Toshiba CARRIER RAV-SP180CT-UL, CARRIER RAV-SP300CT-UL, CARRIER RAV-SP240CT-UL, CARRIER RAV-SP360CT-UL, CARRIER RAV-SP420CT-UL Installation Manual

AIR CONDITIONER (SPLIT TYPE)
Installation Manual
Indoor Unit
Model name:
Under Ceiling Type
RAV-SP180CT-UL RAV-SP240CT-UL RAV-SP300CT-UL RAV-SP360CT-UL RAV-SP420CT-UL
Not accessible to the general public
Vente interdite au grand public
Installation Manual Air conditioner
(Split type) 1
(Type split) 33
English
Français
Under Ceiling Type
Please read this Installation manual carefully before installing the Air Conditioner.
• This Manual describes the installation method of the indoor unit.
• For installation of the outdoor unit, follow the Installation Manual attached to the outdoor unit.
Installation Manual
ADOPTION OF NEW REFRIGERANT
This Air Conditioner uses R410A an environmentally friendly refrigerant.
Contents
1 ACCESSORY PARTS. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
2 PRECAUTIONS FOR SAFETY. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
3 SELECTION OF INSTALLATION PLACE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
4 REFRIGERANT PIPING AND EVACUATING . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
5 DRAIN PIPING WORK . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
6 ELECTRICAL CONNECTION. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
7 APPLICABLE CONTROLS. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
8 TEST RUN. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
9 TROUBLESHOOTING . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
1-EN
–1–
Under Ceiling Type
Installation Manual
1 ACCESSORY PARTS
Accessory parts
Part name Q’ty Shape Usage
Owner’s Manual 1 – Installation Manual 1 This manual – Installation pattern 1 Drawing-out port of hanging bolt pipe
Thermal insulation pipe 2 For thermal insulation of pipe connecting section
Washer 4 3/8” (M10) × Ø1.0” (25 mm) For holding down unit
Hose band 2 For connecting drain pipe
Drain hose 1 For connecting drain pipe
Bushing Ø2.2” (Ø56) 1 For protection of edge at hole for remote control wires
Bushing Ø1.1” (Ø28) 1 For sealing the back side conduit hole
Thermal insulator 1
Thermal insulator of top plate
Banding band 2 For prevention of open of drain hose thermal insulator
1
For thermal insulation of drain hose (0.4” - thickness × 7.9” × 7.9” (10 - thickness × 200 × 200 mm))
For upper pipe hole of indoor unit (0.2” - thickness × 5.1” × 6.3” (6 - thickness × 130 × 160 mm))
–2–
EN
2-EN
Under Ceiling Type
Installation Manual
2 PRECAUTIONS FOR SAFETY
Installing, starting up, and servicing air--conditioning equipment can be hazardous due to system pressures, electrical components, and equipment location (roofs, elevated structures, etc.). Only trained, qualified installers and service mechanics should install, start--up, and service this equipment. Untrained personnel can perform basic maintenance functions such as cleaning heat exchanger. All other operations should be performed by trained service personnel. When working on the equipment, observe precautions in the literature and on tags, stickers, and labels attached to the equipment. Follow all safety codes.Wear safety glasses and work gloves. Keep quenching cloth and fire extinguisher nearby when brazing. Use care in handling, rigging, and setting bulky equipment. Read these instructions thoroughly and follow all warnings or cautions included in literature and attached to the unit. Consult local building codes and National Electrical Code (NEC) for special requirements. Recognize safety information. This is the safety--alert symbol . When you see this symbol on the unit and in instructions or manuals, be alert to the potential for personal injury.Understand these signal words: DANGER, WARNING, and CAUTION. These words are used with the safety--alert symbol. DANGER identifies the most serious hazards which will result in severe personal injury or death. WARNING signifies hazards which could result in personal injury or death. CAUTION is used to identify unsafe practices which may result in minor personal injury or product and property damage. NOTE is used to highlight suggestions which will result in enhanced installation, reliability, or operation.
WARNING
Ask an authorized dealer or qualified installation professional to install (including moving)/maintain the air conditioner.
Inappropriate installation may result in water leakage, electric shock or fire.
Be sure to connect ground wire. (grounding work) Incomplete grounding cause an electric shock. Do not connect ground wires to gas pipes, water pipes, lightning rods or ground wires for telephone wires.
Turn off the circuit breaker before attempting any electrical work. Make sure all circuit breaker is off. Failure to do so may cause electric shock.
Install the refrigerant pipe securely during the installation work before operating the air conditioner. If the air conditioner is operated with the valve open and without the refrigerant pipe, the compressor sucks air and the refrigeration cycle is overpressurized, which may cause a burst or injury.
When moving the air conditioner for the installation into another place, be very careful not to enter any
gaseous matter other than the specified refrigerant into the refrigeration cycle.
If air or any other gas is mixed in the refrigerant, the gas pressure in the refrigeration cycle becomes abnormally high and it resultingly causes pipe burst and injuries on persons.
Perform installation work properly according to the Installation Manual. Inappropriate installation may result in water leakage, electric shock or fire.
When the air conditioner is installed in a small room, provide appropriate measures to ensure that the
concentration of refrigerant leakage occur in the room does not exceed the critical level.
Install the air conditioner securely in a location where the base can sustain the weight adequately.
Perform the specified installation work to guard against an earthquake. If the air conditioner is not installed appropriately, accidents may occur due to the falling unit.
If refrigerant gas has leaked during the installation work, ventilate the room immediately. If the leaked refrigerant gas comes in contact with fire, noxious gas may generate.
After the installation work, confirm that refrigerant gas does not leak. If refrigerant gas leaks into the room and flows near a fire source, such as a cooking range, noxious gas might generate.
Electrical work must be performed by a qualified electrician in accordance with the Installation Manual. Make
sure the air conditioner uses an exclusive power supply.
An insufficient power supply capacity or inappropriate installation may cause fire.
Use the specified wires for wiring connect the terminals securely fix.
To prevent external forces applied to the terminals from affecting the terminals.
3-EN
–3–
Under Ceiling Type
Conform to the regulations of the local electric company when wiring the power supply. Inappropriate grounding may cause electric shock.
For the refrigerant recovery work (collection of refrigerant from the pipe to the compressor), stop the
compressor before disconnecting the refrigerant pipe.
If the refrigerant pipe is disconnected while the compressor is working with the valve open, the compressor sucks air and the refrigeration cycle is overpressurized, which may cause a burst or injury.
Installation Manual
CAUTION
THIS AIR CONDITIONER ADOPTS THE NEW HFC REFRIGERANT (R410A) WHICH DOES NOT DESTROY OZONE LAYER.
• The characteristics of R410A refrigerant are ; easy to absorb water, oxidizing membrane or oil, and its pressure is approx. 1.6 times higher than that of refrigerant R22. Accompanied with the new refrigerant, refrigerating oil has also been changed. Therefore, during installation work, be sure that water, dust, former refrigerant, or refrigerating oil does not enter the refrigerating cycle.
• To prevent charging an incorrect refrigerant and refrigerating oil, the sizes of connecting sections of charging port of the main unit and installation tools are changed from those for the conventional refrigerant.
• Accordingly the exclusive tools are required for the new refrigerant (R410A).
• For connecting pipes, use new and clean piping designed for R410A, and please care so that water or dust does not enter.
Tighten the flare nut with a torque wrench in the specified manner. Excessive tightening of the flare nut may cause a crack in the flare nut after a long period, which may result in refrigerant leakage.
Wear heavy gloves during the installation work to avoid injury.
The installation fuse must be used for the power supply line of this conditioner.
