Thank you for purchasing this Toshiba air conditioner.
This Installation Manual describes the installation method of the outdoor unit. For installation of indoor units, follow the
Installation Manual supplied with the indoor unit.
Moreover, as this installation manual includes the important articles concerning the “Machinery” Directive (Directive 2006/42/
EC), please read through the manual and make sure you understand it. After installation, give this Installation Manual, the
Owner’s Manual and the Installation Manual supplied with the indoor unit to the customer and tell the customer to keep them
safe.
Prepare an exclusive power source for indoor units, independent to that for outdoor units.
Y-shaped branching joints or a branching header (separately purchased) are required for connecting pipes between indoor and
outdoor units. Choose either of them considering the system capacity concerning piping. For installing branching pipes, refer to
the installation manual of the Y-shaped branching unit or branching header (separately purchased).
Outdoor connecting branching joints are required for connecting between outdoor units.
Generic Denomination: Air Conditioner
Definition of Qualified Installer or Qualified Service Person
The air conditioner must be installed, maintained, repaired and removed by a qualified installer or qualified service person.
When any of these jobs is to be done, ask a qualified installer or qualified service person to do them for you.
A qualified installer or qualified service person is an agent who has the qualifications and knowledge described in the table
below.
AgentQualifications and knowledge which the agent must have
• The qualified installer is a person who installs, maintains, relocates and removes the air conditioners made by
Toshiba Carrier Corporation. He or she has been trained to install, maintain, relocate and remove the air
conditioners made by Toshiba Carrier Corporation or, alternatively, he or she has been instructed in such
operations by an individual or individuals who have been trained and is thus thoroughly acquainted with the
knowledge related to these o perations.
• The qualified installer who is a llowed to do the electrical work in volved in installation, relocation and removal has
the qualifications pertaining to this electrical work as stipulated by the local laws and regulations, and he or she is
a person who has been trained in matters relating to electrical work on the air conditioners made by Toshiba Carrier
Corporation or, alternatively, he or she has been instructed in such matters by an individual or individuals who have
Qualified installer
Qualified service
person
been trained and is thus thoroughly acquainted with the knowledge related to this work.
• The qualified installer who is allowed to do the refrigerant handling and piping work involved in installation,
relocation and removal has the qualification s pertaining to this refrigerant handling an d piping work as stipulated
by the local laws and regulations, and he or she is a person who has been trained in matters relating to refrigerant
handling and piping work on the air conditioners made by Toshiba Carrier Corporation or, alternatively, he or she
has been instructed in such matters by an individual or individuals who have been trained and is thus thoroughly
acquainted with the knowledge related to this work.
• The qualified installer who is allowed to work at heights has been trained in matters relating to working at heights
with the air conditioners made by Toshiba Carrier Corporation or, alternatively, he or she has been instructed in
such matters by an individu al or individuals who have been trained and is thus thorou ghly acquainted with the
knowledge related to this work.
• The qualified service person is a person who installs, repairs, maintains, relocates and removes the air conditioners
made by Toshiba Carrier Corporation. He or she has been trained to install, repair, maintain, relocate and remove
the air conditioners made by Toshiba Carrier Corporation or, alternatively, he or she has been instructed in such
operations by an individual or individuals who have been trained and is thus thoroughly acquainted with the
knowledge related to these o perations.
• The qualified service person who is allowed to do the electrical work involved in installation, repair, relocation and
removal has the qualifications pertaining to this electrical work as stipulated by the local laws and regulations, and
he or she is a person who has been trained in matters relating to electrical work on the air conditioners made by
Toshiba Carrier Corporation or, alternatively, he or she has been instructed in such matters by an individual or
individuals who have been trained and is thus thoroughly acquainted with the knowledge related to this work.
• The qualified service person who is allowed to do the refrigerant handling and piping work involved in installation,
repair, relocation and removal has the qualifications pertaining to this refrigerant handling and piping work as
stipulated by the local laws and regulations, and he or she is a person who has been trained in matters relating to
refrigerant handling and piping work on the air conditioners made by Toshiba Carrier Corporation or, alternatively,
he or she has been instructed in such matters by an individual or individuals who have been trained and is thus
thoroughly acquainted with the knowledge related to this work.
• The qualified service person who is allowed to work at heights has been trained in matters relating to working at
heights with the air conditioners made by Toshiba Carrier Corporation or, alternatively, he or she has been
instructed in such matters by an individual or individuals who have been trained and is thus thoroughly acquainted
with the knowledge related to this work.
Definition of Protective Gear
When the air conditioner is to be transported, installed, maintained, repaired or removed, wear protective gloves and ‘safety’
work clothing.
In addition to such normal protective gear, wear the protective g ear described below when undertaking the special work detailed
in the table below.
Failure to wear the proper protective gear is dangerous because you will be more susceptible to injury, burns, electric shocks
and other injuries.
SMMS-i
Installation Manual
SMMS-i
Installation Manual
Work undertakenProtective gear worn
All types of work
Electrical-related
work
Work done at heights
(50 cm or more)
Transportation of
heavy objects
Repair of outdoor unit Gloves to provide protection for electricians and from heat
Protective gloves
‘Safety’ working clothing
Gloves to provide protec tion for electricians and from heat
Insulating shoes
Clothing to provide protection from electr ic shock
Helmets for use in industry
Shoes with additional protective toe cap
Warning Indications on the Air Conditioner Unit
Warning indicationDescription
WARNING
ELECTRICAL SHOCK HAZARD
Disconnect all remote
electric power supplies
before servicing.
WARNING
Moving parts.
Do not operate unit with grille
removed.
Stop the unit before the servicing.
CAUTION
High temperature parts.
You might get burned
when removing this panel.
CAUTION
Do not touch the aluminum
fins of the unit.
Doing so may result in injury.
CAUTION
BURST HAZARD
Open the service valves before
the operation, otherwise there
might be the burst.
CAUTION
Do not climb onto the
fan guard.
Doing so may result in injury.
WARNING
ELECTRICAL SHOCK HAZARD
Disconnect all remote electric power supplies before servicing.
WARNING
Moving parts.
Do not operate unit with grille removed.
Stop the unit before the servicing.
CAUTION
High temperature parts.
You might get burned when removing this panel.
CAUTION
Do not touch the aluminium fins of the unit.
Doing so may result in injury.
CAUTION
BURST HAZARD
Open the service valves before the operation, otherwise there might be the
burst.
CAUTION
Do not climb onto the fan guard.
Doing so may result in injury.
1PRECAUTIONS FOR SAFETY
WARNING
General
• Before starting to install the air conditioner, read through the Installation Manual carefully, and follow its instructions to install
the air conditioner. Otherwise, falling down of the unit may occur, or the unit may cause noise, vibration or water leakage.
• Only a qualified installer(*1) or qualified service person(*1) is allowed to do installationwork. If installation is carried out by
an unqualified individual, a fire, electric shocks, injury, water leakage, noise and/or vibration may result.
• If using separately sold products, make sure to use Toshiba specified products only. Using unspecified products may cause
fire, electric shock, water leak or other failure.
• Before opening the service panel of the outdoor unit, set the circuit breaker to the OFF position. Failure to set the circuit
breaker to the OFF position may result in electric shocks through contact with the interior parts. Only a qualified installer(*1)
or qualified service person(*1) is allowed to remove the service panel of the outdoor unit and do the work required.
• Before carrying out the installation, maintenance, repair or removal work, be sure to set the circuit breakers for both the
indoor and outdoor units to the OFF position. Otherwise, electric shock may result.
• Place a “Work in progress” sign near the circuit breaker while the installation, maintenance, repair or removal work is being
carried out. There is a danger of electric shocks if the circuit breaker is set to ON by mistake.
• Only a qualified installer(*1) or qualified service person(*1) is allowed to undertake work at heights using a stand of 50 cm
or more or to remove the intake grille of the indoor unit to undertake work.
• Wear protective gloves and safety work clothing during installation, servicing and removal.
• Do not touch the aluminium fin of the outdoor unit. You may injure yourself if you do so. If the fin must be touched for some
reason, first put on protective gloves and safety work clothing, and then proceed.
• Do not climb onto or place objects on top of the outdoor unit. You may fall or the objects may fall off of the outdoor unit and
result in injury.
• When working at height, put a sign in place so that no-one will approach the work location before proceeding with the work.
Parts or other objects may fall from above, possibly injuring a person below. Also, be sure that workers put on helmets.
• When cleaning the filter or other parts of the outdoor unit, set the circuit breaker to OFF without fail, and place a “Work in
progress” sign near the circuit breaker before proceeding with the work.
• When working at heights, put a sign in place so that no-one will approach the work location, before proceeding with the
work. Parts and other objects may fall from above, possibly injuring a person below.
• The refrigerant used by this air conditioner is the R410A.
• You shall ensure that the air conditioner is transported in stable condition. If you find any part of the product broken, contact
your dealer.
• Do not disassemble, modify, repair or move the product yourself. Doing so may cause fire, electric shock, injury or water
leaks. Ask a qualified installer or qualified service person to do any repairs or to move the product.
Selection of installation location
• If you install the unit in a small room, take appropriate measures to prevent the refrigerant from exceeding the limit
concentration even if it leaks. Consult the dealer from whom you purchased the air conditioner when you implement the
measures. Accumulation of highly concentrated refrigerant may cause an oxygen deficiency accident.
• Do not install in a location where flammable gas may leaks are possible. If the gas should leak and accumulate around the
unit, it may ignite and cause a fire.
• When transporting the air conditioner, wear shoes with protective toe caps, protective gloves and other protective clothing.
• When transporting the air conditioner, do not take hold of the bands around the packing carton. You may injure yourself if
the bands should break.
• Install the indoor unit at least 2.5 m above the floor level since otherwise the users may injure themselves or receive electric
shocks if they poke their fingers or other objects into the indoor unit while the air conditioner is running.
• Do not place any combustion appliance in a place where it is directly exposed to the wind of air conditioner, otherwise it may
cause imperfect combustion.
• Places where the operation sound of the outdoor unit may cause a disturbance. (Especially at the boundary line with
a neighbour, install the air conditioner while considering the noise.)
Installation
• Follow the instructions in the Installation Manual to install the air conditioner. Failure to follow these instructions may cause
the product to fall down or topple over or give rise to noise, vibration, water leakage or other failure.
• The designated bolts (M12) and nuts (M12) for securing the outdoor unit must be used when installing the unit.
• Install the outdoor unit property in a location that is durable enough to support the weight of the outdoor unit. Insufficient
durability may cause the outdoor unit to fall, which may result in injury.
• Install the unit in the prescribed manner for protection against strong wind and earthquake. Incorrect installation may result
in the unit falling down, or other accidents.
• Be sure to fix the screws back which have been removed for installation or other purposes.
EN
3-EN4-EN
–2–
5-EN6-EN
SMMS-i
Installation Manual
–3–
SMMS-i
Installation Manual
Refrigerant piping
• Install the refrigerant pipe securely during the installation work before operating the air conditioner. If the compressor is
operated with the valve open and without refrigerant pipe, the compressor sucks air and the refrigeration cycles is over
pressurized, which may cause a injury.
• Tighten the flare nut with a torque wrench in the specified manner. Excessive tighten of the flare nut may cause a crack in
the flare nut after a long period, which may result in refrigerant leakage.
• Ventilate the air if the refrigerant gas leaks during installation. If the leaked refrigerant gas comes into contact with fire, toxic
gas may be produced.
• After the installation work, confirm that refrigerant gas does not leak. If refrigerant gas leaks into the room and flows near a
fire source, such as a cooking range, noxious gas may be generated.
• When the air conditioner has been installed or relocated, follow the instructions in the Installation Manual and purge the air
completely so that no gases other than the refrigerant will be mixed in the refrigerating cycle. Failure to purge the air
completely may cause the air conditioner to malfunction.
• Nitrogen gas must be used for the airtight test.
• The charge hose must be connected in such a way that it is not slack.
• If refrigerant gas has leaked during the installation work, ventilate the room immediately. If the leaked refrigerant gas comes
in contact with fire, noxious gas may be generated.
Electrical wiring
• Only a qualified installer(*1) or qualified service person(*1) is allowed to carry out the electrical work of the air conditioner.
Under no circumstances must this work be done by an unqualified individual since failure to carry out the work properly may
result in electric shocks and/or electrical leaks.
