Toshiba MMY-MAP1404HT8-E, MMY-MAP1404HT8Z-E, MMY-MAP0804HT8ZG-E, MMY-MAP0804HT8-E, MMY-MAP1204HT8-E User Manual

...
AIR CONDITIONER (MULTI TYPE)
Installation manual
Outdoor Unit
Model name:
<Heat Pump Model>
MMY-MAP0804HT8-E MMY-MAP1004HT8-E MMY-MAP1204HT8-E MMY-MAP1404HT8-E MMY-MAP1604HT8-E
MMY-MAP0804HT8Z-E MMY-MAP1004HT8Z-E MMY-MAP1204HT8Z-E MMY-MAP1404HT8Z-E MMY-MAP1604HT8Z-E
MMY-MAP0804HT8ZG-E MMY-MAP1004HT8ZG-E MMY-MAP1204HT8ZG-E MMY-MAP1404HT8ZG-E MMY-MAP1604HT8ZG-E
<Cooling Only Model>
MMY-MAP0804T8-E MMY-MAP1004T8-E MMY-MAP1204T8-E MMY-MAP1404T8-E MMY-MAP1604T8-E
MMY-MAP0804T8Z-E MMY-MAP1004T8Z-E MMY-MAP1204T8Z-E MMY-MAP1404T8Z-E MMY-MAP1604T8Z-E
MMY-MAP0804T8ZG-E MMY-MAP1004T8ZG-E MMY-MAP1204T8ZG-E MMY-MAP1404T8ZG-E MMY-MAP1604T8ZG-E
Not accessible to the general public
For commercial use
Vente interdite au grand public
Kein öffentlicher Zugang
Non accessibile a clienti generici
No destinado al público en general
Não acessível ao público em geral
Niet geschikt voor huishoudelijk gebruik
Μη προσβάσιμο από το γενικό κοινό
Недоступен для посторонних
Genel erişime açık değildir
Installation manual
1-EN 2-EN
SMMS-i
Installation Manual
–1–
SMMS-i
Installation Manual
Original instruction
ADOPTION OF NEW REFRIGERANT
This Air Conditioner uses R410A an environmentally friendly refrigerant.
Contents
1 PRECAUTIONS FOR SAFETY . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
2 ACCESSORY PARTS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
3 INSTALLATION OF NEW REFRIGERANT AIR CONDITIONER . . . . . . . . . . . . . . . . . 4
4 SELECTION OF INSTALLATION PLACE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
5 CARRYING IN THE OUTDOOR UNIT . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
6 INSTALLATION OF THE OUTDOOR UNIT . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
7 REFRIGERANT PIPING . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
8 ELECTRIC WIRING . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
9 ADDRESS SETTING . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
10 TEST RUN . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
11 TROUBLESHOOTING . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
12 MACHINE CARD AND LOGBOOK . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
Thank you for purchasing this Toshiba air conditioner. This Installation Manual describes the installation method of the outdoor unit. For installation of indoor units, follow the Installation Manual supplied with the indoor unit. Moreover, as this installation manual includes the important articles concerning the “Machinery” Directive (Directive 2006/42/ EC), please read through the manual and make sure you understand it. After installation, give this Installation Manual, the Owner’s Manual and the Installation Manual supplied with the indoor unit to the customer and tell the customer to keep them safe. Prepare an exclusive power source for indoor units, independent to that for outdoor units. Y-shaped branching joints or a branching header (separately purchased) are required for connecting pipes between indoor and outdoor units. Choose either of them considering the system capacity concerning piping. For installing branching pipes, refer to the installation manual of the Y-shaped branching unit or branching header (separately purchased). Outdoor connecting branching joints are required for connecting between outdoor units.
Generic Denomination: Air Conditioner
Definition of Qualified Installer or Qualified Service Person
The air conditioner must be installed, maintained, repaired and removed by a qualified installer or qualified service person. When any of these jobs is to be done, ask a qualified installer or qualified service person to do them for you. A qualified installer or qualified service person is an agent who has the qualifications and knowledge described in the table below.
Agent Qualifications and knowledge which the agent must have
• The qualified installer is a person who installs, maintains, relocates and removes the air conditioners made by Toshiba Carrier Corporation. He or she has been trained to install, maintain, relocate and remove the air conditioners made by Toshiba Carrier Corporation or, alternatively, he or she has been instructed in such operations by an individual or individuals who have been trained and is thus thoroughly acquainted with the knowledge related to these o perations.
• The qualified installer who is a llowed to do the electrical work in volved in installation, relocation and removal has the qualifications pertaining to this electrical work as stipulated by the local laws and regulations, and he or she is a person who has been trained in matters relating to electrical work on the air conditioners made by Toshiba Carrier Corporation or, alternatively, he or she has been instructed in such matters by an individual or individuals who have
Qualified installer
Qualified service person
been trained and is thus thoroughly acquainted with the knowledge related to this work.
• The qualified installer who is allowed to do the refrigerant handling and piping work involved in installation, relocation and removal has the qualification s pertaining to this refrigerant handling an d piping work as stipulated by the local laws and regulations, and he or she is a person who has been trained in matters relating to refrigerant handling and piping work on the air conditioners made by Toshiba Carrier Corporation or, alternatively, he or she has been instructed in such matters by an individual or individuals who have been trained and is thus thoroughly acquainted with the knowledge related to this work.
• The qualified installer who is allowed to work at heights has been trained in matters relating to working at heights with the air conditioners made by Toshiba Carrier Corporation or, alternatively, he or she has been instructed in such matters by an individu al or individuals who have been trained and is thus thorou ghly acquainted with the knowledge related to this work.
• The qualified service person is a person who installs, repairs, maintains, relocates and removes the air conditioners made by Toshiba Carrier Corporation. He or she has been trained to install, repair, maintain, relocate and remove the air conditioners made by Toshiba Carrier Corporation or, alternatively, he or she has been instructed in such operations by an individual or individuals who have been trained and is thus thoroughly acquainted with the knowledge related to these o perations.
• The qualified service person who is allowed to do the electrical work involved in installation, repair, relocation and removal has the qualifications pertaining to this electrical work as stipulated by the local laws and regulations, and he or she is a person who has been trained in matters relating to electrical work on the air conditioners made by Toshiba Carrier Corporation or, alternatively, he or she has been instructed in such matters by an individual or individuals who have been trained and is thus thoroughly acquainted with the knowledge related to this work.
• The qualified service person who is allowed to do the refrigerant handling and piping work involved in installation, repair, relocation and removal has the qualifications pertaining to this refrigerant handling and piping work as stipulated by the local laws and regulations, and he or she is a person who has been trained in matters relating to refrigerant handling and piping work on the air conditioners made by Toshiba Carrier Corporation or, alternatively, he or she has been instructed in such matters by an individual or individuals who have been trained and is thus thoroughly acquainted with the knowledge related to this work.
• The qualified service person who is allowed to work at heights has been trained in matters relating to working at heights with the air conditioners made by Toshiba Carrier Corporation or, alternatively, he or she has been instructed in such matters by an individual or individuals who have been trained and is thus thoroughly acquainted with the knowledge related to this work.
Definition of Protective Gear
When the air conditioner is to be transported, installed, maintained, repaired or removed, wear protective gloves and ‘safety’ work clothing. In addition to such normal protective gear, wear the protective g ear described below when undertaking the special work detailed in the table below. Failure to wear the proper protective gear is dangerous because you will be more susceptible to injury, burns, electric shocks and other injuries.
SMMS-i
Installation Manual
SMMS-i
Installation Manual
Work undertaken Protective gear worn
All types of work
Electrical-related work
Work done at heights (50 cm or more)
Transportation of heavy objects
Repair of outdoor unit Gloves to provide protection for electricians and from heat
Protective gloves ‘Safety’ working clothing
Gloves to provide protec tion for electricians and from heat Insulating shoes Clothing to provide protection from electr ic shock
Helmets for use in industry
Shoes with additional protective toe cap

Warning Indications on the Air Conditioner Unit

Warning indication Description
WARNING
ELECTRICAL SHOCK HAZARD
Disconnect all remote electric power supplies before servicing.
WARNING
Moving parts. Do not operate unit with grille removed. Stop the unit before the servicing.
CAUTION
High temperature parts. You might get burned when removing this panel.
CAUTION
Do not touch the aluminum fins of the unit. Doing so may result in injury.
CAUTION
BURST HAZARD
Open the service valves before the operation, otherwise there might be the burst.
CAUTION
Do not climb onto the fan guard.
Doing so may result in injury.
WARNING
ELECTRICAL SHOCK HAZARD
Disconnect all remote electric power supplies before servicing.
WARNING
Moving parts. Do not operate unit with grille removed. Stop the unit before the servicing.
CAUTION
High temperature parts. You might get burned when removing this panel.
CAUTION
Do not touch the aluminium fins of the unit. Doing so may result in injury.
CAUTION
BURST HAZARD
Open the service valves before the operation, otherwise there might be the burst.
CAUTION
Do not climb onto the fan guard.
Doing so may result in injury.

