7-1 Outline of Air Conditioner Control
7-2 Description of Operation Circuit
Low-Temperature Limit Control
7-3
7-4 Auto Restart Function
8.INSTALLATION PROCEDURE
8-1 Safety Cautions
8-2 Installation Diagram of Indoor and Outdoor Units
8-3 Installation
8-4 Indoor Unit
8-5 Outdoor Unit
8-6 How to Set Remote Control Selector Switch
8-7 Others
9.TROUBLESHOOTING CHART
9-1 Troubleshooting Procedure
9-2 Basic Check Items
9-3 Primary Judgement
9-4 Self-Diagnosis by Remote Control (Check Code)
9-5 Troubleshooting Flowcharts
9-6 Troubleshooting for Remote Control (Including The Indoor P.C. Board)
− 1−
10. PARTS REPLACEMENT
10-1 Indoor Unit
10-2 Outdoor Unit (RAS-07S2SX-1)
10-3 Outdoor Unit (RAS-09SASX-1)
11. EXPLODED VIEWS AND PARTS LIST
11-1
Indoor Unit (E-Parts Assy)
11-2 Indoor Unit
11-3 Outdoor Unit (RAS-07S2SX-1)
11-4 Outdoor Unit (RAS-09SASX-1)
FILE NO. SVM-08028
− 2−
1. SPECIFICATIONS
FILE NO. SVM-08028
MO DE L
RAS-07SKSX-1 / RAS-07S2AX-1
IT E MCooling
Capacity
Power source V 220 - 240
Power consumption kW 0.62 0.66 0.84 0.88
Power factor % 98 96 98 98
RunningIndoorA0.15
current Outdoor A 2.72 2.72 3.75 3.60
Starting current A 13 15
Moisture removal lit/h 0.5 1.2
Noise
Refrigerant
Refrigerant controlCapillary tube
Interconnection
pipe
Indoor (H/M/L) dB 40/35/30 43/38/33
Outdoor dB 46 47 46 47
Name of refrigerantR22
Rated amount kg 0.58
Gas side sizemm
Connection typeFlare connection
Liquid side sizemm6.35
Connection typeFlare connection
Maximum length
(One way)
Maximum height
difference
kW2.002.002.502.50
Phase1
Hz50
m
m
220V240V220V240V
10
RAS-09SKSX-1 / RAS-09SASX-1
9.52
*1
5
INDOOR UNIT RAS-07SKSX-1 RAS-09SKSX-1
Height mm 250
DimensionsWidthmm740
Depth mm 185
Net weight kg
Evaporator typeFinned tube
Indoor fan typeCross flow fan
High fanm3/h
Air volume
Fan motor outputW20
Air filterHoneycomb woven filter with PP frame
OUTDOOR UNIT RAS-07S2AX-1 RAS-09SASX-1
Dimensions Width mm 660
Net weight kg 25
Condenser typeFinned tube
Outdoor fan type Propeller fan
Airflow volume m3/h
Fan motor output W 20 20
Compressor
Safety device
Louver typeAutomatic louver
Usable outdoor temperature range
Medium fan
Low fan
Height mm 530
Depth mm 240
Model PH108X1C-4DZDN2
Output W 605 780
m3/h
m3/h
1580
°C
510
430
350
16201720
Fuse, Overload relay
8
540
470
390
26
1640
QK164PBA
21 ~ 43
– 3 –
Note : 1
• Capacity is based on the following temperature conditions.
FILE NO. SVM-08028
Temperature
Indoor unit inlet air temperature
Outdoor unit inlet air temperature
Note : 2
*1 No need to charge extra refrigerant.
Condition
(DB) 27°C
(WB)
(DB) 35°C
(WB) 24°C
JIS C9612
Cooling
19°C
− 4 −
2. CONSTRUCTION VIEWS
FILE NO. SVM-08028
2-1. Indoor Unit
– 5 –
135
1654
Wireless remote control
2-2. Outdoor Unit
FILE NO. SVM-08028
C
L
C
L
280
− 6 −
400
3. WIRING DIAGRAM
FILE NO. SVM-08028
SINGLE PHASE
1∅220‑240V
50Hz
BRW
BLU
GRN&YEL
Heatexchanger
Heatexchanger
Sensor(TC)
Thermosensor(TA)
CN25
1
1
2
2
3
3
4
4
5
5
6
6
7
7
8
8
andindicationparts.
Infraredraysreceiver
WP‑017
WHI
BLK
GRN&YEL
CN01
N
1
1
22
CN03
1
1
2
2
CN12
BLU
1
1
BLU
2
2
BLU
3
3
BLU
4
4
BLU
5
5
BLU
6
6
BLU
7
7
WHI
8
8
F01
6.3A
250VAC
R62
CN31
4
C25
RY01
R63
21
3
BLK
P04
3
SG01
DSA
C26
L01
4
DB01
R64
C27
Switchingpowersupply
DC5V
Voltageregulator
12V
3
4
MCU
IC03
WP‑018
1
2
CN04
22
11
PNK
DC12V
C07
PNK
Tempfuse73C
CN07
1
22
3
44
55
CN11
1
2
3
CN10
5
33
1
WHI
1
1
1
YEL
22
YEL
3
3
3
YEL
44
YEL
55
YEL
1
GRY
2
BRW
3
WHI
5
BLK
RED
1
o
1
2
3
4
565
1
2
3
4
6
Louvermotor
ACmotor
Fanmotor
TERMINAL
BLOCK
OUTDOOR
TERMINAL
BLOCK
BLK
BLK
OVERLOAD RELAY
(L)
1
FAN MOTOR
BLK
(N)
2
RED
RED
WHI
COMPRESSOR
INDOOR
TERMINAL
CHASSIS
RED
CAPACITOR
PNK
WHI
BLOCK
1
BLK
INDOOR
OUTDOOR
CAPACITOR
GRN&YEL
2
WHI
FAN MOTOR
Type "A" Type "B"
− 7−
FILE NO. SVM-08028
4. SPECIFICATION OF ELECTRICAL PARTS
4-1. Indoor Unit
No.Parts nameTypeSpecifications
1 Fan motor (for indoor) AFS-220-20-4AR AC Motor with 145°C thermo fuse
2Thermo sensor (TA-sensor)10k at 25 C
3 Switching power supply (T01)
4 Microcontroller unit (IC30) TMP87CM40ANG-6P68
5Heat exchanger sensor
• Measure the heat exchanger temperature at the center of U-bend. (By means of TC sensor)
– 10 –
5-2. RAS-09SKSX-1 / RAS-09SASX-1
FILE NO. SVM-08028
Indoor unit
Cooling
0.39m
(Connecting pipe)
∅9.52
O.D.:9.52mmO.D.:6.35mm
Cooling
Packed valve
Cooling
P
(∅9.52)
Compressor
QK164PBA
Heat exchanger
Cross flow fan
T1
Packed valve
(∅6.35)
Capillary tube
700s
∅1.5x
0.49m
(Connecting pipe)
∅6.35
Heat exchanger
Refrigerant
0.58
Cooling
Propeller fan
Outdoor unit
R22 :
Mark ( ) means check points of Gas Leak.
kg.
Ambient temp.
50Hz
Standard
pressure
(MPaG)
P
Surface temp. of heat
exchanger interchanging
pipe
T1
(°C)
Fan speed
(indoor)
conditions DB/WB
(°C)
IndoorOutdoor
Standard 0.50 11.0 High 27/19.5 35/24
Cooling Overload 0.60 15.0 High 32/23 43/26
Low temperature 0.40 2.2 Low 21/15 21/15
Note
• Measure the heat exchanger temperature at the center of U-bend. (By means of TC sensor)
– 11–
Heat Exchange sensor
6. CONTROL BLOCK DIAGRAM
Main Unit Control PanelM.C.U.
Functions
FILE NO. SVM-08028
Operation
Display
Thermo. Sensor
Infrared Rays Signal Reciver
• Louver Control
•3-minutes Delay at Restart
for Compressor
Initiallizing Circuit
Clock Frequency
Oscillator Circuit
Power Supply
Circuit
Noise FilterRelay Driver, Louver Driver
•Motor Revolution Control
•Processing
(Temperature Processing)
•Timer
Compressor
ON/OFF
Signal
Relay
RY01
Timer
Display
Fan Only
Sign Display
Indoor Fan
Motor
Louver
ON/OFF
Signal
Louver
Motor
220-240 V~, 50Hz
REMOTE CONTROL
Compressor, Outdoor Fan Motor
Infrared Rays
Remote Control
Operation (START/STOP)
Operation Mode Selection
AUTO, COOL, DRY, AUTO FAN
Temperature Setting
Fan Speed Selection
ON TIMER Setting
OFF TIMER Setting
Louver Auto Swing
Louver Direction Setting
ECO
− 12 −
7. OPERATION DESCRIPTION
FILE NO. SVM-08028
7-1. Remote control
7-1-1. Function of Push Putton
Infrared signal emitter
1
2
Set louver button (FIX)
Auto Louver button (SWING)
3
Mode select button (MODE)
4
Reset button (RST)
5
On timer button (ON)
6
7
Off timer button (OFF)
Reserve button (SET)
8
Cancel button (CLR)
9
10
Check button (CHK)
11
ECO button (ECO)
12
Fan speed button (FAN)
13
Start/Stop button (START/STOP)
14
Temperature button ( )
1
MODE
AUTO
COOL
AUTO FAN
2
DRY
SWING
TEMP.
Hr.ON OFF
TEMP.
START/STOP
3
MODE
4
5
6
RST
TIMER
ONOFFSETCLR
7
FIX
CHK
FAN
AUTO
B
QUIET
14
13
FAN
12
ECO
11
10
9
8
− 13 −
FILE NO. SVM-08028
7-1-2. Display of Remote Control
All indications, except for the clock time indicator, are displayed by pressing the button.
1.Transmission mark
This transmission mark
remote controller transmits signals to the indoor
unit.
indicates when the
2. Mode indicator
Indicates the current operation mode.
(AUTO, COOL, DRY and AUTO FAN)
3. Temperature indicator
Indicates the temperature setting.
(17°C to 30°C)
4. ECO indicator
Indicates when the ECO is in activated.
Press the ECO button to start and press it again
to stop operate.
