Toshiba RAS-13YKH-ES, RAS-07YKHE, RAS-07YAH-ES, RAS-07YAH-E, RAS-10YKH-E SERVICE MANUAL

...
SERVICE MANUAL
AIR-CONDITIONER
SPLIT WALL TYPE
RAS-07YKH-E/RAS-07YAH-E
FILE NO. DAS-SM-00-003
SUPPLEMENT
RAS-10YKH-E
/
RAS-13YKH-E / RAS-13YAH-E
RAS-07YKH-ES/RAS-07YAH-ES RAS-10YKH-ES / RAS-10YAH-ES RAS-13YKH-ES / RAS-13YAH-ES

CONTENTS

1. SPECIFICATIONS.................................................................................... 3
2. CONSTRUCTION VIEWS ....................................................................... 7
3. WIRING DIAGRAM ................................................................................ 10
4. SPECIFICATIONS OF ELECTRICAL PARTS ..................................... 12
5. REFRIGERANT CYCLE DIAGRAM ..................................................... 15
6. CONTROL BLOCK DIAGRAM ............................................................. 21
7. OPERATION DESCRIPTIONS................................................................ 22
8. INSTALLATION PROCEDURE .............................................................. 30
9. TROUBLESHOOTING CHART.............................................................. 44
10. PART REPLACEMENT.......................................................................... 60
11. EXPLODED VIEWS AND PARTS LIST .............................................. 65
– 2 –

1. SPECIFICATIONS

RAS-10YKH-E / RAS-10YAH-E, RAS-13YKH-E / RAS-13YAH-E
MODEL
ITEM
Capacity kW *1
Phase Single V220–240Power source
Hz 50 Power consumpt i on kW 0,98–1,02 0,89–0,91 1,26–1,30 1,19–1,27 Power fac tor % 95–90 95–88 98–92 95–93
Running current Starting c urr e nt A 19 14 25 25
Moisture remov a l lit/h 1,2 2,0 Noise
(SPL at 1 me te r ) Refrigerant
Refrig erant control Capillary tube
Interconnection pipe
Condensate drain pipe Outer diameter mm 16
INDOOR UNIT RAS-10YKH-E RAS-13YKH-E
Net weight kg 8 Evap orator type Finned tube Indoor fan type Cross flow fan
Fan motor output W 20 Air filter Polypropylene net filter (Washable)
OUTDOOR UNIT RAS-10YAH-E RAS-13YAH-E
Net weight kg 31 42 Condenser type Finned tube Outdoor fan type Propeller Air flow rate (220–240V) m³/h 1500–1700 1690–1730 Fan motor output W 18 28
Compressor Safety device Fuse, Overload relay
Auto l ouver Yes Usable outdoor temperature range °C21–43 -5–21 21–43 -5–21
Indoor/Outdoor A
Indoor (H/M/L) dB (A) 41 / 36 / 29 41 / 36 / 29 44 / 39 / 34 44 / 39 / 34 Outdoor (220–240V) dB (A) 47–49 47–49 49 / 51 49 / 51 Name of refrigerant R-22 Rated volume kg 0,74 0,88
Gas side size mm 9,52 12,7 Connection type Flare connection Liquid side size mm 6,35 Connection type Flare connection Maximum length (of one way) m *210 15 Maximum he ight differenc e Indoor un it Outdoor unit
Height mm 265 Width mm 790Dimensions Depth mm 189
High fan m³/h 600 650 Medium fan m³/h 500 560Air flow rate Low fan m³/h 400 510
Height mm 530 538 Width mm 770 780Dimensions Depth mm 200 300
Model PH120T1-4C PH170T2-4L2 Output W 750 1100
↑ ↓
V220V–240V 220V–240V 220V–240V 220V–240V
m
RAS-10YKH-E/10YAH-E RAS-13YKH-E/13YAH-E
Cooling Heating Cooling Heating
220V–240V 220V–240V 220V–240V 220V–240V
2,65–2,70 3,00–3,10 3,45–3,50 4,00–4,10
0,11/4,58 - 0,11/4,61 0,11/4,17 - 0,11/4,22 0,15/5,70 - 0,15/5,75 0,15 /5,54 - 0,15/5,44
56
Specifications are subject to change without notice.
– 3 –
RAS-10YKH-ES / RAS-10YAH-ES, RAS-13YKH-ES / RAS-13YAH-ES
MODEL
ITEM
Capacity kW *1
Phase Single
V220–240Power source
Hz 50 Power consumpt ion kW 0,98–1,02 0,89–0,91 1,26–1,30 1,19–1,27 Power f acto r % 9 5–90 95–88 98–94 97–93
Runnin g cur r ent Starti ng current A 19 14 25 25
Moisture removal lit/h 1,2 2,0 Noise
(SPL at 1 me t er) Refrigerant
Refrigerant control Capillary tube
Interconnection pipe
Condensate drain pipe Outer diameter mm 16
INDOOR UNIT RAS-10YKH-ES RAS-13YKH-ES
Net weight kg 8 Evap orator type Finned tube Indoor fa n type Cross flow fa n
Fan motor output W 20 Air filter Polypropylene net filter (Washable)
OUTDOOR UNIT RAS-13YAH-E RAS-13YAH-ES
Net weight kg 31 42 Condenser type Finned tube Outdoor fan type Propeller Air flow rate (220–240V) m³/h 1500–1700 1690–1730 Fan motor output W 18 28
Compressor Safety device Fuse, Overload relay
Aut o louve r Yes Usable outdoo r te m perature range °C21–43 -5–21 21–43 -5–21
Indoor/Outdoor A
Indoor (H/M/L) dB (A) 41 / 36 / 29 41 / 36 / 29 44 / 39 / 34 44 / 39 / 34 Outdoor (220–240V) dB (A) 47–49 47–49 49 / 51 49 / 51 Name of refrigerant R-410A Rated volume kg 0,69 0,80
Gas side size mm 9,52 Connection type Flare connection Liquid side size mm 6,35 Connection type Flare connection Maximum length (of one way) m *210 15 Maximum height differenc e Indoor unit Outdoor unit
Height mm 265 Width mm 790Dimensions Depth mm 189
High fan m³/h 600 650 Medium fan m ³/h 500 560Air flow rate Low fan m³/h 400 510
Height mm 530 538 Width mm 770 780Dimensions Depth mm 200 300
Model PA118X1T-4FZ PA160X2T-4FM Output W 750 1100
↑ ↓
V220V–240V
m
RAS- 10 YKH- ES/10YAH-ES RAS-13YKH-ES/13YAH-ES
Cooling Heating Cooling Heating
220V–240V
2,65–2,70 3,00–3,10 3,45–3,50 4,00–4,10
0,11/4,44 - 0,11/4,46 0,11/4,15 - 0,11/4,10 0,15 /5,70 - 0,15/5,61 0,15 /5,43 - 0,15/5,54
56
Specifications are subject to change without notice.
– 4 –
Note :
Capacity is based on the follo wing temperature conditions.
1
*
TEMPERATURE
Indoor unit inlet air temperature
Outdoor unit inlet air temperature
Notes : *2 CHARGELESS
RAS-07YKH-E, RAS-07YKH-ES, RAS-10YKH-E, RAS-10YKH-ES
No additional refrigerant required.
This air conditioner accepts a connection piping length of up to 10m and a head of up to 5m.
There is no need to add the refrigerant as long as the total length of the connection piping is up to 10m.
RAS-13YKH-E, RAS-13YKH-ES
No additional refrigerant required.
This air conditioner accepts a connection piping length of up to 15m and a head of up to 6m.
There is no need to add the refrigerant as long as the total length of the connection piping is up to 15m.
CONDITION COOLING HEATING
(DB) 27 °C 20 °C
(WB) 19 °C 12 °C
(DB) 35 °C 7 °C
(WB) 24 °C 6 °C
6

2-1. Indoor Unit

2. CONSTRUCTION VIEWS

Air inlet
265
Air outlet
Air filter
790
790
232 326 232
Hanger
Heat exchanger
Front panel
Back body
189
47
Knock out system
50
10
Drain hose (0,54m)
Hanger
Connecting pipe (0,39m) (Flare Ø9,52)
(Flare Ø12,7 for 13YKH-E only)
Hanger
46
2,5
Minimum distance
17 20
265
to wall
120 or more 120 or more
178,5
3,5
40,5
Center line
321
65965,5 450
326
66 or more
Minimum distance to ceiling
HangerHanger
Installation
plate outline
790
Connecting pipe (0,49m)
(Flare Ø6,35)
65,5
12626931976
Hanger For stud bolt
(Ø8~Ø10) For stud bolt
(Ø6)
Minimum distance
20 2037
to wall
40,5
60,5
50
47
10
Knock out system
7

2-2. Outdoor Unit

RAS-07YKH-E, RAS-07YKH-ES, RAS-10YKH-E, RAS-10YKH-ES
600 85
Detail Drawing
A
36 50
216
230
25
Ø11x14 Hole
Handle
600
R10
Ø6 Hole
11
A
230
216
Fan guard
36
30
50
111
Ø25 Drain hole
8-Ø6 Holes (For fixing the outdoor unit)
4-Ø11x14 Long holes (For anchor bolt Ø8-Ø10)
111
Gas side (flare Ø9,52)
Liquid side (flare Ø6,35)
200
12
11
525
5
530
Ø420
268
89
59
TOSHIBA
770 59
770
268
89
Electric parts cover
Z
54 62
Service port
250
230
Inlet port
100 or more
View
Z
600
Inlet port
45 or more
Visible outline of the product
Outlet port
Center
400 or more
Mounting dimension of anchor bolt
port
600 or more
(Minimum distance of the wall)
4-Ø11x14 Long holes
(For anchor bolt Ø8-Ø10)
8
RAS-13YAH-E, RAS-13YAH-ES
Detail Drawing
A
325
301
Ø11x14 hole
Handle
300
50 36
600
R10
23
Ø6 hole
538
52,5
325
Fan guard
Ø420
A
Ø25 Drain outlet
120
6-Ø11x14 hole (for Ø8-Ø10 anchor bolt)
600 780
90
Gas side (Flare Ø12,7 for 13YAH-E, Flare Ø9,52 for 13YAH-ES)
Liquid side (Flare Ø6,35)
8-Ø6 hole(for fixing outdoor unit)
Electric parts cover
59
27
100
(8,5)
130
325 (pitch)
342
54
61
Z
Service port
(8,5)
Installation dimension
100 or more
325
100 or more
Z
Air outlet
View
600
Air inlet
600 or more
9
600 or more
4xØ11x14 Long holes (for Ø8-Ø10 anchor bolt)
07 07
07
07
RAS-13YKH-E / RAS-13YAH-E RAS-13YKH-ES / RAS-13YAH-ES
P04
BRW
BLU
1 3
SG01
DSA
POWER
TERMINAL
BLOCK
Ø 220V-240V
BLK
GRN&YEL
L N
50Hz
RY02
BLK
WHI
VARISTOR
3
4
T02
C.T
R22
CN04
250V
3
4
RY04RY03
F01
6,3A
RY01
CR01
CR02
ORN
2
1 1
2
R21
THERMAL FUSE 77˚C x 2
ORN
C15
L01
23
1
23
1
YEL
BLK
BRW
LOUVER MOTOR
INFRARED RAYS RECEIVE
AND INDICATION PARTS
6
7
5
CN07
C01
BLU
6 6
PNK
4
5
4
5
R01
YEL
ORN
RED
3
2
3
2
BRW
1 1
DB01
1
BLU
BLU
BLU
4433221
BLU
4321
5
BLU
5
6
BLU
6
7
PNK
7
8 8
BLK
8
9 9
WHI
9
CN25
CN13
C02
POWER SUPPLY
2 2
BLK
CN03CN10
CIRCUIT
MCC-798
2
1
2
1
BLK
BLK
HEAT
EXCHANGER
SENSOR
DC 12V
CR03 IC 03
DC 5V
C58
CN11 CN01
5 3 1 5 3 1
BLK
PNK
1
23456
1
23456
WHI
1 1
BLK
THERMO
SENSOR
(TA)
(TC)
Detail A
RAS-13YAH-ES RAS-13YAH-E
Same as
figure.
BLK
Detail B
RAS-13YAH-ES
Same as
figure.
RAS-13YAH-E
OVER LOAD
RELAY
BLK
THERMOSTAT
FOR
COMPRESSOR
BLK
COMPRESSOR
INDOOR
TERMINAL
BLOCK
OUTDOOR TERMINAL
BLOCK
COMPRESSOR
B
WHI
BLK
RED
321
321
BLK BLUBLU
RED
A
SOLENOID
COIL
CAPACITOR
PNK
WHI
11
BLU
4
4
RED
GRN&YEL
OUTDOOR
GRN & YEL
CHASSIS
CAPACITOR
RED
AC FAN MOTOR
INDOOR
BLK
WHI
FAN
MOTOR
COLOR IDENTIFICATION
:
BROWN
BRW
:
RED
RED
:
WHITE
WHI
:
YELLOW
YEL
:
BLUE
BLU
:
BLACK
BLK
:
GRAY
GRY
:
PINK
PNK
:
ORANGE
ORN
GRN&YEL
:
GREEN & YELLOW