1 PRECAUTIONS FOR SAFETY

WARNING
General
• Before starting to install the air conditioner, read through the Installation Manual carefully, and follow its instructions to install the air conditioner. Otherwise, falling down of the unit may occur, or the unit may cause noise, vibration or water leakage.
• Only a qualified installer(*1) or qualified service person(*1) is allowed to do installationwork. If installation is carried out by an unqualified individual, a fire, electric shocks, injury, water leakage, noise and/or vibration may result.
• If using separately sold products, make sure to use Toshiba specified products only. Using unspecified products may cause fire, electric shock, water leak or other failure.
• Before opening the service panel of the outdoor unit, set the circuit breaker to the OFF position. Failure to set the circuit breaker to the OFF position may result in electric shocks through contact with the interior parts. Only a qualified installer(*1) or qualified service person(*1) is allowed to remove the service panel of the outdoor unit and do the work required.
• Before carrying out the installation, maintenance, repair or removal work, be sure to set the circuit breakers for both the indoor and outdoor units to the OFF position. Otherwise, electric shock may result.
• Place a “Work in progress” sign near the circuit breaker while the installation, maintenance, repair or removal work is being carried out. There is a danger of electric shocks if the circuit breaker is set to ON by mistake.
• Only a qualified installer(*1) or qualified service person(*1) is allowed to undertake work at heights using a stand of 50 cm or more or to remove the intake grille of the indoor unit to undertake work.
• Wear protective gloves and safety work clothing during installation, servicing and removal.
• Do not touch the aluminium fin of the outdoor unit. You may injure yourself if you do so. If the fin must be touched for some reason, first put on protective gloves and safety work clothing, and then proceed.
• Do not climb onto or place objects on top of the outdoor unit. You may fall or the objects may fall off of the outdoor unit and result in injury.
• When working at height, put a sign in place so that no-one will approach the work location before proceeding with the work. Parts or other objects may fall from above, possibly injuring a person below. Also, be sure that workers put on helmets.
• When cleaning the filter or other parts of the outdoor unit, set the circuit breaker to OFF without fail, and place a “Work in progress” sign near the circuit breaker before proceeding with the work.
• When working at heights, put a sign in place so that no-one will approach the work location, before proceeding with the work. Parts and other objects may fall from above, possibly injuring a person below.
• The refrigerant used by this air conditioner is the R410A.
• You shall ensure that the air conditioner is transported in stable condition. If you find any part of the product broken, contact your dealer.
• Do not disassemble, modify, repair or move the product yourself. Doing so may cause fire, electric shock, injury or water leaks. Ask a qualified installer or qualified service person to do any repairs or to move the product.
Selection of installation location
• If you install the unit in a small room, take appropriate measures to prevent the refrigerant from exceeding the limit concentration even if it leaks. Consult the dealer from whom you purchased the air conditioner when you implement the measures. Accumulation of highly concentrated refrigerant may cause an oxygen deficiency accident.
• Do not install in a location where flammable gas may leaks are possible. If the gas should leak and accumulate around the unit, it may ignite and cause a fire.
• When transporting the air conditioner, wear shoes with protective toe caps, protective gloves and other protective clothing.
• When transporting the air conditioner, do not take hold of the bands around the packing carton. You may injure yourself if the bands should break.
• Install the indoor unit at least 2.5 m above the floor level since otherwise the users may injure themselves or receive electric shocks if they poke their fingers or other objects into the indoor unit while the air conditioner is running.
• Do not place any combustion appliance in a place where it is directly exposed to the wind of air conditioner, otherwise it may cause imperfect combustion.
• Places where the operation sound of the outdoor unit may cause a disturbance. (Especially at the boundary line with a neighbour, install the air conditioner while considering the noise.)
Installation
• Follow the instructions in the Installation Manual to install the air conditioner. Failure to follow these instructions may cause the product to fall down or topple over or give rise to noise, vibration, water leakage or other failure.
• The designated bolts (M12) and nuts (M12) for securing the outdoor unit must be used when installing the unit.
• Install the outdoor unit property in a location that is durable enough to support the weight of the outdoor unit. Insufficient durability may cause the outdoor unit to fall, which may result in injury.
• Install the unit in the prescribed manner for protection against strong wind and earthquake. Incorrect installation may result in the unit falling down, or other accidents.
• Be sure to fix the screws back which have been removed for installation or other purposes.
EN
3-EN 4-EN
–2–
5-EN 6-EN
SMMS-i
Installation Manual
–3–
SMMS-i
Installation Manual
Refrigerant piping
• Install the refrigerant pipe securely during the installation work before operating the air conditioner. If the compressor is operated with the valve open and without refrigerant pipe, the compressor sucks air and the refrigeration cycles is over pressurized, which may cause a injury.
• Tighten the flare nut with a torque wrench in the specified manner. Excessive tighten of the flare nut may cause a crack in the flare nut after a long period, which may result in refrigerant leakage.
• Ventilate the air if the refrigerant gas leaks during installation. If the leaked refrigerant gas comes into contact with fire, toxic gas may be produced.
• After the installation work, confirm that refrigerant gas does not leak. If refrigerant gas leaks into the room and flows near a fire source, such as a cooking range, noxious gas may be generated.
• When the air conditioner has been installed or relocated, follow the instructions in the Installation Manual and purge the air completely so that no gases other than the refrigerant will be mixed in the refrigerating cycle. Failure to purge the air completely may cause the air conditioner to malfunction.
• Nitrogen gas must be used for the airtight test.
• The charge hose must be connected in such a way that it is not slack.
• If refrigerant gas has leaked during the installation work, ventilate the room immediately. If the leaked refrigerant gas comes in contact with fire, noxious gas may be generated.
Electrical wiring
• Only a qualified installer(*1) or qualified service person(*1) is allowed to carry out the electrical work of the air conditioner. Under no circumstances must this work be done by an unqualified individual since failure to carry out the work properly may result in electric shocks and/or electrical leaks.
• When connecting the electrical wires, repairing the electrical parts or undertaking other electrical jobs, wear gloves to provide protection for electricians and from heat, insulating shoes and clothing to provide protection from electric shocks. Failure to wear this protective gear may result in electric shocks.
• When executing address setting, test run, or troubleshooting through the checking window on the electric parts box, put on insulated heat-proof gloves, insulated shoes and other clothing to provide protection fr om electric shock. Otherwise you may receive an electric shock.
• Use wiring that meets the specifications in the Installation Manual and the stipulations in the local regulations and laws. Use of wiring which does not meet the specifications may give rise to electric shocks, electrical leakage, smoking and/or a fire.
• Check that the product is properly earthed. (grounding work) Incomplete earthing may cause electric shock.
• Do not connect the earth line to a gas pipe, water pipe, lightning conductor, or a telephone earth line.
• After completing the repair or relocation work, check that the ground wires are connected properly.
• Install a circuit breaker that meets the specifications in the installation manual and the stipulations in the local regulations and laws.
• Install the circuit breaker where it can be easily accessed by the agent.
• When installing the circuit breaker outdoors, install one which is designed to be used outdoors.
• Under no circumstances must the power cable be extended. Connection trouble in the places where the cable is extended may give rise to smoking and/or a fire.
• Electrical wiring work shall be conducted according to law and regulation in the community and installation manual. Failure to do so may result in electrocution or short circuit.
• Do not supply power from the power terminal block equipped on the outdoor unit to another outdoor unit. Capacity overflow may occur on the terminal block and may result in fire.
• When carrying out electric connection, use the wire specified in the Installation Manual and connect and fix the wires securely to prevent them applying external force to the terminals. Improper connection or fixing may result in fire.
Test run
• Before operating the air conditioner after having completed the work, check that the electrical parts box cover of the indoor unit and service panel of the outdoor unit are closed, and set the circuit breaker to the ON position. You may receive an electric shock if the power is turned on without first conducting these checks.
• When you have noticed that some kind of trouble (such as when an error display has appeared, there is a smell of burning, abnormal sounds are heard, the air conditioner fails to cool or heat or water is leaking) has occurred in the air conditioner, do not touch the air conditioner yourself but set the circuit breaker to the OFF position, and contact a qualified service person. Take steps to ensure that the power will not be turned on (by marking “out of service” near the circuit breaker, for instance) until qualified service person arrives. Continuing to use the air conditioner in the trouble status may cause mechanical problems to escalate or result in electric shocks or other failure.
• After the work has finished, be sure to use an insulation tester set (500V Megger) to check the resistance is 2 MΩ or more between the charge section and the non-charge metal section (Earth section). If the resistance value is low, a disaster such as a leak or electric shock is caused at user’s side.
• Upon completion of the installation work, check for refrigerant leaks and check the insulation resistance and water drainage. Then conduct a test run to check that the air conditioner is operating properly.
Explanations given to user
• Upon completion of the installation work, tell the user where the circuit breaker is located. If the user does not know where the circuit breaker is, he or she will not be able to turn it off in the event that trouble has occurred in the air conditioner.
• If you have discovered that the fan grille is damaged, do not approach the outdoor unit but set the circuit breaker to the OFF position, and contact a qualified service person(*1) to have the repairs done. Do not set the circuit breaker to the ON position until the repairs are completed.
• After the installation work, follow the Owner’s Manual to explain to the customer how to use and maintain the unit.
Relocation
• Only a qualified installer(*1) or qualified service person(*1) is allowed to relocate the air conditioner. It is dangerous for the air conditioner to be relocated by an unqualified individual since a fire, electric shocks, injury, water leakage, noise and/or vibration may result.
• When carrying out the pump-down work shut down the compressor before disconnecting the refrigerant pipe. Disconnecting the refrigerant pipe with the service valve left open and the compressor still operating will cause air or other gas to be suck ed in, raising the pressure inside the refrigeration cycle to an abnormally high level, and possibly resulting in rupture, injury or other trouble.
• Never recover the refrigerant into the outdoor unit. Be sure to use a refrigerant recovery machine to recover the refrigerant when moving or repairing. It is impossible to recover the refrigerant into the outdoor unit. Refrigerant recovery into the outdoor unit may result in serious accidents such as explosion of the unit, injury or other accidents.
(*1) Refer to the “Definition of Qualif ied Installer or Qualified Service Per son.”
CAUTION
New Refrigerant Air Conditioner Installation
THIS AIR CONDITIONER ADOPTS THE NEW HFC REFRIGERANT (R410A) WHICH DOES NOT DESTROY OZONE LAYER.
• The characteristics of R410A refrigerant are; easy to absorb water, oxidizing membrane or oil, and its pressure is approx.
1.6 times higher than that of refrigerant R22. Accompanied with the new refrigerant, refrigerating oil has also been changed. Therefore, during installation work, be sure that water, dust, former refrigerant, or refrigerating oil does not enter the refrigerating cycle.
• To prevent charging an incorrect refrigerant and refrigerating oil, the sizes of connecting sections of charging port of the main unit and installation tools are changed from those for the conventional refrigerant.
• Accordingly the exclusive tools are required for the new refrigerant (R410A).
• For connecting pipes, use new and clean piping designed for R410A, and please care so that water or dust does not enter.
To Disconnect the Appliance from Main Power Supply.
• This appliance must be connected to the main power supply by means of a switch with a contact separation of at least 3 mm.
The installation fuse (all type can be used) must be used for the power supply line of this conditioner.
SMMS-i
Installation Manual
SMMS-i
Installation Manual

2 ACCESSORY PARTS

Part name Q’ty Shape Usage
Owner’s Manual 1 (Be sure to hand it to the customers.)
Installation Manual 2 (Be sure to hand it to the customers.)
CD-ROM (Owner’s manual,
Installation manual)
Attached pipe (for Ø22.2)
Attached pipe (for Ø28.6)
F-GAS label 1 Fill the items on the label after adding refrigerant.
1–
1
1
For other languages that do not appear in this Installation Manual, Please refer to the enclosed CD-ROM.
Connecting pipe for gas side piping (MAP080, MAP100 type)
Connecting pipe for gas side piping (MAP120, MAP140, MAP160 type)
3 INSTALLATION OF NEW REFRIGERANT
AIR CONDITIONER
This air conditioner adopts the new HFC refrigerant (R410A) which does not deplete the ozone layer.
• R410A refrigerant is vulnerable to impurities such as water, oxidizing membranes, or oils because the pressure of R410A refrigerant is higher than that of the former refrigerant by approximately 1.6 times. As well as the adoption of the new refrigerant, the refrigerating oil has been also changed. Therefore, pay attention so that water, dust, former refrigerant, or refrigerating oil does not enter the refrigerating cycle of the new refrigerant air conditioner during installation.
• To prevent mixing of refrigerant or refrigerating oil, the size of the charge port of the main unit or connecting section of the installation tool differs to that of an air conditioner for the former refrigerant. Accordingly, exclusive tools are required for the new refrigerant (R410A) as shown below.
• For connecting pipes, use new and clean piping materials so that water or dust does not enter.

Required Tools and Cautions on handling

It is necessary to prepare the tools and parts for installation as described below. The tools and parts which will be newly prepared in the following items should be restricted to exclusive use.

Explanation of symbols
: Newly prepared (It is necessary to use it exclusively with R410A, separately from those for R22 or R407C.) : Former tool is available.
Gauge manifold
Charging hose Exclusive to R410A
Charging cylinder Charging refrigerant Unusable (Use the Refrigerant charging balance.)
Gas leak detector Checking gas leak Exclusive to R410A
Vacuum pump Vacuum drying
Vacuum pump with counterflow Vacuum drying R22 (Existing article)
Flare tool Flare processing of pipes Usable by adjusting size
Bender Bending processing of pipes R22 (Existing article)
Refrigerant recovery device Recovering refrigerant Exclusive to R410A
Torque wrench Tightening flare nut Exclusive to Ø12.7mm and Ø15.9mm
Pipe cutter Cutting pipes R22 (Existing article)
Refrigerant canister Charging refrigerant
Welding machine/Nitrogen gas cylinder
Refrigerant charging balance Charging refrigerant R22 (Existing article)
Used tools Usage Proper use of tools/parts
Vacuuming, charging refrigerant and operation check
Welding of pipes R22 (Existing article)
Exclusive to R410A
Usable if a counter-flow preventive adapter is attached
Exclusive to R410A Enter the refrigerate name for identification
EN
7-EN 8-EN
–4–
9-EN 10-EN
SMMS-i
Installation Manual
–5–
SMMS-i
Installation Manual

4 SELECTION OF INSTALLATION PLACE

Upon customer’s approval, install the air conditioner in a place which satisfies the following conditions:
• Place where it can be installed horizontally.
• Place which can reserve a sufficient service space for safe maintenance or checks.
• Place where there is no problem even if the drained water overflows.
Avoid the following places:
• Salty places (seaside area) or places with much gas sulfide (hot spring area) (If selecting such a place, special maintenance is required.)
• Places where oil (including machine oil), steam, oil smoke or corrosive gas is generated.
• Places where an organic solvent is used.
• Chemical plants with a cooling system using liquid carbon dioxide.
• Places where a device generating high frequency (inverter, non-utility generator, medical apparatus, or communication equipment) is set. (Malfunction or abnormal control of the air conditioner, or interference to devices listed above may occur.)
• Places where discharged air from the outdoor unit blows against the windows of a neighbour's house.
• Places unable to bear the weight of the unit.
• Places with poor ventilation.

Installation space

Leave space necessary for running, installation and servicing.
Air intake
Air intake
Installation/servicing
500mm or more
(Rear side)
10mm or more
500mm or more
(Front side)
surface
20mm or more
Square hole for handling
Outdoor unit top view
Air discharge
20mm or more
Air intake
Air intake
10mm or more
NOTE
• If there is an obstacle above the outdoor unit, leave a space of 2000mm or more to the top end of the outdoor unit.
• If there is a wall around the outdoor unit, make sure that its height does not exceed 800mm.
SMMS-i
Installation Manual
SMMS-i
Installation Manual
Combination of outdoor units
Model name
(Standard type)
MMY-MAP0804* MMY-MAP0804*
MMY-MAP1004* MMY-MAP1004*
MMY-MAP1204* MMY-MAP1204*
MMY-MAP1404* MMY-MAP1404*
MMY-MAP1604* MMY-MAP1604*
MMY-AP1814* MMY-MAP1004* MMY-MAP0804*
MMY-AP2014* MMY-MAP1004* MMY-MAP1004*
MMY-AP2214* MMY-MAP1204* MMY-MAP1004*
MMY-AP2414* MMY-MAP1204* MMY-MAP1204*
MMY-AP2614* MMY-MAP1604* MMY-MAP1004*
MMY-AP2814* MMY-MAP1604* MMY-MAP1204*
MMY-AP3014* MMY-MAP1604* MMY-MAP1404*
MMY-AP3214* MMY-MAP1604* MMY-MAP1604*
MMY-AP3414* MMY-MAP1204* MMY-MAP1204* MMY-MAP1004*
MMY-AP3614* MMY-MAP1204* MMY-MAP1204* MMY-MAP1204*
MMY-AP3814* MMY-MAP1604* MMY-MAP1204* MMY-MAP1004*
MMY-AP4014* MMY-MAP1604* MMY-MAP1204* MMY-MAP1204*
MMY-AP4214* MMY-MAP1604* MMY-MAP1404* MMY-MAP1204*
MMY-AP4414* MMY-MAP1604* MMY-MAP1604* MMY-MAP1204*
MMY-AP4614* MMY-MAP1604* MMY-MAP1604* MMY-MAP1404*
MMY-AP4814* MMY-MAP1604* MMY-MAP1604* MMY-MAP1604*
Model name
(High Efficiency Model)
MMY-AP1624* MMY-MAP0804* MMY-MAP0804*
MMY-AP2424* MMY-MAP0804* MMY-MAP0804* MMY-MAP0804*
MMY-AP2624* MMY-MAP1004* MMY-MAP0804* MMY-MAP0804*
MMY-AP2824* MMY-MAP1004* MMY-MAP1004* MMY-MAP0804*
MMY-AP3024* MMY-MAP1004* MMY-MAP1004* MMY-MAP1004*
MMY-AP3224* MMY-MAP0804* MMY-MAP0804* MMY-MAP0804* MMY-MAP0804*
MMY-AP3424* MMY-MAP1004* MMY-MAP0804* MMY-MAP0804* MMY-MAP0804*
MMY-AP3624* MMY-MAP1004* MMY-MAP1004* MMY-MAP0804* MMY-MAP0804*
MMY-AP3824* MMY-MAP1004* MMY-MAP1004* MMY-MAP1004* MMY-MAP0804*
MMY-AP4024* MMY-MAP1004* MMY-MAP1004* MMY-MAP1004* MMY-MAP1004*
MMY-AP4224* MMY-MAP1204* MMY-MAP1004* MMY-MAP1004* MMY-MAP1004*
MMY-AP4424* MMY-MAP1204* MMY-MAP1204* MMY-MAP1004* MMY-MAP1004*
MMY-AP4624* MMY-MAP1204* MMY-MAP1204* MMY-MAP1204* MMY-MAP1004*
MMY-AP4824* MMY-MAP1204* MMY-MAP1204* MMY-MAP1204* MMY-MAP1204*
Unit 1 Unit 2 Unit 3
Unit 1 Unit 2 Unit 3
Cooperating outdoor unit
Cooperating outdoor unit
Unit 4

