Toshiba MMD-AP0181SPH, MMD-AP0071SH-C, MMD-AP0091SPH, MMD-AP0151SPH, MMD-AP0121SPH DATA BOOK

...
FILE NO. A05-006
SERVICE MANUAL
<Slim Duct Type>
MMD-AP0071SPH (-C, -K), MMD-AP0091SPH (-C, -K), MMD-AP0121SPH (-C, -K), MMD-AP0151SPH (-C, -K), MMD-AP0181SPH (-C, -K),
MMD-AP0071SH-C, MMD-AP0091SH-C, MMD-AP0121SH-C, MMD-AP0151SH-C, MMD-AP0181SH-C,
PRINTED IN JAPAN, Jul.,2005 ToMo
CONTENTS
SAFETY CAUTION ............................................................................................ 3
1. CONSTRUCTION VIEWS (EXTERNAL VIEWS) ........................................ 8
2. WIRING DIAGRAM..................................................................................... 9
3. PARTS RATING........................................................................................ 10
4. FAN CHARACTERISTICS........................................................................ 50
5. REFRIGERANTING CYCLE DIAGRAM................................................... 52
6. CONTROL OUTLINE................................................................................ 53
7. APPLIED CONTROL................................................................................ 57
8. TROUBLESHOOTING .............................................................................. 62
9. CONFIGURATION OF CONTROL CIRCUIT .......................................... 113
10. DETACHMENTS ..................................................................................... 118
11. P.C. BOARD EXCHANGE PROCEDURES ............................................ 123
12. EXPLODED VIEWS AND PARTS LIST .................................................. 128
2
SAFETY CAUTION
The important contents concerned to the safety are described on the product itself and on this Service Manual. Please read this Service Manual after understanding the described items thoroughly in the following contents,
and keep them.
WARNING
Before troubleshooting or repair work, check the earth wire is connected to the earth terminals of the main unit, otherwise an electric shock is caused when a leak occurs.
Check earth wires.
Prohibition of modification.
Use specified parts.
Do not bring a child
close to the equipment.
Insulating measures
No fire
If the earth wire is not correctly connected, contact an electric engineer for rework.
Do not modify the products.
Do not also disassemble or modify the parts. It may cause a fire, electric shock or injury.
For spare parts, use those specified (
If unspecified parts are used, a fire or electric shock may be caused. : For details, refer to the parts list.
Before troubleshooting or repair work, do not bring a third party (a child, etc.) except the repair engineers close to the equipment.
It causes an injury with tools or disassembled parts. Please inform the users so that the third party (a child, etc.) does not approach the equipment.
Connect the cut-off lead cables with crimp contact, etc, put the closed end side upward and then apply a water-cut method, otherwise a leak or production of fire is caused at the users’ side.
When repairing the refrigerating cycle, take the following measures.
1) Be attentive to fire around the cycle. When using a gas stove, etc, be sure to put out fire before work; otherwise the oil mixed with refrigerant gas may catch fire.
2) Do not use a welder in the closed room. When using it without ventilation, carbon monoxide poisoning may be caused.
3) Do not bring inflammables close to the refrigerant cycle, otherwise fire of the welder may catch the inflammables.
∗∗
∗).
∗∗
Refrigerant
Check the used refrigerant name and use tools and materials of the parts which match with it.
For the products which use R410A refrigerant, the refrigerant name is indicated at a position on the outdoor unit where is easy to see. To prevent miss-charging, the route of the service por t is changed from one of the former R22.
For an air conditioner which uses R410A, never use other refrigerant than R410A. For an air conditioner which uses other refrigerant (R22, etc.), never use R410A.
If different types of refrigerant are mixed, abnormal high pressure generates in the refriger­ating cycle and an injury due to breakage may be caused.
Do not charge refrigerant additionally.
If charging refrigerant additionally when refrigerant gas leaks, the refrigerant composition in the refrigerating cycle changes resulted in change of air conditioner characteristics or refrigerant over the specified standard amount is charged and an abnormal high pressure is applied to the inside of the refrigerating cycle resulted in cause of breakage or injury. Therefore if the refrigerant gas leaks, recover the refrigerant in the air conditioner, execute vacuuming, and then newly recharge the specified amount of liquid refrigerant. In this time, never charge the refrigerant over the specified amount.
When recharging the refrigerant in the refrigerating cycle, do not mix the refrigerant or air other than R410A into the specified refrigerant.
If air or others is mixed with the refrigerant, abnormal high pressure generates in the refrigerating cycle resulted in cause of injury due to breakage.
After installation work, check the refrigerant gas does not leak.
If the refrigerant gas leaks in the room, poisonous gas generates when gas touches to fire such as fan heater, stove or cocking stove though the refrigerant gas itself is innocuous.
Never recover the refrigerant into the outdoor unit.
When the equipment is moved or repaired, be sure to recover the refr igerant with recover­ing device. The refrigerant cannot be recovered in the outdoor unit; otherwise a serious accident such as breakage or injury is caused.
3
Assembly/Cabling
Insulator check
Ventilation
Be attentive to
electric shock
Compulsion
WARNING
After repair work, surely assemble the disassembled parts, and connect and lead the removed cables as before. Perform the work so that the cabinet or panel does not catch the inner cables.
If incorrect assembly or incorrect cable connection was done, a disaster such as a leak or fire is caused at user’s side.
After the work has finished, be sure to use an insulation tester set (500V mugger) to check the resistance is 2MW or more between the charge section and the non-charge metal section (Earth position).
If the resistance value is low, a disaster such as a leak or electric shock is caused at user’s side.
When the refrigerant gas leaks during work, execute ventilation.
If the refrigerant gas touches to a fire, poisonous gas generates. A case of leakage of the refrigerant and the closed room full with gas is dangerous because a shortage of oxygen occurs. Be sure to execute ventilation.
When checking the circuit inevitably under condition of the power-ON, use rubber gloves and others not to touch to the charging section.
If touching to the charging section, an electric shock may be caused.
When the refrigerant gas leaks, find up the leaked position and repair it surely.
If the leaked position cannot be found up and the repair work is interrupted, pump-down and tighten the service valve, otherwise the refrigerant gas may leak into the room. The poisonous gas generates when gas touches to fire such as fan heater, stove or cocking stove though the refrigerant gas itself is innocuous.
When installing equipment which includes a large amount of charged refrigerant such as a multi air conditioner in a sub-room, it is necessar y that the density does not the limit even if the refrigerant leaks.
If the refrigerant leaks and exceeds the limit density, an accident of shortage of oxygen is caused.
For the installation/moving/reinstallation work, follow to the Installation Manual.
If an incorrect installation is done, a trouble of the refrigerating cycle, water leak, electric shock or fire is caused.
Check after rerair
Check after reinstallation
Put on gloves
Cooling check
After repair work has finished, check there is no trouble.
If check is not executed, a fire, electric shock or injury may be caused. For a check, turn off the power breaker.
After repair work (installation of front panel and cabinet) has finished, execute a test run to check there is no generation of smoke or abnormal sound.
If check is not executed, a fire or an electric shock is caused. Before test run, install the front panel and cabinet.
Check the following items after reinstallation.
1) The earth wire is correctly connected.
2) The power cord is not caught in the product.
3) There is no inclination or unsteadiness and the installation is stable. If check is not executed, a fire, an electric shock or an injury is caused.
CAUTION
Be sure to put on gloves (
If not putting on gloves, an injury may be caused with the parts, etc. () Heavy gloves such as work gloves
When the power was turned on, start to work after the equipment has been sufficiently cooled.
As temperature of the compressor pipes and others became high due to cooling/heating operation, a burn may be caused.
∗∗
) during repair work.
∗∗
4
New Refrigerant (R410A)
This air conditioner adopts a new HFC type refrigerant (R410A) which does not deplete the ozone layer.
1. Safety Caution Concerned to New Refrigerant
The pressure of R410A is high 1.6 times of that of the former refrigerant (R22). Accompanied with change of refrigerant, the refrigerating oil has been also changed. Therefore, be sure that water, dust, the former refriger­ant or the former refrigerating oil is not mixed into the refrigerating cycle of the air conditioner with new refriger­ant during installation work or service work. If an incorrect work or incorrect service is performed, there is a possibility to cause a serious accident. Use the tools and materials exclusive to R410A to purpose a safe work.
2. Cautions on Installation/Service
(1) Do not mix the other refrigerant or refrigerating oil.
For the tools exclusive to R410A, shapes of all the joints including the service port differ from those of the former refrigerant in order to prevent mixture of them.