4-2. Outdoor Unit

RAS-10YAH-E, RAS-10YAH-ES RAS-13YAH-E, RAS-13YAH-ES
No. PARTS NAME MODELS TYPE SPECIFICATIONS
Output (Rated) 750W, 2poles, 1phase, 220–240V, 50Hz
1 Compressor
Fan mot or
2
(for outd oor)
Running
3
capacitor (for fan motor)
Running
4
capacitor (for compressor)
5 Overload relay
Thermostat
6
(for com p ressor)
Solenoid coil
7
(for 4-way valve)
RAS-10YAH-E
RAS-13YAH-E
RAS-10YAH-ES
RAS-13YAH-ES
RAS-10YAH-E RAS-10YAH-ES
RAS-13YAH-E RAS-13YAH-ES
RAS-10YAH-E RAS-10YAH-ES
RAS-13YAH-E RAS-13YAH-ES
RAS-10YAH-E RAS-10YAH-ES
RAS-13YAH-E RAS-13YAH-ES
RAS-10YAH-E
RAS-13YAH-E
RAS-10YAH-E
RAS-10YAH-E RAS-13YAH-E
RAS-10YAH-ES RAS-13YAH-ES
PH120T1-4C
PH170T2-4L2
PA118X1T-4FZ
PA160X2T-4FM
UE6-21SJ5P
AF-230-28P
SK-50FMP1,5U1 AC 500V, 1,5mF
SK-50FMP1,5U2 AC 500V, 1,5mF
SK-40CMP25U1 AC 400V, 25mF
SK-40CMP35U1 AC 400V, 35mF
JMRA99269-9200 U/T : 6,8A (90°C), OPEN 135 ± 5°C, CLO S E : 69 ± 11°C JMRA99257-920 0 U/T : 8,0A (80°C), OPEN 145 ± 5°C, CLOSE : 75 ± 11°C
CS-7 OFF : 130°C, ON : 70°C
LB60012 AC 200 / 240V
VHV-01A1501A1 AC 200 / 240V
Winding resista n ce (W) (at 20°C)
Output (Rated) 1 100W, 2poles, 1phase , 220–240V, 50Hz Winding resista n ce (W)
(at 20°C) Output (Rated) 750W, 2poles, 1phase, 220–240V, 50Hz Winding resista n ce (W)
(at 20°C) Output (Rated) 1 100W, 2poles, 1phase , 220–240V, 50Hz Winding resista n ce (W)
(at 20°C) Output (Rated) 1 8W, 6poles, 1phase , 220–240V, 50Hz Winding resista n ce (W)
(at 20°C) Output (Rated) 2 8W, 6poles, 1phase , 220–240V, 50Hz Winding resista n ce (W)
(at 20°C)
C-R C-S
4,53 8,73
C-R C-S
2,22 3,04
C-R C-S
3,17 5,18
C-R C-S
2,26 3,53
Red-Black White-Black
370 370
Red-Black White-Black
198 160
– 13

5. REFRIGERANT CYCLE DIAGRAM

RAS-10YKH-E / RAS-10YAH-E
Indoor unit
Cooling
0,39m (Connecting pipe) ø9,52
O.D.:9,52mm O.D.:6,35mm
Cooling
Heating
Heating
P
Packed valve
(ø9,52)
Heating
4-way valve
Cooling
Compressor
PH120T
Accumulator
1
-4C
Evaporator
Cross flow fan
Dryer
T
0,49m (Connecting pipe) ø6,35
Packed valve
(ø6,35)
Capillary tube
ø1,5x500
Condenser
Refrigerant R-22 0,74kg
Fan speed
(indoor)
Ambient temp.
conditions DB/WB (°C)
Indoor Outdoor
50Hz
Cooling Heating
Standard
pressure P
(kg/cm²G)
Propeller fan Outdoor unit
Surface temp. of heat
exchanger interchanging
pipe T (°C)
Mark( )means check points of Gas Leak
Standard 15,0 40,0 High 21/ - 7/6 High temperature *119–23 52,0–59,0 Low 27/ - 21/15Heating Low temperature 12,5 35,0 High 21/ - -10/-10 Standard 6,0 12,0 High 27/19 35/24 High temperature 6,5 15,0 High 32/23 43/26Cooling Low temperature 4,0 2,0 Low 21/15 21/15
Note : Measure the heat exchanger temperature at the center of U-bend. (By means of TC sensor.)
1 : During heating ov erload, the high temperature limit control operation is included.
*
15
RAS-13YKH-E / RAS-13YAH-E
Indoor unit
Cooling
0,49m (Connecting pipe) ø12,7
O.D.:12,7mm O.D.:6,35mm
Cooling
Heating
Heating
P
Packed valve
(ø12,7) Gas container connection (Reinstall etc.)
Heating
4-way valve
Cooling
Compressor
PH170T2-4L2
Accumulator
Heat exchanger
Cross flow fan
Condenser
T
Capillary tube
ø0,6x1500
Capillary tube
ø1,7x400
0,39m (Connecting pipe) ø6,35
Packed valve
(ø6,35)
Capillary tube
ø1,2x400
Refrigerant R-22 0,88kg
Fan speed
(indoor)
Ambient temp.
conditions DB/WB (°C)
Indoor Outdoor
50Hz
Cooling Heating
Standard
pressure P
(kg/cm²G)
Propeller fan
Outdoor unit
Surface temp. of heat
exchanger interchanging
pipe T (°C)
Mark( )means check points of Gas Leak
Standard 15,0 43,0 High 21/ - 7/6 High temperature *119–23 52,0–59,0 Low 27/ - 21/15Heating Low temperature 12,5 35,0 High 21/ - -10/-10 Standard 5,0 10,0 High 27/19 35/24 High temperature 6,0 14,0 High 32/23 43/26Cooling Low temperature 4,0 2,0 Low 21/15 21/15
Note : Measure the heat exchanger temperature at the center of U-bend. (By means of TC sensor.)
1 : During heating ov erload, the high temperature limit control operation is included.
*
16
RAS-07YKH-E / RAS-07YAH-E
Indoor unit
Cooling
0,39m (Connecting pipe) ø9,52
O.D.:9,52mm O.D.:6,35mm
Cooling
Heating
Heating
P
Packed valve
(ø9,52)
Heating
4-way valve
Cooling
Compressor
PH80T
Accumulator
1
-4C
Evaporator
Cross flow fan
Dryer
T
0,49m (Connecting pipe) ø6,35
Packed valve
(ø6,35)
Capillary tube
ø1,5x1400
Condenser
Refrigerant R-22 0,63kg
Fan speed
(indoor)
Ambient temp.
conditions DB/WB (°C)
Indoor Outdoor
50Hz
Cooling Heating
Standard
pressure P
(kg/cm²G)
Propeller fan
Outdoor unit
Surface temp. of heat
exchanger interchanging
pipe T (°C)
Mark( )means check points of Gas Leak
Standard 15,0 40,0 High 21/ - 7/6 High temperature *119–23 52,0–59,0 Low 27/ - 21/15Heating Low temperature 12,5 35,0 High 21/ - -10/-10 Standard 6,0 12,0 High 27/19 35/24 High temperature 6,5 15,0 High 32/23 43/26Cooling Low temperature 4,0 2,0 Low 21/15 21/15
Note : Measure the heat exchanger temperature at the center of U-bend. (By means of TC sensor.)
1 : During heating overload, the high temperature limit control operation is included.
*
– 17 –
RAS-10YKH-ES / RAS-10YAH-ES
Indoor unit
Cooling
0,39m (Connecting pipe) ø9,52
O.D.:9,52mm O.D.:6,35mm
Cooling
Heating
Heating
P
Packed valve
(ø9,52)
Heating
4-way valve
Cooling
Compressor
Muffler
PA118X1T-4FZ
Accumulator
Condenser
Evaporator
Cross flow fan
Dryer
T
Capillary tube
ø1,2x400
0,49m (Connecting pipe) ø6,35
Packed valve
(ø6,35)
Muffler
Capillary tube
ø0,8x400
Refrigerant R-410A 0,69kg
Fan speed
(indoor)
Ambient temp.
conditions DB/WB (°C)
Indoor Outdoor
50Hz
Cooling Heating
Standard
pressure P
(MPaG)
Propeller fan Outdoor unit
Surface temp. of heat
exchanger interchanging
pipe T (°C)
Mark( )means check points of Gas Leak
Standard 2,5 43,0 High 20/ - 7/6 High temperature *13,1–3,6 51,0–58,0 Low 27/ - 21/15Heating Low temperature 2,2 36,0 High 20/ - -10/-10 Standard 0,9 10,0 High 27/19 35/24 High temperature 1,1 16,0 High 32/23 43/26Cooling Low temperature 0,6 2,0 Low 21/15 21/15
Note : Measure the heat exchanger temperature at the center of U-bend. (By means of TC sensor.)
1 : During heating ov erload, the high temperature limit control operation is included.
*
18
RAS-13YKH-ES / RAS-13YAH-ES
Indoor unit
Cooling
0,49m (Connecting pipe) ø9,52
O.D.:9,52mm O.D.:6,35mm
Cooling
Heating
P
Packed valve
(ø9,52) Gas container connection (Reinstall etc.)
Heating
4-way valve
Cooling
Muffler
Compressor
PA160X2T-4FM
Heat exchanger
Cross flow fan
Dryer
Condenser
T
Packed valve
Capillary tube
ø1,2x1200
(Note) Maximum pipe length is 15m Maximum pipe head is 6m
0,39m (Connecting pipe) ø6,35
(ø6,35)
Capillary tube
ø1,5x500
Refrigerant R-410A 0,80kg
Fan speed
(indoor)
Ambient temp.
conditions DB/WB (°C)
Indoor Outdoor
50Hz
Cooling Heating
Outdoor unit
Standard
pressure P
(MPaG)
Propeller fan
Mark( )means check points of Gas Leak
Surface temp. of heat
exchanger interchanging
pipe T (°C)
Standard 2,7 43,0 High 20/ - 7/6 High temperature *13,2–3,6 52,0–57,0 Low 27/ - 21/15Heating Low temperature 2,0 30,0 High 20/ - -10/-10 Standard 0,9 11,0 High 27/19 35/24 High temperature 1,0 14,0 High 32/23 43/26Cooling Low temperature 0,6 2,0 Low 21/15 21/15
Note : Measure the heat exchanger temperature at the center of U-bend. (By means of TC sensor.)
1 : During heating ov erload, the high temperature limit control operation is included.
*
19
RAS-07YKH-ES / RAS-07YAH-ES
Indoor unit
Cooling
0,39m (Connecting pipe) ø9,52
O.D.:9,52mm O.D.:6,35mm
Cooling
Heating
Heating
P
Packed valve
(ø9,52)
Heating
4-way valve
Cooling
Compressor
PA79X1T-4FZ5
Accumulator
Evaporator
Cross flow fan
Dryer
T
0,49m (Connecting pipe) ø6,35
Packed valve
(ø6,35)
Capillary tube
ø1,2x900
Condenser
Refrigerant R-410A 0,73kg
Fan speed
(indoor)
Ambient temp.
conditions DB/WB (°C)
Indoor Outdoor
50Hz
Cooling Heating
Standard
pressure P
(kg/cm²G)
Propeller fan
Outdoor unit
Surface temp. of heat
exchanger interchanging
pipe T (°C)
Mark( )means check points of Gas Leak
Standard 2,5 43,0 High 20/ - 7/6 High temperature *1 3,1-3,6 51,0–58,0 Low 27/ - 21/15Heating Low temperature 2,2 36,0 High 20/ - -10/-10 Standard 0,9 10,0 High 27/19 35/24 High temperature 1,1 16,0 High 32/23 43/26Cooling Low temperature 0,6 2,0 Low 21/15 21/15
Note : Measure the heat exchanger temperature at the center of U-bend. (By means of TC sensor.)
1 : During heating ov erload, the high temperature limit control operation is included.
*
– 20 –
Main Unit Control Panel
C. P. U
Heat Exchanger Sensor
Thermo. Sensor
Current Sensor
(Compressor Current)
Infrared Rays Signal Receiver
Functions
Louver Control
3-minutes Delay at Restart for Compressor
Operation
Display
Timer
Display
ECONO.
Sign Display

6. CONTROL BLOCK DIAGRAM

Infrared
Rays
Remote Control
Operation (START/STOP)
21
Operation Mode Selection
AUTO, COOL, DRY, HEAT, FAN ONLY
Thermo. Setting
Fan Speed Selection
ON TIMER Setting
Initializing Circuit
Clock Frequency Oscillator Circuit
Power Supply
Circuit
Noise Filter
Motor Revolution Control
Processing
(Temperature Processing)
Timer
Compressor
ON/OFF Signal
Outdoor Fan
ON/OFF Signal
Relay Driver, Louver Driver
4-Way Valve
ON/OFF Signal
PRE-DEF.
Sign Display
Indoor
Fan Motor
Louver
ON/OFF Signal
Louver
Motor
OFF TIMER Setting
Louver AUTO Swing
Louver Direction Setting
ECONO.
AC 220/230/240V ~ 50Hz
Relay
RY02
Compressor
RelayRelayRelay
RY01 RY03 RY04
4-Way ValveOutdoor Fan Motor

7. OPERATION DESCRIPTIONS

7-1. FAN ONLY Operation

(MODE of the remote control : FAN ONLY)
(1) During this mode, the rela y RY01 is always
turned off so that only the indoor fan is operated. R Y02 is always turnd on.

7-2. COOL Operation

(MODE of the remote control : COOL)
(1) Compressor, 4-way valve, outdoor fan and
operation display are controlled as shown in Fig. 7-2-1.
1) When the F AN is set to AUTO, the indoor fan motor operates as shown in Fig. 7-1-1.
2) When the F AN is set to LOW, MED, or HIGH, the indoor fan motor operates with a constant
+1
ON
in volume as listed in Table 7-1-1.
OFF
ON ON
OFF
(Room temp. – Set temp.)
Set
0
temp.
Fig. 7-2-1
(RY02)
(RY01)
Compressor
Common relay
(Room temp. – Set temp.)
Set temp.
28 27 26 25 24
HIGH
MED LOW(+)
LOW
LOW
(2) Rela ys RY01 and RY02 are turned on to ener-
gize the outdoor unit, and a cool operation is carried out.
Fig. 7-1-1 Auto setting of air volume
1) When the F AN is set to AUTO, the indoor fan motor operates as shown in Fig. 7-2-2.
Table 7-1-1 Manual setting of FAN SPEED
2) When the F AN is set to LOW, MED, or HIGH, the indoor fan motor operates with a constant
Indication of
FAN SPEED
3
HIGH Air volume (m
/hr)
RAS-10YKH-E RAS13-YKH-E
in volume as listed in Table 7-1-1.
RAS-10YKH-ES RAS13-YKH-ES
LOW MED
HIGH
*For model : RAS-07YKH-E, RAS-07YKH-ES LOW(+)
(2) Once the setting is made, the operation mode is
memorized in the microcomputer so that the same operation can be effected thereafter simply
400 (430)* 510 500 (490)* 560 600 (550)* 650
(Room temp. – Set temp.)
Set temp.
+4 +3 +2 +1
0
RY01
OFF
FAN
AUTO
HIGH MED
LOW LOW
(continuous)
by pushing the START/STOP b utton.
Fig. 7-2-2
ON
OFF
(RY04)
(RY03)
4-way valve
Outdoor fan
OPERATION
Manual
According to the set
position
display
22
(3) Once the setting is made, the operation mode is
memorized in the microcomputer so that the same operation can be effected thereafter simply by pushing the START/STOP button.