5. A, B change indicator remote controller
When the remote controller switching function is
set, "B" appears in the remote controller display
(When the remote controller seting is "A", there is
no indication at this position.)
1
3
2
7
6
6. Swing
Indicate when louver is swing.
Press swing button to start the swing operation
and press it again to stop the swing operation.
7. FAN speed indicator
Indicates the selected fan speed.
AUTO, QUIET or three fan speed levels
( LOW , MED , HIGH can be shown.
Indicate Auto will be appear with Dry operation
only.
8. ON/OFF TIMER indicator
Indicates when the ON/OFF TIMER operation.
(ON TIMER [Hr. ON], OFF TIMER [OFF]).
•
•
Hr.ON OFF
•
4
•
•
•
•
B
•
•
•
•
7
7
8
5
8
− 14 −
7-2. Outline of Air Conditioner Control
FILE NO. SVM-08028
This is a fixed capacity type air conditioner, which uses
a AC motor for an indoor fan. The AC motor drive
circuit is mounted in the indoor unit. And electrical
parts which operate the compressor and the outdoor
fan motor, are mounted in the outdoor unit.
The air conditioner is mainly controlled by the indoor
unit controller. The controller operates the indoor fan
motor based upon commands transmitted by the
remote control and transfers the operation commands
to the outdoor unit controller.
The outdoor unit receives operation commands from
the indoor unit, and operates the outdoor fan motor
and the compressor.
(1) Role of indoor unit controller
The indoor unit controller receives the operation
commands from the remote control and executes
them.
• Temperature measurement at the air inlet of the
indoor heat exchanger by the indoor
temperature sensor
• Temperature measurement of the indoor heat
exchanger by the heat exchanger sensor
• Louver motor control
• Indoor fan motor operation control
• LED display control
• Transferring of operation commands to the
outdoor unit
• Receiving of information of the operation status
and judging of the information or indication of
error
(2) Role of outdoor unit controller
The outdoor unit controller receives the operation
commands from the indoor controller and
executes them.
• Compressor operation
control
• Operation control of
outdoor fan motor
Operations according
to the commands
from the indoor unit
• Turning off the compressor and outdoor fan
when the outdoor unit receives the shutdown
command
7-2-1. Louver control
(1) Vertical air flow louver
Position of veritcal air flow louver is automatically
controlled according to the operation mode.
Besides, position of vertical air flow louver can be
arbitrarily set by pressing [FIX] button.
The louver position which is set by [FIX] button is
stored in the microcomputer, and the louver is
automatically set at the stored position for the next
operation.
(2) Swing
If [SWING] button is pressed when the indoor unit
is in operation, the vertical air flow louver starts
swinging. When [FIX] button is pressed, it stops
swinging.
7-2-2. Indoor Fan Control
The operation controls the fan speed at indoor unit
side. The indoor fan (cross flow fan) is operated by
the phase control induction motor. The fan rotates in 3
stages in MANUAL model, and in 5 stages in AUTO
mode, respectively. (Table 7-2-1)
1) When setting the fan speed to L, M or H on
the remote controller, the operation is performed
with the constant speed shown in Fig. 7-2-1.
Fig (7-2-1)
Indication
L
M
H
Fan speed
Low
Med
High
2) When setting the fan speed to AUTO on the remote
controller, revolution of the fan motor is controlled
to the fan speed level shown in Table 1 according to
the setup temperature, room temperature, and heat
exchanger temperature.
3) When setting the fan speed to QUIET on the remote
controller, revolution of the fan motor is controlled
to the fan speed level is L-.
Table 7-2-1 Indoor fan and air flow rate
OPERATION
MODE
RAS-07SKSX-1
Model
RAS-09SKSX-1
Cool
Dry
fan speed (rpm)
Air flow (m
fan speed (rpm)
Air flow (m3/h)
3
/h)
Fan speed level
UH H M+ M L+ L L- UL SUL
UHHM+ML+LL-UL SUL
(1) When turning on the breaker, the operation lamp
blinks. This means that the power is on (or the
power supply is cut off.)
(2) When pressing [ ] button on the
remote control, receiving beep sounds from the
indoor unit, and the next operation is performed
together with opening the vertical air flow louver.
(3) Once the operation mode is set, it is memorized in
the microcomputer so that the previous operation
can be effected thereafter simply by pressing
[ ] button.
7-3-1. Fan only operation
([MODE] button on the remote control is set
to the fan only operation.)
(1) When [FAN] button is set to AUTO, the indoor fan
motor operates as shown in Fig. 7-3-1. When
[FAN] button is set to LOW, MED, or HIGH
the motor operates with a constant air flow.
°C
7-3-2. Cooling operation
([MODE] button on the remote control is set
to the cooling operation.)
(1) The compressor, outdoor fan and operation
display lamp are controlled as shown in
Fig. 7-3-2.
°C
ON ON
OFF OFF ON
Compressor
Outdoor fan
-
(Room temp.) (Preset temp.)
Preset
temp.
0.5
0
Fig. 7-3-2
display
OPERATION
+3
+2.5
+2
+1.5
+1
+0.5
(Room temp.) − (Preset temp.)
Preset
temp.
0
(Preset temp.: 24 °C)
NOTE1 : *1 : Fan speed = (M + - L) x 3/4 + L
*2 : Fan speed = (M + - L) x 2/4 + L
*3 : Fan speed = (M + - L) x 1/4 + L
(Linear approximation
from M+ and L)
NOTE2 : ECO operation can not be set.
Fig. 7-3-1 Setting of air flow [FAN:AUTO]
M+
*1
*2
*3
(2) When [FAN] button is set to AUTO, the indoor fan
motor operates as shown in Fig. 7-3-5. When
[FAN] button is set to LOW, MED or HIGH
the motor operates with a constant air flow.
°C
(Room temp.) − (Preset temp.)
Preset
temp.
+3
+2.5
+2
+1.5
+1
+0.5
0
-0.5
M+
*1
*2
*3
NOTE1 : *1 : Fan speed = (M + - L) x 3/4 + L
*2 : Fan speed = (M + - L) x 2/4 + L
*3 : Fan speed = (M + - L) x 1/4 + L
(Linear approximation
from M+ and L)
Fig. 7-3-3 Setting of air flow [FAN:AUTO]
− 16 −
FILE NO. SVM-08028
7-3-3. Dry operation
([MODE] button on the remote control is set
to the dry operation.)
(1) The compressor, outdoor fan and operation
display on the remote control are controlled
as shown in Fig. 7-3-4.
°C
ON:6min.
OFF:4min.
ON:6min.
OFF:4min.
ON:5min.
ON:5min.
OFF:5min.
OFF
OFF
Compressor
ON
OFF:5min.
Outdoor fan
-
(Room temp.) (Preset temp.)
Preset
temp.
+3
+2
+1
0
Fig. 7-3-4
display
OPERATION
(1) One of 2 operations (Cooling or Fan only)
is selected according to difference between the
preset temperature and the room temperature at
which the automatic operation has started, as
shown in Fig. 7-3-6. The Fan only operation
continues until the room temperature reaches a
level at which another mode is selected.
(2) Temporary Auto
When the [RESET] button on the indoor unit
is pushed, the preset temperature is fixed at 24°C
and the indoor unit is controlled as shown in
Fig. 7-3-6.
°C
Cooling operation
0
-
Fan only operation
(2) The microcontroller turns the compressor on and
off at the regular intervals (4 to 6 minutes). While
the compressor is turning off, the indoor fan motor
operates in the SUPER LOW position.
The pattern of operation depending on the relation
between room temperature and preset
temperatures is shown in Fig. 7-3-5.
Room temp.
Preset temp.+1
Preset temp.
Compressor
Outdoor fan
Indoor fan
ONONONON
OFFOFFOFF
L *SL SLLL SL L
*
Super Low
Fig. 7-3-5
(3) [FAN] button on the remote control is set to AUTO
only.
(Room temp.) (Preset temp.)
Fig. 7-3-6
7-4. Low-Temperature Limit Control
The microcontroller detects the indoor heat exchanger
temperature to prevent the indoor heat exchanger from
freezing.
The compressor and outdoor fan motor are controlled
as shown in Fig. 7-4-1
Heat exchanger
temperature
(°C)
5
2
Fig. 7-4-1
Compressor Outdoor fan
ON
Less than 2°C continues
for 5 minutes
OFF
(4) The ECO operation cannot be set.
7-3-4. Automatic operation
([MODE] button on the remote control is set
to the automatic operation.)
− 17 −
FILE NO. SVM-08028
7-5. Auto Restart Function
This indoor unit is equipped with an automatic restarting function which allows the unit to restart operating with
the set operating conditions in the ev ent of a power supply being accidentally shut down.
The operation will resume without warning three minutes after power is restored.
This function is not set to work when shipped from the factory. Therefore it is necessary to set it to work.
7-5-1. How to Set the Auto Restart Function
To set the auto restart function, proceed as follows:
The power supply to the unit must be on ; the function will not set if the power is off.
Press the [RESET] button located in the center of the front panel continuously f or three seconds.
The unit receives the signal and beeps three times.
The unit then restarts operating automatically in the event of power supply being accidentally shut down.
• When the unit is standby (Not operating)
Operation
Press [RESET] button for more than
three seconds. (Less than 10 seconds)
RESET button
• When the unit is in operation
Operation
Press [RESET] button for more than
three seconds. (Less than 10 seconds)
Motions
The unit is on standby.
↓
The unit starts to operate.The green indicator is on.
↓After approx. three seconds,
The unit beeps three timesThe green indicator flashes
and continues to operate.for 5 seconds.
If the unit is not required to operate at this time, press [RESET]
button once more or use the remote controller to turn it off.
Motions
The unit is in operation.The green indicator is on.
↓
The unit stops operating.The g reen indicator is turned off.
↓After approx. three seconds,
The unit beeps three times.The green indicator flashes
for 5 seconds.
If the unit is required to operate at this time, press [RESET] button
once more or use the remote controller to turn it on.
RESET button
• While the filter check indicator is on, the RESET button has the function of filter reset betton.
– 18 –
FILE NO. SVM-08028
7-5-2. How to Cancel the Auto Restart Function
To cancel auto restart function, proceed as follows :
Repeat the setting procedure : the unit receives the signal and beeps three times.
