Toshiba GRD150, GRD150-10 Series, GRD150-20 Series, GRD150-30 Series, GRD150-40 Series User Manual

GRD150
2
FEATURES
Protection functions
Non-directional and directional overcurrent and
earth-fault protection and sensitive earth fault protection (option)
Overvoltage and undervoltage protection Thermal overload protection Underfrequency or overfrequency protection Negative phase sequence overcurrent
protection
Undercurrent protection Circuit breaker failure protection Autoreclose function (option)
Control functions
Indication of the status of switching devices, i.e.
circuit breakers and disconnectors
Open and close commands for switching
devices
Synchronism check function (option) MIMIC configuration display
Monitoring and Metering
Circuit breaker condition monitoring Trip circuit supervision Metering: three-phase currents and voltages,
residual current and voltage, frequency, active and reactive power, power factor, and max. demand values.
Recording
Event record: 480 most recent events Alarm record: 32 most recent alarms Fault record: 8 most recent faults Disturbance record: 9 analog and 32 binary
signals
User Interface
Menu-based HMI system Graphical LCD display PLC function Configurable binary inputs and outputs Configurable LED indications Communication Interface: RS485, Fibre optic
or Ethernet LAN (option)
APPLICATION
GRD150 feeder manager is designed for protection, control, metering and supervision of medium voltage networks.
GRD150 includes multiple, high accuracy, overcurrent protection elements (for phase and/or earth fault) with
inverse time (IDMTL) and definite time delay (DTL) functions. All phase, earth and sensitive earth fault overcurrent elements can be independently subject to directional control. The directional elements provide user-settable characteristic angles.
Other protection functions are also available, including thermal protection to IEC60255-8, negative sequence overcurrent protection, under/overvoltage and under/ over frequency protections.
GRD150 provides continuous monitoring of internal circuits and of software. External circuits are also monitored, by trip circuit supervision, CT and VT supervision, and CB condition monitoring features.
A user-friendly HMI is provided through a backlit LCD, programmable LEDs, keypad and menu-based operating system. PC access is also provided, either for local connection via a front-mounted RS232 port, or for remote connection via a rear-mounted RS485 or fibre optic port. The communication system allows the user to read and modify the relay settings, and to access data gathered by the relay’s metering and recording functions.
Data available either via the relay HMI or communications ports includes the following functions.
Metering Fault recording Event recording Alarm recording Disturbance recording (available via
communications ports)
Figure 1 - Front View
GRD150
3
Table 1 GRD150 models and Functions
GRD150- Models
Function
10 series 20 series 30 series 40 series
Non-directional overcurrent OC (IDMTL, DTL, INST)
Non-directional earth fault EF (IDMTL, DTL, INST)
Non-directional sensitive earth fault SEF (IDMTL, DTL, INST)
Directional overcurrent DOC (IDMTL, DTL, INST)
Directional earth fault DEF (IDMTL, DTL, INST)
Directional sensitive earth fault DSEF (IDMTL, DTL, INST)
Undercurrent UC
Thermal over load THM
Non-directional negative phase overcurrent NOC (IDMTL, DTL, INST)
Directional negative phase overcurrent DNOC (IDMTL, DTL, INST)
Broken conductor detection BCD
Circuit breaker failure protection CBF
Cold load pick-up feature
Overvoltage OV (IDMTL, DTL, INST)
Undervoltage UV (IDMTL, DTL, INST)
Zero phase sequence overvoltage ZOV (IDMTL, DTL, INST)
Negative phase sequence overvoltage NOV (IDMTL, DTL, INST)
Under/over frequency FRQ
Autoreclose function
Fault locator
Indication of the status of switching devices
Open and close commands for switching devices
Synchronism check function
MIMIC configuration picture (*)
PLC function (*)
CT supervision
VT supervision
Trip circuit supervision
Self supervision
CB state monitoring
Trip counter alarm
Iy alarm
CB operate time alarm
Multiple settings groups
Metering
Fault records
Alarm records
Event records
Disturbance records
Communication
IDMTL: inverse definite minimum time DTL: definite time INST: instantaneous
(*): PC tools (MIMIC editor and PLC editor) are option.
GRD150
4
FUNCTIONS
Protection
- 4-stage non-directional and directional overcurrent and earth-fault protection and sensitive earth fault protection (option)
1
st
and 2nd stage: Instantaneous, IDMTL or DTL
3
rd
and 4th stage: Instantaneous or DTL
- 2-stage non-directional and directional negative phase sequence overcurrent protection
1
st
stage: Instantaneous, IDMTL or DTL
2
nd
stage: Instantaneous or DTL
- 2-stage overvoltage and undervoltage protection
1
st
stage: Instantaneous, IDMTL or DTL
2
nd
stage: Instantaneous or DTL
- 6-stage underfrequency or overfrequency protection
- Thermal overload protection
- Cold load protection function or Inrush current (2
nd
harmonic) detector provided for energising the system
- Undercurrent protection
- Broken conductor detection
- Circuit breaker failure protection
- Autoreclose function: 5-shots, 3-phase autoreclose (option)
Control
Two-stepped operation (select-control) is used for the control procedure of circuit breakers, disconnectors, earthing disconnector switches and transformers to ensure highly reliable operation.
