Toshiba RAS-07UAH-E4, RAS-07UKP-E4, RAS-07UKHP-E4, RAS-10UKP-E4, RAS-10UKHP-E4 SERVICE MANUAL

...
SERVICE MANUAL
AIR CONDITIONER
SPLIT WALL TYPE
RAS-13UKHP-E4 / RAS-13UAH-E4 RAS-10UKHP-E4 / RAS-10UAH-E4
RAS-07UKHP-E4 / RAS-07UAH-E4
FILE NO. SVM-05001-1
RAS-13UKP-E4 / RAS-13UA-E4 RAS-10UKP-E4 / RAS-10UA-E4 RAS-07UKP-E4 / RAS-07UA-E4
RAS-13UKPX4 / RAS-13UAX4
RAS-10UKPX4 / RAS-10UAX4 RAS-07UKPX4 / RAS-07UAX4 RAS-12UKPX4 / RAS-12UAX4
Revised Aug, 2005
FILE NO. SVM-05001
CONTENTS
1. SPECIFICATIONS
2. CONSTRUCTION VIEWS
2-1 Indoor Unit
2-2 Outdoor Unit (RAS-13UAH-E4, RAS-10UAH-E4, RAS-13UA-E4, RAS-10UA-E4,
RAS-13UAX4, RAS-10UAX4, RAS-12UAX4)
2-3 Outdoor Unit (RAS-07UAH-E4, RAS-07UA-E4, RAS-07UAX4)
3. WIRING DIAGRAM
3-1 RAS-13UKHP-E4 / RAS-13UAH-E4 3-2 RAS-10UKHP-E4 / RAS-10UAH-E4 3-3 RAS-07UKHP-E4 / RAS-07UAH-E4 3-4 RAS-13UKP-E4 / RAS-13UA-E4
RAS-10UKP-E4 / RAS-10UA-E4
3-5
RAS-07UKP-E4 / RAS-07UA-E4 RAS-13UKPX4 / RAS-13UAX4
3-6
RAS-12UKPX4 / RAS-12UAX4
3-7 RAS-10UKPX4 / RAS-10UAX4
RAS-07UKPX4 / RAS-07UAX4
4. SPECIFICATION OF ELECTRICAL PARTS
4-1 Indoor Unit (RAS-13UKHP-E4, RAS-10UKHP-E4, RAS-07UKHP-E4) 4-2 Outdoor Unit (RAS-13UAH-E4) 4-3 Outdoor Unit (RAS-10UAH-E4) 4-4 Outdoor Unit (RAS-07UAH-E4) 4-5 Indoor Unit (RAS-13UKP-E4, RAS-10UKP-E4, RAS-07UKP-E4, RAS-13UKPX4)
RAS-10UKPX4, RAS-12UKPX4, RAS-07UKPX4) 4-6 Outdoor Unit (RAS-13UA-E4) 4-7 Outdoor Unit (RAS-13UAX4, RAS-12UAX4) 4-8 Outdoor Unit (RAS-10UA-E4, RAS-10UAX4)
4-9 Outdoor Unit (RAS-07UAX4)
4-10 Outdoor Unit (RAS-07UA-E4)
5. REFRIGERATION CYCLE DIAGRAM
5-1 RAS-13UKHP-E4 / RAS-13UAH-E4 5-2 RAS-10UKHP-E4 / RAS-10UAH-E4 5-3 RAS-07UKHP-E4 / RAS-07UAH-E4 5-4 RAS-13UKP-E4 / RAS-13UA-E4, RAS-13UKPX4 / RAS-13UAX4,
RAS-12UKPX4 / RAS-12UAX4
5-5 RAS-10UKP-E4 / RAS-10UA-E4, RAS-10UKPX4 / RAS-10UAX4 5-6 RAS-07UKP-E4 / RAS-07UA-E4, RAS-07UKPX4 / RAS-07UAX4
6. CONTROL BLOCK DIAGRAM
6-1 RAS-13UKHP-E4 / RAS-13UAH-E4, RAS-10UKHP-E4 / RAS-10UAH-E4,
RAS-07UKHP-E4 / RAS-07UAH-E4
6-2 RAS-13UKP-E4 / RAS-13UA-E4, RAS-10UKP-E4 / RAS-10UA-E4,
RAS-07UKP-E4 / RAS-07UA-E4, RAS-13UKPX4 / RAS-13UAX4, RAS-07UKPX4 / RAS-07UAX4, RAS-12UKPX4 / RAS-12UAX4
7. OPERATION DESCRIPTION
7-1 Outline of Air Conditioner Control 7-2 Description of Operation Circuit 7-3 Hi POWER Mode 7-4 High-Temperature Limit Control 7-5 Low-Temperature Limit Control 7-6 Defrost Operation 7-7 Current Limit Control 7-8 Auto Restart Function 7-9 Filter Check Lamp 7-10 Self-Cleaning function
7-11 QUIET Mode 7-12 COMFORT SLEEP mode
8. INSTALLATION PROCEDURE
8-1 Safety Cautions 8-2 Installation Diagram of Indoor and Outdoor Units 8-3 Installation 8-4 Indoor Unit 8-5 Outdoor Unit 8-6 How to Set Remote Control Selector Switch
FILE NO. SVM-05001
8-7 Others
9. TROUBLESHOOTING CHART
9-1 Troubleshooting Procedure 9-2 Basic Check Items 9-3 Primary Judgement 9-4 Self-Diagnosis by Remote Control (Check Code) 9-5 Troubleshooting Flowcharts
9-6 Troubleshooting for Remote Control
10. PART REPLACEMENT
10-1 Indoor Unit 10-2 Outdoor Unit
11. EXPLODED VIEWS AND PARTS LIST
11-1 Indoor Unit (E-Parts Assy for Heat pump model) 11-2 Indoor Unit (E-Parts Assy for Cooling model) 11-3 Indoor Unit (RAS-07,10,13UKHP-E4, UKP-E4)
11-4 Indoor Unit (RAS-07,10,12,13UKPX4) 11-5 Outdoor Unit (RAS-13UAH-E4)
11-6 Outdoor Unit (RAS-10UAH-E4) 11-7 Outdoor Unit (RAS-13UA-E4) 11-8 Outdoor Unit (RAS-10UA-E4) 11-9 Outdoor Unit (RAS-13UAX4, RAS-12UAX4) 11-10 Outdoor Unit (RAS-10UAX4)
11-11 Outdoor Unit (RAS-07UAX4, RAS-07UA-E4) 11-12 Outdoor Unit (RAS-07UAH-E4)
- 2 -
FILE NO. SVM-05001
1. SPECIFICATIONS
MODEL RAS-13UKHP-E4 / RAS-13UAH-E 4 RAS-13UKP-E4 / RAS-13UA-E4
ITEM Cooling Heating Cooling
Capacity
Power source V 220 - 240
Power consumption kW 1.23 1.27 1.26 1.33 1.24 1.28 Power factor % 99 97 98 96 98 95
Running Indoor A 0.15
current Outdoor A 5.50 5.30 5.35 5.15 5.75 5.60
Starting current A 25 24
Moisture removal lit/h 2.0
Noise
Refrigerant
Refrigerant control Capillary tube
Interconnection
pipe
INDOOR UNIT RAS-13UKHP-E4 RAS-13UKP-E4
Dimensions Width mm 790
Net weight kg 10
Evaporator type Finned tube
Indoor fan type Cross flow fan
Air volume Medium fan m3/h 520 550 520
Fan motor output W 20
Air filter Honeycomb woven filter with PP frame
OUTDOOR UNIT RAS-13UAH-E4 RAS-13UA-E4
Dimensions Width mm 780
Net weight kg 37 34
Condenser type Finned tube
Outdoor fan type Propeller fan
Airflow volume m3/h 2120
Fan motor output W
Compressor
Safety device Fuse, Overload relay
Louver type Automatic louver Usable outdoor temperature range °C 15 ~ 43 -10 ~ 24 15 ~ 43
Indoor (H/M/L) dB 41/35/31 Outdoor (220 - 240 V) dB 49 51 49 51 47 48
Name of refrigerant R22
Rated amount kg 1.00 0.80
Gas side size mm Æ12.7
Connection type Flare connection Liquid side size mm Æ6.35
Connection type Flare connection
Maximum length (One way)
Maximum height difference
Height mm 275
Depth mm 208
High fan m3/h 630 650 630
Low fan m3/h 430 490 430
Height mm 550
Depth mm 270
Model
Output W 1100
kW 3.55 3.60 4.10 4.15 3.70 3.75
Phase 1Æ
Hz 50
m
m
220 V 240 V 220 V 240 V 220 V 240 V
1
15*
6
2200
2120 2200 2030 2150
42
PH225X2C-4FT
30
3
FILE NO. SVM-05001
MODEL RAS-10UKHP-E4 / RAS-10UAH-E4 RAS-10UKP-E4 / RAS-10UA-E4
ITEM Cooling Heating Cooling
Capacity
Power source V 220 - 240
Power consumption kW 0.93 0.98 0.84 0.86 0.80 0.85
Power factor % 95 92 94 91 97 95
Running Indoor A 0.15
current Outdoor A 4.30 4.27 3.90 3.77 3.60 3.58
Starting current A 19 16
Moisture removal lit/h 1.2
Noise
Refrigerant
Refrigerant control Capillary tube
Interconnection
pipe
INDOOR UNIT RAS-10UKHP-E4 RAS-10UKP-E4
Dimensions Width mm 790
Net weight kg 10
Evaporator type Finned tube
Indoor fan type Cross flow fan
Air volume Medium fan m3/h 460 520 460
Fan motor output W 20
Air filter Honeycomb woven filter with PP frame
OUTDOOR UNIT RAS-10UAH-E4 RAS-10UA-E4
Dimensions Width mm 780
Net weight kg 32 31
Condenser type Finned tube
Outdoor fan type Propeller fan
Airflow volume m3/h 1740 1850 1740 1850 1740 1850
Fan motor output W 20
Compressor
Safety device Fuse, Overload relay
Louver type Automatic louver Usable outdoor temperature range °C 15 ~ 43 -10 ~ 24 15 ~ 43
Indoor (H/M/L) dB 39/33/26 Outdoor (220 - 240 V) dB 47 49 47 49 44 45
Name of refrigerant R22
Rated amount kg 0.76 0.68
Gas side size mm Æ9.52
Connection type Flare connection Liquid side size mm Æ6.35
Connection type Flare connection
Maximum length (One way)
Maximum height difference
Height mm 275
Depth mm 208
High fan m3/h 570 610 610
Low fan m3/h 340 400 340
Height mm 550
Depth mm 270
Model PH180X1C-4DZDN3 RM5510GNE94
Output W 750
kW 2.65 2.70 2.95 3.00 2.65 2.70
Phase 1Æ
Hz 50
m 10*
m
220 V 240 V 220 V 240 V 220 V 240 V
1
5
- 4 -
FILE NO. SVM-05001
MODEL
RAS-07UKHP-E4/ RAS-07UKP-E4/ RAS-07UKPX4/
RAS-07UAH-E4 RAS-07UA-E4 RAS-07UAX4
ITEM Cooling Heating Cooling Cooling
Capacity
Phase 1
Power source V 220 240
Power consumption kW 0.61 0.68 0.54 0.59 0.58 0.62 0.58 0.62 Power factor % 98 97 98 96 98 96 98 96
Running Indoor A 0.15 current Outdoor A 2.69 2.77 2.35 2.40 2.55 2.55 2.55 2.55
Starting current A 13 11
Moisture removal lit/h 0.8
Noise Indoor (H/M/L) dB 38/32/26
Outdoor (220-240V) dB
Refrigerant
Refrigerant control Capillary tube
Interconnection
pipe
Name of refrigerant R-22 Rated amount kg 0.60 0.57
Gas side size mm 9.52
Connection type Flare connection
Liquid side size mm 6.35
Connection type Flare connection
Maximum length (One way)
Maximum height difference
220V 240V 220V 240V 220V 240V 220V 240V
kW 2.00 2.05 2.00 2.05 2.10 2.15 2.10 2.15
Hz 50
44
m 10*
m 5
45 45
46
44 45
1
44
45
INDOOR UNIT RAS-07UKHP-E4 RAS-07UKP-E4 RAS-07UKPX4
Height mm 275
Dimensions Width mm 790
Depth mm 208
Net weight kg 10
Evaporator type Finned tube
Indoor fan type Cross flow fan
High fan m3/h 570 610 570
Air volume Medium fan m3/h 460 490 460
Low fan m3/h 340 400 340
Fan motor output W 20
Air filter Honeycomb woven filter with PP frame
OUTDOOR UNIT RAS-07UAH-E4 RAS-07UA-E4 RAS-07UAX4
Height mm 530
Dimensions Width mm 660
Depth mm 240
Net weight kg 28 27
Condenser type Finned tube
Outdoor fan type Propeller fan
Airflow volume m3/h 1280 1360 1280 1360 1280 1360 1280 1360
Fan motor output W 20
Compressor
Safety device Fuse, Overload relay
Louver type Automatic louver Usable outdoor temperature range °C 15 ~ 43 −10 ~ 24 15 ~ 43
Model PH108X1C-4DZDN2
Output W 605
21 ~ 43
5
FILE NO. SVM-05001
ITEM Cooling
MODEL
Capacity
RAS-13UKPX4 / RAS-13UAX4 RAS-12UKPX4 / RAS-12UAX4 RAS-10UKPX4 / RAS-10UAX4
220 V 240 V 220 V 240 V
kW 3.70 3.75 2.65 2.70
220 V
240 V
3.483.40
Phase 1Æ
Power source V 220 - 240
Hz 50 Power consumption kW 1.24 1.28 0.80 0.85 Pow er factor % 98 95 97 95
1.24 98 95
1.28
Running Indoor A 0.15 current Outdoor A 5.60 5.45 3.60 3.58
5.60 5.45
Starting current A 24 16 Moisture removal lit/h 2.0 1.2
Noise
Refrigerant
Indoor (H/M/L) dB 41/35/31 39/33/26 Outdoor dB 47 48 44 45
47 48
Name of refrigerant R22 Rated amount kg 0.80 0.68
Refrigerant control Capillar y tube
Gas side size mm Æ12.70 Æ9.52 Connection type Flare connection
Liquid side size mm ∅6.35 Interconnection pipe
Connection type Flare connection
Maximum length
(One way)
Maximum height
difference
m 15*
m
1
6 5
10*
1
INDOOR UNIT RAS-13UKPX4 RAS-12UKPX4 RAS-10UKPX4
Height mm 275 Dimensions Width mm 790
Depth mm 208 Net weight kg 10 Evaporator type Finned tube Indoor fan type Cross flow fan
High fan m3/h 630 610 Air volume Medium fan m3/h 520 460
Low fan m3/h 430 340 Fan motor output W 20 Air filter Honeycomb woven filter with PP frame OUTDOOR UNIT RAS-13UAX4 RAS-12UAX4 RAS-10UAX4
Height mm 550 Dimensions Width mm 780
Depth mm 270 Net weight kg 34 31 Condenser type Finned tube Outdoor fan type Propeller fan Airflow volume m3/h 2030 2150 1740 1850
2030
2150
Fan motor output W 30 20 Compressor
Model PH225X2C-4FT RM5510GNE94
Output W 1100 750 Safety device Fuse, Overload relay Louver type Automatic louver Usable outdoor temperature range °C 21 ~ 43
Note : 1
·
Capacity is based on the following temperature conditions.
FILE NO. SVM-05001
Temperature
Indoor unit inlet air temperature
Outdoor unit inlet air temperature
Note : 2
*1 No need to charge extra refrigerant.
Condition
Cooling Heating
(DB) 27°C20°C
(WB) 19°C15°C
(DB) 35°C7°C
(WB) 24°C6°C
JIS B8615-1
- 7 -
2-1. Indoor Unit
FILE NO. SVM-05001
2. CONSTRUCTION VIEWS
Front panel
Back body
0
66
48
Knock out system
Air inlet
Air filter
790
Heat exchanger
275
Air outlet
120 80
590
Hanger
64
53
48
208
48
Knock out system
0
66
Drain hose (0.54 m)
Hanger
45
Minimum distance to ceiling
275
170 or mor
e
320
Connecting pipe (0.33 m)
(For 13 series ; Flare 12.7 For 07,10 series ; Flare
620
235
215
Minimum distance to ceiling
Hanger
more 5 or
6
235
215
Hanger
160
Installation plate outline
Center line
8
Connecting pipe (0.43 m)
6.35)
(Flare
For stud bolt
8~10)
(
For stud bolt (
26
Minimum distance to ceiling
170 or more
Hanger
150150 160
32
9090
9.52)
6)
4519040
57
Wireless remote control
160
18
FILE NO. SVM-05001
2-2. Outdoor Unit (RAS-13UAH-E4, RAS-10UAH-E4, RAS-13UA-E4, RAS-10UA-E4,
RAS-13UAX4, RAS-10UAX4, RAS-12UAX4)
A
A
Detail Drawing (Back Leg)
6 Hole
302
310
32.5
600
52 36
270
R15
R5.5
310
302
30 Drain outlet
436
530
265
FAN GUARD
115
125
11 x 14 Hole
2-
8-∅
(For
10 anchor bolt)
90
600 780
62
102
6 Hole
11 x 14 Hole
B
B Detail Drawing (Front Leg)
310
302
36
52
R15
310 330
COVER PV
Z
Electrical part cover
Installation dimension
B or more
325
100 or more
Z
Air outlet
View
600
Air inlet
A or more
600 or more
120
54
75
11 Long holes (For 8-∅10 anchor bolt)
4 x
12,
13 Series
600 mm 400 mm
A
B 100 mm 45 mm
Liquid side (Flare 6.35)
Gas side (Flare 9.52) 10 Series
Gas side (Flare 12.7) 12, 13 Series
Service port
10 Series
9
2-3. Outdoor Unit (RAS-07UAH-E4, RAS-07UA-E4, RAS-07UAX4)
A
97
A
Detail Drawing (Back Leg)
660
50
36
6 Hole
265
273.5
R 15
R 5.5
530
273.5
420
59.5
Fan guard
25Drain outlet
2-
11x14 hole
8-∅
(for
B
10 anchor bolt)
B
11x14 Hole
FILE NO. SVM-05001
Detail Drawing (Front Leg)
265
273.5
6 Hole
36 50
R 15
660
Cover PV
Z
242
Installation dimension
100 or more
325
100 or more
Air outlet
500
660
View
Z
600
Air inlet
600 or more
97.5
600 or more
4x
(11)
56
11x14 Long holes (for 8-∅10 anchor bolt)
126
48
297
54
Service port
(12.5)273.5 (pitch)
Liquid side (Flare
Gas side (Flare
6.35)
9.62)
10
3. WIRING DIAGRAM
3-1. RAS-13UKHP-E4 / RAS-13UAH-E4
FILE NO. SVM-05001
BRW
L
BLU
N
GRN & YEL
SINGLE PHASE
220-240V 50Hz
BLK P04
T02 C.T.
