Installation manual Air conditioner
Manuel d'installation Climatiseur
(Split type)
(Type split)
1
23
English
Français
Outdoor Unit
Please read this Installation Manual carefully before installing the Air Conditioner.
• This Manual describes the installation method of the outdoor unit.
• For installation of the indoor unit, refer to the Installation Manual attached to the indoor unit.
Installation Manual
ADOPTION OF NEW REFRIGERANT
This Air Conditioner uses R410A an environmentally friendly refrigerant.
Contents
1 DIMENSION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
2 ACCESSORY PARTS. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
3 SYSTEM REQUIREMENTS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
4 PRECAUTIONS FOR SAFETY. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
5 INSTALLATION OF NEW REFRIGERANT AIR CONDITIONER. . . . . . . . . . . . . . . . . . 7
6 REFRIGERANT PIPING . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
7 ELECTRICAL CONNECTIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
8 EVACUATE AND DEHYDRATE THE SYSTEM. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
9 FINISHING. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
10 TEST RUN. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
11 PERIODIC MAINTENANCE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
12 TROUBLESHOOTING . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
13 UNIT PUMP DOWN. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
14 POWER SAVE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
1-EN
–1–
Outdoor Unit
1 DIMENSION
Installation Manual
5-drain hole
Ø0.8"(20) ~ 3.5"(88)
burring hole
14.4"(365)
0.7"(17.5) 0.7"(17.5)
21.0"(534)
25.8"(655)
21.0"(534)
14.2"(360)
5.0"(128)
Air intake
2.9"(74) 4.6"(118)
5.9"(150)
2.9"(74)
4.8"(121)
22.9"(581) 22.9"(581)
15.0"(380)
Air intake
3.0"(75)
Air discharge
15.1"(383)
21.7"(550)2.0"(52)
1.8"(46)
23.6"(600)
35.4"(900)
2.4"(60)7.9"(200)
1.3"(34)
A legs
2.8"(70)
Drain hole
1.0"(25) burring hole)
6.7"(170)
B legs
1.9"(48)
2.1"(54)
1.5"(39)
3.8"(96)
Refrigerant pipe connecting port (
Ø0.4”(9.5) flare at liquid side)
Refrigerant pipe connecting port
Ø0.6”(15.9) flare at gas side)
(
Conduit connection hole
Refrigerant piping knockout
5.1"(130)
24.1"(613)
23.8"(605)
0.5"(12)
1.2"(30)
2.0"(50)
Mounting bolt hole
Ø0.5"(12) × 0.7"(17) U-shape hole)
(
1.6"(40)
Mounting bolt hole
Ø0.5"(12) × 0.7"(17) long hole)
(
1.6"(40)
12.6"(320)
sgel B fo sliateD
sgel A fo sliateD
52.8"(1340)
2.4"(60) 7"(178)
2.7"(68)
2.7"(70)
3.3"(85)
Mounting hole sold separately
Ø0.1"(3) emboss)
(24 -
20.4"(518)
12.9"(327)
Knockout for bottom piping
7"(178)7"(178)
Z views
Z
0.3"(7)3.3"(83)
2.6"(65) 0.3"(7)
2.2"(56)
3.4"(85)
0.7"(18)
3.9"(99)
15.7"(400)
2.3"(58)
1.0"(24)
0.5"(12) 2.5"(64)
2.2"(55) 3.7"(95)
Refrigerant piping knockout
EN
–2–
2-EN
Outdoor Unit
2 ACCESSORY PARTS
Part name Q’ty Shape Usage
Installation manual 1 This manual (Hand this directly to the customer.)
Drain nipple 1
Waterproof rubber cap 5
Edge Guard 1 Protects piping against sharp edges
NOTE
Use drain nipple and waterproof rubber cap as necessary.
Installation Manual
3-EN
–3–
Outdoor Unit
3 SYSTEM REQUIREMENTS
Installation Manual
Piping (Field supplied)
• Minimum refrigerant line length between the outdoor unit and indoor unit is 16.5” (5 m)
• Maximum pipe lengths
Allowable
pipe length
(ft (m))
Total length LIndoor unit:
246’1” (75) 98’5” (30) 98’5” (30)
Figure of Single
Outdoor Unit
Refrigerant sizes
Liquid side Gas side
Outer
diameter
Ø3/8”
(9.5 mm)
Flare nuts and flaring
• The flare nuts and flaring are different from those for the conventional refrigerant. Use the flare nuts supplied with the air conditioner or those for R410A.
• Before performing flaring, carefully read “REFRIGERANT PIPING”
Insulation
Both lines need to be insulated. Use a minimum 0.4” (10 mm) wall thickness.