- Control of circuit breakers, disconnectors and earthing disconnector switches
- Interlock check
- Synchronism check for circuit breaker closing (option)
- MIMIC configuration picture displayed on LCD
- Double command blocking
- Switchgear operation counter
- Control blocking
Password protection is provided to operate above functions.
Monitoring and Metering
- Status monitoring of switchgear devices and failure monitoring of power apparatus, control equipment, protection relays and ancillary equipment
- Metering: current, voltage, frequency, active power, reactive power and max. demand values
An energy calculation (Watt-hour, var-hour) is also
available.
- Limit value checking of metering
- Opening and closing time monitoring
These data are available on the HMI and at a local or remote PC.
Recording
- Event records: The most recent 480 time-tagged events with 1ms resolution are stored.
- Alarm records: The most recent 32 time-tagged alarms with 1ms resolution are stored.
- Fault records: The most recent 8 time-tagged faults with 1ms resolution are stored.
- Disturbance records: GRD150 can record 9 analog and 32 binary signals, initiated by relay tripping. Pre­trigger and post-trigger recording times can be set, and the maximum number of records which can be stored is dependent on the recording times chosen.
These records are available on the HMI and at a local or remote PC.
GRD150
5
Figure 2 - Operate and Reset Characteristics of IDMTL
Inverse Time Operate and Reset Curves
IEC/UK Inverse Curves
(Time Muliplier TMS = 1)
0.1
1
10
100
1000
1 10 100
Current (Multiple of Setting)
Operating Time (s)
LTI
NI
VI
EI
IEEE/US Inverse Curves
(Time Multiplier TMS = 1)
0.1
1
10
100
1 10 100
Current (Multiple of S etting)
Operating Time (s)
MI
VI
STI
I
EI
IEEE/US Reset Curves
(Time Multiplier T MS = 1)
1.00
10.00
100.00
1000.00
0.1 1
Current (Multiple of S etting)
Time (s)
MI
VI
EI
STI
I
()
⎪ ⎭
⎪ ⎬
⎪ ⎩
⎪ ⎨
+
×= c
Is
I
k
TMSt
1
α
⎟ ⎠
⎞ ⎜ ⎝
×=
2
1
S
r
I
I
t
RTMSt
Inverse time operate function Dependent time reset function
Constants for dependent time curves
Curve Description k
α
C t
r
IEC Normal Inverse (NI)
0.14 0.02 0 -
IEC Very Inverse (VI)
13.5 1 0 -
IEC Extremely Inverse (EI)
80 2 0 -
UK Long Time Inverse (LTI)
120 1 0 -
IEEE Moderately Inverse (MI)
0.0515 0.02 0.114 4.85
IEEE Very Inverse (VI)
19.61 2 0.491 21.6
IEEE Extremely Inverse (EI)
28.2 2 0.1217 29.1
US CO8 Inverse (I)
5.95 2 0.18 5.95
US CO2 Short Time Inverse (STI)
0.02394 0.02 0.01694 2.261
GRD150
6
USER INTERFACE
Relay Front Panel
A user friendly interface is provided on the relay front panel. A menu-based system provides for easy programming of relay functions and access to real­time and stored data. The front panel includes the following features.
Graphical LCD
display with backlight.
12 LEDs including 8
user programmable LEDs.
Keypad. RS232C serial port for connection of local PC.
Local PC Connection
The user can communicate with the GRD150 from a local PC via the RS232C port on the front panel. Using RSM100 software, the user can view and modify settings, monitor real-time metering and analyse recorded data.
Relay Setting and Monitoring (RSM) and Remote Control System
GRD150 can be connected to the RSM system via the rear mounted serial communications port, using RS485 or other connections such as fibre optic, Ethernet LAN, etc., (specified at time of order). Using RSM100 software, the user can view and modify settings, monitor real-time metering and analyse recorded data.
A maximum of 32 relays can be connected to the remote PC in multi-drop mode, by connection via a protocol converter, with data transmission rate of 64kbps using RSM-X protocol. Modbus®(RTU) protocol can be also available.
The figures below show the configuration of the RSM system and typical displays from the RSM100 software.
Using an additional port (option), GRD150 can be connected to a Substation Control System. In this case, GRD150 supports IEC60870-5-103 or DNP3.0 transmission protocols.
Figure 3 - Relay Setting and Monitoring System
Mimic Editor (MMEdit)
Yhe user can configure and customize the MIMIC data displayed on the LCD of GRD150 using MMEdit software. The MIMIC data produced by the MMEdit software can be uploaded to GRD150 via the PC communication port (RS232C).
Figure 4 - PC Display of MMEdit
PLC Editor (PLCEdit)
The user can customize logic functions on GRD150 such as trip and interlock sequence, etc., using PLCEdit software. The PLC data produced by the PLCEdit software can be uploaded to GRD150 via PC communication port (RS232C).
Figure 5 - PC Display of PLCEdit
Converter
G1PR2
Loading...
+ 14 hidden pages