131
CN27
73°C
THERMAL FUSE
Louver Motor
CN25
PNK
SG01
DSA
VARISTOR
BLK
R22
3
4
PNK
112
RY01
2
CN04
T6.3A 250VAC
FUSE F01
MAIN P.C. BOARD
YEL
54321
54321
C01
R21
VARISTOR
YEL
CN07
YEL
YEL
WHI
DC5V
L01
WP-003
RY04RY03
CR01
150°C
1 1
3
CN03
112
BLK
2
BLK
THERMO
SENSOR (TA)
CN01
112
HEAT EXCHANGER
2
BLK
BLK
CR02
SENSOR (TC)
2 2 3 3 4 4 5 5 6 6
INFRARED RAYS RECEIVE
AND INDICATION PARTS
345
1
2
345
1
2
BLU
BLU
BLU
345
2
345
2
Voltage
Regulator
IC03
BLU
R319
R26
BLU
1
1
C02
CR03
C15
5
CN10
BLK
5
GRY YEL
BRW
RED
WHI
789
6
789
6
BLU
BLU
789
6
789
6
Micro
Power
Module
R25
R27
3 1 3 1
10
11
10
11
BLU
BLU
BLU
10
11
10
11
CN14
DC12V
+
DB01 C63
CN11
1 2 3 1 2 3
WHI
INDOOR TERMINAL BLOCK
OUTDOOR TERMINAL BLOCK
COMPRESSOR
BLK
BLK
WHI
2
1 4
(L)2(N)
1
BLK
SOLENOID COIL
RED
RED
RED
PNK
WHI
CAPACITOR
BLU
RED
3
3
BLU
CAPACITOR
FAN MOTOR
BLU
4
WHI
AC FAN MOTOR
GRN&YEL
INDOOR
OUTDOOR
CHASSIS
BLK
11
3-2. RAS-10UKHP-E4 / RAS-10UAH-E4
FILE NO. SVM-05001
BRW
L
BLU
N
GRN & YEL
SINGLE PHASE
220-240V 50Hz
BLK P04
T02 C.T.
131
CN27
73°C
THERMAL FUSE
Louver Motor
CN25
PNK
SG01
DSA
VARISTOR
BLK
R22
3
4
PNK
112
RY01
2
CN04
T6.3A 250VAC
FUSE F01
MAIN P.C. BOARD
YEL
54321
54321
C01
R21
VARISTOR
YEL
CN07
YEL
YEL
WHI
DC5V
L01
WP-003
RY04RY03
CR01
150°C
1 1
3
CN03
112
BLK
2
BLK
THERMO
SENSOR (TA)
CN01
112
HEAT EXCHANGER
2
BLK
BLK
CR02
SENSOR (TC)
2 2 3 3 4 4 5 5 6 6
INFRARED RAYS RECEIVE
AND INDICATION PARTS
345
1
2
345
1
2
BLU
BLU
BLU
345
2
345
2
Voltage
Regulator
IC03
BLU
R319
R26
BLU
1
1
C02
CR03
C15
5
CN10
BLK
5
GRY YEL
BRW
RED
WHI
789
6
789
6
BLU
BLU
789
6
789
6
Micro
Power
Module
R25
R27
3 1 3 1
10
11
10
11
BLU
BLU
BLU
10
11
10
11
CN14
DC12V
+
DB01 C63
CN11
1 2 3 1 2 3
WHI
INDOOR TERMINAL BLOCK
OUTDOOR TERMINAL BLOCK
OVERLOAD RELAY
COMPRESSOR
BLK
BLK
WHI
2
1 4
(L)2(N)
1
BLK
SOLENOID COIL
RED
RED
RED
PNK
WHI
CAPACITOR
BLU
RED
3
3
BLU
CAPACITOR
FAN MOTOR
BLU
GRN&YEL
4
WHI BLK
AC FAN MOTOR
INDOOR
OUTDOOR
CHASSIS
12
3-3. RAS-07UKHP-E4 / RAS-07UAH-E4
FILE NO. SVM-05001
BRW
L
BLU
N
GRN & YEL
SINGLE PHASE
220-240V 50Hz
BLK P04
T02 C.T.
131
CN27
73°C
THERMAL FUSE
Louver Motor
CN25
PNK
SG01
DSA
VARISTOR
BLK
R22
3
4
PNK
112
RY01
2
CN04
T6.3A 250VAC
FUSE F01
MAIN P.C. BOARD
YEL
54321
54321
C01
R21
VARISTOR
YEL
CN07
YEL
YEL
WHI
DC5V
L01
WP-003
RY04RY03
CR01
150°C
1 1
3
CN03
112
BLK
2
BLK
THERMO
SENSOR (TA)
CN01
112
HEAT EXCHANGER
2
BLK
BLK
CR02
SENSOR (TC)
2 2 3 3 4 4 5 5 6 6
INFRARED RAYS RECEIVE
AND INDICATION PARTS
345
1
2
345
1
2
BLU
BLU
BLU
345
2
345
2
Voltage
Regulator
IC03
BLU
R319
R26
BLU
1
1
C02
CR03
C15
5
CN10
BLK
5
GRY YEL
BRW
RED
WHI
789
6
789
6
BLU
BLU
789
6
789
6
Micro
Power
Module
R25
R27
3 1 3 1
10
11
10
11
BLU
BLU
BLU
10
11
10
11
CN14
DC12V
+
DB01 C63
CN11
1 2 3 1 2 3
WHI
INDOOR TERMINAL BLOCK
OUTDOOR TERMINAL BLOCK
OVERLOAD RELAY
COMPRESSOR
BLK
BLK
PNK
WHI
BLK
1
(L)2(N)
1
RED
WHI
2
BLU
SOLENOID COIL
RED
RED
CAPACITOR
RED
3
3
BLU
CAPACITOR
FAN MOTOR
BLU
4
4
WHI
AC FAN MOTOR
GRN&YEL
INDOOR
OUTDOOR
CHASSIS
BLK
13
3-4. RAS-13UKP-E4 / RAS-13UA-E4
Infrared rays receiver and indication parts.
Heat Exchanger Sensor (TC)
Thermo Sensor (TA)
L
N
Single Phase
220V~, 50Hz
GRN&YEL
BRW (L)
BLU (N)
CN01
121
CN03
121
CN25
CN14
2
2
1 1
BLU
1 1
2
BLU
2
43 432
BLU
BLU
432 43
F01
T6.3 A
250 VAC
8
6
7
5 5
BLU
5
R21 R22
C15
6
BLU
6 6587
3
9 11
8
7
9
BLU
BLU
BLU
8
7
9 9
RY01
L01
2
2
3
10 10
10 10
FILE NO. SVM-05001
RED
TRANS (T T-10)
WHI
113
CN05 CN06
3
DB50
C50
+
IC03
BLU
R46
113
Regulator
circuit
R47
R48
GRY
3
MCC-920
DC 12 V
DC 5 V
CN07 1 2 3 4 5
WHI
1
YEL YEL YEL YEL
1
2
2
3
3
4
4
5
5
1 2 3 4 5
Louver motor
CN11
YEL
1
1
GRY
2
2
D38
CR03
C58
3
CN10
5
3
1
BRW
3
WHI
5
BLK
3
RED
1
1 2 3 4 5 6 6
150 C 1 2 3 4 5
Indoor FAN motor
11
BLU
WHI
11
BLK
11
P04
4
SG01
DSA
1
C01
4
CN31
INDOOR
TERMINAL
BLK
1
BLOCK
OUTDOOR TERMINAL
BLOCK
BLK BLK RED
1(L) 2(N)
FAN MOTOR
WHI
2
RED
WHI
COMPRESSOR
GRN&YEL
CHASSIS
CAPACITOR
RED
PNK
WHI
INDOOR
OUTDOOR
CAPACITOR
CN04
PNK
112
2
PNK
TEMP FUSE
73 C
14
3-5. RAS-10UKP-E4 / RAS-10UA-E4
RAS-07UKP-E4 / RAS-07UA-E4
Infrared rays receiver and indication parts.
Heat Exchanger Sensor (TC)
Thermo Sensor (TA)
L
N
Single Phase
220V~, 50Hz
GRN&YEL
BRW (L)
BLU (N)
CN01
121
CN03
121
CN25
CN14
2
2
1 1
BLU
1 1
2
BLU
2
43 432
BLU
BLU
432 43
F01
T6.3 A
250 VAC
8
6
7
5 5
BLU
5
R21 R22
C15
6
BLU
6 6587
3
9 11
8
7
9
BLU
BLU
BLU
8
7
9 9
RY01
L01
2
2
3
10 10
10 10
FILE NO. SVM-05001
RED
TRANS (T T-10)
WHI
113
CN05 CN06
3
DB50
C50
+
IC03
BLU
R46
113
Regulator
circuit
R47
R48
GRY
3
MCC-920
DC 12 V
DC 5 V
CN07 1 2 3 4 5
WHI
1
YEL YEL YEL YEL
1
2
2
3
3
4
4
5
5
1 2 3 4 5
Louver motor
CN11
YEL
1
1
GRY
2
2
D38
CR03
C58
3
CN10
5
3
1
BRW
3
WHI
5
BLK
3
RED
1
1 2 3 4 5 6 6
150 C 1 2 3 4 5
Indoor FAN motor
11
BLU
WHI
11
BLK
11
P04
4
SG01
DSA
1
C01
4
INDOOR
TERMINAL
BLOCK
OUTDOOR TERMINAL BLOCK
BLK
BLK
OVERLOAD RELAY
CN31
BLK
1
1
FAN MOTOR
BLK
(L)
WHI
2
(N)
2
RED
RED
WHI
COMPRESSOR
GRN&YEL
CHASSIS
RED
CAPACITOR
PNK WHI
INDOOR
OUTDOOR
CAPACITOR
CN04
PNK
112
2
PNK
TEMP FUSE
73 C
15
3-6. RAS-13UKPX4 / RAS-13UAX4
RAS-12UKPX4 / RAS-12UAX4
Infrared rays receiver and indication parts.
Heat Exchanger Sensor (TC)
Thermo Sensor (TA)
GRN&YEL
Single Phase
BLU (N) BRW (L)
Power Cord
220-240V 50Hz
CN01
121
CN03
121
CN25
CN14
2
2
1 1
BLU
1 1
2
BLU
2
43 432
BLU
BLU
432 43
F01
T6.3 A
250 VAC
8
6
7
5 5
BLU
5
R21 R22
C15
6
BLU
6 6587
3
9 11
8
7
9
BLU
BLU
BLU
8
7
9 9
RY01
L01
2
2
3
FILE NO. SVM-05001
10 10
11
BLU
WHI
10
11
10
BLK
11
P04
4
SG01
DSA
1
C01
4
RED
TRANS (T T-10)
WHI
113
CN05 CN06
3
DB50
C50
+
IC03
BLU
R46
113
Regulator
circuit
R47
R48
GRY
3
MCC-920
DC 12 V
DC 5 V
CN07 1 2 3 4 5
WHI
1
YEL YEL YEL YEL
1
2
2
3
3
4
4
5
5
1 2 3 4 5
Louver motor
CN11
YEL
1
1
GRY
2
2
D38
CR03
C58
3
CN10
5
3
1
BRW
3
WHI
5
BLK
3
RED
1
1 2 3 4 5 6 6
150 C 1 2 3 4 5
Indoor FAN motor
CN31
INDOOR
TERMINAL
BLK
1
BLOCK
OUTDOOR TERMINAL
BLOCK
BLK BLK RED
1(L) 2(N)
FAN MOTOR
WHI
2
RED
WHI
COMPRESSOR
GRN&YEL
CHASSIS
CAPACITOR
RED
PNK
WHI
INDOOR
OUTDOOR
CAPACITOR
CN04
PNK
112
2
PNK
TEMP FUSE
73 C
16
3.7 RAS-10UKPX4 / RAS-10UAX4 RAS-07UKPX4 / RAS-07UAX4
Infrared rays receiver and indication parts.
Heat Exchanger Sensor (TC)
Thermo Sensor (TA)
GRN&YEL
Single Phase
BLU (N) BRW (L)
Power Cord
220-240V 50Hz
CN01
121
CN03
121
CN25
CN14
2
2
1 1
BLU
1 1
2
BLU
2
43 432
BLU
BLU
432 43
F01
T6.3 A
250 VAC
8
6
7
5 5
BLU
5
R21 R22
C15
6
BLU
6 6587
3
9 11
8
7
9
BLU
BLU
BLU
8
7
9 9
RY01
L01
2
2
3
FILE NO. SVM-05001
10 10
11
BLU
WHI
10
11
10
BLK
11
P04
4
SG01
DSA
1
C01
4
RED
TRANS (T T-10)
WHI
113
CN05 CN06
3
DB50
C50
+
IC03
R46
BLU
113
Regulator
circuit
R47
R48
GRY
3
MCC-920
DC 12 V
DC 5 V
CN07 1 2 3 4 5
WHI
1
YEL YEL YEL YEL
1
2
2
3
3
4
4
5
5
1 2 3 4 5
Louver motor
CN11
YEL
1
1
GRY
2
2
D38
CR03
C58
3
CN10
5
3
1
BRW
3
WHI
5
BLK
3
RED
1
1 2 3 4 5 6 6
150 C 1 2 3 4 5
Indoor FAN motor
INDOOR
TERMINAL
BLOCK
OUTDOOR TERMINAL BLOCK
BLK
BLK
OVERLOAD RELAY
CN31
BLK
1
(L)
1
FAN MOTOR
BLK
WHI
2
(N)
2
RED
RED
WHI
COMPRESSOR
GRN&YEL
CHASSIS
RED
CAPACITOR
PNK WHI
INDOOR
OUTDOOR
CAPACITOR
CN04
PNK
112
2
PNK
TEMP FUSE
73 C
17
FILE NO. SVM-05001
4. SPECIFICATION OF ELECTRICAL PARTS
4-1. Indoor Unit (RAS-13UKHP-E4, RAS-10UKHP-E4, RAS-07UKHP-E4)
No. Parts name Type Specifications
1 Fan motor (for indoor) SKF-220-20-4A-1 AC Motor with 150 C thermo fuse 2 Thermo sensor (TA-sensor) 10k at 25 C 3 Micro Power Module (M01) 4 Microcontroller unit (IC30) TMP87CM40AN 5 Heat exchanger sensor
(TC-sensor) 6 Line filter (L01) LC*SS11V-06270 27mH, 600mA 7 Bridge rectifier (DB01) D3SBA60 4A, 600 V 8 Capacitor (C63) KMH400VSSN47M22S 47mF, 400 V 9 Fuse (F01) BET 6.3A T6.3A, 250VAC
10 Varistor (R21, R22) 15G561K 560 V 11 Resistor (R319) RF-2TK5R6 5.6 , 2 W 12 Louver motor MP24Z 12VDC 13 Relay (Comp., RY01) DI1U Rating 25A/AC250 V, 3-48VDC 14 Relay (Fan, RY03) G5NB-1A Rating 3A/AC250 V, 12VDC 15 Relay (Solenoide, RY04) G5NB-1A Rating 3A/AC250 V, 12VDC
µRM1260V
W
DC 390V, Secondary DC 12V
W
10k at 25 C
W
°
°
°
4-2. Outdoor Unit (RAS-13UAH-E4)
No. Parts name Type Specifications
Output (Rated) 1100 W, 2 poles, 1 phase, 220 - 240 V, 50Hz
1 Compressor PH225X2C-4FT Winding resistance ( ) C-R C-S
°
(at 20 C) 2.35 3.22 Output (Rated) 42 W, 6 poles, 1 phase, 220 - 240 V, 50Hz
2 Fan motor (for outdoor) HF-240-42A Winding resistance ( ) Red-Black White-Black
°
(at 20 C) 176.2 290.5
Running capacitor
3
(for fan motor)
Running capacitor
4
(for compressor)
DS451155BPQC AC 450 V, 1.5mF
DS371356CPNB AC 370 V, 35mF
W
W
- 18 -
FILE NO. SVM-05001
4-3. Outdoor Unit (RAS-10UAH-E4)
No. Parts name Type Specifications
Output (Rated) 750 W, 2 poles, 1 phase, 220 - 240 V, 50Hz
1 Compressor PH180X1C-4DZDN3 Winding resistance ( )
°
(at 20 C) 3.33 3.78 Output (Rated) 20 W, 6 poles, 1 phase, 220 - 240 V, 50Hz
Winding resistance ( ) Red-Black White-Black
°
(at 20 C
2 Fan motor (for outdoor)
Running capacitor
3
(for fan motor)
Running capacitor 4
(for compressor)
HF-240-20B or
SKF-240-20B
DS451155BPQC AC 450 V, 1.5mF
DS371306CPNB AC 370 V, 30mF
W
W
387.3 or 235.2 466.2 or 260.1
C-R C-S
5 Overload relay JMRA99269-9200 U/T : 6.8A (90
°
C), OPEN : 135±5 C, CLOSE : 69±11 C
° °
4-4. Outdoor Unit (RAS-07UAH-E4)
No. Parts name Type Specifications
Output (Rated) 605W, 2poles, 1 phase, 220 240V, 50Hz
1 Compressor PH108X1C-4DZDN2 Winding resistance () C-R C-S
(at 20°C) 4.84 4.40
2 Fan motor (for outdoor)
Running capacitor 3
(for fan motor)
Running capacitor 4
(for compressor)
5 Overload relay JMRA99208-9201 U/T: 4.2A (80°C), OPEN: 135±5°C, CLOSE: 69±11°C
HF-240-20B or SKF-240-20B
DS451155BPQC AC 450V, 1.5µ F
DS371256CPNB AC 370V, 25µ F
Output (Rated) 20W, 6poles, 1 phase, 220 240V, 50Hz
Winding resistance () Red-Black White-Black
(at 20°C)
387.3 or 235.2
466.2 or 260.1
- 19 -
FILE NO. SVM-05001
4-5. Indoor Unit (RAS-13UKP-E4, RAS-10UKP-E4, RAS-07UKP-E4, RAS-13UKPX4,
RAS-10UKPX4, RAS-12UKPX4, RAS-07UKPX4)
No. Parts name Type Specifications
1 Fan motor (for indoor) SKF- 220-20-4A-1 AC Motor with 150 C thermo fuse 2 Thermo sensor (TA-sensor) 10k at 25 C 3 Transformer 4 Microcontroller unit (IC30) TMP87CM40AN 5 Heat exchanger sensor
(TC-sensor) 6 Line filter (L01) *SS11V-06270 27mH, 600mA 7 Bridge rectifier (DB50) KBP06M/51 1.5A, 600 V 8 Capacitor (C50) PF1E222MNN1625 2200mF, 25 V 9 Fuse (F01) BET6.3A T6.3A, 250VAC
10 Varistor (R21, R22) 15G561K 560 V
11 Louver motor MP24Z 12VDC 12 Relay (Comp., RY01) DI1U Rating 25A/AC250 V, 3~48VDC
TT-10
W
10k at 25 C
W
°
°
°
4-6. Outdoor Unit (RAS-13UA-E4)
No. Parts name Type Specifications
Output (Rated) 1100 W, 2 poles, 1 phase, 220 - 240 V, 50Hz
1 Compressor
2 Fan motor (for outdoor) HF-240-30B Winding resistance (W) Red-Black White-Black
Running capacitor
3
Running capacitor
4
(for compressor)
PH225X2C-4FT
DS451155BPQC AC 450 V, 1.5µF
DS371356CPNB AC 370 V, 35 F
Winding resistance (W) C-R C-S
°
(at 20 C) 2.35 3.22 Output (Rated) 30 W, 6 poles, 1 phase, 220 - 240 V, 50Hz
°
(at 20 C) 245 388
m
- 20 -
FILE NO. SVM-05001
4-7. Outdoor Unit (RAS-13UAX4, RAS-12UAX4)
No. Parts name Type Specifications
Output (Rated) 1100 W, 2 poles, 1 phase, 220 - 240 V, 50Hz
1 Compressor Winding resistance (W) C-R C-S
2 Fan motor (for outdoor) HF-240-30B Winding resistance (W) Red-Black White-Black
Running capacitor
3
(for fan motor) Running capacitor
4
(for compressor)
PH225X2C-4FT
(at 20°C) 2.35 3.22 Output (Rated) 30 W, 6 poles, 1 phase, 220 - 240 V, 50Hz
(at 20°C) 245 388
DS451155BPQC AC 450 V, 1.5 F
DS371356CPNB AC 370 V, 35 F
m
m
4-8. Outdoor Unit (RAS-10UA-E4, RAS-10UAX4)
No. Parts name Type Specifications
Output (Rated) 750 W, 2 poles, 1 phase, 220 - 240 V, 50Hz
1 Compressor RM5510GNE94 Winding resistance (W) C-R C-S
(at 20°C) 3.710 4.099 Output (Rated) 20 W, 6 poles, 1 phase, 220 - 240 V, 50Hz Winding resistance (W) Red-Black White-Black (at 20°C)
m
m
U/T : 6.1A (80°C), OPEN : 135±5°C, CLOSE : 78±11°C
387.3 or 235.2
466.2 or 260.1
2 Fan motor (for outdoor)
Running capacitor
3
(for fan motor) Running capacitor
4
(for compressor)
Overload relay
5
LPAP960B
HF-240-20B or SKF-240-20B
DS451155BPQC AC 450 V, 1.5 F
DS371256CPNB AC 370 V, 25 F
- 21 -
FILE NO. SVM-05001
4-9. Outdoor Unit (RAS-07UAX4)
No. Parts name Type Specifications
Output (Rated) 605W, 2poles, 1 phase, 220 240V, 50Hz
1 Compressor Winding resistance () C-R C-S
2 Fan motor (for outdoor)
Running capacitor
3
(for fan motor)
Running capacitor
4
(for compressor)
5 Overload relay JMRA99208-9201 U/T: 4.2A (80°C), OPEN: 135±5°C, CLOSE: 69±11°C
PH108X1C-4DZDN2
(at 20°C) 4.84 4.40
Output (Rated) 20W, 6poles, 1 phase, 220 240V, 50Hz
HF-240-20B or SKF-240-20B
DS451155BPQC AC 450V, 1.5µF
DS371256CPNB AC 370V, 25µF
Winding resistance () Red-Black White-Black
(at 20°C) 387.3 or 235.2 466.2 or 260.1
4-10. Outdoor Unit (RAS-07UA-E4)
No. Parts name Type Specifications
Output (Rated) 605W, 2poles, 1 phase, 220 240V, 50Hz
1 Compressor PH108X1C-4DZDN2 Winding resistance () C-R C-S
(at 20°C) 4.84 4.40
Output (Rated) 20W, 6poles, 1 phase, 220 240V, 50Hz
2 Fan motor (for outdoor) Winding resistance () Red-Black White-Black
Running capacitor
3
(for fan motor)
Running capacitor
4
(for compressor)
5 Overload relay JMRA99208-9201 U/T: 4.2A (80°C), OPEN: 135±5°C, CLOSE: 69±11°C
HF-240-20B or SKF-240-20B
DS451155BPQC AC 450V, 1.5µF
DS371256CPNB
(at 20°C)
AC 370V, 25µF
387.3 or 235.2 466.2 or 260.1
22
5. REFRIGERATION CYCLE DIAGRAM
5-1. RAS-13UKHP-E4 / RAS-13UAH-E4
FILE NO. SVM-05001FILE NO. SVM-05001
Indoor unit
Cooling
0.39 m (Connecting pipe)
Æ12.7
O.D.:12.7 mm O.D.:6.35 mm
Cooling
Heating
Heating
P
Packed valve
(Æ12.7)
Heating
4-way valve
Cooling
Compressor
PH225X2C-4FT
Accumulator
Heat exchanger
Cross flow fan
T1
Capillary tube Æ1.5 x 900
Packed valve
(Æ6.35)
Capillary tube
Æ1.0 x 800
l
0.49 m (Connecting pipe)
Æ6.35
l
Heat exchanger
Refrigerant R22 : 1.00 kg.