Height difference
(Indoor-outdoor H)
(ft (m))
Upper
Indoor Unit
L
Thickness
0.03”
(0.8 mm)
Outdoor unit:
Lower
H
Outer
diameter
Ø5/8”
(15.9 mm)
Number of
bent portions
10 or less
Thickness
0.04”
(1.0 mm)
Refrigerant charge
Length of refrigerant
pipe connected to
indoor/outdoor unit
9’10” - 98’5”
(3 - 30 m)
*98’5” - 246’1”
(30 - 75 m)
Additional refrigerant
None
Add 0.43 oz/ft (40 g/m) of refrigerant for piping that exceeds 98’5” (30 m) up to 246’1” (75 m).
* Caution during addition of refrigerant
Max. amount of additional refrigerant is 1.8 lbs (800 g). Charge the refrigerant accurately. Overcharging may cause serious trouble with the compressor.
* Minimum refrigerant pipe is 16’5”(5 m).
This may cause a malfunction of the compressor or other devices.
Metering Device is an electronic EXV (PMV) in outdoor unit.
Connecting power and control cables (Field supplied)
• The main power is supplied to the outdoor unit. The field supplied connecting cables from the outdoor unit to the indoor unit consist for 4 wires and provides the power for the indoor unit as well as the communication signal between the outdoor and indoor unit.
• System interconnection wire size must be AWG12.
• Breaker must have a capacity specified in the following table.
• All wiring must comply with local electric codes and NEC (National Electric Code) or CEC (Canadian Electric Code).
Model RAV- SP420 Power supply 208/230 V, 60 Hz MCA 24 A MOCP (MAX Fuse/CB) 40 A Breaker 25 A System interconnection wires AWG12
MCA = Minimum Circuit Amps MOCP =Maximum Over Protection Device Amps.
–4–
EN
4-EN
Outdoor Unit
Installation Manual
4 PRECAUTIONS FOR SAFETY
Installing, starting up, and servicing air--conditioning equipment can be hazardous due to system pressures, electrical components, and equipment location (roofs, elevated structures, etc.). Only trained, qualified installers and service mechanics should install, start--up, and service this equipment. Untrained personnel can perform basic maintenance functions such as cleaning coils. All other operations should be performed by trained service personnel. When working on the equipment, observe precautions in the literature and on tags, stickers, and labels attached to the equipment. Follow all safety codes. Wear safety glasses and work gloves. Keep quenching cloth and fire extinguisher nearby when brazing. Use care in handling, rigging, and setting bulky equipment. Read these instructions thoroughly and follow all warnings or cautions included in literature and attached to the unit. Consult local building codes and National Electrical Code (NEC) for special requirements. Recognize safety information. This is the safety--alert symbol . When you see this symbol on the unit and in instructions or manuals, be alert to the potential for personal injury.Understand these signal words: DANGER, WARNING, and CAUTION. These words are used with the safety--alert symbol. DANGER identifies the most serious hazards which will result in severe personal injury or death. WARNING signifies hazards which could result in personal injury or death. CAUTION is used to identify unsafe practices which may result in minor personal injury or product and property damage. NOTE is used to highlight suggestions which will result in enhanced installation, reliability, or operation.
WARNING
Ask an authorized dealer or qualified installation professional to install/maintain the air conditioner. Perform installation work properly according to the Installation Manual.
Inappropriate installation may result in water leakage, electric shock or fire.
Be sure to ground the equipment
Improper grounding may cause an electric shock. Do not connect ground wires to gas pipes, water pipes, lightning rods or ground wires for telephone wires.
Turn off the circuit breaker before attempting any electrical work and maintenance.
Make sure the circuit breaker is off. Failure to do so may cause electric shock. Use an exclusive power circuit for the air conditioner. Use the rated voltage.
When moving the air conditioner for installation to another place, be very careful not to allow the specified
refrigerant (R410A) to become mixed with any other gaseous body into the refrigeration cycle.
If air or any other gas mixes with the refrigerant, the gas pressure in the refrigeration cycle will become abnormally high and it may result in the pipe bursting or personal injuries.
Do not modify this unit by removing any of the safety guards or by by-passing any of the safety interlock
switches.
Do not touch the intake or aluminium fins of the outdoor unit.
Doing so may result in injury.
Tighten the flare nut with a torque wrench in the specified manner.
Excessive tightening of the flare nut may cause a crack in the flare nut after a long period, which may result in refrigerant leakage.
Install the air conditioner securely in a location where the base can sustain the weight of the unit adequately.
If refrigerant gas has leaked during the installation work, ventilate the room immediately.
If the leaked refrigerant gas comes in contact with fire, noxious gas may be generated.
