be made at a slight downward slant on
the outdoor side.
Do not form the
Do not rise the
drain hose.
50 mm
or more
Do not put
the drain
hose end
into water.
drain hose into
a wavy shape.
Do not put
the drain
hose end in
the drainage
ditch.
Fig. 8-4-15
2. Put water in the drain pan and make sure that the
water is drained out of doors.
3. When connecting extension drain hose, insulate the
connecting part of extension drain hose with shield
pipe.
PressPress
Fig. 8-4-14
Press
(unhook)
Shield pipe
Drain hose
Inside the room
Extension drain hose
Fig. 8-4-16
CAUTION
Arrange the drain pipe for proper drainage from the
unit.
Improper drainage can result in dew-dropping.
This air conditioner has the structure designed to drain
water collected from dew, which forms on the back of
the indoor unit, to the drain pan.
Therefore, do not store the power cord and other parts
at a height above the drain guide.
Wall
Drain guide
Space for pipes
- 41 -
Fig. 8-4-17
Page 43
8-5. Outdoor Unit
8-5-1. Installation place
• A place which provides the spaces around the
outdoor unit as shown in the installation diagram
of indoor and outdoor unit.
•
A place which can bear the weight of the outdoor
unit and does not allow an increase in noise level
and vibration.
• A place where the operation noise and discharged
air do not disturb your neighbors.
• A place which is not exposed to a strong wind.
• A place free of a leakage of combustible gases.
• A place which does not block a passage.
• When the outdoor unit is to be installed in an
elevated position, be sure to secure its feet.
• An allowable length of the connecting pipe is up
15 m. (Refer to the table of TO CHARGE
REFRIGERANT for detail.)
• An allowable height level is up to 8 m.
• A place where the drain water does not raise any
problem.
FILE NO. SVM-06020
8-5-2. Refrigerant piping connection
1. Cut the pipe with a pipe cutter.
90°
Obliquity
Fig. 8-5-2
2. Insert a flare nut into the pipe, and flare the pipe.
• Projection margin in flaring : A (Unit : mm)
Die
Pipe
Fig. 8-5-3
Rigid (Clutch type)
Roughness Warp
A
CAUTION
1. Install the outdoor unit without anything blocking
the air discharging.
2. When the outdoor unit is installed in a place
exposed always exposed to strong wind like a
coast or on a high storey of a building, secure
the normal fan operation using a duct or a wind
shield.
3. In particularly windy areas, install the unit such
as to avoid admission of wind.
4. Installation in the following places may result in
trouble.
Do not install the unit in such places.
• A place full of machine oil.
• A saline-place such as the coast.
• A place full of sulfide gas.
• A place where high-frequency waves are likely
to be generated as from audio equipment,
welders, and medical equipment.
Strong
wind
Fig. 8-5-1
Outer dia. R410A Conventional
of copper pipe tool used tool used
6.35 0 to 0.5 1.0 to 1.5
12.70 0 to 0.5 1.0 to 1.5
Imperial (wing nut type, conventional tool)
Outer dia.
of copper pipe
R410A
6.35 1.5 to 2.0
12.70 2.0 to 2.5
<Tightening connection>
Align the centers of the connecting pipes and tighten
the flare nut as far as possible with your fingers. Then
tighten the nut with a spanner and torque wrench as
shown in the figure.
CAUTION
• Do not apply excess torque.
• Otherwise, the nut may crack depending on the
conditions.
- 42 -
Page 44
FILE NO. SVM-06020
(Unit : N·m)
Outer dia.
of copper pipe
Tightening torque
∅6.35 mm 16 to 18 (1.6 to 1.8 kgf·m)
∅9.52 mm 30 to 42 (3.0 to 4.2 kgf·m)
∅12.70 mm 50 to 62 (5.0 to 6.2 kgf·m)
• Tightening torque of flare pipe connections
The operating pressure of R410A is higher than that of
R22. (Approx. 1.6 times). It is therefore necessary to
firmly tighten the flare pipe connecting sections (which
connect the indoor and outdoor units) up to the
specified tightening torque. Incorrect connections may
cause not only a gas leakage, but also damage to the
refrigerant cycle.
Flare at indoor unit side
Flare at outdoor unit side
Fig. 8-5-4
Flare nutHalf union
Externally
threaded side
Use a wrench to secure.
Use a torque wrench to tighten.
Internally
threaded side
Fig. 8-5-5
8-5-3. Evacuating
After the piping has been connected to the indoor unit,
you can perform the air purge together at once.
AIR PURGE
Evacuate the air in the connecting pipes and in the
indoor unit using
a vacuum pump. Do not use the refrigerant in the
outdoor unit.
For details, see the manual of the vacuum pump.
<Using a vacuum pump>
Be sure to use a vacuum pump with counter-flow
prevention function so that inside oil of the pump does
not flow backward into pipes of the air conditioner
when the pump stops. (If oil inside of the vacuum pump
enters into the air conditioner, which use R410A,
refrigeration cycle trouble may result.)
1. Connect the charge hose from the manifold valve to
the service port of the gas side packed valve.
2. Connect the charge hose to the port of the vacuum
pump.
3. Open fully the low pressure side handle of the
gauge manifold valve.
4. Operate the vacuum pump to start evacuating.
Perform evacuating for about 15 minutes if the
piping length is 20 meters. (15 minutes for
20 meters) (assuming a pump capacity of 27 liters
per minute. Then confirm that the compound
pressure gauge reading is –101 kPa (–76 cmHg).
5. Close the low pressure side valve handle of gauge
manifold.
6. Open fully the valve stem of the packed valves
(both side of Gas and Liquid).
7. Remove the charging hose from the service port.
8. Securely tighten the caps on the packed valves.
CAUTION
•
KEEP IMPORTANT 4 POINTS FOR PIPING WORK
(1) Take away dust and moisture (Inside of the
connecting pipes.)
(2) Tight connection (between pipes and unit)
(3) Evacuate the air in the connecting pipes using
VACUUM PUMP.
(4) Check gas leak (connected points)
- 43 -
Compound pressure gauge
–101 kPa (–76 cmHg)
Handle Lo
Charge hose (For R410A only)
Connecting pipe
Packed valve
at liquid side
Pressure gauge
Manifold valve
Handle Hi
(Keep full closed)
Charge hose (For R410A only)
Vacuum pump adapter
for counter-flow
prevention
(For R410A only)
Vacuum
pump
Packed valve at gas side
Service port (Valve core (Setting pin))
Fig. 8-5-6
Page 45
FILE NO. SVM-06020
TO CHARGE REFRIGERANT
Refrigerant
No need to charge
refrigerant
Need to charge Over 15 m up to Over 15 m up to
refrigerant 25 m (20g/m) 20 m (20g/m)
24 Class
15 m or less 15 m or less
18 Class
<Packed valve handling precautions>
• Open the valve stem all the way out; but do not try
to open it beyond the stopper.
• Securely tighten the valve stem cap with torque in
the following table:
Gas side 50 to 62 N·m
(∅12.70 mm) (5.0 to 6.2 kgf·m)
Liquid side 16 to 18 N·m
(∅6.35 mm) (1.6 to 1.8 kgf·m)
Service port
9 to 10 N·m
(0.9 to 1.0 kgf·m)
Hexagonal wrench
is required.