Cooling Heating
Propeller fan Outdoor unit
Mark ( ) means check points of Gas Leak.
Ambient temp.
50Hz
Standard
pressure
(MPaG)
P
Surface temp. of heat
exchanger interchanging
pipe
T1
(°C)
Fan speed
(indoor)
conditions DB/WB
(°C)
Indoor Outdoor
Standard 1.84 46.0 High 20/15 7/6
Heating Overload*1 2.00 ~ 2.42 52.0 ~ 59.0 Low 27/- 24/18
Low temperature 1.50 38.0 High 20/
-
-10/-10
Standard 0.49 10.0 High 27/19 35/24
Cooling Overload 0.60 15.0 High 32/23 43/26
Low temperature 0.45 2.0 Low 21/15 21/15
Note
Measure the heat exchanger temperature at the center of U-bend. (By means of TC sensor)
·
·
*1 During heating overload operation, a value for the high temperature limit control operation is included.
- 23 -
5-2. RAS-10UKHP-E4 / RAS-10UAH-E4
FILE NO. SVM-05001
Indoor unit
Cooling
0.39 m (Connecting pipe) Æ9.52
O.D.:9.52 mm O.D.:6.35 mm
Cooling
Heating
Heating
P
Packed valve
(Æ9.52)
Heating
4-way valve
Cooling
Compressor
PH180X1C-4DZDN3
Accumulator
Heat exchanger
Cross flow fan
T1
0.49 m (Connecting pipe) Æ6.35
Packed valve
(Æ6.35)
Capillary tube
Æ1.5 x 1000l
Heat exchanger
Refrigerant R22 : 0.76 kg.
Cooling
Heating
Propeller fan Outdoor unit
Mark ( ) means check points of Gas Leak.
Ambient temp.
50Hz
Standard
pressure
(MPaG)
P
Surface temp. of heat
exchanger inter changing
pipe
T1
(°C)
Fan speed
(indoor)
conditions DB/WB
(°C)
Indoor Outdoor
Standard 1.65 40.0 High 20/15 7/6
Heating Overload*1 2.00 ~ 2.40 52.0 ~ 59.0 Low 27/- 24/18
Low temperature 1.40 35.0 High 20/-
-10/-10
Standard 0.50 12.0 High 27/19 35/24
Cooling Overload 0.60 15.0 High 32/23 43/26
Low temperature 0.48 5.0 Low 21/15 21/15
Note
· Measure the heat exchanger temperature at the center of U-bend. (By means of TC sensor)
*1 · During heating overload operation, a value for the high temperature limit control operation is included.
- 24 -
5-3. RAS-07UKHP-E4 / RAS-07UAH-E4
FILE NO. SVM-05001
Indoor unit
Cooling
0.39m (Connecting pipe) 9.52
O.D.:9.52mm O.D.:6.35mm
Cooling
Heating
Heating
P
Packed valve
(9.52)
Heating
4-way valve
Cooling
Compressor
PH108X1C-4DZDN2
Accumulator
Heat exchanger
Cross flow fan
T1
0.49m (Connecting pipe) 6.35
Packed valve
(6.35)
Capillary tube
1.0x900S
(2 pcs.)
Heat exchanger
Refrigerant R-22 : 0.60 kg.
Fan speed
(indoor)
Ambient temp.
conditions DB/WB
(°C)
Indoor Outdoor
Cooling Heating
50Hz
Propeller fan Outdoor unit
Standard
pressure P
(MPaG)
Mark( )means check points of Gas Leak.
Surface temp. of heat
exchanger interchanging
pipe T1 (°C)
Standard 1.32 33.0 High 20/– 7/6
Heating Overload 1.69 49.0 Low 27/– 24/18
Low temperature 1.10 30.0 High 20/––10/–10 Standard 0.59 12.0 High 27/19 35/24
Cooling Overload 0.68 16.0 High 32/23 43/26
Low temperature 0.50 2.0 Low 21/15 21/15
Note :
Measure the heat exchanger temperature at the center of U-bend. (By means of TC sensor)
25
5-4. RAS-13UKP-E4 / RAS-13UA-E4
RAS-13UKPX4 / RAS-13UAX4 RAS-12UKPX4 / RAS-12UAX4
FILE NO. SVM-05001
Indoor unit
Cooling
0.39 m (Connecting pipe) Æ12.7
O.D.:12.7 mm O.D.:6.35 mm
Cooling
Packed valve
Cooling
P
(Æ12.7)
Compressor
PH225X2C-4FT
Heat exchanger
Cross flow fan
T1
Packed valve
(Æ6.35)
Capillary tube Æ1.7 x 1000
0.49 m (Connecting pipe) Æ6.35
l
Heat exchanger
Refrigerant R22 : 0.80 kg.
Cooling
Propeller fan
Outdoor unit
Mark ( ) means check points of Gas Leak.
Ambient temp.
50Hz
Standard
pressure
(MPaG)
P
Surface temp. of heat
exchanger interchanging
pipe
T1
(°C)
Fan speed
(indoor)
conditions DB/WB
(°C)
Indoor Outdoor
Standard 0.48 9.0 High 27/19 35/24
Cooling Overload 0.59 15.0 High 32/23 43/26
Low temperature 0.45 2.0 Low 21/15 21/15
Note
· Measure the heat exchanger temperature at the center of U-bend. (By means of TC sensor)
− 26
5-5. RAS-10UKP-E4 / RAS-10UA-E4
RAS-10UKPX4 / RAS-10UAX4
FILE NO. SVM-05001
Indoor unit
Cooling
0.39 m (Connecting pipe) Æ9.52
O.D.:9.52 mm O.D.:6.35 mm
Cooling
Packed valve
Cooling
P
(Æ9.52)
Compressor
RM5510GNE94
Heat exchanger
Cross flow fan
T1
0.49 m (Connecting pipe) Æ6.35
Packed valve
(Æ6.35)
Capillary tube Æ1.5 x 1100l
Heat exchanger
Refrigerant R22 : 0.68 kg.
Cooling
Propeller fan Outdoor unit
Mark ( ) means check points of Gas Leak.
Ambient temp.
50Hz
Standard
pressure
(MPaG)
P
Surface temp. of heat
exchanger interchanging
pipe
T1
(°C)
Fan speed
(indoor)
conditions DB/WB
(°C)
Indoor Outdoor
Standard 0.54 13.0 High 27/19 35/24
Cooling Overload 0.65 17.0 High 32/23 43/26
Low temperature 0.48 5.0 Low 21/15 21/15
Note
· Measure the heat exchanger temperature at the center of U-bend. (By means of TC sensor)
− 27
5-6. RAS-07UKP-E4 / RAS-07UA-E4
RAS-07UKPX4 / RAS-07UAX4
FILE NO. SVM-05001
Indoor unit
Cooling
0.39m (Connecting pipe) 9.52
O.D.:9.52mm O.D.:6.35mm
Cooling
Packed valve
Cooling
P
(9.52)
Compressor
PH108X1C-4DZDN2
Heat exchanger
Cross flow fan
T1
0.49m (Connecting pipe) 6.35
Packed valve
(6.35)
Capillary tube
1.5x1200S
Heat exchanger
Refrigerant R-22 : 0.57 kg.
Fan speed
(indoor)
50Hz
Cooling
Propeller fan
Outdoor unit
Standard
pressure P
(MPaG)
Mark( )means check points of Gas Leak.
Surface temp. of heat
exchanger interchanging
pipe T1 (°C)
Standard 0.59 13.5 High 27/19 35/24
Cooling
Overload 0.69 18.0 High 32/23 43/26 Low temperature 0.32 2.0 Low 21/15 21/15
Note :
Measure the heat exchanger temperature at the center of U-bend. (By means of TC sensor)
Ambient temp.
conditions DB/WB
(°C)
Indoor Outdoor
28
FILE NO. SVM-05001
6. CONTROL BLOCK DIAGRAM
6-1. RAS-13UKHP-E4 / RAS-13UAH-E4, RAS-10UKHP-E4 / RAS-10UAH-E4,
RAS-07UKHP-E4 / RAS-07UAH-E4
Heat Exchange sensor
Thermo. Sensor
Current Sensor
(Compressor Current)
Infrared Rays Signal Reciver
Main Unit Control Panel
Functions
 Louver Control
3-minutes Delay at Restart
for Compressor
Initiallizing Circuit
Clock Frequency Oscillator Circuit
Power Supply
Circuit
Noise Filter Relay Driver, Louver Driver
Motor Revolution Control
Processing
(Temperature Processing)
Timer
Compressor
ON/OFF
Signal
Outdoor Fan
Relay
RY01
M.C.U.
ON/OFF
Signal
Relay
4-Way Valve
ON/OFF
Signal
RY03
Operation
Display
Timer
Display
Filter Sign
Display
Hi Power
Sign Display
PRE DEF.
Sign Display
Indoor Fan
Motor
Louver
ON/OFF
Signal
Louver
Motor
Relay
RY04
220-240 V~, 50Hz
REMOTE CONTROL
Compressor 4-Way Valve
Remote Control
Outdoor Fan Motor
Operation ( )
Operation Mode Selection
AUTO, COOL, DRY, HEAT, FAN ONLY
Temperature Setting
Fan Speed Selection
ON TIMER Setting
OFF TIMER Setting
Louver Auto Swing
Louver Direction Setting
ECO
Hi power
TIMER 1.3.5.9H
COMFORT SLEEP
QUIET
Infrared Rays
29
FILE NO. SVM-05001
6-2. RAS-13UKP-E4 / RAS-13UA-E4, RAS-10UKP-E4 / RAS-10UA-E4, RAS-07UKP-E4 / RAS-07UA-E4
RAS-13UKPX4 / RAS-13UAX4, RAS-10UKPX4 / RAS-10UAX4, RAS-07UKPX4 / RAS-07UAX4 RAS-12UKPX4 / RAS-12UAX4
Main Unit Control Panel M.C.U.
Heat Exchange sensor
Thermo. Sensor
Infrared Rays Signal Reciver
Initiallizing Circuit
Clock Frequency Oscillator Circuit
Functions
 Louver Control
3-minutes Delay at Restart
for Compressor
Motor Revolution Control
Processing
(Temperature Processing)
Timer
Operation
Display
Timer
Display
Filter Sign
Display
Hi Power
Sign Display
Fan Only
Sign Display
Indoor Fan
Motor
220-240 V~, 50Hz
REMOTE CONTROL
Power Supply
Circuit
Noise Filter Relay Driver, Louver Driver
Operation Mode Selection
AUTO, COOL, DRY, FAN ONLY
Louver Direction Setting
Compressor
ON/OFF
Signal
Relay
RY01
Compressor, Outdoor Fan Motor
Remote Control
Operation ( )
Operation ( )
Temperature Setting
Fan Speed Selection
ON TIMER Setting
OFF TIMER Setting
Louver Auto Swing
ECO
Hi power
TIMER 1.3.5.9H
Infrared Rays
Louver
ON/OFF
Signal
Louver
Motor
COMFORT SLEEP
QUIET
30
7. OPERATION DESCRIPTION
FILE NO. SVM-05001
7-1. Outline of Air Conditioner Control
This is a fixed capacity type air conditioner, which uses AC motor for an indoor fan. The AC motor drive circuit is mounted in the indoor unit. And electrical
parts which driving the compressor and the outdoor
fan motor, are mounted in the outdoor unit.
The air conditioner is controlled by the controller mounted in the indoor unit. The controller operates all components based on the commands transmitted from the remote control and the feedback data of the sensor is as follow:
The temperature measurement at the air inlet of the indoor heat exchanger by the indoor temperature sensor
The temperature measurement at the indoor heat exchanger by the indoor heat exchanger temperature sensor
Indoor fan motor operation control
Louver motor control
LED display control
Outdoor fan motor operation control
4-WAYS-VALVE operation control
(Heat pump model only)
Compressor operation control
Receiving the information of the operation
status and judging the information or the indication of errors
Table 7-1-1
7-1-1. Louver control
(1) Vertical air flow louver
Position of veritcal air flow louver is automatically
controlled according to the operation mode. Besides, position of vertical air flow louver can be arbitrarily set by pressing [FIX] button.
The louver position which is set by [FIX] button is
stored in the microcontroller, and the louver is automatically set at the stored position for the next operation.
(2) Swing
If [SWING] button is pressed when the indoor unit
is in operation, the vertical air flow louver starts
swinging. When [SWING] button is pressed again, it stops swinging.
7-1-2. Indoor fan control (AC Fan motor)
(1) The indoor fan is operated by the stepless speed
change AC motor.
(2) For air flow level, speed of the indoor fan motor is
controlled in five steps (LOW, LOW
+
, MED, MED and HIGH). If AUTO mode is selected, the fan motor speed is automatically controlled by the difference between the preset temperature and the room temperature.
LOW
=
LOW+MED
+
2
MED+=
MED+HIGH
2
+
OPERATION
MODE
RAS-07UK Series
RAS-07UKH Series
RAS-10UK Series
Model
RAS-10UKH Series
RAS-13UK Series
RAS-13UKH Series
FAN TA P
Cooling UH H M L L- UL SL
Fan only H M L L-
Dry M L L- UL SL
Heat UH H M L L- UL SL
rpm 1350 1300 1200 1050 1000 950 900 800 750 700 650
Air flow volume (m3/h) 650 630 570 490 460 430 400 340 310 280 250
rpm 1300 1200 1050 1000 900 800 750 700 650
Air flow volume (m3/h) 630 570 490 460 400 340 310 280 250
rpm 1350 1250 1050 1000 950 900 800 750 700 650
Air flow volume (m3/h) 650 610 490 460 430 400 340 310 280 250
rpm
Air flow volume (m3/h)
rpm
Air flow volume (m3/h)
rpm
Air flow volume (m3/h)
1300 1200 1100 1000 900 800 750 700 650
1250
610
1300
630
1250
630 570 520 460 400 340 310 280 250
610
1350 1300 1150 1100 1050 1000 950 900 850 750
650 630 550 520 490 460 430 400 370 310
1350 1300 1150 1100 1050 1020 950 900 850 750
650 630 550 520 490 470 430 400 370 310
800
340
800
340
700
280
700
280
31
FILE NO. SVM-05001
7-2. Description of Operation Circuit
(1) When turning on the breaker, the operation lamp
blinks. This means that the power supply is on.
(2) When pressing [ ] button on the remote control,
receiving beep sounds from the indoor unit, and the next operation is performed together with opening the vertical air flow louver.
(3) Once the operation mode is set, it is memorized in
the microcontroller so that the previous operation can be effected thereafter simply by pressing [ ] button.
7-2-1. Fan only operation
([MODE] button on the remote control is set to the fan only operation.)
(1) When [FAN] button is set to AUTO, the indoor fan
motor operates as shown in Fig. 7-2-1. When [FAN] button is set to LOW, LOW HIGH, the motor operates with a constant air flow.
°C
+3 +2.5 +2
-
+1.5 +1 +0.5
(Room temp.) (Preset temp.)
Preset temp.
0
(Preset temp.: 22°C)
NOTE :
*1: The values marked with *1 are calculated and
controlled by the difference in motor speed between M+ and L-.
(2) The Hi POWER, ECO and COMFORT SLEEP
operation cannot be set.
Fig. 7-2-1 Setting of air flow [FAN:AUTO]
+
, MED, MED+ or
M+
*1 *1 *1 L
-
7-2-2. Cooling operation
([MODE] button on the remote control is set to the cooling operation.)
(1) The compressor, 4-way valve, outdoor fan and
operation display on the remote control are controlled as shown in Fig. 7-2-2.
°C
ON ON
OFF OFF OFF ON
4-way valve
Compressor
Outdoor fan
OPERATION
-
(Room temp.) (Preset temp.)
Preset temp.
0.5
0
Fig. 7-2-2
(2) When [FAN] button is set to AUTO, the indoor fan
motor operates as shown in Fig. 7-2-3. When [FAN] button is set to LOW, LOW
+
, MED, MED+ or
HIGH, the motor operates with a constant air flow.
°C
(Preset temp.)
(Room temp.)
Preset temp.
+3 +2.5 +2 +1.5 +1
+0.5
0
-0.5
M+
*1 *1 *1
L
-
NOTE :
*1: The values marked with *1 are calculated and
controlled by the difference in motor speed between M+ and L-.
display
- 32 -
Fig. 7-2-3 Setting of air flow [FAN:AUTO]
FILE NO. SVM-05001
7-2-3. Dry operation
([MODE] button on the remote control is set to the dry operation.)
(1) The compressor, 4-way valve, outdoor fan and
operation display on the remote control are controlled as shown in Fig. 7-2-4.
°C
ON:6min.
-
(Room temp.) (Preset temp.)
Preset temp.
+3
+2
+1
ON:6min.