(2) As the use pressure of the new refrigerant is high, use material thickness of the pipe and tools which are
specified for R410A.
(3) In the installation time, use clean pipe materials and work with great attention so that water and others do
not mix in because pipes are affected by impurities such as water, oxide scales, oil, etc. Use the clean pipes.
Be sure to brazing with flowing nitrogen gas. (Never use gas other than nitrogen gas.) (4) For the earth protection, use a vacuum pump f or air purge. (5) R410A refrigerant is azeotropic mixture type refrigerant. Theref ore use liquid type to charge the refrigerant.
(If using gas for charging, composition of the refrigerant changes and then characteristics of the air condi-
tioner change.)
3. Pipe Materials
For the refrigerant pipes, copper pipe and joints are mainly used. It is necessary to select the most appropriate pipes to conform to the standard. Use clean material in which impurities adhere inside of pipe or joint to a minimum.
(1) Copper pipe
<Piping>
The pipe thickness, flare finishing size, flare nut and others differ according to a refrigerant type. When using a long copper pipe for R410A, it is recommended to select “Copper or copper-base pipe without
seam” and one with bonded oil amount 40mg/10m or less. Also do not use crushed, deformed, discolored (especially inside) pipes. (Impurities cause clogging of expansion valves and capillary tubes.)
<Flare nut>
Use the flare nuts which are attached to the air conditioner unit.
(2) Joint
The flare joint and socket joint are used for joints of the copper pipe.
The joints are rarely used for installation of the air conditioner. How ever clear impurities when using them.
5
4. Tools
(1) Required Tools for R410A
Mixing of different types of oil may cause a trouble such as generation of sludge, clogging of capillary, etc.
Accordingly, the tools to be used are classified into the following three types.
1) Tools exclusive for R410A (Those which cannot be used for conventional refrigerant (R22))
2) Tools exclusive for R410A, but can be also used for conventional refrigerant (R22)
3) Tools commonly used for R410A and for conventional refrigerant (R22)
The table below shows the tools exclusive for R410A and their interchangeability.
Tools exclusive for R410A (The following tools for R410A are required.)
Tools whose specifications are changed for R410A and their interchangeability
Conventional air
conditioner installation
Whether new equipment can be used with conventional refrigerant
Yes
*(Note 1)
No
No
Yes
Yes
No
Yes
No
No.
Q
R
S
T
U
V
W
X
Y
Y
Used tool
Flare tool Copper pipe gauge for
adjusting projection margin
Torque wrench
Gauge manifold Charge hose
Vacuum pump adapter Electronic balance for
refrigerant charging Refrigerant cylinder Leakage detector Charging cylinder
Usage
Pipe flaring
Flaring by conventional flare tool
Connection of flare nut
Evacuating, refrigerant charge, run check, etc.
Vacuum evacuating
Refrigerant charge Refrigerant charge
Gas leakage check Refrigerant charge
air conditioner installation
Existence of new equipment for R410A
Yes
Yes
Yes
Yes
Yes
Yes Yes
Yes
(Note 2)
R410A
Whether conven­tional equipment can be used
*(Note 1)
*(Note 1)
No
No
No
Yes
No No No
(Note 1) When flaring is carried out for R410A using the conventional flare tools, adjustment of projection
margin is necessary. For this adjustment, a copper pipe gauge , etc. are necessary.
(Note 2) Charging cylinder for R410A is being currently dev eloped.
General tools (Conventional tools can be used.)
In addition to the above exclusive tools, the following equipments which serve also for R22 are necessary as the general tools.
(1) Vacuum pump
Use vacuum pump b y
attaching vacuum pump adapter. (2) Torque wrench (3) Pipe cutter (4) Reamer
(7) Screwdriver (+, –) (8) Spanner or Monkey wrench (9) Hole core drill (10) Hexagon wrench (Opposite side 4mm) (11) Tape measure (12) Metal saw
(5) Pipe bender (6) Level vial
Also prepare the following equipments for other installation method and run check. (1) Clamp meter (2) Thermometer
(3) IInsulation resistance tester (4) Electroscope
6
5. Recharge of Refrigerant
VLV
H
Connected to indoor unit
Main pipe
Valve fully closed (gas side)
Center unit
Low-
pressure gauge
High-
pressure gauge
Gauge manifold
Brazed
Service port
Service port
Ø6.4
Copper pipe
Ø6.4 Copper pipe
Fully tightened
Fully tightened
Reducing valve
Nitrogen
gas
Valve fully closed (liquid side)
Valve fully closed (balance)
Connected to other terminal units
When recharge of the refrigerant is required, charge the new refrigerant with the specified amount in the procedure as described below .
Recover the refrigerant and check there is no refrigerant in the equipment.
Connect the charge hose to the packed valve service ports at gas side, liquid side, and balance side of the outdoor unit.
Connect the charge hose to vacuum pump adaptor.
Leave it as it is for 1 to 2 minutes and check the indicator of the compound gauge does not return.
Set the refrigerant cylinder on the electron balance, connect the charge hose to connecting ports of the cylinder and the electron gauge, and then charge the liquid refrigerant from the service port at liquid side. (Shield with the gauge manifold so that refrigerant does not flow to gas side.)
Open the packed valves of the balance pipe fully at liquid and gas sides, and then return the valve at gas side a little to the closed side.
Open fully PMV of the outdoor unit.
• Turn on power of the outdoor unit.
• Short CN30 on I/F P.C. board of the outdoor unit.
Turn off power of the outdoor unit within 2 minutes after short-circuiting.
Open fully the handle Low of the gauge manifold, and then turn on the power of vacuum pump for vacuuming.
When the pressure has lowered until indication of the compound gauge pointed -0.1MPa (-76cmHg), open fully the handle Low and turn off the power of vacuum pump.
Never charge the refrigerant ov er the specified amount.
Q
Do not charge the additional refrigerant.
R
If charging refrigerant additionally when refrigerant gas leaks, the refrigerant composition in the refrigerating cycle changes resulted in change of air conditioner characteristics or refrigerant over the specified stan­dard amount is charged and an abnormal high pressure is applied to the inside of the refrigerating
cycle resulted in cause of breakage or injury.
(Charge the refrigerant as below.)
4mm-hexagonal wrench is required.
6. Environment
Use “Vacuum pump method” for an air purge (Discharge of air in the connecting pipe) in installation time.
• Do not discharge flon gas into the air to protect the earth environment.
• Using the vacuum pump method, clear the remained air (Nitrogen, etc.) in the unit. If the air remains, the
Set the equipment so that liquid refrigerant can be charged.
Q
When using a cylinder with siphon pipe, liquid can be charged without inversing the cylinder.
R
[ Cylinder with siphon ] [ Cylinder without siphon ]
Refrigerant
cylinder
Electronic
balance
Gauge manifold
OUTDOOR unit
Electronic
balance
Gauge manifold
cylinder
Refrigerant
OUTDOOR unit
Siphon
R410A refrigerant is consisted with HFC mixed refrigerant. Therefore if the refrigerant gas is charged, the composition of the charged refrigerant changes and characteristics of
pressure in the refrigerating cycle becomes abnormally high and an injury and others are caused due to burst.
the equipment changes.
7
1. CONSTRUCTION VIEWS (EXTERNAL VIEWS)
MMD-AP0071SPH(-K), AP0091SPH(-K), AP0121SPH(-K), AP0151SPH(-K), AP0181SPH(-K)
21
845
57
Ø92
59
80
Fresh air inlet (knock-out hole)
168
4-Ø4
80
(inside)
21
21
20
19
168
120
Air filter
805
910
210
21803 (inside)
67
511
645
67
Refrigerant piping
103
31
33
163
372
502
422
359
40
Drain-up port
Hung-up plate
MMD-AP0071SPH-C, AP0091SPH-C, AP0121SPH-C, AP0151SPH-C, AP0181SPH-C, MMD-AP0071SH-C, AP0091SH-C, AP0121SH-C, AP0151SH-C, AP0181SH-C
845
57
210
168(inside)
Ø92
Fresh air inlet (knock-out hole)
21
21 21
20
19
4-Ø4
168
146 80
120
5980
803 (inside)
805 910
21
Natural drain port
67
511
67
Hang-up plate
645
Refrigerant piping
103
31
33
163
Drain-up port (SPH model only)
359
40
372
422
502
8
9
Flow
Selector unit
Earth screw
indication
RED : RED WHI : WHITE YEL : YELLOW BLU : BLUE BLK : BLACK GRY : GRAY PNK : PINK ORN : ORANGE BRN : BRWN GRN : GREEN
Closed-end
connector
Indoor unit
Earth screw
Color
WHI
RED
220-240V~, 50Hz
R(L) S(N)
Power supply 220V~, 60Hz
Non Drain pump type ("SH" T ype)
CN68 (BLU)
1
3
Drain pump type ("SPH" T ype)
DM
U1 U2
RED
WHI
CN44
(BRW)
CN68 (BLU)
1
1
3
BLK
A B
2. WIRING DIAGRAM
MMD-AP0071SPH(SH), AP0091SPH(SH), AP0121SPH(SH), AP0151SPH(SH), AP0181SPH(SH)
Non Drain pump type
PMV
FM
1
2
3
4
6 6
CN333
5
3
(WHI)
54 3
32 1
circuit
CN309
(YEL)
1. indicates the terminal bolock. Letter at inside indicates the terminal number.
2. A dotted line and broken line indicate the wiring at side
Fuse T3.15A 250V~
CN50 (WHI)
1 2 3 4 5
1 2 3 4 5 6 1
BLU
CN41 (BLU)
1 233
BLK
CN334 (WHI)
BLK
1 1
Motor drive
31
5 4 1 5
RY302
313
1
CN304
(GRY)
3
Fuse T6.3A 250V~
1
3
CN67 (BLK)
P301
1
CN66 (WHI)
2 1
CN40 (BLU)
2
11221
BLU
3. indicate a control P.C. board.
5
4
2
3
3
Power supply circuit
1
4
(External static pressure setup)
2
5
CN82
1 2
(BLU)
1 2
5 3
6
CN112
(WHI)
DC20V DC15V DC12V DC7V
CN61 (YEL)
1 2 3 4 5 6
1 2
CN111
CN110
(WHI)
Control P.C. board
for undoor unit
CN32 (WHI)
1 2
1 2 3 4 5 6
Fan drive
1 2 1 2
(WHI)
MCC-1402
CN60 (WHI)
Option
Symbol
FM TA TC1,TC2,TCJ RY302 PMV DM FS
("SH" T ype)
1 3 1 2 3
CN33 (WHI)
4 5
CN71
(CHK)
CN72
(DISP)
CN81 (BLK)
1 2 3 4 5
Parts name
Fan motor Indoor temp sensor Temp sensor Drain control relay Pulse motor valve Drain pump motor Float switch
Drain pump type ("SPH" T ype)
CN34 (RED)
CN20
(BLU)
1 2 3 4 5
1 3 1 2 3
CN104
(YEL)
CN102
(RED)
CN101
(BLK)
CN100
(BRW)
CN80
(GRN)
CN73
(RED)
CN70 (WHI)
FS
CN34 (RED)
212
212
1 2
131
1 2 3
1 2
1 2
1
1
1 2
3
PNL
EXCT
TA
TCJ
TC2
TC1
U1 U2
Outdoor unit
A B
Wired remote controller