• When connecting the electrical wires, repairing the electrical parts or undertaking other electrical jobs, wear gloves to
provide protection for electricians and from heat, insulating shoes and clothing to provide protection from electric shocks.
Failure to wear this protective gear may result in electric shocks.
• When executing address setting, test run, or troubleshooting through the checking window on the electric parts box, put on
insulated heat-proof gloves, insulated shoes and other clothing to provide protection fr om electric shock. Otherwise you may
receive an electric shock.
• Use wiring that meets the specifications in the Installation Manual and the stipulations in the local regulations and laws. Use
of wiring which does not meet the specifications may give rise to electric shocks, electrical leakage, smoking and/or a fire.
• Check that the product is properly earthed. (grounding work)
Incomplete earthing may cause electric shock.
• Do not connect the earth line to a gas pipe, water pipe, lightning conductor, or a telephone earth line.
• After completing the repair or relocation work, check that the ground wires are connected properly.
• Install a circuit breaker that meets the specifications in the installation manual and the stipulations in the local regulations
and laws.
• Install the circuit breaker where it can be easily accessed by the agent.
• When installing the circuit breaker outdoors, install one which is designed to be used outdoors.
• Under no circumstances must the power cable be extended. Connection trouble in the places where the cable is extended
may give rise to smoking and/or a fire.
• Electrical wiring work shall be conducted according to law and regulation in the community and installation manual.
Failure to do so may result in electrocution or short circuit.
• Do not supply power from the power terminal block equipped on the outdoor unit to another outdoor unit. Capacity overflow
may occur on the terminal block and may result in fire.
• When carrying out electric connection, use the wire specified in the Installation Manual and connect and fix the wires
securely to prevent them applying external force to the terminals. Improper connection or fixing may result in fire.
Test run
• Before operating the air conditioner after having completed the work, check that the electrical parts box cover of the indoor
unit and service panel of the outdoor unit are closed, and set the circuit breaker to the ON position. You may receive an
electric shock if the power is turned on without first conducting these checks.
• When you have noticed that some kind of trouble (such as when an error display has appeared, there is a smell of burning,
abnormal sounds are heard, the air conditioner fails to cool or heat or water is leaking) has occurred in the air conditioner,
do not touch the air conditioner yourself but set the circuit breaker to the OFF position, and contact a qualified service
person. Take steps to ensure that the power will not be turned on (by marking “out of service” near the circuit breaker, for
instance) until qualified service person arrives. Continuing to use the air conditioner in the trouble status may cause
mechanical problems to escalate or result in electric shocks or other failure.
• After the work has finished, be sure to use an insulation tester set (500V Megger) to check the resistance is 2 MΩ or more
between the charge section and the non-charge metal section (Earth section). If the resistance value is low, a disaster such
as a leak or electric shock is caused at user’s side.
• Upon completion of the installation work, check for refrigerant leaks and check the insulation resistance and water drainage.
Then conduct a test run to check that the air conditioner is operating properly.
Explanations given to user
• Upon completion of the installation work, tell the user where the circuit breaker is located. If the user does not know where
the circuit breaker is, he or she will not be able to turn it off in the event that trouble has occurred in the air conditioner.
• If you have discovered that the fan grille is damaged, do not approach the outdoor unit but set the circuit breaker to the OFF
position, and contact a qualified service person(*1) to have the repairs done. Do not set the circuit breaker to the ON position
until the repairs are completed.
• After the installation work, follow the Owner’s Manual to explain to the customer how to use and maintain the unit.
Relocation
• Only a qualified installer(*1) or qualified service person(*1) is allowed to relocate the air conditioner. It is dangerous for the
air conditioner to be relocated by an unqualified individual since a fire, electric shocks, injury, water leakage, noise and/or
vibration may result.
• When carrying out the pump-down work shut down the compressor before disconnecting the refrigerant pipe. Disconnecting
the refrigerant pipe with the service valve left open and the compressor still operating will cause air or other gas to be suck ed
in, raising the pressure inside the refrigeration cycle to an abnormally high level, and possibly resulting in rupture, injury or
other trouble.
• Never recover the refrigerant into the outdoor unit. Be sure to use a refrigerant recovery machine to recover the refrigerant
when moving or repairing. It is impossible to recover the refrigerant into the outdoor unit. Refrigerant recovery into the
outdoor unit may result in serious accidents such as explosion of the unit, injury or other accidents.
(*1) Refer to the “Definition of Qualif ied Installer or Qualified Service Per son.”
CAUTION
New Refrigerant Air Conditioner Installation
• THIS AIR CONDITIONER ADOPTS THE NEW HFC REFRIGERANT (R410A) WHICH DOES NOT DESTROY OZONE
LAYER.
• The characteristics of R410A refrigerant are; easy to absorb water, oxidizing membrane or oil, and its pressure is approx.
1.6 times higher than that of refrigerant R22. Accompanied with the new refrigerant, refrigerating oil has also been changed.
Therefore, during installation work, be sure that water, dust, former refrigerant, or refrigerating oil does not enter the
refrigerating cycle.
• To prevent charging an incorrect refrigerant and refrigerating oil, the sizes of connecting sections of charging port of the
main unit and installation tools are changed from those for the conventional refrigerant.
• Accordingly the exclusive tools are required for the new refrigerant (R410A).
• For connecting pipes, use new and clean piping designed for R410A, and please care so that water or dust does not enter.
To Disconnect the Appliance from Main Power Supply.
• This appliance must be connected to the main power supply by means of a switch with a contact separation of at least 3 mm.
The installation fuse (all type can be used) must be used for the power supply line of this conditioner.
SMMS-i
Installation Manual
SMMS-i
Installation Manual
2ACCESSORY PARTS
Part nameQ’tyShapeUsage
Owner’s Manual1–(Be sure to hand it to the customers.)
Installation Manual2–(Be sure to hand it to the customers.)
CD-ROM
(Owner’s manual,
Installation manual)
Attached pipe
(for Ø22.2)
Attached pipe
(for Ø28.6)
F-GAS label1Fill the items on the label after adding refrigerant.
1–
1
1
For other languages that do not appear in this Installation Manual,
Please refer to the enclosed CD-ROM.
Connecting pipe for gas side piping
(MAP080, MAP100 type)
Connecting pipe for gas side piping
(MAP120, MAP140, MAP160 type)
3INSTALLATION OF NEW REFRIGERANT
AIR CONDITIONER
This air conditioner adopts the new HFC refrigerant (R410A) which does not deplete the ozone layer.
• R410A refrigerant is vulnerable to impurities such as water, oxidizing membranes, or oils because the pressure
of R410A refrigerant is higher than that of the former refrigerant by approximately 1.6 times.
As well as the adoption of the new refrigerant, the refrigerating oil has been also changed. Therefore, pay
attention so that water, dust, former refrigerant, or refrigerating oil does not enter the refrigerating cycle of the
new refrigerant air conditioner during installation.
• To prevent mixing of refrigerant or refrigerating oil, the size of the charge port of the main unit or connecting
section of the installation tool differs to that of an air conditioner for the former refrigerant.
Accordingly, exclusive tools are required for the new refrigerant (R410A) as shown below.
• For connecting pipes, use new and clean piping materials so that water or dust does not enter.
Required Tools and Cautions on handling
It is necessary to prepare the tools and parts for installation as described below. The tools and parts which will be
newly prepared in the following items should be restricted to exclusive use.
Explanation of symbols
: Newly prepared (It is necessary to use it exclusively with R410A, separately from those for R22 or R407C.)
: Former tool is available.
Gauge manifold
Charging hoseExclusive to R410A
Charging cylinderCharging refrigerantUnusable (Use the Refrigerant charging balance.)
Gas leak detectorChecking gas leakExclusive to R410A
Vacuum pumpVacuum drying
Vacuum pump with counterflowVacuum dryingR22 (Existing article)
Flare toolFlare processing of pipesUsable by adjusting size
BenderBending processing of pipesR22 (Existing article)
Refrigerant recovery deviceRecovering refrigerantExclusive to R410A
Torque wrenchTightening flare nutExclusive to Ø12.7mm and Ø15.9mm
Vacuuming, charging refrigerant
and operation check
Welding of pipesR22 (Existing article)
Exclusive to R410A
Usable if a counter-flow preventive adapter is
attached
Exclusive to R410A
Enter the refrigerate name for identification
EN
7-EN8-EN
–4–
9-EN10-EN
SMMS-i
Installation Manual
–5–
SMMS-i
Installation Manual
4SELECTION OF INSTALLATION PLACE
Upon customer’s approval, install the air conditioner in a place which satisfies the following conditions:
• Place where it can be installed horizontally.
• Place which can reserve a sufficient service space for safe maintenance or checks.
• Place where there is no problem even if the drained water overflows.
Avoid the following places:
• Salty places (seaside area) or places with much gas sulfide (hot spring area) (If selecting such a place, special
maintenance is required.)
• Places where oil (including machine oil), steam, oil smoke or corrosive gas is generated.
• Places where an organic solvent is used.
• Chemical plants with a cooling system using liquid carbon dioxide.
• Places where a device generating high frequency (inverter, non-utility generator, medical apparatus, or
communication equipment) is set. (Malfunction or abnormal control of the air conditioner, or interference to
devices listed above may occur.)
• Places where discharged air from the outdoor unit blows against the windows of a neighbour's house.
• Places unable to bear the weight of the unit.
• Places with poor ventilation.
Installation space
Leave space necessary for running, installation and servicing.
Air intake
Air intake
Installation/servicing
500mm or more
(Rear side)
10mm or more
500mm or more
(Front side)
surface
20mm or more
Square hole for
handling
Outdoor unit top view
Air discharge
20mm or more
Air intake
Air intake
10mm or more
NOTE
• If there is an obstacle above the outdoor unit, leave a space of 2000mm or more to the top end of the outdoor unit.
• If there is a wall around the outdoor unit, make sure that its height does not exceed 800mm.
Handle the outdoor unit carefully, observing the following items.
• When using a forklift or other machinery for loading/unloading in transportation, insert the prongs of the forklift
into the rectangular holes for handling as shown below.
• When lifting up the unit, insert a rope able to bear the unit’s weight into the rectangular holes for handling, and
tie the unit from 4 sides.
(Apply padding in positions where the rope comes into contact with the outdoor unit so that no damage is caused
to the outer surface of the outdoor unit.)
(There are reinforcing plates on the side surfaces, so the rope cannot be passed through.)
GOODNO GOODNO GOOD
Plaster
Rope
Rectangular
holes for
handling
Front /Back
GOOD
Side
NO GOOD
Prongs of the
forklift
Plaster
Rectangular
holes for
lifting
Reinforcing
plate
EN
11-EN12-EN
–6–
13-EN14-EN
SMMS-i
Installation Manual
–7–
SMMS-i
Installation Manual
Weight centre and weight
◆ Weight centre of an outdoor unit
(A)
Anchor bolt position
700
755
Anchor bolt position
Y
6INSTALLATION OF THE OUTDOOR UNIT
WARNING
(B)
Anchor bolt position
920
755
Anchor bolt position
Y
• Be sure to install the outdoor unit in a place able to bear its weight.
If strength is insufficient, the unit may fall down resulting in human injury.
• Perform specified installation work to protect against strong wind and earthquakes.
If the outdoor unit is imperfectly installed, an accident by falling or dropping may be caused.
CAUTION
• Drain water is discharged from the outdoor unit. (Especially while heating)
Install the outdoor unit in a place with good drainage.
• For installation, be careful of the strength and level of the foundation so that abnormal sounds (vibration or noise)
are not generated.
REQUIREMENT
Installation in a snowfall area
1. Install the outdoor unit on a higher foundation than the snowfall or set up a stand to install the unit so that snowfall
will not affect the unit.
• Set up a stand higher than the snowfall.
• Apply an angled structure to the stand so that drainage will not be prevented. (Avoid using a stand with a flat
surface.)
2. Mount a snowfall-hood onto the air inlet and the air outlet.
• Leave enough space for the snowfall-hood so that it will not be an obstacle for the air inlet and the air outlet.