OFF:4min.
ON:5min.
OFF:5min.
OFF
0
Compressor
OFF
ON:5min.
OFF
4-way valve
OFF:4min.
OFF:5min.
Outdoor fan
Fig. 7-2-4
ON
display
OPERATION
7-2-4. Heating operation *Heat pump model only
([MODE] button on the remote control is set to the heating operation.)
(1) The compressor, 4-way valve, outdoor fan and
operation display on the remote control are controlled as shown in Fig. 7-2-6.
°C
Preset temp.
0
-0.5
-
(Room temp.) (Preset temp.)
ON
OFF
ON
Compressor
ON
OFF
ON
4-way valve
Outdoor fan
Fig. 7-2-6
display
OPERATION
(2) The microcontroller turns the compressor on and
off at the regular intervals (4 to 6 minutes). While the compressor is turning off, the indoor fan motor operates in the SUPER LOW position. The pattern of operation depending on the relation between room temperature and preset temperatures is shown in Fig. 7-2-5.
Room temp.
Preset temp.+1 Preset temp.
Compressor Outdoor fan
Indoor fan
ON ON ON ON
OFF OFF OFF
L *SL SLLL SL L
*
Super Low
Fig. 7-2-5
(3) [FAN] button on the remote control is set to AUTO
only.
(2) When [FAN] button is set to AUTO, the indoor fan
motor operates as shown in Fig. 7-2-7. When [FAN] button is set to LOW, LOW
+
, MED, MED+ or
HIGH, the motor operates with a constant air flow.
Preset
temp.
°C
0
-0.5
-1
-1.5
-2
-
-5.0
-5.5
[FAN AUTO]
(Room temp.) (Preset temp.)
L *1
*2
+
M
H
*1, *2 : The values marked with *1 and *2 are
calculated and controlled by the difference in motor speed between M+ and L.
Fig. 7-2-7 Setting of air flow [FAN:AUTO]
(4) The Hi POWER, ECO, COMFORT SLEEP and
QUIET operations cannot be set.
- 33 -
FILE NO. SVM-05001
(3) The indoor heat exchanger restricts revolving
speed of the fan motor to prevent a cold draft. The upper limit of the revolving speed is shown in Fig. 7-2-8 and Table 7-2-1.
13UKH Series
°C
424134
33
292821
20
*2
A+4
A+4
A− 8
A− 8
*6 *5
Indoor heat exchanger temperature
AUTO
*4
*3
SL
SL*1
Stop
Manual (One of 5 steps)
-
H (Up to
L seting speed)
10UKH Series 07UKH Series
°C
464534
33
323121
20
*2
A+4
A+4
A
8
A
8
*6 *5
Indoor heat exchanger temperature
AUTO
*4
*3
SL
SL*1
Stop
Manual (One of 5 steps)
L- H (Up to seting speed)
NOTES :
*1: The fan stops for 2 minutes after thermostat-OFF. *2: A is 24°C when the preset temperature is 24°C or
more and A is the preset temperature when it is
under 24°C. *3: SL means Super Low. *4: Calculated from difference in motor speed
between SL and H.
Fig. 7-2-8 Cold draft preventing control
*5 and *6:
Table 7-2-1
Fan *5 *6 speed Starting period Stabilized period
·
AUTO Up until 12 minutes
Manual Room temperature (L H) < Preset temperature
-
·
passed after starting the unit
·
From 12 to 25 minutes passed after starting the unit and room temperature is 3°C lower than preset temperature
·
·
-
 From 12 to 25 minutes
passed after starting the unit and room temperature is between preset temperature and 3°C lower than preset temperature
 25 minutes or more
·
passed after starting the unit
 Room temperature
·
Preset temperature
4°C
-
3.5°C
7-2-5. Automatic operation
([MODE] button on the remote control is set to the automatic operation.)
(1) One of 3 operations (Cooling, Fan only or Heating)
is selected according to difference between the preset temperature and the room temperature at which the automatic operation has started, as shown in Fig. 7-2-9. The Fan only operation continues until the room temperature reaches a level at which another mode is selected.
(2) Temporary Auto
When the [TEMPORARY] button on the indoor unit
is pushed, the preset temperature is fixed at 24°C and the indoor unit is controlled as shown in Fig. 7-2-9.
°C
Cooling operation
The louver moves to the position same as Hi POWER operation.
+4
Cooling operation
0
-
34
-
1
-
(Room temp.) (Preset temp.)
-
Fan only operation
Heating operation
UKH Series UK Series
Fig. 7-2-9
FILE NO. SVM-05001
7-3. Hi POWER Mode
([Hi POWER] button on the remote control is pressed.)
When [Hi POWER] button is pressed while the indoor unit is in Auto, Cooling or Heating operation, Hi POWER mark is indicated on the display of the remote control and the unit operates as follows.
(1) Automatic operation
The indoor unit operates in according to the
·
current operation.
(2) Cooling operation
The setting temperature drops 3°C. (The value of the setting temperature on the remote control does not change.)
If the room temperature is higher than the setting temperature by 3.5°C or more, the horizontal louver moves to the Hi POWER position automatically. Then when the room temperature is 1°C less than the setting temperature the horizontal louver returns automatically.
FAN speed : [AUTO] If the room temperature is higher than the setting temperature by 3.5°C or more, the air conditioner operates at maximum airflow level. If the room temperature is higher than the setting temperature by less than 3.5°C, the air conditioner operates at normal airflow level.
FAN speed : One of 5 levels If the room temperature is higher than the setting temperature by 3.5°C or more, the air conditioner operates at higher consecutive airflow level. If the room temperature is higher than the setting temperature by less than 3.5°C, the air conditioner operates at normal airflow level.
7-4. High-Temperature Limit Control
*Heat pump model only
The microcontroller detects the indoor heat exchanger temperature to prevent pressure of a refrigerating cycle from increasing excessively. The compressor and outdoor fan motor are controlled as shown in Fig. 7-4-1.
Compressor
OFF
ON
ON
Outdoor fan
OFF
OFF
ON
Heat exchanger temp.
(°C) 60
53 52
Fig. 7-4-1
7-5. Low-Temperature Limit Control
The microcontroller detects the indoor heat exchanger temperature to prevent the indoor heat exchanger from freezing. The compressor and outdoor fan motor are controlled as shown in Fig. 7-5-1 and 7-5-2.
13UKH Series 13UK Series 12UK Series
Heat exchanger temperature
(°C)
6
2
Compressor Outdoor fan
ON
Less than 2°C continues
for 5 minutes
OFF
(3) Heating operation (UKH Series only)
The preset temperature increases 2°C,
·
(The value of the preset temperature on the remote control does not change.) The indoor unit operates in normal heating
·
mode except the preset temperature is higher (+2°C).
(4) The Hi POWER mode can not be set in Dry or Fan
only operation.
-
10UKH Series 10UK Series
07UKH Series 07UK Series
Heat exchanger temperature
(°C)
7
5
35
-
Fig. 7-5-1
Compressor
Fig. 7-5-2
Outdoor fan
ON
Less than 5°C continues
for 5 minutes
OFF
FILE NO. SVM-05001
7-6. Defrost Operation *Heat pump model only
During the heating operation, the outdoor heat exchanger temperature goes down and sometimes it is frozen. In this case, the air conditioner stops the heating operation and starts the defrost operation to melt ice.
7-6-1. Condition to start the defrost operation
The defrost operation starts whichever below conditions are satisfied.
(1) When the cumulative compressor operating time is
longer than 40 or 90 minutes and difference between the indoor heat exchanger temperature and the room temperature is less than the specified value. (This value is decided by the microprocessor.) (Control example is shown in Fig. 7-6-1. In case of B or C, the defrost operation starts.)
(2) When the current limit control or the high
temperature limit control is performed for total of 90 minutes.
D
<In case of C>
(1) The heating operation is performed for at least 90
minutes.
(2) The defrost operating time is 10 minutes.
7-6-3. Ending condition at defrost operation
(1) When the compressor current becomes 7.5A or
more during defrost operation, the defrost operation stops and the heating operation restarts. (The current sensor detects the compressor current.)
(2) The defrost operation continues for at most
6 minutes or 10 minutes.
DEFROST LAMP :
·
During defrost operation, the PRE-DEF. lamp is on and the indoor and outdoor fans are off.
·
The compressor start protection timer is inter­looked with the PRE-DEF. lamp . So the PRE-DEF. Lamp is off (the fans stop) for about 3 minutes after the [ ] button is turned on. When the compressor is turned on, the PRE-DEF. lamp comes on. After the heat ex-changer is preheated to about 24 goes off, and the indoor fan starts.
°C or higher
, the PRE-DEF. Lamp
xchanger temp
Indoor heat e
- Room temp
A
B
C
Cumulative compressor operating time
Fig. 7-6-1 (Indoor fan speed : M)
7-6-2. Defrost operation time control
<In case of B>
(1) The heating operation is performed for at least
40 minutes.
(2) The maximum defrost operating time is 6 minutes.
The defrost operating time for the 4th cycle is 10 minutes. (When the outdoor temperature is very low, however, the defrost operating time is 10 minutes.)
minutes
40
Heating
minutes
40
Defrost
Heating
minutes
40
Defrost
Heating
minutes
40
Defrost
Heating
Defrost
Max 6 minutes
1 cycle
Fig. 7-6-2
10 minutes
-
36
-
7-7. Current Limit Control *Heat pump model
only
The microcontroller detects the input current so as to prevent it exceeds a specified value by means of controlling the outdoor fan control as described in (1) and (2).
(1) Current limit control (Cooling operation)
Control is performed as shown below by detecting the compressor operating current with a current sensor (C.T).
Input current
FILE NO. SVM-05001
13UKH Series / 10UKH Series
/ 07UKH Series
13.5A / 19.2A I4
12.5A / 17.8A I3
(2) Current limit control (Heating operation)
Control is performed as shown in Fig. 7-7-2
Input current
13UKH Series / 10UKH Series
/ 07UKH Series
13.5A / 19.2A I4
12.5A / 17.8A I3
Compressor Outdoor fan More than I4 continues for 3 seconds
OFF
More than I3 continues for 5 seconds
OFF
ON
Fig. 7-7-1
Compressor Outdoor fan More than I4 continues for 3 seconds
OFF
More than I3 continues for 5 seconds
OFF
10A / 15.6A I2
9A / 15.0A I1
ON OFF
ON
Fig. 7-7-2
Remark :
1. This function is available only for heat pump model (Cooling models have no a current sensor (C.T.)).
2. For 07UKH Series and 10UKH Series, the value of currents shown on the diagram above are two times the actual operating value. This is because the lead wire operated two times through the C.T.
37
-
-
FILE NO. SVM-05001
7-8. Auto Restart Function
The indoor unit is equipped with an automatic restarting function which allows the unit to restart operating with the set operating conditions in the event of power supply being accidentally shut down. The operation will resume without warning three minutes after power is restored. This function is not set to work when shipped from the factory. Therefore it is necessary to set it to work.
7-8-1. How to set auto restart function
To set the auto restart function, proceed as follows: The power supply to the unit must be on; the function will not set if the power is off. Push the [TEMPORARY] button located in the center of the front panel continuously for three seconds. The unit receives the signal and beeps three times. The unit then restarts operating automatically in the event of power supply being accidentally shut down.
When the unit is on standby (Not operating)
Operation Motions
Push [TEMPORARY] button for more The unit is on standby. than three seconds.
¯
The unit starts to operate. The green lamp is on.
¯
The unit beeps three times The lamp changes from and continues to operate. green to orange.
If the unit is not required to operate at this time, push [TEMPORARY]
[TEMPORARY] button
0
3S
button once more or use the remote control to turn it off.
After approx. three seconds,
When the unit is in operation
Operation Motions
Push [TEMPORARY] button for more The unit is in operation. The green lamp is on. than three seconds.
¯
The unit stops operating. The green lamp is turned off.
After approx. three seconds,
¯
0
3S
The unit beeps three times If the unit is required to operate at this time, push [TEMPORARY]
[TEMPORARY] button
While this function is being set, if the unit is in
·
operation, the orange lamp is on.
·
This function can not be set if the timer operation has been selected.
·
When the unit is turned on by this function, the
button once more or use the remote control to turn it on.
·
While the filter check lamp is on, the
[TEMPORARY] button has the function of filter reset button.
louver will not swing even though it was swinging automatically before shutting down.
-
38
-
7-8-2. How to cancel auto restart function
To cancel auto restart function, proceed as follows: Repeat the setting prodedure: the unit receives the signal and beeps three times. The unit will be required to be turned on with the remote control after the main power supply is turned off.
When the unit is on standby (Not operating)
Operation Motions
Push [TEMPORARY] button for more The unit is on standby. than three seconds.
¯
The unit starts to operate. The orange lamp is on.
¯
0
3S
The unit beeps three times The lamp changes from and continues to operate. orange to green.
¯
FILE NO. SVM-05001
After approx. three seconds,
[TEMPORARY] button
If the unit is not required to operate at this time, push [TEMPORARY] button once more or use the remote control to turn it off.
When the unit is in operation
Operation Motions
Push [TEMPORARY] button for more The unit is in operation. The orange lamp is on. than three seconds.
¯
The unit stops operating. The orange lamp is turned off.
After approx. three seconds,
¯
0
3S
The unit beeps three times If the unit is required to operate at this time, push [TEMPORARY]
[TEMPORARY] button
·
While this function is being set, if the unit is in
button once more or use the remote control to turn it on.
7-9. Filter Check Lamp
operation, the orange lamp is on.
When the elapsed time reaches 1000 hours, the filter
7-8-3. Power failure during timer operation
check lamp indicates. After cleaning the filters, turn off the filter check lamp.
When the unit is in Timer operation, if it is turned off because of power failure, the timer operation is
7-9-1. How to turn off filter check lamp
cancelled. Therefore, set the timer operation again.
Push [TEMPORARY] button on the indoor unit.
Note:
If [TEMPORARY] button is pushed while the filter check lamp is not indicating, the indoor unit will start the Automatic Operation.
- 39 -
FILE NO. SVM-05001
7-10. Self-Cleaning function
Self-Cleaning function is designed to reduce humidity that causes mold to form inside the air conditioning unit. This advanced, efficient system reduces moisture in the coil. When air conditioner is turned off, the internal fan activates and dries the moisture in the coil for 20 minutes, then it turns off automatically.
Operation display ON OFF OFF
FCU fan
FCU louver OPEN CLOSE CLOSE
Timer display
Compressor
CDU fan ON or OFF
rpm is depend on presetting. rpm is SL speed.
depend on presetting of timer function. depend on presetting of timer function.
depend on presetting per room temperature.
depend on presetting per room temperature.
Cool mode or dry mode
operation more than 10 mins.
ON ON
ON or OFF
ON or OFF
8
Self-Cleaning mode
operate 20 mins.
Turn off by remote controller or
timer-off function.
ON
OFF OFF
OFF OFF
8
Automatically turn-off.
The Self-Cleaning function is set as default at ex-factory.
Self-Cleaning operation can stop manually by press [
7-
10-1. How to cancel Self-Cleaning function
To cancel the Self-Cleaning function, proceed as follows:
• Press [
TEMPORARY] button one time or use remote control to turn on air conditioner. The OPERATION display will show in orange color (When AUTO­RESTART is ON) or green color (When AUTO­RESTART is OFF).
• Hold down the [
TEMPORARY] button for more than 20 seconds. (The air conditioner will stop suddenly when the [
TEMPORARY] button is pressed but keep holding it continue. Then will beep 3 times in the first 3 seconds but it is not related to Self-Cleaning function)
After holding about 20 seconds, the air conditioner will beep 5 times without any blinking of display.
The Self-Cleaning Operation had been cancelled.
] button of the remote control two more time.
10-2. How to set Self-Cleaning function.
7-
To set the Self-Cleaning function, proceed as follows.
• Press [
TEMPORARY] button one time or use remote control to turn on air conditioner. The OPERATION display will show in orange color (When AUTO­RESET is ON) or green color (When AUTO­RESTART is OFF).
• Hold down the [
TEMPORARY] button for more than 20 seconds. (The air conditioner will stop suddenly when the [ holding it
TEMPORARY] button is pressed but keep
continue. Then will beep 3 times is the first 3 seconds but it is not related to Self-Cleaning function)
After holding about 20 seconds, the air conditioner will beep 5 times and OPERATION display blinks 5 times.
The Self-Cleaning function had been set.
OFF
ON or OFF
-
Operation time
Remarks
Per setting of Self-Cleaning function above, AUTO­RESTART function had been cancelled. To set AUTO-RESTART again, please follow item 7-
8-1.
Remarks
Per setting of Self-Cleaning function above, AUTO­RESTART function had been cancelled. To set AUTO-RESTART again, please follow item 7-
– 40 –
8-1.
FILE NO. SVM-05001
7-11. QUIET Mode
Quiet mode is the system which, control the revolving speed of indoor fan to work constantly
at lower than speed L. In addition, noise level of indoor unit is less than usual.
When the [QUIET] button is pressed, the fan of the indoor unit will be restricted the revolving speed at
speed L
again (cancel Quiet mode).
Remarks :
1. Quiet mode is unable to work in dry mode.
2. Quiet mode is appropriate to work with less
-
until the [QUIET] button is pressed once
cooling load and less heating load condition. Because of the fan speed L- may cause not
enough the cooling capacity or heating capacity.
7-12. COMFORT SLEEP mode
The principles of comfort sleep mode are:
Quietness for more comfortable.
Save energy by changing room temperature
automatically.
The air condition can shut down by itself
automatically.
7-12-1. Cooling mode
The fan speed of indoor unit operates automatically,
it relates with the compressor's operation.
Compressor’s Operation Fan Speed
ON L
OFF SL
The preset temperature will increase 1°C after the
Comfort sleep mode has operated for 1 hour and the temperature will increase another 1°C after the comfort sleep mode has operated for 2 hour. (The value of the preset temperature on the remote control
does not change.)
Press the [COMFORT SLEEP] button to choose the
operating hours. Repeat pressing to select the hours. (1hr, 3hr, 5hr or 9hr)
If the [COMFORT SLEEP] button is pressed again
means cancel comfort sleep mode.
7-12-2. Heating mode
The fan speed of indoor unit operates automatically,
it relates with the compressor's operation.
Compressor’s Operation Fan Speed
ON L
OFF SL
-
-
Remarks:
1. Comfort sleep mode will not operate in dry mode
and fan only mode.
2. Comfort sleep mode is appropriate to work with less
cooling load and less heating load condition. Because of the fan speed L- may cause not enough
the cooling capacity or heating capacity.
The preset temperature will drop down 1°C after the
comfort sleep mode has operated for 1 hour and the temperature will decrease another 1°C after the comfort sleep mode has operated for 2 hour. (The
value of the preset temperature on the remote control. dose not change.)
Press the [COMFORT SLEEP] button to choose the
operating hours. Repeat pressing to select the hours. (1hr, 3hr, 5hr or 9 hr)
If the [COMFORT SLEEP] button is pressed again
means cancel comfort sleep mode.
-
41
-
FILE NO. SVM-05001
8. INSTALLATION PROCEDURE
8-1. Safety Cautions
For general public use
Power supply cord of parts of appliance for Outdoor use shall be at least polychloroprene sheathed flexible cord (design H07 RN-F), or cord designation 245 IEC66.
CAUTION
This appliance must be connected to the main power supply by means of a circuit breaker or a switch with a contact separation of at least 3 mm. If this is not possible, a power supply plug with earth must be used. This plug must be easily accessible after installation. The plug must be disconnected from the power supply socket in order to disconnect the appliance completely from the mains.
To Disconnect the Appliance from the Main Power Supply
DANGER
FOR USE BY QUALIFIED PERSONS ONLY.
TURN OFF MAIN POWER SUPPLY BEFORE ATTEMPTING ANY ELECTRICAL WORK. MAKE SURE
ALL POWER SWITCHES ARE OFF. FAILURE TO DO SO MAY CAUSE ELECTRIC SHOCK.