3. PARTS RATING

3-1. Parts Rating
Model MMD-
Fan motor Pulse motor Pulse motor valve Drain pump motor Float switch TA sensor TC1 sensor TC2 sensor TCJ sensor
“SPH” series only
AP0071SPH AP0091SPH AP0121SPH AP0151SPH AP0181SPH
SWF-280-60-1
EDM-MD12TF-3
EDM-B25YGTF EDM-B40YGTF
ADP-1409
FS-0218-102
Lead wire length : 1558mm Vinyl tube Ø4 size lead wire length : 1200mm Vinyl tube (Blue) Ø6 size lead wire length : 1200mm Vinyl tube (Black) Ø6 size lead wire length : 1200mm Vinyl tube (Red)
3-2. Name of Each Part
Air inlet
Suction duct is connected.
Air filter
(Air filter is not provided to some models in the series.)
Earth screw
It is included in the electric parts box.
Air outlet
Discharge duct is connected.
10
3-3. Parts Name of Remote Controller
ON / OFF
Display section
In the display example, all indicators are displayed for the explanation. In reality only, the selected contents are indicated.
• When turning on the leak breaker at the first time, [SET DATA] flashes on the display part of the remote controller. While this display is flashing, the model is being automatically confirmed. Accordingly, wait for a while after [SET DATA] display has disappeared, and then use the remote controller.
78 9
2
1 4
3 5
SET
H
DATA
SETTING
TEST
UNIT No.
R.C. No.
CODE No.
6
15
1
SET DATA display
Displayed during setup of the timer.
2
Operation mode select display
The selected operation mode is displayed.
3
CHECK display
Displayed while the protective device works or a trouble occurs.
4
Timer time display
Time of the timer is displayed. (When a trouble occurs, the check code is dis­played.)
5
Timer SETIN setup display
When pushing the Timer SETIN button, the display of the timer is selected in order of [OFF]
[OFF] repeat OFF timer → [ON] No display.
6
Filter display
If “FILTER ” is displayed, clean the air filter.
7
TEST run display
Displayed during a test run.
8
Flap position display (for 4-Way Air Discharge Cassette T ype and Under Ceiling Type model only)
Displays flap position.
9
SWING display
Displayed during up/down movement of the flap.
10
Set up temperature display
The selected set up temp. is displayed.
11
Remote controller sensor display
Displayed while the sensor of the remote controller is used.
12
PRE-HEAT display
Displayed when the heating operation starts or defrost operation is carried out.
While this indication is displayed, the indoor fan stops or the mode enters in LOW.
13
Operation ready display
Displayed when cooling or heating operation is impossible because the outdoor temperature goes out of the operable range.
14
No function display
Displayed if there is no function even if the button is pushed.
15
Air volume select display
The selected air volume mode is displayed. (AUTO) (MED.) (LOW)
In the Concealed Duct High Static Pressure type models, [HIGH] only is displayed for the air speed.
16
Mode select control display
Displayed when pushing “Operation mode select
” button while the operation mode is fixed to heating or cooling by the system manager of the air conditioner.
17
Central control display
Displayed when using the remote controller to­gether with the central control remote controller, etc. If Remote controller is prohibited at the centralcontrol side,
the change is not accepted. (The contents available to be set up on the remote controller differ according to the central control mode. For details, refer to Owner’s Manual of the central control remote controller.)
CODE No.
ON / OFF
FAN
MODE
SWING/FIXTIME
VENT
UNITSET CL
Display section
Operation section
FILTER RESET
SET
DATA
H
TEMP.
TEST
SETTING
TEST
TIMER SET
UNIT No.
R.C. No.
17
10
16
11
13
12
14
(HIGH)
flashes when operating
MODE
,
, / buttons and
11
Operation section
ON / OFF
Push each button to select a desired operation.
• The details of the operation needs to be set up once, afterward, the air conditioner can be used by pushing
ON / OFF
button only.
1
7
TEMP.
10
2
FIL TER
TEST
RESET
5 3
1
Air volume select button
Selects the desired air volume mode. The Concealed Duct High Static Pressure type
models cannot be operated.
2
Timer set button
TIMER SET button is used when the timer is set up.
3
Check button
The CHECK button is used for the check opera­tion. During normal operation, do not use this button.
4
Fan button
FAN button is used when a fan which is sold on the market or etc. is connected.
• If is displayed on the remote controller when pushing the FAN button, a fan is not connected.
TIMER SET
ON / OFF
8
FAN
SWING/FIXTIME
MODE
VENT
9 4
UNITSET CL
6
7
Operation lamp
Lamp is lit during the operation. Lamp is off when stopped.
Although it flashes when operating the protection device or abnormal time.
8
When the button is pushed, the operation starts, and it stops by pushing the button again.
When the operation has stopped, the operation lamp and all the displays disappear.
9
Operation select button
Selects desired operation mode.
10
Set up temperature button
Adjusts the room temperature. Set the desired set temperature by pushing
button
or .
5
Filter reset button
Resets (Erases) “FILTER ” display.
6
Wind direction and Swing
UNIT
:
If the multiple indoor units are operated by only one remote controller, select the units when the air direction is adjusted.
SWING/FIX
:
Set up the auto swing and angle of the flap.
• This function is not provided to Concealed Duct Standard Type, High Static Pressure Type, Floor standing Cabinet Type, Floor Standing Concealed Type, or Slim Duct Type.
OPTION :
Remote controller sensor
UUsually the TEMP. sensor of the indoor unit senses the temperature. The temperature on the surround­ing of the remote controller can also be sensed. For details, contact the dealer from which y ou have purchased the air conditioner.
• In case that one remote controller controls the multiple indoor units, the setup operation is unavailab le in g roup control.
12
3-4. Correct Usage
LOW MED. HIGH
AUTO
When you use the air conditioner for the first time or when you change the SET DATA value, follow the proce­dure below. From the next time, the operation displayed on the remote controller will start by pushing the
ON / OFF
Preparation
Turn on the main power switch and/or the leakage breaker.
• When the power supply is turned on, a partition line is displayed on the display part of the remote controller . * After the power supply is turned on, the remote controller does not accept an operation for approx. 1 minute,
but it is not a f ailure.
• While using the air conditioner, operate it only with
button only.
switch and the leak breaker.
REQUIREMENT
ON / OFF
button without turning off the main power
TEMP.
ON / OFF
1
4
TIMER SET
FIL TER
TEST
RESET
1
Push
The operation lamp goes on, and the operation starts.
2
Select an operation mode with the “MODE” button.
One push of the button, and the display changes in the order shown on the right.
• In HEAT mode, if the room temperature reaches to the set temperature, the outdoor unit stops and the air flow becomes LOW and the air volume decreases.
• In the defrost mode, the fan stops so that cool air is not discharged and PRE-DEF is displayed.
3
Select air volume with “ ” button.
One push of the button, and the display changes in the order shown on the right.
ON / OFF
button.
FAN
SWING/FIXTIME
UNITSET CL
MODE
VENT
DRY COOL FAN
HEAT DRY COOL FAN
3
2
Cooling only model
Heat-pump model
(Dehumidity)
• When air volume is “AUTO ”, air volume differs according to the temperature difference between set temp. and room temp.
• In DRY mode, “AUTO ” is displayed and the air volume is LOW .
• In heating operation, if the room temperature is not heated sufficiently with VOLUME “LOW ” operation, select “MED. ” or “HIGH ” operation.
4
Determine the set up temperature by pushing the “TEMP. TEMP. ” or “TEMP. ” button.
Stop
Push
The operation lamp goes off, and the operation stops.
ON / OFF
button.
13
3-5. Automatic Operation (Super Heat Recovery Type Only)
When you set the air conditioner in mode or switch over from AUTO operation because of some settings change, it will automatically select either cooling, heating, or fan only operation depending on the indoor tem­perature.
TEMP.
ON / OFF
1
3
FIL TER RESET
TIMER SET
TEST
FAN
SWING/FIXTIME
UNITSET CL
Start
ON / OFF
1
Push this button to start the air conditioner.
2
Mode select button (MODE)
Select Auto.
3
Temperature button
Set the desired temperature.
• In case of cooling, start the operation after approx. 1 minute.
• In case of heating, the operation mode is selected in accordance with the room temperature and operation starts after approximately 3 to 5 minutes.
• When you select the Auto mode, it is unnecessary to set the fan speed. The FAN speed display will show AUTO and the fan speed will be automatically controlled.
• After the heating operation has stopped, FAN operation may continue for approx. 30 seconds.
• When the room temperature reaches the set temperature and the outdoor unit stops, the super low wind is discharged and the air volume decreases excessively . During defrost operation, the fan stops so that cool air is not discharged and “HEAT READY” is displayed.
• If the Auto mode is uncomfortable, y ou can select the desired conditions manually.
button
MODE
VENT
2
NOTE
When restarting the operation after stop
• When restarting the operation immediately after stop, the air conditioner does not operate for approx. 3 minutes to protect the machine.
Stop
Push
Push this button again to stop the air conditioner.
ON / OFF
button.
14
3-6. TIMER Operation
OFF
(OFF timer) (Repeat OFF timer)
No display
(ON timer)
OFF ON
A type of timer operation can be selected from the following three types . OFF timer : The operation stops when the time of timer has reached the set time. Repeat OFF timer : Every time, the operation stops after the set time has passed. ON timer : The operation starts when the time of timer has reached the set time.
Timer operation
1
FIL TER RESET
1
Push TIMER SET button.
• The timer display (type) changes for every
push of the button.
• SET TIME and timer time displays flash.
2
Push
TIME
to select “SET TIME”.
TEMP.
TEST
TIMER SET
3
4
ON / OFF
FAN
SWING/FIXTIME
UNITSET CL
MODE
VENT
2
For every push of button, the set time increases in the unit of 0.5 hr (30 minutes). The maximum set time is 72.0 hr. For every push of button, the set time decreases in the unit of 0.5 hr (30 minutes). The minimum set time is 0.5 hr.
3
Push SET button.
display disappears and timer time display goes on.
SETTING
(When ON timer is activated, timer time, ON timer are displayed and other displays disappear.)
Cancel of timer operation
4
Push CL button.
• TIMER display disappears.
NOTICE
• When the operation stops after the timer reached the preset time, the Repeat OFF timer resumes the operation by pushing set time.
ON / OFF
button and stops the operation after the time of the timer has reached the
15
3-7. Information
Confirmation before operation
• Turn on the power switch 12 hours before starting the operation.
• Make sure whether earth wire is connected.
• Make sure the air filter is connected to the indoor unit.
Heating capacity
• A heat pump system which absorbs heat from outside of the room and then discharges heat into the room is adopted for heating. If the outside temperature falls, the heating capacity decreases .
• When the outside temperature is too low, it is recommended to use this air conditioner together with other heating equipment.
Defrost during heating operation
• In heating operation, if there is frost on the outdoor unit, the operation changes automatically to the defrost operation (Approx. 2 to 10 minutes) to increase the heating efficiency.
• During defrost operation, the fan of the indoor unit stops.
3-minutes protection
Protective device (High pressure switch)
This device stops automatically an operation when excessive force is applied on the air conditioner.
If the protective device works , the operation stops and the operation lamp flashes.
When the protective device w orks, the indication and the check code are displayed on the display
section of the remote controller. In the following cases, the protective device may work.
In cooling operation
• The suction port or discharge port of the outdoor unit is closed.
• A strong wind continuously blows to the discharge port of the outdoor unit.
In heating operation
• Dust or waste adheres excessively to air filter of the indoor unit.
• The discharge port of the indoor unit is closed.
If the protective device works, turn off the main power switch, solve the cause, and then start the operation again.
TEST
• When restarting the operation just after the operation has been stopped or the main power switch has turned on, the outdoor unit does not work for approx. 3 minutes in order to protect the air conditioner.
Power failure
• If a power failure occurred during operation, all operations stop.
• When the power is returned after a power failure, the operation lamp notifies the power-ON by flashing operation lamp on the remote controller.
• When restarting the operation, push button again.
ON / OFF
Fan rotation in stopped unit
• In heating operation even in the stopped indoor unit, the fan rotates once for several minutes per approx. an hour when the other indoor unit is operating to protect the air conditioner.
Cooling/Heating operation of Super Modular Multi system air conditioner
• Although each indoor unit can be individually controlled in the Super Modular Multi system air conditioner, the cooling oper ation and the heating operation cannot be simultaneously performed in the multiple indoor units which are connected to an outdoor unit.
• If the cooling operation and the heating operation are simultaneously performed, the indoor unit
which executes cooling operation stops, and on the operation section lights up. On the other hand, the indoor unit which executes heating operation continues running. In a case that the manager of the air conditioner has fixed the operation to cooling or heating, an operation other than that set up is unavailab le. If an operation other than that
set up is executed, on the operation section lights up and the operation stops.
Characteristics of heating operation
• The wind is not out just after starting an operation. The hot wind starts to blow 3 to 5 minutes after (Time differs according to indoor/outdoor tempera­ture.) the indoor heat exchanger has warmed up.
• During operation, the outdoor unit may stop if the outside temperature rises.
16
3-8. Air Conditioner Operations and Performance
3 minutes protection function
3-minutes protection function prevents the air conditioner from starting for initial 3 minutes after the main power switch/circuit breaker is turned on f or re-starting the air conditioner .
Power failure
P o wer failure during operation will stop the unit completely.
• To restart the operation, push the START/STOP button on the remote controller.
• Lightning or a wireless car telephone operating nearby may cause the unit to malfunction. Turn off the main power switch or circuit breaker and then turn them on again. Push the START/STOP button on the remote controller to restart.
Heating characteristics Preheating operation
The air conditioner will not deliver warm air immediately after it is turned on. Warm air will start to flow out after approximately 5 minutes when the indoor heat exchanger warmed up.
Warm air control (In heating operation)
When the room temperature reaches the set temperature, the fan speed is automatically reduced to prevent to blow cold draft. At this time, the outdoor unit will stop.
Defrosting operation
If the outdoor unit is frosted during the heating operation, defrosting starts automatically (for approximately 2 to 10 minutes) to maintain the heating capacity.
• The fans in both indoor and outdoor units will stop during the defrosting operation.
• During the defrosting operation, the defrosted water will be drained from the bottom plate of the outdoor unit.
Heating capacity
In the heating operation, the heat is absorbed from the outside and brought into the room. This way of heating is called heat pump system. When the outside temperature is too low, it is recommended to use another heating apparatus in combination with the air conditioner.
Attention to snowfall and freeze on the outdoor unit
• In snowy areas, the air inlet and air outlet of the outdoor unit are often covered with snow or froz en up. If snow or freeze on the outdoor unit is left as it is, it may cause machine failure or poor warming.