7-2-1. Louver Control

0
–1
ON
OFF
ON
OFF
ON
ON ON
(Room temp. – Set temp.)
4-way valve
(RY04)
Outdoor fan
(RY03)
OPERATION
display
Compressor
(RY01)
Common relay
(RY02)
(Room temp. – Set temp.)
0
-1
-2
-3
-4
Set temp.
MED
RY01 OFF
MED(-)
LOW(+)
LOW
FAN
Manual
AUTO
According to the set position
(1) By pushing the SET button of the remote control
during the operation, the louver can be set to the desired position.
And the louver position is stored in the micro­computer , the louv ers will be set to the position automatically at the next operation.
(2) When the AUTO button is pushed, the louv er
vertically swings within range of 25deg.

7-3. DRY Operation

(MODE of the remote control : DRY)
(1) Compressor 4-way valve, outdoor fan and
operation display are controlled as shown in Fig. 7-3-1.
ON:6min.
+3
ON:6min.
OFF:4min.
OFF:4min.

7-4. HEAT Operation

(MODE of the remote control : HEAT)
(1) Relays compressor 4-way valve, outdoor fan and
operation display are controlled as shown in Fig. 7-4-1.
(Room temp. – Set temp.)
Set temp.
+2
+1
0
ON
ON:5min.
OFF:5min.
OFF
(RY01)
Compressor
Common relay
OFF
(RY02)
4-way valve
Fig. 7-3-1
The microprocessor turns the compressor on and off at regular intervals (4 to 6 minutes on and/or off). During the compressor off, the indoor fan will operate in the super lo w position.
The indoor fan will operate in the AUTO position.
(2) The pattern of operation depending on the
relation between room temperature and set temperature is shown below:
Room temp.
ON
ON:5min.
OFF:5min.
OFF
(RY04)
(RY03)
Outdoor fan
(2) Relays RY01 and RY02 are turned on to ener-
display
OPERATION
Fig. 7-4-1
gize the outdoor unit, and a heat operation is carried out. The indoor fan motor operates as shown in Fig. 7-4-2, when the FAN is set to AUTO.
The motor operates with a constant air volume as listed in Table 7-1-1, when the FAN is set to LOW, MED, or HIGH.
Set temp.+1 Set temp.
Compressor Outdoor fan
Indoor fan
ON ON ON ON
OFF OFF OFF
L.*S.L. S.L.L. L. S.L. L.
*
Super Low
Fig. 7-3-2
Fig. 7-4-2
(3) Once the setting is made, the operation mode is
memorized in the microcomputer so that the same operation can be effected thereafter simply by pushing the START/STOP button.
23

7-6. ECONO. Mode

7-7. Current Limit Control

When the ECONO. button is pushed, during COOL and A UT O operation, the OPERATION display is turned off and the ECONO. display is lit and the indoor unit operates quietly and mildly with controlling airflow .

7-6-1. Cooling

(1) In the ECONO. mode, the set temp. by the
remote control is changed automatically as shown in Fig. 7-6-1.
(2) Fan speed LOW
(˚C)
Set temp. is changed
+2
Set temp. is changed
+1
Set temp.
ECONO. button is pushed
1H 2H TIME0H
The microprocessor detects the input current so as to prevent it exceeds a specified value by means of controlling the outdoor fan control as described in (1) and (2).
(1) Current limit control (Cooling)
Control is performed as shown below by detect­ing the compressor operation current with a current sensor (C.T).
RAS-07YKH-E, RAS-10YKH-E, RAS-13YKH-E RAS-07YKH-ES, RAS-10YKH-ES, RAS-13YKH-ES
Input current
13,5A/ 10A I
12,5,A/ 9A I
Compressor
More than I
4
3
More than I3 continues for 5 minutes
4
Outdoor fan
continues for 3 seconds
OFF
OFF
ON
Fig. 7-7-1
Fig. 7-6-1

7-6-2. Heating

(1) In the ECONO. mode, the set temp. by the
remote control is changed automatically as shown in Fig. 7-6-2.
(2) Fan speed LOW
ECONO. button is pushed
1H 2H TIME0H
Set temp.
-1
Set temp. is changed
-2
Set temp. is changed
(˚C)
(2) Current limit control (Heating)
Control is performed as shown in Fig. 7-7-2.
RAS-07YKH-E, RAS-10YKH-E, RAS-13YKH-E RAS-07YKH-ES, RAS-10YKH-ES, RAS-13YKH-ES
Input current
13,5A/ 10A I
12,5A/ 9A I
10A/ 8A I
9A/
7.5A I
4
3
2
1
Compressor Outdoor fan
More than I
More than I3 continues for 5 minutes
4
continues for 3 seconds
OFF
OFF
ON OFF
ON
Fig. 7-7-2
Fig. 7-6-2
– 25
7-8. High-Temperature Limit Control
According to the
set position
Indoor fan speed
35 32 30 20
Heat exchanger temperature
(˚C)
U.L. (Ultra Low)
Room temp.
Set temp.
S.L (Super Low)
Room temp.
Set temp.
OFF
>
<
According to the
set position
Indoor fan speed
30 25 20
Heat exchanger temperature
(˚C)
U.L. (Ultra Low)
Room temp.
Set temp.
S.L (Super Low)
Room temp.
Set temp.
OFF
>
<
(Heating Operation)
7-10. Cool Airflow Prevention Control
(Heating Operation)
The microprocessor detects the indoor heat ex­changer temperature so as to prev ent exceeding the condensate pressure.
Control is performed as shown in Fig. 7-8-1.
Heat exchanger temperature
(˚C)
60
*
1
53
52
*
1 ····· Only outdoor fan is turned off.
Compressor,
Outdoor fan
OFF
ON
Fig. 7-8-1
7-9. Low-Temperature Limit Control
(Cooling Operation)
The microprocessor detects the indoor heat ex­changer temperature so as to prevent freezing up the indoor heat exchanger .
Control is performed as shown in Fig. 7-9-1 and 7-9-
2.
(1) During the heating operation, the indoor f an
speed is controlled automatically in accordance with the indoor heat exchanger temperature to prevent bl owing the cool air .
Control is performed as shown in Fig. 7-10-1 and 7-10-2.
RAS-07YKH-E, RAS-07YKH-ES, RAS-10YKH-E, RAS-10YKH-ES
Fig. 7-10-1
RAS-13YKH-E, RAS-13YKH-ES
RAS-07YKH-E, RAS-07YKH-ES, RAS-10YKH-E, RAS-10YKH-ES
Heat exchanger temperature
(˚C)
7 5
Compressor
Less than 5˚C continues
Fig. 7-9-1
RAS-13YKH-E, RAS-13YKH-ES
Heat exchanger temperature
(˚C)
6 2
Fig. 7-9-2
Compressor
Less than 2˚C continues
for 5 minutes
for 5 minutes
Outdoor fan
ON
OFF
Fig. 7-10-2
(2) As soon as the defrost operation starts, the
indoor fan stops.
Outdoor fan
ON
OFF
26

7-11. Defrost Operation

During the heating operation, the outdoor heat exchanger temperature goes down and sometimes it is frozen.
In this case, the air conditioner stops the heating operation and starts the defrost operation to melt ice.
7-11-1. Condition to Start the Defrost
Operation
The defrost operation starts whichever below condi­tions are specified.
(1) When the cumulativ e compressor operation time
is longer than 40 or 90 minutes and difference between the indoor heat exchanger temper ature and the room temperature is less than the specified value. (This value is decided by the microprocessor .) (Control e xample is sho wn in Fig. 7-11-1. In case of B or C, the defrost opera­tion starts.)
(2) When the current limit control or the high tem-
perature limit control is performed for total of 90 minutes.

7-11-2. Defrost Operation Time Control

<In case of B>
(1) The heating operation is performed for at least 40
minutes.
(2) The maximum defrost oper ation time is 6 min-
utes. The defrost operation time for the 4th cycle is 10 minutes. (When the outdoor temperature is very low , however, the defrost operation time is 10 minutes.)
minutes40minutes40minutes40minutes
Heating
Defrost
Max 6 minutes 10 minutes
Heating
1 cycle
Defrost
Heating
Fig. 7-11-2
40
Defrost
Heating
Defrost
(˚C)
19
10
Indoor heat exchanger temp.
–Room temp.
A
40 90
B
Fig. 7-11-1 (Indoor fan speed : M)
<In case of C>
(1) The heating operation is performed for at least 90
minutes.
D
(2) The defrost oper ation time is 10 minutes .
7-11-3. Ending Condition at Defrost
Operation
more during defrost operation, the defrost opera­tion stops and the heat operation restarts. (The current sensor detects the compressor current.)
minutes or 10 minutes.
on and the indoor and outdoor fans are off.
interlocked with the PRE-DEF. lamp. So the PRE-DEF. lamp is off (the fans stop) for about 3 minutes after the START/STOP button is turned on. When the compressor is turned on, the PRE-DEF. lamp comes on. After the heat exchanger is preheated to about 30°C or higher , the PRE-DEF. lamp goes off, and the indoor fan starts.
C
(min.)
Cumulative compressor operation time
(1) When the compressor current becomes 7,5A or
(2) The defrost operation contin ues f or at most 6
DEFROST LAMP :
During defrost operation, the PRE-DEF. lamp is
The compressor start protection timer is
27

7-12. Auto Restart Function

This unit is equipped with an Automatic restarting facility which allows the unit to restart and resume the set operating conditions in the ev ent of a po wer supply shutdown without the use of the hand control.
The operation will resume without warning three minutes after the power is restored.
The Auto Restart function is set not to work on shipment from the factory, and so it is necessary to set it to function as required.
When the system is stand-by (not running)

7-12-1. How to Set the Auto Restart

To set the Auto Restart function, proceed as follows: Access the TEMPORARY button located in the lower
right hand corner beneath the hinged front panel of the indoor unit (please refer to section on PARTS NAME). The power supply to the unit must be on ­the function will not be set if the power is off.
To enable the Auto Restart function, press the TEMPORAR Y button continuously f or three seconds .
The unit will acknowledge the setting and beep three times. The system will now restart automatically.
The abov e Auto Restart settings can be carried out:
OPERATION
Push the TEMPORARY button continuously more than three seconds.
0
TEMPORARY
When the system is operating
OPERATION
Push the TEMPORARY button continuously more than three seconds.
0
TEMPORARY
MOTION
Stand-by
The system starts to operate. The green light will be lit.
about three seconds after
3S
The unit beeps three times. The orange light will be lit.
The system is operating. The orange light is lighting. If the system is not required to run at this time, push the TEMPORARY
button once more or use the remote control and the unit will stop.
MOTION
Operating The green light is lit.
The system stops to operate. The green light is turned off.
about three seconds after
3S
The unit beeps three times.
The system stops. If the system is not required to stop at this time, use the remote control
and to restart.
During subsequent operation, the orange light goes on.
The Auto Restart function will not accept an instruction if timer operation with the remote control is selected. (Please refer to the section on setting the timer or setting the louver.)
During louver swing (AUTO) operation, after restarting by the Auto Restart function, the louver s wing stops .
28

7-12-2. How to Cancel the Auto Restart

To cancel the Auto Restart function, proceed as follows:
Repeat the setting procedure: the unit will ac knowl­edge the instruction and bleep three times.
When the system is stand-by (not running)
The system will now be required to manually restart with the remote control after the main supply is turned off.
Cancellation is carried out:
OPERATION
Push the TEMPORARY button continuously more than three seconds.
0
TEMPORARY
When the system is operating
OPERATION
Push the TEMPORARY button continuously more than three seconds.
0
TEMPORARY
MOTION
Stand-by
The system starts to operate. The orange light will be lit.
about three seconds after
3S
The unit beeps three times. The green light will be lit.
The system is operating. If the system is not required to run at this time, push the TEMPORARY
button once more or use the remote control and stop the unit.
MOTION
Operating The orange light is lit.
The system stops to operate. The orange light is turned off.
about three seconds after
3S
The unit beeps three times.
The system stops. If the system is not required to stop at this time, use the remote control
and to restart.
During subsequent operation, the green light is lighting.
7-12-3. In Case of Power Failure during the
Timer Operation
(1) If ON-TIMER operation is reserved with setting of
Auto Restart operation, it is cancelled with power failure. (The OPERATION lamp on the main unit goes on and off to inform of power failure .) In that case, try to reserve ON-TIMER operation once again.
– 29
(2) If OFF-TIMER operation is reserved without
setting of Auto Restart operation, the reservation is cancelled with power failure . (The OPERATION lamp on the main unit goes on and off to inform of power f ailure .) In that case, try to reserve OFF-TIMER operation. When Auto Restart operation is set, OFF-TIMER reservation is also cancelled with power failure .