After the installation work, confirm that refrigerant gas does not leak.
If refrigerant gas leaks into the room and flows near a fire source, such as a cooking range, noxious gas may be generated.
Electrical work must be performed by a qualified electrician in accordance with the NEC or local code. Make
sure the air conditioner uses an exclusive power supply.
An insufficient power supply capacity or inappropriate installation may cause fire.
Use only the specified wiring during the unit installation. Ensure that all terminals are securely fixed, so
preventing any external forces having a negative effect on the terminals.
5-EN
–5–
Outdoor Unit
Installation Manual
WARNING
When the air conditioner cannot cool or heat a room well, contact the dealer from whom you purchased the air conditioner as refrigerant leakage is considered as the cause. In the case of repair that requires refill of refrigerant, ask service personnel about details of the repair.
The refrigerant used in the air conditioner is harmless. Generally, the refrigerant does not leak. However, if the refrigerant leaks in a room and a heater or stove burner in the room catches fire, it may generate toxic gas. When you ask service personnel for repairing refrigerant leakage, confirm that the leakage portion has been completely repaired.
Do not install the air conditioner in a location that may be subjected to a risk of exposure to a combustible
gas.
If a combustible gas leaks and becomes concentrated around the unit, a fire may occur.
Install the refrigerant pipe securely during the installation work before operating the air conditioner. If the compressor is operated with the valve open and without the refrigerant pipe, the compressor sucks air and the refrigeration cycle is over pressurized, which may cause a burst or injury.
When carrying out the pump-down work, shut down the compressor before disconnecting the refrigerant
pipe.
Disconnecting the refrigerant pipe with the service valve left open and with the compressor still operating will cause air, etc. to be sucked in, raising the pressure inside the refrigeration cycle to an abnormally high level, and possibly resulting in rupturing, injury, etc.
CAUTION
Do not climb onto or place objects on top of the outdoor unit. You may fall or the objects may fall off of the outdoor unit and result in injury.
Wear heavy gloves during the installation work to avoid injury.
EQUIPMENT DAMAGE HAZARD
Failure to follow this caution may result in equipment damage or improper operation. Do not bury more than 36 in. (914 mm) of refrigerant pipe in the ground. If any section of pipe is buried, there must be a 6 in. (152 mm) vertical rise to the valve connections on the outdoor units. If more than the recommended length is buried, refrigerant may migrate to the cooler buried section during extended periods of system shutdown. This causes refrigerant slugging and could possibly damage the compressor at start-up.
–6–
EN
6-EN
Outdoor Unit
Installation Manual
5 INSTALLATION OF NEW REFRIGERANT
AIR CONDITIONER
CAUTION
New Refrigerant Air Conditioner Installation
THIS AIR CONDITIONER ADOPTS THE NEW HFC REFRIGERANT (R410A) WHICH DOES NOT DESTROY OZONE LAYER.
R410A refrigerant is apt to be affected by impurities such as water, oxidizing membrane, and oils because the working pressure of R410A refrigerant is approx. 1.6 times as that of refrigerant R22. Accompanied with the adoption of the new refrigerant, the refrigerant oil has also been changed. Therefore, during installation work, be sure that water, dust, former refrigerant, or refrigerant oil does not enter the new type refrigerant R410A air conditioner cycle. To prevent mixing of refrigerant or refrigerant oil, the sizes of connecting sections of charging port on main unit and installation tools are different from those of the conventional refrigerant units. Accordingly, special tools are required for the new refrigerant (R410A) units. For connecting pipes, use new and clean piping materials with high pressure fittings made for R410A only, so that water and/or dust does not enter.
Required Tools/Equipment and Precautions for Use
Prepare the tools and equipment listed in the following table before starting the installation work.
: R410A exclusive : Generic
Tools/equipment Use
Manifold gauge* Charging hose Gas leak detector Gas leak check Vacuum pump with backflow
prevention function Flare tool Flare machining of pipes Usable if dimensions are adjusted. Bender Bending pipes Refrigerant recovery equipment Refrigerant recovery Torque wrench Tightening flare nuts Ø1/2” (12.7 mm) and 5/8” (Ø15.9 mm) Pipe cutter Cutting pipes Brazing torch and nitrogen
cylinder Refrigerant charging scales Charging refrigerant 4 mm hexagon wrench Opening liquid valve
Vacuuming/charging refrigerant and operation check
Vacuum drying
Braze pipes
7-EN
–7–
Outdoor Unit
Installation Manual
Installation Location
WARNING
Install the outdoor unit in a location that can support the weight of the outdoor unit.
Insufficient durability may cause the outdoor unit to fall, which may result in injury.