• In cold areas, pay attention to the drain hose so that it perfectly drains water without water remaining inside for freeze prevention. If water freezes in the drain hose or inside the outdoor unit, it may cause machine failure or poor warming.
Air conditioner operating conditions
For proper performance, operate the air conditioner under the following temperature conditions:
Cooling operation
Dry operation
Outdoor temperature : –5°C to 43°C (Dry valve temp.) Room temperature : 21°C to 32°C (Dry valve temp.), 15°C to 24°C (Wet valve temp.)
CAUTION
Outdoor temperature : 15°C to 21°C (Dry valve temp.), –15°C to 15.5°C (Wet valve temp.) Room temperature : 15°C to 28°C (Dry valve temp.)
Room relative humidity – less than 80 %. If the air conditioner operates in excess of this figure, the surface of the air conditioner may cause dewing.
If air conditioner is used outside of the above conditions, safety protection may work.
17
3-9. When the Following Symptoms are Found
Check the points described below before asking repair servicing.
Symptom
Outdoor unit • White misty cold air
or water is out.
• Sometimes, noise “Pushu !” is heard.
Indoor unit •“Swish” sound is
heard sometimes.
• Slight “Pishi!” sound is heard.
• Discharge air smells.
• The operation lamp flashes
•“STANDBY” indication is lit.
Check again.
• Sound or cool air is output from the stand by indoor unit.
• When power of the air conditioner is turned on, “Ticktock” sound is heard.
Cause
• Fan of the outdoor unit stops automatically and performs defrost operation.
• Solenoid valve works when defrost operation starts or finishes.
• When the operation has started, dur ing the operation, or immediately after the operation has stopped, a sound such as water flows may be heard, and the operation sound may become larger for 2 or 3 minutes immediately after the operation has started. They are flowing sound of refrigerant or draining sound of dehumidifier.
• This is sound generated when heat exchanger, etc. expand and contract slightly due to change of temperature.
• Various smell such as one of wall, carpet, clothes, cigarette, or cosmetics adhere to the air conditioner.
• Flashes when power is turned on again after power failure, or when power switch is turned on.
• When cooling operation cannot be performed because another indoor unit performs heating operation.
• When the manager of the air conditioner has fixed the operation to COOL or HEAT, and an operation contrary to the setup operation is performed.
• When fan operation stopped to prevent discharge of hot air.
• Since refrigerant is flowed temporarily to prevent stay of oil or refrigerant in the stand by indoor unit, sound of flowing refrigerant, “Kyururu” or “Shaa” may be heard or white steam when other indoor unit operates in HEAT mode, and cold air in COOL mode may be blow-out.
• Sound is generated when the expansion valve operates when power has been turned on.
Operates or stops automatically. Does not operate.
Silent
Air is not cooled or warmed sufficiently.
It is not a failure.
It’s strange.
• Is the timer “ON” or “OFF”?
• Is it a power failure?
• Is the power switch turned off?
• Is the power fuse or breaker blown?
• Has the protective device operated? (The operation lamp goes on.)
• Is the timer “ON”? (The operation lamp goes on.)
• Are COOL and HEAT selected simultaneously? (“STANDBY” indica­tion is lit on the display column of the remote controller.)
• Is the suction port or discharge port of the outdoor unit obstructed?
• Are any door or window open?
• Is the air filter clogged with dust?
• Is discharge louver of the indoor unit set at appropriate position?
• Is air selection set to “LOW” “MED”, and is the operation mode set to “FAN”?
• Is the setup temp. the appropr iate temperature?
• Are COOL and HEAT selected simultaneously? (“STANDBY” indica­tion is lit on the display column of the remote controller.)
When the following symptoms are found, stop the operation immediately, turn off the power switch, and contact the dealer which you have purchased the air conditioner.
• Activation of switch is unstable.
• Fuse or breaker is blown periodically.
• Foreign matters or water entered by mistake.
• When if activation cause of the protective device has been removed, the operation is not performed.
• Other unusual status occurred.
18
Accessory parts
3-10. Installation Manual
19
H Accessory parts
Part name
Installation Manual
Insulating pipe
Washer
Hose band
Flexible hose
Heat insulator
1
PRECAUTIONS FOR SAFETY
• Ensure that all Local, National and International regulations are satisfied.
• Read this “PRECAUTIONS FOR SAFETY” carefully before Installation.
• The precautions described below include the important items regarding safety. Observe them without fail.
• After the installation work, perform a trial operation to check for any problem. Follow the Owner’s Manual to explain how to use and maintain the unit to the customer.
• Turn off the main power supply switch (or breaker) before the unit maintenance.
• Ask the customer to keep the Installation Manual together with the Owner’s Manual.
Q’ty
1
2
8
1
1
1
CAUTION New Refrigerant Air Conditioner Installation
• THIS AIR CONDITIONER ADOPTS THE NEW HFC REFRIGERANT (R410A) WHICH DOES NOT
DESTROY OZONE LAYER.
The characteristics of R410A refrigerant are ; easy to absorb water, oxidizing membrane or oil, and its pressure is approx. 1.6 times higher than that of refrigerant R22. Accompanied with the new refrigerant, refrigerating oil has also been changed. Therefore, during installation work, be sure that water, dust, former refrigerant, or refrigerating oil does not enter the refrigerating cycle.
To prevent charging an incorrect refrigerant and refrigerating oil, the sizes of connecting sections of charging port of the main unit and installation tools are charged from those for the conventional refrigerant.
Accordingly the exclusive tools are required for the new refrigerant (R410A). For connecting pipes, use new and clean piping designed for R410A, and please care so that water or
dust does not enter. Moreover, do not use the existing piping because there are problems with pressure­resistance force and impurity in it.
Shape
This manual
M10 × Ø34
——
Usage
(Be sure to hand over to customers)
For insulating pipe connecting section
For hanging down the unit
For connecting drain pipe
For adjustment of drain pipe centering
For insulating drain connecting section
CAUTION To Disconnect the Appliance from Main Power Supply.
This appliance must be connected to the main power supply by means of a switch with a contact separation of at least 3 mm.
WARNING
• Ask an authorized dealer or qualified installation professional to install/maintain the air conditioner.
Inappropriate installation may result in water leakage, electric shock or fire.
• Turn off the main power supply switch or breaker before attempting any electrical work.
Make sure all power switches are off. Failure to do so may cause electric shock.
• Connect the connecting wire correctly.
If the connecting wire is connected in a wrong way, electric parts may be damaged.
• When moving the air conditioner for the installation into another place, be very careful not to enter any gaseous matter other than the specified refrigerant into the refrigeration cycle.
If air or any other gas is mixed in the refrigerant, the gas pressure in the refrigeration cycle becomes abnormally high and it as a result causes pipe burst and injuries on persons.
• Do not modify this unit by removing any of the safety guards or by by-passing any of the safety interlock switches.
• Exposure of unit to water or other moisture before installation may cause a short-circuit of electrical parts.
Do not store it in a wet basement or expose to rain or water.
• After unpacking the unit, examine it carefully if there are possible damage.
• Do not install in a place that might increase the vibration of the unit.
• To avoid personal injury (with sharp edges), be careful when handling parts.
• Perform installation work properly according to the Installation Manual.
Inappropriate installation may result in water leakage, electric shock or fire.
• When the air conditioner is installed in a small room, provide appropriate measures to ensure that the concentration of refrigerant leakage occur in the room does not exceed the critical level.
• Install the air conditioner securely in a location where the base can sustain the weight adequately.
• Perform the specified installation work to guard against an earthquake.
If the air conditioner is not installed appropriately, accidents may occur due to the falling unit.
• If refrigerant gas has leaked during the installation work, ventilate the room immediately.
If the leaked refrigerant gas comes in contact with fire, noxious gas may generate.
• After the installation work, confirm that refrigerant gas does not leak.
If refrigerant gas leaks into the room and flows near a fire source, such as a cooking range, noxious gas might generate.
• Electrical work must be performed by a qualified electrician in accordance with the Installation Manual. Make sure the air conditioner uses an exclusive power supply.
An insufficient power supply capacity or inappropriate installation may cause fire.
• Use the specified wires for wiring connect the terminals securely fix. To prevent external forces applied to the terminals from affecting the terminals.
• Conform to the regulations of the local electric company when wiring the power supply.
Inappropriate grounding may cause electric shock.
• Do not install the air conditioner in a location subject to a risk of exposure to a combustible gas.
If a combustible gas leaks, and stays around the unit, a fire may occur.
“SPH” series
2
INSTALLATION OF NEW REFRIGERANT AIR CONDITIONER
3
SELECTION OF INSTALLATION PLACE
20
This air conditioner adopts the new HFC refrigerant (R410A) which does not deplete the ozone layer.
• R410A refrigerant is apt to be affected by impurity such as water, oxidizing membrane, or oils because the pressure of R410A refrigerant is higher than that of the former refrigerant by approx. 1.6 times. Accompanied with adoption of the new refrigerant, refrigerating oil has been also changed. Therefore pay attention so that water, dust, former refrigerant, or refrigerating oil does not enter into the refrigerating cycle of the new refrigerant air conditioner during installation work.
• To prevent from mixing of refrigerant or refrigerating oil, the size of charge port of the main unit or connecting section of installation tool differs from that of the air conditioner for the former refrigerant. Accordingly the exclusive tools are required for the new refrigerant (R410A) as shown below.
• For connecting pipes, use the new and clean piping materials so that water or dust does not enter.
Required tools and cautions on handling
It is necessary to prepare the tools and parts as described below for the installation work. The tools and parts which will be newly prepared in the following items should be restricted to the exclusive use.
Explanation of symbols
: Newly prepared (It is necessary to use it properly exclusive to R410A separated from those for R22 or R407C.)
l
¡ : Former tool is available.
Used tools
Gauge manifold Charging hose Charging cylinder Gas leak detector Vacuum pump Vacuum pump with counter-
flow preventive adapter Flare tool Bender Refrigerant recovery device Torque wrench Pipe cutter Refrigerant cylinder
Welding machine/ Nitrogen gas cylinder
Refrigerant charging balance
Usage
Vacuuming or charging of refrigerant and operation check
Charges refrigerant Checks gas leak Vacuum drying Vacuum drying
Flare processing of pipes Bending processing of pipes Recovers refrigerant Tightens flare nut Cuts pipes Charges refrigerant
Welding of pipes
Charges refrigerant
Newly prepared, Exclusive to R410A
l
Newly prepared, Exclusive to R410A
l
Unusable (Use the Refrigerant charging balance.)
Newly prepared
l
Usable if a counter-flow preventive adapter is attached
: R22 (Existing article)
¡
: Usable by adjusting size
¡
: R22 (Existing article)
¡
Exclusive to R410A
l
Ø12.7mm, Exclusive for Ø15.9mm
l
: R22 (Existing article)
¡
Exclusive to R410A
l
ID : Refrigerant name entered
: R22 (Existing article)
¡
: R22 (Existing article)
¡
Proper use of tools/parts
WARNING
• Install the air conditioner where there is sufficient strength to weight of the unit.
If strength is insufficient, the unit may fall down resulting in human injury.
• Perform a specified installation work to guard against an earth quake.
An incomplete installation can cause accidents by the units failing and dropping.
• Install the air conditioner at a height 2.5m or more from the floor.
If you insert your hands or others directly into the unit while the air conditioner operates, it is dangerous because you may contact with revolving fan or active electricity.
CAUTION
• Do not install the air conditioner in a location subject to a risk of exposure to combustible gas.
Should the combustible gas leak and collect near the unit, fire may occur.
Upon approval of the customer, install the air conditioner in a place that satisfies the following conditions.
• Place where the unit can be installed horizontally.
• Place where a sufficient servicing space can be ensured for safe maintenance and check.
• Place where drained water will not cause any problem.
Avoid installing in the following places.
• Place exposed to air with high salt content (seaside area), or place exposed to large quantities of sulfide gas (hot spring). (Should the unit be used in these places, special protective measures are needed.)
• Place exposed to oil, vapor, oil smoke or corrosive gas.
• Place where organic solvent is used nearby.
• Place close to a machine generating high frequency.
• Place near door or window where may come to contact with the fresh air of high humidity. (Dewing may be caused.)
• Place where special spray is frequently used.
• Place with poor ventilation.
Installation under high-humidity atmosphere
In some cases including the rainy season, especially inside of the ceiling may become high-humidity atmosphere (dew-point temperature: 23°C or higher).
1. Installation to inside of the ceiling with tiles on the roof
2. Installation to inside of the ceiling with slated roof
3. Installation to a place where inside of the ceiling is used for pathway to intake the fresh air
• In the above cases, additionally attach the heat insulator to all positions of the air conditioner, which come to contact with the high-humidity atmosphere. In this case, arrange the side plate (Check port) so that it is easily removed.
• Apply also a sufficient heat insulation to the duct and connecting part of the duct.
[Reference] Dewing test conditions
Indoor side: 27°C dry bulb temperature
24°C wet bulb temperature
Air volume: Low air volume, operation time 4 hours
“SPH” series
3
Remove the filter from the main unit while pushing down on the tabs.
Force
Air filter
Main unit
Remove the cover plate and then fix it to the bottom surface.
Main unit
(after remover)
Air filter
Do surely hooking to the main unit.
SELECTION OF INSTALLATION PLACE
21
Installation space
Reserve space required for maintenance the indoor unit and service work.
Air outlet
100 or more
250
or more
<Under air inlet> <Back air inlet>
5 or more
235
210
or more
Ceiling
Air inlet
2500 or more
Floor surface
50 or more
Ceiling
Service space
Air outlet
Ceiling
50
945
50
Service door (Ceiling opening)
645
5 or more 210
235 or more
Air inlet
300 or more
Floor surface
645
(Unit : mm)
5 or more 210
2500 or more
235 or more
Arranging the to back air inlet type
<Back air inlet>
Notification of filter cleaning term setup
The lighting term setup of the filter sign (Notification of filter cleaning) of the remote controller can be changed according to the condition of installation.
For setup method, refer to “Change of lighting term of filter sign” and “To secure better effect of heating” in the Applicable controls of this Manual.
945
Service door (Ceiling opening)
945
745
645
745
Air filter
In case of wireless type
The sensor of indoor unit with wireless remote controller can receive a signal 8m or less.
Based upon it, determine a place where the remote controller is operated and the installation place of the indoor unit.
• To prevent a malfunction, select a place where is not influenced by a florescent light or direct sunlight.
• Two or more (Up to 6 units) indoor units with wireless remote controller can be installed in the same room.
“SPH” series
8m or less
4
Anchor bolt
(Blade type
bracket)
(Slide type
bracket)
(Pipe hanging
anchor bolt)
Reinforcing steel
Hanging bolt
Hanging bolt Support angle