Snowfall-hood for air
outlet (locally procured)
Snowfall-hood for air
outlet
(4 faces)
(locally procured)
X
Z
No.Model typeX (mm)Y (mm)Z (mm)
MAP080
(A)
(B)
MAP120
MAP140
MAP160
500390645242241MAP100
605350700330330
Z
X
Weight (kg)
Heat pump modelCooling only model
Stand
(locally procured)
1. To install multiple outdoor units, arrange them with 20mm or more spaces in between.
Fix each outdoor unit with M12 anchor bolts at 4 positions. 20mm projection is appropriate for an anchor bolt.
20
20mm or more
20mm or more
M12 anchor bolt
4 positions/unit
SMMS-i
Installation Manual
SMMS-i
Installation Manual
• Anchor bolt positions are as shown below:
Continuous hole
(15 x 20 long hole)
310 or
more
AAA
Model typeAB
MAP080*, MAP1000*, MAP120*700990
MAP1404*, 1604*9201210
2. When drawing out the refrigerant pipe from the
underside, set the height of the stand to 500mm or
310 or
more
755
790
B
(Unit: mm)
3. Do not use 4 stands on the corner to support the
outdoor unit.
more.
NO GOODGOOD
500mm or more
4. Mount the vibration-proof rubber (including vibration-proof blocks) so that it fits under the whole clamping leg.
GOODGOOD
Install the vibration-proof
rubber so that the bent part
Anchor bolt
Vibration-proof rubber
of the fixing leg is
grounded.
5. Be careful of the connecting arrangement of the header unit and follower units. Set the outdoor units in order of
capacity from the one with the largest capacity. (A (Header unit) ≥ B ≥ C ≥ D)
• Be sure to use a header unit for the leading outdoor unit to be connected to the main pipe. (Figure 1 and 3)
• Be sure to use a T-shaped branch joint (RBM-BT14E/RBM-BT24E: separately purchased) to connect each
outdoor unit.
• Be careful of the direction of the Outdoor unit connection piping kit for the liquid side. (As shown in Figure 2, a
Outdoor unit connection piping kit cannot be attached so that the refrigerant of the main pipe flows directly into
the header unit.)
Liquid piping
▼ Figure 1▼ Figure 2
GOOD
Header unit AFollower unit BFollower unit
Main pipe
To the indoor unit
C
NO GOOD
Header unit AFollower unit BFollower unit
NO GOOD
Main pipe
To the indoor unit
C
Gas piping
▼ Figure 3▼ Figure 4
GOOD
Header unit AFollower unit BFollower unit
C
[Inverse connection of a gas-side branch unit]
NO GOOD
Header unit AFollower unit
B
Follower unit
C
Main pipe
NO GOODNO GOODNO GOOD
The bent part of the
fixing leg is not
grounded.
To the indoor unit
Extension valve
• When attaching a Y-shaped branch unit for the gas side, attach it level with the ground (Be sure not to exceed
Main pipe
To the indoor unit
To gas-side branch
unit
±15 degrees.). Regarding a T-shape branch joints for the liquid side, there is no restriction for its angle.
(Horizontal line)
A
B
(A arrow view)
Within ±15 degrees
(Horizontal line)
(B arrow view)
Within ±15
degrees
Do not connect
a branch unit
vertically.
At a level position
EN
15-EN16-EN
–8–
17-EN18-EN
SMMS-i
Installation Manual
–9–
SMMS-i
Installation Manual
When drawing pipes downward
▼ Figure 5▼ Figure 6
GOOD
Header unit AFollower unit BFollower unit
L-shaped
pipe
To gas-side branch
unit
C
To gas-side branch
unit
• Adding only one follower unit is possible. Install the additional unit so that its position is opposite to the header
unit. Use an extension valve for installation (See the figure above.).
Specify the pipe diameter in advance to allow for adding another unit.
[Vertical connection of branch units]
NO GOOD
To gas-side
branch unit
To gas-side
branch unit
7REFRIGERANT PIPING
WARNING
• If the refrigerant gas leaks during installation, ventilate the room.
If the leaked refrigerant gas comes into contact with fire, noxious gas may be generated.
• After installation, check that the refrigerant gas does not leak.
If the refrigerant gas leaks into the room and comes into contact with fire such as a fan heater, stove, or kitchen range,
noxious gas may be generated.
Connection of refrigerant pipe
• The refrigerant pipe connecting section is set in the
outdoor unit. Remove the front panel and the piping/
wiring panel. (M5: 9 pcs.)
• As shown in the illustration on the right, the hooks are
at the right and left sides of the front panel. Lift up and
remove the front panel.
• Pipes can be drawn out forward or downward from the
outdoor unit.
• When drawing out the pipe forward, draw it out to the
outside via the piping/wiring panel, and leave a space
of 500mm or more from the main pipe connecting the
outdoor unit with the indoor unit, considering service
work or other work on the unit. (For replacing the
compressor, 500mm or more space is required.)
• When drawing out the pipe downward, remove the
knockouts on the base plate of the outdoor unit, draw
o
m
m
0
e
r
0
o
5
m
D
r
a
w
(Left piping)
r
i
n
(Left
piping)
g
o
u
t
f
o
r
w
(Right
piping)
a
r
d
Drawing out
downward
the pipes out of the outdoor unit, and perform piping on
the right/left or rear side. Downward length of the balance pipe should be 5m or less.
Hook
Front panel
Piping/wiring panel
(Rear piping)
(Right piping)
Ball valve of gas
side
Packed valve of liquid
side
Packed valve of
balance pipe
(MAP080, MAP100, MAP120)(MAP140, MAP160)
Ball valve of gas
side
Ball valve of liquid
side
Packed valve of
balance pipe
SMMS-i
Installation Manual
SMMS-i
Installation Manual
REQUIREMENT
• For a welding work of the refrigerant pipes, be sure to use nitrogen gas in order to prevent oxidation of the inside
of the pipes; otherwise clogging of the refrigerating cycle due to oxidized scale may occur.
• Use clean and new pipes for the refrigerant pipes and perform piping work so that water or dust does not
contaminate the refrigerant.
• Be sure to use a double spanner to loosen or tighten the flare nut. If a single spanner is used, the required level
of tightening cannot be obtained. Tighten the flare nut with the specified torque. (If it is hard to loosen or tighten
the flare nut of the balance pipe or packed valve of the liquid side with a double spanner, loosen or tighten the
flare nut while holding the valve mounting plate with a spanner.)
Packed valve of
Outer dia. of
copper pipe
6.4 mm14 to 18 (1.4 to 1.8 kgf•m)
9.5 mm33 to 42 (3.3 to 4.2 kgf•m)
12.7 mm50 to 62 (5.0 to 6.2 kgf•m)
15.9 mm63 to 77 (6.3 to 7.7 kgf•m)
Tightening torque (N•m)
balance pipe
Ball valve of gas side
Packed valve of liquid
side
Pipe connection method of valve at the gas side (Example)
Type
MAP080
MAP100
Pipe
diameter
Ø22.2
Draw-out forwardDraw-out downward
Cut the L-shaped pipe at the horizontal straight
section, then braze the supplied attachment
pipe and the socket and pipe procured locally.
Gas
Liquid
pipe
Balance
pipe
Cut the L-shaped pipe at the horizontal straight
section, then braze the supplied attachment
pipe and the socket and pipe procured locally.
Gas pipe
Attachment
pipe
Socket
Pipe
pipe
Section to be
cut
Cut the L-shaped pipe at the vertical straight
section, then braze the supplied attachment
pipe and the socket and pipe procured locally.
Liquid
pipe
Balance
pipe
Cut the L-shaped pipe at the vertical straight
section, then braze the supplied attachment
pipe and the socket and pipe procured locally.
Gas pipe
Attachment
pipe
Socket
Pipe
Gas
pipe
Section
to be cut
Type
MAP140
MAP160
Pipe
diameter
Ø28.6
Draw-out forwardDraw-out downward
Cut the L-shaped pipe at the horizontal straight
section, then braze the supplied attachment
pipe, and the socket and pipe procured locally.
Gas
Liquid
pipe
Balance
pipe
Gas pipe
Attachment pipe
Socket
Pipe
pipe
Section
to be cut
Cut the L-shape pipe at the vertical straight
section, then braze the supplied attachment
pipe, and the socket and pipe procured locally.
Liquid
pipe
Balance
pipe
Gas pipe
Attachment
pipe
Socket
Pipe
Gas
pipe
Section
to be cut
Extruding margin of copper pipe with flare machining: B (Unit: mm)
Copper pipe outer
dia.
9.5
12.7
15.9
When using R410A
tool
0 to 0.51.0 to 1.5
When using
conventional tool
B
Extruding margin of copper pipe with flare tools: A (Unit: mm)
Copper pipe outer dia.A
9.513.2
12.716.6
15.919.7
* When using the conventional flare tool, to connect R410A pipes with flaring, make a margin approx. 0.5mm
longer than that of an R22 pipe so that the flare size matches the one specified. It is convenient to use a copper
pipe gauge for size adjustment of the extruding margin.
+0
-0.4
A
MAP120
Ø28.6
pipe
Balance
pipe
Gas pipe
Attachment pipe
Socket
Pipe
Gas
pipeLiquid
Section to be
cut
Liquid
pipe
Balance
pipe
Gas pipe
Attachment
pipe
Socket
Pipe
Gas
pipe
Section
to be cut
EN
19-EN20-EN
–10–
21-EN22-EN
SMMS-i
Installation Manual
–11–
SMMS-i
Installation Manual
Coupling size of brazed pipe
Connected section
External sizeInternal size
K
ØC
G
ØF
(Unit: mm)
Connected section
Standard outer dia.
of connected
copper pipe
6.356.35 (±0.03)6.45 ()760.06 or less0.50
9.529.52 (±0.03)9.62 ()870.08 or less0.60
12.7012.70 (±0.03)12.81 ()980.10 or less0.70
15.8815.88 (±0.03)16.00 ()980.13 or less0.80
19.0519.05 (±0.03)19.19 ()11100.15 or less0.80
22.2222.22 (±0.03)22.36 ()11100.16 or less0.82
28.5828.58 (±0.04)28.75 ()13120.20 or less1.00
34.9234.90 (±0.04)35.11 ()14130.25 or less1.20
38.1038.10 (±0.05)38.31 ()15140.27 or less1.26
41.2841.28 (±0.05)41.50 ()15140.28 or less1.35
External sizeInternal size
Standard outer dia.
(Allowable difference)
CFKG
+0.04
-0.02
+0.04
-0.02
+0.04
-0.02
+0.04
-0.02
+0.03
-0.03
+0.03
-0.03
+0.06
-0.02
+0.04
-0.04
+0.08
-0.02
+0.08
-0.02
Min. depth of
insertion
Oval value
Min. thickness
of coupling
Selection of pipe size
◆ Capacity code of indoor and outdoor units
Selection of pipe material
• For the indoor unit, the capacity code is decided at each capacity rank. (Table 1)
• The capacity codes of the outdoor units are decided at each capacity rank. The maximum number of connectable
indoor units and the total value of capacity codes of the indoor units are also decided. (Table 2)
NOTE
Compared with the capacity code of the outdoor unit, the total value of capacity codes of the connectable indoor units differs
based on the height difference between the indoor units.
• When the height difference between the indoor units is 15m or less: Up to 135% of the capacity code (Equivalent
to HP) of the outdoor unit (Equivalent to HP) of the outdoor unit
• When the height difference between the indoor units is over 15m: Up to 105% of the capacity code
Table 1
Indoor unit
capacity rank
0070.82.2
00912.8
0121.253.6
0151.74.5
01825.6
0242.57.1
02738
0303.29
036411.2
048514
056616
072822.4
0961028
Equivalent to HP
Capacity code
Equivalent to
capacity
Table 2
Outdoor unit
model name
(Standard model)
MMY-MAP0804∗822.413— — ——
MMY-MAP1004∗102816————
MMY-MAP1204∗1233.520————
MMY-MAP1404∗144023————
MMY-MAP1604∗164527MMY-AP1624∗164527
MMY-AP1814∗1850.430————
MMY-AP2014∗205633————
MMY-AP2214∗2261.537————
MMY-AP2414∗246840MMY-AP2424∗246840
MMY-AP2614∗267343MMY-AP2624∗267343
MMY-AP2814∗2878.547MMY-AP2824∗2878.547
MMY-AP3014∗308548MMY-AP3024∗308548
MMY-AP3214∗329048MMY-AP3224∗329048
MMY-AP3414∗349648MMY-AP3424∗349648
MMY-AP3614∗3610148MMY-AP3624∗3610148
MMY-AP3814∗38106.548MMY-AP3824∗38106.548
MMY-AP4014∗4011248MMY-AP4024∗4011248
MMY-AP4214∗4211848MMY-AP4224∗4211848
MMY-AP4414∗4412348MMY-AP4424∗4412348
MMY-AP4614∗4613048MMY-AP4624∗4613048
MMY-AP4814∗4813548MMY-AP4824∗4813548
Capacity code
Equivalent to HPEquivalent to
capacity
No. of
indoor
units
Outdoor unit
model name
(High Efficiency
model)
Capacity code
Equivalent to HPEquivalent to
capacity
No. of
indoor
units
* For combination of the outdoor units, refer to “Combination of outdoor units”.