The unit will be required to be turned on with the remote controller after the main power supply is turned off.
• When the system is on stand-by (not operating)
Operation
Press [RESET] button for more than
three seconds. (Less than 10 seconds)
RESET button
• When the system is operating
Operation
Press [RESET] button for more than
three seconds. (Less than 10 seconds)
Motions
The unit is on standby.
↓
The unit starts to operate.The green indicator is on.
↓After approx. three seconds,
The unit beeps three times and continues to operate.
If the unit is not required to operate at this time, press [RESET]
button once more or use the remote controller to turn it off.
Motions
The unit is in operation.The green indicator is on.
↓
The unit stops operating.The g reen indicator is turned off.
The unit beeps three times.
If the unit is required to operate at this time, press [RESET] button
once more or use the remote controller to turn it on.
RESET button
7-5-3. Power Failure During Timer Operation
When the unit is turned off because of power failure
during timer operation, the timer operation is cancelled. In that case, set the timer operation again.
NOTE :
The Everyday Timer is reset while a command signal
can be received from the remote controller even if it
stopped due to a power failure .
↓After approx. three seconds,
– 19 –
FILE NO. SVM-08028
8. INSTALLATION PROCEDURE
8-1. Safety Cautions
For general public use
Power supply cord of parts of appliance for Outdoor use shall be at least polychloroprene sheathed flexible cord
(design H07 RN-F), or cord designation 245 IEC66.(Shall be installed in accordance with national wiring regulations.)
CAUTION
This appliance must be connected to the main power supply by means of a circuit breaker or a switch with a
contact separation of at least 3 mm in all poles.
If this is not possible, a power supply plug with earth must be used. This plug must be easily accessible after
installation. The plug must be disconnected from the power supply socket in order to disconnect the
appliance completely from the mains.
To Disconnect the Appliance from the Main Power Supply
DANGER
• FOR USE BY QUALIFIED PERSONS ONLY.
• TURN OFF MAIN POWER SUPPLY BEFORE ATTEMPTING ANY ELECTRICAL WORK. MAKE SURE
ALL POWER SWITCHES ARE OFF. FAILURE TO DO SO MAY CAUSE ELECTRIC SHOCK.
• CONNECT THE CONNECTING CABLE CORRECTLY. IF THE CONNECTING CABLE IS CONNECTED
WRONGLY, ELECTRIC PARTS MAY BE DAMAGED.
• CHECK THE EARTH WIRE THAT IT IS NOT BROKEN OR DISCONNECTED BEFORE INSTALLATION.
• DO NOT INSTALL NEAR CONCENTRATIONS OF COMBUSTIBLE GAS OR GAS VAPORS.
FAILURE TO FOLLOW THIS INSTRUCTION CAN RESULT IN FIRE OR EXPLOSION.
• TO PREVENT OVERHEATING THE INDOOR UNIT AND CAUSING A FIRE HAZARD, PLACE THE UNIT
WELL AWAY (MORE THAN 2 M) FROM HEAT SOURCES SUCH AS RADIATORS, HEATORS,
FURNACE, STOVES, ETC.
• WHEN MOVING THE AIR-CONDITIONER FOR INSTALLING IT IN ANOTHER PLACE AGAIN, BE VERY
CAREFUL NOT TO GET THE SPECIFIED REFRIGERANT (R410A) WITH ANY OTHER GASEOUS
BODY INTO THE REFRIGERATION CYCLE. IF AIR OR ANY OTHER GAS IS MIXED IN THE
REFRIGERANT, THE GAS PRESSURE IN THE REFRIGERATION CYCLE BECOMES ABNORMALLY
HIGH AND IT RESULTINGLY CAUSES BURST OF THE PIPE AND INJURIES ON PERSONS.
• IN THE EVENT THAT THE REFRIGERANT GAS LEAKS OUT OF THE PIPE DURING THE
INSTALLATION WORK, IMMEDIATELY LET FRESH AIR INTO THE ROOM. IF THE REFRIGERANT GAS
IS HEATED BY FIRE OR SOMETHING ELSE, IT CAUSES GENERATION OF POISONOUS GAS.
WARNING
• Never modify this unit by removing any of the safety guards or bypassing any of the safety interlock
switches.
• Do not install in a place which cannot bear the weight of the unit.
Personal injury and property damage can result if the unit falls.
• Before doing the electrical work, attach an approved plug to the power supply cord.
Also, make sure the equipment is properly earthed.
• Appliance shall be installed in accordance with national wiring regulations.
If you detect any damage, do not install the unit. Contact your TOSHIBA dealer immediately.
CAUTION
• Exposure of unit to water or other moisture before installation could result in electric shock.
Do not store it in a wet basement or expose to rain or water.
• After unpacking the unit, examine it carefully for possible damage.
• Do not install in a place that can increase the vibration of the unit. Do not install in a place that can amplify
the noise level of the unit or where noise and discharged air might disturb neighbors.
• To avoid personal injury, be careful when handling parts with sharp edges.
• Please read this installation manual carefully before installing the unit. It contains further important
instructions for proper installation.
− 20 −
FILE NO. SVM-08028
REQUIREMENT OF REPORT TO THE LOCAL POWER SUPPLIER
Please make absolutely sure that the installation of this appliance is reported to the local power supplier
before installation. If you experience any problems, or if the installation is not accepted by the supplier, the
service agency will take adequate countermeasures.
Remark per EMC Directive 89/336/EEC
To prevent flicker impressions during the start of the compressor (technical process) following installation
conditions do apply.
1. The power connection for the air conditioner has to be done at the main power distribution. This distribution
has to be of an impedance.
Normally the required impedance is reached at a 32A fusing point. Air conditioner fuse has to be 16A max.!
2. No other equipment should be connected to this power line.
3. For detailed installation acceptance, please contact your power supplier whether its restriction does apply
for products like washing machines, air conditioners or electrical ovens.
4. For power details of the air conditioner, refer to the rating plate of the product.
− 21 −
8-2. Installation Diagram of Indoor and Outdoor Units
120 m
m or more
Hook
47 mm or more
1 Installation
plate
FILE NO. SVM-08028
For the rear left and left piping
Wall
(
A
t
t
a
5
Active Carbon-Catechin filter
Before installing the
wireless remote control
• With the remote control cover
open, load the batteries supplied
correctly, observing their
polarity.
2 Wireless remote control
3 Batteries
Hook
120 mm or more
Insert the cushion between
the indoor unit and wall, and
tilt the indoor unit for better
operation.
A
ir
f
ilt
e
r
Do not allow the drain hose to
get slack.
c
h
t
o
t
h
e
f
r
o
n
t
p
a
n
e
l
.)
Pan head wood screw
7
Shield pipe
Make sure to run the drain
hose sloped downward.
Cut the piping
hole sloped
slightly.
The auxiliary piping can be
connected to the left, rear left,
rear right, right, bottom right
or bottom left.
4 Remote control holder
Right
2 Wireless remote control
Rear right
Bottom
right
Rear
left
Insulate the refrigerant pipes
separately with insulation, not
together.
Left
Bottom left
Vinyl tape
Apply after carrying
out a drainage test.
45 mm or more
600 mm or more
10
0
mm o
r mor
e
e
r
o
m
r
o
m
m
0
0
4
Extension
drain hose
(Not available,
provided by
installer)
1
0
0
m
m
o
Saddle
r m
o
re
6 mm thick heat resisting
polyethylene foam
− 22 -
8-3. Installation
8-3-1. Optional installation parts
FILE NO. SVM-08028
Part
Code
Parts name
Refrigerant piping
A
Liquid side : ∅6.35 mm
Gas side : ∅ 9.52 mm
Pipe insulating material
B
(polyethylene foam, 6 mm thick)
Putty, PVC tapes
C
<Fixing bolt arrangement of outdoor unit>
500 mm
Air inlet
97 mm
53 mm
280 mm
Air outlet
Drain outlet
Fig. 8-3-1
Q'ty
One
each
1
One
each
• Secure the outdoor unit with fixing bolts and nuts if the unit is likely to be exposed to a strong wind.
• Use ∅8 mm or ∅10 mm anchor bolts and nuts.
− 23 −
8-3-2. Accessory and installation parts
FILE NO. SVM-08028
Part
No.
Part name (Q'ty)
1
Installation plate x 1
2
Wireless remote control x 1
Others
Owner’s manual
Installation manual
Name
Part
No.
Part name (Q'ty)
3
Battery x 2
4
Remote control holder x 1
Part
No.
Part name (Q'ty)
5
Active Carbon-Catechin filter x 2
6
Mounting screw ∅ 4 x 25 x 6
7
Pan head wood screw
∅ 3.1 x 16 x 2
l
l
− 24 −
FILE NO. SVM-08028
8-4. Indoor Unit
8-4-1. Installation place
• A place which provides the spaces around the
indoor unit as shown in the above diagram.
• A place where there is no obstacle near the air inlet
and outlet.
• A place that allows easy installation of the piping to
the outdoor unit.
• A place which allows the front panel to be opened.
CAUTION
• Direct sunlight to the indoor unit's wireless
receiver should be avoided.
• The microprocessor in the indoor unit should not
be too close to RF noise sources.
(For details, see the owner's manual.)
<Remote control>
• A place where there are no obstacles such as a
curtain that may block the signal from the indoor
unit.
• Do not install the remote control in a place exposed
to direct sunlight or close to a heating source, such
as a stove.
• Keep the remote control at least 1 m apart from the
nearest TV set or stereo equipment. (This is
necessary to prevent image disturbances or noise
interference.)
• The location of the remote control should be
determined as shown below.
Remote
control
(Top view)
Indoor unit
Reception
range
45
°
°
45
Remote control
Indoor unit
(Side view)
°
75
Reception
range
8-4-2. Cutting a hole and mounting installation
plate
<Cutting a hole>
When installing the refrigerant pipes from the rear.
90 mm
66 mm
Pipe hole
42 mm
65 mm
Fig. 8-4-2
1. After determining the pipe hole position on the
mounting plate (A), drill the pipe hole (∅65 mm) at
a slight downward slant to the outdoor side.
NOTE
• When drilling a wall that contains a metal lath, wire
lath or metal plate, be sure to use a pipe hole brim
ring sold separately.