INSTALLATION OF INDOOR UNIT

22
WARNING
Install the air conditioner certainly to sufficiently withstand the weight. If the strength is insufficient, the unit may fall down resulting in human injury. Perform a specified installation work to guard against strong wind or earthquake. An incomplete installation can cause accidents by the units falling and dropping.
REQUIREMENT
Strictly comply with the following rules to prevent damage of the indoor units and human injury.
• Do not put a heavy article on the indoor unit. (Even units are packaged)
• Carry in the indoor unit as it is packaged if possible. If carrying in the indoor unit unpacked by necessity, be sure to use buffering cloth, etc. to not damage the unit.
• To move the indoor unit, hold the hooking metals (4 positions) only. Do not apply force to the other parts (refrigerant pipe, drain pan, foamed parts, or resin parts, etc.).
• Carry the package by two or more persons, and do not bundle it with PP band at positions other than specified.
External view
845
21
57
Ø92
80
Fresh air inlet (knock-out hole)
168
(inside)
21
21
20
19
4-Ø4
168
80
120
59
803 (inside)
Air filter
805 910
21
210
103
67
511
645
67
Hung-up plate
Refrigerant piping
31
33
163
Drain-up port
Opening hole on ceiling and placing of hanging bolt
• Considering the indoor unit and the hanged-up piping/wiring work, determine the installation position and direction.
• After installation position of the indoor unit has been determined, open a hole on the wiring and place the hanging bolt.
• For opening size of the ceiling and the hanging bolt pitch, see the external view.
• When the ceiling has already boarded, draw the drain pipe, refrigerant pipe, inter-unit wire between indoor and outdoor units, central control system wire, and remote controller wire up to the position where pipes and wires are connected before hanged-up the indoor unit.
The hanging bolts and nuts will be procured locally.
Hanging bolt
Nut
M10 or W3/8 M10 or W3/8
4 pieces
12 pieces
Installation of hanging bolt
Use M10 hanging bolts (4 pcs, to be local procure). Matching to the existing structure, set pitch according to size in the unit external view as shown below.
New concrete slab
Install the bolts with insert brackets or anchor bolts.
Installation of indoor unit
• Attach the nuts (M10 or W3/8: Procured locally) and the attached washers (Ø34) to the hanging bolt.
• Put washers at up and down of T-groove of the hanging bracket of the indoor unit to hang down the indoor unit.
• Using a level vial, check that four sides are
372
502
422
359
40
horizontal. (Horizontal degree: Within 5mm)
Steel flame structure
Use existing angles or install new support angles.
Hanging bolt (W3/8 or M10)
Nut (W3/8 or M10)
Nut (W3/8 or M10)
(1)Required those other than M10 flat washer at site. (2)To prevent falling-off of bolt (safety), be sure to set it
just under the hanging bracket as shown in the figure.
Existing concrete slab
Use a hole-in anchors, hole-in plugs, or a hole-in bolts.
(1) M10 flat washer (Accessory)
(2) M10 flat washer (Accessory)
“SPH” series
5
Rising up
687mm or less
Rising up 850mm or less
300mm or less
Indoor unit
Underneath of ceiling

