Toshiba GRD130, GRD130-210, GRD130-410 User Manual

GRD130
2
FEATURES
Phase undervoltage protection with IDMTL or
DTL.
DTL.
Zero phase sequence overvoltage (neutral voltage
displacement) protection with IDMTL/DTL.
Negative phase sequence overvoltage protection
with IDMTL or DTL.
Programmable reset characteristics. Four settings groups. Configurable binary inputs and outputs. Circuit breaker condition monitoring. Trip circuit supervision. Automatic self-supervision. Menu-based HMI system. Configurable LED indication. Metering and recording functions. Communications for remote setting and data
download is provided via the RSM (Relay Setting and Monitoring system.
Front mounted RS232 serial port for local PC
communications.
Rear mounted RS485 or fibre optic serial port
for remote PC communications.
The IEC60870-5-103 protocol is provided for
communication with substation control and automation systems.
APPLICATION
The GRD130 is a range of fully numeric voltage protection relays. GRD130 has two models which differ according to the number of voltage inputs fitted, see Table 1.
Table 1 - GRD130 Models
Model Configuration
GRD130-210 2 pole GRD130-410 4 pole
Both models include multiple, high accuracy, phase under/overvoltage protection with inverse time and definite time delay functions. Voltage inputs can be configured for phase to phase or phase to neutral operation. Zero sequence overvoltage (neutral voltage displacement) protection is available for detection of earth faults in high impedance earthed or isolated systems. For protection against operation on unbalanced supply voltages, negative phase sequence overvoltage protection is also available. The ZPS and NPS overvoltage protections are available depending on
the model and on the configuration selected, see Table 2.
GRD130 provides continuous monitoring of internal circuits and of software. External circuits are also monitored, by trip circuit supervision and CB condition monitoring features.
A user-friendly HMI is provided through a backlit LCD, programmable LEDs, keypad and menu-based operating system. PC access is also provided, either for local connection via a front-mounted RS232 port, or for remote connection via a rear-mounted RS485 or fibre optic port. The communication system allows the user to read and modify the relay settings, and to access data gathered by the relay’s metering and recording functions.
Data available either via the relay HMI or communications ports includes the following functions.
Metering Fault recording Event recording Disturbance recording (available via
communications ports)
Table 2 - GRD130 Features
GRD130 - Model Number
210 410
Configuration 1V
ph-ph
+ V
0
1V
ph-n
+ V0
2V
ph-ph
3V
ph-n
3V
ph-n
+ V
0
3V
ph-ph
+ V
0
2V
ph-ph
+ V
0
Phase O/V (IDMTL) 59 Phase O/V (DTL) 59 Phase U/V (IDMTL) 27 Phase U/V (DTL) 27 ZPS O/V (IDMTL) 59N  -  ZPS O/V (DTL) 59N  -  NPS O/V (IDMTL) 47 - NPS O/V (DTL) 47 - Trip circuit supervision Self supervision CB State Monitoring Trip Counter Alarm Multiple settings groups Metering Fault records Event records Disturbance records Communication
GRD130
3
PROTECTION FUNCTIONS
Phase Overvoltage Protection
GRD130 overvoltage protection provides three independent overvoltage thresholds. The first and second thresholds may be set for inverse time or definite time operation. The third threshold can be programmed for definite time operation.
The first and second thresholds has a programmable reset feature, selectable for instantaneous or definite time operation. Each element gives outputs for alarm and trip, and each trip output can be inhibited by binary input.
Phase Undervoltage Protection
GRD130 undervoltage protection provides three independent undervoltage thresholds. The first and second thresholds may be set for inverse time or definite time operation. The third threshold can be programmed for definite time operation.
The first and second thresholds has a programmable reset feature, selectable for instantaneous or definite time operation. Each element gives outputs for alarm and trip, and each trip output can be inhibited by binary input.
An undervoltage blocking function prevents undervoltage tripping in the case of a dead line.
Zero Phase Sequence Overvoltage Protection (ZPS)
GRD130 provides ZPS protection with two independent
overvoltage thresholds. The two thresholds may be set for inverse time or definite time operation. The two thresholds have a programmable reset feature, selectable for instantaneous or definite time operation.
In the case of GRD130-410, the zero sequence voltage, V
0
may either be calculated from the three measured phase voltages, or it may be measured directly in the form of the system residual voltage, typically using a five limb VT.
In the case of GRD130-210, the V
0
must be measured
directly.
The low voltage settings which may be applied make the ZPS element susceptible to any 3
rd
harmonic component which may be superimposed on the input signal. Therefore, a 3
rd
harmonic filter is provided to
suppress such superimposed components.
Each element gives outputs for alarm and trip, and each trip output can be inhibited by binary input.
Negative Phase Sequence Overvoltage Protection (NPS)
GRD130 provides NPS protection with two independent overvoltage thresholds. The two thresholds may be set for inverse time or definite time operation.
The two thresholds have a programmable reset feature, selectable for instantaneous or definite time operation. Each element gives outputs for alarm and trip, and each trip output can be inhibited by binary input.