–4–
EN
4-EN
Under Ceiling Type
Installation Manual
3 SELECTION OF INSTALLATION PLACE
WARNING
Install the air conditioner at enough strong place to withstand the weight of the unit.
If the strength is not enough, the unit may fall down resulting in injury.
Install the air conditioner at a height 8’ (2.4 m) or
more from the floor.
If you insert your hands or others directly into the unit while the air conditioner operates, it is dangerous because you may contact with revolving fan or active electricity.
CAUTION
Do not install the air conditioner in a location subject to a risk of exposure to a combustible gas.
If a combustible gas leaks and stays around the unit, a fire may occur.
Upon approval of the customer, install the air conditioner in a place that satisfies the following conditions.
• Place where the unit can be installed horizontally.
• Place where a sufficient servicing space can be ensured for safety maintenance and check.
• Place where drained water will not cause any problem.
Avoid installing in the following places.
• Place exposed to air with high salt content (seaside area), or place exposed to large quantities of sulfide gas (hot spring). (Should the unit be used in these places, special protective measures are needed.)
• Place exposed to oil, vapor, oil smoke or corrosive gas.
• Place where organic solvent is used nearby.
• Place close to a machine generating high frequency.
• Place where the discharged air blows directly into the window of the neighbor house. (Outdoor unit)
• Place where noise of the outdoor unit is easily transmitted. (When install the outdoor unit on the boundary with the neighbor, pay due attention to the level of noise.)
• Place with poor ventilation. (Before air ducting work, check whether value of fan speed, static pressure and duct resistance are correct.)
Installation space
Secure the specified space in the figure for installation and servicing.
Unit: in (mm)
9.8” (250) or more
19.7” (500) or more
9.8” (250) or more
Height of ceiling
Set the installable height of the ceiling within 13’1” (4 m), otherwise the air distribution will become poor. If height of ceiling exceeds 11’6” (3.5 m), hot air becomes difficult to reach the floor surface, and then the change of setup of high ceiling is necessary. For the change method of high ceiling, refer to the application control, “In case of installation to high ceiling” and “In case of incorporating filter sold separately” in this Manual.
List of installable ceiling height
Setup data
0000
0001 High ceiling 1
According to the conditions of installation, setup time of turning-on of filter sign (notification of filter cleaning) of the remote control can be changed. When it is difficult to warm up the room due to installation place or structure of the room, the detection temperature of heating can be raised. For change the setup time, refer to the application control, “Change of filter sign turning-on time” and “How to increase the heating effect” in this Manual.
Standard
(Factory default)
11’6” (3.5 m) or less
more than 11’6” (3.5 m)
up to 13’1” (4.0 m)
5-EN
–5–
Under Ceiling Type
Installation Manual
Wireless remote control
Decide the position which remote control is operated and the installation place. And then refer to the Installation Manual of the wireless remote controller kit sold separately. (The signal of the wireless type remote control can be received within approx. 23’ (7 m). This distance is a criterion and varies a little according to capacity of the battery, etc.)
• To prevent malfunction, select a place where is not affected by a fluorescent lamp or direct sunlight.
• Two or more (up to 6 units) wireless-type indoor units can be set in a room.
A
p
p
r
o
x
.
2
3
(
7
m
)
2 Removing wire guard
Remove the screws (2 pcs.) which are fixing the wire guard. Remove the clamp fixing screws and remove the wire guard.
Clamps
Screw
CAUTION
Attach back the wire guard once indoor unit is installed. Remove the 2 screws fixing the wire guard and hung the wire guard with the clamps during a service.
Before installation
1 Removal of suction grille
Slide the suction grille fixing knobs (2 positions) toward the arrow direction, and then open the suction grille. Under the condition of suction grille opened, push the hook section of hinges (2 positions) at the rear side, and then pull out the suction grille.
Hinge
Suction grille fixing knob
Suction grille
Pull out suction grille while pushing hook.
Wire guard
S
l
i
d
e
EN
–6–
6-EN
Under Ceiling Type
3 Removal of side panel
After removing the side panel fixing screws (1 each at right and left), slide the side panel forward and then remove it.
Protector
Side panel
Level louver
Slide forward.
4 Removal of protective vinyl
Peel out the protective vinyl on the level louver.
Installation Manual
5 Removal of protector
Remove the protector (1 pcs.) of the fan. (RAV-SP240CT only)
External view
REQUIREMENT
Strictly comply with the following rules to prevent damage of the indoor units and human injury.
• Do not put a heavy article on the indoor unit. (Even units are packaged)
• Carry in the indoor unit as it is packaged if possible. If carrying in the indoor unit unpacked by necessity, be sure to use buffering cloth, etc. to not damage the unit.
• Do not apply force to the other parts (refrigerant pipe, drain pan, foamed parts, or resin parts, etc.).
• Carry the package by two or more persons, and do not bundle it with plastic band at positions other than specified.
7-EN
–7–
Under Ceiling Type
Upper pipe draw-out port (knockout)
Hole for remote control wires (knockout)
3.3” (84)
6.7” (170)
(Hole for power supply cable. knockout)
12.6” (320)
Left drain size
Conduit hole
2.8”
(70)
Refrigerant pipe (Liquid side ØC)
Refrigerant pipe (Gas side ØD)
B (Hanging position)
3.0” (75)
5.3” (135)
2.1”
(53)
12.2” (311)
10.3” (262)
1.5” (39)
2.0” (52)
8.5” (216)
5.7” (146)
13.7” (347)
3.5”
(90)
4.3” (110)
3.0” (76)
4.1” (105)
5.1” (130)
Drain pipe connecting port
3.8” (97)
8.3” (210)
2.0” (50)
26.8” (680)
7.9” (200) (Liquid pipe)
Hole for remote control wires
Conduit hole (knockout)
3.6” (92)
1.3” (32)
Installation Manual
Unit: in (mm)
6.6” (167)
Pipe draw-out port (knockout)
Drain port VP20 (Inner dia. Ø1.0” (26), hose attached)
4.5” (114)
5.6” (141)
8.5” (216) (Gas pipe)
3.3” (84)
Hanging bolt
Within
2.0” (50)
Ceiling surface
Unit
Pipe hole on wall (Ø3.9” (100) hole)
A
Outside air take-in port (Duct sold separately) Knockout hole Ø3.6” (92))
5.7” (145) Hole for power supply cable
Left drain pipe draw-out port (knockout)
Wireless sensor mounting section
Unit: in (mm)
Model name A B C D
180CT
240CT
300CT, 360CT to 420CT
35.8” (910)
46.5”
(1180)
62.8”
(1595)
33.7” (855)
44.3”
(1125)
60.6”
(1540)
Ø1/4”
(6.4)
Ø3/8”
(9.5)
Ø1/2” (12.7)
Ø5/8” (15.9)
Considering pipe/wire connecting work inside the ceiling after the indoor unit has been hanged, select an installation place and determine piping direction.
• If the ceiling has already been set before hanging the main unit, prepare refrigerant pipe, drain pipe, indoor connecting wire, remote control cord, etc. up to the place where pipe and wire can be connected.
• Check the size of the indoor unit, and match the indoor unit size using the attached installation pattern.
6.7” (171)
EN
–8–
8-EN
Under Ceiling Type
Installation Manual
Using attached installation pattern
Ceiling surface Wall face
Installation pattern
Using the pattern, positioning of the hanging bolt and pipe hole can be performed. * As an error to some degree may generate on the
pattern size due to temperature and humidity, be sure to confirm the size.
Installation of hanging bolts
Use 3/8” (M10) hanging bolts (4 pcs, to be local procure). Matching to the existing structure, set pitch according to size in the unit external view as shown below.