DRAIN PIPING WORK

23
CAUTION
• Following the Installation Manual, perform the drain piping work so that water is properly drained, and apply a heat insulation so as not to cause a dew. Inappropriate piping work may result in water leakage in the room and wet of furniture.
Pipe material/Insulator and size
The following materials for piping work and insulating process are procured locally.
Hard vinyl chloride pipe socket for VP25
Pipe material
Insulator
Hard vinyl chloride pipe VP25 (Nominal outer diameter Ø32mm)
Foamed polyethylene foam, thickness: 10mm or more
REQUIREMENT
• Be sure to perform heat insulation of the drain pipes of the indoor unit.
• Never forget to perform heat insulation of the connecting part with the indoor unit. An incomplete heat insulation causes dewing.
• Set the drain pipe with downward slope (1/100 or more), and do not make swelling or trap on the piping. It may cause an abnormal sound.
• For length of the traversing drain pipe, restrict to 20m or less. In case of a long pipe, provide support brackets with interval of
1.5 to 2m in order to prevent waving.
• Set the collective piping as shown in the right figure.
• Do not mount an air purge pipe, otherwise drain water spouts out resulted in water leak.
(Collective pipes)
• The hard vinyl-chloride pipe cannot be directly connected to the drain pipe connecting port of
As long as possible (100mm or more)
VP25
VP30 or more
the indoor unit. For connection with the drain pipe connecting port, be sure to fix the attached flexible hose.
• Adhesive agent cannot be used for the pipe connecting port (hard socket) of the indoor unit.
Drain pipe connecting port (Hard socket)
Align the attached hose band to the end of hose, set the tightening position upward, and then tighten it.
Be sure to use the attached hose band for fixing, otherwise damage or water leakage of the drain pipe connecting port is caused.
Soft socket Hard socket
Indoor unit
Adhesive agent prohibited
VP25
1.5m to 2m
Heat insulator
Arched shape
Tra p
Downward slope 1/100 or more
Support bracket
1/100 or more downward
NO
GOOD
VP25
Ø25 vinyl chloride pipe (Local supply)
Socket for VP25 (Local supply)
Connection of flexible hose
• Insert the soft socket of the attached flexible hose into the connecting port of the drain pipe until it strikes against the end.
• Align the attached hose band to the end of the pipe connecting port, and then tighten it surely.
Connection of drain pipe
• Connect the hard socket (local supply) to the hard socket side of the attached flexible hose which has been installed.
• Connect the drain pipes (local supply) successively to the connected the hard socket.
REQUIREMENT
• Using adhesive agent for vinyl chloride, connect
the hard vinyl chloride pipes certainly so that water does not leak.
• It requires several times to dry and harden the
adhesive agent. (Refer to Guide Manual of the adhesive agent.) In this time, be sure not to apply force to the connecting section with the drain pipes.
Drain up
When a downward grading cannot be secured on the drain pipe, a drain-up work is possible.
• Set the height of the drain pipe within 850mm from the bottom surface of the indoor unit.
• Draw out the drain pipe within 300mm from the end of the drain pipe connecting port of the indoor unit, and then raise it vertically.
• After the drain pipe has been raised, set a grading so that it is immediately bent downward.
Check the draining
After drain piping work, check that water drain is properly performed and water does not leak from the connecting part of the pipes. In this time, check also there is no abnormal sound of the motor of the drain pump. Be sure to check draining when installed in the heating period.
When the electric work has finished:
• Pour water as shown in the following figure, check water is drained from the drain pipe connecting port in COOL mode, and then check there is no water leak from the drain pipes.
When the electric work has not finished:
• Pull out the float switch connector (3P: Red) from P.C. board connector (CN34: Red) of the electric parts box. (In this time, be sure to check the power is turned off.)
• Connect the single-phase 220-240V 50Hz (or 220V 60Hz) power to the terminal blocks R (L) and S (N). (Never apply 220-240V to (A), (B), (U1),and (U2), otherwise a trouble of P.C. board occurs.)
• Pour water referring to the figure. (Amount: 1500cc to 2000cc)
• When the power is turned on, the drain pump motor drives automatically.
Check water is drained from the drain pipe connecting port, and then check there is no water leak from the drain pipes.
• After check of draining and water leak, turn off the power supply, attach the float switch connector to the original position (CN34) of P.C. board, and then set the electric parts box as before.
220–240V ~, 50Hz 220V
~
, 60Hz
R(L) S(N)
CN34 (RED)
Black
Pull out connector CN34 (Red) from P.C. board.
Black
White
Red
REQUIREMENT
• Be sure to fix the soft socket with the attached hose band and set the tightening position at upper side.
• Use the attached flexible hose by bending it with 45° or less so that no breakage or clogging occurs.
OK NO GOOD
Top view
Air outlet
max
45˚
max
45˚
Side view
Air outlet
Side viewSide view
Air outlet
“SPH” series
Riser (Trap)
90˚ Bend
24
Remove the cover plate and then fix it to the bottom surface.
Remove the filter from the main unit while pushing down on the tabs.
Force
Air filter
Main unit
CAUTION
Take out this cover plate.
Air inlet sideAir outlet side
Indoor unit
Aluminum tape (Local supply)
Aluminum tape (Local supply)
Duct:Insulation material (Local supply)
Aluminum tape
(Local supply)
Under surface
Cover a screw
Flange
Connect a duct to the inside of the flange
Heat insulator with sticking material (100mm-width Local supply)
Heat insulator with sticking material (100mm-width Local supply)
Aluminum tape (Local supply)
Flange (Local supply)
5
DRAIN PIPING WORK
Insert the edge of hose into the drain pan and bend it downward.
Pump
Vessel
Heat insulating process
• After drain check, using the attached heat insulator for drain connecting section, wrap the flexible hose without clearance from the end of the drain pipe connecting port of the indoor unit.
• Covering the attached heat insulator for drain connecting section, wrap the drain pipe with heat insulator (local supply) without clearance.
Cover plate
Water (1500cc~2000cc)
Attached heat insulator
CAUTION
Pour water slowly.
If it is poured urgently, water is spread inside of the indoor unit resulted in a trouble.
Flexible hose
Hose band
Heat insulator to be procured locally
Hard vinyl chloride pipe
Be sure to mount an air filter to the air inlet side; otherwise decrease of capacity and etc. may be caused.
<Under air inlet> <Back air inlet>
6
AIR DUCTING
6-1. Arrangement
Referring to the following dimensions, manufacture duct at the local site.
<Under air inlet> <Back air inlet>
266
12.5 100100100
805
100100
825
100
100 100
8.2 or less
12.5
170
286.8
12.5
45.3 41.5100100
6-2. Connecting method of the duct
805
“SPH” series
188
12.5
100 100 100
100
100100
100100
825
44.3 100 44.3
Incomplete heat insulation of the supply air flange and sealing may occur dewing resulted in falling of water drop.
CAUTION
7
B
Work using double spanner

