Toshiba MMY-MAP1606FT8P-UK, MMY-MAP0806FT8P-UK, MMY-MAP0806FT8JPUK, MMY-MAP2006FT8P-UK, MMY-MAP1806FT8P-UK Installation Manual

...
AIR CONDITIONER (MULTI TYPE)
AMP Air Conditioning
www.ampair.co.uk | sales@ampair.co.uk
Installation Manual
Outdoor Unit
Model name:
MMY-MAP0806FT8P-UK MMY-MAP1006FT8P-UK MMY-MAP1206FT8P-UK MMY-MAP1406FT8P-UK MMY-MAP1606FT8P-UK MMY-MAP1806FT8P-UK MMY-MAP2006FT8P-UK
MMY-MAP0806FT8JPUK MMY-MAP1006FT8JPUK MMY-MAP1206FT8JPUK MMY-MAP1406FT8JPUK MMY-MAP1606FT8JPUK MMY-MAP1806FT8JPUK MMY-MAP2006FT8JPUK
For commercial use
English
– 1 –
AMP Air Conditioning
www.ampair.co.uk | sales@ampair.co.uk
Original instruction
ADOPTION OF NEW REFRIGERANT
This Air Conditioner uses R410A an environmentally friendly refrigerant.
Contents
1 Precautions for safety ......................................................... 3
2 Accessory parts. .......................................................... .....
3 Installation of new refrigerant air conditioner . ............................ .....
4 Selection of installation place. ..................................................
5 Carrying in the outdoor unit . .................................................
6 Installation of the outdoor unit. ...............................................
7 Refrigerant piping
. ..........................................................
8 Electric wiring. ................................................................
9 Address setting . .............................................................
10 How to set up the cooling only indoor unit . ...................................
11 Test run 12 Troubleshooting
. ............................ .................... ............ .........
................ .............................................
.
13 Machine card and logbook. ...................................................
..
11 12 14
24 28
37
38
40
41
Thank you for purchasing this Toshiba air conditioner. This Installation Manual describes the installation method of the outdoor unit. For installation of indoor units, follow the Installation Manual supplied with the indoor unit. Moreover, as this installation manual includes the important articles concerning the “Machinery Directive” (Directive 2006/42/EC), please read through the manual and make sure you understand it. After installation, give this Installation Manual with the Owner’s Manual, the Owner’s Manual and the Installation Manual supplied with the indoor unit to the customer and tell the customer to keep them safe. Prepare an exclusive power source for indoor units, independent to that for outdoor units. Y-shaped branching joints or a branching header (separately purchased) are required for connecting pipes between indoor and outdoor units. Choose either of them considering the system capacity concerning piping. For installing branching pipes, refer to the installation manual of the Y-shaped branching unit or branching header (separately purchased). Outdoor connecting branching joints are required for connecting between outdoor units.
Generic Denomination: Air Conditioner
8 9 9
Denition of Qualied Installer or Qualied Service Person
The air conditioner must be installed, maintained, repaired and removed by a qualied installer or qualied service person. When any of these jobs is to be done, ask a qualied installer or qualied service person to do them for you. A qualied installer or qualied service person is an agent who has the qualications and knowledge described in the table below.
Agent Qualications and knowledge which the agent must have
• The qualied installer is a person who installs, maintains, relocates and removes the air conditioners made by Toshiba Carrier Corporation. He or she has been trained to install, maintain, relocate and remove the air conditioners made by Toshiba Carrier Corporation or, alternatively, he or she has been instructed in such operations by an individual or individuals who have been trained and is thus thoroughly acquainted with the knowledge related to these operations.
• The qualified installer who is allowed to do the electrical work involved in installation, relocation and removal has the qualications pertaining to this electrical work as stipulated by the local laws and regulations, and he or she is a person who has been trained in matters relating to electrical work on the air conditioners made by Toshiba Carrier Corporation or, alternatively, he or she has been instructed in such matters by an individual or individuals who have
Qualied installer
Qualied service person
been trained and is thus thoroughly acquainted with the knowledge related to this work.
• The qualified installer who is allowed to do the refrigerant handling and piping work involved in installation, relocation and removal has the qualications pertaining to this refrigerant handling and piping work as stipulated by the local laws and regulations, and he or she is a person who has been trained in matters relating to refrigerant handling and piping work on the air conditioners made by Toshiba Carrier Corporation or, alternatively, he or she has been instructed in such matters by an individual or individuals who have been trained and is thus thoroughly acquainted with the knowledge related to this work.
• The qualified installer who is allowed to work at heights has been trained in matters relating to working at heights with the air conditioners made by Toshiba Carrier Corporation or, alternatively, he or she has been instructed in such matters by an individual or individuals who have been trained and is thus thoroughly acquainted with the knowledge related to this work.
• The qualified service person is a person who installs, repairs, maintains, relocates and removes the air conditioners made by Toshiba Carrier Corporation. He or she has been trained to install, repair, maintain, relocate and remove the air conditioners made by Toshiba Carrier Corporation or, alternatively, he or she has been instructed in such operations by an individual or individuals who have been trained and is thus thoroughly acquainted with the knowledge related to these operations.
• The qualified service person who is allowed to do the electrical work involved in installation, repair, relocation and removal has the qualications pertaining to this electrical work as stipulated by the local laws and regulations, and he or she is a person who has been trained in matters relating to electrical work on the air conditioners made by Toshiba Carrier Corporation or, alternatively, he or she has been instructed in such matters by an individual or individuals who have been trained and is thus thoroughly acquainted with the knowledge related to this work.
• The qualified service person who is allowed to do the refrigerant handling and piping work involved in installation, repair, relocation and removal has the qualications pertaining to this refrigerant handling and piping work as stipulated by the local laws and regulations, and he or she is a person who has been trained in matters relating to refrigerant handling and piping work on the air conditioners made by Toshiba Carrier Corporation or, alternatively, he or she has been instructed in such matters by an individual or individuals who have been trained and is thus thoroughly acquainted with the knowledge related to this work.
• The qualified service person who is allowed to work at heights has been trained in matters relating to working at heights with the air conditioners made by Toshiba Carrier Corporation or, alternatively, he or she has been instructed in such matters by an individual or individuals who have been trained and is thus thoroughly acquainted with the knowledge related to this work.
2-EN1-EN
Denition of Protective Gear
AMP Air Conditioning
www.ampair.co.uk | sales@ampair.co.uk
When the air conditioner is to be transported, installed, maintained, repaired or removed, wear protective gloves and ‘safety’ work clothing. In addition to such normal protective gear, wear the protective gear described below when undertaking the special work detailed in the table below. Failure to wear the proper protective gear is dangerous because you will be more susceptible to injury, burns, electric shocks and other injuries.
Work undertaken Protective gear to wear
All types of work
Electrical-related work
Work at heights (50 cm or more)
Transportation of heavy objects
Repair of outdoor unit Gloves to provide protection for electricians and from heat
Protective gloves ‘Safety’ working clothing
Gloves to provide protection for electricians and from heat Insulating shoes Clothing to provide protection from electric shock
Helmets for use in industry
Shoes with additional protective toe cap
Warning indications on the air conditioner unit
Warning indication Description
WARNING
ELECTRICAL SHOCK HAZARD
Disconnect all remote electric power supplies before servicing.
WARNING
Moving parts. Do not operate unit with grille removed. Stop the unit before the servicing.
CAUTION
High temperature parts. You might get burned when removing this panel.
WARNING
ELECTRICAL SHOCK HAZARD
Disconnect all remote electric power supplies before servicing.
WARNING
Moving parts. Do not operate unit with grille removed. Stop the unit before the servicing.
CAUTION
High temperature parts. You might get burned when removing this panel.
CAUTION
Do not touch the aluminum fins of the unit. Doing so may result in injury.
CAUTION
BURST HAZARD
Open the service valves before the operation, otherwise there might be the burst.
CAUTION
Do not climb onto the fan guard.
Doing so may result in injury.
CAUTION
Do not touch the aluminium ns of the unit. Doing so may result in injury.
CAUTION
BURST HAZARD
Open the service valves before the operation, otherwise there might be the burst.
CAUTION
Do not climb onto the fan guard.
Doing so may result in injury.
– 2 –
4-EN3-EN
– 3 –
AMP Air Conditioning
www.ampair.co.uk | sales@ampair.co.uk
1 Precautions for safety
The manufacturer shall not assume any liability for the damage caused by not observing the description of this manual.
WARNING
General
• Before starting to install the air conditioner, read through the Installation Manual carefully, and follow its instructions to install the air conditioner. Otherwise, falling down of the unit may occur, or the unit may cause noise, vibration or water leakage.
• Only a qualied installer(*1) or qualied service person(*1) is allowed to do installation work. If installation is carried out by an unqualied individual, a re, electric shocks, injury, water leakage, noise and/or vibration may result.
• If using separately sold products, make sure to use Toshiba specied products only. Using unspecied products may cause re, electric shock, water leak or other failure.
• Do not use any refrigerant different from the one specied for complement or replacement.
Otherwise, abnormally high pressure may be generated in the
refrigeration cycle, which may result in a failure or explosion of the product or an injury to your body.
• Before opening the service panel of the outdoor unit, set the circuit breaker to the OFF position. Failure to set the circuit breaker to the OFF position may result in electric shocks through contact with the interior parts. Only a qualied installer(*1) or qualied service person(*1) is allowed to remove the service panel of the outdoor unit and do the work required.
• Before carrying out the installation, maintenance, repair or removal work, be sure to set the circuit breakers for both the indoor and outdoor units to the OFF position. Otherwise, electric shock may result.
• Place a “Work in progress” sign near the circuit breaker while the installation, maintenance, repair or removal work is being carried out. There is a danger of electric shocks if the circuit breaker is set to ON by mistake.
• Only a qualied installer(*1) or qualied service person(*1) is allowed to undertake work at heights using a stand of 50 cm or more or to remove the intake grille of the indoor unit to undertake work.
• Wear protective gloves and safety work clothing during installation, servicing and removal.
• Do not touch the aluminium n of the outdoor unit. You may injure yourself if you do so. If the n must be touched for some reason, rst put on protective gloves and safety work clothing, and then proceed.
• Do not climb onto or place objects on top of the outdoor unit. You may fall or the objects may fall off of the outdoor unit and result in injury.
• When working at height, put a sign in place so that no-one will approach the work location before proceeding with the work. Parts or other objects may fall from above, possibly injuring a person below. Also, be sure that workers put on helmets.
• When cleaning the lter or other parts of the outdoor unit, set the circuit breaker to OFF without fail, and place a “Work in progress” sign near the circuit breaker before proceeding with the work.
• The refrigerant used by this air conditioner is the R410A.
• You shall ensure that the air conditioner is transported in stable condition. If you nd any part of the product broken, contact your dealer.
• Do not disassemble, modify or move the product yourself. Doing so may cause re, electric shock, injury or water leaks.
6-EN5-EN
• This appliance is intended to be used by expert or trained users
AMP Air Conditioning
www.ampair.co.uk | sales@ampair.co.uk
in shops, in light industry, or for commercial use by lay persons.
• We do not take any responsibility on the local design.
Selection of installation location
• If you install the unit in a small room, take appropriate measures to prevent the refrigerant from exceeding the limit concentration even if it leaks. Consult the dealer from whom you purchased the air conditioner when you implement the measures. Accumulation of highly concentrated refrigerant may cause an oxygen deciency accident.
• Do not install in a location where ammable gas may leaks are possible. If the gas should leak and accumulate around the unit, it may ignite and cause a re.
• When transporting the air conditioner, wear shoes with protective toe caps, protective gloves and other protective clothing.
• When transporting the air conditioner, do not take hold of the bands around the packing carton. You may injure yourself if the bands should break.
• Other than floor standing and console types, install the indoor unit at least 2.5 m above the oor level since otherwise the users may injure themselves or receive electric shocks if they poke their ngers or other objects into the indoor unit while the air conditioner is running.
• Do not place any combustion appliance in a place where it is directly exposed to the wind of air conditioner, otherwise it may cause imperfect combustion.
• Do not install outdoor units where the operation sound may cause a disturbance. (Especially at the boundary line with a neighbour, install the air conditioner while considering the noise.)
Installation
• Follow the instructions in the Installation Manual to install the air conditioner. Failure to follow these instructions may cause the product to fall down or topple over or give rise to noise, vibration, water leakage or other failure.
• The designated bolts (M12) and nuts (M12) for securing the outdoor unit must be used when installing the unit.
• Install the outdoor unit property in a location that is durable enough to support the weight of the outdoor unit. Insufcient durability may cause the outdoor unit to fall, which may result in injury.
• Install the unit in the prescribed manner for protection against strong wind and earthquake. Incorrect installation may result in the unit falling down, or other accidents.
• Be sure to x the screws back which have been removed for installation or other purposes.
Refrigerant piping
• Install the refrigerant pipe securely during the installation work before operating the air conditioner. If the compressor is operated with the valve open and without refrigerant pipe, the compressor sucks air and the refrigeration cycles is over pressurized, which may cause a injury.
• Tighten the flare nut with a torque wrench in the specified manner. Excessive tighten of the are nut may cause a crack in the are nut after a long period, which may result in refrigerant leakage.
• Ventilate the air if the refrigerant gas leaks during installation. If the leaked refrigerant gas comes into contact with re, toxic gas may be produced.
– 4 –
8-EN7-EN
– 5 –
AMP Air Conditioning
www.ampair.co.uk | sales@ampair.co.uk
• After the installation work, conrm that refrigerant gas does not leak. If refrigerant gas leaks into the room and ows near a re source, such as a cooking range, noxious gas may be generated.
• When the air conditioner has been installed or relocated, follow the instructions in the Installation Manual and purge the air completely so that no gases other than the refrigerant will be mixed in the refrigerating cycle. Failure to purge the air completely may cause the air conditioner to malfunction.
• Nitrogen gas must be used for the airtight test.
• The charge hose must be connected in such a way that it is not slack.
• If refrigerant gas has leaked during the installation work, ventilate the room immediately. If the leaked refrigerant gas comes in contact with re, noxious gas may be generated.
Electrical wiring
• Only a qualied installer(*1) or qualied service person(*1) is allowed to carry out the electrical work of the air conditioner.
Under no circumstances must this work be done by an
unqualied individual since failure to carry out the work properly may result in electric shocks and/or electrical leaks.
• When connecting the electrical wires, repairing the electrical parts or undertaking other electrical jobs, wear gloves to provide protection for electricians and from heat, insulating shoes and clothing to provide protection from electric shocks. Failure to wear this protective gear may result in electric shocks.
• When executing address setting, test run, or troubleshooting through the checking window on the electrical control box, put on insulated heat-proof gloves, insulated shoes and other clothing to provide protection from electric shock. Otherwise you may receive an electric shock.
• Use wiring that meets the specications in the Installation Manual and the stipulations in the local regulations and laws. Use of wiring which does not meet the specications may give rise to electric shocks, electrical leakage, smoking and/or a re.
• Check that the product is properly earthed. (grounding work)
Incomplete earthing may cause electric shock.
• Do not connect the earth line to a gas pipe, water pipe, lightning conductor, or a telephone earth line.
• After completing the repair or relocation work, check that the ground wires are connected properly.
• Install a circuit breaker that meets the specications in the installation manual and the stipulations in the local regulations and laws.
• Install the circuit breaker where it can be easily accessed by the agent.
• When installing the circuit breaker outdoors, install one which is designed to be used outdoors.
• Under no circumstances must the power cable be extended. Connection trouble in the places where the cable is extended may give rise to smoking and/or a re.
• Electrical wiring work shall be conducted according to law and regulation in the community and installation manual.
Failure to do so may result in electrocution or short circuit.
• Do not supply power from the power terminal block equipped on the outdoor unit to another outdoor unit. Capacity overow may occur on the terminal block and may result in re.
• When carrying out electric connection, use the wire specied in the Installation Manual and connect and x the wires securely to prevent them applying external force to the terminals. Improper connection or xing may result in re.
10-EN9-EN
Test run
AMP Air Conditioning
www.ampair.co.uk | sales@ampair.co.uk
• Before operating the air conditioner after having completed the work, check that the electrical parts box cover of the indoor unit and service panel of the outdoor unit are closed, and set the circuit breaker to the ON position. You may receive an electric shock if the power is turned on without rst conducting these checks.