CAUTION
Do not install the outdoor unit in a location that is subject to combustible gas leaks.
Accumulation of combustible gas around the outdoor unit may cause a fire.
Install the outdoor unit in a location that meets the following conditions.
• A well-ventilated location free from obstacles near the air inlets and air outlet
• A location that does not increase the operating noise or vibration of the outdoor unit
• A location that does not produce any drainage problems from discharged water
• Location with easy access to power.
Do not install the outdoor unit in the following location.
• A location with a saline atmosphere (coastal area) or one that is full of sulfide gas (hot-spring area) (Special maintenance is required.)
• A location subject to oil, vapor, oily smoke, or corrosive gases
• A location in which organic solvent is used
• A location where high-frequency equipment (including inverter equipment, private power generator, medical equipment, and communication equipment) is used (Installation in such a location may cause malfunction of the air conditioner, abnormal control or problems due to noise from such equipment.)
• A location in which the discharged air of the outdoor unit blows against the window of a neighboring house
• A location where the operating noise of the outdoor unit is transmitted
• When the outdoor unit is installed in an elevated position, be sure to secure its feet.
• A location in which drain water poses any problems.
When an outdoor unit is installed in a location that is always exposed to strong winds like a coast or on the high stories of a building, one of the following is recommended.
• Install the unit so that its discharge faces the wall of the structure. Keep a distance 19.7” (500 mm) or more between the unit and wall.
19.7" (500 mm)
• Install the unit so that the discharge is at a right angle relative to the wind direction.
Strong wind
Strong wind
• Use wind baffle. Produce those parts in the field.
• When outside temperature conditions are 23 °F (-5 °C) or lower and unit is running in cooling mode.
<Example>
Wind shield
Wind shield
Wind shield
–8–
EN
8-EN
Outdoor Unit
Installation Manual
Required Clearances Unit : in (mm)
Barrier at rear side
Upper side is free
1. Single unit installation
2. Barrier on right, left and rear.
The height of the
or more
7.9” (200)
5.9” (150) or more
3. Multiple units installation
5.9” (150) or more
The height of the obstacle should be lower than the height of the outdoor unit.
11.8” (300) or more
barrier should be lower than the height of the outdoor unit.
11.8” (300) or more
11.8” (300) or more
or more
5.9” (150)
11.8” (300) or more
Barrier in front
Above unit is free
1. Single unit installation
2. Multiple units installation
Barrier also above unit
7.9” (200) or more
39.4” (1000) or more
19.7”(500)
39.4” (1000)
or more
or more
39.4” (1000)
or more
Barrier also above unit
19.7” (500)
or more
9-EN
5.9” (150) or more
–9–
Outdoor Unit
Installation Manual
Barriers in front and back of unit
Open above and to the right and left of the unit. The height of an barrier in both the front and rear of the unit, should be lower than the height of the outdoor unit.
Standard installation
1. Single unit installation
5.9” (150)
or more
39.4” (1000)
or more
2. Multiple unit installation a. Intake and supply parallel
7.9” (200)
or more
Installation of Outdoor Unit
• Before installation, check the strength and horizontal of the base so that abnormal sounds do not emanate.
• According to the following base diagram, fix the base firmly with the anchor bolts. (Anchor bolt, nut: 3/8” (M10) x 4 pairs)
Drain hole
5.9” (150)
15.8” (400)
14.4” (365)
Drain nipple mounting hole
Drain hole
20.7” (525)
23.6” (600)
1.8” (45)
1) Field fabricate a snow or an ice stand for the unit using the above dimension.
2) Place snow or ice stand on a foundation/pad and secure it to the foundation/pad and secure it to the foundation/pad by anchor bolts.
5.9” (150)
11.8” (300) or more
b. Intake and supply in line
Open above and to the right and left of the unit. The height of an obstacle in both the front and rear of the unit should be lower than the height of the outdoor unit.
Standard installation
39.4” (1000) or more
11.8” (300) or more
59.1” (1500) or more
11.8” (300) or more
78.7” (2000) or more
7.9” (200) or more
39.4” (1000)
or more
NOTE
When the outdoor unit is anchored directly on the foundation/pad (cooling only protrude a minimum of 0.6” (15 mm)).
0.6” (15 mm) or less
EN
–10–
10-EN
Outdoor Unit
3) Place unit on stand. Make sure it is level and fasten securely to the stand.
• As shown in the figure below, install the foundation and vibration-proof rubber pads to directly support the bottom surface of the fixing leg that is in contact with the bottom plate of the outdoor unit.
• When installing the foundation for an outdoor unit with downward piping, consider the piping work.