8. INSTALLATION PROCEDURE

8-1. Safety Cautions

For general public use
Po wer supply cord of parts of appliance for Outdoor use shall be more than polychloroprene sheathed fle xible cord (design H05 RN-F), or cord designation 245 IEC 57.
CAUTION
TO DISCONNECT THE APPLIANCE FROM THE MAINS SUPPLY. This appliance must be connected to the mains by means of a circuit break er or a switch with a contact separation
of at least 3 mm. If this is not possible, a power supply plug with earth must be used. This plug must be easily accessible after
installation. The plug must be disconnected from the power supply socket in order to disconnect the appliance completely from the mains.
DANGER
` FOR ELECTRICAL WORKS THE WIRING AND CABLES MUST BE PERFORMED IN COMPLIANCE WITH
NATIONAL WIRING STANDARD OR REGULATION. IF INCORRECT AND INCOMPLETE WIRING IS CARRIED OUT, IT WILL CA USE AN ELECTRICAL FIRE OR ELECTRICAL SHOCK.
` USE THE SPECIFIED CABLE (1,5 to 2,0mm²) AND CONNECT TIGHTLY FOR INDOOR/OUTDOOR
CONNECTION. CONNECT TIGHTLY AND CLAMP THE CABLE SO THA T EXTERNAL FORCE WILL BE ACTED ON THE TERMINAL.
` WIRE ROUTING MUST BE PROPERLY ARRANGED SO THAT CONTROL BOARD CO VER IS FIXED
PROPERLY. ` DO NOT D AMAGE OR SCRATCH THE CONDUCTIVE CORE AND INNER INSULATOR OF THE CABLES. ` DO NOT DEFORM OR SMASH ON THE SURFACE OF THE CABLES. DO NOT PRESS OR FIX THE CORD
AND CABLES FIRMLY WITH STAPLES, etc. ` DO NOT USE THE EXTENSION CABLE FOR POWER SUPPLY CORD OR INTER-CONNECTING CABLE.
NEVER EXECUTE THE CONNECTION OF WIRING WITH OTHER METHOD THAN THE APPROVED ONE.
OTHERWISE, OVERHEAT, SMOKE OR FIRE MAY BE GENERATED BY CONTACT ERROR. ` TURN OFF MAIN POWER SUPPLY AND BREAKER BEFORE ATTEMPTING ANY ELECTRICAL WORK.
MAKE SURE ALL POWER SWITCHES AND BREAKER TURN OFF. FAILURE TO DO SO MAY CAUSE
ELECTRIC SHOCK. ` CONNECT THE CONNECTING CABLE CORRECTLY. IF THE CONNECTING CABLE IS CONNECTED BY
WRONG WAY, ELECTRIC PARTS MAY BE DAMAGED. ` GROUNDING WIRE WORKS MUST BE CONSTRUCTED IN COMPLIANCE WITH INSTALLATION MANUAL. ` DO NOT INSTALL NEAR CONCENTRATIONS OF COMBUSTIBLE GAS VAPORS.
FAILURE TO FOLLOW THIS INSTRUCTION CAN RESULT IN FIRE OR EXPLOSION. ` TO PREVENT OVERHEATING THE INDOOR UNIT AND CAUSING A FIRE HAZARD. PLACE THE UNIT WELL
AWAY (MORE THAN 2M.) FROM HEAT SOURCE SUCH AS RADIATORS, HEAT REGISTORS. FURNACE,
STO VES, etc. ` IF A REFRIGERATION GAS LEAKS DURING INSTALLATION, BE SURE TO PERFORM VENTLATION.
IF THE REFRIGERANT GAS COMES INTO CONTACT WITH FIRE, A POISONOUS GAS MAY OCCUR.
WHEN INSTALLING AN AIR CONDITIONER, DO NOT ALLO W AIR OR MOISTURE TO REMAIN IN THE
REFRIGERATION CYCLE. OTHER WISE, PRESSURE IN THE REFRIGERATION CYCLE MAY BECOME
ABNORMALLY HIGH SO THAT A RUPTURE OR PERSONAL INJURY MAY BE CAUSED. ` BE SURE TO USE THE CORD-CLAMPS AND THE ELECTRIC PAR TS COVER TO THE SPECIFIED
POSITION WITH ATTACHED TO THE PRODUCT. MOUNT THE ELECTRIC PARTS COVER FOR CABLES OF
CONNECTING SECTION FIRMLY WITH THE SCREWS.
ENGAGE DEALER OR SPECIALIST FOR INSTALLA TION.
30
WARNING
Nev er modify this unit b y removing any of the safety guards or by-passing any of the saf ety interloc k
switches.
Do not install in a place which cannot bear the weight of the unit.
P ersonal injury and property damage can result if the unit falls.
Before doing the electrical work, attach an approv ed plug to the pow er supply cord.
And make sure the equipment to be earthed.
Appliance shall be installed in accordance with national wiring requlations.
If you detect any damage, do not install the unit. Contact your T oshiba dealer immediately.
CAUTION
Exposure of unit to water or other moisture before installation will result in an electrical short.
Do not store in a wet basement or expose to r ain or water.
After unpacking the unit, e xamine it carefully f or possib le damage.
Do not install in a place that can increase the vibration of the unit. Do not install in a place that can amplify
the noise lev el of the unit or where noise and discharged air might disturb users neighbors.
To avoid personal injury, be careful when handling parts with sharp edges.
Please read the installation manual carefully before installing the unit. It contains further important
instructions for proper installation.
UK Plugs and Sockets etc (Safety) Regulations 1994
SI Number 1768
With regard to Schedule 3, Item 7 of the above UK Regulations, this appliance m ust be permanently con­nected to the fixed wiring of the main electrical supply by means other than the use of an approved 13 Amp. plug-top as outlined in the Regulations.
Electrical work must be carried by suitably qualified persons and in accordance with all relevant safety standards and codes of practice.
We recommend that the power supply f or this appliance is deriv ed from a suitab ly protected dedicated circuit.
(for U.K. only)
31
8-2. Installation Diagram of Indoor and Outdoor Units
For installation of the indoor unit, use the paper pattern on the back.
For the rear left and left piping
Front cabinet
Front panel
(Attach to the front cabinet)
(Attach to the front cabinet)
5 Deodorizing filter
6 Purifying filter
Clip anchor
120 mm or more
Air filter
2 Wireless remote control
Hook
Pan head wood screw
9
66 mm or more
Hook
8 Remote control holder
Hook
1 Installation plate
120 mm
or more
4 Mounting screw
Shield pipe
Wall
Insert the cushion between the indoor unit and wall, and lift indoor unit to make work easier.
Do not allow the drain hose to get slack.
Cut the piping hole sloped slightly
Make sure to run the drain hose sloped downward.
The auxiliary piping can be connected the left, rear left, rear, right or bottom.
Right
100 mm or more
Before install the wireless remote control
With the remote control cover open, load the batteries supplied correctly, observing their polarity.
Wireless remote control
2
3 Batteries
Cover
RAS-10YA-ES RAS-10YAH-ES
A 400 * 600 B 45* 100
RAS-13YA-ES *Included RAS-07YKH-E, RAS-07YKH-ES RAS-13YAH-ES
A mm or more
Be sure to use the Electric parts cover
Loop the connective cable (about 100 mm in diameter and 300~350 mm long).
B mm or more
600 mm or more
32
Extension drain hose (Option: RB-821SW)
600 mm or more
Rear
Bottom
Rear left
Left
Insulation of refrigerant pipes insulates the pipes separately, not together.
6 mm thick heat resisting polyethylene foam

8-3. Installation

Secure the outdoor unit with the anchor bolts if the unit is likely to be exposed to a strong wind.

8-3-1. Optional Parts

Part
code
Parts name
Q’ty
Use ø8 or ø10 anchor bolts.
If it is necessary to drain the defrost water from the
outdoor unit, attach plate of the outdoor unit before installing it.
Refrigerant piping
A
Liquid side : ø6,35 mm Gas side : ø12,7 mm (ø9,52 mm)
Pipe insulating material
B
(polyethylene foam, 6 mm thickness)
C
Putty, PVC tapes
For model RAS-13YAH-ES
*
Each
one
*
1
Each
one
The drain nipple is located as shown abov e .
<Drainage>
Bottom plate
<Anchor bolt arrangement of outdoor unit> RAS-07YAH-E, RAS-07YAH-ES, RAS-10YAH-E, RAS-10YAH-ES
drain nipple to the bottom
W
ø25
7
Drain nipple
Drain hose sold separately or one on the market.
600mm
Air inlet
120mm
301mm
52,5mm
Air outlet
Fig 8-3-1-1 Air outlet
RAS-13YAH-E, RAS-13YAH-ES
600mm
Air inlet
111mm
7
Drain nipple
Fig. 8-3-2
Install the provided drain nipple in the hole of the bottom plate of the outdoor unit. (See the abo v e figure.)
P erform proper drainage processing using a drain hose sold separately or one on the market. (Inner diameter : 16 mm)
Do not use an ordinary hose on the market, be­cause it tends to get flat and as a result, it prev ents water from draining.
30mm
230mm
7
Drain nipple
Air outlet
Fig. 8-3-1-2 Air outlet
33

8-3-2. Installation Parts

Parts with an asterisk (*) are packaged with the outdoor unit.
Part
No.
1 4 7
Name of parts
Q'ty
Part
No.
Installation plate x 1
2 5 8
Wireless remote control x 1
3 6 9
Batteries x 2
Name of parts
Q'ty
Mounting screw ø4x 25 x 6
Deodorizing filter x 1
Purifying filter x 1
Others
Part
No.
Name of parts
Q'ty
Drain nipple* x 1
Remote control holder x 1
Pan head wood screw ø3,1 x 16 x 2
Name
Installation manual
Owner’s manual
This model is not equipped with an extension drain hose.
Option : F or the extension drain hose, use an optionally availab le RB-821SW or commercially av ailab le one .
– 34

8-4. Indoor Unit

Indoor unit
Pipe hole
65,5mm
120mm
or more
Thread
Weight
1
Installation plate
4
Mounting screw
Pipe hole
65,5mm
66mm or more
Anchor bolt hole
K Installation place
A place which provides the spaces around the indoor unit as shown in the diagram in section 8-2.
A place where there is no obstacle near the air inlet and outlet.
A place which allows an easy installation of the piping to the outdoor unit.
A place which allows the front panel to be opened.
8-4-1. Cutting a Hole and Mounting
Installation Plate
<Cutting a hole>
When installing the refrigerant pipes from the rear.
CAUTION
Direct sunlight to the indoor unit wireless
receiver should be avoided.
The microprocessor in the indoor unit should
not be too close to r-f noise sources. (For details, see the owner’s manual.)
<Remote control>
A place where there are no obstacles such as a curtain that may block the signal from the remote control.
Do not install the remote control in a place exposed to direct sunlight or close to a heating source, such as a stove.
K eep the remote control at least 1 m apart from the nearest TV set or stereo equipment. (This is necessary to prevent image disturbances or noise interference.)
The location of the remote control should be determined as shown below.
The center of the piping slot
The center of the pipe hole is above the arrow.
is above the arrow.
Pipe hole
80mm
65mm
40,5
Fig. 8-4-2
(1) After determining the pipe hole position with the
mounting plate (80 mm ), drill the pipe hole (ø65 mm) at a slight downward slant to the outdoor side.
NOTE :
When drilling the wall that contains a metal lath, wire lath or metal plate, be sure to use a pipe hole brim ring sold separately .
<Mounting the installation plate>
For installation of the indoor unit, use the paper pattern on the back.
mm
(Side view) Indoor unit
7m
75˚
Reception range
(Top view)
Remote
control
Fig. 8-4-1
Indoor unit
Reception range
*:Axial distance
5m
45˚
45˚
Remote control
5m
*7m
Fig. 8-4-3
35
<When the installation plate is directly mounted on the wall>
(1) Securely fit the installation plate onto the wall b y
screwing it in the upper and low er parts to hook up the indoor unit.
(2) Install the installation plate horizontally in the
wall.
(3) To mount the installation plate on a concrete wall
with anchor bolts, utilize the anchor bolt holes as shown in the abov e figure .
CAUTION
When installing the installation plate with mount­ing screw, do not use the anchor bolt hole. Otherwise the unit may fall down and result in personal injury and property damage.
Installation plate (Keep horizontal direction)
Anchor bolt
Projection 15mm or less
5mm dia, hole
Clip anchor
CAUTION
F ailure to firmly install the unit may result in per­sonal injury and property damage if the unit falls.
In case of bloc k, brick, concrete or similar type walls, make holes in the w all.
Insert clip anchors for appropriate T mounting screws.
NOTE :
Install the installation plate using 4 to 6 pieces of mounting screw securing four corners with screws .

8-4-2. Electrical Work

(1) The supply v oltage must be the same as the
rated voltage of the air conditioner .
(2) Prepare the power source f or exclusive use with
the air conditioner.
CAUTION
Use power specified abo v e tab l e.
This appliance can be connected to the mains
in either of the follo wing two w a ys .
(1) Connection to fixed wiring:
A switch or circuit breaker which disconnects all poles and has a contact separation of at least 3 mm must be incorporate in the fixed wiring. An appro ved circuit breaker or switches must be used.
(2) Connection with power supply plug:
Attach power supply plug with power cord and plug it into wall outlet. An approved power supply cord and plug must be used.
Mounting screw Ø4 x 25
4
Fig. 8-4-4
MODEL
Power source 50Hz *220–240V ~ Single-phase Maximum running current 7,5A (4,0A For RAS-07YKH-E, ES only) 12A Plug socket & fuse rating 16A 16A Wiring 1mm2 or more 1,3mm2 or mo re
No adjustment is necessary .
*
RAS-07YKH-E, RAS-10YKH-E
RAS-07YKH-ES, RAS-10YKH-ES
NOTE :
Perform wiring works so as to allow a generous wiring capacity .
RAS-13YKH-E RAS-13YKH-ES
36