• When you have noticed that some kind of trouble (such as when an error display has appeared, there is a smell of burning, abnormal sounds are heard, the air conditioner fails to cool or heat or water is leaking) has occurred in the air conditioner, do not touch the air conditioner yourself but set the circuit breaker to the OFF position, and contact a qualied service person. Take steps to ensure that the power will not be turned on (by marking “out of service” near the circuit breaker, for instance) until qualied service person arrives. Continuing to use the air conditioner in the trouble status may cause mechanical problems to escalate or result in electric shocks or other failure.
• After the work has nished, be sure to use an insulation tester set (500V Megger) to check the resistance is 1 MΩ or more between the charge section and the non-charge metal section (Earth section). If the resistance value is low, a disaster such as a leak or electric shock is caused at user’s side.
• Upon completion of the installation work, check for refrigerant leaks and check the insulation resistance and water drainage.
Then conduct a test run to check that the air conditioner is
operating properly.
• If you have discovered that the fan grille is damaged, do not approach the outdoor unit but set the circuit breaker to the OFF position, and contact a qualied service person(*1) to have the repairs done. Do not set the circuit breaker to the ON position until the repairs are completed.
• After the installation work, follow the Owner’s Manual to explain to the customer how to use and maintain the unit.
Relocation
• Only a qualied installer(*1) or qualied service person(*1) is allowed to relocate the air conditioner. It is dangerous for the air conditioner to be relocated by an unqualied individual since a re, electric shocks, injury, water leakage, noise and/or vibration may result.
• When carrying out the pump-down work shut down the compressor before disconnecting the refrigerant pipe. Disconnecting the refrigerant pipe with the service valve left open and the compressor still operating will cause air or other gas to be sucked in, raising the pressure inside the refrigeration cycle to an abnormally high level, and possibly resulting in rupture, injury or other trouble.
• Never recover the refrigerant into the outdoor unit. Be sure to use a refrigerant recovery machine to recover the refrigerant when moving or repairing. It is impossible to recover the refrigerant into the outdoor unit. Refrigerant recovery into the outdoor unit may result in serious accidents such as explosion of the unit, injury or other accidents.
Explanations given to user
• Upon completion of the installation work, tell the user where the circuit breaker is located. If the user does not know where the circuit breaker is, he or she will not be able to turn it off in the event that trouble has occurred in the air conditioner.
– 6 –
(*1) Refer to the “Denition of Qualied Installer or Qualied Service Person.”
12-EN11-EN
CAUTION
AMP Air Conditioning
www.ampair.co.uk | sales@ampair.co.uk
New refrigerant air conditioner installation
This air conditioner adopts the new HFC refrigerant (R410A) which does not destroy ozone layer.
• The characteristics of R410A refrigerant are; easy to absorb water, oxidizing membrane or oil, and its pressure is approx. 1.6 times higher than that of refrigerant R22. Accompanied with the new refrigerant, refrigerating oil has also been changed.
Therefore, during installation work, be sure that water, dust,
former refrigerant, or refrigerating oil does not enter the refrigerating cycle.
• To prevent charging an incorrect refrigerant and refrigerating oil, the sizes of connecting sections of charging port of the main unit and installation tools are changed from those for the conventional refrigerant.
• Accordingly the exclusive tools are required for the new refrigerant (R410A).
• For connecting pipes, use new and clean piping designed for R410A, and please care so that water or dust does not enter.
– 7 –
To Disconnect the Appliance from Main Power Supply.
• This appliance must be connected to the main power supply by means of a switch with a contact separation of at least 3 mm.
The installation fuse (all type can be used) must be used for the power supply line of this conditioner.
Do not wash air conditioners with pressure washers.
• Electric leaks may cause electric shocks or res.
13-EN 14-EN
2 Accessory parts
AMP Air Conditioning
www.ampair.co.uk | sales@ampair.co.uk
Q’ty
Part name
Owner’s Manual 1111
Installation Manual 1111 – This manual for installer.
F-GAS label 1111
Attached clamp lter –––1
Attached binding band –––1 Attached pipe
(Ø22.2 both forward and downward)
Attached pipe (Ø28.6 both forward and downward)
Attached pipe (Ø19.1 both forward and downward)
Attached pipe (Ø19.1 both forward and downward)
Attached pipe (Ø22.2 both forward and downward)
MAP080 MAP100
MAP120 MAP140
1–––
–111
1–––
–1––
––11
MAP160 MAP180 MAP200
Shape Usage
(Be sure to hand it to the customers.)
Fill the items on the label after adding refrigerant.
For earth line.
Suction-side gas pipe Ø25.4Ø22.2 pipe tting
Suction-side gas pipe Ø25.4Ø28.6 pipe tting
Discharge-side gas pipe Ø15.9Ø19.1 pipe tting * Flare the connector on the
outdoor unit for installation.
Discharge-side gas pipe * Flare the connector on the
outdoor unit for installation.
Discharge-side gas pipe Ø19.1Ø22.2 pipe tting * Flare the connector on the
outdoor unit for installation.
Part name
Attached pipe (Ø12.7 for draw-out forward)
Attached pipe (Ø12.7 for draw-out downward)
Attached pipe (Ø15.9 for draw-out forward)
Attached pipe (Ø15.9 for draw-out downward)
Attached pipe (Ø19.1 for draw-out forward)
Attached pipe (Ø19.1 for draw-out downward)
Q’ty
MAP080 MAP100
MAP120 MAP140
–1––
–1––
––1–
––1–
–––1
–––1
MAP160 MAP180 MAP200
Shape Usage
Liquid pipe Ø15.9Ø12.7 pipe tting * Flare the connector on the
outdoor unit for installation.
Liquid pipe * Flare the connector on the
outdoor unit for installation.
Liquid pipe Ø15.9Ø19.1 pipe tting * Flare the connector on the
outdoor unit for installation.
Attached pipe (Ø12.7 for draw-out forward)
Attached pipe (Ø12.7 for draw-out downward)
1 5 -EN 16 -EN
1–––
1–––
Liquid pipe * Flare the connector on the
outdoor unit for installation.
– 8 –
– 9 –
AMP Air Conditioning
www.ampair.co.uk | sales@ampair.co.uk
3 Installation of new refrigerant air conditioner
This air conditioner adopts the new HFC refrigerant (R410A) which does not deplete the ozone layer.
• R410A refrigerant is vulnerable to impurities such as water, oxidizing membranes, or oils because the pressure
of R410A refrigerant is higher than that of the former refrigerant by approximately 1.6 times.
As well as the adoption of the new refrigerant, the refrigerating oil has been also changed. Therefore, pay
attention so that water, dust, former refrigerant, or refrigerating oil does not enter the refrigerating cycle of the new refrigerant air conditioner during installation.
• To prevent mixing of refrigerant or refrigerating oil, the size of the charge port of the main unit or connecting
section of the installation tool differs to that of an air conditioner for the former refrigerant.
Accordingly, exclusive tools are required for the new refrigerant (R410A) as shown below.
• For connecting pipes, use new and clean piping materials so that water or dust does not enter.
Required tools and cautions on handling
It is necessary to prepare the tools and parts for installation as described below. The tools and parts which will be newly prepared in the following items should be restricted to exclusive use.
Explanation of symbols
: Newly prepared (It is necessary to use it exclusively with R410A, separately from those for R22 or R407C.)
: Former tool is available.
Used tools Usage Proper use of tools/parts
Gauge manifold Charging hose
Charging cylinder Charging refrigerant Unusable (Use the Refrigerant charging balance.) Gas leak detector Checking gas leak
Vacuum pump Vacuum drying Vacuum pump with counterow Vacuum drying
Flare tool Flare processing of pipes Usable by adjusting size Bender Bending processing of pipes Refrigerant recovery device Recovering refrigerant Torque wrench Tightening are nut Pipe cutter Cutting pipes
Refrigerant canister Charging refrigerant Brazing machine/Nitrogen gas
cylinder Refrigerant charging balance Charging refrigerant
Vacuuming, charging refrigerant and operation check
Brazing of pipes
Exclusive to R410A Exclusive to R410A
Exclusive to R410A
Usable if a counter-ow preventive adapter is attached
R22 (Existing article)
R22 (Existing article) Exclusive to R410A Exclusive to Ø12.7mm and Ø15.9mm R22 (Existing article)
Exclusive to R410A Enter the refrigerate name for identication
R22 (Existing article) R22 (Existing article)
4 Selection of installation place
Upon customer’s approval, install the air conditioner in a place which satises the following conditions:
• Place where it can be installed horizontally.
• Place which can reserve a sufcient service space for safe maintenance or checks.
• Place where there is no problem even if the drained water overows.
Avoid the following places:
• Salty places (seaside area) or places with much gas sulde (hot spring area) (If selecting such a place, special maintenance is required.)
• Places where oil (including machine oil), steam, oil smoke or corrosive gas is generated.
• Places where iron or other metal dust is present. If iron or other metal dust adheres to or collects on the interior of the air conditioner, it may spontaneously combust and start a re.
• Places where an organic solvent is used.
• Chemical plants with a cooling system using liquid carbon dioxide.
• Places where a device generating high frequency (inverter, non-utility generator, medical apparatus, or communication equipment) is set. (Malfunction or abnormal control of the air conditioner, or interference to devices listed above may occur.)
• Places where discharged air from the outdoor unit blows against the windows of a neighbour’s house.
• Places unable to bear the weight of the unit.
• Places with poor ventilation.
• The cooling performance may decline considerably when total operating capacity of cooling indoor units is less than 4HP while ambient temperature is below 0°C.
1 7 -EN
18-EN
Installation space
AMP Air Conditioning
www.ampair.co.uk | sales@ampair.co.uk
Leave space necessary for running, installation and servicing.
Air discharge
Air intake
Air intake
Air intake
500mm or more
(Rear side)
10mm or more
500mm or more
(Front side)
Installation/servicing
surface
Square hole for handling
Outdoor unit top view
20mm or more20mm or more
NOTE
• If there is an obstacle above the outdoor unit, leave a space of 2000mm or more to the top end of the outdoor unit.
• If there is a wall around the outdoor unit, make sure that its height does not exceed 800mm.
Air intake
10mm or more
q Combination of outdoor units (* : FT8P-UK , FT8JPUK )
Model name Unit 1 Unit 2 Unit 3
MMY-MAP0806* MMY-MAP0806* - ­MMY-MAP1006* MMY-MAP1006* - ­MMY-MAP1206* MMY-MAP1206* - ­MMY-MAP1406* MMY-MAP1406* - ­MMY-MAP1606* MMY-MAP1606* - ­MMY-MAP1806* MMY-MAP1806* - ­MMY-MAP2006* MMY-MAP2006* - ­MMY-AP2216* MMY-MAP1206* MMY-MAP1006* ­MMY-AP2416* MMY-MAP1406* MMY-MAP1006* ­MMY-AP2616* MMY-MAP1406* MMY-MAP1206* ­MMY-AP2816* MMY-MAP1406* MMY-MAP1406* ­MMY-AP3016* MMY-MAP1606* MMY-MAP1406* ­MMY-AP3216* MMY-MAP1806* MMY-MAP1406* ­MMY-AP3416* MMY-MAP1806* MMY-MAP1606* ­MMY-AP3616* MMY-MAP1806* MMY-MAP1806* ­MMY-AP3816* MMY-MAP2006* MMY-MAP1806* ­MMY-AP4016* MMY-MAP2006* MMY-MAP2006* ­MMY-AP4216* MMY-MAP1406* MMY-MAP1406* MMY-MAP1406*
– 0 1 –
20-EN19-EN
– 1 1 –
AMP Air Conditioning
www.ampair.co.uk | sales@ampair.co.uk
5 Carrying in the outdoor unit
CAUTION
Handle the outdoor unit carefully, observing the following items.
When using a forklift or other machinery for loading/unloading in transportation, insert the fork of the forklift into
the rectangular holes for handling as shown below.
When lifting up the unit, insert a rope able to bear the unit’s weight into the rectangular holes for handling, and
tie the unit from 4 sides.
(Apply padding in positions where the rope comes into contact with the outdoor unit so that no damage is
caused to the outer surface of the outdoor unit.)
(There are reinforcing plates on the side surfaces, so the rope cannot be passed through.)
INCORRECT INCORRECTCORRECT
Plaster board
Rope
Rectangular
holes for handling
Front/Back
CORRECT
Fork of the forklift
Side
INCORRECT
Plaster board
Rectangular holes for lifting
Reinforcing plate
Weight centre and weight
¿ Weight centre of an outdoor unit
Anchor bolt positionA. B. C.Anchor bolt position Anchor bolt position
700
755
Y
Anchor bolt position
X
Z
No. Model type X (mm) Y (mm) Z (mm) Weight (kg)
MMY-MAP080*
A
MMY-MAP100* MMY-MAP120*
B
MMY-MAP140* MMY-MAP160*
C
MMY-MAP200*
755
Anchor bolt position
500 385 635 263
605 370 630 316
780 365 650 377MMY-MAP180*
920
755
Y
Anchor bolt position
Z
1310
Y
XX
Z
(Unit : mm)
22-EN21-EN
6 Installation of the outdoor unit
AMP Air Conditioning
www.ampair.co.uk | sales@ampair.co.uk
WARNING
Be sure to install the outdoor unit in a place able to bear its weight. If strength is insufcient, the unit may fall down resulting in human injury.
Perform specied installation work to protect against strong wind and earthquakes. If the outdoor unit is imperfectly installed, an accident by falling or dropping may be caused.
CAUTION
• Drain water is discharged from the outdoor unit. (Especially while heating) Install the outdoor unit in a place with good drainage.
• For installation, be careful of the strength and level of the foundation so that abnormal sounds (vibration or
noise) are not generated.
REQUIREMENT
Installation in a snowfall area
1. Install the outdoor unit on a higher foundation than the snowfall or set up a stand to install the unit so that
snowfall will not affect the unit.
• Set up a stand higher than the snowfall.
• Apply an angled structure to the stand so that drainage will not be prevented. (Avoid using a stand with a at
surface.)
2. Mount a snowfall-hood onto the air intake and the air discharge.
• Leave enough space for the snowfall-hood so that it will not be an obstacle for the air intake and the air
discharge.
Snowfall-hood for air discharge (locally procured)
Snowfall-hood for air intake (4 faces) (locally procured)
• Anchor bolt positions are as shown below:
Continuous hole (15 x 20 long hole)
Model type A B C
MAP080*, MAP100* 700 990 – MAP120*, MAP140* 920 1210 – MAP160*, MAP180*, MAP200* 1310 1600 1500
310 or more
A A A
2. When drawing out the refrigerant pipe from the underside, set the height of the stand to 500mm or more.
500mm or more
310 or more
755
790
B
C* A
B
*Only MAP160, MAP180, MAP200 type has holes for additional strength.
3. Do not use 4 stands on the corner to support the outdoor unit.
Incorrect Correct
(Unit : mm)
4. Mount the vibration-proof rubber (including vibration-proof blocks) so that it ts under the whole clamping leg.
Correct Correct
1. To install multiple outdoor units, arrange them with 20mm or more spaces in between. Fix each outdoor unit with M12 anchor bolts at 4 positions. 20mm projection is appropriate for an anchor bolt.
20
20mm or more 20mm or more
M12 anchor bolt 4 positions/unit
Stand (locally procured)
Vibration-proof rubber
2 1 –
Anchor bolt
Install the vibration-proof rubber so that the bent part of the xing leg is grounded.
The bent part of the xing leg is not grounded.
IncorrectIncorrect Incorrect
24-EN23-EN
– 13 –
AMP Air Conditioning
www.ampair.co.uk | sales@ampair.co.uk
5. Be careful of the connecting arrangement of the header unit and follower units. Set the outdoor units in order of capacity from the one with the largest capacity. (A (Header unit) B C)
• Be sure to use a header unit for the leading outdoor unit to be connected to the main pipe. (Figure 1, 3 and 6)
• Be sure to use a T-shaped branch joint (RBM-BT14FE/RBM-BT24FE: separately purchased) to connect each
outdoor unit.
• Be careful of the direction of the Outdoor unit connection piping kit for the liquid side. (As shown in Figure 2, a
Outdoor unit connection piping kit cannot be attached so that the refrigerant of the main pipe ows directly into the header unit.)