GOOD
Drain nipple
Installation Manual
Waterproof rubber cap (5pcs.)
Mounting leg
Foundation
GOOD
Bottom plate
of outdoor unit
Foundation
Support the bottom surface of the mounting leg that is in contact with and underneath the bottom plate of the outdoor unit.
If only the end of the mounting leg is supported, it may deform.
Foundation
NO GOOD
• When water is to be drained through the drain hose, attach the following drain nipple and waterproof rubber cap, and use the drain hose (Inner diameter:
0.6” (16 mm)) sold on the market. Also seal the screws securely with silicone material, etc., to prevent water from leaking. Some conditions may cause condensation or dripping of water.
• When collectively draining discharged water completely, use a drain pan.
Do not support the outdoor unit only with the mounting leg.
Drain nipple
Waterproof rubber cap
For Reference
If a heating operation is to be continuously performed for a long time under the condition that the outdoor temperature is 32 °F (0 °C) or lower, draining defrosted water may be difficult due to the bottom plate freezing, resulting in trouble with the cabinet or fan.
11-EN
–11–
Outdoor Unit
6 REFRIGERANT PIPING
Installation Manual
Piping connections are inside the front panel of the unit and the front panel and pipe cover needs to be removed before piping and wiring connections are made.
Piping can enter the outdoor unit from the back, from the side or from the bottom as shown
Front panel
Pipe cover
Rear
Side
Bottom
1. Remove the front panel of the unit.
2. Remove the pipe cover.
3. Remove the appropriate knockout depending on the orientation of the piping.
The pipe cover is easily mounted by cutting off the slit at the lower part of the pipe cover.
Flaring
1. Cut the pipe with a pipe cutter. Be sure to remove burrs that may cause a gas leak.
2. Insert the supplied flare nut into the pipe, and then flare the pipe. As the flaring sizes of R410A differ from those of refrigerant R22, the flare tools newly manufactured for R410A are recommended.
However, the conventional tools can be used by adjusting the projection margin of the copper pipe.
Projection margin in flaring : B (Unit : in (mm))
Rigid (Clutch type)
Outer diameter of
copper pipe
3/8” (9.5)
5/8” (15.9)
R410A tool
used
R410A
0 - 0.02” (0 - 0.5)
Flaring diameter size : A (Unit : in (mm))
Outer diameter of copper pipe A
3/8” (9.5) 0.52” (13.2)
5/8” (15.9) 0.78” (19.7)
* In case of flaring for R410A with the
conventional flare tool, pull the tool out approx. 0.02” (0.5 mm) more than that for R22 to adjust it to the specified flare size. The copper pipe gauge is useful for adjusting the projection margin size.
Conventional
tool used
0.04” - 0.06” (1.0 - 1.5)
+0
-0.02"(–0.4)
A
B
* Be sure to wear heavy work gloves while working.
4. Remove the burrs from the knockout opening and use the factory supplied protective edge guard material around the opening to protect the piping and the wiring.
5. Remove the flare nut from the service valve on outdoor unit. Insert the flare nut into the field piping, and flare the pipe. Bend the pipe approx. 90 degree with a pipe bender for side and rear piping.
6. When the piping connections are complete re­install the pipe cover.
–12–
EN
12-EN
Outdoor Unit
Installation Manual
Tightening of Flare
Connections
1. Align the centers of the flare connections and fully tighten the flare nuts with your fingers.
Valve at liquid side
Cap
Loosened
2. Use two wrenches to loosen or tighten the flare nut on the gas service valve as shown in the figure. Use only one wrench to loosen or tighten the flare not on the liquid service valve. The final tightening with a torque wrench should be to the specifications shown in table below.
Outer diameter of copper pipe Tightening torque
3/8” (9.5 mm) 24 - 31 (33 - 42)
5/8” (15.9 mm) 50 - 60 (68 - 82)
Valve at gas side
Piping valve
Tightened
Flare nut
Unit : ft•lbs (N•m)
Cover
• After the installation work, be sure to check for gas leaks of the pipe connections with nitrogen.
NO GOOD
Charge orifice
Cover
CAUTION
1. Do not put the crescent wrench on the charge orifice or cover.
The valve may be broken.
2. If applying excessive torque, the nut may break according to some installation conditions.
• Pressure of R410A is higher than that of R22 (Approx. 1.6 times). Therefore, using a torque wrench, tighten the flare pipe connecting sections that connect the indoor/ outdoor units at the specified tightening torque. Incomplete connections may cause not only a gas leak, but also trouble with the refrigeration cycle.
Do not apply refrigerant oil to the flared surface.