SMMS-i
Outdoor unit
(3) Main
piping
Header
unit A
(8)
(2)
(6)
First branch
Y-shape
branching joint
Follower
Follower
unit B
unit C
(8)
(8)
(2)
(8) Outdoor unit connection piping kit (For linking of outdoor units)
(4)
(6)
Follower
unit D
(1)(1)(1)
(4) Branching pipe
(5) Indoor unit connecting pipe
Indoor unit
(4)
Indoor unit
(2) Balance pipes Ø9.5
(1) Outdoor unit connecting pipes
(7) Branching header
(5)(5)(5)(5)
(6)
(6)
(4)
(6) Y-shaped branching joint
(4)
(6)
(4)
Installation Manual
(5)(5)(5)(5)(5)
SMMS-i
No.
Piping partsNameSelection of pipe sizeRemarks
Connecting pipe size of outdoor unit
TypeGas sideLiquid side
Outdoor unit
È
(1)
Outdoor unit
connection piping
kit
Between Outdoor
unit connection
(2)
piping kits
Outdoor unit
connection piping
kit of header unit
(3)
È
First branching
section
Branching section
È
(4)
Branching section
Outdoor unit
connecting pipe
Main connecting
piping between
outdoor units
Main piping
Branching pipe
MAP080Ø22.2Ø12.7
MAP100Ø22.2Ø12.7
MAP120Ø28.6Ø12.7
MAP140Ø28.6Ø15.9
MAP160Ø28.6Ø15.9
Pipe size for connecting piping between outdoor units
Total capacity codes of
outdoor units at the
downstream side
Equivalent to HPEquivalent to
16 to below 22
22 to below 26
26 to below 36
36 or more101.0 or more Ø41.3Ø22.2
Size of main piping
Total capacity codes of all
capacity
45.0 to below
61.5
61.5 to below
73.0
73.0 to below
101.0
outdoor units
Equivalent to HPEquivalent to
8 to below 1222.4 to below 33.5 Ø22.2Ø12.7
12 to below 14 33.5 to below 38.4 Ø28.6Ø12.7
14 to below 22 38.4 to below 61.5 Ø28.6Ø15.9
22 to below 36
36 to below 46
46 or more130.0 or more* Ø41.3Ø22.2
* Maximum equivalent length of main pipe is 70m or less (The actual
length is 50m or less.).
Pipe size between branching sections *1
Total capacity codes of indoor
units at downstream side
Equivalent to HP
Below 2.4Below 6.6Ø12.7Ø9.5
2.4 to below 6.46.6 to below 18. 0Ø15.9Ø9.5
6.4 to below 12.2 18.0 to below 34.0Ø22.2Ø12.7
12.2 to below 20.2 34.0 to below 56 .5Ø28.6Ø15.9
20.2 to below 35.2 56.5 to below 98.5Ø34.9Ø19.1
35.2 or more98.5 ore moreØ41.3Ø22.2
61.5 to below
101.1 to below
Equivalent to
capacity
101.0
130.0
capacity
Gas
Liquid
side
side
Ø28.6Ø15.9
Ø34.9Ø19.1
Ø34.9Ø19.1
Gas
side
Ø34.9Ø19.1
Ø41.3Ø22.2
Gas
side
Balanc
e pipe
Ø9.5
Liquid
side
Liquid
side
Installation Manual
Same as connecting
pipe size of the
outdoor unit.
Pipe size differs based
on the total capacity
code value of outdoor
units at the
downstream side.
(See Table 2.)
Pipe size differs based
on the capacity code
of the outdoor unit.
(See Table 2.)
Pipe size differs based
on the total capacity
code value of indoor
units at the
downstream side. If
the total value
exceeds the capacity
code of the outdoor
unit, apply the
capacity code of the
outdoor unit. (See
Table 1 and 2.)
*1: If exceeding the main pip e size, set the size to the same as the
main pipe size.
23-EN24-EN
–12–
EN
25-EN26-EN
SMMS-i
No.
Piping partsNameSelection of pipe sizeRemarks
Connecting pipe size of indoor unit
Capacity rankGas side
Branching section
È
(5)
Indoor unit
Indoor unit
connecting pipe
007 to 012 type
015 to 018 typeØ12.7Ø6.4
024 to 056 typeØ15.9Ø9.5
072 to 096 typeØ22.2Ø12.7
Selection of branching section (Y-shaped branching joint)
15m or less real lengthØ9.5Ø6.4
Real length exceeds 15mØ12.7Ø6.4
Installation Manual
Liquid
side
Total capacity code of indoor units
Model name
Branching section
(6)
Y-shaped
branching joint
Equivalent to HP
Below 6.4Below 18.0RBM-BY55E
Y-shape
branching joint
Selection of branching section (Branching header)
6.4 to below 14.218.0 to below 40.0RBM-BY105E
14.2 to below 25.240.0 to below 70.5RBM-BY205E
25.2 or more70.5 or moreRBM-BY305E
Equivalent to
capacity
Total capacity code of indoor units
Model name
*3
Model name
Branching section Branching header
(7)
Outdoor unit
Branching section
(8)
connection piping
kit (For linking of
outdoor units)
Equivalent to HP
For 4
*2
Branching header
*2: Up to a total of 6.0 maximum equivalent to HP capacity codes is connectable to one line
after branching of header. When the total capacity codes of all outdoor units are 12 to below
26 (equivalent to HP) and you use a branching header for the first branching section, use
a RBM-HY2043E or RBM-HY2 083E regardless of the total capacity codes of outdo or units
at downstream side. In addition, you cannot use a branching header for the first branching
section when the total capacity codes of all outdoor units are over 26 (equivalent to HP).
Outdoor unit connection piping kit (For linking of outdoor units)
branches
For 8
branches
Below 14.2Below 40.0RBM-HY1043E
14.2 to below 25.2 40.0 to below 70.5 RBM-HY2043E
Below 14.2Below 40.0RBM-HY1083E
14.2 to below 25.2 40.0 to below 70.5 RBM-HY2083E
Equivalent to
capacity
Total capacity code of outdoor units
Equivalent to
capacity
Outdoor unit
connection piping
kit (For linking of
outdoor units)
Equivalent to HP
Below 26.0Below 73.0RBM-BT14E
26.0 or moreAbove 73.0RBM-BT24E
–13–
SMMS-i
Installation Manual
Allowable length of refrigerant pipes and allowable height
difference between units
D
Follower unit
Outdoor unit
A
B
Height
difference
between
outdoor
units
H3 ≤ 5 m
Height
difference
between
outdoor
and indoor
units:
H1 ≤ 70 m
Header
Follower
unit
La
LA
Outdoor unit connection piping kit
(For linking of outdoor units)
The longest piping between outdoor units:
L0 ≤ 25 m
Main piping L1
First branching
section
unit
Lb
LB
L3
Y-shaped
branching joint
C
Follower
unit
Ld
Lc
Outdoor unit connecting pipes
Branching header
Indoor unit connecting
pipe
Indoor unit
abcde
The longest piping length: L ≤ 235 m
The longest piping length fr om the first branch: Li ≤ 90 m
L4
f
g
Indoor unit
L7
L5
L6
h
Y-shaped branching
joint
i
j
(j)
Height
difference
between
indoor units:
H2 ≤ 40 m
*3: Downstream side when regarding the main piping as the start point
SMMS-i
Installation Manual
SMMS-i
Installation Manual
◆ System restriction
Outdoor unit combinationUp to 4 units
Total capacity of outdoor units Up to 48 HP
Indoor unit connection Up to 48 units
Total capacity of indoor units
(varies depending on the height difference between
indoor units.)
H2 ≤ 15m135% of outdoor units’ capacity
15m < H2105% of outdoor units’ capacity
◆ Cautions for installation
• Set the outdoor unit first connected to the bridging pipe to the indoor units as the header unit.
• Install the outdoor units in order of their capacity codes: A (header unit) ≥ B ≥ C ≥ D
• When connecting gas pipes to indoor units, use Y-shaped branching joints to keep pipes level.
• When piping to outdoor units using Outdoor unit connection piping kits, intersect the pipes to the outdoor unit
and those to indoor units at a right angle as shown in figure 1 on “6. INSTALLATION OF THE OUTDOOR UNIT”.
Do not connect them as in figure 2 on “6. INSTALLATION OF THE OUTDOOR UNIT”.
◆ Allowable length and allowable height difference of refrigerant piping
Item
Total extension of
pipe (liquid pipe,
real length)
Farthest piping length L (*1)
Main piping length
Pipe length
Height
difference
*1: Farthest outdoor unit from the first branch: (D), farthest indoor unit: (j)
*2: If the total capacity of outdoor units is 46HP or more, make the equivalent length 7 0m (real length 50m) or less .
*3: Make the difference 65m or less if the height difference between outdoor and indoor units (H1) is more than 3m.
*4: Make the difference 50m or less if the height difference between indoor units (H2) is more than 3m.
*5: Make the difference 30m or less if the height difference between indoor units (H2) is more than 3m.
Farthest equivalent piping length from the first branch Li
(*1)
Farthest equivalent piping length between outdoor units L0
(*1)
Maximum equivalent piping length of pipes connected to
outdoor units
Maximum real length of pipes connected to indoor units30ma, b, c, d, e, f, g, h, i, j
Maximum equivalent length betwee n branching sections50mL2, L3, L4, L5, L6, L7
Height between outdoor and indoor
units H1
Height between indoor units H240m–
Height between indoor units H35m–
Less than 96kW
96kW or more34HP or more500m
Less than 34HP or
less
Equivalent length235m
Real length190m
Equivalent length120m (*2)
Real length100m (*2)
Upper outdoor
units
Lower outdoor
units
Allowable
value
300m
LA + LB + La + Lb + Lc + Ld + L1 + L2 + L3 + L4
+ L5 + L6 + L7 + a + b + c + d + e + f + g + h + i + j
LA + LB + Ld + L1 + L3 + L4 + L5 + L6 + j
90m (*3)L3 + L4 + L5 + L6 + j
25mLA + LB + Ld (LA + Lb, LA + LB + Lc)
10m La, Lb, Lc, Ld
70m (*4)–
40m (*5)–
Pipes
L1
Airtightness test
After the refrigerant piping has been finished, execute an airtight test.
For an airtight test, connect a nitrogen gas canister as shown in the figure on the next page and apply pressure.
• Be sure to apply pressure from the service ports of the packed valves (or ball valves) at the liquid side, gas side
and balance pipe side.
• An airtight test can only be performed at the service ports at the liquid side, gas side and balance pipe side on
header unit.
• Close the valves fully at the gas side, liquid side and balance pipe side. As there is a possibility that the nitrogen
gas will enter into the cycle of outdoor units, re-tighten the valve rods at the liquid side and balance pipe side
before applying pressure.
(When using MAP140 or MAP160, you do not have to re-tighten the liquid side valve rod as their valves at the
liquid side are ball valves.)
• For each refrigerant line, apply pressure gradually in steps at the liquid side, gas side and balance pipe side.
Be sure to apply pressure at the gas side, liquid side, and balance pipe side.
WARNING
Never use oxygen, flammable gases, or noxious gases in an airtight test.