• When attaching a Y-shaped branch unit for the outdoor unit connection piping kit, attach it level with the
ground (Be sure not to exceed ±15 degrees.). Regarding a T-shape branch joints for the liquid side, there is no restriction for its angle.
At a level position
(Horizontal line) (Horizontal line)
A
(A arrow view) (B arrow view)
B
Within ±15 degrees
Within ±15 degrees
Do not connect a branch unit vertically.
• In case of using the Y-shaped branching joint for connecting between
outdoor units (Discharge gas joint and Suction gas joint), please keep the straight part of at least 500mm at the inlet.
500 mm
or more
Discharge side gas piping / Liquid piping
q Figure 1 q Figure 2
Correct Incorrect
Header unit A
Follower unit B
Follower unit C
Header unit A
Follower unit B
Follower unit C
<Upright connection of suction gas joint>
q Figure 5
Incorrect
Header unit A Follower unit B
Main pipe To indoor unit
Suction gas joint
Suction gas joint
A
Vertical line
A view
Unit
<When drawing pipes downward>
[Vertical connection of branch units]
q Figure 6 q Figure 7
Correct Incorrect
Header unitAFollower unitBFollower unit
C
Main pipe
To indoor unit
Liquid joint
Discharge gas joint
Suction side gas piping
q Figure 3 q Figure 4
Correct Incorrect
Header unit A
Main pipe To the indoor unit
Follower unit B
Suction gas joint
Follower unit C
Liquid joint
To indoor unit
Main pipe
Discharge gas joint
[Inverse connection of suction gas joint]
Header unit A
Main pipe To the indoor unit
Follower unit B
Suction gas joint
Follower unit C
Main pipe
L-shaped
pipe
To the indoor unit
Suction gas joint
Suction gas joint
Suction gas joint
26-EN25-EN
7 Refrigerant piping
AMP Air Conditioning
www.ampair.co.uk | sales@ampair.co.uk
WARNING
If the refrigerant gas leaks during installation, ventilate the room. If the leaked refrigerant gas comes into contact with re, noxious gas may be generated.
After installation, check that the refrigerant gas does not leak. If the refrigerant gas leaks into the room and comes into contact with re such as a fan heater, stove, or
kitchen range, noxious gas may be generated.
Connection of refrigerant pipe
• The refrigerant pipe connecting section is set in the
outdoor unit. Remove the front panel and the piping/ wiring panel.
• As shown in the illustration on the right, the hooks are
at the right and left sides of the front panel. Lift up and remove the front panel.
• Pipes can be drawn out forward or downward from the
outdoor unit.
• When drawing out the pipe forward, draw it out to the
outside via the piping/wiring panel, and leave a space of 500mm or more from the main pipe connecting the outdoor unit with the indoor unit, considering service work or other work on the unit. (For replacing the compressor, 500mm or more space is required.)
• When drawing out the pipe downward, remove the
knockouts on the base plate of the outdoor unit, draw the pipes out of the outdoor unit, and perform piping on the right/left or rear side. Downward length of the balance pipe should be 5m or less.
(Left
500mm or
more
Drawing out forward
(Left piping)
Packed valve of liquid side Ball valve of suction gas side
Packed valve of balance pipe
Ball valve of discharge gas side
piping)
(Right piping)
Drawing out downward
(Rear piping)
Hook
Front panel
Piping/wiring panel
(Right piping)
REQUIREMENT
• For Brazing work of the refrigerant pipes, be sure to use nitrogen gas in order to prevent oxidation of the inside of the pipes; otherwise clogging of the refrigerating cycle due to oxidized scale may occur.
• Use clean and new pipes for the refrigerant pipes and perform piping work so that water or dust does not contaminate the refrigerant.
• Be sure to use two spanners to loosen or tighten the are nut. If a single spanner is used, the required level of tightening cannot be obtained. Tighten the are nut with the specied torque. (If it is hard to loosen or tighten the are nut of the balance pipe or packed valve of the liquid side with two spanners, loosen or tighten the are nut while holding the valve mounting plate with a spanner.)
Outer dia. of
copper pipe
6.4 mm 14 to 18 (1.4 to 1.8 kgf•m)
9.5 mm 33 to 42 (3.3 to 4.2 kgf•m)
12.7 mm 50 to 62 (5.0 to 6.2 kgf•m)
15.9 mm 68 to 82 (6.8 to 8.2 kgf•m)
19.1 mm 100 to 120 (10 to 12 kgf•m)
Tightening torque (N•m)
Do not apply refrigerating oil to the surface of the are.
Ball valve of discharge gas side
Do not clamp the service port with two spanners, doing so may damage the service port.
Pipe connection method (Example)
Draw-out forward Draw-out downward
Suction-side gas pipe
Discharge-side gas pipe
Liquid pipe
Liquid pipe
Attachment
Attachment
Elbow
Socket
Cut the L-shaped pipe, then braze the socket procured locally.
Braze the supplied attachment pipe and elbow procured locally.
Braze the supplied attachment pipe and socket procured locally.
Pipe
Suction-side gas pipe
Balance pipe
L-shaped
pipe Pipe Socket
Pipe
Discharge-side gas pipe
pipe
pipe
Pipe
Suction-side
gas pipe
Section to be cut
Suction-side gas pipe
Discharge-side gas pipe
Liquid pipe
Discharge-side gas pipe
Liquid pipe
Attachment
pipe
Attachment
pipe
Socket
Cut the L-shaped pipe, then braze the socket procured locally.
Braze the supplied attachment pipe and socket procured locally.
Braze the supplied attachment pipe and socket procured locally.
Pipe
Pipe
Suction-side gas pipe
L-shaped pipe
Socket Pipe Socket
Balance pipe
Pipe
Suction-side
Section to be cut
gas pipe
– 4 1 –
28-EN27-EN
– 1 5 –
AMP Air Conditioning
www.ampair.co.uk | sales@ampair.co.uk
Extruding margin of copper pipe with are machining: B (Unit: mm)
Copper pipe outer
dia.
9.5
12.7
15.9
19.1
When using R410A
tool
0 to 0.5 1.0 to 1.5
When using
conventional tool
Extruding margin of copper pipe with are tools: A (Unit: mm)
Copper pipe outer
dia.
9.5 13.2
12.7 16.6
15.9 19.7
19.1 24.0
• When using the conventional are tool, to connect R410A pipes with aring, make a margin approx. 0.5mm longer than that of an R22 pipe so that the are size matches the one specied. It is convenient to use a copper pipe gauge for size adjustment of the extruding margin.
• The flared supplied attachment pipe (Ø19.1) must be used to connect with discharge-side gas pipe valve (Ø19.1). (MAP120 to MAP200) Do not use half hard or hard materials instead of the supplied attachment pipe. The half hard or hard materials may be cracked and may cause leakage of refrigerant when it is ared.
• Use the flare nut provided with the product.
• After flaring the connection, be sure the flared part is not damaged, deformed, uneven, or flattened, and that there are no cutting chips on it.
CAUTION
Wrap the ball valve in a wet cloth to keep it cool and prevent the heat from the torch from damaging it when connecting the pipe to the ball valve on the suction side gas line.
+0
A
0.4
Wet cloth
Coupling size of brazed pipe
Connected section
External size Internal size
K
Standard outer dia.
of connected
copper pipe
ØC
G
ØF
External size Internal size
Standard outer dia.
(Allowable difference) CFKG
6.35 6.35 (±0.03)
9.52 9.52 (±0.03)
12.70 12.70 (±0.03)
15.88 15.88 (±0.03)
19.05 19.05 (±0.03)
22.22 22.22 (±0.03)
28.58 28.58 (±0.04)
34.92 34.90 (±0.04)
38.10 38.10 (±0.05)
41.28 41.28 (±0.05)
Selection of pipe size
Connected section
+0.04
( )
6.45
0.02 +0.04
( )
9.62
0.02 +0.04
( )
12.81
0.02 +0.04
( )
16.00
0.02 +0.03
( )
19.19
0.03 +0.03
( )
22.36
0.03 +0.06
( )
28.75
0.02 +0.04
( )
35.11
0.04 +0.08
( )
38.31
0.02 +0.08
( )
41.50
0.02
Min. depth of
insertion
7 6 0.06 or less 0.50 8 7 0.08 or less 0.60 9 8 0.10 or less 0.70
9 8 0.13 or less 0.80 11 10 0.15 or less 0.80 11 10 0.16 or less 0.82 13 12 0.20 or less 1.00 14 13 0.25 or less 1.20 15 14 0.27 or less 1.26 15 14 0.28 or less 1.35
Oval value
Min. thickness
of coupling
(Unit: mm)
Torch
¿ Capacity code of indoor and outdoor units
Selection of pipe material
• For the indoor unit, the capacity code is decided at each capacity rank. (Table 1)
• The capacity codes of the outdoor units are decided at each capacity rank. The maximum number of connectable indoor units and the total value of capacity codes of the indoor units are also decided. (Table 2)
NOTE
Compared with the capacity code of the outdoor unit, the total value of capacity codes of the connectable indoor units differs based on the height difference between the indoor units.
• When the height difference between the indoor units is 15m or less: Up to 135% of the capacity code (Equivalent to HP) of the outdoor unit.
• When the height difference between the indoor units is over 15m: Up to 105% of the capacity code.
30-EN29-EN
Table 1
AMP Air Conditioning
www.ampair.co.uk | sales@ampair.co.uk
Indoor unit
capacity rank
*005 0.6 1.7
005 0.8 2.2 007 0.8 2.2 009 1 2.8 012 1.25 3.6 015 1.7 4.5 018 2 5.6 024 2.5 7.1 027 3 8 030 3.2 9 036 4 11.2 048 5 14 056 6 16 072 8 22.4 096 10 28
Equivalent to HP
Capacity code
Equivalent to
capacity
*005 Indoor model: MMU-AP0056MH*, MMD-AP0056SPH*, MMK-AP0054MHP*
Table 2
Outdoor unit
model name*1
(Standard model)
MMY-MAP0806* 8 22.4 18 MMY-MAP1006* 10 28 22 MMY-MAP1206* 12 33.5 27 MMY-MAP1406* 14 40 31 MMY-MAP1606* 16 45 36 MMY-MAP1806* 18 50.4 40 MMY-MAP2006* 20 56 41 MMY-AP2216* 22 61.5 49 MMY-AP2416* 24 68 54 MMY-AP2616* 26 73.5 58 MMY-AP2816* 28 80 63 MMY-AP3016* 30 85 64 MMY-AP3216* 32 90.4 64 MMY-AP3416* 34 95.4 64 MMY-AP3616* 36 100.8 64 MMY-AP3816* 38 106.4 64 MMY-AP4016* 40 112 64 MMY-AP4216* 42 120 64
Equivalent to HP
Capacity code
Equivalent to
capacity
Max. No. of
indoor units*2
*1 For combination of the outdoor units, refer to “Combination of outdoor units”. *2 Under centralized control maximum 54 unit.
– 6 1 –
32-EN31-EN
– 1 7 –
AMP Air Conditioning
www.ampair.co.uk | sales@ampair.co.uk
Outdoor unit
(1) Balance pipes Ø9.5
Liquid pipe
Discharge-side
gas pipe
Suction-side
(3) Main piping
Header unit A
gas pipe
(9)
Follower unit B
(2)
First branch
Follower unit C
(8) Branching header
(7) Y-shaped branching joint
(4)
(1)(1)(1)
(4)
(10)
(5)
(10)
(5)
(4)
(4)*2
(6) (6)
Cooling only Cooling only
(9)
(7)(7)
(10) Single port type Flow selector unit
(7)
(4)
(5)
(7)
(4)
(4)
(4)
(10)
(5)
(10)
(7)
(4)*2
(6) (6) (6)
(4)*2
(7)
Indoor unit
(4)
(4)
(4)
(10)Multi port type
Flow selector unit
(4)*2
(7)
(6)
(6)
(6) (6)
Indoor unit
(7)
(4)*2
(6) (6)
(7)
(4)
(6)
(4)
(10)
(10)Single port type Flow selector unit (Long piping model)
(4)*2
(7)
(6)
(6)
34-EN33-EN
Selection of pipe size
AMP Air Conditioning
www.ampair.co.uk | sales@ampair.co.uk
No. Title Use part Selection of pipe size Remarks
Outdoor unit
(1)
connecting pipe
Between Outdoor unit connection
(2)
piping *6
Main piping
(3)
Branching pipe
(4)
*1, *2, *6
Indoor unit
(5)
connecting pipe
Outdoor unit
Ô
Outdoor unit connection piping kit
Outdoor unit connection piping kit
Ô
Outdoor unit connection piping kit
Outdoor unit connection piping kit of header unit
Ô
First branching section
Branching section
Ô
Branching section Branching section
Ô
Flow Selector unit Flow Selector unit
Ô
Branching section
Flow Selector unit Ô Indoor unit
Type
MMY-MAP0806* Ø9.5 Ø22.2 Ø19.1 Ø12.7 MMY-MAP1006* Ø9.5 Ø22.2 Ø19.1 Ø12.7 MMY-MAP1206* Ø9.5 Ø28.6 Ø19.1 Ø12.7 MMY-MAP1406* Ø9.5 Ø28.6 Ø22.2 Ø15.9 MMY-MAP1606* Ø9.5 Ø28.6 Ø22.2 Ø19.1 MMY-MAP1806* Ø9.5 Ø28.6 Ø22.2 Ø19.1 MMY-MAP2006* Ø9.5 Ø28.6 Ø22.2 Ø19.1
Total capacity codes of outdoor units at the
Equivalent to capacity Equivalent to HP
45.0 to below 61.5 16 to below 22 Ø28.6 Ø22.2 Ø15.9
61.5 to below 73.0 22 to below 26 Ø34.9 Ø28.6 Ø19.1
73.0 to below 101.0 26 to below 36 Ø34.9 Ø28.6 Ø22.2
101.0 or more 36 or more Ø41.3 Ø28.6 Ø22.2
Total capacity codes of all
Equivalent to
capacity
22.4 to below 33.5 8 to below 12 Ø22.2 Ø19.1 Ø12.7
33.5 to below 38.4 12 to below 14 Ø28.6 Ø19.1 Ø12.7
38.4 to below 45.0 14 to below 16 Ø28.6 Ø22.2 Ø15.9
45.0 to below 61.5 16 to below 22 Ø28.6 Ø22.2 Ø19.1
61.5 to below 73.0 22 to below 26 Ø34.9 Ø28.6 Ø19.1
73.0 to below 101.0 26 to below 36 Ø34.9 Ø28.6 Ø22.2
101.0 or more 36 or more Ø41.3 Ø34.9 Ø22.2
Total capacity codes of indoor
units at the downstream side
Equivalent to
capacity
Below 18 Below 6.4 Ø15.9 Ø12.7 Ø9.5
18 to below 34 6.4 to below 12.2 Ø22.2 Ø19.1 Ø12.7
34 to below 45.5 12.2 to below 16.2 Ø28.6 Ø22.2 Ø15.9
45.5 to below 56.5 16.2 to below 20.2 Ø28.6 Ø22.2 Ø19.1
56.5 to below 70.5 20.2 to below 25.2 Ø34.9 Ø28.6 Ø19.1
70.5 to below 98.5 25.2 to below 35.2 Ø34.9 Ø28.6 Ø22.2
98.5 or more 35.2 or more Ø41.3 Ø34.9 Ø22.2
Capacity rank Equivalent to HP Gas side Liquid side
005 to 012 0.8 to 1.25 Ø9.5 Ø6.4 015 to 018 1.7 to 2.0 Ø12.7 Ø6.4 024 to 056 2.5 to 6.0 Ø15.9 Ø9.5 072 to 096 8.0 to 10.0 Ø22.2 Ø12.7
Balance pipe
downstream side
outdoor units
Equivalent to HP
Equivalent to HP
side
Suction gas
side
Suction
gas
side
Suction
gas
side
Suction
gas side
Discharge
gas side
Discharge
gas side
Discharge
gas side
Discharge
gas side
Liquid
side
Liquid
side
Liquid side
Liquid side
Pipe size differs based on the total capacity codes of all outdoor units (See Table 2.)
Pipe size differs based on the total capacity code value of indoor units at the downstream side. (See Table 1 and 2.)