Cap
Charge orifice
Loosened
13-EN
Piping valve
Flare nut
Tightened
–13–
Outdoor Unit
7 ELECTRICAL CONNECTIONS
Installation Manual
WARNING
ELECTRICAL SHOCK HAZARD Failure to follow this warning could result in
personal injury or death.
• The unit cabinet must have an uninterrupted or unbroken ground to minimize personal injury if an electrical fault should occur. The ground may consist of electrical wire or metal conduit when installed in accordance with existing electrical codes.
• Before performing service or maintenance, be sure main power switch is turned OFF.
CAUTION
All wiring and connections must comply with NEC, CEC, local codes.
UNIT DAMAGE HAZARD Failure to follow this caution may result in damage
or improper operation.
• Unit failure as a result of operation on improper line voltage or excessive phase imbalance constitutes abuse and may cause damage to electrical components.
• Wrong wiring may cause a burn-out of some electrical parts.
• Do not damage or scratch the conductive core or inner insulator of the power and inter-connecting wires when peeling them.
Electrical control box
Field wiring terminal blocks
Banding band
Conduit connection holes
Front panel
Field wiring
The dashed lines show field wiring.
(Field power supply)
Input power
208/230 V~, 60 Hz
circuit breaker
ground
• System interconnection wire size must be AWG12.
• Breaker must have a capacity specified in the following table.
• All wiring must comply with local electric codes and NEC (National Electric Code) or CEC (Canadian Electric Code).
Model RAV- SP420 Power supply 208/230 V, 60 Hz MCA 24 A MOCP (MAX Fuse/CB) 40 A Breaker 25 A System interconnection wires AWG12
MCA = Minimum Circuit Amps MOCP =Maximum Over Protection Device Amps.
• Connect the system interconnection (indoor to outdoor) wires to the identical terminal numbers on the terminal block of each unit. Incorrect connection may cause a failure.
1. With the front panel removed the electrical control
box is exposed at the top right corner of the unit.
2. Terminate the field wiring conduit (if used) at the
conduit connection holes provided.
3. Route the field power wires and the system
interconnection wires as shown on the following pages. Terminate the wires at field wiring terminal blocks located immediately below the electrical control box.
(System interconnection wires)
L
L
1
L
1
L
2
L
2
S
Outdoor unit Indoor unit
1
L
2
S
Remote controller
Front pipe cover
Piping knockout
–14–
EN
14-EN
Outdoor Unit
r
Installation Manual
Field power supply terminal block
L1L
2
Ground screw
System interconnection wires
Banding band
System interconncection terminal block
L1L2S
Ground screw
Field power supply wires
Wiring
1. Remove front panel and remove the front pipe cover.
2. Remove the wire cover from back of the front pipe cover.
Wire cover
Cable cove
3. Pass the wires through the conduit connection holes and attach the conduit connecters.
Remove the 4 screws.
Conduit connector
4. Connect the wires to the terminal blocks and fix the wires to the wiring guide with the 3 included banding
Front pipe cover
band.
Terminal block
Wire guide
Fix with the 3 banding band
15-EN
–15–
Outdoor Unit
Installation Manual
5. Pass the wires through the wiring guide of the front pipe cover and adjust the wire lengths.
Wiring guide
6. Attach the wire cover and hold the wires with the wiring guide hooks. Do not clip or damage the wires with the cover.
Fix with a screw.
Hook
8. Connect 2 conduits.
conduit
Wire cover
7. Attach the front pipe cover with 4 screws.
Fix with 4 screws.
EN
–16–
16-EN
Outdoor Unit
8 EVACUATE AND DEHYDRATE THE
SYSTEM
Installation Manual
CAUTION
UNIT DAMAGE HAZARD
Failure to follow this caution may result in equipment damage or improper operation. Never use the system compressor as a vacuum pump.
Refrigerant tubes and indoor heat exchanger should be evacuated using the recommended deep vacuum method of 500 microns. The alternate triple evacuation method may be used if the procedure outlined below is followed. Always break a vacuum with dry nitrogen.
SYSTEM VACUUM AND
CHARGE
Using Vacuum Pump
1. Completely tighten flare nuts A, B, C, D, connect manifold gage charge hose to a charge port of the low side service valve.
Service Valve
Outdoor Unit
A
Refrigerant
Low Side
Indoor Unit
C
6. After evacuation is complete, fully close the low side of manifold gage and stop operation of vacuum pump.
Deep Vacuum Method
The deep vacuum method requires a vacuum pump capable of pulling a vacuum of 500 microns and a vacuum gage capable of accurately measuring this vacuum depth. The deep vacuum method is the most positive way of assuring a system is free of air and liquid water.