<Mounting the installation plate>
35
55.5
1
Installation
plate
120
65
Pipe hole
Indoor unit
Hook
Hook
Thread
Weight
Hook
Pipe hole
Mounting screw
6
Fig. 8-4-1
Fig. 8-4-3
− 25 −
FILE NO. SVM-08028
<When the installation plate is directly mounted on
the wall>
1. Securely fit the installation plate onto the wall by
screwing it in the upper and lower parts to hook up
the indoor unit.
2. To mount the installation plate on a concrete wall
with anchor bolts, utilize the anchor bolt holes as
illustrated in the above figure.
3. Install the installation plate horizontally in the wall.
CAUTION
When installing the installation plate with a
mounting screw, do not use the anchor bolt hole.
Otherwise the unit may fall down and result in
personal injury and property damage.
Installation plate
<Keep horizontal direction>
Anchor
bolt
Projection
5 mm dia. hole
Clip anchor
(local parts)
Fig. 8-4-4
15 mm or less
6 Mounting
screw
ss
∅4 x 25
s
ss
8-4-3. Electrical work
1. The supply voltage must be the same as the rated
voltage of the air conditioner.
2. Prepare the power source for exclusive use with the
air conditioner.
CAUTION
• This appliance can be connected to the mains in
either of the following two ways.
(1) Connection to fixed wiring:
A switch or circuit breaker which disconnects
all poles and has a contact separation of at
least 3 mm must be incorporate in the fixed
wiring. An approved circuit breaker or
switches must used.
(2) Connection with power supply plug:
Attach power supply plug with power cord
and plug it into wall outlet. An approved
power supply cord and plug must be used.
NOTE
• Ensure all wiring is used within its electrical rating.
Model
Power source 50 Hz, 220 − 240 V Single phase
Maximum
running current
Plug socket &
fuse rating
Power cord
RAS-07,09SKSX-1
7.5A
16A
1 mm2or more
CAUTION
Failure to firmly install the unit may result in
personal injury and property damage if the unit falls.
• In case of block, brick, concrete or similar type
walls, make 5 mm dia. holes in the wall.
• Insert clip anchors for appropriate
screws.
NOTE
• Secure four corners and lower parts of the
installation plate with 4 to 6 mounting screws to
install it.
6 mounting
− 26 −
<How to connect the connecting cable>
Wiring of the connecting cable can be carried out
without removing the front panel.
1. Remove the air inlet grille.
Open the air inlet grille upward and pull it toward
you.
2. Remove the terminal cover and cord clamp.
3. Insert the connecting cable (according to the local
cords) into the pipe hole on the wall.
4. Take out the connecting cable through the cable
slot on the rear panel so that it protrudes about
15 cm from the front.
5. Insert the connecting cable fully into the terminal
block and secure it tightly with screws.
6. Tightening torque : 1.2 N·m (0.12 kgf·m)
7. Secure the connecting cable with the cord clamp.
8. Fix the terminal cover, rear plate bushing and air
inlet grille on the indoor unit.
CAUTION
• Be sure to refer to the wiring system diagram
labeled inside the front panel.
• Check local electrical cords and also any specific
wiring instructions or limitations.
Connecting cable
about 15 cm
Stripping length of the connecting cable
FILE NO. SVM-08028
Terminal cover
Screw
Fig. 8-4-5
65 mm
10 mm
10 mm
50 mm
Cord clamp
Screw
Earth line
Terminal block
Earth line
Connecting cable
Fig. 8-4-6
NOTE
• Use stranded wire only.
• Wire type : H07 RN-F or more
<How to install the air inlet grille on the indoor unit>
• When attaching the air inlet grille, the contrary of
the removed operation is performed.
Fig. 8-4-7
− 27 −
FILE NO. SVM-08028
8-4-4. Piping and drain hose installation
<Piping and drain hose forming>
* Since dewing results in a machine trouble, make
sure to insulate both the connecting pipes. (Use
polyethylene foam as insulating material.)
Rear right
Rear left
Bottom left
Changing
Left
Bottom right
Right
Die-cutting
Front panel slit
drain hose
Piping preparation
1. Die-cutting Front panel slit
For leftward connection, cut out slit on the left side of
the front panel. (A knife will produce splinters, so use
nippers.)
2. Changing drain hose
For leftward connection, bottom leftward connection
and rear leftward connection’s piping, it is necessary to
change the drain hose and drain cap.
How to remove the drains cap
Clip drain cap by needle-nose plier, and pull out.
How to fix the drains cap
1) Insert hexagonal wrench (4 mm) in a center
head.
4 mm
Fig. 8-4-10
2) Firmly insert drains cap.
No gap
Do not apply lubricating oil
(refrigerant machine oil) when
inserting the drain cap.
Application causes deterioration
Insert a hexagon
wrench (4 mm)
and drain leakage of the plug.
Fig. 8-4-11
CAUTION
Firmly insert the drain hose and drain cap; otherwise,
water may leak.
<In case of right or left piping>
Fig. 8-4-8
How to install the drain hose
Firmly insert drain hose connecting part until hitting on
a heat insulator.
Heat insulator
Drain hose
Fig. 8-4-9
• After scribing slits of the front panel with a knife or a
making-off pin, cut them with a pair of nippers or an
equivalent tool.
Slit
Fig. 8-4-12
<In case of bottom right or bottom left piping>
• After scribing slits of the front panel with a knife or a
making-off pin, cut them with a pair of nippers or an
equivalent tool.
Slit
− 28 −
Fig. 8-4-13
FILE NO. SVM-08028
<Left-hand connection with piping>
Bend the connecting pipe so that it is laid within 43 mm
above the wall surface. If the connecting pipe is laid
exceeding 43 mm above the wall surface, the indoor
unit may unstably be set on the wall. When bending the
connecting pipe, make sure to use a spring bender so
as not to crush the pipe.
Bend the connection pipe within a radius of 30 mm.
To connect the pipe after installation of the unit (figure)
(To the forefront of flare)
210 mm
165 mm
R 30 mm (Use polisin (polyethylene)
43 mm
core or the like for bending pipe.)
0
8
Gas side
Liquid side
Outward form of indoor unit
Use the handle of screwdriver, etc.
Fig. 8-4-14
8-4-5. Indoor unit fixing
1. Pass the pipe through the hole in the wall, and hook
the indoor unit on the installation plate at the upper
hooks.
2. Swing the indoor unit to right and left to confirm that
it is firmly hooked up on the installation plate.
3. While pressing the indoor unit onto the wall, hook it
at the lower part on the installation plate. Pull the
indoor unit toward you to confirm that it is firmly
hooked up on the installation plate.
1
2
Hook
Hook here
1 Installation
plate
Press
(unhook)
Fig. 8-4-15
• For detaching the indoor unit from the installation
plate, pull the indoor unit toward you while pushing
its bottom up at the specified parts.
NOTE
If the pipe is bent incorrectly, the indoor unit may
unstably be set on the wall.
After passing the connecting pipe through the pipe
hole, connect the connecting pipe to the auxiliary pipes
and wrap the facing tape around them.
CAUTION
• Bind the auxiliary pipes (two) and connecting
cable with facing tape tightly. In case of leftward
piping and rear-leftward piping, bind the auxiliary
pipes (two) only with facing tape.
Indoor unit
Auxiliary pipes
Installation plate
• Carefully arrange pipes so that any pipe does not
stick out of the rear plate of the indoor unit.
• Carefully connect the auxiliary pipes and
connecting pipes to each other and cut off the
insulating tape wound on the connecting pipe to
avoid double-taping at the joint, moreover, seal
the joint with the vinyl tape, etc.
• Since dewing results in a machine trouble, make
sure to insulate both the connecting pipes. (Use
polyethylene foam as insulating material.)
• When bending a pipe, carefully do it, not to crush it.
Connecting cable
PushPush
Fig. 8-4-16
− 29 −
FILE NO. SVM-08028
8-4-6. Drainage
1. Run the drain hose sloped downwards.
NOTE
• Hole should be made at a slight downward slant on
the outdoor side.
Do not form the
Do not rise the
drain hose.
50 mm
or more
Do not put
the drain
hose end
into water.
Fig. 8-4-
drain hose into
a wavy shape.
17
Do not put
the drain
hose end in
the drainage
ditch.
2. Put water in the drain pan and make sure that the
water is drained out of doors.
3. When connecting extension drain hose, insulate the
connecting part of extension drain hose with shield
pipe.
Shield pipe
Drain hose
Inside the room
Fig. 8-4-
Extension drain hose
18
CAUTION
Arrange the drain pipe for proper drainage from the
unit.
Improper drainage can result in dew-dropping.
This air conditioner has the structure designed to drain
water collected from dew, which forms on the back of
the indoor unit, to the drain pan.
Therefore, do not store the power cord and other parts
at a height above the drain guide.
8-5. Outdoor Unit
8-5-1. Installation place
• A place which provides the spaces around the
outdoor unit as shown in the left diagram.
A place which can bear the weight of the outdoor
•
unit and does not allow an increase in noise level
and vibration.
A place where the operation noise and discharged
•
air do not disturb your neighbors.
A place which is not exposed to a strong wind.
•
A place free of a leakage of combustible gases.
•
A place which does not block a passage.
•
When the outdoor unit is to be installed in an
•
elevated position, be sure to secure its feet.
An allowable length of the connecting pipe is up to
•
10 m.
An allowable height level is up to 5 m.
•
• A place where the drain water does not raise any
problem.
CAUTION
1. Install the outdoor unit without anything blocking
the air discharging.
2. When the outdoor unit is installed in a place
exposed always exposed to strong wind like a
coast or on a high storey of a building, secure
the normal fan operation using a duct or a wind
shield.
3. In particularly windy areas, install the unit such
as to avoid admission of wind.
4. Installation in the following places may result in
trouble.
Do not install the unit in such places.
A place full of machine oil.
•
A saline-place such as the coast.
•
A place full of sulfide gas.
•
A place where high-frequency waves are likely
•
to be generated as from audio equipment,
welders, and medical equipment.