8-4-3. Wiring Connection

WARNING
To plug the cable in the plug receptacle, take the following precaution.
THIS APPLIANCE MUST BE EARTHED .
Taking out the power cord
Slitted portion
IMPORTANT
THE WIRES IN THIS MAINS LEAD ARE COLORED IN ACCORD ANCE WITH THE FOLLOWING CODE:
L
: Brown
N
: Blue : Green and Yellow
As the colors of the flexible cord of this appliance may not correspond with the colored markings, to identify terminals in your plug, as follows:
Connect BROWN colored core to plug terminal marked letter “L”.
Connect BLUE colored core to plug terminal marked letter “N”.
Connect GREEN AND YELLOW colored core to plug terminal marked Earth Symbol
<How to remove the front cabinet>
4
-LIVE
-NEUTRAL
-EARTH
Fig. 8-4-5
L N
.
4
Cut off the slitted portion in the side face of the
rear panel to take out the power cord. After this, remove b urrs , sharp edges, etc., to smooth the cut face.
<How to connect the power cord>
For the air conditioner that has no power cord, connect a power cord to it as mentioned below.
After removing the front cabinet, remo v e the terminal cover and the cord clamp.
Connect and secure the power supply cord and secure the cord clamp and the terminal cover .
Cut the rear panel f ollo wing the cutting mark and put the power supply cord through the notch.
Be sure to smooth out the notch with a file, etc.
Terminal block
Power supply cord
L
N
Cord clamp
Terminal cover
Screw
2
1
3
1
2
Vertical air flow louver.
Fig. 8-4-6
How to open the screw cap
Place your finger on the lower part and push up to open the screw cap .
(1) Open the screw caps and remove the two screws
securing the front cabinet.
(2) Close the screw caps as behind. (3) Open the v ertical airflow louver horizontally b y
hand.
(4) Slightly open the low er part of the front cabinet
then pull the upper part of the front cabinet toward y ou to remov e it from the rear plate .
– 37
Screw
Earth line
Fig. 8-4-7
<Stripping length of power cord>
30mm
10mm
L
N
10mm
40mm
NOTE :
Use standard wire only.
Wire type: More than H05-RN-F
Fig. 8-4-8
Screw
Earth line
<How to connect the connecting cable>
Wiring of the connecting cable can be carried out without removing of the front panel.
(1) Remov e the front panel.
Fully open the front panel. Disengage the support arm located in the upper center while pushing its handle leftwards, and then remov e the front panel toward you.
(2) Remov e the terminal cov er and cord clamp . (3) Insert the connecting cable (according to local
codes) into pipe hole on the wall.
(4) Take out the connecting cable through the cable
slot on the rear panel so that it is exploded by about 15 cm long in the front side.
(5) Insert the connecting cable fully into the terminal
block and secure it b y screw tightly.
(6) Tightening torque:1,2 Nm (0,12 kgfm) (7) Secure the connecting cable with the cord clamp. (8) Fix the terminal cover and front panel on the
indoor unit.
<How to install the front cabinet on the indoor unit>
Install the front cabinet through the opposite order of How to remov e the front cabinet.
When the panel is removed and mounted again, tak e the follo wing actions:
After fastening the two screws, one each at the left and right of the air outlet, be sure to push the upper center Q right end R , left end S and the lower center T of the air outlet, and confirm that no gap is left between the front cabinet and the rear plate.
If cooling (dry) operation is made without pushing the air outlet, dew can be deposited on the front cabinet surface. In addition a gap between the front cabinet and the rear plate will become wider, spoiling the appearance.
Push Push
3
1
4
Push
2
CAUTION
Be sure to ref er the wiring system diagram labeled inside the front panel.
Check local electrical codes and also any specific wiring instructions or limitation.
Connecting cable
about 15cm
<Stripping length of connecting cable>
4 3 2 1
NOTE :
Use stranded wire only.
Wire type:More than H05 RN-F
Terminal block
Screw
Screw
Cord clamp
Connecting cable
Screw
Terminal cover
Fig. 8-4-9
50mm
10mm
10mm
40mm
Earth line
For a five conductor cable
Fig. 8-4-10
21
Earth line
Push
Fig. 8-4-11

8-4-4. Piping and Drain Hose Installation

<In case of rightward piping>
After scribing slits of the front panel and the rear panel by a knif e or a marking-off pin, cut them b y a pair of nippers or the like.
Slit (front panel)
Slit (rear panel)
Fig. 8-4-12
<In case of downward piping>
After scribing the slit of the front panel and slit in the lower part of the rear panel by a knife or a marking-off pin, cut them by a pair of nippers or the like.
Slit (front panel)
Slit (rear panel)
Fig. 8-4-13
38
<Left-hand connection with piping>
Bend the connecting pipe so that it is laid within 43 mm above the wall surf ace. If the connecting pipe is laid exceeding 43 mm above the wall surface, the indoor unit may unstab ly be set on the wall. When bending the connecting pipe, make sure to use spring bender so as not to crush the pipe.
Bend the connection pipe within a radius of 30 mm.
To connect pipe after installation of unit (figure)
(To the forefront of flare)
196mm
Side of liquid flow
96mm
Side of gas flow
Outward form of indoor unit
R 30mm (Use polisin or the like for bending pipe.)
43mm
˚
80
Use the handle of screwdriver,etc.

8-4-5. Indoor Unit Installation

(1) Pass the pipe through the hole in the wall, and
hook the indoor unit on the installation plate at the upper hooks.
(2) Swing the indoor unit to right and left to confirm
that it is firmly hooked up on the installation plate.
(3) While pushing the indoor unit onto the w all b y the
lower part, hook it up on the installation plate by the lower part. Pull the indoor unit tow ard you by the lower part to confirm that it is firmly hooked up on the installation plate.
(1)
(2)
Hook
Hook here
Installation
1
plate
Push
Fig. 8-4-14
NOTE :
If the pipe is bent incorrectly, the indoor unit may unstably be set on the wall.
After passing the connecting pipe through the pipe hole, connect the connecting pipe to auxiliary pipes and wrap the facing tape around them.
CAUTION
Bind the auxiliary pipes (two) and connecting cable with f acing tape tightly. In case of leftward piping and rear-leftward piping, bind the auxiliary pipes (two) only with facing tape.
Indoor unit
Auxiliary pipes
Installation plate
Carefully arrange pipes so that any pipe does not stick out of the rear plate of the indoor unit.
Carefully connect the auxiliary pipes and connecting pipes to each other and cut off the insulating tape wound on the connecting pipe to avoid doub le-taping at the joint, moreover, seal the joint with the vinyl tape, etc.
Since dewing results in a machine troub le, make sure to insulate both the connecting pipes. (Use polyethylene foam as insulating material.)
When bending a pipe, carefully do it not to crush it.
Connecting cable
Fig. 8-4-15
For detaching the indoor unit from the installation plate pull the indoor unit toward y ou while pushing its bottom up by the specified parts.
Push Push
Fig. 8-4-16
39

8-4-6. Drainage

(1) Run the drain hose sloping downwards.
NOTE :
Hole should be made at a slight downward slant to the outdoor side.
Do not rise the drain hose.
50 mm or more
Do not put the drain hose end into water.
Fig. 8-4-17
(2) Put water in the drain pan and mak e sure that the
water is drained outdoors.
(3) When connecting e xtension drain hose , insulate
the connecting part of extension drain hose with
shield pipe.
U
5
Shield pipe
Do not form the drain hose into the wared shape.
Do not put the drain hose end in the drainage ditch.

8-5. Outdoor Unit

KInstallation place
A place which provides the spaces around the outdoor unit as shown in the diagram in page 7.
A place which can bear the weight of the outdoor unit and does not allow an increase in noise leve l and vibration.
A place where the operation noise and discharged air do not disturb your neighbors.
A place which is not exposed to a strong wind.
A place free of a leakage of combustible gases.
A place which does not bloc k a passage.
When the outdoor unit is to be installed in an
elevated position, be sure to secure its f eet.
An allowab le length of the connecting pipe is up to :
**RAS-10YKH-E, RAS-10YKH-ES : 10 m
RAS-13YKH-E, RAS-13YKH-ES : 15 m
An allowable head level is up to :
**RAS-10YKH-E, RAS-10YKH-ES : 5 m
RAS-13YKH-E, RAS-13YKH-ES : 6 m
** Included RAS-07YKH-E, RAS-07YKH-ES
• A place where the drain water does not raise any problem.
Drain hose
Inside the room
Extension drain hose
Fig. 8-4-18
CAUTION
Arrange the drain pipe for proper drainage from the unit.
Improper drainage can result in damage to property.
This air conditioner has the structure designed to drain water collected from dew, which forms on the back of the indoor unit, to the drain pan.
Therefore, do not store the power cord and other parts at a height above the drain guide.
Wall
Drain guide
CAUTION
(1) Install the outdoor unit without anything
blocking the air discharging.
(2) When the outdoor unit is installed in a place
exposed alwa ys to a strong wind lik e a coast or on a high story of a building, secure the normal fan operation using a duct or a wind shield.
(3) Specially in windy area, install the unit to
prev ent the admission of wind.
Strong wind
Fig. 8-5-1
Space for pipes
Fig. 8-4-19
40
CAUTION
90˚
Obliquity
Roughness
Warp
Die Pipe
A
Installation in the following places ma y result in trouble. Do not install the unit in such places.
A place full of machine oil.
A saline place such as coast.
A place full of sulfide gas.
A place where high-frequency wav es are lik ely
to be generated as from radio equipment, welders, and medical equipment.

8-5-2. Refrigerant Piping Connection

<Flaring>
(1) Cut the pipe with a pipe cutter.
Fig. 8-5-2
(2) Insert a flare nut into the pipe, and flare the pipe.

8-5-1. Required Tools for Installation Work

1) Philips screw driver
2) Hole core drill (65mm)
3) Gaugramanifold
4) Spanner
5) Pipe cutter
6) Knife
7) Reamer
8) Gas leak detector
9) Tape measure
10) Thermometer
11) Mega-tester
12) Electro circuit tester
13) Vacuum pump
14) Hexagonal wrench (5mm)
15) Torque wrench
Outer
dia.
6,35mm 9,52mm 12,7mm
A (mm) R22
Imperial Rigid
1,0 ~ 1,5 0,5 ~ 1,0 1,0 ~ 1,5 0,5 ~ 1,0 1,5 ~ 2,0 0,5 ~ 1,1
A (mm) R410A
Imperial Rigid
1,5 ~ 2,0 1,0 ~ 1,5 1,5 ~ 2,0 1,0 ~ 1,5
Fig. 8-5-3
<Tightening connection>
Align the centers of the connecting pipes and tighten the flare nut as far as possib le with your fingers. Then tighten the nut with a spanner and torque wrench as shown in the figure.
CAUTION
Do not apply excess torque. Otherwise, the
nut may crac k depending on the installation conditions.
Outer dia.
6,35mm 9,52mm 12,7mm
Half union or packed valve
Externally threaded side
Use a wrench to secure.
Tightening touque
Nm (kgfm)
16 ~ 18 (1,6 ~ 1,8) 30 ~ 42 (3,0 ~ 4,2) 50 ~ 62 (5,0 ~ 6,2)
Flare nut
Internally threaded side
Use a torque wrench to tighten.
Fig. 8-5-4
41

8-5-3. Vacuum Pumping

5mm
Flare nut
Stopper
Wrench
Valve body
Valve stem
Service port cap
Service port
Valve stem cap
INFORMATION
In order to prev ent an y other refrigerant from being charged accidentally, each port of the manifold has been changed in shape.
Differences in Port Size between Conventional R22 and R410A
Manifold for R22 Manifold for R410A
Port size
AIR PURGE
Evacuate the air in the connecting pipes and in the indoor unit using vacuum pump.
Do not use the refrigerant in the outdoor unit. For details, see the man ual of v acuum pump .
<Use of vacuum pump>
(1) Connect the charge hose (A) from the manif ol d
valv e to the charge inlet of the gas side pac k ed valve.
(2) Connect the charge hose (B) to the port of
vacuum pump .
(3) Open fully the low pressure side handle of the
manifold v alve . (4) Operate the vacuum pump. (5) Close the low pressure side handle of manif ol d
valv e after v acuumizing and stop the v acuum
pump.
Continue vacuumizing more than 15 minutes and check the pressure gage indicates –0,1MPa (–76 cmHg).
7/16 UNF 1/2 UNF
20 threads per inch 20 threads per inch
Indoor unit
Pressure gage
Low pressure side handle
Charge hose (A)
Outdoor unit
Gas (Ø9,52)
C
A
Manifold valve
Service port
Lo Hi
High pressure side handle
Charge hose (B)
VP
D
B
Liquid (Ø6,35)
Fig. 8-5-5
CAUTION
KEEP IMPORTANT 4 POINTS FOR INSTALLATION (PIPING W ORK)
(1) Take awa y dust and moisture (Inside of the
connecting pipes.) (2) Tight connection (between pipes and unit) (3) Ev acuate the air in the connecting pipes using
V A CUUM PUMP. (4) Check gas leak (connected points)
<Packed Valve Handling Precautions>
Open the valve stem all the way out; so not try to open it beyond the stopper.
Securely tighten the valve stem cap with the wrench or like.
Valve stem cap tightening torque is as follows;
Gas pipes side (Ø12,7) : 49 ~ 62 Nm (5,0 ~ 6,2 kgfm) Gas pipes side (Ø9,52) : 30 ~ 42 Nm (3,0 ~ 4,2 kgfm) Liquid pipe side (Ø6,35): 16 ~ 18 Nm (1,6 ~ 1,8 kgfm) Service port cap : 9 ~ 10 Nm (0,9 ~ 1,0 kgfm)
Packed valve
(6) Open the stems of pack ed valves A and B all the
way .
(7) Securely tighten the stem cap to each of the
packed valve stems.
<A5 mm hexagon wrench is required.>
Note : Service port at Gas pipes valve only.
Fig. 8-5-6
42

8-5-4. Wiring Connection

(1) Remove the electric parts cover from the outdoor
unit.
(2) Connect the connecting cable to the terminals as
identified with their respective matched numbers on the terminal block of indoor and outdoor units.
(Strip the sheath of connecting cable with follo w­ing stripping length to and insert into the terminal block.)
(3) When connect the connecting cable to outdoor
unit terminal, make a loop as shown in the installation diagram of indoor and outdoor unit, to prev ent water coming in the outdoor unit.
(4) Insulate the unused cords (conductors) with
water coming in the outdoor unit. Process them so that they do not touch any electrical or metal parts.

8-6. Others

8-6-1. Gas Leak Test

Flare nut connections (indoor unit)
Electric parts cover
Flare nut connections (Outdoor unit)
C
D
Valve stem cap connection
A
B
Valve stem cap connection
Service port
<Stripping length of connecting cable>
Terminal block
70mm
10mm
4 3 2 1
Earth line
10mm
60mm
Terminal screw
Connecting cable
1234
Screw
Fig. 8-5-7
CAUTION
Wrong wiring connections may cause some electrical parts to burn out.
Be sure to comply with local code on running the wire from the indoor unit to outdoor unit. (size of wire and wiring method etc.)
Every wire must be connected firmly.
NOTE :
Wipe type : More than H05 RN-F
Cord clamp
Fig. 8-6-1
Check the flare nut connections, valve stem cap connections and service cap connections for gas leak with a leak detector or soap water.