4 mm
8-5-4. Wiring connection
1. Remove the valve cover from the outdoor unit.
2. Connect the connecting cable to the terminal as
identified with their respective matched numbers on
the terminal block of indoor and outdoor unit.
3. When connecting the connecting cable to the
outdoor unit terminal, make a loop as shown in the
installation diagram of indoor and outdoor unit, to
prevent water coming in the outdoor unit.
4. Insulate the unused cords (conductors) from any
water coming in the outdoor unit. Proceed them so
that they do not touch any electrical or metal parts.
<Stripping length of connecting cable>
Terminal block
LN132
Terminal
screw
Cord clamp
Power supply cord
10
60
N
L
10
70
70
Earth line
Screw
Cord clamp
Connecting cable
123
10
10
80
Fig. 8-5-7
Earth line
Power supply cord
Connecting cable
Fig. 8-5-8
Model
Power source 50 Hz, 220 ∼ 240 V Single phase
Maximum running current 18A 16A
Plug socket & fuse rating
Power cord
24 Class
20A 20A
2
(H07R N-F or 245 IE C 66)
4 mm
or 3.5 mm2 (AWG -12)
CAUTION
• Wrong wiring connection may cause some
electrical parts burn out.
• Be sure to comply with local codes on running
the wire from indoor unit to outdoor unit (size of
wire and wiring method etc).
• Every wire must be connected firmly.
NOTE: Connecting cable
• Wire type: More than 1.5 mm
245 IEC66) or 1.3 mm
- 44 -
2
(H07RN-F or
2 (AWG-16)
18 Class
Page 46
FILE NO. SVM-06020
8-6. How to Set Remote Control Selector
Switch
When two indoor units as installed in seperated rooms,
there is no need to change the selector switch.
<Remote control selector switch>
• When two indoor units are installed in the same
room or the adjacent two rooms, they may be
controlled simultaneously with a single remote
control. To prevent this, set either unit and its
remote control to B setting. (Both units are set to A
setting before shipment.)
• The remote control signal is not recived when the
indoor unit setting is different from the remote
control one.
1. Set the remote control selectors witch with the
indoor unit.
1) Turn the circuit breaker of the main power switch off
before setting the selector switch.
2) Remove the Air inlet grille and Front panel. (Refer to
Chapter 10-1, procedure 1 )
3) Open the Electrical part cover (Refer to chapter
10-1, procedure 2 ), then cut the jumper (J90)
with only the nippers.
2. Set the remote control selector switch with the
remote control
[B] is indicated on the liquid crystal display when
setting remote control selector switch to B. [A] is
not indicated on the display even if the selector
switch is set to A.
1) Load the remote control with the batteries.
2) Press the [CHECK] button using something with
sharp point. (The preset temperature on the remote
control changes to [00].)
3) Press the [MODE] button while pressing the
[CHECK] button, [B] is indicted at the right of the
present temperature display.
• To reset the switch to the [A] setting, press the
[MODE] button again while pressing the [CHECK]
button.
CAUTION
Do not use any other sharp tools (such
as cutters, pliers, or the like). Such tools
may cause breakage or damage.
See Fig. 8-6-1
Fig. 8-6-1
[MODE] button
[CHK] button
Fig. 8-6-2
3. Confirm that the indoor unit can operate with
the new setting.
- 45 -
Page 47
FILE NO. SVM-06020
8-7. Others
8-7-1. Gas leak test
Flare nut connections
(Indoor unit)
Flare nut connections
(Outdoor unit)
B
A
Valve stem cap connection
Service port cap connection
Valve stem cap connection
Fig. 8-7-1
• Check the flare nut connections, valve stem cap
connections and service port cap connections for
gas leak with a leak detector or soap water.
8-7-2. Test operation
8-7-3. Auto restart setting
This product is designed so that, after a power failure,
it can restart automatically in the same operating mode
as before the power failure.
Information
The product was shipped with Auto Restart function
in the off position. Turn it on as required.
<How to set the auto restart>
• Press and hold the TEMPORARY button for about
3 seconds. After 3 seconds, the electronic beeper
makes three short beeps to tell you the Auto
Restart has been selected.
• To cancel the Auto Restart, follow the steps
described in the section Auto Restart Function of
the Owner’s Manual.
To switch the TEST RUN (COOL) mode, press
TEMPORARY button for 10 sec.
(The beeper will make a shaort beep.)
TE MPO R AR Y button
Fig. 8-7-2
- 46 -
Page 48
9. TROUBLESHOOTING CHART
FILE NO. SVM-06020
9-1. T r oub leshooting Pr ocedure :
9-2-2. Incorrect cable connection between Indoor
and outdoor units
Follow the details of 9-2. Basic Check Items.
If there is no trouble corresponding to 9-2, check
whether or not there are faulty parts following
9-4. Self-Diagnosis by Remote Control.
9-2. Basic Check Items
The indoor unit is connected to the outdoor unit with
4 cables. Check that the indoor and outdoor units have
been properly connected with terminals assigned the
same numbers. If the connectors are not properly
connected, the outdoor unit will not operate normally,
or OPERATION lamp and TIMER lamp will blink (5 Hz).
9-2-1. Power supply voltage
The line voltage must be AC 220 – 240 V. If it is not
within this range, the air conditioner may not operate
normally.
9-2-3. Program control
The microcontroller operates as shown in Table 9-2-1
to control the air conditioner. If there are any operational problems, check whether or not the problems
correspond to Table 9-2-1. If they correspond to the
Table, they are not problems with the air conditioner,
but they are indispensable operations to control and
maintain the air conditioner properly.
Table 9-2-1
No.Operation of air conditionerDescriptions
1When the main power supply is turned
on, the OPERATION lamp on the
indoor unit blinks.
2The indoor fan motor speed does not
change in the Dry operation.
3The compressor is not turned off even
though the room temperature is in the
range that the compressor is turned off.
4The compressor is not turned on and
off even though the thermo control is
operated in the Dry operation.
*5The PRE-DEF. lamp is indicated when
the Heating operation starts.
The OPERATION lamp blinks to indicate that power is turned on. If the
[ ] button is pressed, the lamp stops blinking.
The indoor fan motor speed is automatically controlled in the Dry
operation.
The compressor has a function that it is not turned off for 3 minutes
after it is turned on even though the room temperature is in the range
that the compressor is turned off.
In the Dry operation, the compressor is turned on and off automatically
at the regular intervals, independent of the thermo control.
The PRE-DEF. lamp is indicated during the Defrosting operation or if
the indoor heat exchanger temperature is low when the Heating
operation starts. At this time, the indoor fan motor stops to prevent
cold air from blowing in the room.
*6The outdoor fan motor stops in the
Heating operation.
7The compressor is not turned on even
though the room temperature is in the
range that the compressor is turned on.
8The operation mode changes in the
Automatic operation.
9The Fan only operation continues in the
Automatic operation.
10The ECO operation or Hi-POWER
operation does not work.
11When [Hi POWER] button is pressed,
the display on the remote control does
not change at all.
Note *5 and *6 are for Heat pump model :
When the indoor heat exchanger temperature is high, the outdoor fan
motor is stopped by the high-temperature limit control operation.
The compressor is not turned on in the restart delay timer (3-minutes
timer) operation. It is also not turned on after the power supply is
turned on because of this timer operation.