Space for pipes
Fig. 8-4-
19
Wall
Drain guide
− 30 −
Strong
wind
Fig. 8-5-1
FILE NO. SVM-08028
8-5-2. Refrigerant piping connection
1. Cut the pipe with a pipe cutter.
90°
Obliquity
Roughness Warp
Fig. 8-5-2
2. Insert a flare nut into the pipe, and flare the pipe.
• Projection margin in flaring : A (Unit : mm)
A
Die
Pipe
Fig. 8-5-3
Outer dia.
of copper pipe
Rigid Imperial
A
(Unit : N·m)
Outer dia.
of copper pipe
∅
6.35
16 to 18 (1.6 to 1.8 kgf·m)
Tightening torque
∅9.52 30 to 42 (3.0 to 4.2 kgf·m)
• Tightening torque of flare pipe connections
Flare at indoor unit side
Flare at outdoor unit side
Fig. 8-5-4
6.35 0.5 to 1.0 1.0 to 1.5
9.52 0.5 to 1.0 1.0 to 1.5
<Tightening connection>
Align the centers of the connecting pipes and tighten
the flare nut as far as possible with your fingers. Then
tighten the nut with a spanner and torque wrench as
shown in the figure.
CAUTION
• Do not apply excess torque.
• Otherwise, the nut may crack depending on the
conditions.
Externally
threaded side
Use a wrench to secure.
Mark line
Fig. 8-5-5
Flare nutHalf union
Internally
threaded side
Use a torque wrench to tighten.
Fig. 8-5-6
CAUTION
•
KEEP IMPORTANT 4 POINTS FOR PIPING WORK
(1) Take away dust and moisture (Inside of the
connecting pipes.)
(2) Tight connection (between pipes and unit)
(3) Evacuate the air in the connecting pipes using
VACUUM PUMP.
(4) Check gas leak (connected points)
− 31−
FILE NO. SVM-08028
8-5-3. Evacuating
After the piping has been connected to the indoor unit,
you can perform the air purge together at once.
AIR PURGE
Evacuate the air in the connecting pipes and in the
indoor unit using
a vacuum pump. Do not use the refrigerant in the
outdoor unit.
For details, see the manual of the vacuum pump.
<Using a vacuum pump>
Be sure to use a vacuum pump with counter-flow
prevention function so that inside oil of the pump does
not flow backward into pipes of the air conditioner
when the pump stops. (If oil inside of the vacuum pump
enters into the air conditioner, which use R410A,
refrigeration cycle trouble may result.)
1. Connect the charge hose from the manifold valve to
the service port of the gas side packed valve.
2. Connect the charge hose to the port of the vacuum
pump.
3. Open fully the low pressure side handle of the
gauge manifold valve.
4. Operate the vacuum pump to start evacuating.
Perform evacuating for about 15 minutes if the piping
length is 20 meters. (15 minutes for 20 meters)
(assuming a pump capacity of 27 liters per minute.)
Then confirm that the compound pressure gauge
reading is −101 kPa (76 cmHg).
5. Close the low pressure side valve handle of gauge
manifold.
6. Open fully the valve stem of the packed valves
(both sides of Gas and Liquid).
7. Remove the charging hose from the service port.
8. Securely tighten the caps on the packed valves.
<Packed valve handling precautions>
• Open the valve stem all the way out; but do not try
to open it beyond the stopper.
• Securely tighten the valve stem cap with torque in
the following table:
Gas side30 to 42 N·m
(∅9.52 mm)(3.0 to 4.2 kgf·m)
Liquid side16 to 18 N·m
(∅6.35 mm)(1.6 to 1.8 kgf·m)
Service port
9 to 10 N·m
(0.9 to 1.0 kgf·m)
Hexagonal wrench
is required.
mm
4
Fig. 8-5-8
Compound
pressure gauge
-101 kPa
(76 cmHg)
Handle Lo
Charge hoseCharge hose
Connecting pipe
Packed valve at gas side
Service port (Valve core (Setting pin))
Packed valve at liquid side
Pressure gauge
Vacuum pump adapter
for counter-flow
prevention
Fig. 8-5-7
Manifold valve
Handle Hi
(Keep full closed)
Vacuum
pump
− 32 −
FILE NO. SVM-08028
8-5-4. Wiring connection
1. Remove the valve cover from the outdoor unit.
2. Connect the connecting cable to the terminal as
identified with their respective matched numbers on
the terminal block of indoor and outdoor unit.
3. When connecting the connecting cable to the
outdoor unit terminal, make a loop as shown in the
installation diagram of indoor and outdoor unit, to
prevent water coming in the outdoor unit.
4. Insulate the unused cords (conductors) from any
water coming in the outdoor unit. Proceed them so
that they do not touch any electrical or metal parts.
<Stripping length of connecting cable>
Terminal block
1(L) 2(N)
Cord clamp
10 mm
75 mm
Earth line
10 mm
65 mm
Terminal
screw
Connecting
cable
Screw
Earth
line
8-6. How to Set Remote Control Selector
Switch
When two indoor units ae installed in seperated rooms,
there is no need to change the selector switch.
<Remote control selector switch>
• When two indoor units are installed in the same
room or the adjacent two rooms, they may be
controlled simultaneously with a single remote
control. To prevent this, set either unit and its
remote control to B setting. (Both units are set to A
setting before shipment.)
• The remote control signal is not recived when the
indoor unit setting is different from the remote
control one.
1. Setting the remote control selector switch
with the indoor unit.
1. Press RESET button on the indoor unit to turn
the air conditioner ON.
2. Point the remote control at the indoor unit.
Note: 1. Repeat above step to reset Remote Control to be A.
2. Remote Control A has not “A” display.
3. Default setting of Remote Control from factory is A.
Fig. 8-5-9
CAUTION
• Wrong wiring connection may cause some
electrical parts burn out.
• Be sure to comply with local codes on running
the wire from indoor unit to outdoor unit (size of
wire and wiring method etc.)
• Every wire must be connected firmly.
NOTE
• Wire type: H07 RN-F or 245 IEC66 (2.0 mm2 or
more)
−33 −
FILE NO. SVM-08028
B
2. Set the remote control selector switch with the
remote control
[B] is indicated on the liquid crystal display when
setting remote control selector switch to B. [A] is
not indicated on the display even if the selector
switch is set to A.
1) Load the remote control with the batteries.
2) Press the [CHECK] button using something with
sharp point. (The preset temperature on the remote
control changes to [00].)
3) Press the [MODE] button while pressing the
[CHECK] button, [B] is indicted at the right of the
present temperature display.
• To reset the switch to the [A] setting, press the
[MODE] button again while pressing the [CHECK]
button.
8-7. Others
8-7-1. Gas leak test
Valve cover
Valve stem cap
connection
Service cap
connection
Fig. 8-7-1
• Check the flare nut connections, valve stem cap
connections and service port cap connections for
gas leak with a leak detector or soap water.
8-7-2. Test operation
To switch the TEST RUN (COOL) mode, press
RESET button for 10 seconds.
(The beeper will make a short beep.)
[MODE]
button
MODE
TEMP.
AUTO
COOL
DRY
AUTO FAN
START/STOP
SWING
MODE
RST
ONOFF SETCLR
TEMP.
FIX
CHK
TIMER
FAN
AUTO
B
QUIET
FAN
ECO
[CHECK]
button
Fig. 8-6-1
3. Confirm that the indoor unit can operate with
the new setting.
RESET button
Fig. 8-7-2
8-7-3. Auto restart setting
This product is designed so that, after a power failure,
it can restart automatically in the same operating mode
as before the power failure.
Information
The product was shipped with Auto Restart function
in the off position. Turn it on as required.
<How to set the auto restart>
• Press and hold the RESET button for about
3 seconds. the electronic beeper makes
three short beeps to tell you the Auto Restart
has been selected.
• To cancel the Auto Restart, follow the steps
described in the section Auto Restart Function of
the Owner’s Manual.
− 34 −
9. TROUBLESHOOTING CHART
FILE NO. SVM-08028
9-1. Troubleshooting Procedure
Follow the details of 9-2. Basic Check Items.
If there is no troub le corresponding to 9-2, check
whether or not there are faulty parts following
9-4. Self-Diagnosis by Remote Control.
9-2. Basic Check Items
9-2-1. Power supply voltage
The line voltage must be AC 220 − 240V. If it is not
within this range, the air conditioner may not operate
normally.
Table 9-2-1
No.
1
2 The indoor fan motor speed does not
The compressor is not turned off even
3
Operation of air conditioner
When the main power supply is turned on,
the OPERATION lamp on the indoor unit
blinks.
change in the Dry operation.
though the room temperature is in the
range that the compressor is turned off.
The OPERATION lamp blinks to indicate that power is turned on. If the
[START/STOP] button is pressed, the lamp stops blinking.
The indoor fan motor speed is automatically controlled in the Dry
operation.
The compressor has a function that it is not turned off for 3 minutes
after it is turned on even though the room temperature is in the range
that the compressor is turned off.
9-2-2. Incorrect cable connection between Indoor
and outdoor units
The indoor unit is connected to the outdoor unit with
5 cables (Heat pump model) or 3 cables (Cooling Only
model). Check that the indoor and outdoor units have
been properly connected with terminals assigned the
same numbers. If the connectors are not properly
connected, the outdoor unit will not operate normally,
or OPERATION lamp and TIMER lamp will blink (5Hz).
9-2-3. Program control
The microcontroller operates as shown in Table 9-2-1
to control the air conditioner. If there are any operational problems, check whether or not the problems
correspond to Table 9-2-1. If they correspond to the
Table, they are not problems with the air conditioner,
but they are indispensable operations to control and
maintain the air conditioner properly.
Descriptions
4 The compressor is not turned on and
off even though the thermo control is
operated in the Dry operation.
The compressor is not turned on even
5
though the room temperature is in the
range that the compressor is turned on.
6 The operation mode changes in the
Automatic operation.
7 The Auto Fan operation continues in the
Automatic operation.
8 The ECO operation
operation does not work.
In the Dry operation, the compressor is turned on and off automatically
at the regular intervals, independent of the thermo control.
The compressor is not turned on in the restart delay timer (3-minutes
timer) operation. It is also not turned on after the power supply is
turned on because of this timer operation.
In Automatic operation, the room temperature is detected all time
for control fan speed and the operation mode is changed every
15 minutes according to difference between the room temperature
and the preset temperature.
When the room temperature is in the range
(Preset temperature ± 1°C), the Auto Fan operation is selected.
These operations do not work when the unit is in the Dry
operation or Auto Fan operation.