No. Title Use part Selection of pipe size Remarks
Indoor unit
(6)
connecting pipe
Y-shaped branching joint
(7)
*3, *4
Branching header
(8)
*3, *4, *5
Outdoor unit connection
(9)
piping kit *6
Terminal branching section
Ô
Indoor unit Multi port type or Single port
type (L ong piping model) FS unit
Ô
Indoor unit
Branching section
Branching section
Branching section
Capacity rank
005 to 012 0.6 to 1.25
015 to 018 1.7 to 2.0 024 to 056 2.5 to 6.0 - Ø15.9 Ø9.5
072 to 096 8.0 to 10.0 - Ø22.2 Ø12.7
Equivalent to capacity Equivalent to HP For 3 piping For 2 piping
For 4 branches
For 8 branches
Total capacity codes of outdoor units at the downstream side
18.0 to below 40.0 6.4 to below 14.2 RBM-BY105FE RBM-BY105E
40.0 to below 70.5 14.2 to below 25.2 RBM-BY205FE RBM-BY205E
70.5 or more 25.2 or more RBM-BY305FE RBM-BY305E
Equivalent to capacity Equivalent to HP
Equivalent to
HP
Total capacity code of indoor units Model name
Below 18.0 Below 6.4 RBM-BY55FE RBM-BY55E
Total capacity code of indoor units Model name
Equivalent to
capacity
Below 40.0 Below 14.2 RBM-HY1043FE RBM-HY1043E
40.0 to below 70.5 14.2 to below 25.2 RBM-HY2043FE RBM-HY2043E Below 40.0 Below 14.2 RBM-HY1083FE RBM-HY1083E
40.0 to below 70.5 14.2 to below 25.2 RBM-HY2083FE RBM-HY2083E
Below 73.0 Below 26.0 RBM-BT14FE
73.0 or more 26.0 or more RBM-BT24FE
Length of piping Gas side Liquid side
15 m or less real length Ø9.5 Ø6.4
Exceeds 15 m real length Ø12.7 Ø9.5
15 m or less real length Ø12.7 Ø6.4
Exceeds 15 m real length Ø15.9 Ø9.5
Equivalent to HP For 3 piping For 2 piping
Model name
Single port type*7 / Single port type (Long piping model) *8
Total capacity codes of connected indoor units
Equivalent to capacity Equivalent to HP
Below 11.2 Below 4.0
Flow Selector unit
(10)
*1: Use the same size as the main pipe if it is larger than the main pipe. *2: Use a suction gas pipe and a liquid pipe for the two pipes branching downstream from the ow selector unit and the dedicated cooling circuit. *3: Select the branch pipe of the rst branch according to the outdoor capacity code. *4: Select according to the outdoor unit capacity code if the total of the indoor capacity codes exceeds the outdoor unit capacity code. *5: It is possible to select up to a maximum capacity code total 16 (6 hp) for each one branch of the branching header. When using a branch header for the rst branch with an outdoor unit capacity code of 33.5 (12 hp equivalent) or more and 73.5 (26 hp
equivalent) or less, use RBM-HY2043FE (4 branches) and RBM-HY2083FE (8 branches) regardless of the total value of the capacity codes of the downstream indoor units. And, a branch header cannot be used as the rst branch if the performance rank is over 73.5 (26 hp
equivalent). *6: The downstream starting point is the main pipe. *7: The group connection of the multiple indoor units is possible up to maximum 8 units, and it is possible only within one FS unit. *8: The group connection of the multiple indoor units is possible up to 8 units if one remote controller is used, and it is possible up to 7 units if two
remote controllers are used. The group connection of the multiple indoor units is possible only within one branch or one FS unit. *9: In the downstream of the multi type FS unit, the header branch cannot be used.
Flow Selector unit Ô Indoor unit
11.2 to below 18.0 4.0 to below 6.4
18.0 to 28.0 or less 6.4 to below 10.0
Multi port type*8, *9
Equivalent to capacity Equivalent to HP
Below 18.0 Below 6.4
No. of
branch
4 RBM-Y1801F4PE* 6 RBM-Y1801F6PE*
Model name
RBM-Y1123FE / RBM-Y1124FE
/ RBM-Y1804FE
RBM-Y1803FE
/ RBM-Y2804FE
RBM-Y2803FE
Model name
– 8 1 –
36-EN35-EN
– 1 9 –
AMP Air Conditioning
www.ampair.co.uk | sales@ampair.co.uk
Allowable length of refrigerant pipes and allowable height
difference between units
C Follower unit
(c)
LO
Lc
Lb
Outdoor unit connecting
Branching pipe
Indoor unit connecting pipe
a
f
Indoor unit
The longest piping length from the First branch: Li
L5
d
i
Indoor unit
L10
Indoor unit connecting pipe
v
Branching header
L2
L1
b c
g
The longest piping length:
The longest piping length in Flow selector unit group : Ln
L6 L7
h
L8
e
m
j
Multi port type Flow Selector unit
p
q
4
k
tnioj gnihcnarb depahs-Ygnihcnarb tsriF
l
L
n
(m)
o
(n)
H4
Y-shaped branching joint
L11
r
s
Height difference between outdoor units
H3
Height difference between outdoor and indoor units:
H1
Outdoor unit
A
Header
Follower
unit
(b)(a)
La
LA
L1
Outdoor unit connection piping kit
Main piping
L3
L4
L9
Flow Selector unit
L12
Single port type Flow Selector unit (Long piping model)
L13
u
B
unit
¿ System restriction
Outdoor unit combination Up to 3 units Total capacity of outdoor units Up to 42 HP Indoor unit connection Up to 64 units (*1) Total capacity of indoor units
(varies depending on the height difference between indoor units.)
(*1) : In case without central control. It is up to 54 units in case with central control. (*2) : MAP200* : 125%, AP381* : 130%, AP401* : 125%
H2 15m 135% of outdoor units’ capacity (*2) 15m < H2 105% of outdoor units’ capacity
¿ Cautions for installation
• Set the outdoor unit rst connected to the bridging pipe to the indoor units as the header unit.
• Install the outdoor units in order of their capacity codes: A (header unit) B C
• When connecting gas pipes to indoor units, use Y-shaped branching joints to keep pipes level.
• When piping to outdoor units using Outdoor unit connection piping kits, intersect the pipes to the outdoor unit
and those to indoor units at a right angle as shown in gure 1 on “6. Installation of the outdoor unit”. Do not connect them as in gure 2 on “6. Installation of the outdoor unit”.
(o)
Height difference between indoor units H2
t
H6
Indoor unit
H5
38-EN37-EN
¿ Allowable length and allowable height difference of refrigerant piping
AMP Air Conditioning
www.ampair.co.uk | sales@ampair.co.uk
Item
Less than 34 HP or less 300 m
34 HP or more
Equivalent length 200 m Real length 180 m
H2 > 3 m
H2 3 m
Equivalent length 100 m Real length 85 m Equivalent length 120 m Real length 100 m H1 > 3 m 50 m H1 [ 3 m
Pipe length
Total extension of pipe (liquid pipe, real length)
Farthest piping length L (*1) (*2)
Max. equivalent length of Main piping
Farthest equivalent piping length from the rst branch Li (*1)
Farthest equivalent piping length between outdoor units LO (*1) 15 m LA+Lc (LA+Lb) maximum equivalent piping length of pipes connected to outdoor
units Maximum real length of terminal branching section to indoor
units Maximum real length of between Flow Selec-
tor unit and indoor unit
Single port type 15 m f, g, h, i, j,L7+m,L7+L8+o
Multi port type Single port type (Long piping model)
Maximum equivalent length between branching section 50 m L2, L3, L4, L5, L9, L10, L12
Upper outdoor units Lower outdoor units 30 m (*5)
Upper outdoor units 40 m Lower outdoor units (*3) 15 m
Single port type
H4
Single port type (Long piping model) H6
Height difference
Height between outdoor and indoor units H1
Height between indoor units
H2
Height between outdoor units H3 (*4) 5 m
Height difference between indoor units in one Flow Selector unit
Multi port type H5
*1: Farthest outdoor unit from the rst branch: (C), farthest indoor unit: (o) *2: Allowable values for length equivalent to furthest pipe are shown below and they vary according to performance rank of outdoor
unit.
22.4 to 56.0: 185m, 61.5 to 112.0: 195m, 120.0: 200m *3: When system capacity is greater than 28 HP, height difference between indoor units is limited to 3 m. If the piping exceeds 3 m
with a capacity greater than 28 HP there may be a case of capacity shortage in cooling. *4: Ensure that the header unit is installed below all connected follower outdoor unit(s). Possible product failure may occur if header unit is installed above any follower unit(s). *5: 40m is possible for a system that uses only the ow selector unit (multi port type), whose all the indoor units are 3HP or higher,
and working ambient temperature is 0ºC or higher. *6: If the height difference (H2) between indoor units exceed 3 m, set 50 m or less. *7: Total charging refrigerant is 140 kg or less.
*8: The total piping length in one Multi port type FS unit in case of branching to 4 : 120m (p + q + r + L11 + s + t), In case of branching
to 6 : 180m.
*9: Length of whole pipe should be shorter than 50 m (L11+s+t, L13+u+v) in one branch.
Allowable
value
LA + La + L b + L c + L 1 + L 2 + L 3 + L4 + L5 + L6 +L7 + L8 + L9 + L10 + L11 + L12 + L13 + L14 +
1000 m
a + b + c + d + e + f + g + h + i + j + k
(*7)
+ l + m + n + o+ p + q + r + s + t + u + v LA+Lc+L1+L3+L4+L5+L6+L7+L8+o
(LA+Lc+L1+L3+L9+L10+L11+t) (LA+Lc+L1+L3+L9+L12+L13+v)
L1
L3+L4+L5+L6+L7+L8+o (L3+L9+L10+L11+t) (L3+L9+L12+L13+v)
65 m
10 m Lc (La, Lb)
a+f, b+g, c+h, d+i, e+j, k, l,L6+L7+L8+o(Ln)
30 m
50 m
(*8) (*9)
(*6)(*10)
p, q, r,L11+s,L11+t,L13+u,L13+v
70 m
0.5 m
3 m
Pipes
*10: Extension up till 90 m is possible with conditions below
- Outdoor Temperature Cooling : 10°C to 46°C (Dry-bulb temp.) Heating : -5°C to 15°C (Wet-bulb temp.) Simultaneous operating : 7°C to 25°C (Dry-bulb temp.)
- Equivalent length of farthest piping from rst branching Li < 50 m
- Actual length of main piping L1 < 100 m
- Height difference between indoor units H2 < 3 m
- Single CDU, and up to 18 HP
- Minimum capacity of connectable indoor : unit 036 type or Larger
- Height difference between FS units < 0.5 m
- The total value of capacity codes of the connectable indoor units to the capacity code of the outdoor unit : 90% to 100%
Airtightness test
After the refrigerant piping has been nished, execute an airtight test. For an airtight test, connect a nitrogen gas canister as shown in the gure on this page and apply pressure.
• Be sure to apply pressure from the service ports of the packed valves (or ball valves) at the suction gas side, discharge gas side, liquid side and balance pipe side.
• An airtight test can only be performed at the service ports at the suction gas side, discharge gas side, liquid side and balance pipe side.
• Close the valves fully at the suction gas side, discharge gas side, liquid side and balance pipe side. As there is a possibility that the nitrogen gas will enter into the cycle of outdoor units, re-tighten the valve rods at the liquid side and balance pipe side before applying pressure.
• For each refrigerant line, apply pressure gradually in steps at the suction gas side, discharge gas side, liquid side and balance pipe side.
Be sure to apply pressure at the suction gas side, discharge gas side, liquid side and balance pipe side.
WARNING
Never use oxygen, ammable gases, or noxious gases in an airtight test.
To gauge manifold
Liquid-side service port
Liquid-side valve
Piping at site
To outdoor unit
Service port of discharge gas side
Ball valve of discharge gas side
Service port of suction gas side
Ball valve of suction gas side
To outdoor unit
Piping at site
Packed valve details
To outdoor unit
Service
To
port
gauge
of balance
manifold
pipe side
Packed valve
Piping at site
of balance pipe side
Piping at site
To outdoor unit
Connected to indoor unit
Main piping
Brazed
Fully closed
Fully closed
Fully closed
Connected to other follower units
Low pressure
Suction gas side valve fully closed
Header outdoor unit
Service port
Ø6.4 copper pipe
Service port
Discharge gas side valve fully closed
Service port
Liquid side valve fully closed
Service port
Balanced pipe side valve fully closed
gauge
High pressure gauge
VL
V
H
Reducing valve
Ø6.4 copper pipe
Gauge manifold
Nitrogen gas
– 0 2 –
40-EN39-EN
– 2 1 –
AMP Air Conditioning
www.ampair.co.uk | sales@ampair.co.uk
Able to detect a serious leakage
1. Apply pressure 0.3MPa (3.0kg/cm
2
G) for 5 minutes or more.
2. Apply pressure 1.5MPa (15kg/cm2G) for 5 minutes or more.
Available to detect slow leakage
3. Apply pressure 3.73MPa (38kg/cm2G) for approx. 24 hours.
• If there is no pressure decrease after 24 hours, the test is passed.
NOTE
However, if the environmental temperature changes from the moment of applying pressure to 24 hours after that, the pressure will change by about 0.01MPa (0.1kg/cm
2
G) per 1°C. Consider the pressure change when checking
the test result.
REQUIREMENT
When pressure decrease is detected in steps 1-3, check the leakage at the connecting points. Check the leakage using a foaming agent or other measures and seal the leak with re-brazing, are retightening or other methods. After sealing, execute an airtight test again.
Vacuum drying
• Be sure to use a vacuum pump equipped with the counter-ow prevention function so that oil in the pump will not ow back into piping for air conditioners. (If oil in the vacuum pump enters in the air conditioner with R410A refrigerant, a problem may be caused in the refrigerating cycle.)
After nishing the airtight test and discharging nitrogen gas, connect the gauge manifold to the service ports of the suction gas side, discharge gas side, liquid side and balance pipe side and connect a vacuum pump as shown in the gure below. Be sure to perform vacuuming for the suction gas side, discharge gas side, liquid side and balance pipe side.
Low pressure
To gauge manifold
Liquid-side service port
Liquid-side valve
Piping at site
Service port of suction gas side
Ball valve of suction gas side
To outdoor unit
Service port of discharge gas side
Ball valve of discharge gas side
To outdoor unit
Piping at site
Packed valve details
To outdoor unit
To gauge manifold
Piping at site
Piping at site
Service port of balance pipe side
To outdoor unit
Packed valve of balance pipe side
Connected to indoor unit
Fully closed
Fully closed
Fully closed
Connected to other follower units
Main pipe
Brazed
Suction gas side valve fully closed
Header outdoor unit
Service port
Discharge gas side valve fully closed
Balanced pipe side valve fully closed
Service port
Service port
Liquid side valve fully closed
Service port
• Use a vacuum pump with a high vacuuming degree [-100.7kPa (5Torr, -755mmHg)] and large exhaust gas amount (40L/minute or larger).
• Perform vacuuming for 2 or 3 hours, though the time differs depending on the pipe length. Check that all the valves at the suction gas side, discharge gas side, liquid side and balance pipe side are fully closed.
• If the pressure does not reach -100.7kPa or less even after vacuuming for over 2 hours, continue vacuuming for 1 hour or more. If the pressure does not reach -100.7kPa after 3 hours of vacuuming, stop vacuuming and check for air leakage.
• If the pressure reaches -100.7kPa or less after vacuuming for 2 hours or more, close the valves VL and VH on the gauge manifold fully and stop the vacuum pump. Leave it as it is for 1 hour to conrm that the vacuuming degree does not change.
If the degree of vacuum loss is large, moisture may remain in the pipes. In that case, inject dry nitrogen gas and
apply pressure to 0.05MPa and perform vacuuming again.
• After finishing the above procedure of vacuuming, exchange the vacuum pump with a refrigerant canister and advance to the additional charging of refrigerant.
gauge
High pressure gauge
V
L
VH
Vacuum
Gauge manifold
P
pump
42-EN41-EN
Adding refrigerant
AMP Air Conditioning
www.ampair.co.uk | sales@ampair.co.uk
After nishing vacuuming, exchange the vacuum pump with a refrigerant canister and start additional charging of refrigerant.