In Automatic operation, the room temperature is detected all time
for control fan speed and the operation mode is changed every
15 minutes according to difference between the room temperature
and the preset temperature.
When the room temperature is in the range
(Preset temperature ± 1°C), the Fan only operation is selected.
These operations do not work when the unit is in the Dry
operation or Fan only operation.
The display on the remote control does not change when
[Hi POWER] button is pressed. However the microcontroller gives
commands to change the preset temperature and air flow level.
- 47 -
Page 49
FILE NO. SVM-06020
9-3. Primary Judgement
9-3-1. Role of indoor unit controller
The indoor unit controller receives the operation
commands from the remote control and executes
them.
Temperature measurement at the air outlet of the
·
indoor heat exchanger by the indoor temperature
sensor
Temperature setting of the indoor heat exchanger by
·
the heat exchanger sensor
Louver motor control
·
Indoor fan motor operation control
·
LED display control
·
Transferring of operation commands to the outdoor
·
unit
Table 9-3-1
LampsSelf-diagnosis
AOPERATION lamp is blinking. (1Hz)
BOPERATION lamp is blinking. (5Hz)
COPERATION lamp is blinking. (5Hz)
DOPERATION lamp is blinking. (5Hz)
EOPERATION lamp is blinking. (5Hz)
FOPERATION and TIMER lamps are blinking.
(5Hz)
9-3-2. Failure diagnosis
The indoor unit diagnoses the operation condition and
indicates the information of the self-diagnosis with the
lamps on the display panel of the indoor unit.
Power failure (when the power supply is turning on)
Thermo sensor (TA) short or break
Heat exchanger sensor (TC) short or break
Indoor fan motor lock or failure
Indoor P.C. board failure
Wrong wiring of connecting cable
GOPERATION, TIMER and PRE-DEF.
(or FAN ONLY for cooling only model) lamps
are blinking.
Table 9-3-2 Diagnosis by detective operation
SymptomCheckPrimary judgement
The remote control
does not work.
The outdoor fan
does not rotate.
Turn off the power supply once,
then turn it on. Try to operate
the remote control.
The compressor operates.
The compressor does not operate.
Cycle failure
Gas shortage or other refrigerant cycle trouble
·
Heat exchanger sensor open, break or short
·
·
Overload relay or thermostat trouble of compressor
The remote control
still does not work.
The remote control
works.
The indoor unit (and/or remote
control) is/are defective .
OK.
The outdoor unit (Outdoor fan
motor) is defective.
An internal part of the
compressor or P.C. board is
defective.
- 48 -
Page 50
9-4. Self-Diagnosis by Remote Control
(Check Code)
(1) If the lamps are indicated as shown B to G in Table
9-3-1, exchanger the self-diagnosis by the remote
control.
(2) When the remote control is set to the service
mode, the indoor controller diagnoses the
operation condition and indicate the information of
the self-diagnosis on the display of the remote
control with the check codes. If a fault is detected,
all lamps on the indoor unit will blink at 5Hz and it
will beep for 10 seconds (Pi, Pi, Pi....). The timer
lamp usually blinks (5Hz) during the self-diagnosis.
9-4-1. How to use remote control in service mode
FILE NO. SVM-06020
(1) Press [CHK] button with a tip of pencil to set the
remote control to the service mode.
• “00” is indicated on the display of the remote
control.
• The timer lamp on the indoor unit blinks
continuously. (5 times per 1 sec.)
(2) Press [TIMER 8] button.
If there is no fault with a code, the indoor unit will
beep once (Pi) and the display of the remote
control will change as follows:
00
01
•
Check the unit with all 35 check codes (00 to 22).
as shown in Table 9-4-1.
• Press [TIMER 9] button to change the check
code backwards.
If there is a fault, the indoor unit will beep for 10
seconds (Pi, Pi, Pi...).
Note the check code on the display of the remote
control.
• 2-digits alphanumeric will be indicated on the
display.
• All lamps on the indoor unit will blink. (5 times
per 1 sec.)
(3) Press [CLR] button. After service finish for clear
service code in memory.
• “7F” is indicated on the display of the remote
control.
1d
02
1E
22
•
Alphanumeric characters are used for the check code.
is 5.is 6.
is A.is B.
is C.is D.
* This illustration in only for Heat pump model.
For Cooling only model, there is not the ( ) symbol.
(4) Press [ ] button to release the service
mode.
• The display of the remote control returns to as it
was before service mode was engaged.
- 49 -
Page 51
Table 9-4-1
Block level Diagnosis function
Check
code code status
Block
Indoor
P.C. board
Cable
connection
Outdoor
P.C. board
Other parts
(including
compressor)
Check
Symptom
The indoor thermo sensor (TA) is
defective.
Disconnection or short-circuit
The indoor heat exchanger
sensor (TC) is defective.
Disconnection or short-circuit
The indoor fan motor or its circuit
is defective.
The part other than the above
parts on the indoor P.C. board is
defective.
EEPROM access error
IOL operation
The serial signals can not be
transmitted and received between
indoor and outdoor units.
• The crossover wire is
connected wrongly.
• The serial signal transmitting
circuit on the outdoor P.C. board
is defective.
• The serial signal receiving
circuit on the indoor P.C. board
is defective.
The operation command signals
are not transmitted from the
indoor unit to the outdoor unit.
The outdoor thermo sensor (TE)
is defective.
Disconnection or short-circuit
The outdoor heat exchanger (TD)
sensor is defective.
Disconnection or short-circuit
The reply serial signal has been
transmitted when starting the
unit, but stops being transmitted
shortly after.
1. Compressor thermo operation
• Gas shortage
• Gas leak
2. Instantaneous power failure
The discharge temperature is
over 120°C.
The IOL operation is defective.
Unit
Operation
continues.
Operation
continues.
All off
Operation
continues.
All off
Operation
continues.
Operation
continues.
All off
All off
Operation
continues.
All off
All off
Condition
The lamp on the
indoor unit blinks
when error is
defected.
The lamp on the
indoor unit blinks
when error is
defected.
The lamp on the
indoor unit blinks
when error is
defected.
The lamp on the
indoor unit blinks
when error is
defected.
The lamp on the
indoor unit blinks
when error is
.
defected
The lamp on the
indoor unit blinks
when error is
defected.
The lamp on the
indoor unit blinks
when error is
defected. And it
returns to the
normal condition
when recovering
from errors.
The lamp on the
indoor unit blinks
when error is
defected.
The lamp on the
indoor unit blinks
when error is
defected.
The lamp on the
indoor unit blinks
when error is
defected. And it
returns to the
normal condition
when recovering
from errors.
The lamp on the
indoor unit blinks
when error is
defected.
The lamp on the
indoor unit blinks
when error is
detected.
FILE NO. SVM-06020
Judgement and action
1. Check the indoor thermo sensor (TA).
2. Check the indoor P.C. board.
1. Check the indoor heat exchanger
sensor (TC).
2. Check the indoor P.C. board.
1. Check the connector circuit of the
indoor fan motor (CN10).
2. Check the indoor fan motor.
3. Check the indoor P.C. board.
1. Check the indoor P.C. board.
(EEPROM and peripheral circuits)
Overload operation of refrigerating cycle
1. In the case of the outdoor unit not
operating at all;
• Check the crossover cable and
connect it properly.
• Check the outdoor P.C. board.