5 CARRYING IN THE OUTDOOR UNIT

CAUTION
Handle the outdoor unit carefully, observing the following items.
• When using a forklift or other machinery for loading/unloading in transportation, insert the prongs of the forklift into the rectangular holes for handling as shown below.
• When lifting up the unit, insert a rope able to bear the unit’s weight into the rectangular holes for handling, and tie the unit from 4 sides. (Apply padding in positions where the rope comes into contact with the outdoor unit so that no damage is caused to the outer surface of the outdoor unit.) (There are reinforcing plates on the side surfaces, so the rope cannot be passed through.)
GOOD NO GOOD NO GOOD
Plaster
Rope
Rectangular
holes for handling
Front /Back
GOOD
Side
NO GOOD
Prongs of the forklift
Plaster
Rectangular holes for lifting
Reinforcing plate
EN
11-EN 12-EN
–6–
13-EN 14-EN
SMMS-i
Installation Manual
–7–
SMMS-i
Installation Manual

Weight centre and weight

Weight centre of an outdoor unit
(A)
Anchor bolt position
700
755
Anchor bolt position
Y

6 INSTALLATION OF THE OUTDOOR UNIT

WARNING
(B)
Anchor bolt position
920
755
Anchor bolt position
Y
Be sure to install the outdoor unit in a place able to bear its weight. If strength is insufficient, the unit may fall down resulting in human injury.
Perform specified installation work to protect against strong wind and earthquakes. If the outdoor unit is imperfectly installed, an accident by falling or dropping may be caused.
CAUTION
• Drain water is discharged from the outdoor unit. (Especially while heating) Install the outdoor unit in a place with good drainage.
• For installation, be careful of the strength and level of the foundation so that abnormal sounds (vibration or noise) are not generated.
REQUIREMENT
Installation in a snowfall area
1. Install the outdoor unit on a higher foundation than the snowfall or set up a stand to install the unit so that snowfall
will not affect the unit.
• Set up a stand higher than the snowfall.
• Apply an angled structure to the stand so that drainage will not be prevented. (Avoid using a stand with a flat surface.)

2. Mount a snowfall-hood onto the air inlet and the air outlet.

• Leave enough space for the snowfall-hood so that it will not be an obstacle for the air inlet and the air outlet.
Snowfall-hood for air outlet (locally procured)
Snowfall-hood for air outlet (4 faces) (locally procured)
X
Z
No. Model type X (mm) Y (mm) Z (mm)
MAP080
(A)
(B)
MAP120
MAP140
MAP160
500 390 645 242 241MAP100
605 350 700 330 330
Z
X
Weight (kg)
Heat pump model Cooling only model
Stand (locally procured)

1. To install multiple outdoor units, arrange them with 20mm or more spaces in between. Fix each outdoor unit with M12 anchor bolts at 4 positions. 20mm projection is appropriate for an anchor bolt.

20
20mm or more
20mm or more
M12 anchor bolt 4 positions/unit
SMMS-i
Installation Manual
SMMS-i
Installation Manual
• Anchor bolt positions are as shown below:
Continuous hole (15 x 20 long hole)
310 or more
A A A
Model type A B
MAP080*, MAP1000*, MAP120* 700 990
MAP1404*, 1604* 920 1210
2. When drawing out the refrigerant pipe from the underside, set the height of the stand to 500mm or
310 or more
755
790
B
(Unit: mm)

3. Do not use 4 stands on the corner to support the outdoor unit.

more.
NO GOOD GOOD
500mm or more

4. Mount the vibration-proof rubber (including vibration-proof blocks) so that it fits under the whole clamping leg.

GOOD GOOD
Install the vibration-proof rubber so that the bent part
Anchor bolt
Vibration-proof rubber
of the fixing leg is grounded.
5. Be careful of the connecting arrangement of the header unit and follower units. Set the outdoor units in order of capacity from the one with the largest capacity. (A (Header unit) B C D)
• Be sure to use a header unit for the leading outdoor unit to be connected to the main pipe. (Figure 1 and 3)
• Be sure to use a T-shaped branch joint (RBM-BT14E/RBM-BT24E: separately purchased) to connect each
outdoor unit.
• Be careful of the direction of the Outdoor unit connection piping kit for the liquid side. (As shown in Figure 2, a
Outdoor unit connection piping kit cannot be attached so that the refrigerant of the main pipe flows directly into the header unit.)
Liquid piping
Figure 1 Figure 2
GOOD
Header unit AFollower unit BFollower unit
Main pipe
To the indoor unit
C
NO GOOD
Header unit AFollower unit BFollower unit
NO GOOD
Main pipe
To the indoor unit
C
Gas piping
Figure 3 Figure 4
GOOD
Header unit AFollower unit BFollower unit
C
[Inverse connection of a gas-side branch unit]
NO GOOD
Header unit AFollower unit
B
Follower unit C
Main pipe
NO GOOD NO GOODNO GOOD
The bent part of the fixing leg is not grounded.
To the indoor unit
Extension valve
• When attaching a Y-shaped branch unit for the gas side, attach it level with the ground (Be sure not to exceed
Main pipe
To the indoor unit
To gas-side branch unit
±15 degrees.). Regarding a T-shape branch joints for the liquid side, there is no restriction for its angle.
(Horizontal line)
A
B
(A arrow view)
Within ±15 degrees
(Horizontal line)
(B arrow view)
Within ±15 degrees
Do not connect a branch unit vertically.
At a level position
EN
15-EN 16-EN
–8–
17-EN 18-EN
SMMS-i
Installation Manual
–9–
SMMS-i
Installation Manual
When drawing pipes downward
Figure 5 Figure 6
GOOD
Header unit AFollower unit BFollower unit
L-shaped
pipe
To gas-side branch unit
C
To gas-side branch unit
• Adding only one follower unit is possible. Install the additional unit so that its position is opposite to the header unit. Use an extension valve for installation (See the figure above.). Specify the pipe diameter in advance to allow for adding another unit.
[Vertical connection of branch units]
NO GOOD
To gas-side
branch unit
To gas-side
branch unit

7 REFRIGERANT PIPING

WARNING
If the refrigerant gas leaks during installation, ventilate the room. If the leaked refrigerant gas comes into contact with fire, noxious gas may be generated.
After installation, check that the refrigerant gas does not leak. If the refrigerant gas leaks into the room and comes into contact with fire such as a fan heater, stove, or kitchen range, noxious gas may be generated.

Connection of refrigerant pipe

• The refrigerant pipe connecting section is set in the outdoor unit. Remove the front panel and the piping/ wiring panel. (M5: 9 pcs.)
• As shown in the illustration on the right, the hooks are at the right and left sides of the front panel. Lift up and remove the front panel.
• Pipes can be drawn out forward or downward from the outdoor unit.
• When drawing out the pipe forward, draw it out to the outside via the piping/wiring panel, and leave a space of 500mm or more from the main pipe connecting the outdoor unit with the indoor unit, considering service work or other work on the unit. (For replacing the compressor, 500mm or more space is required.)
• When drawing out the pipe downward, remove the knockouts on the base plate of the outdoor unit, draw
o
m
m
0
e
r
0
o
5
m
D
r
a
w
(Left piping)
r
i
n
(Left piping)
g
o
u
t
f
o
r
w
(Right piping)
a
r
d
Drawing out downward
the pipes out of the outdoor unit, and perform piping on the right/left or rear side. Downward length of the balance pipe should be 5m or less.
Hook
Front panel
Piping/wiring panel
(Rear piping)
(Right piping)
Ball valve of gas side
Packed valve of liquid side
Packed valve of balance pipe
(MAP080, MAP100, MAP120) (MAP140, MAP160)
Ball valve of gas side
Ball valve of liquid side
Packed valve of balance pipe
SMMS-i
Installation Manual
SMMS-i
Installation Manual
REQUIREMENT
• For a welding work of the refrigerant pipes, be sure to use nitrogen gas in order to prevent oxidation of the inside of the pipes; otherwise clogging of the refrigerating cycle due to oxidized scale may occur.
• Use clean and new pipes for the refrigerant pipes and perform piping work so that water or dust does not contaminate the refrigerant.
• Be sure to use a double spanner to loosen or tighten the flare nut. If a single spanner is used, the required level of tightening cannot be obtained. Tighten the flare nut with the specified torque. (If it is hard to loosen or tighten the flare nut of the balance pipe or packed valve of the liquid side with a double spanner, loosen or tighten the flare nut while holding the valve mounting plate with a spanner.)
Packed valve of
Outer dia. of
copper pipe
6.4 mm 14 to 18 (1.4 to 1.8 kgf•m)
9.5 mm 33 to 42 (3.3 to 4.2 kgf•m)
12.7 mm 50 to 62 (5.0 to 6.2 kgf•m)
15.9 mm 63 to 77 (6.3 to 7.7 kgf•m)
Tightening torque (N•m)
balance pipe
Ball valve of gas side
Packed valve of liquid side
Pipe connection method of valve at the gas side (Example)
Type
MAP080 MAP100
Pipe
diameter
Ø22.2
Draw-out forward Draw-out downward
Cut the L-shaped pipe at the horizontal straight section, then braze the supplied attachment pipe and the socket and pipe procured locally.
Gas
Liquid
pipe
Balance
pipe
Cut the L-shaped pipe at the horizontal straight section, then braze the supplied attachment pipe and the socket and pipe procured locally.
Gas pipe
Attachment pipe
Socket
Pipe
pipe
Section to be cut
Cut the L-shaped pipe at the vertical straight section, then braze the supplied attachment pipe and the socket and pipe procured locally.
Liquid
pipe
Balance
pipe
Cut the L-shaped pipe at the vertical straight section, then braze the supplied attachment pipe and the socket and pipe procured locally.
Gas pipe
Attachment pipe
Socket
Pipe
Gas pipe
Section to be cut
Type
MAP140 MAP160
Pipe
diameter
Ø28.6
Draw-out forward Draw-out downward
Cut the L-shaped pipe at the horizontal straight section, then braze the supplied attachment pipe, and the socket and pipe procured locally.
Gas
Liquid
pipe
Balance
pipe
Gas pipe
Attachment pipe
Socket
Pipe
pipe
Section to be cut
Cut the L-shape pipe at the vertical straight section, then braze the supplied attachment pipe, and the socket and pipe procured locally.
Liquid
pipe
Balance
pipe
Gas pipe
Attachment pipe
Socket
Pipe
Gas pipe
Section to be cut
Extruding margin of copper pipe with flare machining: B (Unit: mm)
Copper pipe outer
dia.
9.5
12.7
15.9
When using R410A
tool
0 to 0.5 1.0 to 1.5
When using
conventional tool
B
Extruding margin of copper pipe with flare tools: A (Unit: mm)
Copper pipe outer dia. A
9.5 13.2
12.7 16.6
15.9 19.7
* When using the conventional flare tool, to connect R410A pipes with flaring, make a margin approx. 0.5mm
longer than that of an R22 pipe so that the flare size matches the one specified. It is convenient to use a copper pipe gauge for size adjustment of the extruding margin.
+0
-0.4
A
MAP120
Ø28.6
pipe
Balance
pipe
Gas pipe
Attachment pipe
Socket
Pipe
Gas pipeLiquid
Section to be cut
Liquid
pipe
Balance
pipe
Gas pipe
Attachment pipe
Socket
Pipe
Gas pipe
Section to be cut
EN
19-EN 20-EN
–10–
21-EN 22-EN
SMMS-i
Installation Manual
–11–
SMMS-i
Installation Manual
Coupling size of brazed pipe
Connected section
External size Internal size
K
ØC
G
ØF
(Unit: mm)
Connected section
Standard outer dia.
of connected
copper pipe
6.35 6.35 (±0.03) 6.45 ( ) 7 6 0.06 or less 0.50
9.52 9.52 (±0.03) 9.62 ( ) 8 7 0.08 or less 0.60
12.70 12.70 (±0.03) 12.81 ( ) 9 8 0.10 or less 0.70
15.88 15.88 (±0.03) 16.00 ( ) 9 8 0.13 or less 0.80
19.05 19.05 (±0.03) 19.19 ( ) 11 10 0.15 or less 0.80
22.22 22.22 (±0.03) 22.36 ( ) 11 10 0.16 or less 0.82
28.58 28.58 (±0.04) 28.75 ( ) 13 12 0.20 or less 1.00
34.92 34.90 (±0.04) 35.11 ( ) 14 13 0.25 or less 1.20
38.10 38.10 (±0.05) 38.31 ( ) 15 14 0.27 or less 1.26
41.28 41.28 (±0.05) 41.50 ( ) 15 14 0.28 or less 1.35
External size Internal size
Standard outer dia.
(Allowable difference)
CFKG
+0.04
-0.02
+0.04
-0.02
+0.04
-0.02
+0.04
-0.02
+0.03
-0.03
+0.03
-0.03
+0.06
-0.02
+0.04
-0.04
+0.08
-0.02
+0.08
-0.02
Min. depth of
insertion
Oval value
Min. thickness
of coupling