− 35 −
9-3. Primary Judgement
9-3-1. Role of indoor unit controller
The indoor unit controller receives the operation
commands from the remote control and executes
them.
•Temperature measurement at the air outlet of the
indoor heat exchanger by the indoor temperature
sensor
•Temperature setting of the indoor heat exchanger by
the heat exchanger sensor
•Louver motor control
•Indoor fan motor operation control
•LED display control
•Transferring of operation commands to the outdoor
unit
Table 9-3-1
LampsSelf-diagnosis
FILE NO. SVM-08028
9-3-2. Failure diagnosis
The indoor unit diagnoses the operation condition and
indicates the information of the self-diagnosis with the
lamps on the display panel of the indoor unit.
AOPERATION lamp is blinking. (1Hz)
BOPERATION lamp is blinking. (5Hz)
COPERATION lamp is blinking. (5Hz)
DOPERATION lamp is blinking. (5Hz)
EOPERATION lamp is blinking. (5Hz)
FOPERATION and TIMER lamps are blinking.
(5Hz)
G OPERATION and TIMER lamps are blinking.
Table 9-3-2 Diagnosis by detective operation
SymptomCheckPrimary judgement
The remote control
does not work.
The outdoor fan
does not rotate.
Turn off the power supply once,
then turn it on. Try to operate
the remote control.
The compressor operates.
The compressor does not operate.
Power failure (when the power supply is turning on)
Thermo sensor (TA) short or break
Heat exchanger sensor (TC) short or break
Indoor fan motor lock or failure
Indoor P.C. board failure
Wrong wiring of connecting cable
Cycle failure
•Gas shortage or other refrigerant cycle trouble
•Heat exchanger sensor open, break or short
•Overload relay or thermostat trouble of compressor
The remote control
still does not work.
The remote control
works.
The indoor unit (and/or remote
control) is/are defective.
OK.
The outdoor unit (Outdoor fan
motor) is defective.
An internal part of the
compressor or PCB is defective.
−36−
9-4. Self-Diagnosis by Remote Control
(Check Code)
(1) If the lamps are indicated as shown B to G in Table
9-3-1, exchanger the self-diagnosis by the remote
control.
(2) When the remote control is set to the service
mode, the indoor controller diagnoses the operation condition and indicate the information of the
self-diagnosis on the display of the remote control
with the check codes. If a fault is detected, all
lamps on the indoor unit will blink at 5Hz and it will
beep for 10 seconds (Pi, Pi, Pi....). The timer lamp
usually blinks (5Hz) during the self-diagnosis.
9-4-1. How to use remote control in service mode
FILE NO. SVM-08028
(1) Press [CHK] button with a tip of pencil to set the
remote control to the service mode.
•
“00” is indicated on the display of the remote
control.
•
The timer lamp on the indoor unit blinks
continuously. (5 times per 1 sec.)
TEMP.
START/STOP
SWING
FIX
MODE
ONOFFSETCLR
WC-K10JE
RST
TIMER
CHK
ECO
FAN
(2) Press [8TEMP.] button.
If there is no fault with a code, the indoor unit will
beep once (Pi) and the display of the remote
control will change as follows:
00011d1E0222
•
Check the unit with all 35 check codes (00 to
22). as shown in Table 9-4-1.
•
Press [9TEMP.] button to change the check
code backwards.
If there is a fault, the indoor unit will beep for 10
seconds (Pi, Pi, Pi...).
Note the check code on the display of the remote
control.
•
2-digits alphanumeric will be indicated on the
display.
•
All lamps on the indoor unit will blink. (5 times
per 1 sec.)
•
Alphanumeric characters are used for the check code.
is 5.is 6.
is A.is B.
is C.is D.
(4) Press [START/STOP] button to release the service
mode.
•
The display of the remote control returns to as it
was before service mode was engaged.
– 37 –
Block level Diagnosis function
CheckCheck
code
Block
Indoor
P.C. board
code
SymptomConditionerCondition
Thermo. sensor
short/break.
Table 9-4-1
Continued
operation.
Air
status
Indicated
when detected
abnormal
FILE NO. SVM-08028
Judgement and action
1.Check thermo sensor.
2.If it is OK, check
P.C. board.
Cable
connection/
Thermal
fuse
Refrigerant
system
Heat exchanger
sensor
short/break.
Indoor fan lock,
abnormality of
indoor fan or
thermal fuse break.
Abnormality of other
indoor unit P.C.
board.
1) Wrong wiring or
disconnection of
connective cable.
2) Terminal fuse cut
off.
Continued
operation.
All off
All off
All off
Indicated
when detected
abnormal
Indicated
when detected
abnormal
Indicated
when detected
abnormal
Indicated
when detected
abnormal
1.Check heat exchanger
sensor.
2.If it is OK, check
P.C. board.
1.Check heat thermal
fuse is blow or not?
(Terminal block part.)
2.If the thermal fuse is
not blow, check indoor
fan motor.
(Refer to trouble
shooting flow charts.)
Replace P.C. borad.
1.Check connective
cable correct if wiring is
wrong.
2.Check thermal fuse
and Terminal blocks.
3.If it is OK, check
P.C. board.
Other parts
(including
compressor)
1) Overload relay or
thermostat for
compressor
All off
Indicated
when detected
abnormal
1.If overload relay and
break.
2.If refrigerant cycle is
3. If heat exchanger
Content detected by the check codes "
" o " t " are stored in memory of the microcomputer even if the
power supply is turned off. Therefore, contents of operations in the past are all displayed.
– 38−
themostat for compressor are OK, check
refrigerant cycle.
OK, check P.C. board.
sensor is OK, check
overload relay and
themostat for
compressor.
9-5. Troubleshootig Flowcharts
9-5-1. Power can not be turned on (No operation at all)
<Preliminary checks>
(1) Is the supply voltage normal?
(2) Is the connection to the AC output OK.?
Shut off the power supply
from AC outlet once and
turn it on after 5 seconds.
FILE NO. SVM-08028
Operation
Check Items
Main cause
Countermeasure
Symptom
Does the thermal
(Under PF. Terminal)
Is the indication voltage
NO
(DC12V or 5V) of main
P.C. board correct?
Is the voltage
across C27 measured
DC310 ~ 340V?
YES
NO
Does the fuse
(F01) blow?
fuse blow?
NO
Does the OPERATION
lamp blink?
Does the power turn on
by pushing the
button of the
remote control?
NO
NO
YES
Refer to the paragraph
"Pre-check", or defective circuit
before power P.C. board block.
YES
[START/STOP]
YES
YES
YES
Parts (R62, R63, SG01,
C25, C26, DB01, C27, T01)
are defective.
Wrong wiring of
AC cord or connecting
cable is defective.
Does the CN12
connector the wrong
connecting?
NONO
Does the transmission
indicator of remote
control flash normally
and transmit certainly?
(No problem)
YES
NO
YES
P.C. board is
defective.
Remote control is
defective.
Replace the remote
control.
Replace the
thermal fuse set.
Check connection.
Replace the main
P.C. board.
Re-wiring the cable.
Is the voltage
across C32
measured DC12V?
YES YES
* Be sure to disconnect the motor connector CN10 after shut off the power supply, or it will be a cause of damage of the motor.
Shut off the power
supply once, and turn
NO NO
it on again after
disconnecting the motor
connector CN10*.
Is the voltage across C32
measured DC12V?
Replace the main
Motor is defective.
– 39−
P.C. board.
9-5-2. Power can not be turned on after replacing indoor P.C. board
<Checking Procedure>
Connect the AC
Power supply
FILE NO. SVM-08028
Does the OPERATION
lamp blink?
YES
NONO
Black
White
Is it wired as shown
in Figure below?
YES
1 2
Indoor Terninal Block
Blue
Brown
Green/Yellow
Return the wiring of the
power relay is returned to
the normal procedure.
To the paragraph of
"No Power turns on".
CN31
4
RY01
3
Supply
AC 220~240V
50/60 Hz
– 40−
9-5-3. Outdoor unit does not operate
Shut off the power supply
from AC outlet once and turn
it on after 5 seconds.
FILE NO. SVM-08028
Does the OPERATION lamp blink?
YES
Does the power turn on by pushing
the [START/STOP] button
of the remote control?
YES
Is AC 220-240V supplied between
terminal block 1 -
Is cable connection between indoor
and outdoor units correct?
Check items as following procedure
in 9-5-4, 9-5-5, 9-5-6
YES
YES
2
?
NO
NO
NO
NO
See "Power can not be turned on".
See "Power can not be turned on".
Relays (RY01)
Q02 or IC30 is failure.
Correct cabling between indoor
and outdoor units.
Replace the
P.C. board.
– 41 −
9-5-4. Only compressor does not operate
Shut off the power supply
from AC outlet once and turn
it on after 5 seconds.
FILE NO. SVM-08028
Does the OPERATION lamp blink?
YES
Does the power turn on by
pushing the [START/STOP] button
of the remote control?
YES
Is the voltage across the indoor terminal
( 1 - 2 ) AC 220-240V?
YES
Is cable connection between indoor
and outdoor units correct?
YES
Is the voltage across the outdoor terminal
( 1 - 2 ) AC 220-240V?
YES
Are all the cords for compressor normal?
YES
NO
NO
NO
NO
NO
NO
See "Power can not be turned on".
See "Power can not be turned on".
Relays (RY01) or Q02
or IC30 is failure.
Correct cabling between indoor
and outdoor units.
Cables between indoor and
outdoor units are defective.
Re-wire or replace the defective cords.
Replace the
P.C. board.
Is the compressor motor winding normal?
(Check the winding resistor.)
YES
Is the capacitor for compressor normal.
YES
Is the overload relay normal?
YES
Does the compressor start?
YES
Compressor starts but
it stops after a while?
YES
Is the gas quantity normal?
(Check the pressure)
YES
Compressor is defective
NO
NO
NO
NO
NO
Compressor is defective.
Capacitor is defective.
Overload relay is defective.
Compressor is defective.
Gas shortage (Gas leakage)
− 42 −
9-5-5. Only outdoor fan does not operate
Shut off the power supply
from AC outlet once and
turn it on after 5 seconds.
FILE NO. SVM-08028
Does the OPERATION lamp blink?