New concrete slab
Install the bolts with insert brackets or anchor bolts.
Rubber
(Blade type
bracket)
Use existing angles or install new support angles.
(Slide type
bracket)
Steel flame structure
Hanging bolt
Anchor bolt
(Pipe hanging
anchor bolt)
Pipe knockout hole
• Piping from rear side
* Cut off the groove section with a plastic cutter, etc.
Rear cover
100
Opened when
Grooves
Opened when only drain pipe is taken out from the rear side
• Piping from right side
* Cut off the groove section with a metal saw or
plastic cutter, etc.
• Piping from left side Taking pipe from left side is applied only to the drain pipe. The refrigerant pipe cannot be taken out from the left side.
* Cut off the groove section with a metal saw or
plastic cutter, etc.
refrigerant pipe is taken out from the rear side
Groove
Side panel (Right side)
Hanging bolt Support angle
Existing concrete slab
Use a hole-in anchors, hole-in plugs, or a hole-in bolts.
Draw-out direction of pipe/
wire
• Decide installation place of the unit and draw-out direction of pipe and wire.
9-EN
Groove
Piping from upper side
Taking pipe from upper side is applied only to the refrigerant pipe. When taking out the drain pipe from the upper side, use a drain up kit sold separately.
Open the upper pipe draw-out port (Knockout hole) shown in the external view. (Knockout hole of thin plate) After piping, cut off the attached thermal insulator of the top plate to pipe shape, and then seal the knockout hole.
–9–
Side panel (Left side)
Under Ceiling Type
Installation Manual
Installation of indoor unit
• Preparation before holding down main unit
* Confirm the presence of the ceiling material
beforehand because the fixing method of hanging metal when the ceiling material is set differs from that when the ceiling material is not set.
There is ceiling material
Hanging bolt (Procured locally)
Indoor
unit
Hanging metal
Nut (Procured locally)
Indoor
unit
Hanging metal
* Tighten the hanging metal with upper/lower nuts
as shown in the figure.
There is no ceiling material
Indoor
unit
• Holding down of main unit
(1) Attach washer and nuts to the hanging bolt.
Ceiling surface
Ceiling surface
Washer (Accessory)
Double nut (Procured locally)
Hanging bolt (Procured locally)
Ceiling surface
Washer (Accessory)
Double nut (Procured locally)
Hanging bolt (Procured locally)
Washer (Procured locally)
Washer (Accessory)
Double nut (Procured locally)
2.0” (50 mm)
(2) Hang the unit to the hanging bolt as shown the
figure below.
(3) As shown in the figure below, fix the ceiling material
securely with the double nuts.
REQUIREMENT
• The ceiling surface may not be horizontal. Be sure to confirm that width and depth directions are level.
Installation of remote control (Sold separately)
For installation of the wired remote control, follow the Installation Manual attached with the remote control.
• Pull out the remote control cord together with the refrigerant pipe or drain pipe. Be sure to pass the remote control cord through upper side of the refrigerant pipe and drain pipe.
• Do not leave the remote control at a place exposed to the direct sunlight and near a stove.
• Operate the remote control, confirm that the indoor unit receives a signal surely, and then install it. (Wireless type)
• Keep 3’3” (1 m) or more from the devices such as television, stereo, etc. (Disturbance of image or noise may generate.) (Wireless type)
Washer (Accessory)
Hanging bolt
Double nut (Procured locally)
0.8” - 1.2”
(20 - 30 mm)
–10–
EN
10-EN
Under Ceiling Type
Installation Manual
4 REFRIGERANT PIPING AND EVACUATING
Refrigerant Piping
• The connecting sections of the refrigerant pipes are provided at the positions in the figure below.
Upper side
Right
Rear side
1. Use copper pipe with 0.03” (0.8 mm) or more
thickness. (In case pipe size is Ø5/8” (15.9 mm), with 0.04” (1.0 mm) or more.)
2. Flare nut and flare works are also different from
those of the conventional refrigerant. Take out the flare nut attached to the main unit of the air conditioner, and use it.
REQUIREMENT
When the refrigerant pipe is long, provide support brackets at intervals of 8’2” - 9’10” (2.5 - 3 m) to clamp the refrigerant pipe. Otherwise, abnormal sound may be generated.
* When using the drain
pump kit sold separately, the pipe can be drawn out only from the upper side.
Permissible Piping Length
and Height Difference
They vary according to the outdoor unit. For details, refer to the Installation Manual attached to the outdoor unit.
Flaring
• Cut the pipe with a pipe cutter. Remove burrs completely. Remaining burrs may cause gas leakage.
• Insert a flare nut into the pipe, and flare the pipe. As the flaring sizes of R410A differ from those of refrigerant R22, the flare tools newly manufactured for R410A are recommended.
However, the conventional tools can be used by adjusting projection margin of the copper pipe.
Projection margin in
flaring: B (Unit: in (mm))
Rigid (Clutch type)
Outer dia. of
copper pipe
1/4” - 5/8”
(6.4 - 15.9)
R410A tool used
0 - 0.02” (0 - 0.5)
Conventional
tool used
0.04” - 0.06” (1.0 - 1.5)
B
CAUTION
IMPORTANT 4 POINTS FOR PIPING WORK
1. Remove dust and moisture from the inside of the connecting pipes.
2. Tight connection (between pipes and unit)
3. Evacuate the air in the connecting pipes using VACUUM PUMP.
4. Check the gas leakage. (Connected points)
Pipe size
Model name
Pipe size
RAV-
Gas side
Liquid side
SP180
type
1/2"
(12.7 mm)
1/4"
(6.4 mm)
SP240, SP300, SP360, SP420 type
5/8"
(15.9 mm)
3/8"
(9.5 mm)
Outer dia. of copper pipe
1/4” (6.4) or 3/8” (9.5) 0.06” - 0.08” (1.5 - 2.0)
1/2” (12.7) or 5/8” (15.9) 0.08” - 0.1” (2.0 - 2.5)
Imperial
(Wing nut type)
Flaring dia. meter size: A (Unit: in (mm))
Outer dia. of copper pipe A
1/4” (6.4) 0.36” (9.1)
3/8” (9.5) 0.52” (13.2) 1/2” (12.7) 0.65” (16.6) 5/8” (15.9) 0.78” (19.7)
+0
-0,02" (–0.4)
* In case of flaring for R410A with the
conventional flare tool, pull it out approx.
0.02” (0.5 mm) more than that for R22 to adjust to the specified flare size. The copper pipe gauge is useful for adjusting projection margin size.
A
11-EN
–11–
Under Ceiling Type
Installation Manual
Tightening connection
CAUTION
• Do not apply excessive torque. Otherwise, the nut may crack depending on the conditions.
(Unit: ft•lbs (N•m))
Outer dia. of copper
Tightening torque of flare pipe connections
pipe
1/4” (6.4 mm) 10 -13 (14 - 18)
3/8” (9.5 mm) 24 - 31 (33 - 42) 1/2” (12.7 mm) 37 - 46 (50 - 62) 5/8” (15.9 mm) 46 - 57 (63 - 77)
Pressure of R410A is higher than that of R22. (Approx. 1.6 times) Therefore, using a torque wrench, tighten the flare pipe connecting sections which connect the indoor and outdoor units of the specified tightening torque. Incorrect connections may cause not only a gas leak, but also a trouble of the refrigeration cycle. Align the centres of the connecting pipes and tighten the flare nut as far as possible with your fingers. Then tighten the nut with a spanner and torque wrench as shown in the figure.