VLV
Copper
pipe
High pressure
gauge
Gauge
H
manifold
Reducing
valve
Nitrogen
gas
Connected to indoor unit
Main piping
Packed valve details
To gauge manifold
Liquid-side service port
Liquid-side valve
Balance
service port
Balance valve
Piping at site
To
outdoor
unit
Piping at site
To outdoor unit
Gas-side valve
To
outdoor
unit
Gas-side
service port
Piping at site
Connected to other follower units
Brazed
Fully
closed
Fully
closed
Able to detect a serious leakage
1. Apply pressure 0.3MPa (3.0kg/cm²G) for 5 minutes or more.
2. Apply pressure 1.5MPa (15kg/cm²G) for 5 minutes or more.
Available to detect slow leakage
3. Apply pressure 3.73MPa (38kg/cm²G) for approx. 24 hours.
Gas side valve fully closed
Header outdoor unit
Service port
Service port
Liquid valve fully closed
Service port
Balanced pipe side valve
fully closed
Low pressure
gauge
Copper pipe
• If there is no pressure decrease after 24 hours, the test is passed.
EN
27-EN28-EN
–14–
29-EN30-EN
SMMS-i
Installation Manual
–15–
SMMS-i
Installation Manual
NOTE
However, if the environmental temperature changes from the moment of applying pressure to 24 hours after that, the pressure
will change by about 0.01MPa (0.1kg/cm²G) per 1°C. Consider the pressure change when checking the test result.
REQUIREMENT
When pressure decrease is detected in steps 1-3, check the leakage at the connecting points.
Check the leakage using a foaming agent or other measures and seal the leak with re-brazing, flare retightening or other
methods. After sealing, execute an airtight test again.
Vacuum drying
• Be sure to perform vacuuming from both liquid and gas sides.
• Be sure to use a vacuum pump equipped with the counter-flow prevention function so that oil in the pump will
not flow back into piping for air conditioners. (If oil in the vacuum pump enters in the air conditioner with R410A
refrigerant, a problem may be caused in the refrigerating cycle.)
After finishing the airtight test and discharging nitrogen gas, connect the gauge manifold to the service ports of the liquid side,
gas side, and balance pipe side and connect a vacuum pump as shown in the figure below. Be sure to perform vacuuming for
the liquid, gas, and balance pipe sides.
Low pressure
gauge
Service port
Service port
Packed valve details
To gauge manifold
Liquid-side service port
Liquid-side valve
valve
To
outdoor
unit
Piping at site
Balance
service port
Balance
To
outdoor
unit
Piping at site
Main pipe
To outdoor unit
Gas-side valve
Gas-side
service port
Piping at site
Connected to indoor unit
Brazed
Fully
closed
Fully
closed
Follower units
Packed valve fully closed
(gas side)
Header outdoor unit
Service port
Packed valve fully closed
(liquid side)
Packed valve fully closed
(balance)
• Use a vacuum pump with a high vacuuming degree [-100.7kPa (5Torr, -755mmHg)] and large exhaust gas
amount (40L/minute or larger).
• Perform vacuuming for 2 or 3 hours, though the time differs depending on the pipe length. Check that all the
packed valves at the liquid side, gas side, and balance pipe side are fully closed.
• If the pressure does not reach -100.7kPa or less, continue vacuuming for 1 hour or more. If the pressure does
not reach -100.7kPa after 3 hours of vacuuming, stop vacuuming and check for air leakage.
• If the pressure reaches -100.7kPa or less after vacuuming for 2 hours or more, close the valves VL and VH on
the gauge manifold fully and stop the vacuum pump. Leave it as it is for 1 hour to confirm that the vacuuming
degree does not change.
If the degree of vacuum loss is large, moisture may remain in the pipes. In that case, inject dry nitrogen gas and
apply pressure to 0.05MPa and perform vacuuming again.
• After finishing the above procedure of vacuuming, exchange the vacuum pump with a refrigerant canister and
advance to the additional charging of refrigerant.
High pressure
gauge
VL VH
Vacuum pump
Gauge
manifold
P
SMMS-i
Installation Manual
SMMS-i
Installation Manual
Adding refrigerant
After finishing vacuuming, exchange the vacuum pump with a refrigerant canister and start additional charging of refrigerant.
Calculation of additional refrigerant charge amount
Refrigerant charge amount at shipment from the factory does not include the refrigerant for pipes at the local site.
For refrigerant to be charged in pipes at the local site, calculate the amount and charge it additionally.
NOTE
If the additional refrigerant amount indicates minus as the result of calculation, use the air conditioner without additional
refrigerant.
• Keeping the valve of the outdoor unit closed, be sure to charge the liquid refrigerant into the service port at the
liquid side.
• If the specified amount of refrigerant cannot be charged, fully open the valves of the outdoor unit at liquid and
gas sides, operate the air conditioner in COOL mode, and then charge refrigerant into service port at the gas
side. In this time, choke the refrigerant slightly by operating the valve of the canister to charge liquid refrigerant.
• The liquid refrigerant may be charged suddenly, therefore be sure to charge refrigerant gradually.
EN
31-EN32-EN
–16–
33-EN34-EN
SMMS-i
Installation Manual
–17–
SMMS-i
Installation Manual
Full opening of the valve
Open the valves of the outdoor unit fully.
MAP080
MAP100
MAP120
Packed valve
Using a 4mm-hexagonal wrench,
fully open the valve rods.
Liquid side
Balance pipe
Gas side
Balance packed valve
Using a 4mm-hexagonal wrench, fully open the valve rods.
Ball valve
Using a minus screwdriver, turn it counterclockwise by 90° until it hits the stopper.
(Full open)
MAP140
MAP160
Ball valve
Using a flathead screwdriver, turn it counterclockwise by 90° until it hits the
stopper. (Full open)
Service
port
Valve unit
Using flathead
screwdriver, turn it
counterclockwise by
(1)
(2)
90° until it hits the
stopper. (Full open)
Flare nut
Position of screwdriver slot
Fully closed
* When opened fully, do not apply
excessive torque after the screwdriver hits
the stopper; otherwise a problem may be
caused on the valve. (5 N•m or less)
Fully opened
Slot
F-GAS label
This product contains fluorinated greenhouse gases covered by the Kyoto Protocol
• Chemical Name of GasR410A
• Global Warming Potential (GWP) of Gas1975
CAUTION
1. Stick the enclosed refrigerant label adjacent to the charging and/or recovering location.
2. Clearly write the charged refrigerant quantity on the refrigerant label using indelible ink. Then, place the included
transparent protective sheet over the label to prevent the writing from rubbing off.
3. Prevent emission of the contained fluorinated greenhouse gas. Ensure that the fluorinated greenhouse gas is
never vented to the atmosphere during installation, service or disposal. When any leakage of the contained
fluorinated greenhouse gas is detected, the leak shall be stopped and repaired as soon as possible.
4. Only qualified service personnel are allowed to access and service this product.
5. Any handling of the fluorinated greenhouse gas in this product, such as when moving the product or recharging
the gas, shall comply under (EC) Regulation No. 842/2006 on certain fluorinated greenhouse gases and any
relevant local legislation.
6. Periodical inspections for refrigerant leaks may be required depending on European or local legislation.
7. Contact dealers, installers, etc., for any questions.
Pre-charged Refrigerant at Factory [kg],
R410A
specified in the nameplate
kg
Additional Charge on Installation Site
[kg]
kg
kg
Fully closed
Fully opened
Heat insulation for pipe
• Apply heat insulation of pipe separately at the liquid, gas, and balance sides.
• Be sure to use thermal insulator resistant up to 120°C or higher for pipes at the gas side.
Finishing after connecting pipes
• After piping connection work has been finished, cover the opening of the piping/wiring panel with the piping
cover, or fill silicon or putty into the space between the pipes.
• In case of drawing-out the pipes downward or sideward, also close the openings of the base plate and the side
plate.
• Under the opened condition, a problem may be caused due to the entering of water or dust.
SMMS-i
Installation Manual
SMMS-i
Installation Manual
When using the piping coverWhen not using the piping cover
Piping/wiring panel
Drawing-out
frontward
Drawing-out
downward
Drawing-out sideward
Close the opening with the
pipe cover.
Piping/wiring panel
Drawing-out
frontward
Drawing-out
downward
◆ Pipe holding bracket
Attach pipe holding brackets following the table below.
Diameter of pipe (mm)Interval
Ø15.9 - Ø19.12m
Ø22.2 - Ø41.33m
Drawing-out sideward
Fill silicon or putty into the
periphery of the pipes.
8ELECTRIC WIRING
WARNING
The appliance shall be installed in accordance with national wiring regulations.
Capacity shortages of the power circuit or an incomplete installation may cause an electric shock or fire.
CAUTION
• Perform wiring of power supply complying with the rules and regulations of the local electric company.
• Do not connect 380V - 415V power to the terminal blocks for control cables (U1, U2, U3, U4, U5, U6); otherwise,
the unit may break down.
• Be sure that electric wiring does not come into contact with high-temperature parts of piping; otherwise, the
coating of cables may melt and cause an accident.
• After connecting wires to the terminal block, take off the traps and fix the wires with cord clamps.
• Follow the same structure for both the control wiring and refrigerate piping.
• Do not conduct power to indoor units until vacuuming of the refrigerant pipes has finished.
• For the wiring of power to indoor units and that between indoor and outdoor units, follow the instructions in the
installation manual of each indoor unit.
Power supply specifications
Do not bridge the power between outdoor units
through the equipped terminal blocks (L
N).
Communication wiring between indoor and outdoor units
(Shield wire)
Communication wiring between indoor units (Shield wire)
U1 U2
ABABU2U1U2U1A BU2U1 A B
Indoor unit
ABABAB
Remote controller
Follower outdoor
Communication wiring between outdoor units (Shield wire)
Indoor unit
Remote controller
Remote controller
(Group control)
Indoor unit
Circuit breaker
(Earth leakage breaker)
Main switch
(Fuse)
• Communication wiring and central control wiring use 2-core non-polarity wires.
Use 2-core shield wires to prevent noise trouble.
In this case, for the system grounding, close (connect) the end of shield wires, and isolate the end of terminal.
Perform the ground of wires at one side only for the header outdoor unit.
• Use 2-core non-polarity wire for remote controller. (A, B terminals)
Use 2-core non-polarity wire for wiring of group control. (A, B terminals)
SMMS-i
Installation Manual
SMMS-i
Installation Manual
Be sure to keep the rule of below tables about size and length of communication wiring.
Central
control
controller
U1U3U2
U4
Outdoor unit
Indoor unit
Remote controller
Header
unit
U1 U2
L1
U1 U2
U3 U4
A B
U5 U6
Table-3
U1 U2
U1 U2
U3 U4
A B
Header
unit
U5 U6
Remote controller
Super modular multi system
U3 U4
U5 U6
U1 U2
A B
Table-1
Follower
unit
U3 U4
U1 U2
U5 U6
Table-1
L7
L4
U5 U6
U1 U2
Follower
unit
U1 U2
L5
A B
Follower
unit
U3 U4
U1 U2
L2L3
U1 U2
A B
Remote controller
U1 U2
U1 U2
U3 U4
A B
Header
unit
U5 U6
Table-2
U1 U2
Follower
unit
U3 U4
U1 U2
A B
L6
U5 U6
U1 U2
A B
Table-1Communication wiring between indoor and outdoor units (L1, L2, L3), Central control wiring
(L4)
Wiring2-core, non-polarity
TypeShield wire
Size/Length1.25 mm
(*1): Total length of Communication wiring length for all refrigerant circuits (L1 + L2 + L3 + L4)
2
: Up to 1000 m/2.0 mm2: Up to 2000 m (*1)
Table-2Communication wiring between outdoor units (L5)
Wiring2-core, non-polarity
TypeShield wire
Size/Length1.25 mm
2
to 2.0 mm2/Up to 100 m (L5)
◆ Group control through a Remote Controller
Group control of multiple indoor units (8 units) through a single remote controller switch
Indoor unit
No.1
ABABABABABAB
Remote controller
(A.B)
No.2
No.3
No.4
No.7
No.8
Connection of power wires and communication wires
Remove knockouts on the piping/wiring panel on the front of the unit and the panel on the bottom to get the power and
communication wires through the holes.
Piping/wiring panel
Knockout for the
communication wire
Knockout for the power
wire
NOTE
Be sure to separate the power wire and communication wires.
Knockout for the power
supply wire
Table-3Remote controller wiring (L6, L7)
Wire2-core, non-polarity
Size0.5 mm
Length
2
to 2.0 mm2
• Up to 500 m (L6 + L7)
• Up 400 m in case of wireless remote controller in group control.