REFRIGERANT PIPING

25
WARNING
• If refrigerant gas has leaked during the installation work, ventilate the room immediately.
• If the leaked refrigerant gas comes in contact with fire, noxious gas may generate.
• After the installation work, confirm that refrigerant gas does not leak.
• If refrigerant gas leaks into the room and flows near a fire source, such as a cooking range, noxious gas may generate.
REQUIREMENT
When the refrigerant pipe is long, set the support brackets to fix the pipe with 2.5 to 3m intervals. If the pipe is not fixed, abnormal sound may generate.
Be sure to use the flare nuts attached to the indoor unit or those fro R410A.
Permissible pipe length and permissible height difference
They are different according to the used outdoor unit. For details, refer to the Installation Manual attached to the outdoor unit.
Piping material and dimensions
Piping material Model MMD-
Pipe size (mm)
• Use a clean and new pipe, and check that impurity such as dust, oil, moisture, etc. does not adhere in the pipe.
Gas side Liquid side
Pipe forming/End positioning
Flaring
1. Cut the pipe with a pipe cutter.
NO GOODOK
90˚
2. Insert a flare nut into the pipe, and flare the pipe. As the flaring sizes of R410A differ from those of
refrigerant R22, the flare tools newly manufactured for R410A are recommended. However, the conventional tools can be used by adjusting projection margin of the copper pipe.
Obliquity Roughness Warp
Phosphor deoxidization joint-less pipe for air conditioner
AP007 to AP012 AP015 to AP018
Ø9.5 Ø12.7 Ø6.4 Ø6.4
• Flaring diam. meter size :
A
A (Unit : mm)
+0
A
Outer diam. of
copper pipe
6.4
9.5
12.7
In case of flaring for R410A with the conventional
*
flare tool, pull it out approx. 0.5 mm more than that for R22 to adjust to the specified flare size. The copper pipe gauge is useful for adjusting projection margin size.
- 0.4
R410A
9.1
13.2
16.6
• Projection margin in flaring : B (Unit : mm)
Rigid (Clutch type)
Outer diam. of
copper pipe
6.4
9.5
12.7
Imperial (Wing nut type)
Outer diam. of copper pipe
R410A tool used
R410A R22
0 to 0.5 (Same as left) 0 to 0.5 (Same as left) 0 to 0.5 (Same as left)
6.4
9.5
12.7
Conventional tool used
R410A R22
1.0 to 1.5 0.5 to 1.0
1.0 to 1.5 0.5 to 1.0
1.0 to 1.5 0.5 to 1.0
R410A R22
1.5 to 2.0 1.0 to 1.5
1.5 to 2.0 1.0 to 1.5
2.0 to 2.5 1.5 to 2.0
Connection of refrigerant pipe
Connect all the refrigerant pipes with flare connecting work.
• Since the atmospheric pressure only is sealed as the sealing gas, it is not abnormal that “Pushu…” sound is not heard when the flare nut is removed.
• Be sure to use a double spanner for pipe connecting work of the indoor unit.
• Refer to the following table for tightening torque.
Connecting pipe
outer dia. (mm)
Ø6.4
Ø9.5
Ø12.7
Tightening torque
(N•m)
14 to18 (1.4 to 1.8 kgf•m)
33 to 42 (3.3 to 4.2 kgf•m) 50 to 62 (5.0 to 6.2 kgf•m)
Re-tightening
torque (N•m)
18 (1.8 kgf•m)
42 (4.2 kgf•m) 62 (6.2 kgf•m)
• Tightening torque of flare pipe connections
Pressure of R410A is higher than that of R22 by approx. 1.6 times. Therefore, using a torque wrench, tighten the flare pipe connecting sections which connect the indoor and outdoor units of the specified tightening torque. Incorrect connections may cause not only a gas leak, but also a trouble of the refrigerating cycle.
REQUIREMENT
If an excessive torque is applied, the nut may crack depending on the installation conditions.
Airtight test/Air purge, etc.
For airtight test, air purge, addition of refrigerant, and gas leak check, follow the Installation Manual attached to the outdoor unit.
REQUIREMENT
Be sure to use the tool such as charge hose exclusive to R410A.
Do not turn on the power until the airtight test and the vacuuming have finished. (If turning on the power, the incorporated PMV is closed fully and the period until the vacuuming finishes elongates.
Open fully valves of the outdoor unit
Gas leak check
Check with a leak detector or soap water whether gas leaks or not, from the pipe connecting section or cap of the valve.
REQUIREMENT
Use a leak detector manufactured exclusively for HFC refrigerant (R410A, R134a, etc.).
“SPH” series
7
Remote controller inter-unit wiring
Indoor unit
Remote
controller
Indoor unit
L1 L2 Ln
(Max. 8 units)
Indoor unit Indoor unit
Remote controller wiring
REFRIGERANT PIPING
26
Heat insulating process
Perform heat insulating for pipes at liquid side and gas side separately. In cooling time, temperature at both liquid and gas sides becomes lower. Therefore, perform heat insulating process sufficiently to avoid dewing.
• For heat insulator of pipe at gas side, be sure to use one with heat-resisting temp.120°C or more.
• Using the attached heat insulating pipe, perform heat insulating process securely for pipe connecting part of the indoor units without clearance.
8
ELECTRIC WORK
Apply the heat insulation to the pipe connecting section of the indoor unit securely up to the root without exposure of the pipe. (The pipe exposed to the outside causes water leak.)
Using tape, fix the heat insulator.
REQUIREMENT
Set notching upward.
Pipe side
Attached heat insulating pipe
(Required at the site)
WARNING
1. Using the specified wires, ensure to connect the wires, and fix wires securely so that the
external strength of the wires do not transmit to the connecting part of the terminals.
Incomplete connection or fixation may cause a fire, etc.
2. Be sure to connect earth wire. (Grounding work)
Do not connect the earth wire to gas pipe, city water pipe, lightning rod, or the earth wire of telephone. Incomplete grounding causes an electric shock.
3. For electric work, strictly follow to the Local Regulation in each country and the Installation
Manual, and use an exclusive circuit.
Capacity shortage of power circuit or incomplete installation may cause an electric shock or a fire.
Power supply cord and communication wires specifications
Power supply cord and communication wires are procured locally. For the power supply specifications, follow to the table below. If capacity is little, it is dangerous because overheat or
seizure may be caused. For specifications of the power capacity of the outdoor unit and the power supply wires, refer to the Installation
Manual attached to the outdoor unit.
Indoor unit power supply
• For the power supply of the indoor unit, prepare the exclusive power supply separated from that of the outdoor unit.
• Arrange the power supply, earth leakage breaker, and main switch of the indoor unit connected to the same outdoor unit so that they are commonly used.
• Power supply cord specification : Cable 3-core 2.5mm², in conformity with Design 60245 IEC 57.
~ 50Hz
220–240V
220V
~ 60Hz
Twist wire : 2.0 mm² Twist wire : 3.5 mm²
Power supply
Power supply
Power supply switch/Earth leakage breaker or power supply wiring/fuse rating for indoor units should be selected by the accummulated total current values of the indoor units.
Power supply wiring
Below 20m Below 50m
Control wiring, Central controller wiring
• 2-core with polarity wires are used for the Control wiring between indoor unit and outdoor unit and Central controller wiring.
• To prevent noise trouble, use 2-core shield wire.
• The length of the communication line means the total length of the inter-unit wire length between indoor and outdoor units added with the central control system wire length.
Communication line
Control wiring between indoor unit and outdoor unit (2-core shield wire)
Central control line wiring (2-core shield wire)
Wire size
Wire size
(Up to 1000m) Twist wire : 1.25 mm² (Up to 2000m) Twist wire : 2.00 mm²
(Up to 1000m) Twist wire : 1.25 mm² (Up to 2000m) Twist wire : 2.00 mm²
CAUTION
Be sure to install an earth leakage breaker.
If an earth leakage breaker is not installed, an electric shock may be caused.
REQUIREMENT
• For power supply wiring, strictly conform to the Local Regulation in each country.
• For wiring of power supply of the outdoor units, follow to the Installation Manual of each outdoor unit.
• Never connect 220–240V power to the terminal blocks (A, B, U1, U2, X, Y, etc.) for control wiring. (Otherwise, the system will be failed.)
• Perform the electric wiring so that it does not come to contact with the high-temperature part of the pipe. The coating may melt resulted in an accident.
• After connecting wires to the terminal blocks, provide a trap and fix wires with the wire clamp.
• Store the refrigerant piping line and control wiring line in the same line.
• Do not turn on the power of the indoor unit until vacuuming of the refrigerant pipes completes.
Remote controller wiring
• 2-core with non-polarity wire is used for wiring of the remote controller wiring and group remote controllers wiring.
Remote controller wiring, remote controller inter-unit wiring
Total wire length of remote controller wiring and remote controller inter-unit wiring = L + L1 + L2 + … Ln
Total wire length of remote controller inter-unit wiring = L1 + L2 + … Ln
Twist wire: 0.5mm
In case of wired type only In case of wireless type included
2
to 2.0mm2 × 2
Up to 500m Up to 400m Up to 200m
CAUTION
The remote controller wire (Communication line) and AC220–240V wires cannot be parallel to contact each other and cannot be stored in the same conduits. If doing so, a trouble may be caused on the control system due to noise, etc.
“SPH” series
8
Terminal block for remote controller wiring of indoor unit
A B
Remote controller wire (Field supply)
Remote controller unit
A B
Terminal block
Indoor power supply 220-240V, ~50Hz 220V~60Hz
Outdoor Power supply 380V-415V ~ 50Hz 380V ~ 60Hz
Earth leakage breaker
Header outdoor unit
Indoor unit
Remote controller
Pull box
Earth leakage breaker power switch
Pull box Pull box
Header outdoor unit
Earth leakage breaker
Control wiring between indoor and outdoor units
Earth
Earth
terminal
U1 U2
U1 U2 U3 U4L1 L2 L3 N U5 U6
L N A B
A B
Control wiring between outdoor units
Outdoor Power supply 380V-415V ~ 50Hz 380V ~ 60Hz
Earth
terminal
U1 U2 U3 U4L1 L2 L3 N U5 U6
Control wiring between indoor units
Indoor unit
Remote controller
Earth
U1 U2L N A B
A B
Indoor unit
Remote controller
Earth
U1 U2L N A B
A B
Indoor unit
Earth
U1 U2L N A B

ELECTRIC WORK

27
Cable connection
REQUIREMENT
• Be sure to pass the wire through the wire connection port of the indoor unit.
• Keep a margin (Approx. 100mm) on a wire to hang down the electric parts box at servicing, etc.
• The low-voltage circuit is provided for the remote controller.
• Before remove the electric parts cover, remove the cover plate and air filter.
• Remove the cover of the electric parts box by taking off the mounting screws (2 positions) and pushing the hooking section. (The cover of the electric parts box remains hanged to the hinge.)
• Tighten the screws of the terminal block, and fix the wires with cord clamp attached to the electric parts box. (Do not apply tension to the connecting section of the terminal block.)
• Be sure to set a loop for the connecting wire of the storing part of the indoor unit electric parts; otherwise the electric parts box cannot be drawn out in service time.
• Mount the cover of the electric parts box without pinching wires.
Control wire
R
(L
)
S
(N
)
Electric
Power supply cord
Cable cramp
30
Remote controller wire
R
(L)S(N)
10
10
Earth line
Power supply cord
70
parts box
Electric parts box cover
Screw (2 positions)
Cover plate
Air filter
Remote controller wiring
• As the remote controller wire has no polarity, there is no problem if connections to indoor unit terminal blocks A and B are reversed.
<Wiring diagram>
Wiring between indoor and outdoor units
<Wiring example>
An outdoor unit connected with control wiring between indoor and outdoor units wire becomes automatically the header unit.
NOTE
“SPH” series
Address setup
Set up the addresses according to the Installation Manual attached to the outdoor unit.
9
T
T
T
T
T
T
t
C
2
C
1
C
0
n
C
2
C
1
C
0
C
2
C
1
C
0
C
2
C
1
C
0