Calculation of additional refrigerant charge amount
Refrigerant charge amount at shipment from the factory does not include the refrigerant for pipes at the local site. For refrigerant to be charged in pipes at the local site, calculate the amount and charge it additionally.
NOTE
If the additional refrigerant amount indicates minus as the result of calculation, use the air conditioner without additional refrigerant.
Outdoor unit type MAP080 MAP100 MAP120 MAP140 MAP160 MAP180 MAP200
Charging amount (kg) 11.0
Additional refrigerant
charge amount at local site
Real length of liquid pipe
=
Additional refrigerant
charge amount per 1 m
×
liquid pipe (Table 1)
1.3
×
Table 1
Liquid pipe dia. (mm) 6.4 9.5 12.7 15.9 19.1 22.2 Additional refrigerant amount / 1 m
liquid pipe (kg/m)
0.025 0.055 0.105 0.160 0.250 0.350
Corrective amount of
refrigerant depending on HP
+
of co-operating outdoor units
(Table 2)
Table 2
Equivalent
HP
8HP MAP0806* MAP0806* - - 2 10HP MAP1006* MAP1006* - - 3 12HP MAP1206* MAP1206* - - 8 14HP MAP1406* MAP1406* - - 10 16HP MAP1606* MAP1606* - - 12 18HP MAP1806* MAP1806* - - 14 20HP MAP2006* MAP2006* - - 15 22HP AP2216* MAP1206* MAP1006* - 6 24HP AP2416* MAP1406* MAP1006* - 8 26HP AP2616* MAP1406* MAP1206* - 12 28HP AP2816* MAP1406* MAP1406* - 12 30HP AP3016* MAP1606* MAP1406* - 14 32HP AP3216* MAP1806* MAP1406* - 15 34HP AP3416* MAP1806* MAP1606* - 16 36HP AP3616* MAP1806* MAP1806* - 18 38HP AP3816* MAP2006* MAP1806* - 22 40HP AP4016* MAP2006* MAP2006* - 24 42HP AP4216* MAP1406* MAP1406* MAP1406* 14
Model name of
outdoor unit
MMY-
Combination of outdoor unit
Unit 1 Unit 2 Unit 3
MMY-
Corrective of
refrigerant
(kg)
Charging of refrigerant
• Keeping the valve of the outdoor unit closed, be sure to charge the liquid refrigerant into the service port at the liquid side.
• If the specied amount of refrigerant cannot be charged, fully open the valves of the outdoor unit at liquid and gas sides, operate the air conditioner in COOL mode, and then charge refrigerant into service port at the gas side. In this time, choke the refrigerant slightly by operating the valve of the canister to charge liquid refrigerant.
• The liquid refrigerant may be charged suddenly, therefore be sure to charge refrigerant gradually.
– 2 2 –
44-EN43-EN
– 2 3 –
AMP Air Conditioning
www.ampair.co.uk | sales@ampair.co.uk
Full opening of the valve
Open the valves of the outdoor unit fully.
MAP080 MAP100
Balance pipe
Liquid side
Discharge gas side
Packed valve
Using a 4 mm-hexagonal wrench, fully open the valve shaft.
Ø12.7 packed valve
Using a 4 mm-hexagonal wrench, fully open the valve shaft.
Ball valve
Using a athead screwdriver, turn it counterclockwise by 90° until it hits the stopper. (Full open)
Service port
(1)
(2)
Valve unit
Using athead screwdriver, turn it counterclockwise by 90° until it hits the stopper. (Full open)
Flare nut
MAP120 MAP140 MAP160 MAP180 MAP200
Ø15.9 packed valve
Using a 5 mm-hexagonal wrench, fully open the valve shaft.
Position of screwdriver slot
Fully closed Fully opened
* When opened fully, do not apply excessive
torque after the screwdriver hits the stopper; otherwise a problem may be caused on the valve. (5 N•m or less)
Slot
F-GAS label
This product contains uorinated greenhouse gases
• Chemical Name of Gas R410A
• Global Warming Potential (GWP) of Gas 2088 (ex.R410A ref.AR4)
CAUTION
1. Stick the enclosed refrigerant label adjacent to the service ports for charging or recovering location and where
possible adjacent to existing nameplates or product information label.
2. Clearly write the charged refrigerant quantity on the refrigerant label using indelible ink. Then, place the
included transparent protective sheet over the label to prevent the writing from rubbing off.
3. Prevent emission of the contained uorinated greenhouse gas. Ensure that the uorinated greenhouse gas is
never vented to the atmosphere during installation, service or disposal. When any leakage of the contained uorinated greenhouse gas is detected, the leak shall be stopped and repaired as soon as possible.
4. Only qualified service personnel are allowed to access and service this product.
5. Any handling of the uorinated greenhouse gas in this product, such as when moving the product or recharging
the gas, shall comply under (EU) Regulation No. 517/2014 on certain uorinated greenhouse gases and any relevant local legislation.
6. Periodical inspections for refrigerant leaks may be required depending on European or local legislation.
7. Contact dealers, installers, etc., for any questions.
Ball valve
Using a wrench, turn the valve shaft counterclockwise by 90° until it hits the stopper. (Full open)
Suction gas side
Fully closed Fully opened
46-EN45-EN
Heat insulation for pipe
AMP Air Conditioning
www.ampair.co.uk | sales@ampair.co.uk
• Apply heat insulation of pipe separately at the liquid, gas, and balance sides.
• Be sure to use thermal insulator resistant up to 120°C or higher for pipes at the gas side.
Finishing after connecting pipes
• After piping connection work has been nished, cover the opening of the piping/wiring panel with the piping cover, or ll silicon or putty into the space between the pipes.
• In case of drawing-out the pipes downward or sideward, also close the openings of the base plate and the side plate.
• Under the opened condition, a problem may be caused due to the entering of water or dust.
When using the piping cover When not using the piping cover
Piping/wiring panel
Drawing-out sideward
Piping/wiring panel
Drawing-out sideward
8 Electric wiring
WARNING
The appliance shall be installed in accordance with national wiring regulations.
Capacity shortages of the power circuit or an incomplete installation may cause an electric shock or re.
CAUTION
• Perform wiring of power supply complying with the rules and regulations of the local electric company.
• Do not connect 380V - 415V power to the terminal blocks for control cables (U1, U2, U3, U4, U5, U6, S); otherwise, the unit may break down.
• Be sure that electric wiring does not come into contact with high-temperature parts of piping; otherwise, the coating of cables may melt and cause an accident.
• After connecting wires to the terminal block, take off the traps and x the wires with cord clamps.
• Follow the same structure for both the control wiring and refrigerate piping.
• Do not conduct power to indoor units until vacuuming of the refrigerant pipes has nished.
• Refer to the installation manuals of indoor unit and ow selector unit for power wiring and communication wiring of indoor unit and ow selector unit.
Close the opening with the pipe cover.
Drawing-out frontward
Drawing-out downward
¿ Pipe holding bracket
Attach pipe holding brackets following the table below.
Diameter of pipe (mm) Interval
Ø15.9 - Ø19.1 2m Ø22.2 - Ø41.3 3m
Drawing-out frontward
Drawing-out downward
Fill silicon or putty into the periphery of the pipes.
Power supply specications
Do not bridge the power between outdoor units through the equipped terminal blocks (L1, L2, L3, N)
Power supply for
outdoor units
L
1
L
2
L
3
N
L
L
1
1
L
L
2
2
L
L
3
3
N
N
Incorrect
– 42 –
48-EN47-EN
– 2 5 –
U1
U2
U1
U2
U1
U2
U1
U2
U1
U2
U1
U2
Multi port type FS unit (4port)
AMP Air Conditioning
www.ampair.co.uk | sales@ampair.co.uk
¿ Power wiring selection
• Select the power supply cabling of each outdoor unit from the following specications: Cable 5-core, in conformance with design H07 RN-F or 60245 IEC 66.
• To decide nominal cross sectional area of conductor, refer to following table of Maximum Overcurrent Protection (Amps).
MOCP:Maximum Overcurrent Protection (Amps)
Model name
Phase and frequency Nominal Voltage
Power Supply
MMY-MAP0806* MMY-MAP1006* 26.1 32 MMY-MAP1206* 31.0 40 MMY-MAP1406* 35.8 50
3N~50Hz 380-400-415V MMY-MAP1606* 40.6 50 MMY-MAP1806* 44.9 50 MMY-MAP2006* 49.3 63 MMY-AP2216* MMY-AP2416* 62.0 80 MMY-AP2616* 66.8 80 MMY-AP2816* 71.6 80 MMY-AP3016* 76.5 100 MMY-AP3216* 81.3 100
3N~50Hz 380-400-415V MMY-AP3416* 85.6 100
MMY-AP3616* 89.8 100 MMY-AP3816* 94.2 125 MMY-AP4016* 98.6 125 MMY-AP4216*
3N~50Hz 380-400-415V
MCA:Minimum Circuit Amps
MCA
(A)
MOCP
(A)
21.5 25
57.1 63
107.4 125
Specications for communication wiring
¿ Design of communication wiring
Summary of communication wiring
Outdoor unit Header outdoor
*1
S
U6
U3
Central remote device (option)
U1 U2 U3 U4
Single port type FS unit Single port type FS unit Single port type FS unit
U1
CN02
CN81
Indoor unit
Remote controller Remote controller Remote controller
S
U4
U2
U5
W1
W2
U1 U2 A B U1 U2 A B U1 U2 A B U1 U2 A B
AB AB AB
CN81
Indoor unit Indoor unit Indoor unit Indoor unit
Outdoor unit Follower outdoor
W1 Control wiring between indoor and outdoor units (Shield wire) W2 Control wiring between indoor units (Shield wire) W3 Control wiring between outdoor units (Shield wire)
S
U6
U3
U1
W3
CN02
CN81
Indoor unit Indoor unit Indoor unit
A B CN81
A B A B A B A B
Remote controller Remote controller Remote controller Remote controller
S
U4
U2
U5
CN02
CN81
A B CN81 U1U2A B CN81
*1 When perform a central control, connect a relay connector
between [U1, U2] and [U3, U4] terminals in the header unit. (At shipment from factory : No connection) *2 Connection of shield wire must be connected (Connected to all connecting sections in each Indoor unit) *3 Group control
*2
CN81
A B A B A B A B
*3
A B
Circuit breaker
(Earth leakage breaker)
Main switch (Fuse)
L1L2L3 N
L1L2L3 N L1L2L3N
CN81
Indoor unit Indoor unit Indoor unit Indoor unit
• Communication wiring and central control wiring use 2-core non-polarity wires. Use 2-core shield wires to prevent noise trouble.
• Connecting the closed end terminal of shield wire. (Connected to all connecting sections in each unit)
• Use 2-core non-polarity wire for remote controller. (A, B terminals) Use 2-core non-polarity wire for Multi port type FS unit and Single port type FS unit (L ong piping model) (A, B terminals) Use 2-core non-polarity wire for wiring of group control. (A, B terminals)
In case of Single port type FS unit, control wire and power line wire between FS unit and indoor unit are the accessory parts of FS unit. (Wire length : 6m)
If the length between indoor unit and Flow selector unit exceeds 5m, connect by using the Connection cable kit sold separately
(RBC-CBK15FE).
A B CN81
A B A B A B A B
Remote controller Remote controller Remote controller Remote controller
A B A B A B A B
Single port type FS unit
(Long piping model)
A B CN81 U1U2A B CN81
Single port type FS unit
(Long piping model)
Single port type FS unit
(Long piping model)
A B
Single port type FS unit
(Long piping model)
50-EN49-EN
Restriction of control wiring
AMP Air Conditioning
www.ampair.co.uk | sales@ampair.co.uk
Be sure to keep the rule of below tables about size and length of control wiring.
Central
control
device
U2
U1
U4
U3
Outdoor
unit
Indoor
unit
U3 U4
U1 U2 U5 U6
L1
U1 U2
AB
Remote
controller
Header unit
U3 U4
U1 U2 U5 U6
U1 U2
AB
Header unit
Super modular multi system
L4
Follower
Follower
unit
unit
U3 U4
U1 U2 U5 U6
U1 U2 U5 U6
L5
L2
U1 U2
U1 U2
AB
AB
Remote
controller
U3 U4
U1 U2
AB
Table-1
Table-1
Table-3
U3 U4
U1 U2 U5 U6
U1 U2
AB
L7
Remote
controller
Header unit
Follower unit
U3 U4
U1 U2 U5 U6
Table-2
L3
U1 U2
U1 U2
AB
L6
Table-3
Multi port type FS unit and
Single port type FS unit
(Long piping model)
AB
Table-1 Control wiring between indoor and outdoor units (L1, L2, L3), Central control wiring (L4)
Wiring 2-core, non-polarity Type Shield wire Size/Length 1.25 mm
(*1): Total length of Communication wiring length for all refrigerant circuits (L1 + L2 + L3 + L4)
2
: Up to 1000 m/2.0 mm2: Up to 2000 m (*1)
Table-2 Communication wiring between outdoor units (L5)
Wiring 2-core, non-polarity Type Shield wire Size/Length 1.25 mm
2
to 2.0 mm2/Up to 100 m (L5)
L8
Table-3
A BA BA B
AB
¿ Group control through a Remote Controller
Group control of multiple indoor units (8 units) through one or two remote controller switch
Indoor unit
No.1 No.2 No.3 No.4 No.7 No.8
AB AB AB AB AB AB
Remote controller
(A.B)
For the group connection within each branch of the Multi port type FS unit and Single port type FS unit (Long piping model) : It is up to 8 units if one remote controller is used, and it is up to 7 units if two remote controllers are used.
Connection of power wires and communication wires
Remove knockouts on the piping/wiring panel on the front of the unit and the panel on the bottom to get the power and communication wires through the holes.
Piping/wiring panel
Knockout for the communication wire
Knockout for the power wire
NOTE
Be sure to separate the power wire and communication wires.
Knockout for the power supply wire
Table-3 Remote controller wiring (L6, L7), Multi port type FS unit and Single port type FS unit (Long piping model) wiring (L8)
Wiring 2-core, non-polarity Type 0.5 mm
Size/Length
2
to 2.0 mm
• Up to 500 m (L6 + L7)
• Up 400 m in case of wireless remote controller in group control.
• Up to 200 m total length of control wiring between indoor units and Multi port type FS unit and Single port type FS unit (Long piping model) (L6+L8)
• Up to 300 m (L6 + L7+L8)
• Up to 300 m (L7)
2
– 6 2 –
52-EN51-EN
Power supply terminal block
AMP Air Conditioning
www.ampair.co.uk | sales@ampair.co.uk
Clamp lter (only MAP160 to MAP200 type)
Cord clamps
Communication terminal block
– 2 7 –
Screw size and tightening torque
Screw size
Tightening torque
(N•m) Power supply terminal M6 2.5 to 3.0 Earth screw M8 5.5 to 6.6
¿ Communication wire connection
Get the communication wire through the cutout on the side of the electrical control box and connect it to the communication wire terminals, then x it with the communication cable clamp.
JK0-B2F
Earth screw
Communication wires
Power supply wires
Cord clamp
¿ Power supply wire connection
1. Insert the power supply wire through the cutout on the side of the electrical control box and connect the power supply wire to the power supply terminal block and the earth line to the earth screw. After that, x the power supply wire with the 2 cord clamps.
2. Be sure to use round-type crimping terminals for power connection.
Also, apply insulating sleeves to the crimping parts. Use a driver of appropriate size to x the terminal screws.
L1
3
L2 L3 N
Power supply wire
N
10mm or more
Attached clamp lter Fixed on attached binding band (only MAP160 to MAP200 type)
L1 L2L
Earth line
U1
U2
TO
INDOOR
SHIELD SHIELD
UNIT
U4
U3
TO
CENTRAL
CONTROLLER
U5
TO
OUTDOOR
UNIT
U6SS
U5, U6: Communication wiring between outdoor units
3, U4: Central control device
U S: Shield wire earth
1, U2: Communication wiring between indoor/outdoor units
U
Screw size and tightening torque
Screw size
Tightening torque
(N•m)
Communication wire terminal M4 1.2 to 1.4
54-EN53-EN
Regulation of high frequency wave
AMP Air Conditioning
www.ampair.co.uk | sales@ampair.co.uk
9 Address setting
This equipment complies with IEC 61000-3-12 provided that the short-circuit power Ssc is greater than or equal to Ssc (*1) at the interface point between the user’s supply and the public system. It is the responsibility of the installer or user of the equipment to ensure, by consultation with the distribution network operator if necessary, that the equipment is connected only to a supply with a short-circuit power Ssc greater than or equal to Ssc (*1)
Furthermore, when similar equipment or other equipment which may cause harmonic current emissions are to be connected to the same interface point with this equipment, to reduce the risk of possible problems which may be caused from addition of those harmonic current emissions, it is recommended to make sure that the short-circuit power Ssc at the interface point is greater than the sum of the minimum Ssc required by all the equipment which will be connected to the interface point.