Deep Vacuum Graph
5000
4500
4000
3500
3000
2500
2000
MICRONS
1500
1000
500
0
1 2 3 4 5 6 7
MINUTES
LEAK IN
SYSTEM
VACUUM TIGHT
TOO WET
TIGH T DRY
SYSTEM
D
Service Valve
B
High Side
2. Connect charge hose to vacuum pump.
3. Fully open the low side of manifold gage.
Manifold
500 microns
Low side valve
Charge hose
Manifold Gage
High side valve
Charge hose
Vacuum pump
Low side valve
4. Start vacuum pump.
5. Evacuate using either deep vacuum or triple evacuation method.
Triple Evacuation Method
The triple evacuation method should only be used when vacuum pump is only capable of pumping down to 28 in. of mercury vacuum and system does not contain any liquid water. Refer to “Triple Evacuation Method chart” and proceed as follows:
1. Pump system down to 28 in. of mercury and allow pump to continue operating for an additional 15 minutes.
2. Close service valves and shut off vacuum pump.
3. Connect a nitrogen cylinder and regulator to system and open until system pressure is 2 psig.
4. Close service valve and allow system to stand for 1 hr. During this time, dry nitrogen will be able to diffuse throughout the system absorbing moisture.
5. Repeat this procedure as indicated in the chart. System will then be free of any cotaminants and water vapor.
17-EN
–17–
Outdoor Unit
Installation Manual
Triple Evacuation Method chart
EVACUATE
BREAK VACUUM WITH DRY NITROGEN
WAIT
EVACUATE
BREAK VACUUM WITH DRY NITROGEN
WAIT
EVACUATE
CHECK FOR TIGHT, DRY SYSTEM
(IF IT HOLDS DEEP VACCUM)
RELEASE CHARGE INTO SYSTEM
Final Tubing Check
IMPORTANT:
Check to be certain factory tubing on both indoor and outdoor unit has not shifted during shipment. Ensure tubes are not rubbing against each other or any sheet metal. Pay close attention to feeder rubes, making sure wire ties on feeder tubes are secure and tight.
Open service valves
Open or close the valve.
Liquid side
Open the valve with a 4 mm hexagon wrench.
Gas side
Valve unit
Using a straight blade screwdriver, turn it 90° counter clockwise until the valve is fully open (against the stop).
Charge orifice
Flare nut
Handle position
Fully closed Fully opened
Stop pin
Main stopper
• While the valve is fully opened, after the screwdriver
has reached the stopper, do not apply torque exceeding 4 ft•lbs (5 N•m). Applying excessive torque may damage the valve.
Valve handling precautions
• Open the valve stem until it reaches the stop.
It is unnecessary to apply further force.
• Securely tighten the cap with a torque wrench.
• Cap tightening torque
Valve size
Charge port 10 - 13 ft•lbs (14 - 18 N•m)
Ø3/8” (9.5 mm) 24 - 31 ft•lbs (33 - 42 N•m) Ø5/8” (15.9 mm) 15 - 18 ft•lbs (20 - 25 N•m)
EN
–18–
18-EN
Outdoor Unit
Installation Manual
9 FINISHING
After the refrigerant pipe, inter-unit wires, and drain pipe have been connected, make sure they are supported and fixed in place for the entire length. Keep the power wires and system interconnection wires away from all factory wiring and piping.
10TEST RUN
Turn on the circuit breaker at least 12 hours before starting the system to preheat the compressor and prevent damage.
To protect the compressor, power is supplied from the 208/230 VAC input to the unit to preheat the compressor.
Check the following before starting a test run:
That all pipes are connected securely without leaks.
That the valve is open.
If the compressor is operated with the valve closed, the outdoor unit will become over pressurized, which may damage the compressor or other components. If there is a leak at a connection, air can be sucked in and the internal pressure further increases, which may cause a burst or injury.
• Operate the air conditioner using the correct procedure as specified in the Owner’s Manual.
11PERIODIC MAINTENANCE
• For an air conditioning system that is operated on a regular basis, cleaning and maintenance of the indoor/ outdoor units are strongly recommended. As a general rule, if an indoor unit is operated for about 8 hours daily, the indoor/outdoor units will need to be cleaned at least once every 3 months. This cleaning and maintenance should be carried out by a qualified service person. Failure to clean the indoor/outdoor units regularly will result in poor performance, icing, water leaking and even compressor failure.
19-EN
–19–
Outdoor Unit
Installation Manual
12TROUBLESHOOTING
You can perform fault diagnosis of the outdoor unit with the LEDs on the P.C. board of the outdoor unit in addition to using the check codes displayed on the wired remote controller of the indoor unit. Use the LEDs and error codes for various checks. Details of the error codes displayed on the wired remote controller of the indoor unit are described in the Installation Manual of the indoor unit.