Selection of pipe size

Capacity code of indoor and outdoor units
Selection of pipe material
• For the indoor unit, the capacity code is decided at each capacity rank. (Table 1)
• The capacity codes of the outdoor units are decided at each capacity rank. The maximum number of connectable indoor units and the total value of capacity codes of the indoor units are also decided. (Table 2)
NOTE
Compared with the capacity code of the outdoor unit, the total value of capacity codes of the connectable indoor units differs based on the height difference between the indoor units.
• When the height difference between the indoor units is 15m or less: Up to 135% of the capacity code (Equivalent to HP) of the outdoor unit (Equivalent to HP) of the outdoor unit
• When the height difference between the indoor units is over 15m: Up to 105% of the capacity code
Table 1
Indoor unit
capacity rank
007 0.8 2.2
009 1 2.8
012 1.25 3.6
015 1.7 4.5
018 2 5.6
024 2.5 7.1
027 3 8
030 3.2 9
036 4 11.2
048 5 14
056 6 16
072 8 22.4
096 10 28
Equivalent to HP
Capacity code
Equivalent to
capacity
Table 2
Outdoor unit model name
(Standard model)
MMY-MAP0804 822.413— — ——
MMY-MAP1004 10 28 16
MMY-MAP1204 12 33.5 20
MMY-MAP1404 14 40 23
MMY-MAP1604 16 45 27 MMY-AP1624 16 45 27
MMY-AP1814 18 50.4 30
MMY-AP2014 20 56 33
MMY-AP2214 22 61.5 37
MMY-AP2414 24 68 40 MMY-AP2424 24 68 40
MMY-AP2614 26 73 43 MMY-AP2624 26 73 43
MMY-AP2814 28 78.5 47 MMY-AP2824 28 78.5 47
MMY-AP3014 30 85 48 MMY-AP3024 30 85 48
MMY-AP3214 32 90 48 MMY-AP3224 32 90 48
MMY-AP3414 34 96 48 MMY-AP3424 34 96 48
MMY-AP3614 36 101 48 MMY-AP3624 36 101 48
MMY-AP3814 38 106.5 48 MMY-AP3824 38 106.5 48
MMY-AP4014 40 112 48 MMY-AP4024 40 112 48
MMY-AP4214 42 118 48 MMY-AP4224 42 118 48
MMY-AP4414 44 123 48 MMY-AP4424 44 123 48
MMY-AP4614 46 130 48 MMY-AP4624 46 130 48
MMY-AP4814 48 135 48 MMY-AP4824 48 135 48
Capacity code
Equivalent to HPEquivalent to
capacity
No. of
indoor
units
Outdoor unit model name
(High Efficiency
model)
Capacity code
Equivalent to HPEquivalent to
capacity
No. of
indoor
units
* For combination of the outdoor units, refer to “Combination of outdoor units”.
SMMS-i
Outdoor unit
(3) Main piping
Header unit A
(8)
(2)
(6)
First branch
Y-shape branching joint
Follower
Follower
unit B
unit C
(8)
(8)
(2)
(8) Outdoor unit connection piping kit (For linking of outdoor units)
(4)
(6)
Follower unit D
(1)(1)(1)
(4) Branching pipe
(5) Indoor unit connecting pipe
Indoor unit
(4)
Indoor unit
(2) Balance pipes Ø9.5
(1) Outdoor unit connecting pipes
(7) Branching header
(5) (5) (5) (5)
(6)
(6)
(4)
(6) Y-shaped branching joint
(4)
(6)
(4)
Installation Manual
(5)(5)(5)(5)(5)
SMMS-i
No.
Piping parts Name Selection of pipe size Remarks
Connecting pipe size of outdoor unit
Type Gas side Liquid side
Outdoor unit
È
(1)
Outdoor unit connection piping kit
Between Outdoor unit connection
(2)
piping kits
Outdoor unit connection piping kit of header unit
(3)
È
First branching section
Branching section
È
(4)
Branching section
Outdoor unit connecting pipe
Main connecting piping between outdoor units
Main piping
Branching pipe
MAP080 Ø22.2 Ø12.7
MAP100 Ø22.2 Ø12.7
MAP120 Ø28.6 Ø12.7
MAP140 Ø28.6 Ø15.9
MAP160 Ø28.6 Ø15.9
Pipe size for connecting piping between outdoor units
Total capacity codes of
outdoor units at the
downstream side
Equivalent to HPEquivalent to
16 to below 22
22 to below 26
26 to below 36
36 or more 101.0 or more Ø41.3 Ø22.2
Size of main piping
Total capacity codes of all
capacity
45.0 to below
61.5
61.5 to below
73.0
73.0 to below
101.0
outdoor units
Equivalent to HPEquivalent to
8 to below 12 22.4 to below 33.5 Ø22.2 Ø12.7
12 to below 14 33.5 to below 38.4 Ø28.6 Ø12.7
14 to below 22 38.4 to below 61.5 Ø28.6 Ø15.9
22 to below 36
36 to below 46
46 or more 130.0 or more * Ø41.3 Ø22.2
* Maximum equivalent length of main pipe is 70m or less (The actual
length is 50m or less.).
Pipe size between branching sections *1
Total capacity codes of indoor
units at downstream side
Equivalent to HP
Below 2.4 Below 6.6 Ø12.7 Ø9.5
2.4 to below 6.4 6.6 to below 18. 0 Ø15.9 Ø9.5
6.4 to below 12.2 18.0 to below 34.0 Ø22.2 Ø12.7
12.2 to below 20.2 34.0 to below 56 .5 Ø28.6 Ø15.9
20.2 to below 35.2 56.5 to below 98.5 Ø34.9 Ø19.1
35.2 or more 98.5 ore more Ø41.3 Ø22.2
61.5 to below
101.1 to below
Equivalent to
capacity
101.0
130.0
capacity
Gas
Liquid
side
side
Ø28.6 Ø15.9
Ø34.9 Ø19.1
Ø34.9 Ø19.1
Gas side
Ø34.9 Ø19.1
Ø41.3 Ø22.2
Gas side
Balanc
e pipe
Ø9.5
Liquid
side
Liquid
side
Installation Manual
Same as connecting pipe size of the outdoor unit.
Pipe size differs based on the total capacity code value of outdoor units at the downstream side. (See Table 2.)
Pipe size differs based on the capacity code of the outdoor unit. (See Table 2.)
Pipe size differs based on the total capacity code value of indoor units at the downstream side. If the total value exceeds the capacity code of the outdoor unit, apply the capacity code of the outdoor unit. (See Table 1 and 2.)
*1: If exceeding the main pip e size, set the size to the same as the
main pipe size.
23-EN 24-EN
–12–
EN
25-EN 26-EN
SMMS-i
No.
Piping parts Name Selection of pipe size Remarks
Connecting pipe size of indoor unit
Capacity rank Gas side
Branching section
È
(5)
Indoor unit
Indoor unit connecting pipe
007 to 012 type
015 to 018 type Ø12.7 Ø6.4
024 to 056 type Ø15.9 Ø9.5
072 to 096 type Ø22.2 Ø12.7
Selection of branching section (Y-shaped branching joint)
15m or less real length Ø9.5 Ø6.4
Real length exceeds 15m Ø12.7 Ø6.4
Installation Manual
Liquid
side
Total capacity code of indoor units
Model name
Branching section
(6)
Y-shaped branching joint
Equivalent to HP
Below 6.4 Below 18.0 RBM-BY55E
Y-shape branching joint
Selection of branching section (Branching header)
6.4 to below 14.2 18.0 to below 40.0 RBM-BY105E
14.2 to below 25.2 40.0 to below 70.5 RBM-BY205E
25.2 or more 70.5 or more RBM-BY305E
Equivalent to
capacity
Total capacity code of indoor units
Model name
*3
Model name
Branching section Branching header
(7)
Outdoor unit
Branching section
(8)
connection piping kit (For linking of outdoor units)
Equivalent to HP
For 4
*2 Branching header
*2: Up to a total of 6.0 maximum equivalent to HP capacity codes is connectable to one line
after branching of header. When the total capacity codes of all outdoor units are 12 to below 26 (equivalent to HP) and you use a branching header for the first branching section, use a RBM-HY2043E or RBM-HY2 083E regardless of the total capacity codes of outdo or units at downstream side. In addition, you cannot use a branching header for the first branching section when the total capacity codes of all outdoor units are over 26 (equivalent to HP).
Outdoor unit connection piping kit (For linking of outdoor units)
branches
For 8 branches
Below 14.2 Below 40.0 RBM-HY1043E
14.2 to below 25.2 40.0 to below 70.5 RBM-HY2043E
Below 14.2 Below 40.0 RBM-HY1083E
14.2 to below 25.2 40.0 to below 70.5 RBM-HY2083E
Equivalent to
capacity
Total capacity code of outdoor units
Equivalent to
capacity
Outdoor unit connection piping kit (For linking of outdoor units)
Equivalent to HP
Below 26.0 Below 73.0 RBM-BT14E
26.0 or more Above 73.0 RBM-BT24E
–13–
SMMS-i
Installation Manual
Allowable length of refrigerant pipes and allowable height
difference between units
D Follower unit
Outdoor unit
A
B
Height difference between outdoor units H3 5 m
Height difference between outdoor and indoor units: H1 70 m
Header
Follower
unit
La
LA
Outdoor unit connection piping kit (For linking of outdoor units)
The longest piping between outdoor units: L0 25 m
Main piping L1
First branching
section
unit
Lb
LB
L3
Y-shaped branching joint
C
Follower
unit
Ld
Lc
Outdoor unit connecting pipes
Branching header
Indoor unit connecting pipe
Indoor unit
abcde
The longest piping length: L 235 m
The longest piping length fr om the first branch: Li 90 m
L4
f
g
Indoor unit
L7
L5
L6
h
Y-shaped branching joint
i
j
(j)
Height difference between indoor units: H2 40 m
*3: Downstream side when regarding the main piping as the start point
SMMS-i
Installation Manual
SMMS-i
Installation Manual
System restriction
Outdoor unit combination Up to 4 units
Total capacity of outdoor units Up to 48 HP
Indoor unit connection Up to 48 units
Total capacity of indoor units (varies depending on the height difference between indoor units.)
H2 15m 135% of outdoor units’ capacity
15m < H2 105% of outdoor units’ capacity
Cautions for installation
• Set the outdoor unit first connected to the bridging pipe to the indoor units as the header unit.
• Install the outdoor units in order of their capacity codes: A (header unit) B C ≥ D
• When connecting gas pipes to indoor units, use Y-shaped branching joints to keep pipes level.
• When piping to outdoor units using Outdoor unit connection piping kits, intersect the pipes to the outdoor unit and those to indoor units at a right angle as shown in figure 1 on “6. INSTALLATION OF THE OUTDOOR UNIT”. Do not connect them as in figure 2 on “6. INSTALLATION OF THE OUTDOOR UNIT”.
Allowable length and allowable height difference of refrigerant piping
Item
Total extension of pipe (liquid pipe, real length)
Farthest piping length L (*1)
Main piping length
Pipe length
Height difference
*1: Farthest outdoor unit from the first branch: (D), farthest indoor unit: (j) *2: If the total capacity of outdoor units is 46HP or more, make the equivalent length 7 0m (real length 50m) or less . *3: Make the difference 65m or less if the height difference between outdoor and indoor units (H1) is more than 3m. *4: Make the difference 50m or less if the height difference between indoor units (H2) is more than 3m. *5: Make the difference 30m or less if the height difference between indoor units (H2) is more than 3m.
Farthest equivalent piping length from the first branch Li (*1)
Farthest equivalent piping length between outdoor units L0 (*1)
Maximum equivalent piping length of pipes connected to outdoor units
Maximum real length of pipes connected to indoor units 30m a, b, c, d, e, f, g, h, i, j
Maximum equivalent length betwee n branching sections 50m L2, L3, L4, L5, L6, L7
Height between outdoor and indoor units H1
Height between indoor units H2 40m
Height between indoor units H3 5m
Less than 96kW
96kW or more 34HP or more 500m
Less than 34HP or
less
Equivalent length 235m
Real length 190m
Equivalent length 120m (*2)
Real length 100m (*2)
Upper outdoor
units
Lower outdoor
units
Allowable
value
300m
LA + LB + La + Lb + Lc + Ld + L1 + L2 + L3 + L4 + L5 + L6 + L7 + a + b + c + d + e + f + g + h + i + j
LA + LB + Ld + L1 + L3 + L4 + L5 + L6 + j
90m (*3) L3 + L4 + L5 + L6 + j
25m LA + LB + Ld (LA + Lb, LA + LB + Lc)
10m La, Lb, Lc, Ld
70m (*4)
40m (*5)
Pipes
L1

Airtightness test

After the refrigerant piping has been finished, execute an airtight test. For an airtight test, connect a nitrogen gas canister as shown in the figure on the next page and apply pressure.
• Be sure to apply pressure from the service ports of the packed valves (or ball valves) at the liquid side, gas side and balance pipe side.
• An airtight test can only be performed at the service ports at the liquid side, gas side and balance pipe side on header unit.
• Close the valves fully at the gas side, liquid side and balance pipe side. As there is a possibility that the nitrogen gas will enter into the cycle of outdoor units, re-tighten the valve rods at the liquid side and balance pipe side before applying pressure. (When using MAP140 or MAP160, you do not have to re-tighten the liquid side valve rod as their valves at the liquid side are ball valves.)
• For each refrigerant line, apply pressure gradually in steps at the liquid side, gas side and balance pipe side.
Be sure to apply pressure at the gas side, liquid side, and balance pipe side.
WARNING
Never use oxygen, flammable gases, or noxious gases in an airtight test.
VLV
Copper pipe
High pressure gauge
Gauge
H
manifold
Reducing valve
Nitrogen gas
Connected to indoor unit
Main piping
Packed valve details
To gauge manifold
Liquid-side service port
Liquid-side valve
Balance
service port
Balance valve
Piping at site
To outdoor unit
Piping at site
To outdoor unit
Gas-side valve
To outdoor unit
Gas-side service port
Piping at site
Connected to other follower units
Brazed
Fully closed
Fully closed
Able to detect a serious leakage

1. Apply pressure 0.3MPa (3.0kg/cm²G) for 5 minutes or more.

2. Apply pressure 1.5MPa (15kg/cm²G) for 5 minutes or more.

Available to detect slow leakage

3. Apply pressure 3.73MPa (38kg/cm²G) for approx. 24 hours.

Gas side valve fully closed
Header outdoor unit
Service port
Service port
Liquid valve fully closed
Service port
Balanced pipe side valve fully closed
Low pressure gauge
Copper pipe
• If there is no pressure decrease after 24 hours, the test is passed.
EN
27-EN 28-EN
–14–
29-EN 30-EN
SMMS-i
Installation Manual
–15–
SMMS-i
Installation Manual
NOTE
However, if the environmental temperature changes from the moment of applying pressure to 24 hours after that, the pressure will change by about 0.01MPa (0.1kg/cm²G) per 1°C. Consider the pressure change when checking the test result.
REQUIREMENT
When pressure decrease is detected in steps 1-3, check the leakage at the connecting points. Check the leakage using a foaming agent or other measures and seal the leak with re-brazing, flare retightening or other methods. After sealing, execute an airtight test again.