2. In the case of the outdoor unit operating
normally;
• Check whether or not both of serial
LED (Green) and serial LED (Orange)
is blinking.
If the serial LED (Green) is not
blinking, check the outdoor P.C. board.
If the serial LED (Orange) is not
blinking, check the indoor P.C. board.
If the operation command signals continue
to be transmitted between 2 and 3 of the
indoor terminal block, replace the outdoor
P.C. board.
1. Check the outdoor thermo sensor (TE).
2. Check the outdoor P.C. board.
1. Check the outdoor heat exchanger
sensor (TD).
2. Check the outdoor P.C. board.
1. Repeatedly turn the indoor unit on and
off with the interval of approx. 10 to 40
minutes. (The check code is not
indicated during operation.) And supply
gas. (Check gas leak.)
2. The indoor unit operates normally
during the check.
If the reply serial signal continues to be
transmitted between 2 and 3 of the
indoor terminal block, replace the
outdoor P.C. board.
If the signal stops between them,
replace the indoor P.C. board.
1. Check the heat exchanger sensor (TD).
2. Gas purging
When turning on the unit, the normal
phase (RST) is detected but T-R waveform
has not been detected for 120 seconds or
more.
- 50 -
Page 52
9-5. How To Diagnose Faulty Parts
[04 Serial signal error] (Heat pump model)
FILE NO. SVM-06020
Operation
Check item
Conceivable principle cause
Measure
Does outdoor
unit operate?
YES
NO
Are 1, 2 and 3 crossover
wires connected properly?
YES
Is connector
connected properly?
YES
Does LED (Orange) on
outdoor P.C. board blink?
YES
Does LED (Green) on
outdoor P.C. board blink?
YES
NO
NO
NO
NO
Outdoor P.C. board
is defective.
Indoor P.C. board
is defective.
Item by symptoms
Connect crossover
wires properly.
Connect connector
properly.
Replace
P.C. board.
Replace
P.C. board.
[08 Four-way valve error] (Heat pump model)
Does four-way valve
operate properly?
YES
Is TC sensor
resistance value
(10kΩ at 25°C) normal?
NO
NO
YES
Does coil terminal
have 220 − 240 V
in heating operation?
YES
Are circuit
wires normal?
YES
Is outdoor P.C. board
normal?
YES
YES
NO
NO
Four-way valve
is defective.
Outdoor P.C. board
is defective.
(CN11 220 − 240V)
Indoor P.C. board
is defective.
Replace
Four-way valve
Circuit check/modification
Replace
P.C. board.
Replace
P.C. board.
Replace TC sensor.
- 51 -
Page 53
[09 Other cycle error] (1) (Heat pump model)
FILE NO. SVM-06020
NO
Replace TC
sensor.
YES
Connect TC
sensor properly.
Does compressor operate?
YES
Is compressor
turned off shortly?
NO
Is TC sensor
resistance value
(10kΩ at 25°C) normal?
YES
Is TC sensor
disconnected from
the sensing element?
NO
NO
YES
Does inner
overload relay
(in compressor)
operate?
NO
Is circuit wiring
normal?
YES
Is outdoor P.C.
board normal?
YES
YES
NO
NO
Check charged amount of refrigerant.
Check defective overload.
Check compressor.
Failure
compressor.
Wiring check/modification
Outdoor P.C. board
is defective.
Indoor P.C. board
is defective.
Replace
Replace
P.C. board.
Replace
P.C. board.
[09 Other cycle error] (2)
NO
Connect
connector
properly.
NO
Replace
condenser.
NO
Replace
fan motor.
Is connector
connected properly?
Is condenser normal?
Is indoor fan
motor normal?
YES
YES
YES
NO
Does indoor
fan operate?
Are filters clogged?
Is TC sensor
resistance value
(10kΩ at 25°C) normal?
Is charged amount
of refrigerant normal?
Is outside air
low load?
YES
NO
YES
YES
NO
YES
NO
NO
YES
Anti-freezing operation
Anti-freezing operation
Clean filters.
Replace
TC sensor.
Charge
refrigerant.
Indoor P.C. board
is defective.
- 52 -
Replacd
P.C. board.
Page 54
[0C Indoor TA sensor error]
FILE NO. SVM-06020
Is CN04 (TA sensor connector)
connected properly?
YES
Is TA sensor resistance value
(10 kΩ at 25
°C)
YES
normal?
[0d Indoor TC sensor error]
Is CN05 (TC sensor connector)
connected properly?
YES
NO
NO
NO
Indoor P.C. board is defective.
Connect CN04 properly.
Replace TA sensor.
Replace P.C. board.
Connect CN05 properly.
Is TC sensor resistance value
(10 k
Ω
at 25°C) normal?
YES
NO
Indoor P.C. board is defective.
[18 outdoor TE sensor error] (Heat pump model)
Is TE sensor connector
connected properly?
YES
Is TE sensor resistance value
(10 k
Ω
at 25°C) normal?
YES
NO
NO
Replace TC sensor.
Replace P.C. board.
Connect connector
properly.
Replace TE sensor.
Indoor P.C. board is defective.
- 53 -
Replace P.C. board.
Page 55
[19 outdoor TD sensor error] (Heat pump model)
FILE NO. SVM-06020
Is TD sensor
connected properly?
YES
Is TD sensor resistance value
(50 k
Ω
at 25°C) normal?
YES
NO
NO
Outdoor P.C. board is defective.
[1E Discharge temp. error] (Heat pump model)
Connect connector
properly.
Replace TD sensor.
Replace P.C. board.
Is protective
controller such as discharge
thermostat normal?
YES
Is charged amount
of refrigerant normal?
YES
Is overload relay normal?
NO
Is TD sensor resistance value
(50 kΩ at 25°C) normal?
YES
NO NO
NO
YES
NO
Are wires connected
to connector properly?
Outdoor P.C. board is defective.
Connect wires to
connector properly.
Check and modify charged
amount of refrigerant.
Unit operates normally.
Replace TD sensor.
Replace P.C. board.
- 54 -
Page 56
FILE NO. SVM-06020
Operation
Measure
Item by symptoms
Check item
Conceivable principle
cause
9-6.
Troubleshooting for Indoor unit
9-6-1. Power can not be turned on. (The unit does not operate at all.)
<Primar check>
(1) Is the supply voltage normal?
(2)Is the connection to the AC output OK?
(3) Is the fuse (F01) blown?
Turn off power
supply once, and 5
second later, turn it
on again.
NO
Is OPERATION
lamp blinking?
YES
Does
Is it possible to
turn on power
supply by
pressing
[START/STOP]
button on remote
control?
YES
NO
transmission
mark on
remote
control flash
normally, and
is its signal
transmitted
properly?
YES
NO
Remote control is
defective.
Refer to 9-9
ÒTroubleshooting for
Remote Control.Ó
Is DC 310 -
340V across
C63?
Are DC 12V,
across C66?
YES
YES
NO
NO
Is fuse (F01)
control board
Is voltage (DC
12V or 5V)
NO
indicated on
rear of indoor
control board
Turn off breaker
once and turn it
on again after
removing motor.
of indoor
blown?
normal?
NO
YES
YES
Parts (R21,
R22, SG01,
C01, DB01,
C02,
M01 and IC04)
are defective.
Are DC 12V,
across C66?
YES
- 55 -
NO
Does the fan
motor
connector
between 1
and 2 short-
circuit?