• Up to 200 m total length of communication wiring between indoor units (L6)
EN
39-EN40-EN
–20–
41-EN42-EN
SMMS-i
Installation Manual
–21–
SMMS-i
Installation Manual
Screw size and tightening torque
Tightening torque
(N•m)
Power supply terminal
block
Screw size
Power supply terminalM62.5 to 3.0
Earth screwM85.5 to 6.6
Cord clamps
Communication
terminal block
Power supply wires
Cord clamp
Earth screw
Communication
wires
◆ Power supply wire connection
1. Insert the power supply wire through the cutout on the side of the electric parts box and connect the power supply
wire to the power supply terminal block and the earth line to the earth screw. After that, fix the power supply wire
with the 2 cord clamps.
2. Be sure to use round-type crimping terminals for power connection.
Also, apply insulating sleeves to the crimping parts. Use a driver of appropriate size to fix the terminal screws.
L1 L2 L3
N
◆ Communication wire connection
Get the communication wire through the cutout on the side of the electric parts box and connect it to the communication wire
terminals, then fix it with the communication cable clamp.
U1 U2 U3 U4 U5 U6
TO
INDOOR
UNIT
Screw size and tightening torque
Communication wire terminalM3.50.80 to 0.96
TO
CENTRAL
CONTROL
LER
TO
OUTDOOR
UNIT
U5, U6: Communication wiring between outdoor units
U
3, U4: Central control device
U
1, U2: Communication wiring between Indoor/Outdoor unit
Screw size
Tightening torque
(N•m)
10mm or more
Earth line
L1 L2 L3 N
Power supply wire
SMMS-i
Installation Manual
SMMS-i
Installation Manual
Regulation of high frequency wave
This equipment complies with IEC 61000-3-12 provided that the short-circuit power Ssc is greater than or equal to Ssc (*1)
at the interface point between the user’s supply and the public system. It is the responsibility of the installer or user of the
equipment to ensure, by consultation with the distribution network operator if necessary, that the equipment is connected
only to a supply with a short-circuit power Ssc greater than or equal to Ssc (*1)
Furthermore, when similar equipment or other equipment which may cause harmonic current emissions are to be
connected to the same interface point with this equipment, to reduce the risk of possible problems which may be caused
from addition of those harmonic current emissions, it is recommended to make sure that the short-circuit power Ssc at the
interface point is greater than the sum of the minimum Ssc required by all the equipment which will be connected to the
interface point.
Ssc (*1)
MMY-MAP0804HT8(Z)(ZG)-E
MMY-MAP0804T8(Z)(ZG)-E
MMY-MAP1004HT8(Z)(ZG)-E
MMY-MAP1004T8(Z)(ZG)-E
MMY-MAP1204HT8(Z)(ZG)-E
MMY-MAP1204T8(Z)(ZG)-E
MMY-MAP1404HT8(Z)(ZG)-E
MMY-MAP1404T8(Z)(ZG)-E
MMY-MAP1604HT8(Z)(ZG)-E
MMY-MAP1604T8(Z)(ZG)-E
ModelSsc (kVA)
1004
1290
1560
1692
1942
9ADDRESS SETTING
On this unit, it is required to set the addresses of the indoor units before starting air conditioning.
Set the addresses following the steps below.
CAUTION
• Be sure to complete the electric wiring before setting the addresses.
• If you turn on the outdoor unit before turning on the indoor units, the CODE No. [E19] is indicated on the 7segment display on the interface P.C. board of the outdoor unit until the indoor units are turned on. This is not a
malfunction.
• It may take up to ten minutes (normally about five minutes) to address one refrigerant line automatically.
• Settings on the outdoor unit are required for automatic addressing. (Address setting is not started simply by
turning on the power.)
• Running the unit is not required for address setting.
• The addresses can be set manually.
Automatic addressing:setting addresses using SW15 on the interface P.C. board on the header outdoor unit
Manual addressing:
REQUIREMENT
• High voltage parts exist in the electrical control box.
If you set addresses on an outdoor unit, operate the
unit through the access door shown on the illustration
on the right to avoid electric shock. Do not remove the
cover of electrical control box.
* After finishing operations, close the access door cover
and fix it with the screw.
setting addresses on the wired remote controller.
* When setting an address manually, the wired remote controller must temporarily be
paired with an indoor unit one-to-one. (when the system is organized for group
operation and no Remote controller)
Access
door cover
Cover of the electrical
control box
Fixing screw for the
access door cover
Automatic address setting
No central control:go to Address setting procedure 1
Central control of 2 or more refrigerant lines:go to Address setting procedure 2
(Example)
Address setting
procedure
System wiring
diagram
43-EN44-EN
–22–
When controlling a single refrigerant line
Outdoor
Indoor
Remote
controller
centrally
To procedure 1To procedure 2
Indoor
Central
remote
controller
Indoor
Central
remote
controller
Indoor
Remote
controller
Outdoor
Remote
controller
When controlling 2 or more refrigerant lines
Outdoor
Indoor
Remote
controller
centrally
Indoor
Remote
controller
Outdoor
Indoor
Remote
controller
Central
remote
controller
Indoor
EN
45-EN46-EN
SMMS-i
Installation Manual
–23–
SMMS-i
Installation Manual
◆ Address setting procedure 1
1 Turn on indoor units first, and then turn on outdoor units.
2 About one minute after turning the power on, confirm that the 7-segment display on the interface
P.C. board of the header outdoor unit indicates .
U. 1. L08 (U. 1. flash)
3 Press SW 15 to start the automatic address setting.
(It may take up to 10 minutes (normally about 5 minutes) to complete one line’s setting.)
4 The 7-segment display indicates .
After the indication, starts flashing on the display.
When the flashing stops and remain lit on the display, the setting is
U. 1. - - - (U. 1. flash)
Auto 1 → Auto 2 → Auto 3
U. 1. - - - (U. 1. light)
complete.
Interface P.C. board on the header outdoor unit
SW05SW15
SW04
D600 D601 D602 D603
D604
3
2,4
SW02SW03
SW01
REQUIREMENT
• When 2 or more refrigerant lines are controlled as a group, be sure to turn on all the indoor units in the group
before setting addresses.
• If you set the unit addresses of each line separately, each line’s header indoor unit is set separately. In that case,
the CODE No. “L03” (Indoor header unit overlap) is indicated as running starts. Change the group address to
make one unit the header unit using wired remote controller.
(Example)Controlling 2 or more refrigerant lines as a group
System wiring
diagram
Outdoor
Indoor
Remote
controller
Indoor
(Group control)
Outdoor
Indoor
Indoor
◆ Address setting procedure 2
1 Set a system address for each system using SW 13 and 14 on the interface P.C. board on the
header outdoor unit of each system.
(Factory default: Address 1)
NOTE
Be sure to set a unique address on each system. Do not use a same address as another system (refrigerant line) or a custom
side.
Interface P.C. board on the header outdoor unit
SW06SW07SW09SW10
12341234 12341234
SW11SW12SW13SW14
12341234 12341234
Switch settings for a line (system) address on the interface P.C. board on the outdoor unit
({: switch ON, ✕: switch OFF)
Line (system) address
1–––✕✕✕✕✕
2–––✕{✕✕✕
3–––✕✕{✕✕
4–––✕{{✕✕
5–––✕✕✕{✕
6–––✕{✕{✕
7–––✕✕{{✕
8–––✕{{{✕
9–––✕✕✕✕{
10–––✕{✕✕{
11–––✕✕{✕{
12–––✕{{✕{
13–––✕✕✕{{
14–––✕{✕{{
15–––✕✕{{{
16–––✕{{{{
17–––{✕✕✕✕
18–––{{✕✕✕
19–––{✕{✕✕
20–––{{{✕✕
21–––{✕✕{✕
22–––{{✕{✕
23–––{✕{{ ✕
24–––{{{{✕
25–––{
12341234
SW13SW14
✕✕✕{
SMMS-i
Installation Manual
SMMS-i
Installation Manual
Line (system) address
26–––{{✕✕{
27–––{✕{✕{
28–––{{{✕{
“–”: not used for system address setting (Do not change their positions.)
12341234
SW13SW14
2 Be sure to disconnect the relay connectors between the [U1U2] and [U3U4] terminals on all the
header outdoor units that will be connected to the central control. (Factory default: disconnected)
2
U1 U2 U3 U4 U5 U6
TO
INDOOR
UNIT
TO
CENTRAL
CONTROL
LER
TO
OUTDOOR
UNIT
3 Turn on indoor units first, and then turn on outdoor units.
4 About 1 minute after turning the power on, confirm that the 7-segment display on the interface
P.C. board of the header outdoor unit indicates .
U. 1. L08 (U. 1. flash)
5 Press SW 15 to start the automatic address setting.
(It may take up to 10 minutes (normally about 5 minutes) to complete one line’s setting.)
6 The 7-segment display indicates .
After the indication, starts flashing on the display.
When the flashing stops and , remains lit on the display, the setting is
U. 1. - - - (U. 1. flash)
Auto 1 → Auto 2 → Auto 3
U. 1. - - - (U. 1. light)
complete.
7 Repeat steps 4 to 6 for other refrigerant lines.
8 After completing address setting of all systems, turn off dip switch 2 of SW30 on the interface P.C.
boards of all the header outdoor units connected to the same central control, except the unit that
has the lowest address.
(For unifying the termination of the wiring for the central control of indoor and outdoor units)
9 Connect the relay connectors between the [U1, U2] and [U3, U4] terminals of the header outdoor
unit of each refrigerant line.
9
U1 U2 U3 U4 U5 U6
TO
INDOOR
UNIT
10
Set the central control address.
(For the setting of the central control address, refer to the installation manuals of the central control devices.)
Header unit interface P.C. board
7-segment
display
SW13SW14
12
SW30
TO
CENTRAL
CONTROL
LER
SW04
D600 D601 D602 D603 D604
SW01 SW02
OUTDOOR
SW05
TO
UNIT
SW15
SW03
EN
47-EN48-EN
–24–
49-EN50-EN
SMMS-i
Installation Manual
–25–
SMMS-i
Installation Manual
Switch setting (setting example when
controlling 2 or more refrigerant lines
centrally)
Outdoor units (setting manually)
Outdoor unit’s interface
P.C. board
SW13, 14
(Line (system) address)
Dip switch 2 of SW30
(Terminator of indoor/
outdoor communication
line and central control
line)
Relay connector
Header unit
Relay
connector
Header unit Follower unit Header unit Follower unit Header unitFactory default
Remote
(No setting
required)
(No setting
required)
Open
Header unit
connector
Relay
1
ON
Connect after
setting
addresses.
Follower unit
U3 U4U3 U4U3 U4U3 U4U3 U4
U1 U2
U5 U6 U1 U2 U5 U6U1 U2 U5 U6 U1 U2 U5 U6U1 U2
U1 U2U1 U2U1 U2U1 U2U1 U2
A
BABABABAB
Remote
controller
controller
Individual
2
Set to OFF
after setting
addresses.
Connect after
setting
addresses.
Remote
controller
Group
*The items in bold font must be set manually.
(No setting
required)
(No setting
required)
Open
Follower unit
31
Set to OFF
after setting
addresses.
Connect after
setting
addresses.
Header unit
Remote
controller
U5 U6
Relay
connector
ON
Open
controller
Central
control
CAUTION
Relay connector connection
Never connect relay connectors between the [U1, U2] and [U3, U4] terminals before completing address setting of all
the refrigerant lines. Otherwise, the addresses cannot be set correctly.
Manual address setting using the remote controller
Procedure when setting indoor units’ addresses first under the condition that indoor wiring has been completed and
outdoor wiring has not been started (manual setting using the remote controller)
▼ Wiring example of 2 refrigerant lines
Refrigerant line 1
Outdoor
unit
Indoor unit 1
Remote
controller
Line (system) address11122
Indoor unit address12312
Group address
Header unit2Follower unit2Follower unit2Follower unit2Follower unit
Indoor unit 2
1
Indoor unit 3
In the example above, disconnect the remote controller connections between the indoor units and connect
a wired remote controller to the target unit directly before address setting.
Refrigerant line 2
Outdoor
unit
Indoor unit 1
Indoor unit 2
Indoor units
(automatic setting)
Line (system) address11223
Indoor unit address12121
Group address00120
SET
SET DATA
2, 5, 8
TEMP.
4, 7, 10
FILTER
11
Pair the indoor unit to set and the remote controller
one-to-one.
Turn on the power.
SET
CL
1 Push and hold the , , and buttons at
the same time for more than 4 seconds.