YES
Does the power turn on by
pushing the [START/STOP] button
of the remote control?
YES
Is the voltage across the terminal
-
:
12
AC 220-240V?
YES
Is cable connection between indoor
and outdoor units correct?
YES
Is the voltage across the terminal
-
:
12
AC 220-240V?
YES
Are all the cords for outdoor
fan motor normal?
YES
NO
NO
NO
NO
NO
NO
See "Power can not be turned on".
See "Power can not be turned on".
Relays (RY01) or Q02
or IC30 is failure.
Correct cabling between indoor
and outdoor units.
Cables between indoor
and outdoor units are defective.
Correct the wire or
replace the defective cords.
Replace the
P.C. board.
Is the outdoor fan motor winding normal?
(Check the winding resistance)
YES
Is the capacitor for compressor normal?
YES
Outdoor fan motor is defective.
NO
NO
Outdoor fan motor is defective.
Capacitor for outdoor
fan motor is defective.
− 43 −
Shut off the
power supply once.
Turn the power supply.
FILE NO. SVM-08028
Does the fan stop in
no operating status?
YES
Start the operation
with low fan setting
in cool operation.
Does the fan rotate?
YES
Change the setting of
cooling to hight fan.
Does the fan speed
become higher?
YES
NO
NO
NO
Control P.C. board is defective.
Does AC 120V
or higher voltage apply
to between red and black
lead of fan motor?
YES
Shut off the power supply.
Does the cross flow
fan rotate normally?
YES
Turn on the power supply.
Operation
stops
NO
NO
Does connecting
terminal, connecting
cable or power supply
cord completely?
Does not found the short
wire about connecting
cable and power cord?
Repair the
bearing of
the fan.
Motor control circuit failure
(IC30, IC03, Q08) or 12V
power circuit failire.
Replace the P.C. board.
Replace the P.C. board.
NO
YES
Thermal fuse operated
due to prevent
temperature rising cause
of incompleted connecting.
Normal
Is the rotation signal (DC+12V-0V)
output between 2 (gray lead wire)
and 3 (brown lead wire) of the motor
connector (CN11) when rotating
the cross flow fan by hand in no
operating status?
(1 pulse/one turn)
YES
Replace the control
P.C. board.
−44 −
NO
Replace the fan motor
Replace connecting
the cable (or power cord),
thermal fuse and
terminal block.
FILE NO. SVM-08028
9-6. Troubleshooting for Remote Control (Including the Indoor P.C. Board)
There is no been from
Push the [START/STOP] button.
the indoor unit.
The operation lamp of
the air conditioner main
unit does not light.
Is there direct
sunlight on the
receptor of the air
conditioner?
YES
NO
Is there any
thyristor
fluorescent light
near by?
YES
NO
YES
NONO
Is operation possible
when setting the
temporary switch of the
air conditioner main unit
to "TEST RUN" or
"TEMPORARY AUTO"?
Does the transmission
indicator blink?
Is operation
possible when the
transmitter is moved
nearer to the infrared
signal receiver of the
air conditioner?
YES
Battery life
NO
Reset the remote control
by use the tip pencil push
in the RESET hole
Push the [START/STOP]
button
Dose the
transmission
indicator light?
YES
NO
Avoid direct
sunlight.
Keep the air
conditioner away
from thyristor
fluorescent light.
YES
Can any signal
tone be heard
when transmitting
within 5 cm distance
from the radio?
YES
P.C. board is failure.
Replace
P.C. board
NO
Replace the
batteries
NO
Normal
Is there any
beep and
operation?
YES
Remote control
is failure.
Replace remote
control.
−45 −
FILE NO. SVM-08028
9-6-1 How to check the P.C. board
(1) Operating precautions
1) When removing the front panel or the P.C. board,
be sure to shut off the power supply.
2) When removing the P.C. board, hold the edge of
the P.C. board and do not apply force to the
parts.
3) When connecting or disconnecting the connectors on the P.C. board, hold the Whole housing.
Do not pull at the lead wire.
(2) Inspection procedres
1) When a P.C. board is judged to be defective,
check for disconnection, burning, or discoloration of the copper foil pattern or this P.C. board.
2) The P.C. board consists of the following 2 parts
a. Main P.C. board part:
power relay, indoor fan motor drive circuit and
control circuit, C.P.U. and peripheral circuits,
buzzer drive circuit and buzzer.
b. Infrared rays receive and indication parts:
Infrared rays receiver unit and LED.
− 46 −
(3) Checking procedure
TVab
FILE NO. SVM-08028
le 9-6-1
No.
Shut off the power supply and
remove the P.C. board assembly
from the electronic parts base.
Remove the connecting cable from
the terminal block.
Remove the connector for the motor,
and turn the power on.
If the OPERATION lamp blinks
(0.5 sec. : ON, 0.5 sec. : OFF) when
the power turning on, the checking
points described as 1-4 of right
column are not necessary to
perform.
Make the operation status by
pushing once the [START/STOP]
button, except the status of [FAN
ONLY], [ON TIMER].
4
Start the operation with the system
which the time of the restart delay
timer is shortened.
ocedure
Check Point (Symptom)Causes
1.Is the fuse blown?
oltage chec
1.
Betw1een 4 of RY01 and CN31
(A2C 220~240V)
2.3Between + and − of C27
(DC 310 ~ 340V)
35. Between
41..•Between
Voltage check
1.Voltage of relay coil. (DC 12V)
Between pin C of Q02 and GND
2.Between No. 1 and 2 of
connecting cable terminal block.
(AC 220~240V)
1.All indicators light for 3 sec..
2. Indicators do not indicate normally
after approximate 3 sec..
k
5V andPrGND
12V
and
GND
Application of shoc
•Ov1.er•load bAy shor
par
C po
wer cord is def
oor contact of the ter
Miss wir
•2Capacitor (C25, C26) is def.ectivPe
Line filter (L01) is def
•
Diode (DB01) is def
3
IC02 is def
T01, DB01, R64, C27 are
detective.
1•.PBreaking wire of the rela
def•ectiv
}
e rela
oor contact of rela.y•.
Def
ectivee indicator., or poor
housing assemb
k v
t-circuit of the
ing of the po
ectivloew.
y dr
.2.
ly
. (CN12)
oltage
ectivtse..
minal plate.
wer relaivyer.
ectiv
ectiv
e1..
y coil,
.
Make the operation status by
pressing once the [START/STOP]
button.
1.The time of the restart delay timer
is shortened.
2.Cool operation
3.Air volume [AUTO]
4. Make the setting temperature lower
enough than room temperature.
5.Continuous operation.
6
Turn the power on after connecting
the motor connector. Start the
operation with the following
condition.
1.Operation [Cooling]
2.Airflow [High fan]
3.Continuous operation
1.Compressor does not operate.
2.OPERATION lamp blinks.
1.Motor does not rotate. (The key
operation is accepted.)
2.The Motor rotates, but it vibrates
too much.
The temperature of the indoor
heat e. xchanger is abnor
er4..
2.
Poor contact of the heat
exchanger sensor. (The connector
is disconnected.) (CN01)
3.Heat exchanger sensor, main
P.C. board are defective. (Refer to
Table 9-6-2 for the judgment of
defective resistance values.)
4.Main P.C. board is defective.
1.Poor contact of the motor
connector.
2.P.C. board is defective.
mally
− 47 −
FILE NO. SVM-08028
Table 9-6-3 Approximate resistance value of thermo sensor
Temperature0°C10°C20°C25°C30°C
Resistance value33.820.3512.5910.007.99
9-6-3. How to shorten time of restart delay timer
1
Press [CLR] button while pressing [CHK] button
with a tip of a pencil.
2
Then press [START/STOP]
signal to the indoor unit.
2
MODE
AUTO
COOL
DRY
AUTO FAN
SWING
MODE
TEMP.
Hr.ON OFF
TEMP.
START/STOP
FIX
ECO
RST
CHK
TIMER
FAN
AUTO
QUIET
FAN
1
(kΩ)
ONOFFSETCLR
− 48 −
FILE NO. SVM-08028
10. PART REPLACEMENT
10-1. Indoor Unit
No. Part name Procedures Remarks
1 Front panel
2 Electrical part
How to remove the front panel
1) Stop the operation of the air conditioner and
turn off its main power supply.
2) Pull the air inlet grille toward you to open it
and remove the air inlet grille.
Then remove the 2 screws fixing the front
panel.
3) First open the horizontal louver, and then
remove the front panel from the back body
by pulling it toward you.
How to mount the front panel
Push the front panel back in and make sure
all hooks are locked.
How to remove the electrical part.
1) Remove the front panel with procedure 1 .
2) Remove the screw holding the electrical part
cover.
3) Disconnect the 3 connectors 2-(3P) for the fan
motor and the connector (5P) for the louver
motor from the P.C. board assembly.
4) Pull out the TC sensor from the sensor
holder.
5) Remove the screw for the ground connection,
remove the screw for the electrical part box.
Then remove the LED and the electrical part
box from the main unit.
2
2
2 2-Screws
3
2 Screws
4 TC Sensor
2
3 Horizontal
louver
How to mount the electrical part.
1) To put back the electrical part box, lock it to
the upper hook of the back body.
2)
Tighten the screws on the electrical part box.
3) Connect the 3 connectors and arrange the
wiring same as original condition and then
tighten the screw from the LED unit to the
back body.
4) Attach the TC sensor to the holder.
5) Tighten the screw for the ground connection.
6) Tighten the screw on the electrical part cover.
1) Remove the front panel and the electrical
part following procedure 2.
2) Remove the center shaft of the horizontal
louver from the back body.
3) Remove the left shaft from the back body.
4) Remove the horizontal louver from the back
body.
3 Left shaft
3-Connectors
5
2 Center shaft
3
Screws
− 49 −
FILE NO. SVM-08028
No. Part name Procedures Remarks
4 Heat exchanger
5 Cross flow fan
1) Remove the front panel, electrical part and
the horizontal louver following procedure 3.
2) Remove the pipe holder at the rear side of
main unit.
3) Remove the 2 screws on the heat exchanger
at the base bearing.
4) Remove the screw on the heat exchanger
at the fixed plate from the back body and then
pull out the right hand side until the socket of
heat exchanger released from the hook of the
band motor (L), and then pull out the upper
side of heat exchanger slowly.