NO
Microcomputer is
defective.
M01 is
def
ec
tive.
Unit operates
normally.
YES
Replace main P.C.
board.
Replace motor.
Page 57
FILE NO. SVM-06020
9-6-2. Only the indoor fan does not operate
<Primary chec k>
(1) Is it possible to detect the power supply voltage (200 − 240V) between 1 and 2 on the terminal block?
(2) Does the indoor fan motor operate in cooling operation?
(In heating operation, the indoor fan motor does not operate for approximately 5 minutes after it is turned on,
to prevent a cold air from blowing in.)
Shut off the
power supply once.
Turn the power supply.
Does the fan stop in
no operating status?
YES
Start the operation
with low fan setting
in cool operation.
Does the fan rotate?
YES
Change the setting of
cooling to high fan.
Does the fan speed
become higher?
YES
NO
NO
NO
Control P.C. board is defective.
Does AC 120V
or higher voltage apply
to between red and black
lead of fan motor?
YES
Shut off the power supply.
Does the cross flow
fan rotate normally?
YES
Turn on the power supply.
Operation
stops
NO
NO
Replace the P.C. board.
Does connecting
terminal, connecting
cable or power supply
cord completely?
Does not found the short
wire about connecting
cable and power cord?
YES
Repair the
bearing of
the fan.
Motor control circuit failure
(IC30, IC03, D38, R25, R26, Q17)
or 12V power circuit failure.
Replace the P.C. board.
of incompleted connecting.
NO
Thermal fuse operated
due to prevent
temperature rising cause
Normal
Is the rotation signal (DC+5V-0V)
output between 2 (gray lead wire)
and 3 (brown lead wire) of the motor
connector (CN11) when rotating
the cross flow fan by hand in no
operating status?
(1 pulse/one turn)
YES
Replace the control
P.C. board.
- 56 -
NO
Replace the fan motor
Replace connecting
the cable (or power cord),
thermal fuse and
terminal block.
Page 58
FILE NO. SVM-06020
9-6-3. Compressor does not operate.
<Primary check>
(1) Is the preset temperature higher than the room temperature in cooling operation?
(2) Is the crossover cable connected properly?
<Inspection procedure>
Turn on power supply.
Does OPERATION
lamp blink?
YES
Does miniature relay RY04
switch on and off due to
temperature changes?
YES
Is it possible to detect AC
220 – 240V between 2
and 3 on terminal block?
YES
Are all of compressor cords normal?
YES
Is compressor motor winding
normal?
(Check winding resistor.)
YES
Is capacitor for compressor normal?
NO
NO
NO
Is resistance value of thermo
sensor (TA) and heat ex-
changer sensor (TC) normal?
Microcomputer is defective.
Miniature relay RY04 is
defective.
NO
NO
NO
NO
YES
Compressor is defective.
Capacitor is defective.
Refer to 9-6-1 “Power
can not be turned on”.
Thermo sensor or
heat exchanger
sensor is defective.
Replace thermo sensor
or heat exchanger
sensor.
Replace P.C. board.
Rewire or replace
defective cords.
Replace compressor.
Replace capacitor.
YES
Is overload relay normal?
YES
Does compressor start?
YES
Does compressor stop after a while?
YES
Is gas quantity normal?
(Check gas pressure.)
YES
Compressor is defective.
YES
Replace P.C. board.
NO
NO
NO
Overload relay is
defective.
Compressor is defective.
Gas shortage (Gas leak)
- 57 -
Replace overload relay.
Replace compressor.
Supply gas.
Page 59
<Inspection procedure>
- Cooling model -
Turn on power supply.
FILE NO. SVM-06020
Does OPERATION
lamp blink?
YES
Is it possible to start
unit by remote control?
YES
Is it possible to detect AC 200V
between 2 and 3 on terminal block?
YES
Is crossover cable normal?
YES
Are all of compressor cords normal?
YES
Is compressor motor winding normal?
(Check winding resistor.)
YES
Is capacitor for compressor normal?
YES
NO
NO
NO
NO
NO
NO
NO
Compressor is defective.
Capacitor is defective.
Refer to item Power
can not be turned on .
Refer to 9-9 Troubleshooting
for Remote Control .
Replace P.C. Board
Connect crossover
cable properly.
Rewire or replace
defective cords.
Replace compressor.
Replace compressor.
Is overload relay normal?
YES
Does compressor start?
YES
Does compressor stop after a while?
YES
Is gas quantity normal?
(Check gas pressure.)
YES
Compressor is defective.
YES
Replace P.C. borad
NO
NO
NO
Overload relay is defective.
Compressor is defective.
Gas shortage (Gas leak)
Replace overload relay.
Replace compressor.
Supply gas.
- 58 -
Page 60
<Inspection procedure)
- Heating model -
AC 70-100V
FILE NO. SVM-06020
Replace transformer
outdoor
P.C. board.
- 59 -
Page 61
YES
FILE NO. SVM-06020
Are all of compressor cords normal?
YES
Is compressor motor winding normal?
(Check winding resistor.)
YES
Is capacitor for compressor normal?
YES
Is overload relay normal?
YES
Does compressor start?
YES
Does compressor stop after a while?
YES
Is gas quantity normal?
(Check gas pressure.)
YES
NO
NO
NO
NO
NO
NO
Compressor is defective.
Capacitor is defective.
Overload relay is defective.
Compressor is defective.
Gas shortage (Gas leak)
Rewire or replace
defective cords.
Replace compressor.
Replace capacitor.
Replace overload relay.
Replace compressor.
Supply gas.
Compressor is defective.
YES
Replace compressor.
- 60 -
Page 62
FILE NO. SVM-06020
9-7. Troubleshooting for Wiring (Interconnect cable and Serial Signal Wire)
9-7-1. Outdoor unit does not operate.
<Inspection procedure>
(1) Is the voltage between and of the indoor terminal block varied?
1
(2) Are signals from the indoor unit to the outdoor unit transmitted correctly based upon the following diagram?
NOTE:
Measure the voltage for 2 minutes and 30 seconds after starting the unit.
Heatpump model
Terminal block on indoor side
Red
2
3
White
2
1
Terminal block
Tester
Normal condition : Voltage varied between AC70 ~ 100V
Abnormal condition : Voltage does not vary.
Cooling model
Terminal block on indoor side
Red
White
3
2
1
Terminal block
Tester
Fig. 9-7-1
Normal condition : After start operated about 2 minutes and 30 seconds. Voltage between 2 and 3 of the
of the indoor's Terminal block should be equal AC 220 ~ 240V (For Asia model), AC 220V
(For Thai model).
Abnormal condition : Don't found voltage AC 220 ~ 240V (For Asia model), AC 220V (For Thai model) from
terminal block (0V)
9-7-2. Outdoor unit stops a while after starting the unit.
<Confirmation procedure> Select one of 3 cases below and follow the procedure.
(1) The outdoor unit stops between 10 and 20 minutes passed after starting and it takes 10 minutes or more to
restart the unit.
Gas has a low circulation.
Measure gas pressure.
Compressor is turned off and on automatically by thermo sensor
(Heat pump Model) or thermostat (Cooling only Model).
Gas shortage
Gas leak
Pipe clogging
(2) The outdoor unit stops once, it would not operate until the power is turned on again.