8-6-2. Test Operation

To switch the TEST RUN (COOL) mode, push TEMPORAR Y button for 10 sec. (The beeper will make a short beep.)
TEMPORARY button
TEMPORARY
Fig. 8-6-2

8-6-3. Auto Restart Setting

This product is designed so that, after a power failure, it can restart automatically in the same operating mode as before the power f ailure .
43
INFORMATION
The product was shipped with Auto Restart function in the off position. Turn it on as required.
See detail in section 7-7. Auto Restart Function.
*

9. TROUBLESHOOTING CHART

TROUBLESHOOTING PROCEDURES :
Following details of What to be pre-chec k ed first, make sure of the basic items.
When there is no trouble corresponding to above, check in detail the f aulty parts following “How to judge faulty parts by symptoms later.

9-1. What to be Prechecked First

9-1-1. Power Supply Voltage

The line voltage must be A C 220–240V. If the line voltage is not within this range, this air conditioner ma y not work normally.

9-1-2. Incorrect Cable Connection between Indoor and Outdoor Units

The indoor unit is connected to the outdoor unit with 5 cables. Make certain that the indoor and outdoor units have been connected properly, with terminals assigned the same numbers wired to each other. If the connectors are not connected as specified, the outdoor unit will not operate normally, or OPERA TION lamp and TIMER lamp will blink (5Hz).
9-1-3. Misleading but Good Operations (Program Controlled Operation)
The microcomputer performs the operations listed in Table 9-1-1 to control the air conditioner. If a claim is made on the operation, check whether it corresponds to the contents in the Table 9-1-1. If it does, it is an indispensab l e operation for the control and maintenance of the air conditioner: it is not a f ailure of the unit.
Table 9-1-1
No. Operation of air conditioner Description
When the power plug or the power cord of the indoor unit is inserted,
1
the OPERATION lamp on the setting indication part blinks.
Fan speed remains unchanged in
2
the dry mode. The compressor will not switch on
3
or off even when the thermo. con trol is operated in the dry operation.
The PRE-DEF. lamp comes on
4
when the heating operation is started.
The outdoor fan stops once in the
5
while during the heating operation.
Compressor does not work though
6
room temperature is in the range of turning the compressor on.
During automatic oper ation, the
7
operation mode changes. During automatic operation
8
mode, the fan only operation continues.
When the power is turned on, the
9
operation starts automatically.
The OPERATION lamp blinks, indicating that power is turned on. If this happens, pus h the START/STOP button once to cause the lamp to stop blinking. A power outage also causes the lamp to blink.
Fan speed is automatically controlled in the dry mode.
In the dry mode, the compressor goes on and off at regular interval s, independent of the therm o. control.
The PRE-DEF. lamp comes on during defrost oper ation and when the indoor heat exchanger temperature is low when the heating operation is started. At this time, the indoor fan is stopped to prevent cold air from drifting into the room.
When the indoor heat exchanger temperature is high, the outdoor fan may be stopped by the high-temperature limit control operation.
When the compressor current is large, the out door fan may be stopped by the current limit control opera tion.
Compressor does not work while the compressor restart delay (3-min.) timer is active. The same is true after power is turned on, as the time is still active.
After selection of the cooling and heating operation, the operation mode is selected again when the compres sor off mode continue s f or 15min. according to the room temperat ure.
When the r oom temperature is withi n setting temperature ± 1°C the fan only mode is selected.
When the auto restart controlling is selected, the oper ation is performed a utomaticall y in the pr evious ope ration mode after the power supply has been turned on.
– 44

9-2. Primary Judgement of Trouble Sources

9-2-1. Role of Indoor Unit Controller

The indoor unit controller receives the operation commands from the remote control and assumes the f ollo wing functions.
• Measurement of the draft air temperature of the indoor heat exchanger by using the thermo sensor (TA).
• Louver motor control
• Control of the indoor fan motor operation
• Control of the LED display
• Control of the outdoor unit compressor, 4-WAY VALVE and the outdoor fan motor .

9-2-2. Display of Abnormalities and Judgement of the Abnormal Spots

The indoor unit of this machine observes the operation condition of the air conditioner and displays the contents of the self-diagnosis as block displays on the display panel of the indoor unit.
Table 9-2-1
Block display Description
A OPERATION display blinking (1 Hz) Power failure (when pow er is ON)
B OPERATION display blinking (5 Hz) Thermo. sensor (TA) short/break
C OPERATION display blinking (5 Hz) Heat exchanger sensor (TC) short/break
D OPERATION display blinking (5 Hz) Indoor fan lock, abnormality of indoor fan
E OPERATION display blinking (5 Hz) Indoor P.C. board failure
F OPERATION, and TIMER Display blinking (5 Hz)
G OPERATION, TIM ER and PRE-DEF. display b l inki ng ( 5 Hz)
H OPERATION, TIMER and PRE-DEF. display bli nking ( 5 H z) Compressor trouble
Wrong wiring of connecting cable Thermal fuse is blown
Gas shortage, other refrigerant cycle trouble
Heat exchanger sensor open/bre ak/ short
Overload relay or thermostat for compressor troubl e
(1) Judgement from defective operation or abnormal operation
Table 9-2-2
Symptom Check Primary judgement
The indoor part (including the remote control) is defective.
No reaction on remote control operation
Turn off the power once, turn it on again and try to operate the remote control again.
Rem ote control i s not po ssible.
Remote control is possible. OK.
The outdoor fan does not rotate
The compressor oper ates.
The compressor does not operate. The inside part is defective.
The outdoor part is defect ive. (outdoor fan motor)
– 45
(2) Self-diagnosis with remote control
With the indoor unit control, self-diagnosis of protective circuit action can be done b y turning the remote control operation into service mode, operating the remote control, observing the remote control indicators and checking whether TIMER lamp blinks (5 Hz).
[ METHOD ]
1
Push the [CHK] button with a thin tip of pencil or others. The remote control display shows “ ”.
MODE FANTEMP.
AUTO
COOL
DRY
HEA T
FAN ONLY
Hr.ON OFF TIMER
TEMP.
4
START/STOP
AUTO
LOW
MED.
C
HIGH
2 3
6
SET
AUTO
MODE
ACL CHK
TIMER
ON OFF RSV CNL
WH-E1BE
FAN
ECONO.
1
2
Push “ ” key of TEMP. one by one. The receiving beep “Pi!” is heard, and the timer lamp of the air conditioner blinks. (5 times for 1 sec.)
3
Operating “ ” key, the 35 check codes from “ ” to “ ” are sent.
4
To reduce the check code number, push the “ ” key of TEMP. —> <—> <—> <--
--> <—> <---> <—
5
If the check code agrees with the error code, the receiving beep continues ringing “Pi, Pi, Pi ...” (for approx.10 sec.), and all the LED of air conditioner blink. (5 times for 1 sec.)
[ To release the servicing check ]
<Caution of servicing check>
1. After finished servicing check, push [START/ STOP] button and confirm to change main body
and remote control on normal operation mode.
2. After finished servicing check, disconnect plug (or turned off circuit breaker) of main body due to reset operation memory of microcomputer but in case of found the check code, it's stoked in microcomputer memory . Therefore, the memory of check code can not delete after disconnected plug (or turnrd off circuit breaker).
3. After finished repair the main unit, clear the memory of microcomputer.
To clear the memory, need to use another serv­ice check remote control.
(service part No. 43T69058).
6
Push the [START/STOP] button. Display screen returns to one before check. The servicing check operation can be also released by [ACL] button.
<How to clear the memory>
1. Push the button (rear bottom ) of the remote control with a tip of pencil for more than 3 sec­onds.
Make sure the setting temperatur
is dis-
played on.
2. Adjust the check code to
.
(Use [AUTO] b utton and TEMP. , button
3. Push [SET] button. (Data before operation is directly transferred.)
4. Push [ON/OFF] button. (Transfer the signal to main unit.)
– 46
Table 9-2-3
Block level Diagnosis function
Check
code
Block
Indoor P.C. board
Check
code
Symptom
Thermo. sensor short/break.
Heat exchanger sensor short/break.
Indoor fan lock, abnormality of indoor fan or thermal fuse break.
Abnormality of other indoor unit P.C. board.
Air
Conditioner
status
Continued operation
Continued operation
All off Indicated when
All off Indicated when
Condition
Indicated when detected abnormal
Indicated when detected abnormal
detected abnormal
detected abnormal
Judgment and action
1.Check thermo. sensor.
2.If it is OK, check P.C. board.
1.Check heat exchanger sensor.
2.If it is OK, check P.C. board.
1.Check heat thermal fuse is blow or not? (Terminal block part.)
2.If the thermal fuse is not blow, check indoor fan motor. (Refer to trouble shooting flow charts.)
Replace P.C. board.
Cable connectio n/Therm al fuse Refrigera nt system
Contents detected b y the check codes to ” are stored in memo ry of the micro computer ev en if the power s uppl y is turned off. Therefore, contents of oper ations in the past are all displayed.
1) Wrong wiring or disconnection of connective cable.
2) Thermal fuse cut off.
1) Overload relay or thermostat for compressor break.
Compre s sor break down.
All off Indicated when
All off Indicated when
All off
detected abnormal
detected abnormal
Indicated when detected abnormal
1.Check connective cable correct if wiring is wr ong.
2.Check the rmal fuse and Terminal blocks.
3.If it is OK, chec k P.C. board.
1. If overload r elay and themostat for compressor are OK, check refrigerant cycle.
2.If refrigerant cycle is OK, check P.C. board.
3.If heat exchenger sensor is OK, check ov erload relay and thermostat for compressor.
1.Check compressor.
2. If it is OK, check P.C. board.
– 47

9-3. Troubleshooting Flowcharts

9-3-1. Power can not be Turned on (No Operation at All)

<Preliminary checks>
(1) Is the supply voltage normal? (2) Is the connection to the AC output OK.?
Shut off the power supply from AC outlet once and turn it on after 5 seconds.
NO
Does the OPERATION
lamp blink?
YES
Does the power turn
on by pushing the
[START/STOP] button
of the remote control?
YES
Does the fuse
(F01) blow?
NO
YES
Does the transmission
control flash normally and
(No problem)
Parts (R21, R22, SG01,
C15, C01, DB01, C02,
Q01, T01) are defective.
indicator of remote
transmit certainly?
YES
Operation
Check Items
Main cause
Countermeasure
Symptom
NONO
Remote control
is defective.
Replace the remote control.
Does the thermal
(Under PF. Terminal)
Is the indication voltage
NO
(DC12V or 5V) of main
PC board correct?
Is the voltage
across C02 measured
DC310V~340V?
YES
Is the secondary
voltage of SW trans-
former (T01) measured
DC35V, DC12V,
and DC7V ?
YES
fuse blow?
NO
YES
Refer to the paragraph
NO
Pre-check, or defective circuit before power PC board block.
Shut off the power supply once, and turn
NO
it on again after dis­connecting the motor connector CN10
YES
*
Wrong wiring of
AC cord or connecting
cable is defective.
Does the CN13
connector the wrong
connecting?
Is the secondary
voltage of SW
transformer measured
.
DC35V, DC12V,
and DC7V?
YES
YES
NO
NO
P.C. board
is defective.
SW transformer
(T01) or Tr (Q01)
for power supply
is defective.
Replace the thermal fuse set. Check connection.
Replace the main P.C. board.
Re-wiring the cable.
Replace the main P.C. board.
Motor is defective.
Be sure to disconnect the motor connector CN10 after shut off the power supply, or it will be a cause of dam-
*
age of the motor .
– 48
9-3-2. Power can not be Turned on after Replacing Indoor P.C. Board
<Checking Procedure>
Connect the AC
Power supply
Does the OPERATION
lamp blink?
YES
NO
Is it wired as shown
in Figure below?
YES
RAS-07YKH-E, RAS-07YKH-ES, RAS-10YAH-E, RAS-10YAH-ES
Black
White
1 2 3 4
Indoor terminal block
Blue
N L
Power terminal block
Brown
RY01
P.C. board
NO
RY02
Return the wiring of the power relay is returned to the normal procedure.
To the paragraph of No Power turns on.
Bind Band
Double winding
T02
RAS-13YKH-E, RAS-13YKH-ES
Black
White
1 2 3 4
Indoor terminal block
Blue
N L
Power terminal block
Brown
49
RY01
P.C. board
RY02
T02

9-3-3. Outdoor Unit does not Operate

Shut off the power supply from AC outlet once and turn it on after 5 seconds.
Does the OPERATION lamp blink?
YES
Does the power turn on by
pushing the [START/STOP] button
of the remote control?
YES
Is AC 220–240V
supplied between terminal block
1 - 2 ?
YES
Is cable connection
between indoor and outdoor
units correct?
YES
Check items as following procedure in 9-3-4, 9-3-5, 9-3-6.
NO
NO
NO
NO
See Power can not be turned on.
See Power can not be turned on.
Relays (RY01, RY02) or IC31 or IC30 is failure.
Correct cabling between indoor and outdoor units.
Replace the P.C. board.
50

9-3-4. Only Compressor does not Operate

Shut off the power supply from AC outlet once and turn it on after 5 seconds.
Does the OPERATION lamp blink?
YES
Does the power turn on by
pushing the [START/STOP] button
of the remote control?
YES
Is the voltage across the indoor terminal
( 1 - 2 ) AC 220–240V?
YES
Is cable connection between indoor
and outdoor units correct?
YES
Is the voltage across the outdoor terminal
( 1 - 2 ) AC 220–240V?
YES
Are all the cords for compressor normal?
YES
NO
NO
NO
NO
NO
NO
See Power can not be turned on.
See Power can not be turned on.
Relays (RY01, RY02) or IC31 or IC30 is failure.
Correct cabling between indoor and outdoor units.
Cables between indoor and outdoor units are defective.
Re-wire or replace the defective cords.
Replace the P.C. board.
Is the compressor motor winding normal?
(Check the winding resistor.)
YES
Is the capacitor for compressor normal?
YES
Is the overload relay normal?
YES
Does the compressor start?
YES
Compressor starts but
it stops after a while?
YES
Is the gas quantity normal?
(Check the pressure)
YES
Compressor is defective
NO
NO
NO
NO
NO
Compressor is defective.
Capacitor is defective.
Overload relay is defective.
Compressor is defective.
Gas shortage (Gas leakage)
51