1) Remove the front panel, electrical part,
horizontal louver and the heat exchanger
following procedure 4.
2) Remove the 2 screws on the band motor (L)
and remove the 2 screws on the band motor
(R) and then remove the cross flow fan.
3) Loosen the set screw of the cross flow fan
then separate the fan and the fan motor.
Notice
To assemble cross flow fan and fan motor to the
unit, please turn the fan motor unit the center of
its terminal meets the top position of band motor
(R).
Fix the cross flow fan with the set screw at the
position where the gap between the back body
and the right surface of the cross flow fan is
4.7 mm.
2 Pipe holder
3
2-Screws
2-Screws (R)
2
2-Screws (L)
2
4.7 mm
6 Set screw
Middle of the fan motor terminal
4 Screws
6 Base bearing
1) Remove the front panel, electrical part,
horizontal louver, heat exchanger and the
cross flow fan following procedure 5.
2) Remove the 2 screws fixing the base bearing.
3) Remove the bearing from the base bearing. If
the housing protrudes from the base bearing,
put the housing in position and attach the
bearing to the base bearing.
−50 −
2
2-Screws
FILE NO. SVM-08028
10-2. Outdoor Unit
No.Part nameProceduresRemarks
1Common
procedure
1. Detachment
1) Stop operation of the air conditioner, and
turn off the main switch and breaker of the
air conditioner.
2) Remove the valve cover. (ST1T∅4 x 10s
1 pc)
• After removing screw, remove the valve
cover pulling it downward.
3) Remove the wiring cover (ST1T∅4 x 10s2
pcs.), and then remove the power cord,
connecting cable, and cord clamp
(ST2T∅4 x 16s2 pcs.).
4) Remove the upper cabinet.
(ST1T∅4 x 10s5 pcs.)
• After removing screws, remove the
upper cabinet pulling it upward.
2. Attachment
1) Attach the upper cabinet.
(ST1T∅4 x 10s5 pcs.)
• Hook the rear side of the upper cabinet
to the claw of the rear cabinet, and then
place it on the front cabinet.
2) After connecting the power cord and
connecting cable, attach the cord clamp
and wiring cover.
• Insert the upper part into the upper
cabinet, and insert the claw which has
been hooked to the lower part into the
square hole, and then fix it with screw.
(ST1T∅4 x 10s 1 pc.)
3)
Attach the valve cover. (ST1T∅4 x 10s 1 pc.)
• Insert the upper part to the upper
cabinet, set the hook claw of the valve
cover to square holes (at three
positions) of the main unit, and attach it
pushing upward.
Upper cabinet
Wiring cover
Valve cover
Upper cabinet
2Front cabinet
1. Detachment
1) Perform work of item 1 of 1.
2) Remove upper screw (ST1T∅4 x 10s3 pcs.)
of the front cabinet, and lower screws
(ST1T∅4 x 10s8 pcs.) of the front cabinet.
• Both side of front cabinet envelop the
unit, so remove it by pulling sideward.
2. Attachment
1) Assemble front cabinet to the unit.
2) Attach the removed screws to the original
positions.
– 51 –
FILE NO. SVM-08028
No.Part nameProceduresRemarks
3 Fan motor
4 Compressor
1) Perform work of item 1 of 1 and 1 of 2.
2) Remove the flange nut fixing the fan motor
and the propeller fan.
• Flange nut is loosened by turning
clockwise.
(To tighten the flange nut, turn counterclockwise.)
3) Remove the propeller fan.
4) Disconnect the connector for the fan motor
from the ASM-E-PARTS.
5) Remove the fixing screws (4 pcs.) holding
the fan motor by hand so that it does not
fall.
6) Cut the motor lead at the point which is
100 mm apart from the connector toward
the fan.
7) Use the connector used for the
ASM-E-PARTS, and pinch the lead wires
using the closed end splice.
1) Perform work of item 1 of
1 of 2,
3
1
,
2) Extract refrigerant gas.
3) Remove the partition board.
(ST1T∅4 x 10s 3 pcs.)
4) Remove the sound-insulation material.
5) Remove the terminal cover of the
compressor, and disconnect the lead wire
of the compressor thermo and the
compressor from the terminal.
6) Remove the pipe connected to the
compressor with a burner.
• Make sure the flame does not touch the
4 way valve.
7) Remove the fixing screw of the base plate
and heat exchanger.
(ST1T∅4 x 10s2 pcs.)
8) Pull upward the refrigeration cycle.
9) Remove the nut fixing the compressor to
the base plate.
Propeller fan
Flange nut
Compressor
Fan motor
100
Closed end
splice
– 52 –
FILE NO. SVM-08028
No.Part nameProceduresRemarks
5 Fan guard
1. Detachment
1) Perform work of item 1 of 1 and 1 of 2.
Requirement:
Perform the work on a corrugated
cardboard, cloth, etc. to prevent
scratches to the product.
2) Remove the front cabinet, and place it
down so that the fan guard side faces
downwards.
3) Remove the hooking claws by pushing a
minus screwdriver according to the arrow
mark in the right figure, and remove the
fan guard.
2. Attachment
1) Insert the claws of the fan guard in the
hole of the front cabinet. Push the hooking
claws (8 positions) by your hand and fix
the claws.
Requirement:
This completes all the attaching
work. Check that all the hooking
claws are fixed to the specified
positions.
Minus screwdriver
Hooking claw
6 Capacitor for
compressor
7 Capacitor for
fan motor
1) Perform the common procedure1.
2) Remove the fixing screw and the capacitor
band.
( 1-Screw ∅4 x 10s)
3) Disconnect the lead wires.
1) Perform the common procedure1.
2) Remove the fixing screw and the capacitor
band.
( 1-Screw ∅4 x 10s)
3) Disconnect the lead wires.
Capacitor for
compressor
Capacitor band
Screws
∅4 x 10s
Capacitor
for fan motor
Screws
∅4 x 10s
– 53 –
11. EXPLODED VIEWS AND PARTS LIST
11-1. Indoor Unit (E-Parts Assy)
FILE NO. SVM-08028
LocationPartLocationPart
No.No.No.No.
40143T60378 TERMINAL41043T62003 CORD CLAMP
40343T69371 SENSOR;HEAT EXCHANGER41143T69745 PC BOARD (RAS-07SKSX-1)
40443T69005 SENSOR;THERMOSTAT41143T69746 PC BOARD (RAS-09SKSX-1)
40543T69612 DISPLAY UNIT41443T60343 POWER CORD
40643T69364 FUSE,TEMPERATURE
DescriptionDescription
− 54 −
11-2. Indoor Unit
FILE NO. SVM-08028
LocationPartLocationPart
No.No.No.No.
20143T00462 FRONT PANEL ASSY21543T49006 HOLDER FOR PLATE
20243T09393 GRILLE OF AIR INLET21743T22312 BEARING ASSY, MOLD
20343T03358 BACK BODY ASSY21843T39319 BASE BEARING
20443T80315 AIR FILTER21943T20323 ASSY CROSS FLOW FAN
20543T09392 HORIZONTAL LOUVER22043T39320 MOTOR BAND(LEFT)
20643T70313 HOSE, DRAIN22143T39321 MOTOR BAND(RIGHT)
20743T79301 CAP-DRAIN22243T21393 FAN MOTOR
20843T21363 MOTOR; STEPPING22443T82309 INSTALLATION PLATE
20943T44424 REFRIGERATION CYCLE ASSY22543T69437 WIRELESS REMOTE CONTROL
21043T47353 PIPE; SUCTION (RAS-13)22643T63002 REMOTE CONTROL HOLDER
21143T47355 PIPE; SUCTION (U1U2_GD)22743T62326 TERMINAL COVER
21243T11317PIPE SHIELD22843T60317CORD MOTOR LOUVER
21343T19333HOLDER, SENSOR22943T07311PIPE HOLDER
21443T49329PLATE OF EVA SEAL
DescriptionDescription
− 55 −
11-3. Outdoor Unit (RAS-07S2AX-1)
27
29
FILE NO. SVM-08028
16
15
26
14
28
13
18
21
24
5
1
19
25
2
3
4
8,10
7,9
6
22
17
23
20
12
LocationPartLocationPart
No.No.No.No.
143T42335 BASE PLATE ASSEMBLY1643T19335 FAN GUARD
243T41365 COMPRESSOR(Made in China)1743T04304 PARTITION
343T49327 CUSHION,RUBBER1843T39326 MOTOR BASE CONNECTION PLATE
443T97001 NUT1943T39325 MOTOR BASE
543T43407 CONDENSER ASSEMBLY2043T19337 PACKED VALVE COVER
643T00448 FIXING PLATE VALVE2143T00481 UPPER CABINET
743T46332 VALVE;PACKED 6.35 DIA2243T96305BUSHING
843T00347 VALVE;PACKED 9.52 DIA2343T62323TERMINAL COVER
943T47331 BONNET, 6.35 DIA2443T19336FIN GUARD
1043T47332 BONNET, 9.52 DIA2543T54314RELAY;OVERLOAD
1143T47007 CAPILLARY TUBE; 1.2 DIA2643T61310ELECTRIC PARTS BASE
1243T00486 FRONT CABINET2743T55338 CAPACITOR,PLASTIC FILM
1343T21401 MOTOR;FAN2843T55325 CAPACITOR; PLASTIC-FILM
1443T20324 PROPELLER FAN2943T60367 TERMINAL-2P
1543T47001 NUT FLANGE
DescriptionDescription
− 55 −
11-4. Outdoor Unit (RAS-09SASX-1)
FILE NO. SVM-08028
LocationPartLocationPart
No.No.No.No.
143T42335 BASE PLATE ASSEMBLY1643T19335 FAN GUARD
243T41390 COMPRESSOR1743T04304 PARTITION
343T49327 CUSHION,RUBBER1843T39326 MOTOR BASE CONNECTION PLATE
443T97001 NUT1943T39325 MOTOR BASE
543T43406 CONDENSER ASSEMBLY2043T19337 PACKED VALVE COVER
643T00448 FIXING PLATE VALVE2143T00481 UPPER CABINET
743T46332 VALVE;PACKED 6.35 DIA2243T96305BUSHING
843T00347 VALVE;PACKED 9.52 DIA2343T62323TERMINAL COVER