Refer to 9-6-4 "Compressor does not operate"
(3) The outdoor unit stops between 10 minutes to 1 hour after starting and a check code is indicated on the
remote control. (Check code 03-1E : Refer to Table 9-4-1.)
- 61 -
Page 63
FILE NO. SVM-06020
9-8. Troubleshooting for P.C. board
9-8-1. How to check indoor P.C. board
<Cautions for handling P.C. board>
(1) When removing the front panel and the P.C. board,
be sure to turn off the power supply.
(2) When removing the P.C. board, hold the edge of
the P.C. board and do not apply force to the parts.
(3) When connecting or disconnecting the connectors
on the P.C. board, hold the housing. Do not pull at
lead wires.
<Inspection procedure>
(1) If the P.C. board is detective, check for disconnec-
tion, burn or discoloration of the copper foil pattern
of the P.C. board.
(2) The P.C. board consists of the following 2 parts:
a. Main P.C. board parts.
Power relay, indoor fan motor drive circuit and
control circuit, C.P.U. and peripheral circuits, buzzer
drive circuit and buzzer.
b. Infrared rays parts:
Infrared rays receiving circuit
Check the defects of the P.C. board with Table 9-8-1.
Table 9-8-1 Inspection pr ocedure
No. Procedure Check points Causes
1Turn off the power supply and
remove the P.C. board assembly
from electric parts base. Remove
the connecting cables from the
terminal block.
2Remove the connector of the motor
and turn on the power supply. If
OPERATION lamp blinks (once per
second), it is not neccessary to
check steps (1 to 3) in the right
next column.
Check whenther or not the fuse (F01)
is blown.
Check power supply voltage;
1. Between CN30 and CN31
(220 − 240 V AC) : Except
2. Between + and − of C63
(DC310 − 340 V)
3. Between 12 V and GND
4. Between 5 V and GND
Impluse voltage was applied or the
indoor fan motor short-circuited.
1. The terminal block or the
crossover cable is connected
wrongly.
2. The capacitor (C01 and C02 )
line filter (L01), resistor (R319), or
the diode (DB01) is defective.
3. C65, C66 and M01 are defective.
4. IC04, C05, C06 and C07 are
defective.
3 Press [ ] button once
to start the unit. (Do not set the
mode to Fan Only or On-Timer
operation).
4Shorten the line of the restart delay
timer and start unit.
Check power supply voltage;
<Heat pump model>
1. Between CN31 and CN23
(DC15 − 60 V)
<Cooling only model>
1. Between connector of Q24 and
GND (for relay coil (DC12 V))
2. Between 1 and 2 of terminal
block for connecting cable
Check whether or not all lamps
(OPERA TION, TIMER, PRE.-DEF.
(or FAN ONLY), FILTER.and Hi Power)
are indicated for 3 seconds and they
return to normal 3 seconds later.
<Heat pump model>
IC32 and IC33 are defectice.
<Cooling only model>
1. The wire of the relay coil (RY04)
comes down or the relay drive
(Q24) is defective.
2. CN27 or RY04 is connected
wrongly.
The lamps are defective or the
housing assembly (CN13) is
defective.
- 62 -
Page 64
FILE NO. SVM-06020
No.ProcedureCheck pointsCauses
5 Press [ ] button once
to start the unit.
• Shorten the time of the restart
delay timer.
• Set the operation mode to COOL.
• Set the fan speed level to AUTO.
• Set the preset temperature much
lower than the room temperature.
(The unit (compressor) operates
continuously in the above
condition.)
1. Check whether or not the
compressor operates.
2. Check whether or not the
OPERATION lamp blinks.
1. The temperature of the indoor
heat exchanger is extremely low.
2. The connection of the heat
exchanger sensor is loose.
(The connector is disconnected.)
(CN01)
3. The heat exchanger sensor and
the P.C. board are defective.
(Refer to Table 9-8-2.)
4. The main P.C. board is defective.
6If the above condition (No. 6) still
continues, start the unit in the
following condition.
• Set the operation mode to HEAT.
• Set the preset temperature much
higher than room temperature.
7Connect the motor connector to the
motor and turn on the power supply.
Start the unit in the following
condition.
• Set the operation mode to FAN.
• Set the fan speed level to HIGH.
(The unit (compressor) operates
continuously in the above codition.)
1. Check whether or not the
compressor operates.
2. Check whether or not the
OPERATION lamp blinks.
1. Check it is impossible to detect the
voltage (DC 12 V) between and1
3 of the motor terminals.
2. The motor does not operate.
(But it is possible to receive the
signal from the remote control.)
3. The motor rotates but vibrates
strongly.
1. The temperature of the indoor
heat exchanger is extremely high.
2. The connector of the heat
exchanger sensor short-circuited.
(CN01)
3. The heat exchanger sensor and
the P.C. board are defective. (Refer
to T ab le 9-8-2.)
4. The main P.C. board is defective.
1. The indoor fan motor is defective .
(Protected operation of P.C. board)
2. The connection of the motor
connector is loose.
3. The P.C. board is defective.
Table 9-8-2 Approximate resistance value of thermo sensor
Temperature0°C10°C20°C25°C30°C
Resistance value33.820.3512.5910.07.99
(kΩ)
9-8-2. How to Shorten Time of Restart Delay Timer
1 Press [CLR] button while pressing [CHK] button
with a tip of a pencil.
2 Then press [ ] button to transmit the
signal to the indoor unit.
9-8-3. How to use self cleaning function
The self cleaning function is set from a factory.
To cancel this function, should keep press the
temporary switch for 20 secounds till can hear
the long combination sound and repeat the
same procedure when need to set.
2
1
- 63 -
Page 65
9-9. Troubleshooting for Remote Control
FILE NO. SVM-06020
Is receiver on
indoor unit exposed
to direct sunlight?
YES
NO
Is there any
thyristor fluorescent
light nearby?
YES
YES
NONO
Press START/STOP
button.
Is transmission
mark indicated?
Does indoor unit
operate when
moving remote control
near receiver or
indoor unit?
YES
Batteries are
exhausted.
The unit does not beep at all.
OPERATION lamp on
indoor unit is not indicated.
NO
Press RESET button
on remote control
with tip of pencil.
Press START/STOP
button.
Avoid direct
sunlight.
Keep indoor unit
away from
thyristor
fluorescent light.
Does indoor unit
NO
start to operate by
automatic restart
function?
YES
Does radio sound
is affected by
remote control when
a signal is transmitted
at distance of 5 cm
from radio?
P.C. board is
defective.
Replace
P.C. board.
YES
NO
NO
Replace
batteries.
Note : After replacing batteries,
press the RESET button
with a tip of a pencil.
- 64 -
Is transmission mark
indicated?
YES
Does indoor unit
beep and operate?
YES
Normal
operation
NO
Remote control
is defective.
Replace
remote control.
Page 66
FILE NO. SVM-06020
10. PART REPLACEMENT
10-1. Indoor Unit
No. Part name Procedures Remarks
1 Front panel
How to remove the front panel
1) Stop the operation of the air conditioner and turn off
its main power supply.
2) Pull the inlet grille toward you to open it and remove
4 screws fixing the front panel.
3) Remove upper 3 hooks of the front panel from the
back body.
4) Open the horizontal grille right below by hand.
5) Pull the lower side of the front panel toward you
until it touches the horizontal grille to remove it.
