Toshiba MMD-AP0481HFE, MMD-AP0721HFE, MMD-AP0961HFE DATA BOOK

Engineering Data
Fresh Air Intake
Indoor Unit Type
Tentative
Indoor Unit
MMD-AP0481HFE MMD-AP0721HFE MMD-AP0961HFE
Contents
1. System summary
2. Specifications
3. Dimensions
5. Electrical current characteristics
6. Wiring diagrams
7. Fan characteristics
8. Sound characteristics (NC Curve)
1. System summary
Fresh Air Intake Indoor Unit Type
1. Outline of fresh air intake unit
• Type: Concealed Duct High Static Pressure type
Three models (5HP, 8HP, 10HP) are prepared.
• Connectable outdoor unit
Three series (MMY-MAPXXXXT8, MAPXXXXHT8, MAPXXXXHT7) of Cooling/Heating selecting Super module multi type outdoor unit.
• Corresponding system
Corresponds to a system in which there are the fresh air intake units and the indoor air conditioners. (For the fresh air intake units, up to 2 units for one system and also within 30% to capacity of the connectable indoor air conditioners are allowed.)
• Definition
The fresh air intake unit means an air controller for taken-in fresh air. Intake of the fresh air often influences on the system so that the normal control of the air conditioner becomes difficult or gives a large load upon air controller and cooling performance. Therefore it is frequently adopted to handle the fresh air to a certain condition before the fresh air will enter in the main air conditioner. This handling device is called a fresh air intake unit.
NOTE:
The Fresh Air Intake unit is an air conditioner provided to handle the fresh air load and is not to control the room temperature. For correspondence to the load of the indoor air controller, set an air conditioner separately.
22
1. System summary
Fresh Air Intake Indoor Unit Type
2. System able to be combined
The fresh air intake unit is connectable to S-MMS (Super Modular Multi system). However this is not connectable to S-HRM (Super Heat Recovery Multi system).
0.5m or less
80 to 100% to capacity of the outdoor
Keep the height difference between the fresh air intake units to 0.5m or less.
Up to two fresh air intake units occupy 30% or less
· The fresh air intake unit is usually used together with the indoor units on one line of the multi system.
The fresh air intake unit only cannot be connected.
· The total capacity of the indoor units and the fresh air intake units is restricted to 80% to 100%
against the capacity of the outdoor units. (This restriction should be strictly kept for correct control of the refrigerant.)
· Up to two fresh air intake units can be connected on one line of the multi system.
The allowable total capacity of the two fresh air intake units shall be 30% or less against the total capacity of the indoor units (including the fresh air intake units).
Connection which stretches over two floors is unavailable
Height difference:
0.5m or more
33
1. System summary
Fresh Air Intake Indoor Unit Type
3. Use Conditions
· In COOL mode, if temperature of the fresh air is under the setup temp. +3°C, FAN status is
automatically made. When temperature of the fresh air is under 19°C, FAN status is also made regardless of the setup temperature.
· In HEAT mode, if temperature of the fresh air is over the setup temp. -3°C, FAN status is
automatically made. When temperature of the fresh air is over 15°C, FAN status is also made regardless of the setup temperature.
• Operable mode and discharge temp setup range
Operation mode
COOL
HEAT
• Special mentions
1. The fan operation of the Fresh Air Intake unit stops during defrosting. However the fan operation is enabled to continue by selection.
2. When a central controller is used, divide zone setup of indoor air conditioner and fresh air intake unit.
3. The standard is to control the discharge temperature. However the priority is given to the capacity control for the indoor air conditioner in a system in which the normal indoor air conditioner concurrently operated.