Ssc (*1) :
Model Ssc (kVA)
MMY-MAP0806FT8P- U K MMY-MAP0806FT8JPU K
MMY-MAP1006FT8P-U K MMY-MAP1006FT8JPU K
MMY-MAP1206FT8P-U K MMY-MAP1206FT8JPU K
MMY-MAP1406FT8P-U K MMY-MAP1406FT8JPU K
MMY-MAP1606FT8P-U K MMY-MAP1606FT8JPU K
MMY-MAP1806FT8P-U K MMY-MAP1806FT8JPU K
MMY-MAP2006FT8P-U K MMY-MAP2006FT8JPU K
742
906
1026
1112
1309
1462
1609
On this unit, it is required to set the addresses of the indoor units before starting air conditioning. Set the addresses following the steps below.
CAUTION
• Be sure to complete the electric wiring before setting the addresses.
• If you turn on the outdoor unit before turning on the indoor units, the CODE No. [E19] is indicated on the 7­segment display on the interface P.C. board of the outdoor unit until the indoor units are turned on. This is not a malfunction.
• It may take up to ten minutes (normally about ve minutes) to address one refrigerant line automatically.
• Settings on the outdoor unit are required for automatic addressing. (Address setting is not started simply by turning on the power.)
• Running the unit is not required for address setting.
• The addresses can be set manually.
Automatic addressing: setting addresses using SW15 on the interface P.C. board on the header outdoor unit Manual addressing: setting addresses on the wired remote controller. * When setting an address manually, the wired remote controller must temporarily be paired with an
indoor unit one-to-one. (when the system is organized for group operation and no Remote controller)
REQUIREMENT
• High voltage parts exist in the electrical control box. If you set addresses on an outdoor unit, operate the unit through the access door shown on the illustration
Access door cover
Cover of the electrical control box
Fixing screw for the access door cover
on the right to avoid electric shock. Do not remove the cover of electrical control box.
* After finishing operations, close the access door cover
and x it with the screw.
Automatic address setting
Central control of a single refrigerant line: go to Address setting procedure 1 Central control of 2 or more refrigerant lines: go to Address setting procedure 2
(Example)
Address setting procedure
When controlling a single refrigerant line
centrally
To procedure 1 To procedure 2
When controlling 2 or more refrigerant lines
centrally
– 8 2 –
System wiring diagram
Outdoor Outdoor
Remote
controller
Central remote
controller
Indoor Indoor Indoor Indoor
Remote
controller
Remote
controller
Central remote
controller
Outdoor Outdoor
controller
Indoor Indoor Indoor Indoor
Remote
controller
Remote
controller
Remote
controller
Central remote
56-EN55-EN
– 2 9 –
4
AMP Air Conditioning
www.ampair.co.uk | sales@ampair.co.uk
¿ Address setting procedure 1
Turn on indoor units rst, and then turn on outdoor units.
1
About one minute after turning the power on, conrm that the 7-segment display on the
2
interface P.C. board of the header outdoor unit indicates Press SW15 to start the automatic address setting.
3
(It may take up to 10 minutes (normally about 5 minutes) to complete one line’s setting.)
The 7-segment display indicates
4
After the indication, When the ashing stops and
U. 1. - - - (U. 1. ash
Auto 1 → Auto 2 → Auto 3
)
starts ashing on the display.
U. 1. - - - (U. 1. light
)
U. 1. L08 (U. 1. ash
.
remain lit on the display, the setting is
)
.
complete.
Interface P.C. board on the header outdoor unit
SW05 SW15
SW04
D600 D601 D602 D603
D604
3
2,
SW02 SW03
SW01
REQUIREMENT
• When 2 or more refrigerant lines are controlled as a group, be sure to turn on all the indoor units in the group before setting addresses.
(Note: The group control of more than two refrigerant systems is possible only when all the FS units are single
port type.)
• If you set the unit addresses of each line separately, each line’s header indoor unit is set separately. In that case, the CODE No. “L03” (Indoor header unit overlap) is indicated as running starts. Change the group address to make one unit the header unit using wired remote controller.
(Example) Controlling 2 or more refrigerant lines as a group
Outdoor Outdoor
System wiring diagram
Indoor Indoor Indoor Indoor
Remote
controller
(Group control)
¿ Address setting procedure 2
Set a system address for each system using SW13 and 14 on the interface P.C. board on the
1
header outdoor unit of each system. (Factory default: Address 1)
NOTE
Be sure to set a unique address on each system. Do not use a same address as another system (refrigerant line) or a custom side.
Interface P.C. board on the header outdoor unit
SW06 SW07 SW09 SW10
1234 1234 1234 1234
SW11 SW12 SW13 SW14
1234 1234 1234 1234
Switch settings for a line (system) address on the interface P.C. board on the outdoor unit
(: switch ON, Í: switch OFF)
Line (system) address
1 2 3 4 5 6 7 8
9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25
12341234
―――
―――
―――
―――
―――
―――
―――
―――
―――
―――
―――
―――
―――
―――
―――
―――
―――
―――
―――
―――
―――
―――
―――
―――
―――
SW13 SW14
ННННН
Í
ÍÍ
Í

ÍÍÍ
ÍÍÍ
Í
ÍÍ
Í

Í

ÍÍÍÍ
Í
ÍÍ
Í

ÍÍ
ÍÍÍ
Í
ÍÍ
Í





Í

ÍÍÍÍ
ÍÍÍ
Í
ÍÍ
Í
Í

ÍÍÍ
ÍÍ
ÍÍ
Í
Í
Í
Í
Í
Í


ÍÍ
ÍÍ
Í
Í
Í
Í
58-EN57-EN
Line (system) address
AMP Air Conditioning
www.ampair.co.uk | sales@ampair.co.uk
26 27
“―”: not used for system address setting (Do not change their positions.)
2
28
Be sure to disconnect the relay connectors between the [U1U2] and [U3U4] terminals on
12341234
―――
―――
―――
SW13 SW14


Í
ÍÍ
Í
Í
all the header outdoor units that will be connected to the central control. (Factory default: disconnected)
2
U1
U2
TO
INDOOR
SHIELD SHIELD
UNIT
Turn on indoor units rst, and then turn on outdoor units.
3
About 1 minute after turning the power on, conrm that the 7-segment display on the interface
4
P.C. board of the header outdoor unit indicates Press SW15 to start the automatic address setting.
5
(It may take up to 10 minutes (normally about 5 minutes) to complete one line’s setting.)
The 7-segment display indicates
6
After the indication, When the ashing stops and
U. 1. - - - (U. 1. ash
Auto 1 → Auto 2 → Auto 3
)
starts ashing on the display.
U. 1. - - - (U. 1. light
complete. Repeat steps 4 to 6 for other refrigerant lines.
7
After completing address setting of all systems, turn off DIP switch 2 of SW30 on the interface
8
P.C. boards of all the header outdoor units connected to the same central control, except the unit that has the lowest address.
(For unifying the termination of the wiring for the central control of indoor and outdoor units)
U4
U5
TO
OUTDOOR
UNIT
U6SS
)
.
U3
TO
CENTRAL
CONTROLLER
U. 1. L08 (U. 1. ash
.
)
, remains lit on the display, the setting is
Connect the relay connectors between the [U1, U2] and [U3, U4] terminals of the header
9
outdoor unit of each refrigerant line.
9
U1
U2
TO
INDOOR
SHIELD SHIELD
UNIT
Set the central control address.
10
(For the setting of the central control address, refer to the installation manuals of the central control devices.)
Header unit interface P.C. board
7-segment
display
SW13 SW14
12
SW30
U4
SW05
U5
TO
OUTDOOR
UNIT
SW15
SW03
U6SS
U3
TO
CENTRAL
CONTROLLER
SW04
D600 D601 D602 D603 D604
SW01 SW02
– 0 3 –
60-EN59-EN
– 3 1 –
AMP Air Conditioning
www.ampair.co.uk | sales@ampair.co.uk
Switch setting (setting example when controlling 2 or more refrigerant lines centrally)
Outdoor units (setting manually)
Outdoor unit’s
interface
P.C. board
SW13, 14 (Line (system) address)
DIP switch 2 of SW30 (Terminator of indoor/ outdoor communication line and central control line)
Relay connector
Header unit Header unit Header unitFollower unit Follower unit
Relay
connector
Indoor units (automatic setting)
Line (system) address 1 1223 Indoor unit address 1 2121 Group address 0 0120
Header unit
1
ON
Connect
after setting
addresses.
U3U4 U3U4
U1U2
A
BAB AB
Remote
controller
Individual Group
Remote
controller
Follower
unit
(No setting
required)
(No setting
required)
Open
connector
Header unit
2
Set to OFF
after setting
addresses.
Connect
after setting
addresses.
U3U4 U3U4 U3 U4
Relay
AB AB
Remote
controller
*The items in bold font must be set manually.
Follower
unit
(No setting
required)
(No setting
required)
Open
Header unit Factory default
31
Set to OFF
after setting
addresses.
Connect
after setting
addresses.
controller
2U1U6U5U2U1U6U5U U1U2 U5U6 U1U2 U5U6 U5U6
connector
2U1U2U1U2U1U2U1U2U1U
Remote
Relay
ON
Open
Central control
controller
CAUTION
Relay connector connection
Never connect relay connectors between the [U1, U2] and [U3, U4] terminals before completing address setting of all the refrigerant lines. Otherwise, the addresses cannot be set correctly.
Manual address setting using the remote controller
Procedure when setting indoor units’ addresses rst under the condition that indoor wiring has been completed and outdoor wiring has not been started (manual setting using the remote controller)
q Wiring example of 2 refrigerant lines
(Note: The group control of more than two refrigerant systems is possible only when all the FS units are single
port type.)
Refrigerant line 1 Refrigerant line 2
Outdoor
unit
Indoor unit 1 Indoor unit 1Indoor unit 2 Indoor unit 2Indoor unit 3
Remote
controller
Line (system) address 1 1 1 2 2 Indoor unit address 1 2 3 1 2
Group address
1
Header unit2 Follower unit2 Follower unit2 Follower unit2 Follower unit
In the example above, disconnect the remote controller connections between the indoor units and connect a wired remote controller to the target unit directly before address setting.
DATA
SET
SETTING
2, 5, 8
SET DATA CODE No.
4, 7, 10
11
FILTER RESET
TEMP .
TEST
TIMER SET
TIME
SET CL
UNIT No.
R.C. No.
Outdoor
CODE No.
ON / OFF
unit
3, 6, 9
1
Pair the indoor unit to set and the remote controller one-to-one. Turn on the power.
1
Push and hold the , , and buttons at the same time for more than 4 seconds.
LCD starts ashing.
62-EN61-EN
<Line (system) address>
AMP Air Conditioning
www.ampair.co.uk | sales@ampair.co.uk
2
Push the TEMP. / buttons repeatedly to set the CODE No. to .
Push the TIME / buttons repeatedly
3
to set a system address.
(Match the address with the address on the interface P.C. board of the header outdoor unit in the same refrigerant line.)
Push button.
4
(It is OK if the display turns on.)
<Indoor unit address>
5
Push the TEMP. / buttons repeatedly to set the CODE No. to .
Push the TIME / buttons repeatedly
6
to set an indoor unit address. Push the button.
7
(It is OK if the display turns on.)
<Group address>
8
Push the TEMP. / buttons repeatedly to set the CODE No. to .
Push the TIME / buttons repeatedly
9
to set a group address. If the indoor unit is individual, set the address to header unit,
Individual : 0000 Header unit : 0001 Follower unit : 0002
Push the button.
10
(It is OK if the display turns on.)
Push the button.
11
The address setting is complete. ( ashes. You can control the unit after has disappeared.)
; follower unit, .
In case of group
}
control
NOTE
1. Do not use address numbers 29 or 30 when setting system addresses using the remote controller.
These 2 address numbers cannot be used on
outdoor units and the CODE No. [E04] (Indoor/ outdoor communication error) will appear if they are mistakenly used.
2. If you set addresses to indoor units in 2 or more refrigerate lines manually using the remote controller and will control them centrally, set the header outdoor unit of each line as below.
• Set a system address for the header outdoor unit
of each line with SW13 and 14 of their interface P.C. boards.
• Turn off DIP switch 2 of SW30 on the interface
P.C. boards of all the header outdoor units connected to the same central control, except the unit that has the lowest address. (For unifying the termination of the wiring for the central control of indoor and outdoor units)
• Connect the relay connectors between the [U1,
U2] and [U3, U4] terminals on the header outdoor unit of each refrigerate line.
• After finishing all the settings above, set the
address of the central control devices. (For the setting of the central control address, refer to the installation manuals of the central control devices.)
Conrming the indoor unit
addresses and the position of an indoor unit using the remote controller
¿ Conrming the numbers and
positions of indoor units
To see the indoor unit address of an indoor unit which you know the position of
q When the unit is individual (the indoor unit is
paired with a wired remote controller one-to­one), or it is a group-controlled one.
CODE No.
UNIT No.
FILTER RESET
TEMP .
TEST
TIMER SET
TIME
SET CL
ON / OFF
1
Starts running
2
(Execute it while the units are running.)
;
Push the button if the units stop.
1
Push the button (left side of the
2
button).
A unit numbers is indicated on the LCD (it will disappear after a few seconds). The indicated number shows the system address and indoor unit address of the unit. When 2 or more indoor units are connected to the remote controller (group-controlled units), a number of other connected units appears each
time you push the button).
button (left side of the
To nd an indoor unit’s position from its address
q When checking unit numbers controlled as a
group
SET
DATA
SETTING
TEMP .
TIMER SET
3
Stop
FILTER RESET
TIME
SET CL
TEST
1
(Execute it while the units are stopped.)
The indoor unit numbers in a group are indicated one after another. The fan and louvers of the indicated units are activated.
1
Push and hold the and buttons at the same time for more than 4 seconds.
appears on UNIT No. on the LCD display.
The fans and louvers of all the indoor units in
the group are activated.
Push the button (left side of the
2
button). Each time you push the button, the indoor unit numbers are indicated one after another.
• The first-indicated unit number is the address of the header unit.
• Only the fan and louvers of the indicated indoor unit are activated.
Push the button to nish the procedure.
3
All the indoor units in the group stop.
q To check all the indoor unit addresses using
an arbitrary wired remote controller.
(When communication wirings of 2 or more
refrigerant lines are interconnected for central control)
UNIT No.
R.C. No.
CODE No.
ON / OFF
1 2
– 2 3 –
64-EN63-EN
– 3 3 –
AMP Air Conditioning
www.ampair.co.uk | sales@ampair.co.uk
SET
DATA
SETTING
TEMP .
TIMER SET
1
FILTER RESET
TIME
TEST
CL
SET
6
3
(Execute it while the units are stopped.)
You can check indoor unit addresses and positions of the indoor units in a single refrigerant line. When an outdoor unit is selected, the indoor unit numbers of the refrigerant line of the selected unit are indicated one after another and the fan and louvers of the indicated indoor units are activated.
Push and hold the TIME and buttons
1
at the same time for more than 4 seconds. At rst, the line 1 and CODE No. (Address Change) are indicated on the LCD display. (Select an outdoor unit.)
Push the (left side of the button)
2
and buttons repeatedly to select a system address.
Push the button to conrm the system
3
address selection.
The address of an indoor unit connected to the
selected refrigerant line is indicated on the LCD display and its fan and louvers are activated.
Push the button (left side of the
4
button). Each time you push the button, the indoor unit numbers of the selected refrigerant line are indicated one after another.
• Only the fan and louvers of the indicated indoor unit are activated.
UNIT No.
R.C. No.
CODE No.
ON / OFF
4
2
5
¿ To select another system address
Push the CL button to return to step 2.
5
After returning to step 2, select another system
address and check the indoor unit addresses of the line.