Tightening torque
Flare at outdoor unit side
Flare at indoor unit side
Evacuation
Using a vacuum pump, perform vacuuming from the charge port of valve of the outdoor unit. For details, follow to the Installation Manual attached to the outdoor unit.
• Never use the refrigerant sealed in the outdoor unit for air purge.
REQUIREMENT
For the tools such as charge hose, etc., use those manufactured exclusively for R410A.
Refrigerant amount to be added
For addition of the refrigerant, add refrigerant “R410A” referring to the attached Installation Manual of outdoor unit. Be sure to use a scale to charge the refrigerant of specified amount.
REQUIREMENT
• Charging an excessive or too little amount of refrigerant causes a trouble of the compressor. Be sure to charge the refrigerant of specified amount.
• A personnel who charged the refrigerant should write down the pipe length and the added refrigerant amount in the nameplate attached to the service panel of the outdoor unit. It is necessary to troubleshooter the compressor and refrigeration cycle malfunction.
Half union Flare nut
Externally threaded side
Use a wrench to secure. Use a torque wrench to tighten.
REQUIREMENT
Tightening with an excessive torque may crack the nut depending on installation conditions. Tighten the nut within the specified tightening torque.
Piping with outdoor unit
• Shape of valve differs according to the outdoor unit. For details of installation, refer to the Installation Manual of the outdoor unit.
Internally threaded side
Open the valve fully
Open the valve of the outdoor unit fully. For details, refer to the Installation Manual attached to the outdoor unit.
Gas leak check
Check with a leak detector or soap water whether gas leaks or not, from the pipe connecting section or cap of the valve.
REQUIREMENT
Use a leak detector manufactured exclusively for HFC refrigerant (R410A, R134a, etc.).
–12–
EN
12-EN
Under Ceiling Type
Thermal insulation process
Apply thermal insulation for the pipes separately at liquid side and gas side. For the thermal insulation to the pipes at gas side, be sure to use the material with heat-resisting temperature 248 °F (120 °C) or higher. Using the attached thermal insulation material, apply the thermal insulation to the pipe connecting section of the indoor unit securely without gap.
REQUIREMENT
• Apply the thermal insulation to the pipe connecting section of the indoor unit securely up to the root without exposure of the pipe. (The pipe exposed to the outside causes water leak.)
• Wrap heat insulator with its slits facing up (ceiling side).
Wrap the pipe with the attached heat insulator without any gap between the indoor unit.
Indoor unit
The seam must be faced upward (ceiling side).
Installation Manual
Heat insulation pipe (Accessory)
Union
Flare nut
Heat insulator of the pipe
13-EN
–13–
Under Ceiling Type
5 DRAIN PIPING WORK
Installation Manual
CAUTION
Following the Installation Manual, perform the drain piping work so that water is properly drained, and apply a heat insulation so as not to cause a dew dropping. Inappropriate piping work may result in water leakage in the room and wet of furniture.
Piping/Heat insulating
material
Require the following materials for piping and heat insulating at site.
Piping
Heat insulator
REQUIREMENT
• Be sure to perform heat insulation of the drain pipes of the indoor unit.
• Never forget to perform heat insulation of the connecting part with the indoor unit. An incomplete heat insulation causes dew dropping.
• Set the drain pipe with downward slope (1/100 or more), and do not make swelling or trap on the piping. It may cause an abnormal sound.
• For length of the traversing drain pipe, restrict 65’7” (20 m) or less. In case of a long pipe, provide support brackets with interval of 4’11” - 6’7” (1.5 - 2 m) in order to prevent waving.
Hard vinyl chloride pipe VP20 (Outer dia.: Ø1.0” (26 mm))
Foam polyethylene: Thickness 0.4” (10 mm) or more
4’11” - 6’7” (1.5 - 2 m)
1/100 or more downward
Support bracket
• Set the collective piping as shown in the below figure.
As long as possible (3.9” (100 mm))
VP20
VP30 or more
VP20 VP20
Downward slope 1/100 or more
<Collective piping>
Extended ventilating pipe
• Be sure not to apply force to the connecting part of the drain pipe.
• The hard vinyl-chloride pipe cannot be directly connected to the drain pipe connecting port of the indoor unit. For connection with the drain pipe connecting port, be sure to use/fix the attached flexible hose with the hose band, otherwise a damage or water leak is caused on the drain pipe connecting port.
Drain pipe connecting
port (Hard socket)
Drain pan
Adhesive agent
prohibited
Attached flexible hose
Attached hose bandAttached hose band
Soft socketSoft socket
VP20 vinyl chloride pipe
(procured locally)
Adhesive inhibited:
Use the attached flexible hose and hose band for connecting the drain hose to the clear drain socket. If applying the adhesive, socket will be damaged and cause water leakage.
Thermal insulator
Arched shape
Trap
NO
GOOD
Drain up
When not securing down slope on the drain pipe, use a Drain pump kit sold separately. Also refer to the “Drain pump kit installation manual”. The drain pipe can be raised 23.6” (600 mm) from the top face of the main unit. * When using Drain pump kit, both drain pipe and
refrigerant pipe can be taken only from upper side.
* VP25 PVC pipe is needed when a drain pump is
used.
–14–
EN
14-EN
Under Ceiling Type
Installation Manual
Connection of drain hose
• Insert the attached drain hose into the drain pipe connecting port on the drain pan up to the end.
• Fit the attached hose band to the end of the pipe connecting port, and then tighten it securely.
REQUIREMENT
• Be sure to fix the drain hose with the attached hose band, and set the tightening position upward.
• As the draining is the natural water draining, arrange the pipe outside of the unit on the down slope.
• If piping is performed as shown in the figure, drain cannot be discharged.
NO GOOD
Drain pipe
Fit the attached hose band to the end of the hose, lay down the knob, and then tighten hose band.
Refrigerant pipe
Drain pipe
Connection of drain pipe
• Connect the hard vinyl chloride pipe (procured locally) to the mounted drain hose which was attached.
• Piping from left side
• In case of taking pipe from the left side, exchange
the plug from left to right. Push in the plug of which end is not sharp up to the end.
Drain pan
Plug
Drain pan
Attached drain hose
Confirm that soft hose is pushed in up to the end of the drain pan.
Thermal insulating process
• Using the attached drain hose thermal insulator, lap the connecting section and the drain hose without clearance, and then tighten with two handing band so that thermal insulator does not open.
• Covering the attached drain hose thermal insulator, lap the thermal insulator (procured locally) to the drain pipe without clearance.
Lap covering connecting section between drain pan and drain hose.
Drain hose
Drain pan
Hose band
* Tighten the banding band so that
attached thermal insulator is not pushed excessively.
Banding band
Attached thermal insulator
Hose band
Thermal insulator (procured locally)
Lap the attached thermal insulation so that the one end is put on the other end at the upper side.
15-EN
–15–
Under Ceiling Type
6 ELECTRICAL CONNECTION
Installation Manual
WARNING
1. Using the specified wires, ensure to connect the wires, and fix wires securely so that the external tension to the wires do not affect the connecting part of the terminals.
Incomplete connection or fixation may cause a fire, etc.
2. Be sure to connect ground wire. (grounding work)
Incomplete grounding cause an electric shock. Do not connect ground wires to gas pipes, water pipes, lightning rods or ground wires for telephone wires.
3. Appliance shall be installed in accordance with national wiring regulations.
Capacity shortage of circuit breaker or incomplete installation may cause an electric shock or a fire.
CAUTION
• Consult local building codes, NEC (National Electrical
Code) or CEC (Canadian Electrical Code) for special requirements.
• This indoor unit has no power cord.