CONNECT THE CONNECTING CABLE CORRECTLY. IF THE CONNECTING CABLE IS CONNECTED WRONGLY, ELECTRIC PARTS MAY BE DAMAGED.
CHECK THE EARTH WIRE THAT IT IS NOT BROKEN OR DISCONNECTED BEFORE INSTALLATION.
DO NOT INSTALL NEAR CONCENTRATIONS OF COMBUSTIBLE GAS OR GAS VAPORS.
FAILURE TO FOLLOW THIS INSTRUCTION CAN RESULT IN FIRE OR EXPLOSION.
TO PREVENT OVERHEATING THE INDOOR UNIT AND CAUSING A FIRE HAZARD, PLACE THE UNIT WELL AWAY (MORE THAN 2 M) FROM HEAT SOURCES SUCH AS RADIATORS, HEATORS, FURNACE, STOVES, ETC.
WHEN MOVING THE AIR-CONDITIONER FOR INSTALLING IT IN ANOTHER PLACE AGAIN, BE VERY CAREFUL NOT TO GET THE SPECIFIED REFRIGERANT (R410A) WITH ANY OTHER GASEOUS BODY INTO THE REFRIGERATION CYCLE. IF AIR OR ANY OTHER GAS IS MIXED IN THE REFRIGERANT, THE GAS PRESSURE IN THE REFRIGERATION CYCLE BECOMES ABNORMALLY HIGH AND IT RESULTINGLY CAUSES BURST OF THE PIPE AND INJURIES ON PERSONS.
IN THE EVENT THAT THE REFRIGERANT GAS LEAKS OUT OF THE PIPE DURING THE INSTALLATION WORK, IMMEDIATELY LET FRESH AIR INTO THE ROOM. IF THE REFRIGERANT GAS IS HEATED BY FIRE OR SOMETHING ELSE, IT CAUSES GENERATION OF POISONOUS GAS.
WARNING
Never modify this unit by removing any of the safety guards or bypassing any of the safety interlock switches.
Do not install in a place which cannot bear the weight of the unit. Personal injury and property damage can result if the unit falls.
Before doing the electrical work, attach an approved plug to the power supply cord. Also, make sure the equipment is properly earthed.
Appliance shall be installed in accordance with national wiring regulations. If you detect any damage, do not install the unit. Contact your TOSHIBA dealer immediately.
CAUTION
Exposure of unit to water or other moisture before installation could result in electric shock. Do not store it in a wet basement or expose to rain or water.
After unpacking the unit, examine it carefully for possible damage.
Do not install in a place that can increase the vibration of the unit. Do not install in a place that can amplify
the noise level of the unit or where noise and discharged air might disturb neighbors.
To avoid personal injury, be careful when handling parts with sharp edges.
Please read this installation manual carefully before installing the unit. It contains further important
instructions for proper installation.
 − 42
FILE NO. SVM-05001
REQUIREMENT OF REPORT TO THE LOCAL POWER SUPPLIER
Please make absolutely sure that the installation of this appliance is reported to the local power supplier before installation. If you experience any problems, or if the installation is not accepted by the supplier, the service agency will take adequate countermeasures.
Remark per EMC Directive 89/336/EEC
To prevent flicker impressions during the start of the compressor (technical process) following installation conditions do apply.
1. The power connection for the air conditioner has to be done at the main power distribution. This distribution has to be of an impedance. Normally the required impedance is reached at a 32A fusing point. Air conditioner fuse has to be 16A max.!
2. No other equipment should be connected to this power line.
3. For detailed installation acceptance, please contact your power supplier whether its restriction does apply for products like washing machines, air conditioners or electrical ovens.
4. For power details of the air conditioner, refer to the rating plate of the product.
43
8-2. Installation Diagram of Indoor and Outdoor Units
FILE NO. SVM-05001
Before installing the wireless remote control
With the remote control cover
open, load the batteries supplied correctly, observing their polarity.
22
2 Wireless remote control
22
Cover
33
3 Batteries
33
(Attach to the front panel)
5
Bio-enzyme &
Gingko filter
2 Wireless remote
control
12,13 series 07,10 series
A 600 mm 400 mm
170 mm
or more
Air filter
6 Sasa-zeolite plus filter
8 Pan head wood screw
4 Remote control holder
Hook
Hook
1 Installation
65 mm or more
plate
Shield pipe
170 mm
or more
For the rear left and left piping
Wall
Insert the cushion between the indoor unit and wall, and tilt the indoor unit for better operation.
Do not allow the drain hose to get slack.
Cut the piping hole sloped slightly
Make sure to run the drain hose sloped downward.
The auxiliary piping can be connected the left, rear left, rear right, right, bottom right or bottom left.
B 100 mm 45 mm
100 mm or more
A mm or more
B mm or more
600 mm or more
Vinyl tape Apply after carrying out a drainage test.
Saddle
Extension drain hose
(
Not available,
provided by installer)
600 mm or more
Right
Rear right
Rear left
Bottom right
Bottom left
Insulate the refrigerant pipes separately with insulation, not together.
6 mm thick heat resisting polyethylene foam
Left
 − 44 − 
8-3. Installation
8-3-1. Optional installation parts
FILE NO. SVM-05001
Part
Code
Parts name
Refrigerant piping Liquid side : 6.35 mm
A
Gas side : 9.52 mm (07,10 series) Gas side : 12.70 mm (13 series)
Pipe insulating material
B
(polyethylene foam, 6 mm thick) Putty, PVC tapes
C
Æ Æ Æ
<Fixing bolt arrangement of outdoor unit>
RAS-10,12,13 Series
125 mm115 mm
310 mm
7 mm
32.5 mm
73 mm
Air outlet
30
Æ
600 mm
Air inlet
102 mm
90 mm
Drain outlet
Q'ty
One
each
1
One
each
275 mm
60 mm
RAS-07 Series
500 mm
97 mm
Air outlet
Drain outlet
Air inlet
Fig. 8-3-1
·
Secure the outdoor unit with fixing bolts and nuts if the unit is likely to be exposed to a strong wind. Use 8 mm or 10 mm anchor bolts and nuts.
·
·
Æ
If it is necessary to drain the defrost water, attach drain nipple
Æ
9
and cap w
ater proof
10
to the bottom
plate of the outdoor unit before installing it.
45
8-3-2. Accessory and installation parts
FILE NO. SVM-05001
Part
No.
Part name (Q’ty)
1
Installation plate x 1
2
Wireless remote control x 1
3
Battery x 2
Others
Owner’s manual
Installation manual
Name
Part
No.
Part name (Q’ty)
4
Remote control holder x 1
5
Sasa-zeolite plus filter x 1
6
Bioenzyme & Gingko filter x 1
Part
No.
Part name (Q’ty)
7
Mounting screw 4 x 25 s x 6
8
Pan head wood screw
3.1 x 16 s x 2
9
Drain nipple* x 1
!
Cap water proof* x 2
(For Heat pump model only)
The part marked with asterisk ( outdoor unit.
(For Heat pump model only)
*) is packaged with the
46
62
85
82.5
170
FILE NO. SVM-05001
8-4. Indoor Unit
8-4-1. Installation place
A place which provides the spaces around the indoor unit as shown in the above diagram.
A place where there is no obstacle near the air inlet and outlet.
A place that allows easy installation of the piping to the outdoor unit.
A place which allows the front panel to be opened.
CAUTION
Direct sunlight to the indoor unit’s wireless
receiver should be avoided.
The microprocessor in the indoor unit should not
be too close to RF noise sources. (For details, see the owner’s manual.)
<Remote control>
A place where there are no obstacles such as a curtain that may block the signal from the indoor unit.
Do not install the remote control in a place exposed to direct sunlight or close to a heating source, such as a stove.
Keep the remote control at least 1 m apart from the nearest TV set or stereo equipment. (This is necessary to prevent image disturbances or noise interference.)
The location of the remote control should be determined as shown below.
8-4-2. Cutting a hole and mounting installation
plate
<Cutting a hole>
When installing the refrigerant pipes from the rear.
Pipe hole
65 mm
The center of the pipe hole is above the arrow.
100 mm
Fig. 8-4-2
1. After determining the pipe hole position on the mounting plate (A), drill the pipe hole (65 mm) at a slight downward slant to the outdoor side.
NOTE
When drilling a wall that contains a metal lath, wire lath or metal plate, be sure to use a pipe hole brim ring sold separately.
<Mounting the installation plate>
For installation of the indoor unit, use the paper pattern on the back.
Thread
Hook
Weight
Hook
Pipe hole
7 Mounting screw
1
Installation plate
ndoor unit
I
(Side view)
7 m
°
75
Reception range
Remote control
(Top view)
Indoor unit
Reception range
* : Axial distance
Fig. 8-4-1
5 m
5 m
45
°
45
°
Remote control
* 7 m
Hook
Pipe hole
Indoor unit
Fig. 8-4-3
47
FILE NO. SVM-05001
<When the installation plate is directly mounted on the wall>
1. Securely fit the installation plate onto the wall by screwing it in the upper and lower parts to hook up the indoor unit.
2. To mount the installation plate on a concrete wall with anchor bolts, utilize the anchor bolt holes as illustrated in the above figure.
3. Install the installation plate horizontally in the wall.
CAUTION
When installing the installation plate with a mounting screw, do not use the anchor bolt hole. Otherwise the unit may fall down and result in personal injury and property damage.
Installation plate <Keep horizontal direction>
Anchor bolt
Projection
5 mm dia. hole
Clip anchor (local parts)
15 mm or less
77
7 Mounting
77
screw 4 x 25
ss
s
ss
Fig. 8-4-4
CAUTION
8-4-3. Electrical work
1. The supply voltage must be the same as the rated voltage of the air conditioner.
2. Prepare the power source for exclusive use with the air conditioner.
CAUTION
This appliance can be connected to the mains in either of the following two ways. (1) Connection to fixed wiring:
A switch or circuit breaker which disconnects all poles and has a contact separation of at least 3 mm must be incorporate in the fixed wiring. An approved circuit breaker or switches must used.
(2) Connection with power supply plug:
Attach power supply plug with power cord and plug it into wall outlet. An approved power supply cord and plug must be used.
NOTE
Ensure all wiring is used within its electrical rating.
RAS-13UKHP-E4 RAS-10UKHP-E4
Model
Power source
Maximum running current
Plug socket & fuse rating
Power cord
RAS-13UKP-E4 RAS-07UKHP-E4
RAS-13UKPX4 RAS-12UKPX4
50Hz, 220
1.3 mm
12A 7.5A
2
or more 1 mm
RAS-10UKP-E4 RAS-07UKP-E4
RAS-10UKPX4 RAS-07UKPX4
240 V Single phase
16A
2
or more
Failure to firmly install the unit may result in personal injury and property damage if the unit falls.
In case of block, brick, concrete or similar type walls, make 5 mm dia. holes in the wall.
Insert clip anchors for appropriate 7 mounting screws.
NOTE
Secure four corners and lower parts of the installation plate with 4 to 6 mounting screws to install it.
48
1
2
3
4
1
2
60 mm
10 mm
10 mm
50 mm
FILE NO. SVM-05001
<How to connect the connecting cable>
Wiring of the connecting cable can be carried out without removing the front panel.
1. Remove the air inlet grille. Open the air inlet grille upward and pull it toward you.
2. Remove the terminal cover and cord clamp.
3. Insert the connecting cable (according to the local cords) into the pipe hole on the wall.
4. Take out the connecting cable through the cable slot on the rear panel so that it protrudes about 15 cm from the front.
5. Insert the connecting cable fully into the terminal block and secure it tightly with screws.
6. Tightening torque : 1.2 N·m (0.12 kgf·m)
7. Secure the connecting cable with the cord clamp.
8. Fix the terminal cover, rear plate bushing and air inlet grille on the indoor unit.
CAUTION
Be sure to refer to the wiring system diagram
labeled inside the front panel.
Check local electrical cords and also any specific
wiring instructions or limitations.
For RAS-13/10/07UKP
Terminal cover
Connecting cable
about 15 cm
Screw
Stripping length of the connecting cable
Cord clamp
Screw
Screw
Fig. 8-4-7
1
2
Connecting cable
Earth line
Terminal block
Earth line
For RAS-13/10/07UKHP
Terminal cover
Screw
Connecting cable
about 15 cm
Screw
Fig. 8-4-5
10 mm
10 mm
Stripping length of the connecting cable
Cord clamp
Screw
80 mm
70 mm
10 mm
50 mm
4
1
2
3
Earth line
Terminal block
Earth line
Connecting cable
Fig. 8-4-8
NOTE
Use stranded wire only.
Wire type : H07 RN-F or more
<How to install the air inlet grille on the indoor unit>
When attaching the air inlet grille, the contrary of the removed operation is performed.
Fig. 8-4-9
Fig. 8-4-6
49
FILE NO. SVM-05001
8-4-4. Piping and drain hose installation
<Piping and drain hose forming>
* Since dewing results in a machine trouble, make
sure to insulate both the connecting pipes. (Use polyethylene foam as insulating material.)
Rear right
Rear left
Bottom left
Changing
Left Bottom right Right
Die-cutting
Front panel slit
drain hose
Piping preparation
1. Die-cutting Front panel slit
For leftward connection, cut out slit on the left side of the front panel. (A knife will produce splinters, so use nippers.)
2. Changing drain hose
For leftward connection, bottom leftward connection and rear leftward connection’s piping, it is necessary to change the drain hose and drain cap.
How to remove the drains cap
Clip drain cap by needle-nose plier, and pull out.
How to fix the drains cap
1) Insert hexagonal wrench (4 mm) in a center head.
4 mm
Fig. 8-4-12
2) Firmly insert drains cap.
No gap
Do not apply lubricating oil (refrigerant machine oil) when inserting the drain cap. Application causes deterioration
Insert a hexagon wrench (4 mm)
and drain leakage of the plug.
Fig. 8-4-13
CAUTION
Firmly insert the drain hose and drain cap; otherwise, water may leak.
<In case of right or left piping>
Fig. 8-4-10
How to install the drain hose
Firmly insert drain hose connecting part until hitting on a heat insulator.
Heat insulator
Drain hose
Fig. 8-4-11
After scribing slits of the front panel with a knife or a making-off pin, cut them with a pair of nippers or an equivalent tool.
Slit
Fig. 8-4-14
<In case of bottom right or bottom left piping>
After scribing slits of the front panel with a knife or a making-off pin, cut them with a pair of nippers or an equivalent tool.
Slit
50
Fig. 8-4-15
FILE NO. SVM-05001
<Left-hand connection with piping>
Bend the connecting pipe so that it is laid within 43 mm above the wall surface. If the connecting pipe is laid exceeding 43 mm above the wall surface, the indoor unit may unstably be set on the wall. When bending the connecting pipe, make sure to use a spring bender so as not to crush the pipe.
Bend the connection pipe within a radius of 30 mm.
To connect the pipe after installation of the unit (figure)
(To the forefront of flare)
270 mm
170 mm
R 30 mm (Use polisin (polyethylene)
43 mm
core or the like for bending pipe.)
80
Liquid side
Gas side
Outward form of indoor unit
Use the handle of screwdriver, etc.
Fig. 8-4-16
8-4-5. Indoor unit fixing
1. Pass the pipe through the hole in the wall, and hook the indoor unit on the installation plate at the upper hooks.
2. Swing the indoor unit to right and left to confirm that it is firmly hooked up on the installation plate.
3. While pressing the indoor unit onto the wall, hook it at the lower part on the installation plate. Pull the indoor unit toward you to confirm that it is firmly hooked up on the installation plate.
1
2
Hook
Hook here
1 Installation
plate
Press
(unhook)
Fig. 8-4-17
For detaching the indoor unit from the installation plate, pull the indoor unit toward you while pushing its bottom up at the specified parts.
NOTE
If the pipe is bent incorrectly, the indoor unit may unstably be set on the wall. After passing the connecting pipe through the pipe hole, connect the connecting pipe to the auxiliary pipes and wrap the facing tape around them.
CAUTION
Bind the auxiliary pipes (two) and connecting cable with facing tape tightly. In case of leftward piping and rear-leftward piping, bind the auxiliary pipes (two) only with facing tape.
Indoor unit
Auxiliary pipes
Installation plate
Carefully arrange pipes so that any pipe does not stick out of the rear plate of the indoor unit.
Carefully connect the auxiliary pipes and connecting pipes to each other and cut off the insulating tape wound on the connecting pipe to avoid double-taping at the joint, moreover, seal the joint with the vinyl tape, etc.
Since dewing results in a machine trouble, make sure to insulate both the connecting pipes. (Use polyethylene foam as insulating material.)
When bending a pipe, carefully do it, not to crush it.
Connecting cable
PushPush
Fig. 8-4-18
51
FILE NO. SVM-05001
8-4-6. Drainage
1. Run the drain hose sloped downwards.
NOTE
Hole should be made at a slight downward slant on the outdoor side.
Do not form the Do not rise the drain hose.
50 mm or more
Do not put the drain hose end into water.
drain hose into
a wavy shape.
Do not put the drain hose end in the drainage ditch.
Fig. 8-4-19
2. Put water in the drain pan and make sure that the water is drained out of doors.
3. When connecting extension drain hose, insulate the connecting part of extension drain hose with shield pipe.
Shield pipe
Drain hose
Inside the room
Extension drain hose
Fig. 8-4-20
CAUTION
Arrange the drain pipe for proper drainage from the unit. Improper drainage can result in dew-dropping.
This air conditioner has the structure designed to drain water collected from dew, which forms on the back of the indoor unit, to the drain pan. Therefore, do not store the power cord and other parts at a height above the drain guide.
8-5. Outdoor Unit
8-5-1. Installation place
A place which provides the spaces around the outdoor unit as shown in the left diagram.
A place which can bear the weight of the outdoor unit and does not allow an increase in noise level and vibration.
A place where the operation noise and discharged air do not disturb your neighbors.
A place which is not exposed to a strong wind.
A place free of a leakage of combustible gases.
A place which does not block a passage.
When the outdoor unit is to be installed in an
elevated position, be sure to secure its feet.
An allowable length of the connecting pipe is up to
07,10
10 m (RAS-
UA) or 15 m (RAS-12, 13UA).
An allowable height level is up to 5 m (RAS-07, 10 or 6 m (
RAS-12, 13UA).
A place where the drain water does not raise any problem.
CAUTION
1. Install the outdoor unit without anything blocking the air discharging.
2. When the outdoor unit is installed in a place exposed always exposed to strong wind like a coast or on a high storey of a building, secure the normal fan operation using a duct or a wind shield.
3. In particularly windy areas, install the unit such as to avoid admission of wind.
4. Installation in the following places may result in trouble. Do not install the unit in such places.
A place full of machine oil.
A saline-place such as the coast.
A place full of sulfide gas.
A place where high-frequency waves are likely
to be generated as from audio equipment, welders, and medical equipment.
UA)
Space for pipes
Fig. 8-4-21
Wall
Drain guide
52
Strong
wind
Fig. 8-5-1
FILE NO. SVM-05001
8-5-2. Refrigerant piping connection
1. Cut the pipe with a pipe cutter.
90°
Obliquity
Roughness
Fig. 8-5-2
2. Insert a flare nut into the pipe, and flare the pipe.
Projection margin in flaring : A (Unit : mm)
A
Die
Pipe
Fig. 8-5-3
Outer dia.
of copper pipe
Rigid Imperial
A
6.35 0.5 to 1.0 1.0 to 1.5
(Unit : N·m)
Warp
Outer dia.
of copper pipe
6.35 16 to 18 (1.6 to 1.8 kgf·m)
Tightening torque
9.52 30 to 42 (3.0 to 4.2 kgf·m)
12.70 50 to 62 (5.0 to 6.2 kgf·m)
Tightening torque of flare pipe connections
The operating pressure of R410A is higher than that of R22. (Approx. 1.6 times). It is therefore necessary to firmly tighten the flare pipe connecting sections (which connect the indoor and outdoor units) up to the specified tightening torque. Incorrect connections may cause not only a gas leakage, but also damage to the refrigerant cycle.