Vacuum drying

• Be sure to perform vacuuming from both liquid and gas sides.
• Be sure to use a vacuum pump equipped with the counter-flow prevention function so that oil in the pump will not flow back into piping for air conditioners. (If oil in the vacuum pump enters in the air conditioner with R410A refrigerant, a problem may be caused in the refrigerating cycle.)
After finishing the airtight test and discharging nitrogen gas, connect the gauge manifold to the service ports of the liquid side, gas side, and balance pipe side and connect a vacuum pump as shown in the figure below. Be sure to perform vacuuming for the liquid, gas, and balance pipe sides.
Low pressure gauge
Service port
Service port
Packed valve details
To gauge manifold
Liquid-side service port
Liquid-side valve
valve
To outdoor unit
Piping at site
Balance service port
Balance
To outdoor unit
Piping at site
Main pipe
To outdoor unit
Gas-side valve
Gas-side service port
Piping at site
Connected to indoor unit
Brazed
Fully closed
Fully closed
Follower units
Packed valve fully closed (gas side)
Header outdoor unit
Service port
Packed valve fully closed (liquid side)
Packed valve fully closed (balance)
• Use a vacuum pump with a high vacuuming degree [-100.7kPa (5Torr, -755mmHg)] and large exhaust gas amount (40L/minute or larger).
• Perform vacuuming for 2 or 3 hours, though the time differs depending on the pipe length. Check that all the packed valves at the liquid side, gas side, and balance pipe side are fully closed.
• If the pressure does not reach -100.7kPa or less, continue vacuuming for 1 hour or more. If the pressure does not reach -100.7kPa after 3 hours of vacuuming, stop vacuuming and check for air leakage.
• If the pressure reaches -100.7kPa or less after vacuuming for 2 hours or more, close the valves VL and VH on the gauge manifold fully and stop the vacuum pump. Leave it as it is for 1 hour to confirm that the vacuuming degree does not change. If the degree of vacuum loss is large, moisture may remain in the pipes. In that case, inject dry nitrogen gas and apply pressure to 0.05MPa and perform vacuuming again.
• After finishing the above procedure of vacuuming, exchange the vacuum pump with a refrigerant canister and advance to the additional charging of refrigerant.
High pressure gauge
VL VH
Vacuum pump
Gauge manifold
P
SMMS-i
Installation Manual
SMMS-i
Installation Manual

Adding refrigerant

After finishing vacuuming, exchange the vacuum pump with a refrigerant canister and start additional charging of refrigerant.
Calculation of additional refrigerant charge amount
Refrigerant charge amount at shipment from the factory does not include the refrigerant for pipes at the local site. For refrigerant to be charged in pipes at the local site, calculate the amount and charge it additionally.
NOTE
If the additional refrigerant amount indicates minus as the result of calculation, use the air conditioner without additional refrigerant.
Heat pump
type
Cooling only
type
Additional refrigerant charge
amount at local site
Table 1
Liquid pipe dia. (mm) 6.4 9.5 12.7 15.9 19.1 22.2
Additional refrigerant amount/1m liquid pipe (kg/m)
Outdoor unit type MAP080 MAP100 MAP120 MAP140 MAP160
Charging amount (kg) 11. 5
Outdoor unit type MAP080 MAP100 MAP120 MAP140 MAP160
Charging amount (kg) 10.5 10.5 10.5 11.5 11.5
Real length of liquid pipe
=
0.025 0.055 0.105 0.160 0.250 0.350
Additional refrigerant charge
amount per 1m liquid pipe
×
(Table 1)
Corrective amount of refrigerant
depending on HP of co-
+
operating outdoor units
(Table 2)
Table 2
C (Corrective amount
of refrigerant) (kg)
Standard type
High Efficiency type
Combined HP (HP) Combined outdoor units (HP)
88HP––– 1.5
10 10HP 2.5
12 12HP 3.5
14 14HP 8.5
16 16HP 10.5
18 10HP 8HP 0.0
20 10HP 10HP 3.0
22 12HP 10HP 5.0
24 12HP 12HP 7.5
26 16HP 10HP 8.5
28 16HP 12HP 9.5
30 16HP 14HP 11.5
32 16HP 16HP 12.5
34 12HP 12HP 10HP 3.0
36 12HP 12HP 12HP 4.0
38 16HP 12HP 10HP 6.0
40 16HP 12HP 12HP 7.0
42 16HP 14HP 12HP 8.0
44 16HP 16HP 12HP 10.0
46 16HP 16HP 14HP 12.0
48 16HP 16HP 16HP 14.0
16 8HP 8HP 0.0
24 8HP 8HP 8HP -4.0
26 10HP 8HP 8HP -4.0
28 10HP 10HP 8HP -2.0
30 10HP 10HP 10HP 0.0
32 8HP 8HP 8HP 8HP -6.0
34 10HP 8HP 8HP 8HP -6.0
36 10HP 10HP 8HP 8HP -6.0
38 10HP 10HP 10HP 8HP -6.0
40 10HP 10HP 10HP 10HP -5.0
42 12HP 10HP 10HP 10HP -4.0
44 12HP 12HP 10HP 10HP -2.0
46 12HP 12HP 12HP 10HP 0.0
48 12HP 12HP 12HP 12HP 2.0
Charging of refrigerant
• Keeping the valve of the outdoor unit closed, be sure to charge the liquid refrigerant into the service port at the liquid side.
• If the specified amount of refrigerant cannot be charged, fully open the valves of the outdoor unit at liquid and gas sides, operate the air conditioner in COOL mode, and then charge refrigerant into service port at the gas side. In this time, choke the refrigerant slightly by operating the valve of the canister to charge liquid refrigerant.
• The liquid refrigerant may be charged suddenly, therefore be sure to charge refrigerant gradually.
EN
31-EN 32-EN
–16–
33-EN 34-EN
SMMS-i
Installation Manual
–17–
SMMS-i
Installation Manual

Full opening of the valve

Open the valves of the outdoor unit fully.
MAP080 MAP100 MAP120
Packed valve
Using a 4mm-hexagonal wrench, fully open the valve rods.
Liquid side
Balance pipe
Gas side
Balance packed valve
Using a 4mm-hexagonal wrench, fully open the valve rods.
Ball valve
Using a minus screwdriver, turn it counterclockwise by 90° until it hits the stopper. (Full open)
MAP140 MAP160
Ball valve
Using a flathead screwdriver, turn it counterclockwise by 90° until it hits the stopper. (Full open)
Service port
Valve unit
Using flathead screwdriver, turn it counterclockwise by
(1)
(2)
90° until it hits the stopper. (Full open)
Flare nut
Position of screwdriver slot
Fully closed
* When opened fully, do not apply
excessive torque after the screwdriver hits
the stopper; otherwise a problem may be
caused on the valve. (5 N•m or less)
Fully opened
Slot

F-GAS label

This product contains fluorinated greenhouse gases covered by the Kyoto Protocol
• Chemical Name of Gas R410A
• Global Warming Potential (GWP) of Gas 1975
CAUTION

1. Stick the enclosed refrigerant label adjacent to the charging and/or recovering location.

2. Clearly write the charged refrigerant quantity on the refrigerant label using indelible ink. Then, place the included
transparent protective sheet over the label to prevent the writing from rubbing off.
3. Prevent emission of the contained fluorinated greenhouse gas. Ensure that the fluorinated greenhouse gas is
never vented to the atmosphere during installation, service or disposal. When any leakage of the contained fluorinated greenhouse gas is detected, the leak shall be stopped and repaired as soon as possible.

4. Only qualified service personnel are allowed to access and service this product.

5. Any handling of the fluorinated greenhouse gas in this product, such as when moving the product or recharging
the gas, shall comply under (EC) Regulation No. 842/2006 on certain fluorinated greenhouse gases and any relevant local legislation.

6. Periodical inspections for refrigerant leaks may be required depending on European or local legislation.

7. Contact dealers, installers, etc., for any questions.

Pre-charged Refrigerant at Factory [kg],
R410A
specified in the nameplate
kg
Additional Charge on Installation Site [kg]
kg
kg
Fully closed
Fully opened

Heat insulation for pipe

• Apply heat insulation of pipe separately at the liquid, gas, and balance sides.
• Be sure to use thermal insulator resistant up to 120°C or higher for pipes at the gas side.

Finishing after connecting pipes

• After piping connection work has been finished, cover the opening of the piping/wiring panel with the piping cover, or fill silicon or putty into the space between the pipes.
• In case of drawing-out the pipes downward or sideward, also close the openings of the base plate and the side plate.
• Under the opened condition, a problem may be caused due to the entering of water or dust.
SMMS-i
Installation Manual
SMMS-i
Installation Manual
When using the piping cover When not using the piping cover
Piping/wiring panel
Drawing-out frontward
Drawing-out downward
Drawing-out sideward
Close the opening with the pipe cover.
Piping/wiring panel
Drawing-out frontward
Drawing-out downward
Pipe holding bracket
Attach pipe holding brackets following the table below.
Diameter of pipe (mm) Interval
Ø15.9 - Ø19.1 2m
Ø22.2 - Ø41.3 3m
Drawing-out sideward
Fill silicon or putty into the periphery of the pipes.

8 ELECTRIC WIRING

WARNING
The appliance shall be installed in accordance with national wiring regulations.
Capacity shortages of the power circuit or an incomplete installation may cause an electric shock or fire.
CAUTION
• Perform wiring of power supply complying with the rules and regulations of the local electric company.
• Do not connect 380V - 415V power to the terminal blocks for control cables (U1, U2, U3, U4, U5, U6); otherwise, the unit may break down.
• Be sure that electric wiring does not come into contact with high-temperature parts of piping; otherwise, the coating of cables may melt and cause an accident.
• After connecting wires to the terminal block, take off the traps and fix the wires with cord clamps.
• Follow the same structure for both the control wiring and refrigerate piping.
• Do not conduct power to indoor units until vacuuming of the refrigerant pipes has finished.
• For the wiring of power to indoor units and that between indoor and outdoor units, follow the instructions in the installation manual of each indoor unit.

Power supply specifications

Do not bridge the power between outdoor units through the equipped terminal blocks (L N).
1, L2, L3,
Power supply for
outdoor units
NO GOOD
Power wiring selection
Standard model
Model
MMY-MAP0804* MMY-MAP1004* MMY-MAP1204* MMY-MAP1404* MMY-MAP1604*
MMY-AP1814* MMY-AP2014* MMY-AP2214* MMY-AP2414* MMY-AP2614* MMY-AP2814* MMY-AP3014* MMY-AP3214*
35-EN 36-EN
–18–
Phase and frequency Nominal Voltage
3N~ 50Hz 380-400-415V
3N~ 50Hz 380-400-415V
Power Supply
MOCP: Maximum Overcurrent Protection (Amps)
MCA: Minimum Circuit Amps
MCA
(A)
23.5
25.5
28.5
33.2
36.5
49.0
51.0
54.0
57.0
62.0
65.0
69.7
73.0
MOCP
(A)
32 32 40 40 50
63 63 63 63 80 80 80
100
EN
37-EN 38-EN
SMMS-i
Installation Manual
–19–
SMMS-i
Installation Manual
Model
MMY-AP3414* MMY-AP3614* MMY-AP3814* MMY-AP4014* MMY-AP4214* MMY-AP4414* MMY-AP4614* MMY-AP4814*
Power Supply
Phase and frequency Nominal Voltage
3N~ 50Hz 380-400-415V
MCA
(A)
82.5
85.5
90.5
93.5
98.2
101.5
106.2
109.5
MOCP
High efficiency model
Model Phase and frequency Nominal Voltage
MMY-AP1624* 3N~ 50Hz 380-400-415V 46.9 63
MMY-AP2424* MMY-AP2624* MMY-AP2824* MMY-AP3024*
MMY-AP3224* MMY-AP3424* MMY-AP3624* MMY-AP3824* MMY-AP4024* MMY-AP4224* MMY-AP4424* MMY-AP4624* MMY-AP4824*
3N~ 50Hz 380-400-415V
3N~ 50Hz 380-400-415V
L1L2L3 N
L1L2L3 N L1L2 L3N L1L2 L3N
MCA
(A)
70.4
72.4
74.5
76.5
93.8
95.9
97.9
100.0
102.0
105.0
108.0
111.0
114.0
MOCP
(A)
100 100 100 125 125 125 125 125
(A)
80
80 100 100
125 125 125 125 125 125 125 125 125