9-3-5. Only Outdoor Fan does not Operate

Shut off the power supply from AC outlet once and turn it on after 5 seconds.
Does the OPERATION lamp blink?
YES
Does the power turn on by
pushing the [START/STOP] button
of the remote control?
YES
Is the voltage across the indoor terminal
( 2 - 4 ) AC 220–240V?
YES
Is cable connection between indoor
and outdoor units correct?
YES
Is the voltage across the terminal
( 2 - 4 ) AC 220–240V?
YES
Are all the cords for outdoor
fan motor normal?
YES
NO
NO
NO
NO
NO
NO
See Power can not be turned on.
See Power can not be turned on.
Relays (RY02, RY03) or IC31 or IC30 is failure.
Correct cabling between indoor and outdoor units.
Cables between indoor and outdoor units are defective.
Correct the wire or replace the defective cords.
Replace the P.C. board.
Is the outdoor fan motor winding normal?
(Check the winding resistance)
YES
Is the capacitor for compressor normal?
YES
Outdoor fan motor is defective.
NO
NO
Outdoor fan motor is defective.
Capacitor for outdoor fan motor is defective.
52

9-3-6. Only 4-Way Valve does not Operate (During Heating Operation)

Shut off the power supply from AC outlet once and turn it on after 5 seconds.
Does the OPERATION lamp blink?
YES
Does the power turn on by
pushing the [START/STOP] button
of the remote control?
YES
Is the voltage across the terminal
( 2 - 3 ) 220-240 V?
YES
Is cable connection between indoor
and outdoor units correct?
YES
Is the voltage across the terminal
( 2 - 3 ) 220-240 V?
YES
Is the wiring of solenoid coil
for 4-way valve normal?
YES
NO
NO
NO
NO
NO
NO
See "Power can not be turned on".
See "Power can not be turned on".
Relays (RY02, RY04) or IC31 or IC30 is failure.
Correct cabling between indoor and outdoor units.
Cables between indoor and outdoor units are defective.
Solenoid coil is defective.
Replace the P.C. board.
4-way valve is defective.
53

9-3-7. Only the Indoor Fan does not Operate

< Check procedure >
Shut off the power supply once.
Turn the power supply.
Does the fan stop in no operating status?
YES
Start the operation with low fan setting in cool operation.
Does the fan rotate?
YES
Change the setting of cooling to high fan.
Does the fan speed
become higher?
NO
NO
NO
Control P.C. board is defective.
Does AC 120V
or higher voltage apply
to between red and black
lead of fan motor?
YES
Shut off the power supply.
Does the cross flow
fan rotate normally?
YES
Turn on the power supply.
Operation
stops
Replace the P.C. board.
Does connecting
terminal, connecting
NO NO
NO
cable or power supply
cord completely?
Does not found the short
wire about connecting
cable and power cord?
YES
Repair the bearing of the fan.
Motor control circuit failure (IC30, IC03) or 12V power circuit failire (D03, Q03).
Thermal fuse operated due to prevent temperature rising cause of incompleted connecting.
YES
Normal
Is the rotation signal
(DC+5V-0V) output between 4
(blue lead wire) and 2 (black
lead wire) of the motor connector
(CN10) when rotating the cross
flow fan by hand in no operating
status? (2 pulses/one turn)
YES
Replace the control P.C. board.
54
Replace the P.C. board.
NO
Replace the fan motor
Replace connecting the cable (or power cord), thermal fuse and terminal block.

9-4. How to Check the Remote Control (Including the Indoor P.C. Board)

There is no beep from the indoor unit.
Push the START/STOP button.
The operation lamp of the air conditioner main unit does not light.
Is there direct sunlight on the receptor of the
air conditioner?
YES
NO
Is there any
thyristor
fluorescent light
near by?
YES
NO
Does the transmission
YES
NO
Is operation
possible when setting
the temporary switch of the
air conditioner main unit to
TEST RUN or
TEMPORARY AUTO?
NO
possible when the
transmitter is moved
nearer to the infrared
signal receiver of the
indicator blink?
Is operation
air conditioner?
YES
Battery life
NO
Short-circuit the metal terminal at the side of the battery compartment (all-clear terminal) with a pencil. (wait about 10 seconds)
Push the START/ STOP button
Does the
transmission
indicator light?
YES
NO
Avoid direct sunlight.
Keep the air
conditioner away
from thyristor
fluorescent light.
YES
Can any signal tone
be heard in a transistor
radio when transmitting
within 5cm distance
from the radio?
YES
P.C. board is failure.
Replace
P.C. board.
After battery replacement,
Note:
shortcircuit the metal terminal at the side of the battery compartment (all-clear terminal) with a pencil.
55
NO
Replace the batteries
NO
Normal
Is there any
beep and
operation?
YES
Remote control
is failure.
Replace remote control.

9-4-1. How to Check the P.C. Board

(1) Operating precautions
1) When removing the front panel or the P.C. board, be sure to shut off the power supply.
2) When removing the P.C. board, hold the edge of the P.C. board and do not apply force to the parts.
3) When connecting or disconnecting the con­nectors on the P.C. board, hold the whole housing. Do not pull at the lead wire .
(2) Inspection procedures
1) When a P.C. board is judged to be defective, check f or disconnection, b urning, or discolora­tion of the copper foil pattern or this P.C. board.
2) The P.C. board consists of the following 2 parts
a. Main P.C. board part:
Power relay , indoor fan motor drive circuit and control circuit, C.P.U. and peripheral circuits, b uzz er drive circuit and buzzer.
b. Infrared rays receive and indication
parts:
Infrared rays receiv e unit and LED.
– 56
(3) Checking procedure
Table 9-4-1
No. Procedure Check Point (Symptom) Causes
1 Shut off the power supply and
remove the P.C. board assembly from the electronic parts base.
Remove the connecting cable from the terminal block.
1. Is the fuse blown? 1. Application of shock voltage.
Overload by short-circuit of the parts.
2 Remove the connector for the motor,
and turn the power on. If the OPERATION lamp blinks (0.5
sec. : ON, 0.5 sec. :OFF) when the power turning on, the checking points described as 1-5 of right column are not necessary to perform.
Make the operation status by pushing
3
once the START/STOP button, except the status of [FAN ONLY], [ON TIMER].
4 Start the operation with the system
which the tim e of th e res t art delay timer is shortened.
Make the operation status by
5
pressin g onc e the S TART/STOP button.
1. The time of th e restart delay timer is shortened.
2. Cool operation
3. Air volume [AUTO]
4. Make the setting temperature lower enou gh th an room temperature.
5. Continuous operation.
Voltage check
1. Between TP1 (AC 220–240V)
2. Between + and – of C02 (DC 310 ~ 340V)
3. Between 12V
4. Between 5 V and GND
Voltage check
1. Voltage of relay coil. (DC 12V) Between pin 10 of IC31 and GNDI Between pin 11 of IC31 and GNDI
2. Between No. 1 and 2 of connecting cable terminal block. (AC 220–240V)
1. All indicators light for 3 sec..
2. Indicators do not in dicate normally after approximate 3 se c..
1. Compressor does not operate.
2. OPERATION lamp blinks.
and TP2
and GND
1. AC power cord is defective.
Poor contact of the terminal plate.
Miss wiring of the power relay.
2. Capacitor (C01, C15) is defective.
Line filter (L 01) is defective.
Resistor (R01) is defective.
Diode (DB01) is defective.
3. Q01, IC02, T01, F03 are defect ive.
4. Q01, IC02, T01, F02, Q29, IC03 are defective.
1. Breaking wire of the relay coil, defective relay driver. (IC31)
2. Poor contact of re lay.
ü
Defective indicator, or poor housing
ý
assembly. (CN13)
þ
1. The temperature of the indoor heat exchanger is abnomally lower.
2. Poor contact of th e he at exc han ger se ns or. (The connector is disconnected.) (CN01)
3. Heat exchang er s ens or, ma in P.C. board are defective. (Refer to Table 9-4-2 for the judgment of defective resistance values.)
4. Main P.C. board is defective.
6 The status of No. 5 is continued, and
make the following condition.
1. Heat operation
2. Make the setting temperature higher eno u gh t h an ro om temperature.
Turn the power on after connecting
7
the motor connector. Start the operation with the following
condition.
1. Operation [Cooling]
2. Airflow [High fan]
3. Continuous operation
1. Compressor does not operate.
2. OPERATION lamp blinks.
1. Motor does not rotate. (The key operat io n is acc ep ted.)
2. The motor rotates, but it vibrates too much.
– 57
1. The temper at ur e of t h e hea t exc hanger is abnor ma lly high.
2. The heat exchanger sensor connector has short-circuit. (CN01)
3. The heat exchanger sensor is defective. (Refer to Table 9-4-2 for the judgment of defective resistance values.)
4. P.C. board is defective.
1. Poor contact of th e mo t or con nec tor.
2. P.C. board is defective.

9-4-2. P.C. Board Layout

Top View
Bottom View
58
Table 9-4-2 Approximate value of the sensor (thermistor) resistance (TA, TC)
(= kΩ)
Temperature
Sensor
0°C10°C20°C25°C30°C
Themo. Sensor 35,8 20,7 12,6 10,0 7,92
9-4-3. How to Reduce the Operation Time of
the Anti-Restart Timer
(1) Set the operation mode, temperature, and air
flow rate to be applied with the timer short mode.
(2) Push the [CNL] button while keeping [CHK]
button pushed. In this case, the check mode is released, and the timer short mode is waited.
(The status is kept e ven if [CHK] and [CNL]
START/STOP
AUTO
MODE
TEMP.
SET
ACL CHK
TIMER
FAN
ECONO.
buttons are released.)
(3) Pushing [START/STOP] b uttons sends oper ation
code + timer short code.
ON OFF RSV CNL
WC-E1BE
(4) The timer short mode is released by only a
transmission. Therefore, repeat steps from (2) to perform the timer short mode again.
[CHK] button
[CNL] button
Fig. 9-4-1
59

10. PART REPLACEMENT

g
y

10-1. Indoor Unit

RAS-07YKH-E, RAS-07YKH-ES, RAS-10YKH-E, RAS-10YKH-ES, RAS-13YKH-E, RAS-13YKH-ES
No. Part name Procedure Remarks
Front panel 1) After stopping the operation of the air conditioner, be
Q
sure to turn off the circuit breaker or disconnect the power plug from the AC wall socket.
2) Open the screw caps and remove the two screws fixi ng the front panel.
3) Close the screw caps as they wer e.
4) Open the horizontal louver right below by your finger.
5) Open the lower side of front panel until it touches the horizontal louver, and remove it from the indoor unit by turning it.
<To assemble the front panel>
1) Fix the two screws to secure the front panel.
2) Close the screw caps as they wer e.
3) Press four places where are the center, right end, left end and lower portions of the air outlet.
4) Check the gap between the front panel and the main unit.
If cooling or drying operation is performed without pressing the center of the air outlet, the surface of the front panel may be covered with frost and have a dew drop.
5
2
3
3
4
3
3
5
2
3
3
Electrical part
R
assembly
Drain-pan
S
assembly
1) Perform the process Q above .
2) Remove the electrical part cover by press ing the nail located on upper portion of the electrical part cover.
3) Remove the drain guide .
4) Remove the screw securing to the end pl ate of the heat exchanger.
5) Remove the connector (3p +3p) for the fan motor and the connector (6p) for the louver motor from the P.C. board assembly.
6) After unhooking the electrical part base by pressing the
nail located on its low er portion, draw the electrical
fixin part base out toward
7) Pull the TC sensor out from the holder of the heat exchanger. (Keep it with the holder of TC sensor.)
8) Dress the connecting cable securely as shown in t he right illustration. (Improper dressing will cause wa t er leakage.)
1) Perf orm the process R above .
2) Remove the drain-pan b y press ing th e f our hooks downwards. (Keep it with the drain hose. )
ou to remove it from the mai n un it.
Drain guide
Upper nail
Screw
Lower fixing nail
When assembling dress the connecting
cable in loop and put it into the drain-pan.
Electrical
part cover
TC-sensor
Hooks
60
No. Part name Procedure Remarks
Horizontal grille
T
Note:
The horizontal grille can not be removed without removing the louver motor.
Heat exchanger 1) Perform the process S.
U
Cross flow fan 1) Perform the process S.
V
1) Perform the process
2) Remove the screw fixing the louver m ot or, and remove the louver motor.
3) Re move the shaft of the horizontal grille fr om th e drain-pan.
2) Remove the pipe holder from the rear side of main unit by removing the screw.
3) Unhook the hooks fixing the left side of the heat exchanger and remove the screw fixing it, then remove the right side of the end plate from the rib fixing the main unit by sliding the heat exchanger slightly to the right side.
2) Loosen the set screw of the cross flow fan.
3) Remove the screw f ixing the shaft bearing base.
4) Lift slightly up the left side of the heat exchanger, and pull the shaft bearing base out left downwards.
R
.
Louver motor
Horizontal grille
Hooks fixing the
heat exchanger
Shaft bearing
base
Screw fixing the
heat exchanger
Hook Screw
Screw
Hooks
Pipe holder
When assembling it, fix it with the set screw on the position where the gap between the rear plate surface and the left end surface of the cross flow fan is 6 ~ 7mm.
Shaft bearing 1) Perform the process V above .
W
2) Remove the shaft bearing from the sha ft bearing base.
<Caution for assembl i ng>
If a part of the shaft bearing is protruded from the housing, assemble it after pushing its portion into the correct position in the housing.
Fan motor 1) Perform the process U above .
X
2) Perform the process
3) Remove the left and right motor bands.
4) Remove the fan motor after pulling the cr oss flow fan out sliding it left and right.
-2) above.
V
Shaft bearing
6~7m
Ribs
Cross flow fan
Rear plate
Mount the fan motor as shown in figure below when assembling.
Put the end of lead wire at the portion between two ribs.
61