Verifying Error code status (Outdoor control board)
1. Check that DIP switch SW803 is set to off.
2. Record the states (on or off) of LED 800 to LED 804
(Display mode 1).
3. Press SW800 for at least 1 second. The LED status
changes to display mode 2.
4. Since display mode 1 covers multiple errors with the
same code display, mode 2 must also be used to determine the final error. Use the status recorded for LED 800 to LED 804 in display mode 1 (Item 2 above) and combine it with the status for the same LED’s in display mode 2 (Item 3 above) to determine the complete error code using the chart below.
No. Cause
1Normal
2 Discharge (TD) sensor error
3 Heat exchanger (TE) sensor error
4 Heat exchanger (TL) sensor error
5 Outside air temperature (TO) sensor error
6 Suction (TS) sensor error
7 Heat sink (TH) sensor error
Outdoor temperature sensor (TE/TS) connection
8
error
9 Outdoor EEPROM error
10 Compressor lock
11 Compressor lock
12 Current detection circuit error
13 Thermostat for compressor activated
Model data not set
14
(on the service P.C. board)
15 MCU-MCU communication error
16
Discharge temperature error
Abnormal power
17
(open phase detected or abnormal voltage)
18 Heat sink overheat
19 Gas leak detected
20 4-way valve reverse error
21 High pressure release operation
D800 D801 D802 D803 D804 D800 D801 D802 D803 D804
●●●●●●●●●●
{{●●{ ●● ●●
{{●●{ ●●
{{●●{ ●●
{{●●{ ●●●
{{●●{ ●●
{{●●{ ●●
{{●●{
{{●●{
●●{ { ●●●●
●●{ { ●●
●●{ { ●●●
●●{ { ●● ●●
{{ { ●●●
{{ {
{{{ { ●●●
{{{ { ●●
{{{ { ●●
{{{ {
{{{ { ●●
{{{ { ●●
Verifying Error code status stored in memory (Outdoor control board)
1. Check that DIP switch SW803 is set to on.
2. Record the states (on or off) of LED 800 to LED 804 (Display mode 1).
3. Press SW800 for at least 1 second. The LED status changes to display mode 2.
4. Since display mode 1 covers multiple errors with the same code display, mode 2 must also be used to determine the final error. Use the status recorded for LED 800 to LED 804 in display mode 1 (Item 2 above) and combine it with the status for the same LED’s in display mode 2 (Item 3 above) to determine the complete error code using the chart below.
NOTE
An outside air temperature (TO) sensor error can be checked only when an error occurs.
Display mode 1 Display mode 2
EN
–20–
20-EN
Outdoor Unit
Installation Manual
22 Outdoor fan motor error
23 Compressor driver short-circuit protection
24 Position detection circuit error in one-line display
{{{ { ●●
{{{ { ●●
{{{ {
(:OFF {:ON :Flashing)
* The LEDs and DIP switches are located on the lower left of the P.C. board of the outdoor unit.
ON
SW804
SW801
1234
SW800
D800 D801 D802 D803 D804 D805
LED
Enlarged view
of LEDs
D800 D801 D802 D803
SW803
1234
ON
SW802
1234
ON
D804 D805
21-EN
–21–
Outdoor Unit
Installation Manual
13UNIT PUMP DOWN
• Use the pump down switch SW801 on the P.C. board of the outdoor unit to pump down the unit.
Procedure
1. Turn on the power of the air conditioner.
2. Select the FAN mode for indoor unit operation with the remote controller.
3. Set SW804 on the P.C. board of the outdoor unit to all OFF, and then press SW801 for 1 second or more. The air conditioner enters the forced cooling mode for up to 10 minutes. Pump down the unit during this 10 minutes.
4. Upon completion of pump down the unit, close the valve and press SW801 for at least 1 second to stop operation.
5. Turn off the power.
Refrigerant recovery switch SW801
Optional connector CN610
Special operation select switch SW804
Power save switch SW802
P.C. board
1234
ON
ON
1234
DANGER
Be careful of electric shock because the P.C. board has an electrical current running through it.
14POWER SAVE
• Power save can be set by setting SW802 dip switch.
Procedure
1. Turn on the SW802 dip switch 2 to activate Power save.
Power save controls reducing compressor periodicity (by approx. 10%) depending on the indoor unit heat exchanger temperature in heating operation
SW802
... Power save setting
1234
ON
* All switches are OFF as factory default.
Do not touch SW802 dip switch 1, 3 and 4. If any changes are made, the unit may not work properly.
CAUTION
–22–
EN
22-EN
EH99865501