(2)
(2)
4-screws
(2)
2 Electrical part
assembly
How to mount the front panel
1) Mount the front panel with the inverse procedure of
“How to remove the front panel”.
2) Push 3 places (right, left and center) of the air
outlet.
3) Check the gap between the front panel and the
back body.
If you operate the air conditioner in cooling or dry
operation without pushing the 3 places, the surface
of the front panel may be covered with frost and
have dewdrops.
1) Remove the front panel with the procedure 1.
2) Remove the screw fixing the electrical part box.
3) Remove the drain guide.
4) Remove the connector (
and the connector (6P) for the louver motor from
the microcomputer assembly.
5) Remove the screw for the earth, and pull the
electrical part base toward you to remove it from the
main unit.
6) Pull out the TC sensor from the sensor holder.
3P x 2) for the fan motor
(3) Drain guide
(3)
(4)
(5) screws
(3P X 2)
6P
(2) screws
- 65 -
(6) TC sensor
When assembling the electrical parts
assembly, make the connecting cable
U-shaped and put it in the drain pan.
Page 67
FILE NO. SVM-06020
No. Part name Procedures Remarks
3 Horizontal louver
4 Heat exchanger
1) Remove center 2 shafts of the horizontal grille from
the back body.
2) Remove left shaft of the horizontal
louver from the
back body.
3) Remove the horizontal
louver from the back body.
1) Remove the front panel, electrical parts assembly
and the horizontal louver with procedure 2 and 3.
2) Remove the screw on the rear side of the main unit
to remove the pipe holder.
3) Remove 2 screws fixing the heat exchanger and the
bearing base.
4) Remove 2 screws fixing the heat exchanger fixtures
(upper and lower) and the back body then pull out
the upper side of the heat exchanger slowly.
(1) Center shafts
(2) Left shafts
(3) 2 screws
(2) Screw
Bearing base
(3)
Pipe holder
(4) 2 screws
5 Cross flow fan
6 Bearing base
1) Remove the front panel, electrical parts assembly,
horizontal
louver and the heat exchanger with
procedure 4.
2) Loosen the set screw of the cross flow fan.
3) Remove 2 screws fixing the bearing base and the
back body.
4) Pull the cross flow fan toward you.
1) Remove the front panel, electrical parts assembly,
horizontal
louver, heat exchanger and the cross flow
fan with procedure 5.
2) Remove the bearing from the bearing base.
If the housing protrudes from the base bearing, put
the housing in position and assemble the bearing to
the bearing base.
(3) Screws
(2) Set screw
When assembling the cross flow fan, fix it
with the set screw at the position where the
gap between the back body and the right
surface of the cross flow fan is 4 mm.
Bearing base
Bearing
7 Fan motor
1) Remove the front panel, electrical parts assembly,
horizontal louver, and the heat exchanger with
procedure 4.
2) Loosen the set screw of the cross flow fan.
3) Remove 2 screws of the motor fixture.
4) Remove the lower side of the body (R) and move it
right to remove it.
5) Remove the motor from the motor fixture.
- 66 -
(3) 2 screws
(4) BODY (R)
(5)
Motor fixture
Page 68
FILE NO. SVM-06020
10-2. Outdoor Unit (RAS-24GAH-ES2, RAS-24GA-ES2)
No. Part name Procedures Remarks
Top cabinet
1Common
procedure
1) Stop the operation of the air conditioner and turn off
its main power supply or remove the power supply
cord.
2) Remove the packed valve cover and the
electrical parts cover (2 screws ∅4 x 10L)
3) Remove 2 cord clamps (4 screws ∅4 x 16L) and
disconnect the power supply cord and connecting
cable after removing 6 screwson on the terminal
block and 1 ground screw on the electrical parts
base.
4) Remove the top cabinet. (7 screws ∅ 4 x 10L)
(Pulling out upward)
5) Remove the top cabinet. (2 screws ∅ 4 x 10L)
(Pull the front right portion toward you, and
remove it pulling out upward)
Front cabinet
2 screws
∅4 x 10L
Packed valve cover
2 Cord clamps
Side cabinet
4 screws ∅4 x 16L
7 screws ∅4 x 10L
Front
cabinet
- 67 -
Page 69
FILE NO. SVM-06020
No.
2Running
3Running
4Magnetic
5 Spark killer
Part name
capacitor
for compressor
capacitor
for fan motor
contactor
(Cooling only model)
Procedures
1) Perform the common procedure 1
2) Remove the capacitor band. (1 screw ∅4 x 10L)
3) Disconnect the lead wires from the capacitor
terminal.
1) Perform the common procedure 1
2) Remove the fixing screw. (1 screw ∅4 x 10L)
3) Disconnect the lead wires from the capacitor
terminal.
1) Perform the common procedure 1
2) Remove the fixing screw. (2 screws ∅4 x 16L)
3) Disconnect the lead wires from the terminal.
1) Perform the common procedure 1
2) Remove the fixing screw. (1 screws ∅4 x 10L)
3) Disconnect the lead wires from the terminal.
Remarks
Running capacitor
for compressor
Running capacitor
for fan motor
Cooling only model
Spark killer
Magnetic contactor
- 68 -
Page 70
FILE NO. SVM-06020
10-3 Outdoor Unit (RAS-18GAH-ES2, RAS-18GA-ES2)
No. Part name Procedures Remarks
1Common
procedure
1) Stop the operation of the air conditioner and turn off
its main power supply or remove the power supply
cord.
2) Remove the packed valved cover and the electrical
Parts cover
(2 screws ∅ 4 x 10L)
3) Remove 2 cord clamps (4 screws ∅ 4 x 16L) and
disconnect the power supply cord and connecting
cable after removing 6 screws on the terminal block
and 1 ground screw on the electrical parts base.
4) Remove the upper cabinet. (4 scerws ∅ 4 x 10L)
(Pulling out upward)
5) Remove the front cabinet. (3 screws∅ 4 x 10L)
(Pull the front right protion toward you, and remove
it pulling out upward.)
Packed valve cover
2 screws ∅4 x 10L
Upper
cabinet
2 Cord clamps
4 screws ∅4 x 16L
Running
2
capacitor
for compressor
Running
3
capacitor
for fan motor
4
Magnetic contactor
Transformer
5
(Heat pump model)
P.C. Board
6
(Heat pump model)
7
Spark killer
(Cooling only model)
1) Perform the common procedure 1
2) Remove the capacitor band. (1 screw ∅4 x 10L)
3) Disconnect the lead wires from the capacitor
terminal.
1) Perform the common procedure 1
2) Remove the fixing screw. (1 screw ∅4 x 10L)
3) Disconnect the lead wires from the capacitor
terminal.
form the common procedure 1
1) Per
2) Remove the fixing screw. (2 screws ∅ 4 x 10L)
3) Disconnect the lead wires from the terminal.
1) Perform the common procedure 1
2) Remove the fixing screw. (2 screws ∅ 4 x 10L)
3) Disconnect the housing from the P.C. Board.
1) Perform the common procedure 1
2) Disconnect the lead wires from the P.C. Board.
3) Remove P.C.Board after unhooking 4 clams.
1) Perform the common procedure 1
2) Remove the fixing screw. (1 screw ∅ 4 x 10L)
3) Disconnect the lead wires from the terminal.