10-2. Microcomputer

y
RAS-07YKH-E, RAS-07YKH-ES, RAS-10YKH-E, RAS-10YKH-ES, RAS-13YKH-E, RAS-13YKH-ES
No. Part name Procedure Remarks
Common
Q
procedure
Thermal fuse
R
replacement
1) Turn the power supply off to stop the operation of air­conditioner, and disconnect the power cor d from the A C supply.
2) Remove the front pan el.
•Remove the two fixing scr ews. (Ø4 x 14 l)
3) Remove the electrical part base.
1) Perform the process Q above .
2)Remov e terminal cover (Up) (Down).
3) Disconnect the terminal bloc ks connected with the connecting cab le, and the pow er cord fr om base-E-parts by removing the screws.
4) Remove the thermal fuse (77°C) from base Electric­parts.
Replace the thermal fuse, terminal block, power cord, microcom put er a ss and the power supply P.C. board assy.
62

10-3. Outdoor Unit

CompressorCompressor
RAS-07YKH-E, RAS-07YKH-ES, RAS-10YAH-E, RAS-10YAH-ES
No. Part name Procedure Remarks
Common
Q
procedure
Capacitor for
R
compressor
1) Stop the operation of air-conditioner , and disconnect the power cord from the AC supply.
2) Remove Electric parts cover . (1- ST1 T Ø4 x 10 l)
3) Remove the cord clamp (2- ST2T Ø4 x 12 l ) and remove the connecting cable.
4) Remove the front cabinet. (7- ST1T Ø4 x 10 l with nylon wash er)
Pull the front lower portion toward you, and remov e it pulling out upward.
1) Remove the fixing screw the capacitor band. (1- ST2T Ø4 x 8 l)
2) Remove the cable connected to the terminal.
Remove 7-ST1T
4 ´10
2-ST2T
4 ´12
1-ST1T
4 ´10
Refer to [ Specifications of Electrical Parts] in page 11.
Capacitor for
S
fan motor
Overload
T
relay
1) Remove the fixing screw of the capacitor band . (1- ST2T Ø4 x 8 l)
2) Remove the cable connected to the terminal.
1) Per form the process Q above .
2) Remove terminal cov e r of compressor.
3) Remove overload relay holder and pul l overload relay up.
4) Remove Fustons of leads.
Same as above.
63
RAS-13YAH-E, RAS-13YAH-ES
y
No. Part name Procedure Remarks
Common
Q
procedure
Capacitor for
R
compressor
1) Stop the operation of air-conditioner, and disconnect the power cord from the AC supply.
2) Remove E-parts cover. (2- ST1T Ø4 x 10 l)
3) Remove the cord cl am p (2- ST2 T Ø4 x 12 l) and remove the connecting cable.
4) Remove the front cab ine t. (7- ST1T Ø4 x 10 l with nylon wash er)
Pull the front lower portion toward
ou, and remove
it pulling out upward.
1) P er form the process Q above .
1) Remove the fixing screw of the capacitor band. (1- ST2T Ø4 x 8 l)
2) Remove the cab le connected to the terminal.
2-ST2T
Ø4
´
12
Remove 7-ST1T
4 ´10
2-ST1T
Ø4
´
10
Capacitor for
S
fan motor
Overload
T
relay
Thermostat
U
bimetal
1) P er form the process Q above .
1) Remove the fixing screw. (1- ST2T Ø4 x 8 l)
2) Remove the cab le connected to the terminal.
1) P er form the process Q above .
2) Remove Fast ons of leads.
3) Remove the fixing screw. (1- ST2T Ø4 x 10 l)
4) Pull OL-Holder up and remove O verlord relay from OL-Holder.
1) P er form the process Q above .
2) Remove terminal co v e r of compr ess or.
3) Remove thermo holder and pull thermostat bimetal up.
4) Remove Fast ons of leads.
1-ST2T
f4 ´
10
OL-Holder
1-ST2T
f4 ´
8
1-ST2T
f4 ´
8
Compressor
Thermo holder
Thermostat bimetal
64

11. EXPLODED VIEWS AND PARTS LIST

11-1. Indoor Unit (1)

402
405
404
403
412
401
406
413
402
Location
No. No.
401 43T60001 Base, T erminal
402 43T60002 Base, T erminal
403 43T69004 Sensor , Heat Exchanger
404 43T69005 Sensor, Thermostat
405 43T60061 Fuse Set, Thermal 77°C
Par t
Description
2P, AC 300V, 20A
3P, AC 300V, 20A
10k, 25°C
10k, 25°C
– 65
Location
No. No.
406 43T69051 P.C. Board Assembly,
406 43T69052 P.C. Board Assembly,
406 43T69031 P.C. Board Assembly,
407 43T61001 Base, E-Parts
Part
Description
MCC-772 (13YKH-E, 13YKH-ES)
MCC-772 (10YKH-E, 10YKH-ES)
WRS-LED , MCC-766
ABS, Black, UL94-5V

11-2. Outdoor Unit

RAS-10YAH-E
19
24
16
23
25
4
17, 26
6
5
12, 15
8, 9
3
14
2
13
10, 11
20 21
22
18
7 : CAPILLARY TUBE 27 : DRYER
1
Location
No. No.
1 43T19001 Guard, Fan 2 43T20001 Fan, Propeller 3 43005037 Cabinet, Front 4 43T43001 Condenser (10YAH-E) 5 43062194 Cover, E-Parts 6 43T00320 Cabinet, Back 7 43T47014 Tube, Capillary 8 43T46017 Valve, Packed 9,52 9 43T47021 Bonnet 10 43T46016 Valve, Packed 6,35 11 43T47020 Bonnet 12 43T46003 4-Way-Valve, VH7100D 13 43T21001 Motor, Fan, UE6-21SJ5P 14 43T47001 Nut, Flange
Par t
Description
67
Location
No. No.
15 43T49030 Solenoid coil 16 43T19005 Handle 17 43T49001 Rubber, Cushion 18 43T79001 Nipple, Drain 19 43T19002 Stopper, Guard 20 43T63001 Holder , OL-Relay 21 43054403 Relay, Over Load 22 43T41400 Compressor , PH120T1-4C 23 43055483 Capacitor, 25µF 400V 24 43T55001 Capacitor, 1,5µF 500V 25 43060049 Base,Terminal , 5P 26 43T97001 Nut, Flat-washer 27 43T45003 Dryer
Part
Description
RAS-10YAH-ES
20
23
17
22
24
4
18
6
5
13, 16, 25, 26
9, 11
3
15
2
14
10, 12
21
19
7 : CAPILLARY TUBE 8 : CAPILLARY TUBE
1
Location
No. No.
1 43T19001 Guard, Fan 2 43T20001 Fan, Propeller 3 43005037 Cabinet, Front 4 43T43011 Condenser 5 43062194 Cover, E-Parts 6 43T00320 Cabinet, Back 7 43T47024 Tube, Capillary, 0,8DIA 8 43T47007 Tube, Capillary, 1,2DIA 9 43T46011 Valve, Packed 9,52 10 43T46010 Valve, Packed 6,35 11 43T47021 Bonnet 12 43T47020 Bonnet 13 43T46012 4-Way-Valve, VHV-0104
Par t
Description
68
Location
No. No.
14 43T21001 Motor, Fan, UE6-21SJ5P 15 43T47001 Nut, Flange 16 43T46013 Coil, 4-Way, VHV-01AI501A 17 43T19005 Handle 18 43T49001 Rubber, Cushion 19 43T79001 Nipple, Drain 20 43T19002 Stopper, Guard 21 43T41406 Compressor, PA118X1T-4FZ 22 43055483 Capacitor, 25µF 400V 23 43T55001 Capacitor, 1,5µF 500V 24 43060049 Base,T erminal , 5P 25 43T46005 Valve, Checked 26 43T45004 Dryer
Part
Description
RAS-13YAH-E
29
30
8
35
5
14
28
13
33
34
2
7
1
10
6
4
Location
No. No.
1 43005144 Cabinet, Front 2 43005143 Cabinet-Side 3 43042446 Base 4 43T19007 Guard, Fan 5 43T19005 Handle 6 43T19002 Stopper, Guard 7 43T62007 Cover, E-Parts 8 43020302 Fan, Propeller 9 43021984 Motor, Fan, AF-230-28P 10 43T47001 Nut, Flange 11 43T46005 Valve, Check 12 43T63004 Holder, Wire, Lead 13 43T96001 Bushing 14 43043609 Condenser 15 43T46016 Valve, Packed 6,35 16 43T47020 Bonnet 17 43T46019 Valve, Packed 12,7 18 43T47018 Bonnet 19 43T47029 ASM, Packed Valve Cap
Par t
Description
12,7, 6,35
9
12
25
20
11
21, 36
17,18
3
23
31, 32
19
24
15,16
27
Location
No. No.
20 43T47007 Tube, Capillary, 1,2DIA 21 43T47014 Tube, Capillary, 1,7DIA 22 43041764 Compressor, PH1702T2-4L2 23 43T97001 Nut, Flat-Washer 24 43T49008 Cushion, Rubber 25 43045085 Dryer 26 43054398 Relay, Over Load 27 43T79004 Nipple, Drain 28 43043610 Condenser, Sub 29 43055496 Capacitor, 35µF 400V 30 43T55009 Capacitor, 1,5µF 500V 31 43T50002 Thermostat, Bimetal 32 43T63005 Holder , Thermostat, Bimetal 33 43146482 4Way-Valve 34 43T49030 Solenoid, Coil 35 43060049 Base,Terminal, 5P 36 43T47017 Tube, Capillary, 0,6DIA
Part Description
26
22
69
RAS-13YAH-ES
26
27
8
13
5
29
30
2
14
28
7
1
10
6
4
Location
No. No.
1 43005144 Cabinet, Front 2 43005143 Cabinet-Side 3 43042446 Base 4 43T19007 Guard, Fan 5 43T19005 Handle 6 43T19002 Stopper, Guard 7 43T62007 Cover, E-Parts 8 43020302 Fan, Propeller 9 43021984 Motor, Fan, AF-230-28P 10 43T47001 Nut, Flange 11 43T46005 Valve, Check 12 43T63004 Holder, Wire, Lead 13 43T96001 Bushing 14 43T43012 Condenser 15 43T46016 Valve, Packed 6,35
Par t
Description
20
11
19
17
18
9
12
22
3
15
23
16
25
Location
No. No.
16 43T47021 Bonnet 17 43T46011 Valve, Packed 9,52 18 43T47020 Bonnet 19 43T47007 Tube, Capillary, 1,2DIA 20 43T47008 Tube, Capillary, 1,5DIA 21 43041700 Compressor, P A160x2T-4FZ 22 43T97001 Nut, Flat-Washer 23 43T49008 Cushion, Rubber 24 43T45004 Dryer 25 43T79004 Nipple, Drain 26 43055496 Capacitor, 35µF 400V 27 43T55009 Capacitor, 1,5µF 500V 28 43060049 Base,Terminal, 5P 29 43T46012 4Way-Valve, VHV-0104 30 43T46013 Coil, 4Way, VHV-01AI501A
Part Description
24
21
70
RAS-07YAH-E
19
23
24
16
25
17
6
4
5
12, 15
8, 9
3
14
2
13
10, 11
20 21
22
18
7 : CAPILLARY TUBE
1
Location
No. No.
1 43T19001 Guard, Fan 2 43T20001 Fan, Propeller 3 43005037 Cabinet, Front 4 43T43001 Condenser 5 43T62007 Cover, E-Parts 6 43T00032 Cabinet, Back 7 43T47307 Tube, Capillary 8 43T46303 Valve, Packed 9.52 9 43T47021 Bonnet , 3/8 IN 10 43T46306 Valve, Packed 6.35 11 43T47020 Bonnet , 1/4 IN 12 43T46003 4-Way-Valve, VH7100D 13 43021928 Motor, Fan, HF­ 14 43T47001 Nut, Flange
Part
Description
Location
No. No.
15 43T49030 Solenoid coil 16 43T19005 Handle 17 43T49001 Rubber, Cushion 18 43T79001 Nipple, Drain 19 43T19002 Stopper, Guard 20 43T63001 OL-Relay 21 43T54302 Relay, Over Load 22 43T41 304 Compressor, PH80T1-4C 23 43055483 Capacitor, 25MF 400V 24 43T55009 Capacitor, PLASTIC-FILM 25 43060049 Terminal Block , 5P
Part
Description
– 71 –
RAS-07YAH-ES
19
21
22
16
23
17
6
4
5
12,15
8, 9
3
14
2
13
10,11
20
18
7 : CAPILLARY TUBE
1
Location
No. No.
1 43T19001 Guard, Fan 2 43T20001 Fan, Propeller 3 43005037 Cabinet, Front 4 43T43011 Condenser 5 43T62007 Cover, E-Parts 6 43T00032 Cabinet, Back 7 43T47306 Tube, Capillary 8 43T46302 Vale,Packed 9.52 9 43T47021 BONNET,3/8IN 10 43T46305 Valve, Packed 6,35 11 43T47020 Bonnet,1/4IN 12 43T46012 Valve,4Way,VHV-0104 13 43021928 Fan-Motor
Part
Description
Location
No. No.
14 43T47001 Nut,Flange 15 43T46013 Coil,4Way,VHV-01AI501A1 16 43T19005 Handle 17 43T49001 Rubber,Cushion 18 43T79001 Drain -Nipple 19 43T19002 Guard - Stopper 20 43T41309 Compressor,PA79X1T-4FZ 21 43055470 Capacitor,15MFD,400V 22 43T55009 Capacitor,Plastic-Film 23 43060049 Terminal Block,5P
Part
Description
– 72 –
TOSHIBA CARRIER (THAILAND) CO., LTD.
144/9 MOO 5, BANGKADI INDUSTRIAL PARK, TIVANON ROAD,
TAMBOL BANGKADI, AMPHUR MUANG, PATHUMTHANI 12000, THAILAND.
Loading...