Flare at indoor unit side
9.52 0.5 to 1.0 1.0 to 1.5
12.70 0.5 to 1.0 1.5 to 2.0
<Tightening connection>
Align the centers of the connecting pipes and tighten the flare nut as far as possible with your fingers. Then tighten the nut with a spanner and torque wrench as shown in the figure.
CAUTION
Do not apply excess torque.
Otherwise, the nut may crack depending on the
conditions.
Externally threaded side
Use a wrench to secure.
CAUTION
Flare at outdoor unit side
Fig. 8-5-4
Mark line
Fig. 8-5-5
Flare nutHalf union
Internally threaded side
Use a torque wrench to tighten.
Fig. 8-5-6
KEEP IMPORTANT 4 POINTS FOR PIPING WORK
(1) Take away dust and moisture (Inside of the
connecting pipes.) (2) Tight connection (between pipes and unit) (3) Evacuate the air in the connecting pipes using
VACUUM PUMP. (4) Check gas leak (connected points)
53
FILE NO. SVM-05001
8-5-3. Evacuating
After the piping has been connected to the indoor unit, you can perform the air purge together at once.
AIR PURGE
Evacuate the air in the connecting pipes and in the indoor unit using a vacuum pump. Do not use the refrigerant in the outdoor unit. For details, see the manual of the vacuum pump.
<Using a vacuum pump>
Be sure to use a vacuum pump with counter-flow prevention function so that inside oil of the pump does not flow backward into pipes of the air conditioner when the pump stops.
1. Connect the charge hose from the manifold valve to the service port of the gas side packed valve.
2. Connect the charge hose to the port of the vacuum pump.
3. Open fully the low pressure side handle of the gauge manifold valve.
4. Operate the vacuum pump to start evacuating. Perform ev acuating for about 15 minutes if the piping length is 20 meters. (15 minutes for 20 meters) (assuming a pump capacity of 27 liters per minute.) Then confirm that the compound pressure gauge reading is 101 kPa ( 76 cmHg).
-
-
5. Close the low pressure side valve handle of gauge manifold.
6. Open fully the valve stem of the packed valves (both sides of Gas and Liquid).
7. Remove the charging hose from the service port.
8. Securely tighten the caps on the packed valves.
<Packed valve handling precautions>
·
Open the valve stem all the way out; but do not try to open it beyond the stopper.
·
Securely tighten the valve stem cap with torque in the following table:
Gas side 50 to 62 Nám ( 12.70 mm) (5.0 to 6.2 kgfám)
Æ
Gas side 30 to 42 Nám
Æ
( 9.52 mm) (3.0 to 4.2 kgfá
m)
Liquid side 16 to 18 Nám
Æ
( 6.35 mm) (1.6 to 1.8 kgfá Service port
9 to 10 Nám (0.9 to 1.0 kgfám)
m)
Hexagonal wrench is required.
m
m
4
Fig. 8-5-8
Compound pressure gauge
-
101 kPa ( 76 cmHg)
-
Handle Lo
Charge hose
Connecting pipe
Service port (Valve core (Setting pin))
Packed valve at liquid side
Pressure gauge
Charge hose
Vacuum pump adapter for counter-flow prevention
Vacuum
pump
Packed valve at gas side
Fig. 8-5-7
Manifold valve
Handle Hi (Keep full closed)
- 54 -
Selector Switch
LED Assembly
FILE NO. SVM-05001
8-5-4. Wiring connection
1.
Remove the valve cover from the outdoor unit.
2. Connect the connecting cable to the terminal as
identified with their respective matched numbers on the terminal block of indoor and outdoor unit.
3. When connecting the connecting cable to the outdoor unit terminal, make a loop as shown in the installation diagram of indoor and outdoor unit, to prevent water coming in the outdoor unit.
Insulate the unused cords (conductors) from any
4.
water coming in the outdoor unit. Proceed them so that they do not touch any electrical or metal parts.
<Stripping length of connecting cable>
For RAS-13/10/07UAH
Terminal block
70 mm
10 mm
10 mm
Earth line
60 mm
Terminal screw
Connecting cable
Screw
Cord clamp
Fig. 8-5-9
Earth line
8-6. How to Set Remote Control Selector
Switch
When two indoor units ae installed in seperated rooms, there is no need to change the selector switch.
<Remote control selector switch>
·
When two indoor units are installed in the same room or the adjacent two rooms, they may be controlled simultaneously with a single remote control. To prevent this, set either unit and its remote control to B setting. (Both units are set to A setting before shipment.) The remote control signal is not recived when the
·
indoor unit setting is different from the remote control one.
1. Set the remote control selector switch with the indoor unit.
1) Turn the circuit breaker of the main power switch off before setting the selector switch.
2) Remove the Air inlet grille and Front panel. (Refer to page 64, 10-1)
3) Select the terminal of selector switch from [A position] to [B position].
For RAS-13/12/10/07UA
Terminal block
10 mm
60 mm
Earth line
10 mm
50 mm
Terminal screw
Connecting cable
Screw
Fig. 8-5-10
CAUTION
Wrong wiring connection may cause some electrical parts burn out.
Be sure to comply with local codes on running
the wire from indoor unit to outdoor unit (size of wire and wiring method etc.)
Every wire must be connected firmly.
Earth line
Cord clamp
Fig. 8-6-1
NOTE
Wire type: H07 RN-F or 245 IEC66 (2.0 mm2 or
more)
55
FILE NO. SVM-05001
2. Set the remote control selector switch with the
remote control
[B] is indicated on the liquid crystal display when setting remote control selector switch to B. [A] is not indicated on the display even if the selector switch is set to A.
1) Load the remote control with the batteries.
2) Press the [CH
K] button using something with sharp point. (The preset temperature on the remote control changes to [00].)
3) Press the [MODE] button while pressing the K] button, [B] is indicted at the right of the
[CH present temperature display.
To reset the switch to the [A] setting, press the
[MODE] button again while pressing the [CH
K]
button.
8-7. Others
8-7-1. Gas leak test
Valve cover
Valve stem cap connection
Service cap connection
Fig. 8-7-1
Check the flare nut connections, valve stem cap connections and service port cap connections for gas leak with a leak detector or soap water.
8-7-2. Test operation
To switch the TEST RUN (COOL) mode, press
TEMPORARY button for 10 sec. (The beeper will make a short beep.)
[MODE] button
[CHK] button
Fig. 8-6-2
3. Confirm that the indoor unit can operate with
the new setting.
TEMPORARY button
Fig. 8-7-2
8-7-3. Auto restart setting
This product is designed so that, after a power failure, it can restart automatically in the same operating mode as before the power failure.
Information
The product was shipped with Auto Restart function in the off position. Turn it on as required.
<How to set the auto restart>
Press and hold the TEMPORARY button for about 3 seconds. After 3 seconds, the electronic beeper makes three short beeps to tell you the Auto Restart has been selected.
To cancel the Auto Restart, follow the steps described in the section Auto Restart Function of the Owner’s Manual.
56
9. TROUBLESHOOTING CHART
FILE NO. SVM-05001
9-1. Troubleshooting Procedure
9-2-2. Incorrect cable connection between Indoor
and outdoor units
Follow the details of 9-2. Basic Chec k Items . If there is no trouble corresponding to 9-2, check whether or not there are faulty parts following 9-4. Self-Diagnosis by Remote Control.
9-2. Basic Check Items
9-2-1. Power supply voltage
The line voltage must be AC 220 240V. If it is not within this range, the air conditioner may not operate normally.
The indoor unit is connected to the outdoor unit with 5 cables (Heat pump model) or 3 cables (Cooling Only model). Check that the indoor and outdoor units have been properly connected with terminals assigned the same numbers. If the connectors are not properly connected, the outdoor unit will not operate normally, or OPERATION lamp and TIMER lamp will blink (5Hz).
9-2-3. Program control
The microcontroller operates as shown in Table 9-2-1 to control the air conditioner. If there are any opera­tional problems, check whether or not the problems correspond to Table 9-2-1. If they correspond to the Table, they are not problems with the air conditioner, but they are indispensable operations to control and maintain the air conditioner properly.
Table 9-2-1
No. Operation of air conditioner Descriptions
1 When the main power supply is turned on,
the OPERATION lamp on the indoor unit blinks.
2 The indoor fan motor speed does not change
in the Dry operation.
The OPERATION lamp blinks to indicate that power is turned on.
If the [ ] button is pressed, the lamp stops blinking.
The indoor fan motor speed is automatically controlled in the Dry operation.
3 The compressor is not turned off even though
the room temperature is in the range that the compressor is turned off.
4 The compressor is not turned on and off even
though the thermo control is operated in the Dry operation.
5 The PRE-DEF. lamp is indicated when the
Heating operation starts.
6 The outdoor fan motor stops in the Heating
operation.
7 The compressor is not turned on even though
the room temperature is in the range that the compressor is turned on.
8 The operation mode changes in the
Automatic operation.
9 The Fan only operation continues in the
Automatic operation.
10 The Hi-POWER operation does not work.
The compressor has a function that it is not turned off for 3 minutes after it is turned on even though the room temperature is in the range that the compressor is turned off.
In the Dry operation, the compressor is turned on and off automatically at the regular intervals, independent of the thermo control.
The PRE-DEF. lamp is indicated during the Defrosting operation or if the indoor heat exchanger temperature is low when the Heating operation starts. At this time, the indoor fan motor stops to prevent cold air from blowing in the room.
When the indoor heat exchanger temperature is high, the outdoor fan motor is stopped by the high-temperature limit control operation.
The compressor is not turned on in the restart delay timer (3-minutes timer) operation. It is also not turned on after the power supply is turned on because of this timer operation.
In Automatic operation, the room temperature is detected all time for control fan speed and the operation mode is changed every 15 minutes according to difference between the room temperature and the preset temperature.
When the room temperature is in the range (Preset temperature ± 1°C), the Fan only operation is selected.
This operation does not work when the unit is in the Dry operation or Fan only operation.
57
FILE NO. SVM-05001
9-3. Primary Judgement
9-3-1. Role of indoor unit controller
The indoor unit controller receives the operation commands from the remote control and executes them.
Temperature measurement at the air outlet of the indoor heat exchanger by the indoor temperature sensor
Temperature setting of the indoor heat exchanger by the heat exchanger sensor
Louver motor control
Indoor fan motor operation control
LED display control
Transferring of operation commands to the outdoor
unit
Table 9-3-1
Lamps Self-diagnosis
A OPERATION lamp is blinking. (1Hz)
B OPERATION lamp is blinking. (5Hz)
C OPERATION lamp is blinking. (5Hz)
D OPERATION lamp is blinking. (5Hz)
E OPERATION lamp is blinking. (5Hz)
F OPERATION and TIMER lamps are blinking.
(5Hz)
9-3-2. Failure diagnosis
The indoor unit diagnoses the operation condition and indicates the information of the self-diagnosis with the lamps on the display panel of the indoor unit.
Power failure (when the power supply is turning on)
Thermo sensor (TA) short or break
Heat exchanger sensor (TC) short or break
Indoor fan motor lock or failure
Indoor P.C. board failure
Wrong wiring of connecting cable
G OPERATION, TIMER and PRE-DEF.
(or FAN ONLY for cooling only model) lamps are blinking.
Table 9-3-2 Diagnosis by detective operation
Symptom Check Primary judgement
The remote control does not work.
The outdoor fan does not rotate.
Turn off the power supply once, then turn it on. Try to operate the remote control.
The compressor operates.
The compressor does not operate.
Cycle failure
Gas shortage or other refrigerant cycle trouble
Heat exchanger sensor open, break or short
Overload relay or thermostat trouble of compressor
The remote control still does not work.
The remote control works.
The indoor unit (and/or remote control) is/are defective.
OK.
The outdoor unit (Outdoor fan motor) is defective.
An internal part of the compressor or PCB is defective.
58
9-4. Self-Diagnosis by Remote Control
(Check Code)
(1) If the lamps are indicated as shown B to G in Table
9-3-1, exchanger the self-diagnosis by the remote control.
(2) When the remote control is set to the service
mode, the indoor controller diagnoses the operation condition and indicate the information of the self-diagnosis on the display of the remote control with the check codes. If a fault is detected, all lamps on the indoor unit will blink at 5Hz and it
will beep for 10 seconds (Pi, Pi, Pi....). The timer
lamp usually blinks (5Hz) during the self-diagnosis.
9-4-1. How to use remote control in service mode
FILE NO. SVM-05001
(1) Press [CHK] button with a tip of pencil to set the
remote control to the service mode.
“00” is indicated on the display of the remote control.
The timer lamp on the indoor unit blinks continuously. (5 times per 1 sec.)
(2) Press [TIMER 8] button.
If there is no fault with a code, the indoor unit will beep once (Pi) and the display of the remote control will change as follows:
00
01
Check the unit with all 35 check codes (00 to 22). as shown in Table 9-4-1.
Press [TIMER 9] button to change the check code backwards.
If there is a fault, the indoor unit will beep for 10 seconds (Pi, Pi, Pi...). Note the check code on the display of the remote control.
2-digits alphanumeric will be indicated on the display.
All lamps on the indoor unit will blink. (5 times per 1 sec.)
(3) Press [CLR] button. After service finish for clear
service code in memory.
“7F” is indicated on the display of the remote control.
1d
02
1E
22
Alphanumeric characters are used for the check code.
is 5. is 6. is A. is B. is C. is D.
* This illustration in only for Heat pump model.
For Cooling only model, there is not the ( ) symbol.
(4) Press [ ] button to release the service
mode.
The display of the remote control returns to as it was before service mode was engaged.
59
Block level Diagnosis function
Check Check
code
Block
Indoor P.C. board
code
Symptom Conditioner Condition
Thermo. sensor short/break.
Table 9-4-1
Continued operation.
Air
status
Indicated when detected abnormal
FILE NO. SVM-05001
Judgement and action
1.Check thermo sensor.
2.If it is OK, check P.C. board.
Cable connection/ Thermal fuse Refrigerant system
Heat exchanger sensor short/break.
Indoor fan lock, abnormality of indoor fan or thermal fuse break.
Abnormality of other indoor unit P.C. board.
1) Wrong wiring or disconnection of connective cable.
2) Terminal fuse cut off.
Continued operation.
All off
All off
All off
Indicated when detected abnormal
Indicated when detected abnormal
Indicated when detected abnormal
Indicated when detected abnormal
1.Check heat exchanger sensor.
2.If it is OK, check P.C. board.
1.Check heat thermal fuse is blow or not? (Terminal block part.)
2.If the thermal fuse is not blow, check indoor fan motor. (Refer to trouble shooting flow charts.)
Replace P.C. borad.
1.Check connective cable correct if wiring is wrong.
2.Check thermal fuse and Terminal blocks.
3.If it is OK, check P.C. board.
Other parts (including compressor)
1) Overload relay or thermostat for compressor
All off
Indicated when detected abnormal
1.If overload relay and
break.
2.If refrigerant cycle is
3. If heat exchanger
Content detected by the check codes "
" o " t " are stored in memory of the microcomputer even if the
power supply is turned off. Therefore, contents of operations in the past are all displayed.
60
themostat for compres­sor are OK, check refrigerant cycle.
OK, check P.C. board.
sensor is OK, check overload relay and themostat for compressor.
9-5. Troubleshooting Flowcharts
9-5-1. Power can not be turned on (No operation at all)
<Preliminary checks>
(1) Is the supply voltage normal? (2) Is the connection to the AC output OK.?
Heat pump Model
Shut off the power supply
from AC outlet once and
turn it on after 5 seconds.
FILE NO. SVM-05001
Operation
Check Items
Main cause
Countermeasure
Symptom
Does the thermal
(Under PF. Terminal)
Is the indication voltage
NO
(DC12V or 5V) of main
P.C. board correct?
Is the voltage
across C63 measured
DC310V ~ 340V?
YES
NO
Does the fuse
(F01) blow?
fuse blow?
NO
Does the OPERATION
lamp blink?
Does the power turn on
by pushing the [ ]
button of the remote
NO
NO
YES
Refer to the paragraph "Pre-check", or defective circuit before power P.C. board block.
control?
YES
YES
YES
YES
NO NO
(No problem)
Parts (R21, R22, SG01,
C01, DB01, C02, C63,
M01) are defective.
Wrong wiring of
AC cord or connecting
cable is defective.
Does the CN14
connector the wrong
connecting?
YES
Does the transmission
indicator of remote
control flash normally
and transmit certainly?
YES
NO
P.C. board is
defective.
Remote control is
defective.
Replace the remote
control.
Replace the
thermal fuse set.
Check connection.
Replace the main
P.C. board.
Re-wiring the cable.
Is the voltage
across C66
measured DC12V?
YES YES
* Be sure to disconnect the motor connector CN10 after shut off the power supply, or it will be a cause of damage of the motor.
Shut off the power
NO NO
supply once, and
disconnecting the motor
connector CN11*.
Check Resistance
of Pin 1 and 3
of Fan-motor
= 162Ω .
Replace Fan-motor
and P.C. board.
Replace P.C. board
61
Cooling Model
Shut off the power supply
from AC outlet once and
turn it on after 5 seconds.
FILE NO. SVM-05001
Operation
Check Items
Main cause
Countermeasure
Symptom
Does the thermal
(Under PF. Terminal)
Is the indication voltage
NO
(DC12V or 5V) of main
P.C. board correct?
Is the voltage
across C50 measured
DC12V ~ 15V?
YES
NO
Does the fuse
(F01) blow?
fuse blow?
NO
Does the OPERATION
lamp blink?
Does the power turn on
by pushing the [ ]
button of the remote
NO
NO
YES
Refer to the paragraph "Pre-check", or defective circuit before power P.C. board block.
control?
YES
YES
YES
NO NO
YES
Parts (R21, R22, SG01,
C15, C01, DB01, C50,
TT-10) are defective.
Wrong wiring of
AC cord or connecting
cable is defective.
Does the CN14
connector the wrong
connecting?
Does the transmission
indicator of remote
control flash normally
and transmit certainly?
(No problem)
YES
NO
YES
P.C. board is
defective.
Remote control is
defective.
Replace the remote
control.
Replace the
thermal fuse set.
Check connection.
Replace the main
P.C. board.
Re-wiring the cable.
Is the secondary
voltage of
transformer (TT-10)
measured DC10~16V?
YES YES
* Be sure to disconnect the motor connector CN10 after shut off the power supply, or it will be a cause of damage of the motor.
Shut off the power
supply once, and turn
NO NO
it on again after
disconnecting the motor
connector CN10*.
Is the secondary
voltage of
transformer
measured DC10~16V?
transformer (TT-10) for power supply is
defective.
Replace the main
Motor is defective.
62
P.C. board.
9-5-2. Power can not be turned on after replacing indoor P.C. board
<Checking Procedure>
Connect the AC
Power supply
FILE NO. SVM-05001
Does the OPERATION
lamp blink?
RAS-13UKHP-E4
YES
Indoor Terminal Block
NO NO
Is it wired as shown
in Figure below?
YES
Brown
L
Blue
N
Green & Yellow
CN31
Return the wiring of the
power relay is returned to
the normal procedure.
To the paragraph of
"No Power turns on".
RY01
White
Black
1
2
Red
3
Blue
4
Green & yellow
RAS-10UKHP-E4, RAS-07UKHP-E4
Brown
L
Blue
N
Green & Yellow
Indoor Terminal Block
White
Black
Blue
Red
4
1
2
3
Green & yellow
T02
PC Board
RY01
CN31
T02
PC Board
63
RAS-13UKP-E4, RAS-10UKP-E4, RAS-07UKP-E4
Black
White
Green / Yellow
2
1
Indooe Terminal Block
Brown
Blue
Green / Yellow
L
N
FILE NO. SVM-05001
RY01
CN31
PC Board
RAS-13UKPX4, RAS-12UKPX4, RAS-10UKPX4, RAS-07UKPX4
Black
Green / Yellow
White
64
9-5-3. Outdoor unit does not operate
Shut off the power supply
from AC outlet once and turn
it on after 5 seconds.