Push the button to nish the procedure.
6
Changing the indoor unit
address using a remote controller
To change an indoor unit address using a wired remote controller.
q The method to change the address of an
individual indoor unit (the indoor unit is paired with a wired remote controller one-to­one), or an indoor unit in a group.
(The method is available when the addresses
have already been set automatically.)
UNIT No.
R.C. No.
ON / OFF
2, 6, 7
CODE No.
4
DATA
SET
SETTING
TEMP .
3 5
8
Finish
FILTER RESET
TIMER SET
TIME
SET CL
TEST
1
(Execute it while the units are stopped.)
Push and hold the , , and buttons
1
at the same time for more than 4 seconds.
(If 2 or more indoor units are controlled in a group, the rst indicated UNIT No. is that of the head unit.)
Push the button (left side of the
2
button) repeatedly to select an indoor unit number to change if 2 or more units are controlled in a group. (The fan and louvers of the selected indoor unit are activated.)
(The fan of the selected indoor unit is turned on.)
3
Push the TEMP. / buttons repeatedly to select for CODE No..
Push the TIME / buttons repeatedly
4
to change the value indicated in the SET DATA section to that you want.
Push the button.
5
Push the button (left side of the
6
button) repeatedly to select another indoor UNIT No. to change.
Repeat steps 4 to 6 to change the indoor unit addresses so as to make each of them unique.
Push the button (left side of the
7
button) to check the changed addresses. If the addresses have been changed
8
correctly, push the button to nish the procedure.
q To change all the indoor unit addresses
using an arbitrary wired remote controller. (The method is available when the addresses have already been set automatically.)
(When communication wirings of 2 or more
refrigerant lines are interconnected for central control)
NOTE
You can change the addresses of indoor units in each refrigerant line using an arbitrary wired remote controller.
* Enter the address check/change mode and change
the addresses.
UNIT No.
R.C. No.
CODE No.
ON / OFF
2
DATA
SET
SETTING
TEMP .
TIMER SET
TIME
1
3
If no number appears on UNIT No., no outdoor unit exists on the line. Push
line following step
(Execute it while the units are stopped.)
1
2
FILTER
CL
SET
TEST
RESET
Cancels the line selection
button and select another
2.
Push and hold the TIME and buttons at the same time for more than 4 seconds. At rst, the line 1 and CODE No. (Address Change) are indicated on the LCD display.
Push (left side of the button) and system address.
buttons repeatedly to select a
66-EN65-EN
Push the button.
AMP Air Conditioning
www.ampair.co.uk | sales@ampair.co.uk
3
• The address of one of the indoor units connected to the selected refrigerant line is indicated on the LCD display and the fan and louvers of the unit are activated.
At first, the current indoor unit address is
displayed in SET DATA.
(No system address is indicated.)
DATA
SET
SETTING
TEMP .
TIMER SET
4 8
Finish
FILTER RESET
TIME
SET CL
TEST
5, 7
Push the TIME / buttons repeatedly
4
CODE No.
UNIT No.
R.C. No.
ON / OFF
Press to nish setting.
to change the value of the indoor unit address in SET DATA. Change the value in SET DATA to that of a new address.
Push the button to conrm the new
5
address on SET DATA. Push the button (left side of the
6
button) repeatedly to select another address to change. Each time you push the button, the indoor unit numbers in a refrigerant line are indicated one after another. Only the fan and louvers of the selected indoor unit are activated.
Repeat steps 4 to 6 to change the indoor unit addresses so as to make each of them unique.
Push the button.
7
(All the segments on the LCD display light up.)
Push the button to nish the procedure.
8
6
Resetting the address
(Resetting to the factory default (address undecided))
Method 1
Clearing each address separately using a wired remote controller. Set the system address, indoor unit address and group address to “0099” using a wired remote controller. (For the setting procedure, refer to the address setting procedures using the wired remote controller on the previous pages.)
Method 2
Clearing all the indoor unit addresses on a refrigerate line at once from the outdoor unit.
Turn off the refrigerant line to reset to the
1
factory default and set the header outdoor unit of the line as below.
1) Disconnect the relay connectors between the [U1, U2] and [U3, U4] terminals.
(Leave them as they are if they have already
been disconnected.)
2) Turn on DIP switch 2 of SW30 on the interface P.C. board of the header outdoor unit if the switch is OFF.
(Leave it as it is if it has already been set to
ON.)
Central control controller
U2
U1
U4
Header unit
U3
U2 U5 U6
U1
U2
U1
A
Remote controller
Turn on the indoor and outdoor units of the refrigerant line for which you want to initialize the
2
Follower unit Follower unit
U1 U2 U5 U6
U1 U2
A
Remote controller
U3 U4
B
U4
B
Header unit
Indoor units to have their addresses initialized
U4
U3
U1 U2 U5 U6
U1 U2
A B
Remote controller
U1 U2 U5 U6
U1 U2
A B
U3
U4
Header unit
U1
U1 U2
U3 U4
U2
Remote controller
U3
U5 U6
B
A
addresses. About one minute after turning on the power, conrm that the 7-segment display on the header outdoor unit indicates “U.1. - - -” and operate the interface P.C. board on the header outdoor unit of the refrigerant line as follows.
SW01 SW02 SW03 SW04 Clearable addresses
212
222
Conrm that the 7-segment display indicates “A.d. c.L.” and set SW01, SW02 and SW03 to 1, 1, 1
3
Conrm that the 7-segment display indicates “A.d.buS” and turn SW04 ON for more than ve seconds.
Conrm that the 7-segment display indicates “A.d.nEt” and turn SW04 ON for more than ve seconds.
System/indoor unit/group address
Central control address
respectively. After a time “U.1.L08” appears on the 7-segment display if the address clearing has been
4
completed successfully. If the 7-segment display indicates “A.d. n.G.”, the outdoor unit may still connected with other refrigerant lines. Check the connection of the relay connectors between [U1, U2] and [U3, U4].
NOTE
Take care to carry out the procedure above correctly; otherwise, addresses in other refrigerate lines may also be cleared.
Set the addresses again after nishing the clearance.
5
– 4 3 –
68-EN67-EN
– 35 –
AMP Air Conditioning
www.ampair.co.uk | sales@ampair.co.uk
Setting when connecting
indoor units to FS (Flow Selector) unit
* 1 : The setting method of Single port type FS unit
(L ong piping model) is same as the one branch of M ulti port type FS unit.
¿ Cautions to connection of indoor
unit
• When connecting the indoor units to a single port type FS unit and a branch of the multi port type FS unit, it is necessary to set up the CODE No..
Be sure to set up the CODE No. after setup of
address.
• When connecting the indoor units to a single port type FS unit and a branch of the multi port type FS unit, it is possible to connect with multiple groups and connect individually.
Single port type FS unit
Control wiring between indoor unit and FS unit (Within 15 m)
Multi port type FS unit (* 1 )
Single port type FS unit
Control wiring between indoor unit and FS unit
Remote controller
Group control
Remote controller
Piping
Piping
Remote controller
Group control
Single port type FS unit
Piping
Piping
Group control
Indoor unit
Indoor unit
Indoor unit
Incorrect
¿ How to set up CODE No. [ 0E ]
It is necessary to set up in case of the group control.
.
2 5
3 4 1
1
Push and hold the , , and buttons at the same time for more than 4 seconds.
is displayed in the UNIT No. window.
• In this time, the fans of all the indoor units in the group control start the fan operation.
Using the set temperature buttons /
2
, select the CODE No. “ ”.
3
Change SET DATA to “ ” by the timer buttons
Push button.
4
Push button. Then the setup nished.
5
¿ How to set up CODE No. [ 1 4 ]
It is necessary to set up group address in case of the group control. 0 : Individual 1 : Header unit 2 : Follower unit
¿ How to set up CODE No. [ FE ]
In cases other than connecting with one indoor unit or one group in one branching, it is necessary to set up.
• As for both single port type and multi port type, set up CODE No. “FE” in one branching within the range of 1~64.
This CODE No. should not be duplicate in one
system.
¿ How to set up CODE No. [ FD ]
In cases other than connecting with one indoor unit or one group in one branching, it is necessary to set up. 0 : Heating prioritized (Factory default) 1 : Cooling prioritized
/ .
q In case of FE/FD without setting
Single port type FS unit
Control wiring between indoor unit and FS unit (Within 15 m)
Multi port type FS unit (* 1 )
Piping
Indoor unit
Remote controller
Group control
Piping
Remote controller
Group control
Indoor unit
q In case of FE/FD with setting
Single port type FS unit
Control wiring between indoor unit and FS unit (Within 15 m)
Multi port type FS unit (* 1 )
Single port type FS unit
Control wiring between indoor unit and FS unit (Within 15 m)
Multi port type FS unit (* 1 )
Piping
Remote controller
Group control
Remote controller
Group control
Remote controller
Group control
Remote controller
Group control
Group control
Piping
Piping
Piping
Indoor unit
Indoor unit
Group control
Indoor unit
Indoor unit
70-EN69-EN
¿ [ Set up example ]
AMP Air Conditioning
www.ampair.co.uk | sales@ampair.co.uk
[ 0E ] : Group setting 0 : Individual (Factory default) 1 : Group
[ 14 ] : Group address
0 : Individual 1 : Header unit 2 : Follower unit
[ FE ] : Branching system address (1~64)
• Should not be duplicate in one system
• Factory default : 99 [ FD ] : Priority operation mode 0 : Heating prioritized (Factory default) 1 : Cooling prioritized (The cooling is
prioritized even if setting only one unit in one branching)
<In case of connecting one group operation of
indoor units>
Single port type FS unit
Control wiring between indoor unit and FS unit (Within 15 m)
[ 0E ] : 1 1 1 [ 14 ] : [ FE ] : It is not necessary to set up [ FD ] : It is not necessary to set up
Multi port type FS unit
Piping
Remote controller
Group control
1
(* 1)
Piping
Indoor unit
2 2
<In case of connecting one group operation of indoor units and two indoor units>
Single port type FS unit
Control wiring between indoor unit and FS unit (Within 15 m)
[ 0E ] : 1 1 0 0 [ 14 ] : 1 [ FE ] : [ FD ] : 0 0 0 0
Multi port type FS unit (* 1)
Piping
Remote controller
Group control
2 0 0
1 1 1 1
Piping
Indoor unit
<Incorrect connection examples>
Incorrect
Single port type FS unit
Single port type FS unit
Control wiring between indoor unit and FS unit (Within 15 m)
Piping
Remote controller
Group control
Incorrect
Multi port type FS unit (* 1)
Piping
Indoor unit
Single port type FS unit
< In case of connecting one indoor unit>
Single port type FS unit
Control wiring between indoor unit and FS unit (Within 15 m)
[ 0E ] : It is not necessary to set up [ 14 ] : It is not necessary to set up [ FE ] : It is not necessary to set up [ FD ] : It is not necessary to set up
Multi port type FS unit (* 1)
[ 0E ] : It is not necessary to set up [ 14 ] : It is not necessary to set up [ FE ] : It is not necessary to set up [ FD ] : It is not necessary to set up
Piping
Piping
Indoor unit
Remote controller
Indoor unit
Remote controller
Indoor unit
Remote controller
[ 0E ] : 1 1 1 [ 14 ] : [ FE ] : It is not necessary to set up [ FD ] : It is not necessary to set up
1
Group control
2 2
<In case of connecting two group operations of
indoor units>
Single port type FS unit
Control wiring between indoor unit and FS unit (Within 15 m)
[ 0E ] : 1 1 1 1 [ 14 ] : 1 1 [ FE ] : [ FD ] : 0 0 0 0
Multi port type FS unit (* 1)
[ 0E ] : 1 1 1 1 [ 14 ] : 1 1 [ FE ] : [ FD ] : 0 0 0 0
Piping
Remote controller
Group control Group control
2 2
1 1 1 1
Piping
Remote controller
Group control Group control
2 2
1 1 1 1
Indoor unit
Indoor unit
Remote controller
[ 0E ] : 1 1 0 0 [ 14 ] : 1 [ FE ] : 1 1 1 1 [ FD ] : 0 0 0 0[ FD ] : 0 0 0 0
Group control
2 0 0
<In case of connecting four indoor units>
Single port type FS unit
Control wiring between indoor unit and FS unit (Within 15 m)
[ 0E ] : 0 0 [ 14 ] : [ FE ] : 1 1 1 1 [ FD ] : 0 0 0 0[ FD ] : 0 0 0 0
Multi port type FS unit
[ 0E ] : 0 0 [ 14 ] : [ FE ] : 1 1 1 1 [ FD ] : 0 0 0 0[ FD ] : 0 0 0 0
Piping
Remote controller
00
(* 1)
Piping
Remote controller
00
– 6 3 –
0 00 0
0 00 0
Indoor unit
Indoor unit
Indoor unit
Remote controller
Incorrect
Multi port type FS unit (* 1)
Piping
Remote controller
Incorrect
Multi port type FS unit
(* 1)
Piping
Remote controller
Group control
Multi port type FS unit (* 1)
Indoor unit
Group control
Indoor unit
Group control
Indoor unit
72-EN71-EN
– 3 7 –
AMP Air Conditioning
www.ampair.co.uk | sales@ampair.co.uk
10How to set up the cooling only indoor unit
When setting the specic indoor unit to Cooling Only unit without connecting to the ow selector unit, setup to the indoor unit to become the Cooling Only unit is necessary. Perform setup in the following procedure.
Setup to the indoor unit is performed by handling the wired remote controller. Even if a wired remote controller is not used, attach a wired remote controller for setup. Change the setup with the wired remote controller before using the air conditioner with a wireless remote controller. Change the setup during stop of the operation. (Be sure to stop operation of the air conditioner.)
DATA
SET
SETTING
No.
4
3
1 6
5 2
1
When pushing + + buttons simultaneously for 4 seconds or more, after a while, the display part ashes as shown in the gure.
Check that the displayed CODE No. is [10].
• If the CODE No. indicates one other than [10],
button to erase the display, and then
push retry the operation from the rst step.
(After pushing
remote controller cannot be accepted after a while.)
button, the operation of
DATA
SET
SETTING
SETTING
UNIT No.
R.C. No.
CODE No.
In a group control, the rstly displayed
2
indoor unit No. becomes the header unit.
Every pushing button), the indoor unit No. in the group control is displayed successively.
Select an indoor unit of which setting is to be changed.
DATA
SET
In this time, the position of the indoor unit of which setup is to be changed can be conrmed because the fan and louver of the selected indoor unit work.
Use and buttons of the set
3
temperature to specify the CODE No. [0F]. Use and buttons of the timer time to
4
select the setup data [0001].
SET DATA 0000 0001
Cooling Only
setup
Push button. In this time, if the display
5
changes from ashing to lighting, the setup completes.
• To change the setup of an indoor unit other than the selected one, start operation from
Procedure
• In a group control, setup change of all the indoor units in a group is necessary.
To change the setup of the set other than
the selected one, start again operation from Procedure
CAUTION
Cooling Only and Heat pump cannot exist in the same group.
button (left side of the
SETTING
SETTING
UNIT No.
R.C. No.
Heat pump Cooling Only
2.
2.
CODE No.
6
When the setup nished, push button. (The setup is determined.)
Pushing button deletes the display and returns to normal stop status. (For some time after the operation of the remote controller cannot be accepted.)
button has been pushed,
(* The display changes according to the indoor unit model.)
• Pushing button clears the set up contents which have been already set.
In this case, retry from Procedure
2.
74-EN73-EN
11 Test run
AMP Air Conditioning
www.ampair.co.uk | sales@ampair.co.uk
Before test run
Conrm that the valve of the refrigerate pipe of the outdoor unit is OPEN.
• Before turning on the power, conrm that the resistance between the terminal block of power supply and the earth is more than 1MΩ using a 500V megohmmeter.
Do not run the unit if it is less than 1MΩ.
CAUTION
• Turn on the power and turn on the case heater of the compressor.
To save the compressor when it is activated, leave
the power on for more than 12 hours.
Methods of test run
¿ When executing a test run using
a remote controller
Operate the system normally to check the running condition using the wired remote controller. Follow the instructions in the supplied owner’s manual when operating the unit. If you use a wireless remote controller for operations, follow the instructions in the installation manual supplied with the indoor unit. To execute a test run forcibly under the condition that the thermostat automatically turns the unit off due to the indoor temperature, follow the procedure below. The forcible test run will automatically stop after 60 minutes to prevent continuous forcible running and return to normal running.