Running capacitor
for fan motor
Running
capacitor
for compressor
Running capacitor
Running capacitor
for compressor
Front
cabinet
Heat pump model
for fan motor
Cooling only model
P.C. Board
Transformer
Magnetic contactor
Spark killer
Magnetic contactor
- 69 -
Page 71
11. EXPLODED VIEWS AND PARTS LIST
11-1. Indoor Unit (E-Parts Assy)
413
FILE NO. SVM-06020
411
407
LocationPartLocationPart
No.No.No.No.
40243T60002 TERMINAL BLOCK; 3P41143T69527 PC BOARD (RAS-24GKHP)
40343T50004 SENSOR; HEAT EXCHANGER41143T69528 PC BOARD (RAS-24GKP)
40443T50314 SENSOR;THERMOSTAT41143T69529 PC BOARD (RAS-18GKHP)
40543T69559 PC BOARD ASSY ; WRS-LED41143T69530 PC BOARD (RAS-18GKP)
40743T62003 CORD CLAMP41343T63310 SENSOR HOLDER
143T42324 BASE PLATE ASSEMBLY2443T19330PACKED VALVE COVER
243T41397 COMPRESSOR;PA290X3CS-4MU2543T00455 UPPER CABINET
343T49011 SPRING BASE(UPPER)2643T96305BUSHING
443T49012 SPRING BASE (LOWER)2743T62325ELECTRIC PART COVER
543T49019 SPRING; BUFFER2843T61306 ELECTRIC PARTS BASE
643T97307 COMPRESSOR BOLT (M6)2943T52301 SWITCH;MAGNET; CLK-35J
743T43391 CONDENSER ASSEMBLY3043T55340MF CAPACITOR
843T00448 FIXING PLATE VALVE3143T55341 CAPACITOR;PLASTIC-FILM
943T46332 VALVE;PACKED 6.35 DIA3243T60352TERMINAL BLOCK; 6P
1043T46335VALVE;PACKED 12.7 DIA (H4)3543T19331 FIN GUARD
1143T47331BONNET, 6.35 DIA3643T00456UPPER FRONT CABINET; A
1243T47333BONNET, 12.70 DIA3743T00457 UPPER FRONT CABINET; B
1343T47013CAPILLARY TUBE; 2.0 DIA3843T 71301HANDLE
1443T00468FRONT CABINET3943T46337 4 WAY VALVE
1543T00474LEFT CABINET 4043T46339COIL;V-4WAY;AC220-240V 50Hz
1643T00454RIGHT CABINET4143T69059 SENSOR; TE
1743T21378FAN MOTOR;AC220-240V 50Hz4243T69060SENSOR; TD
1843T20319PROPELLER FAN4343T79305DRAIN NIPPLE
1943T47001NUT FLANGE4443T58301 TRANSFORMER; TT-05
2043T19329FAN GUARD4543T69580PC BOARD
2143T04302PARTITION4643T60325FILTER;CLAMP
22 43
2343T39318MOTOR BASE
T39317 MOTOR BASE CONNECTION PLATE 47 43T47308 CAPILLARY TUBE; 1.0 DIA
DescriptionDescription
- 72 -
Page 74
11-4. Outdoor Unit (RAS-18GAH-ES2)
FILE NO. SVM-06020
LocationPartLocationPart
No.No.No.No.
1 43T42324 BASE PLATE ASSEMBLY 22 43T39317 MOTOR BASE CONNECTION PLATE
243T41396 COMPRESSOR;PA225X2C-4KU1 2343T39318 MOTOR BASE
343T49011 SPRING BASE(UPPER)2443T19330PACKED VALVE COVER
443T49012 SPRING BASE (LOWER)2543T00460UPPER CABINER ASSEMBLY
543T49019 SPRING; BUFFER2643T96305BUSHING
643T97307 COMPRESSOR BOLT (M6)2743T62325 ELECTRIC PART COVER
743T43392 CONDENSER ASSEMBLY 2843T61307 ELECTRIC PARTS BASE
8 43T00448 FIXING PLATE VALVE 29 43T52302 MAGNETIC CONTACTOR; AC220-240V 50Hz
843T00448 FIXING PLATE VALVE2743T62325 ELECTRIC PART COVER
943T46332 VALVE;PACKED 6.35 DIA2843T61306ELECTRIC PARTS BASE
1043T46335VALVE;PACKED 12.7 DIA (H4)2943T52301 SWITCH;MAGNET; CLK-35J
1143T47331BONNET, 6.35 DIA3043T55340MF CAPACITOR
1243T47333BONNET, 12.70 DIA3143T55341 CAPACITOR;PLASTIC-FILM
1343T47013CAPILLARY TUBE; 2.0 DIA3243T60352TERMINAL BLOCK; 6P
1443T00468FRONT CABINET3343T33002 SPARK-KILLER
1543T00474LEFT CABINET 3543T19331FIN GUARD
1643T00454RIGHT CABINET3643T00456 UPPER FRONT CABINET; A
1743T21377FAN MOTOR;AC220-240V 50Hz3743T00457UPPER FRONT CABINET; B
1843T20319PROPELLER FAN3843T71301HANDLE
1943T47001NUT FLANGE
DescriptionDescription
- 74 -
Page 76
11-6. Outdoor Unit (RAS-18GA-ES2)
FILE NO. SVM-06020
LocationPartLocationPart
No.No.No.No.
143T42324 BASE PLATE ASSEMBLY1943T47001NUT FLANGE
243T41396 COMPRESSOR;PA225X2C-4KU12043T19329 FAN GUARD
343T49011 SPRING BASE(UPPER)2143T04301PARTITION
4 43T49012 SPRING BASE (LOWER) 22 43T39317 MOTOR BASE CONNECTION PLATE
543T49019 SPRING; BUFFER2343T39318 MOTOR BASE
643T97307 COMPRESSOR BOLT (M6)2443T19330 PACKED VALVE COVER
743T43389 CONDENSER ASSEMBLY 2543T00460 UPPER CABINER ASSEMBLY
843T00448 FIXING PLATE VALVE2643T96305 BUSHING
943T46332 VALVE;PACKED 6.35 DIA2743T62325ELECTRIC PART COVER
1043T46335VALVE;PACKED 12.7 DIA (H4)2843T61304 ELECTRIC PART BASE
11 43T47331 BONNET, 6.35 DIA 29 43T52302 MAGNETIC CONTACTOR; AC220-240V 50Hz
1243T47333BONNET, 12.70 DIA3043T55340 MF CAPACITOR
1343T47014CAPILLARY TUBE; 1.7DIA3143T55324 CAPACITOR; PLASTIC-FILM
1443T00468FRONT CABINET3243T60352 TERMINAL BLOCK; 6P
1543T00459LEFT CABINET3343T33002 SPARK-KILLER
1643T00451RIGHT CABINET ASSEMBLY3443T61305 MAGNETIC RELAY BASE
1743T21345FAN-MOTOR(Made in China)3543T19331 FIN GUARD
1843T20319PROPELLER FAN
DescriptionDescription
- 75 -
Page 77
FILE NO. SVM-03009(1)
TOSHIBA CARRIER (THAILAND) CO.,LTD.
144/9 MOO 5, BANGKADI INDUSTRIAL PARK, TIVANON ROAD, TAMBOL BANGKADI,
AMPHUR MUANG, PATHUMTHANI 12000,THAILAND.
– 75 –
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.