LCD starts flashing.
TEST
RESET
UNIT No.
R.C. No.
CODE No.
CODE No.
ON / OFF
3, 6, 9
DATA
SETTING
TIMER SET
TIME
SET CL
TEST
1
SMMS-i
}
Installation Manual
SMMS-i
Installation Manual
<Line (system) address>
2 Push the TEMP. / buttons
repeatedly to set the CODE No. to .
3 Push the TIME / buttons repeatedly to
set a system address.
(Match the address with the address on the
interface P.C. board of the header outdoor unit in
the same refrigerant line.)
4 Push button.
<Indoor unit address>
SET
(It is OK if the display turns on.)
5 Push the TEMP. / buttons
repeatedly to set the CODE No. to .
6 Push the TIME / buttons repeatedly to
set an indoor unit address.
7 Push the button.
(It is OK if the display turns on.)
<Group address>
SET
8 Push the TEMP. / buttons
repeatedly to set the CODE No. to .
9 Push the TIME / buttons repeatedly to
set a group address. If the indoor unit is
individual, set the address to ; header
unit, ; follower unit, .
Individual : 0000
Header unit : 0001
Follower unit : 0002
10
Push the button.
(It is OK if the display turns on.)
11
Push the button.
The address setting is complete.
( flashes. You can contr ol the unit after
SETTINGSETTING
has disappeared.)
SET
TEST
In case of group
}
control
NOTE
1. Do not use address numbers 29 or 30 when setting
system addresses using the remote controller.
These 2 address numbers cannot be used on
outdoor units and the CODE No. [E04] (Indoor/
outdoor communication error) will appear if they are
mistakenly used.
2. If you set addresses to indoor units in 2 or more
refrigerate lines manually using the remote
controller and will control them centrally, set the
header outdoor unit of each line as below.
• Set a system address for the header outdoor unit
of each line with SW13 and 14 of their interface
P.C. boards.
• Turn off dip switch 2 of SW30 on the interface P.C.
boards of all the header outdoor units connected
to the same central control, except the unit that
has the lowest address. (For unifying the
termination of the wiring for the central control of
indoor and outdoor units)
• Connect the relay connectors between the [U1,
U2] and [U3, U4] terminals on the header outdoor
unit of each refrigerate line.
• After finishing all the settings above, set the
address of the central control devices. (For the
setting of the central control address, refer to the
installation manuals of the central control
devices.)
Confirming the indoor unit
addresses and the position of
an indoor unit using the
remote controller
◆ Confirming the numbers and
positions of indoor units
To see the indoor unit address of an
indoor unit which you know the position of
▼ When the unit is individual (the indoor unit is
paired with a wired remote controller one-toone), or it is a group-controlled one.
CODE No.
UNIT No.
FILTER
RESET
TEMP.
TEST
TIMER SET
TIME
SET CL
ON / OFF
1
Starts
running
2
(Execute it while the units are running.)
1 Push the button if the units stop.
2 Push the button (left side of the
button).
A unit numbers is indicated on the LCD (it will
disappear after a few seconds). The indicated
number shows the system address and indoor unit
address of the unit.
When 2 or more indoor units are connected to the
remote controller (group-controlled units), a
number of other connected units appears each
time you push the button (left side of the
button).
ON / OFF
To find an indoor unit’s position from its
address
▼ When checking unit numbers controlled as a
group
UNIT No.
R.C. No.
VENT
CODE No.
ON / OFF
1
2
TEST
DATA
SET
SETTING
TEMP.
TIMER SET
3
Stop
FILTER
RESET
TIME
SET CL
TEST
1
(Execute it while the units are stopped.)
The indoor unit numbers in a group are indicated one after
another. The fan and louvers of the indicated units are
activated.
1 Push and hold the and buttons at
the same time for more than 4 seconds.
• appears on UNIT No. on the LCD display.
• The fans and louvers of all the indoor units in the
group are activated.
2 Push the button (left side of the
button). Each time you push the button, the
indoor unit numbers are indicated one after
another.
• The first-indicated unit number is the address of
the header unit.
• Only the fan and louvers of the indicated indoor
unit are activated.
3 Push the button to finish the procedure.
All the indoor units in the group stop.
▼ To check all the indoor unit addresses using
an arbitrary wired remote controller.
(When communication wirings of 2 or more
TEST
EN
51-EN52-EN
–26–
53-EN54-EN
SMMS-i
Installation Manual
–27–
SMMS-i
Installation Manual
refrigerant lines are interconnected for central
control)
UNIT No.
R.C. No.
CODE No.
ON / OFF
2
4
5
TEST
DATA
SET
SETTING
TEMP.
TIMER SET
1
FILTER
RESET
TIME
TEST
SET CL
6
3
(Execute it while the units are stopped.)
You can check indoor unit addresses and positions of the
indoor units in a single refrigerant line.
When an outdoor unit is selected, the indoor unit numbers of
the refrigerant line of the selected unit are indicated one after
another and the fan and louvers of the indicated indoor units
are activated.
1 Push and hold the TIME and buttons
at the same time for more than 4 seconds.
At first, the line 1 and CODE No.
(Address Change) are indicated on the LCD
display. (Select an outdoor unit.)
2 Push the (left side of the button) and
SWING/FIX
buttons repeatedly to select a system
address.
3 Push the button to confirm the system
SET
address selection.
• The address of an indoor unit connected to the
selected refrigerant line is indicated on the LCD
display and its fan and louvers are activated.
4 Push the button (left side of the
button). Each time you push the button, the
indoor unit numbers of the selected
refrigerant line are indicated one after
another.
• Only the fan and louvers of the indicated indoor
unit are activated.
◆ To select another system address
5 Push the CL button to return to step 2.
• After returning to step 2, select another system
CL
address and check the indoor unit addresses of
the line.
6 Push the button to finish the procedure.
TEST
Changing the indoor unit
address using a remote
controller
To change an indoor unit address using a
wired remote controller.
▼ The method to change the address of an
individual indoor unit (the indoor unit is paired
with a wired remote controller one-to-one), or
an indoor unit in a group.
(The method is available when the addresses
have already been set automatically.)
UNIT No.
R.C. No.
ON / OFF
2, 6, 7
CL
CODE No.
4
TEST
DATA
SET
SETTING
TEMP.
3
5
8
Finish
FILTER
RESET
TIMER SET
TIME
SET CL
TEST
1
(Execute it while the units are stopped.)
1 Push and hold the , , and buttons at
the same time for more than 4 seconds.
(If 2 or more indoor units are controlled in a group,
the first indicated UNIT No. is that of the head
unit.)
SET
2 Push the button (left side of the
button) repeatedly to select an indoor unit
number to change if 2 or more units are
controlled in a group. (The fan and louvers
of the selected indoor unit are activated.)
(The fan of the selected indoor unit is turned on.)
3 Push the TEMP. / buttons
repeatedly to select for CODE No..
4 Push the TIME / buttons repeatedly to
change the value indicated in the SET DATA
section to that you want.
5 Push the button.
SET
6 Push the button (left side of the
button) repeatedly to select another indoor
UNIT No. to change.
Repeat steps 4 to 6 to change the indoor unit
addresses so as to make each of them unique.
7 Push the button (left side of the
button) to check the changed addresses.
8 If the addresses have been changed
correctly, push the button to finish the
procedure.
TEST
▼ To change all the indoor unit addresses using
an arbitrary wired remote controller.
(The method is available when the addresses
have already been set automatically.)
(When communication wirings of 2 or more
refrigerant lines are interconnected for central
control)
NOTE
You can change the addresses of indoor units in each
refrigerant line using an arbitrary wired remote controller.
* Enter the address check/change mode and change
the addresses.
UNIT No.
R.C. No.
CODE No.
ON / OFF
1
FILTER
RESET
SET
TEMP.
DATA
SETTING
TIMER SET
TIME
SET CL
TEST
2
3
If no number appears on UNIT No., no outdoor unit exists on
the line. Push button and select another line following
step
(Execute it while the units are stopped.)
1 Push and hold the TIME / buttons at
2 Push (left side of the button) and
CL
2.
the same time for more than 4 seconds.
At first, the line 1 and CODE No.
(Address Change) are indicated on the LCD
display.
SWING/FIX
buttons repeatedly to select a system
address.
Cancels the line selection
SMMS-i
Installation Manual
SMMS-i
Installation Manual
3 Push the button.
SET
• The address of one of the indoor units
connected to the selected refrigerant line is
indicated on the LCD display and the fan and
louvers of the unit are activated.
At first, the current indoor unit address is
displayed in
SET DATA.
(No system address is indicated.)
UNIT No.
R.C. No.
ON / OFF
Press to finish
setting.
CODE No.
6
4
8
Finish
DATA
SET
SETTING
TEMP.
FILTER
TEST
RESET
5, 7
TIMER SET
TIME
SET CL
4 Push the TIME / buttons repeatedly to
change the value of the indoor unit address
in SET DATA.
Change the value in SET DATA to that of a
new address.
5 Push the button to confirm the new
SET
address on SET DATA.
6 Push the button (left side of the
button) repeatedly to select another address
to change. Each time you push the button,
the indoor unit numbers in a refrigerant line
are indicated one after another. Only the fan
and louvers of the selected indoor unit are
activated.
Repeat steps 4 to 6 to change the indoor unit
addresses so as to make each of them unique.
7 Push the button.
(All the segments on the LCD display light up.)
8 Push the button to finish the procedure.
SET
TEST
Resetting the address
(Resetting to the factory
default (address undecided))
Method 1
Clearing each address separately using a wired remote
controller.
Set the system address, indoor unit address and group
address to “0099” using a wired remote controller.
(For the setting procedure, refer to the address setting
procedures using the wired remote controller on the previous
pages.)
Method 2
Clearing all the indoor unit addresses on a refrigerate line at
once from the outdoor unit.
1 Turn off the refrigerant line to reset to the
factory default and set the header outdoor
unit of the line as below.
1) Disconnect the relay connectors between the
[U1, U2] and [U3, U4] terminals.
(Leave them as they are if they have already
been disconnected.)
2) Turn on dip switch 2 of SW30 on the interface
P.C. board of the header outdoor unit if the
switch is OFF.
(Leave it as it is if it has already been set to
ON.)
Central control
controller
U1U3U2
Header
unit
U3 U4
U1 U2 U5 U6
U1 U2
A B
Remote
controller
Follower unit
U1 U2 U5 U6
U1 U2
A B
Remote
controller
Header
U3 U4
unit
U3 U4
U1 U2 U5 U6
U1 U2
A B
Remote
controller
Indoor units to have their addresses initialized
Follower unit
U1 U2 U5 U6
U1 U2
A B
U3 U4
Header
unit
U1 U2
U1 U2
U3 U4
A B
Remote
controller
U4
U5 U6
2 Turn on the indoor and outdoor units of the refrigerant line for which you want to initialize the
addresses. About one minute after turning on the power, confirm that the 7-segment display on
the header outdoor unit indicates “U.1. - - -” and operate the interface P.C. board on the header
outdoor unit of the refrigerant line as follows.
SW01 SW02 SW03SW04Clearable addresses
212
222
Confirm that the 7-segment display indicates
“A.d.buS” and turn SW04 ON fo r more than five
seconds.
Confirm that the 7-segment display indicates
“A.d.nEt” and turn SW04 ON for mo re than five
seconds.
System/indoor unit/group address
Central control address
3 Confirm that the 7-segment display indicates “A.d. c.L.” and set SW01, SW02 and SW03 to 1, 1, 1
respectively.
4 After a time “U.1.L08” appears on the 7-segment display if the address clearing has been
completed successfully.
If the 7-segment display indicates “A.d. n.G.”, the outdoor unit may still connected with other
refrigerant lines. Check the connection of the relay connectors between [U1, U2] and [U3, U4].
NOTE
Take care to carry out the procedure above correctly; otherwise, addresses in other refrigerate lines may also be cleared.
5 Set the addresses again after finishing the clearance.
EN
55-EN56-EN
–28–
57-EN58-EN
SMMS-i
Installation Manual
–29–
SMMS-i
Installation Manual
10TEST RUN
Before test run
Confirm that the valve of the refrigerate pipe of the outdoor
unit is OPEN.
• Before turning on the power, confirm that the
resistance between the terminal block of power
supply and the earth is more than 1MΩ using a 500V
megohmmeter.