APPLICABLE CONTROLS

28
NOTIFICATION
When using the equipment at the first time, it will take a lot of time that the remote controller accepts an operation after power was on. However, it is not a trouble.
• Automatic address
• While automatic addressing, the operation cannot be performed on the remote controller.
• For automatic addressing, Max. 10 minutes (generally, approx. 5 minutes) are required.
• When power will be turned on after finish of automatic addressing;
• It will require Max. 10 minutes (generally, approx. 3 minutes) that outdoor unit starts operation after power was on.
As all have been set to [Standard] at the shipment, change the setup of the indoor unit if necessary. To change the setup, use the main remote controller (wired remote controller). * The setup change for wireless remote controller, sub remote controller, or remote controller-less system
(Central control remote controller only is provided.) is impossible. In these cases, prepare and mount a separate main remote controller.
TIMER SET
CODE No.
UNIT No.
R.C. No.
ON / OFF
FAN
MODE
SWING/FIXTIME
VENT
UNITSET CL
Exchange of applicable control setup
Basic operation procedure for setup exchange
Change the setup while operation of the equipment stops. (Be sure to stop the operation of a set.)
TEMP.
4
FILTER
TEST
1
RESET
6
Procedure
1
2 3
4 5
6
When pushing flashes as shown in the figure.
Check that the displayed item code is [10].
• If the item code indicates other than [10], push the display, and then retry the operation from the first step. (For some time after the remote controller cannot be accepted.)
(In a group control, the firstly displayed indoor unit No. becomes the header unit.)
Every pushing Select an indoor unit of which setup to be changed.
In this time, the position of the indoor unit of which setup to be changed can be confirmed because the fan and the flap of the selected indoor unit work.
Using , buttons of set temperature, specify the item code [
Using , buttons of timer time, select set data [
Push
• To change the setup of an indoor unit other than the selected one, start operation from Procedure
• To change the setup of another setup in the selected indoor unit, start operation from Procedure
Pushing When the setup finished, push
Pushing normal stop status. (For some time after remote controller cannot be accepted.)
SET, CL
].
**
SET
button. In this time, if the display changes from flashing to lighting, the setup completes.
CL
button clears the set up contents which have been already set. In this case, retry from Procedure 2.
TES
button deletes the display and returns the status to
TES
, and
buttons simultaneously for 4 seconds or more, after a while, the display part
TES
button has been pushed, the operation of
UNIT
button, the indoor unit No. in the group control is displayed successively.
TES
button. (The setup is determined.)
TES
button has been pushed, the operation of the
Description
TES
button to erase
].
****
SETTING
UNIT No.
R.C. No.
(* The display changes according
to the indoor unit model.)
UNIT No.
∗∗
∗∗∗∗∗
R.C. No.
Setup of external static pressure
Be sure to set up a tap change based upon the resistance (external static pressure) of the duct to be connected.
To set up a tap change, follow to the basic operation procedure (
• Specify [5d] to the item code in procedure
• For the setup data of procedure
1
2 3 4 5 6 ).
4
3
.
, select a setup
<Change on wired remote controller>
Setup data
0000 0001 0003 0006
External static pressure
10 Pa Standard (At shipment) 20 Pa High static pressure 1 35 Pa High static pressure 2 50 Pa High static pressure 3
data of the external static pressure to be set up from the following table.
In case of remote controller-less (Group control)
For setup to the high ceiling, there is selecting method by exchanging the short plugs on the indoor microcomputer P.C. board as shown in the following table other than selecting method by standard wired remote controller (sold separately). Utilize this method for remote controller-less (Group control) case.
However, when the setup to high ceiling has been once exchanged, it is required for returning it to 0000 to change
the short plug to the standard (at shipment) position and rewrite data to the setup data 0000 from the wired remote controller sold separately though setup to 0001, 0003 or 0006 are freely available.
3 2 5
CODE No.
CODE No.
∗∗
2
.
3
.
• Select by exchange of short plugs on the indoor P.C. board.
Short plug position
Set data External static pressure
Shor
Ope
N11
N11
N11
N11
N11
N11
N11
N11
N11
N11
N11
N11
0000
0001
0003
0006
10 Pa (At shipment)
20 Pa
35 Pa
50Pa
• Short plug position (CN112, CN111, CN110 from the left)
“SPH” series
9
T
T
APPLICABLE CONTROLS
10
TEST RUN
29
Change of lighting term of filter sign
According to the installation condition, the lighting term of the filter sign (Notification of filter cleaning) can be changed.
Follow to the basic operation procedure
1
2 3 4 5 6 ).
(
• For the item code in Procedure
• For the [Set data] in Procedure data of filter sign lighting terme from the following table.
Setup data
0000 0001 0002 0003 0004
150H 2500H (At shipment from factory) 5000H 10000H
3
, specify [01].
4
, select the setup
Filter sign lighting term
None
To secure better effect of heating
When it is difficult to obtain satisfactory heating due to installation place of the indoor unit or structure of the room, the detection temperature of heating can be raised. Also use a circulator, etc. to circulate heat air near the ceiling.
Follow to the basic operation procedure
1
2 3 4 5 6 ).
(
• For the item code in Procedure
• For the set data in Procedure data of shift value of detection temperature to be set up from the table below.
Setup data
0000 0001 0002 0003 0004 0005 0006
Detection temp shift value
+1°C +2°C (At shipment from factory) +3°C +4°C +5°C +6°C
3
, specify [06].
4
, select the setup
No shift
Group control
In a group control, a remote controller can control up to maximum 8 units.
• For cabling procedure and cables of the individual line (Identical refrigerant line) system, refer to “Electric work” in this Manual.
• Cabling between indoor units in a group is performed in the following procedure.
Connect the indoor units by connecting the remote controller inter-unit cables from the remote controller terminal blocks (A, B) of the indoor unit connected with a remote controller to the remote controller terminal blocks (A, B) of the other indoor unit. (No polarity)
• For address setup, refer to the Installation Manual attached to the outdoor unit.
Before test operation
• Before turning on the power supply, carry out the following items.
1) Using 500V-megger, check there is 1M or more between the terminal block of the power supply and the earth. If 1M or less is detected, do not run the unit.
2) Check that all the valves of the outdoor unit are fully opened.
• Never push the electromagnetic contactor to carry out a forced test operation. (It is very dangerous because a protective device does not work.)
To protect the compressor at starting time, keep power-ON condition before 12 hours or more.
WARNING
How to execute test operation
• To carry out a fan operation in a single indoor unit, turn off the power once, short CN72 on P.C. board, and then turn on the power again. (Start the unit in FAN mode.) In this case, do not forget to clear short-circuit of CN72 after test operation.
• Using the remote controller, check the operation in the usual operation. For the operation procedure, refer to the attached Owner’s Manual.
A forced test operation can be executed in the following procedure under condition of thermo-OFF of room temperature.
In order to prevent a serial operation, the forced test operation is released after 60 minutes and returns to the usual operation.
NOTE
Do not use a forced operation in cases other than test operation because it applies an excessive load to the air conditioner.
In case of wired remote controller
Procedure
TES
Keep
button pushed for 4 seconds or more.
[TEST] is displayed on the display part and the selection of mode in
1
the test mode is permitted.
ON / OFF
Push
2
Using
• Do not run the air conditioner in a mode other than [COOL] or [HEAT].
• The temperature controlling function does not work during test
3
4
operation.
• The detection of error is performed as usual. After the test operation, push
(Display part is same as procedure
button.
MODE
button, select the operation mode, [COOL] or [HEAT].
1, 5
Description
ON / OFF
button to stop the operation.
1
)
FILTER RESET
TEMP.
TIMER SET
TEST
ON / OFF
2, 4
FAN
MODE
SWING/FIXTIME
VENT
UNITSET CL
TEST
3
“SPH” series
TES
Push
button to cancel (release from) the test operation mode.
([TEST] disappears on the display part and the status returns to a
5
normal stop status.)
10
T
T
3
2
1
ON / OFF
FAN
TEMP.
SWING/FIXTIME
MODE
VENT
UNITSET CL
FILTER RESET
TEST
TIMER SET

TEST RUN

11
TROUBLESHOOTING
30
In case of wireless remote controller
Procedure
Remove a small screw which fixes the nameplate of the receiver unit. Remove the nameplate of the sensor section by inserting a minus screwdriver, etc into the notch at the bottom
1
of the plate, and set the Dip switch to [TEST RUN ON]. Execute a test operation with button on the wireless remote controller.
2
3
4
, , and LED flash during test operation.
• Under status of [TEST RUN ON], the temperature adjustment from the wireless remote controller is invalid. Do not use this method in the operation other than test operation because the equipment is damaged.
Use either COOL or HEAT operation mode for a test operation. * The outdoor unit does not operate approx. 3 minutes after power-ON and operation stop.
After the test operation finished, stop the air conditioner from the wireless remote controller, and return Dip switch of the receiver section as before. (A 60-minutes timer clearing function is attached to the receiver section in order to prevent a continuous test operation.)
M4 × 25 screw (2 pieces)
Small screw
Notch
Receiver unit
Nameplate
Description
Spacer
Confirmation and check
When a trouble occurred in the air conditioner, the check code and the indoor unit No. appear on the display part of the remote controller.
The check code is only displayed during the operation. If the display disappears, operate the air conditioner
according to the following “Confirmation of error history” for confirmation.
Confirmation of error history
When a trouble occurred on the air conditioner, the error history can be confirmed with the following procedure. (The error history is stored in memory up to 4 errors.)
This history can be confirmed from either operating status or stop status.
Procedure
TES
When pushing more, the right display appears.
If [Service Check] is displayed, the mode enters in the error history mode.
1
• [01: Order of error history] is displayed in CODE No. window.
• [Check Code] is displayed in CHECK window.
• [Indoor unit address in which an error occurred] is displayed in UNIT No.
Every pushing , buttons, the error history stored in the memory is displayed in order. The numbers in CODE No. indicates CODE No. [01] (Latest) [04] (Oldest).
2
CAUTION
Do not push
After confirmation, push
3
SET
and
buttons simultaneously for 4 seconds or
CL
button because all the error history of the indoor unit will be deleted.
TES
button to return to the usual display.
Description
CODE No.
UNIT No.
R.C. No.
Check code Indoor unit No. in which
an error occurred
UNIT No.
R.C. No.
CODE No.
“SPH” series
Loading...
+ 105 hidden pages