• If incorrect/incomplete wiring is carried out, it will
cause an electrical fire or smoke.
• Be sure to install circuit breaker is not tripped by shock
waves. If circuit breaker is not installed, an electric shock may be caused.
• Be sure to use the cord clamps attached to the
product.
• Do not damage or scratch the conductive core and
inner insulator of power and system interconnection wires when peeling them.
• Use the power cord and system interconnection wire
of specified thickness, type, and protective devices required.
REQUIREMENT
• For power supply wiring, strictly conform to the Local Regulation in each country.
• For wiring of power supply of the outdoor units, follow the Installation Manual of each outdoor unit.
• Never connect 208/230 V power to the terminal blocks (A, B etc.) for control wiring. (Otherwise, the system will fail.)
• Perform the electric wiring so that it does not come to contact with the high-temperature part of the pipe. The coating may melt resulting in an accident.
• Run the refrigerant piping line and control wiring line in the same line.
• Do not turn on the circuit breaker of the indoor unit until vacuuming of the refrigerant pipes completes.
Remote control wiring
• For single system, use 2 x AWG20 non polarity wire is used for the remote control wiring.
Wiring
1. Connect the connecting wire to the terminal as
identified with their respective numbers on the terminal block of indoor and outdoor unit. (4
x AWG12)
2. Insulate the unsheathed redundant cords
(conductors) with electrical insulation tape. Process them so that they do not touch any electrical or metal parts.
3. For inter-unit wiring, do not use a wire jointed to
another on the way.
Wire Quantity x size Indoor unit - Outdoor unit *1 3 x AWG12 (polar) Ground 1 x AWG12 or thicker Remote control 2 x AWG20 (non-polar)
*1 :Length of the system interconnection wires.
RAV- SP180AT2 SP240AT2
Wire
length
164’1” (50 m) or less
229’8” (70 m) or less
–16–
SP300AT2 -
SP420AT2
246’1” (75 m) or
less
EN
16-EN
Under Ceiling Type
CAUTION
Use the same size wire for the field power supply wire and system interconnection wires when the outdoor unit is RAV-SP180AT2.
NOTE
• Use copper supply wires.
• Use UL wires rated 600 V for the system interconnection wires.
• Use UL wires rated 300 V for the remote control wires.
Installation Manual
17-EN
–17–
Under Ceiling Type
Installation Manual
Wire connection
REQUIREMENT
• Be sure to connect the wires matching the terminal numbers. Incorrect connection causes a trouble.
• The low-voltage circuit is provided for the remote control. (Do not connect the high-voltage circuit)
• Loosen the cover mounting screws (2 positions) of the electric parts box, and then remove the cover.
• Attach the conduit pipe to the conduit hole with a lock nut.
• Slit the film of bushing attached to the hole for remote control wire, and then pass through wires.
• Connect the system interconnection wires and the remote control wire to the terminal block of the electric parts box. Secure the ground wire with the ground screw.
• Tighten screws of the terminal block securely, and fix the wires with code clamp attached to the electric parts box. (Do not apply tension to the connecting section of the terminal block.)
• Mount the cover of the electric parts box so that it does not pinch the wires.
Electric parts box
Terminal block for wired remote control
Wire partition plate Pass the remote control wire through the hole for remote control wire and behind this wire partition plate.
Two screws
A
B
P.C. board
Terminal block for system interconnection
L
1
L
2
S
Terminal block
Ground screw
System interconnection wires and ground wire
Cord clamp
Remote control wires
Hole for Remote control wires
Conduit hole
–18–
EN
18-EN
Under Ceiling Type
Installation Manual
CAUTION
Fix the system interconnection wires and the remote control wires separately with the cord clamps as shown below.
Connected at backside
Cord clamp
Conduit pipe
Cord clamp
Hole for remote control wires
Connected at upside
Conduit hole for system interconnection wires
Conduit hole (knockout) for system interconnection wires
Hole for remote control wires (knockout)
Attach the supplied bushing to cover the hole edge.
19-EN
Cord clamp
Attach the supplied bushing to seal the back side conduit hole.
–19–
Cord Clamp
Cord Clamp
Under Ceiling Type
Installation Manual
System interconnection
Wires and Ground Wire
1. Strip wire ends.
System interconnection wire : 0.4” (10 mm). Ground wire : 0.8” (20 mm)
2. Match wire colours with terminal numbers on indoor
and outdoor units’ terminal blocks and firmly screw wires to the corresponding terminals.
3. Secure the ground wire with the ground screw.
4. Fix the wire with cord clamp.
Unit: in (mm)
0.8” (20)
Ground wire
0.4” (10)
Connecting wire
L
1
S
L
2
CAUTION
Remote Control Wiring
• Strip off approx. 0.4” (9 mm) the wire to be connected.
• Non polarity, 2 x AWG20 wire is used for wiring of the remote control.
Terminal block for remote control wiring of indoor unit
A B
Remote control wire (Procured locally)
Terminal block
Remote
A
control
B
unit
Wiring Diagram
Single system
Indoor unit
Low voltage
A B
Remote control
Outdoor unit
208/230-1-60
L
1
L
2
S
High voltage
L
1
L
2
S
• Firmly tighten the screws of the terminal block.
Keep the wire length as shown in figure below when it is connected to the terminal block.
0.08” (2 mm) or less
System interconnection wire
EN
–20–
20-EN
Under Ceiling Type
7 APPLICABLE CONTROLS
Installation Manual
REQUIREMENT
• When you use this air conditioner for the first time, it takes approx. 5 minutes until the remote control becomes available after power-on. This is normal.
<When power is turned on for the first time after installation>
It takes approx. 5 minutes until the remote control becomes available.
Approx. 5 minutes
Power on
<When power is turned on for the second (or later) time>
It takes approx. 1 minute until the remote control becomes available.
Power on
• Normal settings were made as factory default. Change the indoor unit settings as required.
• Use the wired remote control to change the settings.
* The settings cannot be changed using the
“SETTING” flashes
“SETTING” flashes
wireless remote control, sub remote control, or remote-controlless system (for central remote control only). Therefore, install the wired remote control to change the settings.
“SETTING” goes out
Approx. 1 minutes
“SETTING” goes out
Remote control is available
Remote control is available
Changing applicable control
setting
Basic procedure for changing settings
Change the settings while the air conditioner is not working. (Be sure to stop the air conditioner before making settings.)
4
6
1
Procedure 1
When pushing , , and buttons simultaneously for 4 seconds or more, after a while, the display part flashes as shown in the figure. Check that the displayed CODE No. is [10].
• If the CODE No. indicates other than [10], push button to erase the display, and then retry the operation from the first step. (For some time after button has been pushed, the operation of the remote control cannot be accepted.)
(In a group control, the firstly displayed indoor UNIT No. becomes the master unit.)
3
5
2
21-EN
(* Display content varies with
the indoor unit model.)
Procedure 2
Every pushing button, the indoor UNIT No. in the group control is displayed successively. Select an indoor unit of which setup to be changed. In this time, the position of the indoor unit of which setup to be changed can be confirmed because the fan and the louver of the selected indoor unit work.
Procedure 3
Using temp. setup / buttons, specify CODE No. [ ].
Procedure 4
Using timer time / buttons, select SET DATA [
].
–21–
Under Ceiling Type
Installation Manual
Procedure 5
Push button. In this time, if the display changes from flashing to lighting, the setup completes.
• To change the setup of an indoor unit other than the selected one, start operation from Procedure
• To change the setup of another setup in the selected indoor unit, start operation from Procedure
Pushing button clears the set up contents which have been already set. In this case, retry from Procedure
2.