Specifications for communication wiring

Design of communication wiring
Summary of communication wiring
Central control controller
U1 U2 U3 U4
Indoor unit
Header outdoor
U1 U2 U3 U4 U5 U6 U1 U2 U3 U4 U5 U6
Communication wiring between indoor and outdoor units (Shield wire)
Communication wiring between indoor units (Shield wire)
U1 U2
AB AB U2U1U2U1 A B U2U1 A B
Indoor unit
AB AB AB
Remote controller
Follower outdoor
Communication wiring between outdoor units (Shield wire)
Indoor unit
Remote controller
Remote controller
(Group control)
Indoor unit
Circuit breaker
(Earth leakage breaker)
Main switch (Fuse)
• Communication wiring and central control wiring use 2-core non-polarity wires. Use 2-core shield wires to prevent noise trouble. In this case, for the system grounding, close (connect) the end of shield wires, and isolate the end of terminal. Perform the ground of wires at one side only for the header outdoor unit.
• Use 2-core non-polarity wire for remote controller. (A, B terminals) Use 2-core non-polarity wire for wiring of group control. (A, B terminals)
SMMS-i
Installation Manual
SMMS-i
Installation Manual
Be sure to keep the rule of below tables about size and length of communication wiring.
Central
control
controller
U1U3U2
U4
Outdoor unit
Indoor unit
Remote controller
Header
unit
U1 U2
L1
U1 U2
U3 U4
A B
U5 U6
Table-3
U1 U2
U1 U2
U3 U4
A B
Header unit
U5 U6
Remote controller
Super modular multi system
U3 U4
U5 U6
U1 U2
A B
Table-1
Follower unit
U3 U4
U1 U2
U5 U6
Table-1
L7
L4
U5 U6
U1 U2
Follower unit
U1 U2
L5
A B
Follower unit
U3 U4
U1 U2
L2 L3
U1 U2
A B
Remote controller
U1 U2
U1 U2
U3 U4
A B
Header unit
U5 U6
Table-2
U1 U2
Follower unit
U3 U4
U1 U2
A B
L6
U5 U6
U1 U2
A B
Table-1 Communication wiring between indoor and outdoor units (L1, L2, L3), Central control wiring
(L4)
Wiring 2-core, non-polarity
Type Shield wire
Size/Length 1.25 mm
(*1): Total length of Communication wiring length for all refrigerant circuits (L1 + L2 + L3 + L4)
2
: Up to 1000 m/2.0 mm2: Up to 2000 m (*1)
Table-2 Communication wiring between outdoor units (L5)
Wiring 2-core, non-polarity
Type Shield wire
Size/Length 1.25 mm
2
to 2.0 mm2/Up to 100 m (L5)
Group control through a Remote Controller
Group control of multiple indoor units (8 units) through a single remote controller switch
Indoor unit
No.1
AB AB AB AB AB AB
Remote controller
(A.B)
No.2
No.3
No.4
No.7
No.8

Connection of power wires and communication wires

Remove knockouts on the piping/wiring panel on the front of the unit and the panel on the bottom to get the power and communication wires through the holes.
Piping/wiring panel
Knockout for the
communication wire
Knockout for the power wire
NOTE
Be sure to separate the power wire and communication wires.
Knockout for the power supply wire
Table-3 Remote controller wiring (L6, L7)
Wire 2-core, non-polarity
Size 0.5 mm
Length
2
to 2.0 mm2
• Up to 500 m (L6 + L7)
• Up 400 m in case of wireless remote controller in group control.
• Up to 200 m total length of communication wiring between indoor units (L6)
EN
39-EN 40-EN
–20–
41-EN 42-EN
SMMS-i
Installation Manual
–21–
SMMS-i
Installation Manual
Screw size and tightening torque
Tightening torque
(N•m)
Power supply terminal block
Screw size
Power supply terminal M6 2.5 to 3.0
Earth screw M8 5.5 to 6.6
Cord clamps
Communication terminal block
Power supply wires
Cord clamp
Earth screw
Communication
wires
Power supply wire connection
1. Insert the power supply wire through the cutout on the side of the electric parts box and connect the power supply wire to the power supply terminal block and the earth line to the earth screw. After that, fix the power supply wire with the 2 cord clamps.

2. Be sure to use round-type crimping terminals for power connection. Also, apply insulating sleeves to the crimping parts. Use a driver of appropriate size to fix the terminal screws.

L1 L2 L3
N
Communication wire connection
Get the communication wire through the cutout on the side of the electric parts box and connect it to the communication wire terminals, then fix it with the communication cable clamp.
U1 U2 U3 U4 U5 U6
TO
INDOOR
UNIT
Screw size and tightening torque
Communication wire terminal M3.5 0.80 to 0.96
TO CENTRAL CONTROL
LER
TO
OUTDOOR
UNIT
U5, U6: Communication wiring between outdoor units
U
3, U4: Central control device
U
1, U2: Communication wiring between Indoor/Outdoor unit
Screw size
Tightening torque
(N•m)
10mm or more
Earth line
L1 L2 L3 N
Power supply wire
SMMS-i
Installation Manual
SMMS-i
Installation Manual

Regulation of high frequency wave

This equipment complies with IEC 61000-3-12 provided that the short-circuit power Ssc is greater than or equal to Ssc (*1) at the interface point between the user’s supply and the public system. It is the responsibility of the installer or user of the equipment to ensure, by consultation with the distribution network operator if necessary, that the equipment is connected only to a supply with a short-circuit power Ssc greater than or equal to Ssc (*1)
Furthermore, when similar equipment or other equipment which may cause harmonic current emissions are to be connected to the same interface point with this equipment, to reduce the risk of possible problems which may be caused from addition of those harmonic current emissions, it is recommended to make sure that the short-circuit power Ssc at the interface point is greater than the sum of the minimum Ssc required by all the equipment which will be connected to the interface point.
Ssc (*1)
MMY-MAP0804HT8(Z)(ZG)-E MMY-MAP0804T8(Z)(ZG)-E
MMY-MAP1004HT8(Z)(ZG)-E MMY-MAP1004T8(Z)(ZG)-E
MMY-MAP1204HT8(Z)(ZG)-E MMY-MAP1204T8(Z)(ZG)-E
MMY-MAP1404HT8(Z)(ZG)-E MMY-MAP1404T8(Z)(ZG)-E
MMY-MAP1604HT8(Z)(ZG)-E MMY-MAP1604T8(Z)(ZG)-E
Model Ssc (kVA)
1004
1290
1560
1692
1942

9 ADDRESS SETTING

On this unit, it is required to set the addresses of the indoor units before starting air conditioning. Set the addresses following the steps below.
CAUTION
• Be sure to complete the electric wiring before setting the addresses.
• If you turn on the outdoor unit before turning on the indoor units, the CODE No. [E19] is indicated on the 7­segment display on the interface P.C. board of the outdoor unit until the indoor units are turned on. This is not a malfunction.
• It may take up to ten minutes (normally about five minutes) to address one refrigerant line automatically.
• Settings on the outdoor unit are required for automatic addressing. (Address setting is not started simply by turning on the power.)
• Running the unit is not required for address setting.
• The addresses can be set manually.
Automatic addressing: setting addresses using SW15 on the interface P.C. board on the header outdoor unit Manual addressing:
REQUIREMENT
• High voltage parts exist in the electrical control box. If you set addresses on an outdoor unit, operate the unit through the access door shown on the illustration on the right to avoid electric shock. Do not remove the cover of electrical control box.
* After finishing operations, close the access door cover
and fix it with the screw.
setting addresses on the wired remote controller. * When setting an address manually, the wired remote controller must temporarily be
paired with an indoor unit one-to-one. (when the system is organized for group operation and no Remote controller)
Access door cover
Cover of the electrical control box
Fixing screw for the access door cover

Automatic address setting

No central control: go to Address setting procedure 1 Central control of 2 or more refrigerant lines: go to Address setting procedure 2
(Example)
Address setting procedure
System wiring diagram
43-EN 44-EN
–22–
When controlling a single refrigerant line
Outdoor
Indoor
Remote
controller
centrally
To procedure 1 To procedure 2
Indoor
Central
remote
controller
Indoor
Central remote
controller
Indoor
Remote
controller
Outdoor
Remote
controller
When controlling 2 or more refrigerant lines
Outdoor
Indoor
Remote
controller
centrally
Indoor
Remote
controller
Outdoor
Indoor
Remote
controller
Central remote
controller
Indoor
EN
45-EN 46-EN
SMMS-i
Installation Manual
–23–
SMMS-i
Installation Manual
Address setting procedure 1

1 Turn on indoor units first, and then turn on outdoor units. 2 About one minute after turning the power on, confirm that the 7-segment display on the interface

P.C. board of the header outdoor unit indicates .
U. 1. L08 (U. 1. flash)

3 Press SW 15 to start the automatic address setting.

(It may take up to 10 minutes (normally about 5 minutes) to complete one line’s setting.)
4 The 7-segment display indicates .
After the indication, starts flashing on the display. When the flashing stops and remain lit on the display, the setting is
U. 1. - - - (U. 1. flash)
Auto 1 Auto 2 Auto 3
U. 1. - - - (U. 1. light)
complete.
Interface P.C. board on the header outdoor unit
SW05 SW15
SW04
D600 D601 D602 D603
D604
3
2,4
SW02 SW03
SW01
REQUIREMENT
• When 2 or more refrigerant lines are controlled as a group, be sure to turn on all the indoor units in the group before setting addresses.
• If you set the unit addresses of each line separately, each line’s header indoor unit is set separately. In that case, the CODE No. “L03” (Indoor header unit overlap) is indicated as running starts. Change the group address to make one unit the header unit using wired remote controller.
(Example) Controlling 2 or more refrigerant lines as a group
System wiring diagram
Outdoor
Indoor
Remote
controller
Indoor
(Group control)
Outdoor
Indoor
Indoor
Address setting procedure 2
1 Set a system address for each system using SW 13 and 14 on the interface P.C. board on the
header outdoor unit of each system. (Factory default: Address 1)
NOTE
Be sure to set a unique address on each system. Do not use a same address as another system (refrigerant line) or a custom side.
Interface P.C. board on the header outdoor unit
SW06 SW07 SW09 SW10
1234 1234 1234 1234
SW11 SW12 SW13 SW14
1234 1234 1234 1234
Switch settings for a line (system) address on the interface P.C. board on the outdoor unit
({: switch ON, : switch OFF)
Line (system) address
1 –––✕✕✕✕✕
2 ––– { ✕✕✕
3 –––✕✕{ ✕✕
4 ––– {{✕✕
5 –––✕✕✕{
6 ––– { {
7 –––✕✕{{
8 ––– {{{
9 –––✕✕✕✕{
10 ––– { ✕✕{
11 –––✕✕{ {
12 ––– {{ {
13 –––✕✕✕{{
14 ––– { {{
15 –––✕✕{{{
16 ––– {{{{
17 –––{ ✕✕✕✕
18 –––{{✕✕✕
19 –––{ { ✕✕
20 –––{{{✕✕
21 –––{ ✕✕{
22 –––{{ {
23 –––{ {{
24 –––{{{{
25 –––{
12341234
SW13 SW14
✕✕✕{
SMMS-i
Installation Manual
SMMS-i
Installation Manual
Line (system) address
26 –––{{✕✕{
27 –––{ { {
28 –––{{{ {
“–”: not used for system address setting (Do not change their positions.)
12341234
SW13 SW14
2 Be sure to disconnect the relay connectors between the [U1U2] and [U3U4] terminals on all the
header outdoor units that will be connected to the central control. (Factory default: disconnected)
2
U1 U2 U3 U4 U5 U6
TO
INDOOR
UNIT
TO
CENTRAL
CONTROL
LER
TO
OUTDOOR
UNIT

3 Turn on indoor units first, and then turn on outdoor units. 4 About 1 minute after turning the power on, confirm that the 7-segment display on the interface

P.C. board of the header outdoor unit indicates .
U. 1. L08 (U. 1. flash)

5 Press SW 15 to start the automatic address setting.

(It may take up to 10 minutes (normally about 5 minutes) to complete one line’s setting.)
6 The 7-segment display indicates .
After the indication, starts flashing on the display. When the flashing stops and , remains lit on the display, the setting is
U. 1. - - - (U. 1. flash)
Auto 1 Auto 2 Auto 3
U. 1. - - - (U. 1. light)
complete.

7 Repeat steps 4 to 6 for other refrigerant lines. 8 After completing address setting of all systems, turn off dip switch 2 of SW30 on the interface P.C.

boards of all the header outdoor units connected to the same central control, except the unit that has the lowest address.
(For unifying the termination of the wiring for the central control of indoor and outdoor units)
9 Connect the relay connectors between the [U1, U2] and [U3, U4] terminals of the header outdoor
unit of each refrigerant line.
9
U1 U2 U3 U4 U5 U6
TO
INDOOR
UNIT
10

Set the central control address.

(For the setting of the central control address, refer to the installation manuals of the central control devices.)
Header unit interface P.C. board
7-segment
display
SW13 SW14
12
SW30
TO
CENTRAL
CONTROL
LER
SW04
D600 D601 D602 D603 D604
SW01 SW02
OUTDOOR
SW05
TO
UNIT
SW15
SW03
EN
47-EN 48-EN
–24–
49-EN 50-EN
SMMS-i
Installation Manual
–25–
SMMS-i
Installation Manual
Switch setting (setting example when controlling 2 or more refrigerant lines centrally)
Outdoor units (setting manually)
Outdoor unit’s interface
P.C. board
SW13, 14 (Line (system) address)
Dip switch 2 of SW30 (Terminator of indoor/ outdoor communication line and central control line)
Relay connector
Header unit
Relay
connector
Header unit Follower unit Header unit Follower unit Header unit Factory default
Remote
(No setting
required)
(No setting
required)
Open
Header unit
connector
Relay
1
ON
Connect after
setting
addresses.
Follower unit
U3 U4 U3 U4 U3 U4 U3 U4 U3 U4
U1 U2
U5 U6 U1 U2 U5 U6 U1 U2 U5 U6 U1 U2 U5 U6 U1 U2
U1 U2 U1 U2 U1 U2 U1 U2 U1 U2
A
BAB ABAB AB
Remote
controller
controller
Individual
2
Set to OFF
after setting
addresses.
Connect after
setting
addresses.
Remote
controller
Group
*The items in bold font must be set manually.
(No setting
required)
(No setting
required)
Open
Follower unit
3 1
Set to OFF
after setting
addresses.
Connect after
setting
addresses.
Header unit
Remote
controller
U5 U6
Relay
connector
ON
Open
controller
Central control
CAUTION
Relay connector connection
Never connect relay connectors between the [U1, U2] and [U3, U4] terminals before completing address setting of all the refrigerant lines. Otherwise, the addresses cannot be set correctly.