FILE NO. SVM-05001
Does the OPERATION lamp blink?
YES
Does the power turn on by pushing
the [ ] button of the remote control?
YES
Is AC 220-240V supplied between
terminal block 1 -
Is cable connection between indoor
and outdoor units correct?
Check items as following procedure
in 9-5-4, 9-5-5, 9-5-6
YES
YES
2
?
NO
NO
NO
NO
See "Power can not be turned on".
See "Power can not be turned on".
Relays (RY01) or (IC31 : Cooling only model,
Q16 : Heat pump only model)or IC30 is failure.
Correct cabling between indoor
and outdoor units.
Replace the
P.C. board.
65
9-5-4. Only compressor does not operate
Shut off the power supply
from AC outlet once and turn
it on after 5 seconds.
FILE NO. SVM-05001
Does the OPERATION lamp blink?
YES
Does the power turn on by
pushing the [ ] button
of the remote control?
YES
Is the voltage across the indoor terminal
( 1 - 2 ) AC 220-240V?
YES
Is cable connection between indoor
and outdoor units correct?
YES
Is the voltage across the outdoor terminal
( 1 - 2 ) AC 220-240V?
YES
Are all the cords for compressor normal?
YES
NO
NO
NO
NO
NO
NO
See "Power can not be turned on".
See "Power can not be turned on".
Relays (RY01) or (IC31 : Cooling only model,
Q16 : Heat pump only model) or IC30 is failure.
Correct cabling between indoor
and outdoor units.
Cables between indoor and outdoor units are defective.
Re-wire or replace the defective cords.
Replace the
P.C. board.
Is the compressor motor winding normal?
(Check the winding resistor.)
YES
Is the capacitor for compressor normal.
YES
Is the overload relay normal?
YES
Does the compressor start?
YES
Compressor starts but
it stops after a while?
YES
Is the gas quantity normal?
(Check the pressure)
YES
Compressor is defective
NO
NO
NO
NO
NO
Compressor is defective.
Capacitor is defective.
Overload relay is defective.
Compressor is defective.
Gas shortage (Gas leakage)
66
9-5-5. Only outdoor fan does not operate
Shut off the power supply
from AC outlet once and
turn it on after 5 seconds.
FILE NO. SVM-05001
Does the OPERATION lamp blink?
YES
Does the power turn on by
pushing the [ ] button
of the remote control?
YES
Is the voltage across the indoor terminal
( 2 - 4 : Heat pump model, 1 - 2 :
Cooling only model) AC 220-240V?
YES
Is cable connection between indoor
and outdoor units correct?
YES
Is the voltage across the terminal
( 2 - 4 : Heat pump model, 1 - 2 :
Cooling only model) AC 220-240V?
YES
Are all the cords for outdoor
fan motor normal?
YES
NO
NO
NO
NO
NO
NO
See "Power can not be turned on".
See "Power can not be turned on".
Relays (RY03) or Q25
or IC30 is failure.
Correct cabling between indoor
and outdoor units.
Cables between indoor
and outdoor units are defective.
Correct the wire or
replace the defective cords.
Replace the
P.C. board.
Is the outdoor fan motor winding normal?
(Check the winding resistance)
YES
Is the capacitor for compressor normal?
YES
Outdoor fan motor is defective.
NO
NO
Outdoor fan motor is defective.
Capacitor for outdoor
fan motor is defective.
67
9-5-6. Only 4-Way valve does not operate (During heating operation)
Shut off the power supply
from AC outlet once and
turn it on after 5 seconds.
FILE NO. SVM-05001
Does the OPERATION lamp blink?
YES
Does the power turn on by
pushing the [ ] button
of the remote control?
YES
Is the voltage across the indoor terminal
( 2 - 3 ) 220-240V?
YES
Is cable connection between indoor
and outdoor units correct?
YES
Is the voltage across the outdoor terminal
( 2 - 3 ) 220-240V?
YES
Is the wiring of solenoid coil for
4-way valve normal?
YES
NO
NO
NO
NO
NO
NO
See "Power can not be turned on".
See "Power can not be turned on".
Relays (RY04) or Q24, R314
or IC30 is failure.
Correct cabling between indoor
and outdoor units.
Cables between indoor
and outddor units are defective.
Solenoid coil is defective.
Replace the P.C.
board.
4-way valve is defective.
68
9-5-7. Only the indoor fan does not operate
<Check procedure>
Heat Pump Model
Shut off the
power supply once.
Turn the power supply.
FILE NO. SVM-05001
Does the fan stop in
no operating status?
YES
Start the operation
with low fan setting
in cool operation.
Does the fan rotate?
YES
Change the setting of
cooling to high fan.
Does the fan speed
become higher?
YES
NO
NO
NO
Control P.C. board is defective.
Does AC 120V
or higher voltage apply
to between red and black
lead of fan motor?
YES
Shut off the power supply.
Does the cross flow
fan rotate normally?
YES
Turn on the power supply.
Operation
stops
NO
NO
Replace the P.C. board.
Does connecting
terminal, connecting
cable or power supply
cord completely?
Does not found the short
wire about connecting
cable and power cord?
YES
Repair the
bearing of
the fan.
Motor control circuit failure
(IC30, IC03, D38, R25, R26, Q17)
or 12V power circuit failure.
Replace the P.C. board.
of incompleted connecting.
NO
Thermal fuse operated
due to prevent
temperature rising cause
Normal
Is the rotation signal (DC+5V-0V)
output between 2 (gray lead wire)
and 3 (brown lead wire) of the motor
connector (CN11) when rotating
the cross flow fan by hand in no
operating status?
(1 pulse/one turn)
YES
Replace the control
P.C. board.
69
NO
Replace the fan motor
Replace connecting
the cable (or power cord),
thermal fuse and
terminal block.
Cooling Model
Shut off the
power supply once.
Turn the power supply.
FILE NO. SVM-05001
Does the fan stop in
no operating status?
YES
Start the operation
with low fan setting
in cool operation.
Does the fan rotate?
YES
Change the setting of
cooling to hight fan.
Does the fan speed
become higher?
YES
NO
NO
NO
Control P.C. board is defective.
Does AC 120V
or higher voltage apply
to between red and black
lead of fan motor?
YES
Shut off the power supply.
Does the cross flow
fan rotate normally?
YES
Turn on the power supply.
Operation
stops
NO
NO
Replace the P.C. board.
Does connecting
terminal, connecting
cable or power supply
cord completely?
Does not found the short
wire about connecting
cable and power cord?
YES
Repair the
bearing of
the fan.
Motor control circuit failure
(IC30, IC03, IC31, TT-10) or 12V
power circuit failire.
Replace the P.C. board.
temperature rising cause
of incompleted connecting.
NO
Thermal fuse operated
due to prevent
Normal
Is the rotation signal (DC+5V-0V)
output between 2 (gray lead wire)
and 3 (brown lead wire) of the motor
connector (CN11) when rotating
the cross flow fan by hand in no
operating status?
(1 pulse/one turn)
YES
Replace the control
P.C. board.
70
NO
Replace the fan motor
Replace connecting
the cable (or power cord),
thermal fuse and
terminal block.
FILE NO. SVM-05001
9-6. Troubleshooting for Remote Control (Including the Indoor P.C. Board)
There is no been from
Push the [ ] button.
the indoor unit. The operation lamp of the air conditioner main unit does not light.
Is there direct
sunlight on the
receptor of the air
conditioner?
YES
NO
Is there any
thyristor
fluorescent light
near by?
YES
NO
YES
NO NO
Is operation possible
when setting the
temporary switch of the
air conditioner main unit
to "TEST RUN" or
"TEMPORARY AUTO"?
Does the transmission
indicator blink?
Is operation
possible when the
transmitter is moved
nearer to the infrared
signal receiver of the
air conditioner?
YES
Battery life
NO
Reset the remote control
by use the tip pencil push
in the RESET hole
Push the [ ]
button
Dose the
transmission
indicator light?
YES
NO
Avoid direct
sunlight.
Keep the air
conditioner away
from thyristor
fluorescent light.
YES
Can any signal tone
be heard in a trasistor
radio when transmitting
within 5 cm distance
from the radio?
YES
P.C. board is failure.
Replace
P.C. board
NO
Replace the
batteries
NO
Normal
Is there any
beep and
operation?
YES
Remote control
is failure.
Replace remote
control.
71
FILE NO. SVM-05001
9-6-1 How to check the P.C. board (1) Operating precautions
1) When removing the front panel or the P.C. board, be sure to shut off the power supply.
2) When removing the P.C. board, hold the edge of the P.C. board and do not apply force to the parts.
3) When connecting or disconnecting the connec­tors on the P.C. board, hold the Whole housing. Do not pull at the lead wire.
(2) Inspection procedres
1) When a P.C. board is judged to be defective, check for disconnection, burning, or discolora­tion of the copper foil pattern or this P.C. board.
2) The P.C. board consists of the following 2 parts
a. Main P.C. board part:
power relay, indoor fan motor drive circuit and control circuit, C.P.U. and peripheral circuits, buzzer drive circuit and buzzer.
b. Infrared rays receive and indication parts:
Infrared rays receiver unit and LED.
72
(3) Checking procedure
Heat Pump Model
FILE NO. SVM-05001
Table 9-6-1
No.
1
Shut off the power supply and remove the P.C. board assembly from the electronic parts base. Remove the connecting cable from the terminal block.
2
Remove the connector for the motor, and turn the power on. If the OPERATION lamp blinks (0.5 sec. : ON, 0.5 sec. : OFF) when the power turning on, the checking points described as 1-4 of right column are not necessary to perform.
3
Make the operation status by
pushing once the [ ]
button, except the status of [FAN ONLY], [ON TIMER].
4
Start the operation with the system which the time of the restart delay timer is shortened.
Procedure
Check Point (Symptom) Causes
1.Is the fuse blown?
Voltage check
1.Between
(AC 220240V)
2.Between + and of C63
(DC 310 ~ 340V)
3. Between
4.Between
Voltage check
1.Voltage of relay coil. (DC 12V)
Between pin 2 of RY01 and GND
2.Between No. 1 and 2 of connect­ing cable terminal block.
(AC 220240V)
1.All indicators light for 3 sec..
2. Indicators do not indicate normally after approximate 3 sec..
TP1 and
12V and GND
5V
N
and GND
1.•Application of shock voltage.
Overload by short-circuit of the parts.
1.•AC power cord is defective.
Poor contact of the terminal plate.
Miss wiring of the power relay.
2.Capacitor (C01, C02) is defective.
Line filter (L01) is defective.
Resistor (R319) is defective.
Diode (DB01) is defective.
3. M01, DB01, R319, C63 are
defective.
4.IC04 are defective.
defective relay driver.
1.
2.Poor contact of relay.
Defective indicator, or poor
}
housing assembly.
(Q16)
(CN14)
5
Make the operation status by
pressing once the [ ]
button.
1.The time of the restart delay timer is shortened.
2.Cool operation
3.Air volume [AUTO]
4. Make the setting temperature lower enough than room temperature.
5.Continuous operation.
6
The status of No. 5 is continued, and make the following condition.
1.Heat operation
2.Make the setting temperature higher enough than room temperature.
7
Turn the power on after connecting the motor connector. Start the operation with the following condition.
1.Operation [Cooling]
2.Airflow [High fan]
3.Continuous operation
1.Compressor does not operate.
2.OPERATION lamp blinks.
1.Compressor does not operate.
2.OPERATION lamp blinks.
1.Motor does not rotate. (The key operation is accepted.)
2.The Motor rotates, but it vibrates too much.
1. The temperature of the indoor heat exchanger is abnomally lower.
2. Poor contact of the heat exchanger sensor. (The connector is disconnected.) (CN01)
3.Heat exchanger sensor, main P.C. board are defective. (Refer to Table 9-6-2 for the judgment of defective resistance values.)
4.Main P.C. board is defective.
1.The temperature of the heat exchanger is abnormally high.
2.The heat exchanger sensor connector has short-circuit. (CN01)
3.The heat exchanger sensor is defective. (Refer to Table 9-6-2 for the judgment of defective resistance values.)
4.P.C. board is defective.
1.Poor contact of the motor connector.
2.P.C. board is defective.
73
Cooling Model
FILE NO. SVM-05001
Table 9-6-1
No.
1
Shut off the power supply and remove the P.C. board assembly from the electronic parts base. Remove the connecting cable from the terminal block.
2
Remove the connector for the motor, and turn the power on. If the OPERATION lamp blinks (0.5 sec. : ON, 0.5 sec. : OFF) when the power turning on, the checking points described as 1-4 of right column are not necessary to perform.
3
Make the operation status by
pushing once the [ ]
button, except the status of [FAN ONLY], [ON TIMER].
4
Start the operation with the system which the time of the restart delay timer is shortened.
Procedure
Check Point (Symptom) Causes
1.Is the fuse blown?
Voltage check
1.Between 3 of RY01 and CN31 (AC 220~240V)
2.Between + and of C50 (DC 12 ~ 16V)
3.Between
4.Between
Voltage check
1.Voltage of relay coil. (DC 12V) Between pin 10 of IC31 and GND Between pin 11 of IC31 and GND
2.Between No. 1 and 2 of connecting cable terminal block.
(AC 220~240V)
1.All indicators light for 3 sec..
2. Indicators do not indicate normally after approximate 3 sec..
12V and GND
5V
and GND
1.Application of shock voltage.
Overload by short-circuit of the
parts.
1.A C power cord is defective.
Poor contact of the terminal plate.
Miss wiring of the power relay.
2.Capacitor (C01, C15) is defective.
Line filter (L01) is defective.
Diode (DB01) is def
3.
IC51 are detective. IC61 are defective.
4.
1.Breaking wire of the relay coil, defective relay driver. (IC31)
2.Poor contact of relay.
Defective indicator, or poor
}
housing assembly. (CN14)
ective.
5
Make the operation status by
pressing once the [ ]
button.
1.The time of the restart delay timer is shortened.
2.Cool operation
3.Air volume [AUTO]
4. Make the setting temperature lower enough than room temperature.
5.Continuous operation.
Turn the power on after connecting
6
the motor connector. Start the operation with the following condition.
1.Operation [Cooling]
2.Airflow [High fan]
3.Continuous operation
1.Compressor does not operate.
2.OPERATION lamp blinks.
1.Motor does not rotate. (The key operation is accepted.)
2.The Motor rotates, but it vibrates too much.
1. The temperature of the indoor heat exchanger is abnormally lower.
2. Poor contact of the heat exchanger sensor. (The connector is disconnected.) (CN01)
3.Heat exchanger sensor, main P.C. board are defective. (Refer to Table 9-6-2 for the judgment of defective resistance values.)
4.Main P.C. board is defective.
1.Poor contact of the motor connector.
2.P.C. board is defective.
74
FILE NO. SVM-05001
Table 9-6-3 Approximate resistance value of thermo sensor
Temperature 0°C 10°C 20°C 25°C 30°C
Resistance value 33.8 20.35 12.59 10.00 7.99
9-6-3. How to shorten time of restart delay timer
1 Press [CLR] button while pressing [CHK] button
with a tip of a pencil.
2 Then press [ ] button to transmit the
signal to the indoor unit.
(kΩ)
2
9-6-4. How to set/cancel the self cleaning function
The self cleaning function is set from a factory. To cancel this function, should keep press the
temporary switch for 20 seconds till can hear the long combination sound and repeat the same
procedure when need to set.
1
75
FILE NO. SVM-05001
10. PART REPLACEMENT
10-1. Indoor Unit
No. Part name Procedures Remarks
1 Front panel
2 Electrical part
How to remove the front panel
1) Stop the operation of the air conditioner and turn off its main power supply.
2) Pull the air inlet grille toward you to open it and remove the air inlet grille. Then remove the 4 screws fixing the front panel.
3) First open the horizontal louver, and then remove the front panel from the back body by pulling it toward you.
How to mount the front panel
Push the front panel back in and make sure all hooks are locked.
How to remove the electrical part.
1) Remove the front panel with procedure 1 .
2) Remove the screw holding the electrical part cover.
3) Disconnect the 2 connectors (3P) for the fan
motor and the connector (5P) for the louver motor from the P.C. board assembly.
4) Pull out the TC sensor from the sensor
holder.
5) Remove the screw for the ground connection,
remove the 2 screws for the electrical part box and remove the screw from the LED unit. Then remove the LED unit and the electrical part box from the main unit.
How to mount the electrical part.
1) To put back the electrical part box, lock it to the upper hook of the back body.
2)
Tighten the screws on the electrical part box.
3) Connect the 3 connectors and arrange the wiring same as original condition and then tighten the screw from the LED unit to the back body.
4) Attach the TC sensor to the holder.
5) Tighten the screw for the ground connection.
6) Assemble the drain guide (the TC sensor wire should be covered by the drain guide).
7) Tighten the screw on the electrical part cover.
2
6 Screw
2
2
2 4-Screws
3
2 Screws
5 TC Sensor
4
3-Connectors
6 Screw
3 Horizontal
louver
1) Remove the front panel and the electrical part following procedure 2.
2) Remove the center shaft of the horizontal louver from the back body.
3) Remove the left shaft from the back body.
4) Remove the horizontal louver from the back body.
76 −
3 Left shaft
2 Center shaft
FILE NO. SVM-05001
No. Part name Procedures Remarks
4 Heat exchanger
5 Cross flow fan
1) Remove the front panel, electrical part and the horizontal louver following procedure 3.
2) Remove the pipe holder at the rear side of main unit.
3) Remove the 2 screws on the heat exchanger at the base bearing.
4) Remove the 2 screws on the heat exchanger at the 2 fixed plates (upper and lower) from the back body, and then pull out the upper side of the heat exchanger slowly.
1) Remove the front panel, electrical part, horizontal louver and the heat exchanger following procedure 4.
2) Remove the 2 screws on the band motor (L) and remove the 2 screws on the band motor (R) and then remove the cross flow fan.
3) Loosen the set screw of the cross flow fan then separate the fan and the fan motor.
Notice To assemble cross flow fan and fan motor to the unit, please turn the fan motor unit the center of its terminal meets the lowest point of band motor (R) (point A). Fix the cross flow fan with the set screw at the position where the gap between the back body and the right surface of the cross flow fan is 6 mm.
2 Pipe holder
3
2-Screws
4
2-Screws
2
2-Screws
(R)
2 2-Screws (L)
6 mm
6 Set screw
Middle of the fan motor terminal
6 Base bearing
1) Remove the front panel, electrical part, horizontal louver, heat exchanger and the cross flow fan following procedure 5.
2) Remove the 2 screws fixing the base bearing.
3) Remove the bearing from the base bearing. If the housing protrudes from the base bearing, put the housing in position and attach the bearing to the base bearing.
77
2
2-Screws
FILE NO. SVM-05001
10-2. Outdoor Unit
No. Part name Procedures Remarks
1 Common
procedure
1) Stop the operation of air-conditioner, and disconnect the power cord from the AC supply.
2) Remove packed valve cover and Electric parts cover. (3-Screws 4 x 10L)
3) Remove the cord clamp (2-Screws 4 x 16L) and disconnect the connecting cable. Remove the upper cabinet (4-Screws 4 x 10L)
4) Pulling out upword.
5) Remove the front cabinet. (3-Screws
4 x 10L) Pull the front right portion toward you, and remove it pulling out upward.
Cord clamp
2-Screws Ø4 x 16L
Electric parts cover
3-Screws Ø4 x10L
Packed valve cover
Upper cabinet
78
Front cabinet
FILE NO. SVM-05001
No. Part name Procedures Remarks
2 Capacitor for
compressor
3
Capacitor for fan motor
1) Perform the common procedure
2) Remove the fixing screw and the capacit band.