2.
3.
Procedure 6
When settings have been completed, push button to determine the settings. When button is pushed, “SETTING” flashes and then the display content disappears and the air conditioner enters the normal stop mode. (While “SETTING” is flashing, no operation of the remote control is accepted.)
Installation to high ceiling
When the height of the ceiling to be installed exceeds
3.5 m (11’6”), adjustment of fan speed is necessary.
Set up the high ceiling.
• Set according to the basic operation procedure (
1 2 3 4 5 6).
• Item code in Procedure specifies [5d].
• Select [SET DATA] in Procedure from “List of installable ceiling height” in this Manual.
• For the item code in Procedure
• For the SET DATA in Procedure data of static pressure to be set up from the table on the right.
(Exchange by wired remote control)
3, specify [5d].
4, select the setup
Using wireless remote control
Change the high ceiling setting with the DIP switch on the P.C. board of the signal receiving part. Refer to the installation manual of the wireless remote controller kit for the details. High ceiling setting can be changed by arranging the jumper block on the indoor unit micro computer P.C. board as shown in the table below as well.
* However, once the setting is changed, it is
necessary to reset the setting back to 0000 that placing the jumper block back to the factory default position and rewriting the setting data back to 0000 with wired remote control (sold separately). (The setting can be changed to 0001, 0003 and 0006 without resetting.)
• Select by exchange of jumper block on indoor microcomputer P.C. board.
jumper block
position
SET DATA Note
Short Open
0000
0001 High static pressure 1
• Jumper block position (CN112, CN111, CN110 from the left)
Standard filter (Factory default)
SET DATA
0000
0001 High static pressure 1
Standard
(Factory default)
11’6” (3.5 m) or less
more than 11’6” (3.5 m)
up to 13’1” (4.0 m)
–22–
EN
22-EN
Under Ceiling Type
Installation Manual
Filter sign setting
According to the installation condition, the lighting time of the filter sign (Notification of filter cleaning) can be changed. Follow to the basic operation procedure (
1 2 3 4 5 6).
• For the CODE No. in Procedure
• For the [SET DATA] in Procedure
3, specify [01].
4, select the setup
data of filter sign lighting time from the following table.
Setup data Filter sign lighting time
0000 None 0001 150H 0002 2500H (Factory default) 0003 5000H 0004 10000H
To secure better effect of
heating
When it is difficult to obtain satisfactory heating due to installation place of the indoor unit or structure of the room, the detection temperature of heating can be raised. Also use a circulator, etc. to circulate heat air near the ceiling. Follow to the basic operation procedure (
1 2 3 4 5 6).
• For the CODE No. in Procedure
• For the SET DATA in Procedure data of shift value of detection temperature to be set up from the table below.
Setup data Detection temp shift value
0000 No shift 0001 +1.8 °F (+1 °C)
0002
0003 +5.4 °F (+3 °C) 0004 +7.2 °F (+4 °C) 0005 +9.0 °F (+5 °C) 0006 +10.8 °F (+6 °C)
+3.6 °F (+2 °C)
(Factory default)
3, specify [06].
4, select the setup
Group control
Group control for system of multiple units
One remote control can control maximum 8 indoor units as a group.
Group control in single system
Outdoor
unit
Indoor
unit
Remote
control
Outdoor
unit
Indoor
unit
Finish of address setup by power-ON
Outdoor
unit
Indoor
unit
• For wiring procedure and wiring method of the individual line (Identical refrigerant line) system, follow to “Electric work”.
• Wiring between lines is performed in the following procedure. Connect the terminal block (A/B) of the indoor unit connected with a remote control to the terminal blocks (A/B) of the indoor units of other indoor units by wiring the inter-unit wire of the remote control.
• When the power supply has been turned on, the automatic address setup starts and “ ” display which indicates that address is being set up flashes on the display part. During setup of automatic address, the remote control operation is not accepted.
Required time up to the finish of automatic addressing is approx. 5 minutes.
NOTE
In some cases, it is necessary to change the address manually after setup of the automatic address according to the system configuration of the group control.
Procedure example 1
Manual address setup procedure
While the operation stops, change the setup. (Be sure to stop the operation of the unit.)
Outdoor
unit
Indoor
unit
Outdoor
unit
Indoor
unit
(Max. 8 units)
23-EN
–23–
Under Ceiling Type
3
-2,
4
-2,
5
-2
7 3
4 5
Installation Manual
Indoor UNIT No. before setup change is displayed.
-1,
-1,
-1,
7
2,61
Procedure 1
Push simultaneously + + buttons for 4 seconds or more. After a while, the display part flashes as shown below. Check the displayed CODE No. is [10].
• When the CODE No. is other than [10], push
button to erase the display and repeat procedure from the first step. (After pushing control is not accepted for approx. 1 minute.) (For a group control, No. of the firstly displayed indoor unit becomes the header unit.)
Procedure 2
Every pushing button, the indoor UNIT No. in the group control is displayed in order. Select the indoor unit of which setup is changed. In this time, the position of the indoor unit of which setup is changed can be confirmed because fan and louver of the selected indoor unit operate.
Procedure 3
1. Using temp. setup / buttons, specify CODE
No. [12]. (CODE No. [12]: Line address)
2. Using timer time / buttons, change the line
address from [3] to [2].
3. Push button. In this time, the setup finishes when the display changes from flashing to lighting.
button, operation of the remote
(* Display changes according to
the model No. of indoor unit.)
3
4 5
-3,
-3,
-3,
Procedure 4
1. Using temp. setup / buttons, specify CODE
No. [13]. (CODE No. [13]: Indoor address)
2. Using timer time / buttons, change the indoor
address from [3] to [2].
3. Push button. In this time, the setup finishes when the display changes from flashing to lighting.
Indoor UNIT No. before setup change is displayed.
Procedure 5
1. Using temp. setup / buttons, specify CODE No. [14]. (CODE No. [14]: Group address)
2. Using timer time / buttons, change the setup data from [0001] to [0002]. (Setup data [Header unit: 0001] [Follower unit: 0002])
3. Push button. In this time, the setup finishes when the display changes from flashing to lighting.
Indoor UNIT No. before setup change is displayed.
–24–
EN
24-EN
Under Ceiling Type
Procedure 6
If there is other indoor unit to be changed, repeat procedure When the above setup has finished, push to select the indoor UNIT No. before change of setup, specify CODE No. [12], [13], [14] in order with temp. setup / buttons, and then check the changed contents.
Address change check Before change: [3-3-1] After change: [2-2-2]
2 to 5 to change the setup.
1,3
Installation Manual
1
2
Pushing button clears the contents of which setup was changed. (In this case, procedure from
Indoor UNIT No. before setup change is displayed.
2 is repeated.)
Procedure 7
After check of the changed contents, push button. (Setup is determined.) When pushing display disappears and the status becomes the usual stop status. (When pushing from the remote control is not accepted for approx. 1 minute.) * If the operation from the remote control is not
accepted even 1 minute or more passed after pushing setup is incorrect. In this case, the automatic address must be again set up. Therefore repeat procedure of the setup change from the Procedure
button, it is considered that the address
button the operation
1.
button, the
To recognize the position of the corresponding indoor unit though the indoor UNIT No. is known
Check the position during operation stop. (Be sure to stop operation of the set.)
Procedure 1
Push simultaneously + buttons for 4 seconds or more. After a while, the display part flashes and the display appears as shown below. In this time, the position can be checked because fan and louver of the indoor unit operate.
• For the group control, the indoor UNIT No. is
displayed as [ ] and fans and louvers of all the indoor units in the group control operate.