Figure 1 - IDMT curves for Overvoltage, Undervoltage and ZPS, NPS Overvoltage
Inverse Time Operate Curves
Overv oltage Inv erse Time Curv es
0.100
1.000
10.000
100.000
1000.00 0
1 1.5 2 2.5 3
Applied Voltage (x Vs)
Operating Time (secs)
TMS = 1
TMS = 2
TMS = 5
TMS = 10
Undervoltage Inverse Time Curves
1.000
10.000
100.000
1000.000
0 0.2 0.4 0.6 0.8 1
Applied Voltage (x Vs)
Operating Time (secs)
TMS = 10
TMS = 5
TMS = 2
TMS = 1
ZPS, NPS Overvoltage Inverse T ime Curves
0.010
0.100
1.000
10.000
100.000
1000.000
0 5 10 15 20
Applied Voltage (x Vs)
Operating Time (secs)
TMS = 10
TMS = 5
TMS = 2
TMS = 1
()
xTM
S
Vs
V
t
11−
=
()
xTMS
Vs
V
t−=
1
1
()
xTM
S
Vs
V
t
11−
=
GRD130
4
MONITORING FUNCTIONS
Trip Circuit Supervision
The circuit breaker tripping control circuit can be monitored by a binary input. Figure 2 shows a typical scheme. When the trip circuit is complete, a small current flows through the binary input, the circuit breaker auxiliary contacts and the trip coil. This current flows for both the breaker open and closed conditions.
Figure 2 - Trip Circuit Supervision Scheme
If the trip supply is lost or if a connection becomes open circuit then the binary input resets and a Trip Circuit Fail alarm is given in the form of an output contact operation and LCD or LED indication.
Automatic Self-Supervision
Automatic monitoring of internal circuits and software is provided. In the event of a failure being detected, the ALARM LED on the relay fascia is illuminated, the ‘RELAY FAILURE’ binary output operates, and the date and time of the failure is recorded in the event record.
Circuit Breaker State Monitoring
If two binary inputs are programmed to the functions ‘CB OPEN’ and ‘CB CLOSED’ then the CB State Monitoring function becomes active. In normal circumstances these inputs are in opposite states. If both show the same state then a ‘CB Defective’ alarm is raised.
Trip Counter Alarm
The trip counter increments the number of tripping operations performed, and an alarm is issued when the count exceeds a user-defined setting. The trip count is triggered each time a trip is issued, and they can also be triggered by an external device via a binary input.
METERING AND RECORDING
Metering
The following data is continuously available on the relay fascia LCD and at a local or remote PC.
Primary and secondary voltages for each input. Positive and negative phase sequence voltages. Power frequency. CB trip count. CB status. Relay element output status. Binary input and output status.
Event Record
Records are stored for the 480 most recent events, time-tagged to 1ms resolution. The event record is available on the relay fascia LCD and at a local or remote PC. Events are recorded as follows:
Tripping operations. Alarms. Operation of protection elements. Change of state of binary inputs / outputs. Change of relay setting. Failure detected by automatic supervision.
Fault Record
A relay trip initiates fault recording. Records are stored for the 8 most recent faults, time-tagged to 1ms resolution. The fault record is available on the relay fascia LCD and at a local or remote PC. Fault records include the following data:
Date and time of trip operation. Faulted phase. Protection element responsible for trip. Measured voltage data.
Disturbance Record
The relay can record 4 analog and 32 binary signals, initiated by relay tripping. The post-trigger recording time can be set, and the maximum number of records which can be stored is dependent on the recording time chosen.
Date and Time
GRD130 provides a date and time feature for tagging of records.
GRD110
Circuit Breaker
Binar y Input
CB Aux. Contac ts
CB Trip Coil Tr ip Out put +ve Trip
Suppl y
-ve Trip Suppl y
GRD130
5
USER INTERFACE
Relay Front Panel
A user friendly interface is provided on the relay front panel. A menu-based system provides for easy programming of relay functions and access to real­time and stored data. The front panel includes the following features.
16 character, 2-line LCD with backlight. 6 LEDs. Keypad. RS232C serial port for connection of local PC.
Local PC Connection
The user can communicate with the GRD130 from a local PC via the RS232C port on the front panel. Using RSM100 software, the user can view and modify settings, monitor real-time metering and analyse recorded data.
Relay Setting and Monitoring (RSM)
GRD130 can be connected to the RSM system via the rear mounted serial communications port, using either RS485 or fibre optic connections (specified at time of order). Using RSM100 software, the user can view and modify settings, monitor real-time metering and analyse recorded data.
A maximum of 32 x 8 relays can be connected to the remote PC in multi-drop mode, by connection via a protocol converter G1PR2, with a maximum data transmission rate of 64kbps. The G1PR2 can be provided with maximum 8 ports and each port supports maximum 32 relays addressing.
Figure 3 - Relay Setting and Monitoring System
Figure 3 and 4 show the configuration of the RSM system and typical displays from the RSM100 software.
IEC60870-5-103 Communications
GRD130 supports the IEC60870-5-103 communication protocol. This protocol is used for communication with a substation control and monitoring system and is used to transfer measurand data, status data and general commands between the relay and the control system.
Relay Setting
The user can modify relay settings either using the front panel keypad or using the RSM100 software from a local or remote PC. Password protection is available for added security.
Four settings groups are provided, allowing the user to set one group for normal conditions, while the other groups may be set to cover alternative operating conditions.
Using the RSM software, the user can create a settings file on a PC (without being connected to a relay), and store the file ready for download to a relay at a later date.
Binary Outputs
GRD130 provides eight binary output contacts for tripping and alarm, of which seven are user programmable. Each of the programmable binary outputs is driven via a logic gate which can be programmed for OR gate or AND gate operation. Further, each output has a programmable reset characteristic, settable for instantaneous drop-off, delayed drop-off, or for latching operation. If latching operation is selected then an operated relay must be reset by the user, either by pressing the RESET button, by energising a binary input which has been programmed for ‘Remote Reset’ operation, or by a communications command.
Binary Inputs
GRD130 provides eight programmable binary inputs. Each binary input is individually user-programmable for normal or inverted operation and for delayed pick­up and/or drop-off. Each input can also be used to switch relay operation to a different settings group.
General purpose alarm functions are also included. The user can define a text message for each alarm. Then when inputs associated with that alarm are raised, the defined text is displayed on the LCD.
G1PR2
Protocol converter
Loading...
+ 11 hidden pages