Manual address setting using the remote controller

Procedure when setting indoor units’ addresses first under the condition that indoor wiring has been completed and outdoor wiring has not been started (manual setting using the remote controller)

Wiring example of 2 refrigerant lines
Refrigerant line 1
Outdoor
unit
Indoor unit 1
Remote
controller
Line (system) address 1 1 1 2 2
Indoor unit address 1 2 3 1 2
Group address
Header unit2Follower unit2Follower unit2Follower unit2Follower unit
Indoor unit 2
1
Indoor unit 3

In the example above, disconnect the remote controller connections between the indoor units and connect a wired remote controller to the target unit directly before address setting.

Refrigerant line 2
Outdoor
unit
Indoor unit 1
Indoor unit 2
Indoor units (automatic setting)
Line (system) address 1 1 2 2 3
Indoor unit address 1 2 1 2 1
Group address 0 0 1 2 0
SET
SET DATA
2, 5, 8
TEMP.
4, 7, 10
FILTER
11
Pair the indoor unit to set and the remote controller one-to-one.
Turn on the power.
SET
CL
1 Push and hold the , , and buttons at
the same time for more than 4 seconds.
LCD starts flashing.
TEST
RESET
UNIT No.
R.C. No.
CODE No.
CODE No.
ON / OFF
3, 6, 9
DATA
SETTING
TIMER SET
TIME
SET CL
TEST
1
SMMS-i
}
Installation Manual
SMMS-i
Installation Manual
<Line (system) address>
2 Push the TEMP. / buttons
repeatedly to set the CODE No. to .
3 Push the TIME / buttons repeatedly to
set a system address.
(Match the address with the address on the interface P.C. board of the header outdoor unit in the same refrigerant line.)
4 Push button.
<Indoor unit address>
SET
(It is OK if the display turns on.)
5 Push the TEMP. / buttons
repeatedly to set the CODE No. to .
6 Push the TIME / buttons repeatedly to
set an indoor unit address.
7 Push the button.
(It is OK if the display turns on.)
<Group address>
SET
8 Push the TEMP. / buttons
repeatedly to set the CODE No. to .
9 Push the TIME / buttons repeatedly to
set a group address. If the indoor unit is individual, set the address to ; header unit, ; follower unit, .
Individual : 0000 Header unit : 0001 Follower unit : 0002
10
Push the button.
(It is OK if the display turns on.)
11
Push the button.
The address setting is complete. ( flashes. You can contr ol the unit after
SETTING SETTING
has disappeared.)
SET
TEST
In case of group
}
control
NOTE
1. Do not use address numbers 29 or 30 when setting system addresses using the remote controller. These 2 address numbers cannot be used on outdoor units and the CODE No. [E04] (Indoor/ outdoor communication error) will appear if they are mistakenly used.
2. If you set addresses to indoor units in 2 or more refrigerate lines manually using the remote controller and will control them centrally, set the header outdoor unit of each line as below.
• Set a system address for the header outdoor unit
of each line with SW13 and 14 of their interface P.C. boards.
• Turn off dip switch 2 of SW30 on the interface P.C.
boards of all the header outdoor units connected to the same central control, except the unit that has the lowest address. (For unifying the termination of the wiring for the central control of indoor and outdoor units)
• Connect the relay connectors between the [U1,
U2] and [U3, U4] terminals on the header outdoor unit of each refrigerate line.
• After finishing all the settings above, set the
address of the central control devices. (For the setting of the central control address, refer to the installation manuals of the central control devices.)
Confirming the indoor unit
addresses and the position of an indoor unit using the remote controller
Confirming the numbers and positions of indoor units
To see the indoor unit address of an indoor unit which you know the position of
When the unit is individual (the indoor unit is
paired with a wired remote controller one-to­one), or it is a group-controlled one.
CODE No.
UNIT No.
FILTER RESET
TEMP.
TEST
TIMER SET
TIME
SET CL
ON / OFF
1
Starts running
2
(Execute it while the units are running.)
1 Push the button if the units stop. 2 Push the button (left side of the
button).
A unit numbers is indicated on the LCD (it will disappear after a few seconds). The indicated number shows the system address and indoor unit address of the unit. When 2 or more indoor units are connected to the remote controller (group-controlled units), a number of other connected units appears each time you push the button (left side of the button).
ON / OFF
To find an indoor unit’s position from its address
When checking unit numbers controlled as a
group
UNIT No.
R.C. No.
VENT
CODE No.
ON / OFF
1
2
TEST
DATA
SET
SETTING
TEMP.
TIMER SET
3
Stop
FILTER RESET
TIME
SET CL
TEST
1
(Execute it while the units are stopped.)
The indoor unit numbers in a group are indicated one after another. The fan and louvers of the indicated units are activated.
1 Push and hold the and buttons at
the same time for more than 4 seconds.
appears on UNIT No. on the LCD display.
• The fans and louvers of all the indoor units in the group are activated.
2 Push the button (left side of the
button). Each time you push the button, the indoor unit numbers are indicated one after another.
• The first-indicated unit number is the address of the header unit.
• Only the fan and louvers of the indicated indoor unit are activated.
3 Push the button to finish the procedure.
All the indoor units in the group stop.
To check all the indoor unit addresses using
an arbitrary wired remote controller. (When communication wirings of 2 or more
TEST
EN
51-EN 52-EN
–26–
53-EN 54-EN
SMMS-i
Installation Manual
–27–
SMMS-i
Installation Manual
refrigerant lines are interconnected for central control)
UNIT No.
R.C. No.
CODE No.
ON / OFF
2 4
5
TEST
DATA
SET
SETTING
TEMP.
TIMER SET
1
FILTER RESET
TIME
TEST
SET CL
6
3
(Execute it while the units are stopped.)
You can check indoor unit addresses and positions of the indoor units in a single refrigerant line. When an outdoor unit is selected, the indoor unit numbers of the refrigerant line of the selected unit are indicated one after another and the fan and louvers of the indicated indoor units are activated.
1 Push and hold the TIME and buttons
at the same time for more than 4 seconds. At first, the line 1 and CODE No. (Address Change) are indicated on the LCD display. (Select an outdoor unit.)
2 Push the (left side of the button) and
SWING/FIX
buttons repeatedly to select a system
address.
3 Push the button to confirm the system
SET
address selection.
• The address of an indoor unit connected to the selected refrigerant line is indicated on the LCD display and its fan and louvers are activated.
4 Push the button (left side of the
button). Each time you push the button, the indoor unit numbers of the selected refrigerant line are indicated one after another.
• Only the fan and louvers of the indicated indoor unit are activated.
To select another system address
5 Push the CL button to return to step 2.
• After returning to step 2, select another system
CL
address and check the indoor unit addresses of the line.
6 Push the button to finish the procedure.
TEST
Changing the indoor unit
address using a remote controller
To change an indoor unit address using a wired remote controller.
The method to change the address of an
individual indoor unit (the indoor unit is paired with a wired remote controller one-to-one), or an indoor unit in a group. (The method is available when the addresses have already been set automatically.)
UNIT No.
R.C. No.
ON / OFF
2, 6, 7
CL
CODE No.
4
TEST
DATA
SET
SETTING
TEMP.
3 5
8
Finish
FILTER RESET
TIMER SET
TIME
SET CL
TEST
1
(Execute it while the units are stopped.)
1 Push and hold the , , and buttons at
the same time for more than 4 seconds.
(If 2 or more indoor units are controlled in a group, the first indicated UNIT No. is that of the head unit.)
SET
2 Push the button (left side of the
button) repeatedly to select an indoor unit number to change if 2 or more units are controlled in a group. (The fan and louvers of the selected indoor unit are activated.)
(The fan of the selected indoor unit is turned on.)
3 Push the TEMP. / buttons
repeatedly to select for CODE No..
4 Push the TIME / buttons repeatedly to
change the value indicated in the SET DATA section to that you want.
5 Push the button.
SET
6 Push the button (left side of the
button) repeatedly to select another indoor UNIT No. to change.
Repeat steps 4 to 6 to change the indoor unit addresses so as to make each of them unique.
7 Push the button (left side of the
button) to check the changed addresses.
8 If the addresses have been changed
correctly, push the button to finish the procedure.
TEST
To change all the indoor unit addresses using
an arbitrary wired remote controller. (The method is available when the addresses have already been set automatically.)
(When communication wirings of 2 or more refrigerant lines are interconnected for central control)
NOTE
You can change the addresses of indoor units in each refrigerant line using an arbitrary wired remote controller.
* Enter the address check/change mode and change
the addresses.
UNIT No.
R.C. No.
CODE No.
ON / OFF
1
FILTER RESET
SET
TEMP.
DATA
SETTING
TIMER SET
TIME
SET CL
TEST
2
3
If no number appears on UNIT No., no outdoor unit exists on the line. Push button and select another line following step
(Execute it while the units are stopped.)
1 Push and hold the TIME / buttons at
2 Push (left side of the button) and
CL
2.
the same time for more than 4 seconds. At first, the line 1 and CODE No. (Address Change) are indicated on the LCD display.
SWING/FIX
buttons repeatedly to select a system
address.
Cancels the line selection
SMMS-i
Installation Manual
SMMS-i
Installation Manual
3 Push the button.
SET
• The address of one of the indoor units connected to the selected refrigerant line is indicated on the LCD display and the fan and louvers of the unit are activated. At first, the current indoor unit address is displayed in
SET DATA.
(No system address is indicated.)
UNIT No.
R.C. No.
ON / OFF
Press to finish setting.
CODE No.
6
4 8
Finish
DATA
SET
SETTING
TEMP.
FILTER
TEST
RESET
5, 7
TIMER SET
TIME
SET CL
4 Push the TIME / buttons repeatedly to
change the value of the indoor unit address in SET DATA. Change the value in SET DATA to that of a new address.
5 Push the button to confirm the new
SET
address on SET DATA.
6 Push the button (left side of the
button) repeatedly to select another address to change. Each time you push the button, the indoor unit numbers in a refrigerant line are indicated one after another. Only the fan and louvers of the selected indoor unit are activated.
Repeat steps 4 to 6 to change the indoor unit addresses so as to make each of them unique.
7 Push the button.
(All the segments on the LCD display light up.)
8 Push the button to finish the procedure.
SET
TEST
Resetting the address
(Resetting to the factory default (address undecided))
Method 1
Clearing each address separately using a wired remote controller. Set the system address, indoor unit address and group address to “0099” using a wired remote controller. (For the setting procedure, refer to the address setting procedures using the wired remote controller on the previous pages.)
Method 2
Clearing all the indoor unit addresses on a refrigerate line at once from the outdoor unit.
1 Turn off the refrigerant line to reset to the
factory default and set the header outdoor unit of the line as below.
1) Disconnect the relay connectors between the [U1, U2] and [U3, U4] terminals. (Leave them as they are if they have already been disconnected.)
2) Turn on dip switch 2 of SW30 on the interface P.C. board of the header outdoor unit if the switch is OFF. (Leave it as it is if it has already been set to ON.)
Central control controller
U1U3U2
Header unit
U3 U4
U1 U2 U5 U6
U1 U2
A B
Remote controller
Follower unit
U1 U2 U5 U6
U1 U2
A B
Remote controller
Header
U3 U4
unit
U3 U4
U1 U2 U5 U6
U1 U2
A B
Remote controller
Indoor units to have their addresses initialized
Follower unit
U1 U2 U5 U6
U1 U2
A B
U3 U4
Header unit
U1 U2
U1 U2
U3 U4
A B
Remote controller
U4
U5 U6
2 Turn on the indoor and outdoor units of the refrigerant line for which you want to initialize the
addresses. About one minute after turning on the power, confirm that the 7-segment display on the header outdoor unit indicates “U.1. - - -” and operate the interface P.C. board on the header outdoor unit of the refrigerant line as follows.
SW01 SW02 SW03 SW04 Clearable addresses
212
222
Confirm that the 7-segment display indicates “A.d.buS” and turn SW04 ON fo r more than five seconds.
Confirm that the 7-segment display indicates “A.d.nEt” and turn SW04 ON for mo re than five seconds.
System/indoor unit/group address
Central control address
3 Confirm that the 7-segment display indicates “A.d. c.L.” and set SW01, SW02 and SW03 to 1, 1, 1
respectively.
4 After a time “U.1.L08” appears on the 7-segment display if the address clearing has been
completed successfully. If the 7-segment display indicates “A.d. n.G.”, the outdoor unit may still connected with other refrigerant lines. Check the connection of the relay connectors between [U1, U2] and [U3, U4].
NOTE
Take care to carry out the procedure above correctly; otherwise, addresses in other refrigerate lines may also be cleared.
5 Set the addresses again after finishing the clearance.
EN
55-EN 56-EN
–28–
57-EN 58-EN
SMMS-i
Installation Manual
–29–
SMMS-i
Installation Manual

10TEST RUN

Before test run

Confirm that the valve of the refrigerate pipe of the outdoor unit is OPEN.
• Before turning on the power, confirm that the resistance between the terminal block of power supply and the earth is more than 1MΩ using a 500V megohmmeter. Do not run the unit if it is less than 1MΩ.
CAUTION
• Turn on the power and turn on the case heater of the compressor. To save the compressor when it is activated, leave the power on for more than 12 hours.