Check the displayed CODE No. is [01].
• When the CODE No. is other than [01], push
button to erase the display and repeat procedure from the first step. (After pushing control is not accepted for approx. 1 minute.)
button, operation of the remote
(* Display changes according to
the model No. of indoor unit.)
Procedure 2
In the group control, every pushing button, the indoor UNIT No. in the group control is displayed in order. In this time, the position of the indoor unit can be confirmed because only fan of the selected indoor unit operate. (For a group control, No. of the firstly displayed indoor unit becomes the header unit.)
Procedure 3
After confirmation, push button to return the mode to the usual mode. When pushing the status becomes the usual stop status. (When pushing remote control is not accepted for approx. 1 minute.)
button, the display disappears and
button the operation from the
25-EN
–25–
Under Ceiling Type
Installation Manual
Remote control switch
monitoring function
This function is available to call the service monitor mode from the remote control during a test run to acquire temperatures of sensors of the remote control, indoor unit, and outdoor unit.
1. Push and 4 seconds to call the service monitor mode. The service monitor indicator lights up and the header indoor unit number is displayed first. CODE No. is also displayed.
2. Pushing TEMP. buttons, select the number of sensor, etc. (CODE No.) to be monitored. (See the following table.)
3. Pushing indoor unit to be monitored. The sensor temperatures of indoor units and their outdoor unit in the control group are displayed.
4. Push
button to return to the normal display.
buttons simultaneously for at least
(left side of the button), select an
Outdoor unit data
CODE No. Data name
60
61 Outside air temperature (TO) 62 Compressor discharge air temperature (TD) 63 Compressor intake air temperature (TS) 64 65 Heatsink temperature (THS)
6A Operating current (x1/10)
F1
Outdoor unit heat exchanger temperature
(TE)
Compressor cumulative operating hours
(x100h)
2
4
13
Indoor unit data
CODE No. Data name
01 Room temperature (remote control) 02 Indoor unit intake air temperature (TA)
03
04
F3
F8 Indoor unit discharge air temperature
Indoor unit heat exchanger temperature
(TCJ)
Indoor unit heat exchanger temperature
(TC)
Indoor unit fan cumulative operating hours
(x1 h)
–26–
EN
26-EN
Under Ceiling Type
8 TEST RUN
Installation Manual
Before test run
• Before turning on the circuit breaker, carry out the
following procedure.
1) Using 500V-megger, check 1MΩ or more exists between the terminal block L ground. If 1MΩ or less is detected, do not run the unit. Do not apply to the remote control circuit.
2) Check the valve of the outdoor unit being opened fully.
• To protect the compressor at activation time, leave power-ON for 12 hours or more be for operating.
1 to L2 and the
Execute a test run
Using the remote control, operate the unit as usual. For the procedure of the operation, refer to the attached Owner’s Manual. A forced test run can be executed in the following procedure even if the operation stops by thermo.-OFF. In order to prevent a serial operation, the forced test run is released after 60 minutes have passed and returns to the usual operation.
CAUTION
Procedure 2
Push button.
Procedure 3
Using button, select the operation mode, [COOL] or [HEAT].
• Do not run the air conditioner in a mode other than [COOL] or [HEAT].
• The temperature controlling function does not work during test run.
• The detection of error is performed as usual.
Procedure 4
After the test run, push button to stop a test run. (Display part is same as procedure 1.)
Procedure 5
Push check button to cancel (release from) the test run mode. ([TEST] disappears on the display and the status returns to a normal.)
• Do not use the forced test run for cases other than the test run because it applies an excessive load to the devices.
Wired remote control
2, 4 3
1,5
Procedure 1
Keep button pushed for 4 seconds or more. [TEST] is displayed on the display part and the selection of mode in the test mode is permitted.
27-EN
–27–
Under Ceiling Type
Installation Manual
Wireless remote control
Procedure 1
Turn on the circuit breaker of the air conditioner. The operation is not accepted for 5 minutes when circuit breaker is turned on at first time after installation, and 1 minute when circuit breaker is turned on at the next time and after. After the specified time has passed, perform a test operation.
Procedure 2
Push “ON/OFF” button on the remote control, select [COOL] or [HEAT] with “MODE” button, and then select [HIGH] with “FAN” button.
Procedure 3
Cooling test run Heating test run Set the temperature to 64°F
(18°C) with the temp. setup
buttons.
Procedure 4
Cooling test run Heating test run
After confirming a signal receiving sound “beep” immediately set the temperature to 66 °F (19°C) with the temp. setup buttons.
Set the temperature to 86 °F (30°C) with the temp. setup buttons.
After confirming a signal receiving sound “beep” immediately set the temperature to 84 °F (29°C) with the temp. setup buttons.
Heating test run:
ON/OFF 86 °F (30°C) 84 °F (29°C) 86 °F (30°C) 84 °F (29°C) 86 °F (30°C) 84 °F (29°C) 86 °F (30°C) (test run) ON/OFF
Always select [HIGH] fan speed.
2
3, 4,
5, 6
2
2,7
Procedure 5
Cooling test run Heating test run
After confirming a signal receiving sound “beep” immediately set the temperature to 64 °F (18°C) with the temp. setup buttons.
After confirming a signal receiving sound “beep” immediately set the temperature to 86 °F (30°C) with the temp. setup buttons.
Procedure 6
Repeat procedures 4 5 4 5. Indicators “Operation” (green), “Timer” (green), and “Ready” (orange) in the wireless receiver section flash in approx. 10 seconds, and the air conditioner starts operation. If any of these indicators does not flash, repeat procedures
2 to 5.
Procedure 7
Upon completion of the test run, push “ON/OFF” button to stop operation.
<Overview of test run operations using the wireless remote control>
Cooling test run:
ON/OFF 64 °F (18 °C) 66 °F (19°C) 64 °F (18°C) 66 °F (19°C) 64 °F (18°C) 66 °F (19°C) 64 °F (18°C) (test run) ON/OFF
EN
–28–
28-EN
Under Ceiling Type
9 TROUBLESHOOTING
Installation Manual
Confirmation and check
When a trouble occurred in the air conditioner, the check code and the indoor UNIT No. appear on the display part of the remote control. The check code is only displayed during the operation. If the display disappears, operate the air conditioner according to the following “Confirmation of error history” for confirmation.
Check code
Indoor UNIT No. in which an error occurred
Confirmation of error history
When a trouble occurred on the air conditioner, the trouble history can be confirmed with the following procedure. (The trouble history is stored in memory up to 4 troubles.) The history can be confirmed from both operating status and stop status.
Procedure 2
Every pushing of button used to set temperature, the trouble history stored in memory is displayed in order. The numbers in CODE No. indicate CODE No. [01] (latest) [04] (oldest).
REQUIREMENT
Do not push button because all the trouble history of the indoor unit will be deleted.
Procedure 3
After confirmation, push button to return to the usual display.
1. Check the troubles according to the above procedure.
2. Ask an authorized dealer or qualified service (maintenance) professional to repair or maintain the air conditioner.
2
3
Procedure 1
When pushing and buttons at the same time for 4 seconds or more, the following display appears. If [Service check] is displayed, the mode enters in the trouble history mode.
•[01: Order of trouble history] is displayed in CODE
No. window.
• [Check code] is displayed in CHECK window.
• [Indoor unit address in which an error occurred] is displayed in Unit No..