Do not run the unit if it is less than 1MΩ.
CAUTION
• Turn on the power and turn on the case heater of the
compressor.
To save the compressor when it is activated, leave the
power on for more than 12 hours.
Methods of test run
◆ When executing a test run using a
remote controller
Operate the system normally to check the running condition
using the wired remote controller. Follow the instructions in
the supplied owner’s manual when operating the unit.
If you use a wireless remote controller for operations, follow
the instructions in the installation manual supplied with the
indoor unit.
To execute a test run forcibly under the condition that the
thermostat automatically turns the unit off due to the indoor
temperature, follow the procedure below.
The forcible test run will automatically stop after 60 minutes
to prevent continuous forcible running and return to normal
running.
CAUTION
Do not use forcible running except for a test run as it
overloads the unit.
TEMP.
ON / OFF
2, 4
TIMER SET
FILTER
RESET
TEST
TIME
SET CL
3
1, 5
1 Push and hold the button for more than 4
seconds. TEST appears on the LCD display
and the unit enters the trial mode.
(TEST is indicated on the LCD display during
the test run.)
2 Push the button.
3 Push the button to switch the running
mode to COOL or HEAT.
NOTE
• Do not run the unit in any mode other than COOL or
HEAT.
• You cannot change the temperature setting during
the test run.
• Errors are detected as usual.
4 Push the button to stop running
after finishing the trial run.
The indication on the LCD display returns to
the status of procedure 1.
5 Push the button to exit the trial mode.
(TEST disappears on the LCD display and
the status changes to normal stopped
mode.)
TEST
TEST
TEST
ON / OFF
MODE
TEST
ON / OFF
◆ When executing a test run using
the interface P.C. board on the
outdoor unit
You can execute a test run by operating switches on the
interface P.C. board of the header outdoor unit.
“Individual trial”, which tests each indoor unit separately, and
“corrective trial”, which tests all the indoor units connected,
are available.
<Individual test operation>
▼ Starting operation
1 Set the running mode to “COOL” or “HEAT”
on the remote controller of the indoor unit to
be tested.
(The unit will run in the current mode unless
you set the mode otherwise.)
7-segment display
[A]
[U1]
[B]
[ ]
2 Set the rotary switches on the interface P.C.
board of the header outdoor unit: SW01 to
[16], SW02 and SW03 to the address of the
indoor unit to be tested.
SW02SW03Indoor unit address
1 to 1611 to 16 Set number of SW02
1 to 16217 to 32 Set number of SW02 + 16
1 to 16333 to 48 Set number of SW02 + 32
1 to 16449 to 64 Set number of SW02 + 48
7-segment display
[A]
[ ]
Address display of the
corresponding indoor unit
[B]
[ ]
3 Push and hold SW04 for more than 10
seconds.
7-segment display
[A]
[ ]
Address display of the
corresponding indoor unit
[B]
[ ]
[FF] is displayed for 5
seconds.
NOTE
• The running mode follows the mode setting on the
remote controller of the target indoor unit.
• You cannot change the temperature setting during
the test run.
• Errors are detected as usual.
• The unit does not perform test run for 3 minutes after
turning the power on or stopping running.
▼ Finishing operation
1 Set the rotary switches on the interface P.C.
board of the header unit back: SW01 to [1],
SW02 to [1] and SW03 to [1].
7-segment display
[A]
[U1]
[B]
[ ]
SMMS-i
Installation Manual
SMMS-i
Installation Manual
<Corrective trial>
▼ Start operation
1 Set the rotary switches on the interface P.C. board of the header outdoor unit as below.
When in “COOL” mode: SW01=[2], SW02=[5], SW03=[1].
When in “HEAT” mode: SW01=[2], SW02=[6], SW03=[1].
7-segment display
[A]
[C ]
[H ]
[B]
[ ]
[ ]
2 Push and hold SW04 for more than 2 seconds.
NOTE
• You cannot change the temperature setting during the test run.
• Errors are detected as usual.
• The unit does not perform test run for 3 minutes after turning the power on or stopping running.
7-segment display
[A]
[C ]
[H ]
[B]
[ - C ]
[ - H ]
▼ Stop operation
1 Set the rotary switches on the interface P.C. board of the header unit back:
SW01 to [1], SW02 to [1] and SW03 to [1].
7-segment display
[A]
[U1]
[B]
[ ]
Interface PC board
Push switch
7-segment
display [A]
SW04
SW05 SW15
D600 D601 D602 D603 D604
SW01 SW02
Rotary switches
SW03
Push switch
7-segment
display [B]
EN
59-EN60-EN
–30–
61-EN62-EN
SMMS-i
Installation Manual
–31–
SMMS-i
Installation Manual
11TROUBLESHOOTING
In addition to the CODE No. on the remote controller of an indoor unit, you can diagnose failure type of an outdoor unit by
checking the 7-segment display on the interface P.C. board.
Use the function for various checks.
Set every dip switch to OFF after checking.
7-Segment display and check code
Rotary switch setting value
SW01SW02SW03
111Outdoor unit check code
* If a check code has an auxiliary code, the display indicates the check code for three seconds and the auxiliary
code for one second alternately.
IndicationLED
A
BCheck code display*
Check code (indicated on the 7-segment display on the outdoor unit)
Indicated when SW01 = [1], SW02 = [1], and SW03 = [1].
Check code
Auxiliary code
E06Number of indoor units which received normallyDecrease of number of indoor units
E07—Indoor/outdoor communication circuit error
E08Duplicated indoor addressesDuplication of indoor addresses.
01: Communication between indoor and outdoor units
E12
02: Communication between outdoor units
E15—No indoor unit during automatic addressing
00: Capacity over
E16
01~: Number of connected units
00: Header is nothing
E19
02: 2 or more header units
01: Other line indoor connected
E20
02: Other line indoor connected
E23—Sending error between outdoor units communication
E25—Duplicated follower outdoor address set up
E26Number of outdoor units which received normallyDecrease of connected outdoor units
E28Detected outdoorFollower outdoor unit error
E31IPDU quantity information
F04—TD1 sensor error
F05—TD2 sensor error
01: TE1 sensor
F06
02: TE2 sensor
F07—TL sensor error
F08—TO sensor error
F12—TS1 sensor error
01: Compressor 1
F13
02: Compressor 2
03: Compressor 3
(*1)
Automatic addressing start error
Capacity over / number of connected indoor units
Number of header outdoor unit error
Other lines connected during automatic addressing
IPDU communication error
TE1 sensor error
TE2 sensor error
TH (Heat sink) sensor error
D600
AB
Outdoor unit number
Check code nameIndication on 7-segment display on the outdoor unit
D601 D602 D603 D604
(U
1 to U4)
Check code
Check code nameIndication on 7-segment display on the outdoor unit
Check code nameIndication on 7-segment display on the outdoor unit
Auxiliary code
01: Compressor 1
P07
02: Compressor 2
03: Compressor 3
P10Detected indoor unit addressIndoor overflow error
P13—Outdoor unit flow back error detected
01: TS condition
P15
02: TD condition
P17—Discharge temperature TD2 error
P18—Discharge temperature TD3 error
P19Detected outdoor unit number4-way valve inverse error
P20—High-pressure protective operation
0 *: IGBT circuit
1 *: Position detection circuit error
3 *: Motor lock error
4 *: Motor current detected
P22
C *: TH sensor error
D *: TH sensor error
E *: Inverter DC voltage error
(outdoor unit’s fan)
01: Compressor 1
P26
02: Compressor 2
03: Compressor 3
01: Compressor 1
P29
02: Compressor 2
03: Compressor 3
*1PDU number information
01:Compressor 1
02:Compressor 2
03:Compressors 1 and 2
04:Compressor 3
05:Compressors 1 and 3
06:Compressors 2 and 3
07:Compressors 1, 2 and 3
08:Fan
09:Compressor 1 and fan
0A:Compressor 2 and fan
0B:Compressors 1, 2 and fan
0C:Compressor 3 and fan
0D:Compressors 1, 3 and fan
0E:Compressors 2, 3 and fan
0F:Compressors 1, 2, 3, and fan
Heat sink overheat error
Gas leak detection
Outdoor fan IPDU error
(NOTE)
Ignore 0-F appearing in the position of “*”.
G-TR short protection error
Compressor position detecting circuit error
12MACHINE CARD AND LOGBOOK
Machine card
After test run, fill the items on the machine card and paste the card on an accessible place on the product securely before
delivery to the customer.
Describe the following items on the machine card:
name, address and telephone number of the installer, his service department, the service department of the party concerned
or at any addresses and telephone numbers of fire department, police, hospitals and burn centres;
Logbook
Update the log periodically after maintenance as defined in EN378-4.
Describe the following items on the logbook:
1. details of the maintenance and repair works;
2. quantities, kind of (new, reused, recycled) refrigerant which have been charged on each occasion, the quantities
of refrigerant which have been transferred from the system on each occasion (see also EN378-4);
3. if there is an analysis of a reused refrigerant, the results shall be kept in the logbook;
4. source of the reused refrigerant;
5. changes and replacements of components of the system;
6. result of all periodic routine tests;
7. significant periods of non-use.
EN
63-EN64-EN
–32–
WARNINGS ON REFRIGERANT LEAKAGE
Check of Concentration Limit
The room in which the air conditioner is to be installed
requires a design that in the event of refrigerant gas
leaking out, its concentration will not exceed a set limit.
The refrigerant R410A which is used in the air conditioner is
safe, without the toxicity or combustibility of ammonia, and is
not restricted by laws to be imposed which protect the ozone
layer. However, since it contains more than air, it poses the
risk of suffocation if its concentration should rise excessively.
Suffocation from leakage of R410A is almost non-existent.
With the recent increase in the number of high concentration
buildings, however, the installation of multi air conditioner
systems is on the increase because of the need for effective
use of floor space, individual control, energy conservation by
curtailing heat and carrying power etc.
Most importantly, the multi air conditioner system is able to
replenish a large amount of refrigerant compared with
conventional individual air conditioners. If a single unit of the
multi conditioner system is to be installed in a small room,
select a suitable model and installation procedure so that if
the refrigerant accidentally leaks out, its concentration does
not reach the limit (and in the event of an emergency,
measures can be made before injury can occur).
In a room where the concentration may exceed the limit,
create an opening with adjacent rooms, or install mechanical
ventilation combined with a gas leak detection device.
The concentration is as given below.
Total amount of refrigerant (kg)
Min. volume of the indoor unit installed room (m
≤ Concentration limit (kg/m
The concentration limit of R410A which is used in multi air
conditioners is 0.44kg/m
NOTE 1 :
If there are 2 or more refrigerating systems in a single
refrigerating device, the amounts of refrigerant should be as
charged in each independent device.
e.g., charged
amount (10kg)
Room A Room B Room C Room D Room E Room F
For the amount of charge in this example:
The possible amount of leaked refrigerant gas in rooms A,
EH99871699
B and C is 10kg.
The possible amount of leaked refrigerant gas in rooms
D, E and F is 15kg.
3
.
3
)
Outdoor unit
e.g.,
charged amount (15kg)
Indoor unit
Important
NOTE 2 :
The standards for minimum room volume are as
follows.
(1) No partition (shaded portion)
(2) When there is an effective opening with the adjacent
room for ventilation of leaking refrigerant gas (opening
without a door, or an opening 0.15% or larger than the
respective floor spaces at the top or bottom of the door).
Outdoor unit
Refrigerant piping
Indoor unit
(3) If an indoor unit is installed in each partitioned room and
the refrigerant piping is interconnected, the smallest
room of course becomes the object. But when a
mechanical ventilation is installed interlocked with a gas
leakage detector in the smallest room where the density
3
)
limit is exceeded, the volume of the next smallest room
becomes the object.
Refrigerant piping
Outdoor unit
Very
small
room
Small
Medium
room
Large room
Range above the
density limit of
0.44 kg/m
(countermeasures
needed)
room
Mechanical ventilation device - Gas leak detector
NOTE 3 :
The minimum indoor floor area compared with the amount of
refrigerant is roughly as follows:
(When the ceiling is 2.7m high)
40
Range below the
2
35
m
density limit of
3
0.44 kg/m
30
(countermeasures
not needed)
25
20
15
10
5
Min. indoor floor area
0
102030
Total amount of refrigerantkg
Indoor unit
3
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.