CAUTION
Do not use forcible running except for a test run as it overloads the unit.
TEMP.
ON / OFF
2, 4
TIMER SET
FILTER RESET
TEST
TIME
SET CL
3
1, 5
1
Push and hold the button for more than 4 seconds. TEST appears on the LCD display and the unit enters the trial mode. (TEST is indicated on the LCD display during the test run.)
TEST
Push the button.
2
Push the button to switch the
3
running mode to COOL or HEAT.
NOTE
• Do not run the unit in any mode other than COOL or HEAT.
• You cannot change the temperature setting during the test run.
• Errors are detected as usual.
TEST
Push the button to stop running
4
after nishing the trial run. The indication on the LCD display returns to the status of procedure 1.
5
Push the button to exit the trial mode. (TEST disappears on the LCD display and the status changes to normal stopped mode.).
¿ When executing a test run using
the interface P.C. board on the outdoor unit
You can execute a test run by operating switches on the interface P.C. board of the header outdoor unit. “Individual trial”, which tests each indoor unit separately, and “corrective trial”, which tests all the indoor units connected, are available.
<Individual test operation>
q Starting operation
Set the running mode to “COOL” or
1
“HEAT” on the remote controller of the indoor unit to be tested. (The unit will run in the current mode unless you set the mode otherwise.)
7-segment display
[A] [B]
[U1] [ ]
Set the rotary switches on the interface
2
P.C. board of the header outdoor unit: SW01 to [16], SW02 and SW03 to the address of the indoor unit to be tested.
SW02 SW03 Indoor unit address
1 to 16 1 1 to 16 Set number of SW02 1 to 16 2 17 to 32 Set number of SW02 + 16 1 to 16 3 33 to 48 Set number of SW02 + 32 1 to 16 4 49 to 64 Set number of SW02 + 48
7-segment display
[A] [B]
[ ]
Address display of the corresponding indoor unit
Push and hold SW04 for more than 10
3
seconds.
Address display of the corresponding indoor unit
i
7-segment display
[A] [B]
[ ]
i
[ ]
[ ]
[FF] is displayed for 5 seconds.
i
NOTE
• The running mode follows the mode setting on the remote controller of the target indoor unit.
• You cannot change the temperature setting during the test run.
• Errors are detected as usual.
• The unit does not perform test run for 3 minutes after turning the power on or stopping running.
q Finishing operation
Set the rotary switches on the interface
1
P.C. board of the header unit back: SW01 to [1], SW02 to [1] and SW03 to [1].
7-segment display
[A]
[U1]
[B]
[ ]
– 8 3 –
76-EN75-EN
– 3 9 –
AMP Air Conditioning
www.ampair.co.uk | sales@ampair.co.uk
<Corrective trial>
q Start operation
Set the rotary switches on the interface P.C. board of the header outdoor unit as below.
1
When in “COOL” mode: SW01=[2], SW02=[5], SW03=[1]. When in “HEAT” mode: SW01=[2], SW02=[6], SW03=[1]. When in “FAN” mode: SW01=[2], SW02=[9], SW03=[1].
7-segment display
[A] [C ] [H ] [F ]
Push and hold SW04 for more than 2 seconds.
2
NOTE
• You cannot change the temperature setting during the test run.
• Errors are detected as usual.
• The unit does not perform test run for 3 minutes after turning the power on or stopping running.
7-segment display
[A] [C ] [H ] [F ]
q Stop operation
Set the rotary switches on the interface P.C. board of the header unit back:
1
SW01 to [1], SW02 to [1] and SW03 to [1].
7-segment display
[A]
[U1]
[B] [ ] [ ] [ ]
[B]
[ - C ] [ - H ]
[ - F ]
[B] [ ]
Interface PC board
SW04
Push switch Push switch
7-segment display [A]
SW05 SW15
D600 D601 D602 D603 D604
SW01 SW02
Rotary switches
SW03
7-segment display [B]
78-EN77-EN
12Troubleshooting
AMP Air Conditioning
www.ampair.co.uk | sales@ampair.co.uk
In addition to the CODE No. on the remote controller of an indoor unit, you can diagnose failure type of an outdoor unit by checking the 7-segment display on the interface P.C. board. Use the function for various checks. Set every DIP switch to OFF after checking.
7-Segment display and check code
Rotary switch setting value
SW01 SW02 SW03
1 1 1 Outdoor unit check code
Indication LED
A B Check code display*
* If a check code has an auxiliary code, the display indicates the check code for three seconds and the auxiliary
code for one second alternately.
Check code (indicated on the 7-segment display on the outdoor unit)
Indicated when SW01 = [1], SW02 = [1], and SW03 = [1].
Check code
Auxiliary code
E06 Number of indoor units which received normally Decrease of number of indoor units E07 Indoor/outdoor communication circuit error E08 Duplicated indoor addresses Duplication of indoor addresses.
01: Communication between indoor and outdoor units
E12
02: Communication between outdoor units
E15 No indoor unit during automatic addressing
00: Capacity over
E16
01~: Number of connected units 00: Header is nothing
E19
02: 2 or more header units 01: Other line outdoor connected
E20
02: Other line indoor connected E23 — E25 Duplicated follower outdoor address set up E26 Number of outdoor units which received normally Decrease of connected outdoor units E28 Detected outdoor unit No. Follower outdoor unit error E31 IPDU quantity information E31 80 Communication error between MCU and sub MCU F04 TD1 sensor error F05 TD2 sensor error
01: TE1 sensor
F06
02: TE2 sensor F07 01: TL1 sensor TL1 sensor error F08 TO sensor error
(*1)
Automatic addressing start error
Capacity over / number of connected indoor units
Number of header outdoor unit error
Other lines connected during automatic addressing Communication transmission error between outdoor units
IPDU communication error
TE1 sensor error TE2 sensor error
D600
Outdoor unit number
Check code nameIndication on 7-segment display on the outdoor unit
D601 D602 D603 D604
AB
(U
1 to U3)
Check code
Check code nameIndication on 7-segment display on the outdoor unit
Auxiliary code
01: TS1 sensor
F12
02: TS2 sensor 01: Compressor 1
F13
02: Compressor 2 F15 Outdoor temp. sensor miswiring (TE1, TL1) F16 Outdoor pressure sensor miswiring (Pd, Ps) F23 Ps sensor error F24 Pd sensor error F31 Outdoor EEPROM error
01: Compressor 1
H01
02: Compressor 2
01: Compressor 1
H02
02: Compressor 2
01: Compressor 1
H03
02: Compressor 2 H05 TD1 sensor miswiring H06 Low pressure protective operation
H07 Detected outdoor unit No.
01: TK1 sensor error
02: TK2 sensor error
H08
04: TK4 sensor error
05: TK5 sensor error H15 TD2 sensor miswiring
01: TK1 oil circuit error
02: TK2 oil circuit error
H16
04: TK4 oil circuit error
05: TK5 oil circuit error
J10 Flow selector units overow error
Detected indoor unit address L02 L04 Outdoor L06 Number of prior indoor units Duplication of indoor units with priority L08 Indoor unit group/address unset L10 Outdoor unit capacity unset. L12 01: Flow selector unit(s) installation error Flow selector unit(s) system error L17 L18 Detected indoor unit address Flow selector unit error L23 01: Clean Converter setting error Setting error
01: Duplication of
L24
02: Indoor unit(s) operation mode priority setting L28 Outdoor connected quantity over L29 IPDU number information L30 Detected indoor unit address External interlock of indoor unit L31
Inconsistent models of outdoor units
ow selector unit address
(*1)
TS1 or TS2 sensor error
TH (Heat sink) sensor error
Compressor breaking down
Compressor error (Locked)
Current detection circuit error
Oil level down detection (Indicated only on the header outdoor unit)
Temperature sensor error for oil level
Oil level detector circuit error
Outdoor units model disagreement error
system address duplication
Flow selector unit(s) setting error
IPDU quantity error
Compressor IPDU errors
– 0 4 –
80-EN79-EN
– 4 1 –
AMP Air Conditioning
www.ampair.co.uk | sales@ampair.co.uk
Check code
Check code nameIndication on 7-segment display on the outdoor unit
Auxiliary code
P03 Discharge temperature TD1 error
01: Compressor 1
P04
02: Compressor 2 01: Compressor 1
P05
02: Compressor 2 01: Compressor 1
P07
02: Compressor 2 P10 Detected indoor unit address Indoor overow error P13 Outdoor unit ow back error detected
01: TS condition
P15
02: TD condition P17 Discharge temperature TD2 error P19 Detected outdoor unit number 4-way valve inverse error P20 High-pressure protective operation
#0: Element short circuit
#E: Vdc voltage error
#1: Position detection circuit error
#2: Input current sensor error
#3: Motor lock error
P22
#C: Sensor temperature error (No TH sensor)
#4: Motor current error
#D: Sensor short circuit/release error (No TH sensor)
#5: Synchronization/step-out error
*Put in Fan IPDU No. in [#] mark.
01: Compressor 1
P26
02: Compressor 2
01: Compressor 1
P29
02: Compressor 2
High-pressure SW system operation Compressor Vdc error
AC detection circuit error Heat sink overheat error
Gas leak detection
Outdoor fan IPDU error
IPM short protection error
Compressor position detecting circuit error
13Machine card and logbook
Machine card
After test run, ll the items on the machine card and paste the card on an accessible place on the product securely before delivery to the customer.
Describe the following items on the machine card:
name, address and telephone number of the installer, his service department, the service department of the party concerned or at any addresses and telephone numbers of re department, police, hospitals and burn centres;
Logbook
Update the log periodically after maintenance as dened in EN378-4.
Describe the following items on the logbook:
1. details of the maintenance and repair works;
2. quantities, kind of (new, reused, recycled) refrigerant which have been charged on each occasion, the quantities of refrigerant which have been transferred from the system on each occasion (see also EN378-4);
3. if there is an analysis of a reused refrigerant, the results shall be kept in the logbook;
4. source of the reused refrigerant;
5. changes and replacements of components of the system;
6. result of all periodic routine tests;
7. significant periods of non-use.
*1 IPDU number information
01: Compressor 1 error 02: Compressor 2 error 03: Compressor 1 and 2 error 08: Fan 1 error 09: Compressor 1, Fan 1 error 0A: Compressor 2, Fan 1 error 0B: Compressor 1 and 2, Fan 1 error
82-EN81-EN
SMMS wave tool
AMP Air Conditioning
www.ampair.co.uk | sales@ampair.co.uk
“SMMS wave tool” is an application software (“Application”) for the Android OS smartphone and for those who install and do maintenance to the compatible air conditioning equipment. The Application enables checks of some of the system and data and test operations of compatible air conditioning equipment. Please check the information about compatible air conditioning equipment and smartphone from the below URL. Be sure to read the Operating Manual before the use of this Application, “SMMS wave tool”. You can download the Application and the Operating Manual from the below URL or QR code. QR code is a trademark or registered trademark of DENSO WAVE Inc.Android is a trademark or registered trademark of Google Inc. URL : http://www.toshiba-carrier.co.jp/global/appli/smms_wave_tool/
NOTICE
• This Application enables the auto-address setup and the test operation of the outdoor unit by smartphone in 48 hours from the power input to the outdoor unit.
• You should decide whether to make use of this auto-address setup and test operation function at its own responsibility and also be sure to conrm notices in the Operating Manual before performing the test operation.
• If you want to disable the function of the auto-address setup and the test operation, perform the following operations.
• Refer to the service manual for setting change of the auto-address setup and the test operation function to be effective.
Switch setting of some functions prohibition
Step
(1) 2 1 14 - [ nf ] [ c.00 ] Setting preparation (2) 2 1 14 Press for more than 5 secs [ nf ] [ c.01 ] Setting completion (3) 1 1 1 - [ U.1. ] [ - - - ] Return the switch
* Do it again if the 7-segment display is different from the above. * The functions other than the auto-address setup and test operation of this Application can work normally even if
the auto-address set up and test operation function are disabled.
CAUTION
• High voltage parts exist in the electrical control box.
If you set Switch setting, set it from the access door cover of the electrical control box cover to avoid electric
shock.
• After finishing operations, slide the access door cover to the position before and fix it with the screw.
Access door cover
HOW TO USE
• This Application uses the NFC (Near Field Communication) function of smartphone.
• For the use, hold your smartphone to the “TOUCH” mark of the outdoor unit.
• Refer to the Operating Manual of the “SMMS wave tool” for the details.
Rotary switch Push switch 7-segment display
SW01 SW02 SW03 SW04 [ A ] [ B ]
Cover of the electrical control box
Fixing screw for the access door cover
Push switch
7-segment display [A]
Outdoor unit
SW04
D600 D601 D602 D603 D604
SW01 SW02
Rotary switches
NFC receiver for SMMS wave tool
SW05 SW15
SW03
QR code
Condition
7-segment display [B]
Smartphone
WARNINGS ON REFRIGERANT LEAKAGE
Check of Concentration Limit
The room in which the air conditioner is to be installed requires a design that in the event of refrigerant gas leaking out, its concentration will not exceed a set limit.
The refrigerant R410A which is used in the air conditioner is safe, without the toxicity or combustibility of ammonia, and is not restricted by laws to be imposed which protect the ozone layer. However, since it contains more than air, it poses the risk of suffocation if its concentration should rise excessively. Suffocation from leakage of R410A is almost non-existent. With the recent increase in the number of high concentration buildings, however, the installation of multi air conditioner systems is on the increase because of the need for effective use of oor space, individual control, energy conservation by curtailing heat and carrying power etc. Most importantly, the multi air conditioner system is able to replenish a large amount of refrigerant compared with conventional individual air conditioners. If a single unit of the multi conditioner system is to be installed in a small room, select a suitable model and installation procedure so that if the refrigerant accidentally leaks out, its concentration does not reach the limit (and in the event of an emergency, measures can be made before injury can occur). In a room where the concentration may exceed the limit, create an opening with adjacent rooms, or install mechanical ventilation combined with a gas leak detection device. The concentration is as given below.
Total amount of refrigerant (kg)
Min. volume of the indoor unit installed room (m
Concentration limit (kg/m
The concentration limit of R410A which is used in multi air conditioners is 0.3kg/m
NOTE 1 :
If there are 2 or more refrigerating systems in a single refrigerating device, the amounts of refrigerant should be as charged in each independent device.
e.g., charged amount (10kg)
Room A Room B Room C Room D Room E Room F
For the amount of charge in this example:
The possible amount of leaked refrigerant gas in rooms A, B and C is 10kg. The possible amount of leaked refrigerant gas in rooms D, E and F is 15kg.
3
.
e.g., charged amount (15kg)
3
Outdoor unit
Indoor unit
3
)
)
Important
NOTE 2 :
The standards for minimum room volume are as follows. (1) No partition (shaded portion)
(2) When there is an effective opening with the adjacent
room for ventilation of leaking refrigerant gas (opening without a door, or an opening 0.15% or larger than the respective oor spaces at the top or bottom of the door).
(3) If an indoor unit is installed in each partitioned
room and the refrigerant piping is interconnected, the smallest room of course becomes the object. But when a mechanical ventilation is installed interlocked with a gas leakage detector in the smallest room where the density limit is exceeded, the volume of the next smallest room becomes the object.
Very small room
Small
Medium
room
Mechanical ventilation device - Gas leak detector
NOTE 3 :
The minimum indoor oor area compared with the amount of refrigerant is roughly as follows: (When the ceiling is 2.7m high).
40
Range below the
2
35
m
density limit of
0.3 kg/m
30
(countermeasures not needed)
25 20 15 10
5
Min. indoor oor area
0
room
3
10 20 30
Total amount of refrigerant kg
Outdoor unit
Refrigerant piping
Refrigerant piping
Large room
Range above the density limit of
3
0.3 kg/m (countermeasures needed)
Indoor unit
Outdoor unit
Indoor unit
– 2 4 –
84-EN83-EN
AMP Air Conditioning
www.ampair.co.uk | sales@ampair.co.uk
144 / 9 Moo 5, Bangkadi Industrial Park, Tivanon Road, Tambol Bangkadi, Amphur Muang, Pathumthani 12000, Thailand
1117701501
Loading...