(1-Screw 4 x 8L for 10k, 13k)
(1-Screw 4 x 10L for 07k)
3) Disconnect the lead wires.
1) Perform the common procedure
2) Remove the fixing screw (1-Screw 4 x 10L)
3) Disconnect the lead wires.
1
.
or
1
.
Screws 4 x 8L
Capacitor for fan motor
RAS-10K, 12K, 13K
Capacitor band
Screws 4 x 10L
Capacitor
for compressor
Screws Ø4 x10L
Capacitor for
Compressor
Capacitor band
Capacitor for
fan motor
Screws 4 x10L
RAS-07K
79
11. EXPLODED VIEWS AND PARTS LIST
11-1. Indoor Unit (E-Parts Assy)
(For Heat pump model)
FILE NO. SVM-05001
Location Part Location Part
No. No. No. No.
401 43T60001 TERMINAL 406 43T60077 FUSE, TEMPERATURE, 7C
402 43T60002 TERMINAL BLOCK; 3P 410 43T62003 CORD CLAMP 403 43T69004 SENSOR;HEAT EXCHANGER 411 43T69430 PC BOARD (For RAS-07UKHP-E4) 404 43T69005 SENSOR;THERMOSTAT 411 43T69431 PC BOARD (For RAS-10UKHP-E4) 405 43T69079 PC BOARD ASSY;WRS-LED 411 43T69432 PC BOARD (For RAS-13UKHP-E4)
Description Description
- 80 -
11-2. Indoor Unit (E-Parts Assy)
(For Cooling model)
FILE NO. SVM-05001
Location Part Location Part
No. No. No. No.
402 43T60002 TERMINAL BLOCK; 3P 410 43T62003 CORD CLAMP 403 43T69371 TC SENSOR 411 43T69365 PC BOARD (For RAS-07UKP-E4/UKPX4) 404 43T69005 SENSOR;THERMOSTAT 411 43T69366 PC BOARD (For RAS-10UKP-E4/UKPX4)
405 43T69079 PC BOARD ASSY;WRS-LED 411 43T69367 PC BOARD (For RAS-13UKP-E4/UKPX4, 406 43T60077 FUSE, TEMPERATURE, 73°C (For UKP-E4) 406 43T69364 FUSE,TEMPERATURE (For UKPX4)
Description Description
RAS-12UKPX4)
412 43T69361 TRANSFORMER(TT-10)
81
11-3. Indoor Unit (RAS-07,10,13UKHP-E4, UKP-E4)
FILE NO. SVM-05001
Location Part Location Part
No. No. No. No.
201 43T00391 FRONT PANEL ASSY 215 43T19302 HOLDER SENSOR 202 43T09326 INLET GRILLE ASSY 216 43T49302 PLATE OF EVA SEAL 203 43T03302 BACK BODY ASSY 217 43T49006 HOLDER FOR PLATE 204 43T80301 AIR FILTER 219 43T22002 ASM-M-BEARING 205 43T09328 HORIZONTAL LOUVER 220 43T39301 BASE; BEARING 206 43T08392 LED PANEL ASSY 221 43T20302 FAN; CROSS FLOW
(For RAS-07,10,13UKHP-E4) 222 43T39302 BAND MOTOR-L
206 43T08393 LED PANEL ASSY 223 43T21338 MOTOR FAN (SKF-220-20-4A-1)
(For RAS-07,10,13UKP-E4) 224 43T39303 BAND MOTOR-R 207 43T70002 DRAIN-HOSE 225 43T82301 PLATE; INSTALLATION 208 43T79301 CAP-DRAIN 226 43T69421 WIRELESS-REMOCO (WH-H01EE) 209 43T21321 MOTOR; STEPPING (For RAS-01,10,13UKHP-E4) 210 43T44350 REFRIGERATION CYCLE ASSY 226 43T69422 WIRELESS-REMOCO (WC-H01EE)
(For RAS-07UKHP-E4, UKP-E4) (For RAS-01,10,13UKP-E4) 210 43T44352 REFRIGERATION CYCLE ASSY 227 43T83003 HOLDER; REMOTE CONTROLLER
(For RAS-13UKHP-E4/ UKP-E4) 228 43T85468 OWNER'S MANUAL 210 43T44355 REFRIGERATION CYCLE ASSY 228 43T85469 OWNER'S MANUAL
(For RAS-10UKHP-E4, UKP-E4) (For RAS-07,10,13UKHP-E4) 211 43T47006 PIPE; DELIVERY 228 43T85470 OWNER'S MANUAL 212 43T47005 PIPE; SUCTION 228 43T85471 OWNER'S MANUAL
(For RAS-07,10UKHP-E4, UKP-E4) (For RAS-07,10,13UKHP-E4) 212 43T47016 PIPE; SUCTION 228 43T85473 OWNER'S MANUAL
(For RAS-13UKHP-E4, UKP-E4) (For RAS-07,10,13UKHP-E4) 213 43T49009 SPRING 229 43T62302 TERMINAL COVER 214 43T11301 PIPE SHIELD 231 43T60317 CORD MOTOR LOUVER
(For RAS-07,10UKHP-E4, UKP-E4) 233 43T07303 HOLDER PIPE 214 43T11302 PIPE SHIELD 234 43T01304 MARK
(For RAS-13UKHP-E4, UKP-E4)
Description Description
- 82 -
11-4. Indoor Unit (RAS-07,10,12,13UKPX4)
FILE NO. SVM-05001
Location Part Location Part
No. No. No. No.
201 43T00391 FRONT PANEL ASSY 214 43T11302 PIPE SHIELD 202 43T09326 INLET GRILLE ASSY (For RAS-12,13UKPX4) 203 43T03304 BACK BODY ASSY 215 43T19302 HOLDER SENSOR
(For RAS-07,10,12,13UKPX4) 216 43T49302 PLATE OF EVA SEAL 204 43T80301 AIR FILTER 217 43T49006 HOLDER FOR PLATE 205 43T09328 HORIZONTAL LOUVER 219 43T22002 ASM-M-BEARING 206 43T08393 LED PANEL ASSY 220 43T39301 BASE; BEARING
(For RAS-07,10,12,13UKPX4) 221 43T20302 FAN; CROSS FLOW 207 43T70002 DRAIN-HOSE 222 43T39302 BAND MOTOR-L 208 43T79301 CAP-DRAIN 223 43T21338 MOTOR FAN (SKF-220-20-4A-1) 209 43T21321 MOTOR; STEPPING 224 43T39303 BAND MOTOR-R 210 43T44350 REFRIGERATION CYCLE ASSY 225 43T82301 PLATE; INSTALLATION
(For RAS-07UKPX4) 226 43T69422 WIRELESS-REMOCO (WC-H01EE) 210 43T44352 REFRIGERATION CYCLE ASSY (For RAS-07,10,12,13UKPX4)
(For RAS-12,13UKPX4) 227 43T83003 HOLDER; REMOTE CONTROLLER
RAS-12UKPX4) 228 43T85468 OWNER'S MANUAL 210 43T44355 REFRIGERATION CYCLE ASSY 228 43T85472 OWNER'S MANUAL
(For RAS-10UKPX4) (For RAS-07,10,13UKPX4) 211 43T47006 PIPE; DELIVERY 228 43T85473 OWNER'S MANUAL 212 43T47005 PIPE; SUCTION (For RAS-07,10,12,13UKPX4)
(For RAS-07,10UKPX4) 229 43T62302 TERMINAL COVER 212 43T47016 PIPE; SUCTION 230 43T60342 POWER CORD
(For RAS-12,13UKPX4) (For RAS-07,10,12,13UKPX4) 213 43T49009 SPRING 231 43T60317 CORD MOTOR LOUVER 214 43T11301 PIPE SHIELD 233 43T07303 HOLDER PIPE
(For RAS-07,10UKPX4) 234 43T01304 MARK
Description Description
- 83 -
11-5. Outdoor Unit (RAS-13UAH-E4)
FILE NO. SVM-05001-1
Location Part Location Part
No. No. No. No.
01 43T00368 FRONT CABINET ASSEMBLY 15 43T63303 FIXING PLATE VALVE 02 43T03306 BACK CABINET ASSEMBLY 16 43T47011 CAPILLARY TUBE; 1.5DIA
03 43T03327 BASE 17 43T41348 COMPRESSOR (PH225X2C-4FT)
04 43T00396 UPPER CABINET ASSEMBLY 18 43T47324 BOLT COMPRESSOR (M6) 05 43T09318 GUARD FAN 19 43T49008 CUSHION,RUBBER 06 43T62311 ELECTRIC PART COVER 20 43T52310 PACKED VALVE COVER ASSEMBLY 07 43T20307 FAN PROPELLER 21 43T55304 MF CAPACITOR (35uF 370V) 08 43T21308 MOTOR,FAN 22 43T55314 CAPACITOR,PLASTIC FILM 09 43T47001 NUT FLANGE 23 43T60323 TERMINAL-4P 10 43T43342 CONDENSER ASSEMBLY 24 43T46319 4-WAY VALVE 11 43T46311 VALVE;PACKED 6.35 DIA 25 43T46310 COIL; V-4WAY; AC220-240V 50Hz 12 43T46019 VALVE,PACKED 12.7 DIA 26 43T79305 DRAIN NIPPLE 13 43T47331 BONNET, 6.35 DIA 29 43T47308 CAPILLARY TUBE; 1.0 DIA 14 43T47333 BONNET, 12.70 DIA
Description Description
84
11-6. Outdoor Unit (RAS-10UAH-E4)
FILE NO. SVM-05001-1
Location Part Location Part
No. No. No. No.
01 43T00368 FRONT CABINET ASSEMBLY 15 43T63303 FIXING PLATE VALVE 02 43T03308 BACK CABINET ASSEMBLY 16 43T47011 CAPILLARY TUBE; 1.5DIA
03 43T03329 BASE 17 43T41366 COMPRESSOR (PH180X1C-4DZDN3)
04 43T00395 UPPER CABINET ASSEMBLY 18 43T47325 BOLT COMPRESSOR (M6) 05 43T09318 GUARD FAN 19 43T49001 CUSHION,RUBBER 06 43T62311 ELECTRIC PART COVER 20 43T52310 PACKED VALVE COVER ASSEMBLY 07 43T20307 FAN PROPELLER 21 43T55305 CAPACITOR,PLASTIC FILM 08 43T21341 MOTOR;FAN 22 43T55314 CAPACITOR,PLASTIC FILM 09 43T47001 NUT FLANGE 23 43T60323 TERMINAL-4P 10 43T43345 CONDENSER ASSEMBLY 24 43T46321 4 WAY VALVE 11 43T46311 VALVE;PACKED 6.35 DIA 25 43T49307 SOLINOID COIL 12 43T00347 VALVE;PACKED 9.52 DIA 26 43T79305 DRAIN NIPPLE 13 43T47331 BONNET, 6.35 DIA 27 43054403 RELAY; OVERLOAD 14 43T47332 BONNET, 9.52 DIA
Description Description
- 85 -
11-7. Outdoor Unit (RAS-13UA-E4)
FILE NO. SVM-05001-1
Location Part Location Part
No. No. No. No.
01 43T00368 FRONT CABINET ASSEMBLY 13 43T47333 BONNET, 12.70 DIA 02 43T03306 BACK CABINET ASSEMBLY 14 43T63303 FIXING PLATE VALVE
03 43T03327 BASE 15 43T47014 CAPILLARY TUBE; 1.7DIA
04 43T09318 GUARD FAN 16 43T41348 COMPRESSOR (HP225X2C-4FT) 05 43T62311 ELECTRIC PART COVER 17 43T47324 BOLT COMPRESSOR (M6) 06 43T20307 FAN PROPELLER 18 43T49008 CUSHION,RUBBER 07 43T21323 MOTOR;FAN 19 43T52310 PACKED VALVE COVER ASSEMBLY 08 43T47001 NUT FLANGE 20 43T00396 UPPER CABINET ASSEMBLY 09 43T41351 CONDENSER ASSEMBLY 21 43T55304 MF CAPACITOR 10 43T46311 VALVE;PACKED 6.35 DIA 22 43T55314 CAPACITOR,PLASTIC FILM 11 43T46019 VALVE,PACKED 12.7 DIA 23 43T60322 TERMINAL-2P 12 43T47331 BONNET, 6.35 DIA
Description Description
86
11-8. Outdoor Unit (RAS-10UA-E4)
FILE NO. SVM-05001-1
Location Part Location Part
No. No. No. No.
01 43T00368 FRONT CABINET ASSEMBLY 13 43T47332 BONNET, 9.52 DIA 02 43T03308 BACK CABINET ASSEMBLY 14 43T63303 FIXING PLATE VALVE
03 43T03329 BASE 15 43T47011 CAPILLARY TUBE; 1.5DIA
04 43T09318 GUARD FAN 16 43T41316 COMPRESSOR 05 43T62311 ELECTRIC PART COVER 17 43T47325 BOLT COMPRESSOR (M6) 06 43T20307 FAN PROPELLER 18 43T49001 CUSHION,RUBBER 07 43T21341 MOTOR;FAN 19 43T52310 PACKED VALVE COVER ASSEMBLY 08 43T47001 NUT FLANGE 20 43T00395 UPPER CABINET ASSEMBLY 09 43T41352 CONDENSER ASSEMBLY 21 43T55305 CAPACITOR,PLASTIC FILM 10 43T46311 VALVE;PACKED 6.35 DIA 22 43T55314 CAPACITOR,PLASTIC FILM 11 43T00347 VALVE;PACKED 9.52 DIA 23 43T60322 TERMINAL-2P 12 43T47331 BONNET, 6.35 DIA 24 43T54303 RELAY;OVERLOAD
Description Description
87
11-9. Outdoor Unit (RAS-13UAX4, RAS-12UAX4)
FILE NO. SVM-05001-1
Location Part Location Part
No. No. No. No.
01 43T00368 FRONT CABINET ASSEMBLY 13 43T47333 BONNET, 12.70 DIA 02 43T03306 BACK CABINET ASSEMBLY 14 43T63303 FIXING PLATE VALVE
03 43T03327 BASE 15 43T47014 CAPILLARY TUBE; 1.7DIA
04 43T09318 GUARD FAN 16 43T41348 COMPRESSOR (PH225X2C-4FT) 05 43T62311 ELECTRIC PART COVER 17 43T47324 BOLT COMPRESSOR (M6) 06 43T20307 FAN PROPELLER 18 43T49008 CUSHION,RUBBER 07 43T21323 MOTOR;FAN 19 43T52310 PACKED VALVE COVER ASSEMBLY 08 43T47001 NUT FLANGE 20 43T00396 UPPER CABINET ASSEMBLY 09 43T41351 CONDENSER ASSEMBLY 21 43T55304 MF CAPACITOR 10 43T46311 VALVE;PACKED 6.35 DIA 22 43T55314 CAPACITOR,PLASTIC FILM 11 43T46019 VALVE,PACKED 12.7 DIA 23 43T60322 TERMINAL-2P 12 43T47331 BONNET, 6.35 DIA
Description Description
88
11-10. Outdoor Unit (RAS-10UAX4)
FILE NO. SVM-05001-1
Location Part Location Part
No. No. No. No.
01 43T00368 FRONT CABINET ASSEMBLY 13 43T47332 BONNET, 9.52 DIA 02 43T03308 BACK CABINET ASSEMBLY 14 43T63303 FIXING PLATE VALVE
03 43T03329 BASE 15 43T47011 CAPILLARY TUBE; 1.5DIA
04 43T09318 GUARD FAN 16 43T41316 COMPRESSOR (RM5510GNE94) 05 43T62311 ELECTRIC PART COVER 17 43T47325 BOLT COMPRESSOR (M6) 06 43T20307 FAN PROPELLER 18 43T49001 CUSHION,RUBBER 07 43T21341 MOTOR;FAN 19 43T52310 PACKED VALVE COVER ASSEMBLY 08 43T47001 NUT FLANGE 20 43T00395 UPPER CABINET ASSEMBLY 09 43T41352 CONDENSER ASSEMBLY 21 43T55305 CAPACITOR,PLASTIC FILM 10 43T46311 VALVE;PACKED 6.35 DIA 22 43T55314 CAPACITOR,PLASTIC FILM 11 43T00347 VALVE;PACKED 9.52 DIA 23 43T60322 TERMINAL-2P 12 43T47331 BONNET, 6.35 DIA 24 43T54303 RELAY;OVERLOAD
Description Description
89
11-11. Outdoor Unit (RAS-07UAX4, RAS-07UA-E4)
FILE NO. SVM-05001-1
Location Part Location Part
No. No. No. No.
01 43T19313 FAN GUARD 13 43T47001 NUT FLANGE 02 43T20306 PROPELLER FAN 14 43T19312 HANDLE 03 43T00398 04 43T43340 CONDENSER ASSEMBLY 17 43T54302 RELAY;OVERLOAD
05 43T62309 TERMINAL COVER 18 43T41365 COMPRESSOR (PH108X1C-4DZDN2)
06 43T00397 07 43T47011 CAPILLARY TUBE; 1.5DIA 20 43T00394 08 43T00347 VALVE;PACKED 9.52 DIA 21 43T63301 FIXING PLATE VALVE 09 43T47332 BONNET, 9.52 DIA 22 43T42313 BASE COATING ASSEMBLY 10 43T46311 VALVE;PACKED 6.35 DIA 23 43T55305 11 43T47331 BONNET, 6.35 DIA 24 43T55314 CAPACITOR,PLASTIC FILM, 1.5uF 450V 12 43T21341 MOTOR;FAN 25 43T60322 TERMINAL-2P
FRONT CABINET COATING ASSEMBLY 15 43T49001 CUSHION,RUBBER
BACK CABINET COATING ASSEMBLY 19 43T62305 PACKED VALVE COVER
Description Description
UPPER CABINET COATING ASSEMBLY
CAPACITOR,PLASTIC FILM
90
11-12. Outdoor Unit (RAS-07UAH-E4)
FILE NO. SVM-05001-1
Location Part Location Part
No. No. No. No.
01 43T19313 FAN GUARD 15 43T49001 CUSHION,RUBBER 02 43T20306 PROPELLER FAN 17 43T54302 RELAY;OVERLOAD 03 43T00398 04 43T43350 CONDENSER ASSEMBLY 19 43T62305 PACKED VALVE COVER
05 43T62309 TERMINAL COVER 20 43T00394
06 43T00397 BACK CABINET COATING ASSEMBLY 21 43T63301 FIXING PLATE VALVE 07 43T47308 CAPILLARY TUBE; 1.0 DIA 22 43T42314 BASE COATING ASSEMBLY 08 43T00347 VALVE;PACKED 9.52 DIA 23 43T55305 09 43T47332 BONNET, 9.52 DIA 24 43T55314 CAPACITOR,PLASTIC FILM, 1.5uF 450V 10 43T46311 VALVE;PACKED 6.35 DIA 25 43T60323 TERMINAL-4P 11 43T47331 BONNET, 6.35 DIA 26 43T46312 4WAY-VALVE 12 43T21341 MOTOR;FAN 27 43T46316 COIL,VALVE 4WAY 13 43T47001 NUT FLANGE 28 43T79305 DRAIN NIPPLE 14 43T19312 HANDLE
FRONT CABINET COATING ASSEMBLY 18 43T41365 COMPRESSOR
Description Description
UPPER CABINET COATING ASSEMBLY
CAPACITOR,PLASTIC FILM
91
FILE NO. SVM-03004(1)
TOSHIBA CARRIER (THAILAND) CO.,LTD.
144/9 MOO 5, BANGKADI INDUSTRIAL PARK, TIVANON ROAD, TAMBOL BANGKADI,
AMPHUR MUANG, PATHUMTHANI 12000, THAILAND.
– 75 –