Methods of test run

When executing a test run using a remote controller
Operate the system normally to check the running condition using the wired remote controller. Follow the instructions in the supplied owner’s manual when operating the unit. If you use a wireless remote controller for operations, follow the instructions in the installation manual supplied with the indoor unit. To execute a test run forcibly under the condition that the thermostat automatically turns the unit off due to the indoor temperature, follow the procedure below. The forcible test run will automatically stop after 60 minutes to prevent continuous forcible running and return to normal running.
CAUTION
Do not use forcible running except for a test run as it overloads the unit.
TEMP.
ON / OFF
2, 4
TIMER SET
FILTER RESET
TEST
TIME
SET CL
3
1, 5
1 Push and hold the button for more than 4
seconds. TEST appears on the LCD display and the unit enters the trial mode. (TEST is indicated on the LCD display during the test run.)

2 Push the button. 3 Push the button to switch the running

mode to COOL or HEAT.
NOTE
• Do not run the unit in any mode other than COOL or HEAT.
• You cannot change the temperature setting during the test run.
• Errors are detected as usual.
4 Push the button to stop running
after finishing the trial run. The indication on the LCD display returns to the status of procedure 1.
5 Push the button to exit the trial mode.
(TEST disappears on the LCD display and the status changes to normal stopped mode.)
TEST
TEST
TEST
ON / OFF
MODE
TEST
ON / OFF
When executing a test run using the interface P.C. board on the outdoor unit
You can execute a test run by operating switches on the interface P.C. board of the header outdoor unit. “Individual trial”, which tests each indoor unit separately, and “corrective trial”, which tests all the indoor units connected, are available.
<Individual test operation>
Starting operation
1 Set the running mode to “COOL” or “HEAT”
on the remote controller of the indoor unit to be tested. (The unit will run in the current mode unless you set the mode otherwise.)
7-segment display
[A]
[U1]
[B]
[ ]
2 Set the rotary switches on the interface P.C.
board of the header outdoor unit: SW01 to [16], SW02 and SW03 to the address of the indoor unit to be tested.
SW02 SW03 Indoor unit address
1 to 16 1 1 to 16 Set number of SW02
1 to 16 2 17 to 32 Set number of SW02 + 16
1 to 16 3 33 to 48 Set number of SW02 + 32
1 to 16 4 49 to 64 Set number of SW02 + 48
7-segment display
[A]
[ ]
Address display of the corresponding indoor unit
[B]
[ ]
3 Push and hold SW04 for more than 10
seconds.
7-segment display
[A]
[ ]
Address display of the corresponding indoor unit

[B]
[ ]
[FF] is displayed for 5 seconds.
NOTE
• The running mode follows the mode setting on the remote controller of the target indoor unit.
• You cannot change the temperature setting during the test run.
• Errors are detected as usual.
• The unit does not perform test run for 3 minutes after turning the power on or stopping running.
Finishing operation
1 Set the rotary switches on the interface P.C.
board of the header unit back: SW01 to [1], SW02 to [1] and SW03 to [1].
7-segment display
[A]
[U1]
[B]
[ ]
SMMS-i
Installation Manual
SMMS-i
Installation Manual
<Corrective trial>
Start operation
1 Set the rotary switches on the interface P.C. board of the header outdoor unit as below.
When in “COOL” mode: SW01=[2], SW02=[5], SW03=[1]. When in “HEAT” mode: SW01=[2], SW02=[6], SW03=[1].
7-segment display
[A] [C ] [H ]
[B] [ ] [ ]

2 Push and hold SW04 for more than 2 seconds.

NOTE
• You cannot change the temperature setting during the test run.
• Errors are detected as usual.
• The unit does not perform test run for 3 minutes after turning the power on or stopping running.
7-segment display
[A] [C ] [H ]
[B] [ - C ] [ - H ]
Stop operation
1 Set the rotary switches on the interface P.C. board of the header unit back:
SW01 to [1], SW02 to [1] and SW03 to [1].
7-segment display
[A]
[U1]
[B]
[ ]
Interface PC board
Push switch
7-segment
display [A]
SW04
SW05 SW15
D600 D601 D602 D603 D604
SW01 SW02
Rotary switches
SW03
Push switch
7-segment display [B]
EN
59-EN 60-EN
–30–
61-EN 62-EN
SMMS-i
Installation Manual
–31–
SMMS-i
Installation Manual

11TROUBLESHOOTING

In addition to the CODE No. on the remote controller of an indoor unit, you can diagnose failure type of an outdoor unit by checking the 7-segment display on the interface P.C. board. Use the function for various checks. Set every dip switch to OFF after checking.
7-Segment display and check code
Rotary switch setting value
SW01 SW02 SW03
1 1 1 Outdoor unit check code
* If a check code has an auxiliary code, the display indicates the check code for three seconds and the auxiliary
code for one second alternately.
Indication LED
A
B Check code display*
Check code (indicated on the 7-segment display on the outdoor unit)
Indicated when SW01 = [1], SW02 = [1], and SW03 = [1].
Check code
Auxiliary code
E06 Number of indoor units which received normally Decrease of number of indoor units
E07 Indoor/outdoor communication circuit error
E08 Duplicated indoor addresses Duplication of indoor addresses.
01: Communication between indoor and outdoor units
E12
02: Communication between outdoor units
E15 No indoor unit during automatic addressing
00: Capacity over
E16
01~: Number of connected units
00: Header is nothing
E19
02: 2 or more header units
01: Other line indoor connected
E20
02: Other line indoor connected
E23 Sending error between outdoor units communication
E25 Duplicated follower outdoor address set up
E26 Number of outdoor units which received normally Decrease of connected outdoor units
E28 Detected outdoor Follower outdoor unit error
E31 IPDU quantity information
F04 TD1 sensor error
F05 TD2 sensor error
01: TE1 sensor
F06
02: TE2 sensor
F07 TL sensor error
F08 TO sensor error
F12 TS1 sensor error
01: Compressor 1
F13
02: Compressor 2 03: Compressor 3
(*1)
Automatic addressing start error
Capacity over / number of connected indoor units
Number of header outdoor unit error
Other lines connected during automatic addressing
IPDU communication error
TE1 sensor error TE2 sensor error
TH (Heat sink) sensor error
D600
AB
Outdoor unit number
Check code nameIndication on 7-segment display on the outdoor unit
D601 D602 D603 D604
(U
1 to U4)
Check code
Check code nameIndication on 7-segment display on the outdoor unit
Auxiliary code
F15
F16
F22 TD3 sensor error
F23 Ps sensor error
F24 Pd sensor error
F31 Outdoor EEPROM error
01: Compressor 1
H01
02: Compressor 2 03: Compressor 3
01: Compressor 1
H02
02: Compressor 2 03: Compressor 3
01: Compressor 1
H03
02: Compressor 2 03: Compressor 3
H05 TD1 sensor miswiring
H06 Low pressure proctive operation
H07 Oil level down detection
01: TK1 sensor error 02: TK2 sensor error
H08
03: TK3 sensor error 04: TK4 sensor error 05: TK5 sensor error
H15 TD2 sensor miswiring
01: TK1 oil circuit error 02: TK2 oil circuit error
H16
03: TK3 oil circuit error 04: TK4 oil circuit error 05: TK5 oil circuit error
H25 TD3 sensor miswiring
L04 Outdoor system address duplication
L06 Number of prior indoor units Duplication of indoor units with priority
L08 Indoor unit group/address unset
L10 Outdoor unit capacity unset.
L17 Mismatch of the outdoor unit model
L28 Outdoor connected quantity over
L29 IPDU number information
L30 Detected indoor unit address External interlock of indoor unit
L31 Other compressor errors
P03 Discharge temperature TD1 error
01: Compressor 1
P04
02: Compressor 2 03: Compressor 3
00: Phase missing/power failure detection
01: Compressor 1
P05
02: Compressor 2 03: Compressor 3
(*1)
Outdoor temp. sensor miswiring Outdoor pressure sensor miswiring (TE1, TL)
Outdoor temp. sensor miswiring Outdoor pressure sensor miswiring (Pd, Ps)
Compressor breaking down
Compressor error (Locked)
Current detection circuit error
Temperature sensor error for oil level
Oil level detector circuit error
IPDU quantity error
High-pressure SW system operation
Inverter DC voltage error (on compressor)
SMMS-i
Installation Manual
SMMS-i
Installation Manual
Check code
Check code nameIndication on 7-segment display on the outdoor unit
Auxiliary code
01: Compressor 1
P07
02: Compressor 2 03: Compressor 3
P10 Detected indoor unit address Indoor overflow error
P13 Outdoor unit flow back error detected
01: TS condition
P15
02: TD condition
P17 Discharge temperature TD2 error
P18 Discharge temperature TD3 error
P19 Detected outdoor unit number 4-way valve inverse error
P20 High-pressure protective operation
0 *: IGBT circuit 1 *: Position detection circuit error 3 *: Motor lock error 4 *: Motor current detected
P22
C *: TH sensor error D *: TH sensor error E *: Inverter DC voltage error
(outdoor unit’s fan)
01: Compressor 1
P26
02: Compressor 2 03: Compressor 3
01: Compressor 1
P29
02: Compressor 2 03: Compressor 3
*1PDU number information
01:Compressor 1 02:Compressor 2 03:Compressors 1 and 2 04:Compressor 3 05:Compressors 1 and 3 06:Compressors 2 and 3 07:Compressors 1, 2 and 3 08:Fan 09:Compressor 1 and fan 0A:Compressor 2 and fan 0B:Compressors 1, 2 and fan 0C:Compressor 3 and fan 0D:Compressors 1, 3 and fan 0E:Compressors 2, 3 and fan 0F:Compressors 1, 2, 3, and fan
Heat sink overheat error
Gas leak detection
Outdoor fan IPDU error
(NOTE)
Ignore 0-F appearing in the position of “*”.
G-TR short protection error
Compressor position detecting circuit error

12MACHINE CARD AND LOGBOOK

Machine card

After test run, fill the items on the machine card and paste the card on an accessible place on the product securely before delivery to the customer.
Describe the following items on the machine card:
name, address and telephone number of the installer, his service department, the service department of the party concerned or at any addresses and telephone numbers of fire department, police, hospitals and burn centres;

Logbook

Update the log periodically after maintenance as defined in EN378-4.
Describe the following items on the logbook:

1. details of the maintenance and repair works;

2. quantities, kind of (new, reused, recycled) refrigerant which have been charged on each occasion, the quantities of refrigerant which have been transferred from the system on each occasion (see also EN378-4);

3. if there is an analysis of a reused refrigerant, the results shall be kept in the logbook;

4. source of the reused refrigerant;

5. changes and replacements of components of the system;

6. result of all periodic routine tests;

7. significant periods of non-use.

EN
63-EN 64-EN
–32–
WARNINGS ON REFRIGERANT LEAKAGE
Check of Concentration Limit
The room in which the air conditioner is to be installed requires a design that in the event of refrigerant gas leaking out, its concentration will not exceed a set limit.
The refrigerant R410A which is used in the air conditioner is safe, without the toxicity or combustibility of ammonia, and is not restricted by laws to be imposed which protect the ozone layer. However, since it contains more than air, it poses the risk of suffocation if its concentration should rise excessively. Suffocation from leakage of R410A is almost non-existent. With the recent increase in the number of high concentration buildings, however, the installation of multi air conditioner systems is on the increase because of the need for effective use of floor space, individual control, energy conservation by curtailing heat and carrying power etc. Most importantly, the multi air conditioner system is able to replenish a large amount of refrigerant compared with conventional individual air conditioners. If a single unit of the multi conditioner system is to be installed in a small room, select a suitable model and installation procedure so that if the refrigerant accidentally leaks out, its concentration does not reach the limit (and in the event of an emergency, measures can be made before injury can occur). In a room where the concentration may exceed the limit, create an opening with adjacent rooms, or install mechanical ventilation combined with a gas leak detection device. The concentration is as given below.
Total amount of refrigerant (kg)
Min. volume of the indoor unit installed room (m
Concentration limit (kg/m
The concentration limit of R410A which is used in multi air conditioners is 0.44kg/m
NOTE 1 :
If there are 2 or more refrigerating systems in a single refrigerating device, the amounts of refrigerant should be as charged in each independent device.
e.g., charged amount (10kg)
Room A Room B Room C Room D Room E Room F
For the amount of charge in this example:
The possible amount of leaked refrigerant gas in rooms A,
EH99871699
B and C is 10kg. The possible amount of leaked refrigerant gas in rooms D, E and F is 15kg.
3
.
3
)
Outdoor unit
e.g., charged amount (15kg)
Indoor unit
Important
NOTE 2 :
The standards for minimum room volume are as follows.
(1) No partition (shaded portion)
(2) When there is an effective opening with the adjacent
room for ventilation of leaking refrigerant gas (opening without a door, or an opening 0.15% or larger than the respective floor spaces at the top or bottom of the door).
Outdoor unit
Refrigerant piping
Indoor unit
(3) If an indoor unit is installed in each partitioned room and
the refrigerant piping is interconnected, the smallest room of course becomes the object. But when a mechanical ventilation is installed interlocked with a gas leakage detector in the smallest room where the density
3
)
limit is exceeded, the volume of the next smallest room becomes the object.
Refrigerant piping
Outdoor unit
Very small room
Small
Medium room
Large room
Range above the density limit of
0.44 kg/m (countermeasures needed)
room
Mechanical ventilation device - Gas leak detector
NOTE 3 :
The minimum indoor floor area compared with the amount of refrigerant is roughly as follows: (When the ceiling is 2.7m high)
40
Range below the
2
35
m
density limit of
3
0.44 kg/m
30
(countermeasures not needed)
25
20
15
10
5
Min. indoor floor area
0
10 20 30
Total amount of refrigerant kg
Indoor unit
3
Loading...