4. The fresh air intake unit cannot be connected with remote controller group of the indoor air conditioner.
5. In heating operation, if the temperature is below –5°C, the operation stops automatically. (FAN stop) (To protect the refrigerant cycle)
6. In cooling operation, if the temperature is below 5°C, the operation stops automatically. (FAN stop)
At shipment from factory Setup range
18°C 16 to 27°C
25°C 16 to 27°C
44
2. Specifications
Fresh Air Intake Indoor Unit Type
50Hz
Model name
Cooling/Heating capacity (Note 1) (kW)
Electical
characteristics
Outer
dimension
Total weight
Heat exchanger
Soundproof / Heat-insulating material
Fan unit
Air filter
Controller
Connecting pipe
Sound pressure level (Note 2) (dB(A))
(High/Med./Low)
Sound power level (High/Med./Low) (dB(A))
Operation range
Power supply
Running current (A)
Power consumption (kW)
Starting current (A)
Main unit Height (mm)
Width (mm)
Depth (mm)
Main unit (kg)
Fan
Standard air flow (m3/h)
Motor (W)
External static pressure
(factory setting)
External static pressure
Air flow limit (m3/h)
Lower limit/Upper limit
Gas pipe (mm)
Liquid pipe (mm)
Drain pipe
Cooling (Note 3) (°C)
Heating (Note 4) (°C)
MMD-AP0481HFE MMD-AP0721HFE MMD-AP0961HFE
14.0/8.9 22.4/13.9 28.0/17.4
1 phase 50Hz 230V (220-240V)
1.43 2.52 2.73
0.28 0.45 0.52
3.50 7.00 7.00
492
892 1,392
1,262
93 144
Finned tube
Non-flammable insulation
Centrifugal fan
1,080 1,680 2,100
160 160 x 2
210 165 190
170-210-230 140-165-180 160-190-205
756 1,176 1,470
Option or field supply
Wired remote controller
15.9 22.2
9.5 12.7
R1
45/43/41 46/45/44
65/63/61 66/65/64
5 - 43
-5 - 43
* The setting temperature is 16 - 27°C(standard FCU…18 - 29°C). * An option humidifier is not available with Fresh Air Intake Indoor unit. * Height difference between Fresh Air Intake Indoor units must be within 0.5m.
Height difference between Fresh Air Intake Indoor unit and standard FCU must be within 30m.
Note 1: Rated conditions Cooling : Outdoor air temperature 33°C DB/28°C WB setting temperature 18°C
Heating : Outdoor air temperature 0°C DB/-2.9°C WB setting temperature 18°C Piping : Length 7.5m / Height 0m
Note 2: The sound level are measured in an anechoic chamber in accordance with JIS B8616. Normally, the
values meausured in the actual operating environment become large than the indicated values due to the effects of external sound.
Note 3: * When supply air temperature is “setting temperature + 3°C” or less, Fresh Air Intake unit operates as
FAN mode.
* When supply air temperature is 19°C or less, Fresh Air Intake Indoor unit operates as FAN mode.
Note 4: * When supply air temperature is “setting temperature - 3°C” or over, Fresh Air Intake unit operates as
FAN mode.
55
2. Specifications
Fresh Air Intake Indoor Unit Type
Model name
Cooling/Heating capacity (Note 1) (kW)
Electical
characteristics
Outer
dimension
dimension
Total weight
Heat exchanger
Soundproof / Heat-insulating material
Fan unit
Air filter
Controller
Connecting pipe
Sound pressure level (Note 2) (dB(A))
(High/Med./Low)
Sound power level (High/Med./Low) (dB(A))
Operation range
Power supply
Running current (A)
Power consumption (kW)
Starting current (A)
Main unit
Main unit (kg)
Fan
Standard air flow (m3/h)
Motor (W)
External static pressure
(factory setting)
External static pressure
Air flow limit (m3/h)
Lower limit/Upper limit
Gas pipe (mm)
Liquid pipe (mm)
Drain pipe
Cooling (Note 3) (°C)
Heating (Note 4) (°C)
Height (mm)
Width (mm)
Depth (mm)
60Hz
MMD-AP0481HFE MMD-AP0721HFE MMD-AP0961HFE
14.0/8.9 22.4/13.9 28.0/17.4
1 phase 60Hz 220V
1.66 2.75 3.12
0.34 0.55 0.65
3.40 6.80 6.80
492
892 1,392
1,262
93 144
Finned tube
Non-flammable insulation
Centrifugal fan
1,080 1,680 2,100
160 160 x 2
215 210 180
115-215-260 150-210-235 80-180-220
1,188 1,848 2,310
Option or field supply
Wired remote controller
15.9 22.2
9.5 12.7
R1
45/43/41 46/45/44
65/63/61 66/65/64
5 - 43
-5 - 43
* The setting temperature is 16 - 27°C(standard FCU…18 - 29°C). * An option humidifier is not available with Fresh Air Intake Indoor unit. * Height difference between Fresh Air Intake Indoor units must be within 0.5m.
Height difference between Fresh Air Intake Indoor unit and standard FCU must be within 30m.
Note 1: Rated conditions Cooling : Outdoor air temperature 33°C DB/28°C WB setting temperature 18°C
Heating : Outdoor air temperature 0°C DB/-2.9°C WB setting temperature 18°C Piping : Length 7.5m / Height 0m
Note 2: The sound level are measured in an anechoic chamber in accordance with JIS B8616. Normally, the
values meausured in the actual operating environment become large than the indicated values due to the effects of external sound.
Note 3: * When supply air temperature is “setting temperature + 3°C” or less, Fresh Air Intake unit operates as
FAN mode.
* When supply air temperature is 19°C or less, Fresh Air Intake Indoor unit operates as FAN mode.
Note 4: * When supply air temperature is “setting temperature - 3°C” or over, Fresh Air Intake unit operates as
FAN mode.
66
Loading...
+ 13 hidden pages