1
29-EN
–29–
Under Ceiling Type
Check codes and parts to be checked
Installation Manual
Wired remote control display
Indication
E01
E02
E03
E04
E08
E09
E10
E18
E31
F01 ALT
F02 ALT
F04 ALT
F06 ALT
F07
(F06)
F08 ALT
F10 ALT
F12
(F06)
F13
(L29)
F15
(F06)
F29 SIM
Wireless remote control
Sensor block display of
receiving unit
Operation Timer Ready GR GR OR
Main defective parts
Flashing
No header remote control
Remote control communication error
Remote control transmission error
Indoor unit-remote control regular communication error
Indoor unit-outdoor unit serial communication error
IPDU-CDB communication error
Duplicated indoor addresses
Duplicated header remote controls
CPU-CPU communication error
Header indoor unit­indoor follower unit regular communication error
IPDU communication error
Indoor unit heat exchanger sensor (TCJ) error
Indoor unit heat exchanger sensor (TC) error
Outdoor unit discharge temp. sensor (TD) error
Outdoor unit temp. sensor (TE/TS) error
ALT TL sensor error Outdoor
Outdoor unit outside air temp. sensor error
Indoor unit room temp. sensor (TA) error
ALT TS sensor error Outdoor
ALT Heat sink sensor error Outdoor
Temp. sensor
ALT
connection error
Indoor unit, other P.C. board error
Judging
device
Remote control
Remote control
Indoor
Indoor
Indoor
Remote control
Indoor
Indoor
Outdoor Communication error between IPDU and CDB Entire stop
Indoor
Indoor
Outdoor
Outdoor
Outdoor
Indoor
Outdoor Temp. sensor (TE/TS) may be connected incorrectly. Entire stop
Indoor Indoor P.C. board --- EEPROM error Auto-reset
Parts to be checked / error description
Incorrect remote control setting --- The header remote control has not been set (including two remote controls).
No signal can be received from the indoor unit.
System interconnection wires, indoor P.C. board, remote control
--- No signal can be sent to the indoor unit.
Remote control, network adapter, indoor P.C. board --­No data is received from the remote control or network adapter.
System interconnection wires, indoor P.C. board, outdoor P.C. board --- Serial communication error between indoor unit and outdoor unit
Indoor address setting error --- The same address as the self-address was detected.
Remote control address setting error --- Two remote controls are set as header in the double-remote control control.
(* The header indoor unit stops raising alarm and follower indoor units continue to operate.)
Indoor P.C. board --- Communication error between main MCU and motor microcomputer MCU
Indoor P.C. board --- Regular communication is not possible between header and follower indoor units or between twin header (main) and follower (sub) units.
Heat exchanger sensor (TCJ) , indoor P.C. board --­Open-circuit or short-circuit of the heat exchanger sensor (TCJ) was detected.
Heat exchanger sensor (TC), indoor P.C. board --- Open­circuit or short-circuit of the heat exchanger sensor (TC) was detected.
Outdoor temp. sensor (TD), outdoor P.C. board --- Open­circuit or short-circuit of the discharge temp. sensor was detected.
Outdoor temp. sensors (TE/TS), outdoor P.C. board --­Open-circuit or short-circuit of the heat exchanger temp. sensor was detected.
TL sensor may be displaced, disconnected or short­circuited.
Outdoor temp. sensor (TO), outdoor P.C. board --- Open­circuit or short-circuit of the outdoor air temp. sensor was detected.
Room temp. sensor (TA), indoor P.C. board --- Open­circuit or short-circuit of the room temp. sensor (TA) was detected.
TS sensor may be displaced, disconnected or short­circuited.
Abnormal temperature was detected by the temp. sensor of the IGBT heat sink.
Air
conditioner
status
*
*
Auto-reset
Auto-reset
Auto-reset
*
Auto-reset
Auto-reset
Auto-reset
Auto-reset
Entire stop
Entire stop
Entire stop
Operation continued
Auto-reset
Entire stop
Entire stop
EN
–30–
30-EN
Under Ceiling Type
Installation Manual
F31
(L29)
H01
H02
H03
H04
(P04)
H06
L03 SIM
L07 SIM
L08 SIM
L09 SIM
L10
(L29)
L20 SIM
L29 SIM
L30 SIM
L31 SIM
P01 ALT Indoor unit fan error Indoor
P03 ALT
P04 ALT
P05
(P04)
P07 ALT Heat sink overheat Outdoor
P10 ALT
P15
(L29)
P19
(L29)
P20
(P04)
Outdoor unit P.C.
SIM
board
Outdoor unit compressor breakdown
Outdoor unit compressor lock
Outdoor unit current detect circuit error
Case thermostat operation
Outdoor unit low­pressure system error
Duplicated header indoor units
Group line in individual indoor unit
Indoor group address not set
Indoor power level not set
Outdoor unit P.C.
SIM
board
LAN communication error
Other outdoor unit error
Abnormal external input into indoor unit (interlock)
Phase sequence error, etc.
Outdoor unit discharge temp. error
Outdoor unit high­pressure system error
ALT Open phase detected Outdoor
Indoor unit water overflow detected
ALT Gas leakage detected Outdoor
ALT 4-way valve error
High-pressure
ALT
protective operation
Outdoor Outdoor P.C. board ---- In the case of EEPROM error. Entire stop
Outdoor
Outdoor
Outdoor
Outdoor Malfunction of the case thermostat Entire stop
Outdoor
Indoor
Indoor
Indoor
Indoor Indoor power level has not been set. Entire stop
Outdoor
Network adapter central control
Outdoor
Indoor
Outdoor
Outdoor
Outdoor
Indoor
Outdoor (Indoor)
Outdoor High-pressure protection Entire stop
Current detect circuit, power voltage --- Minimum frequency was reached in the current releasing control or short-circuit current (Idc) after direct excitation was detected Wiring error of compressor (open phase)
Compressor circuit --- Compressor lock was detected. Wiring error of compressor (open phase)
Current detect circuit, outdoor unit P.C. board --­Abnormal current was detected in AC-CT or a phase loss was detected.
Current, high-pressure switch circuit, outdoor P.C. board
--- Ps pressure sensor error was detected or low-pressure protective operation was activated.
Indoor address setting error --- There are two or more header units in the group.
Indoor address setting error --- There is at least one group-connected indoor unit among individual indoor units.
Indoor address setting error --- Indoor address group has not been set.
In the case of outdoor P.C . board jumper wire (for service) setting error
Address setting, central control remote control, network adapter --- Duplication of address in central control communication
Other outdoor unit error Entire stop
1) Communication error between IPDU MCU and CDB MCU
2) Abnormal temperature was detected by the heat sink temp. sensor in IGBT.
External devices, outdoor unit P.C. board --- Abnormal stop due to incorrect external input into CN80
Power supply phase sequence, outdoor unit P.C. board -
-- Abnormal phase sequence of the 3-phase power supply
Indoor fan motor, indoor P.C. board --- Indoor AC fan error (fan motor thermal relay activated) was detected.
An error was detected in the discharge temp. releasing control.
High-pressure switch --- The IOL was activated or an error was detected in the high-pressure releasing control using the TE.
The power cable may be connected incorrectly. Check open phase and voltages of the power supply.
Abnormal temperature was detected by the temp. sensor of the IGBT heat sink.
Drain pipe, clogging of drainage, float switch circuit, indoor P.C. board --- Drainage is out of order or the float switch was activated.
There may be gas leakage from the pipe or connecting part. Check for gas leakage.
4-way valve, indoor temp. sensors (TC/TCJ) --- An error was detected due to temperature drop of the indoor unit heat exchanger sensor when heating.
Entire stop
Entire stop
Entire stop
Entire stop
Entire stop
Entire stop
Entire stop
Entire stop
Auto-reset
Entire stop
Entire stop
Operation continued
(thermostat
OFF)
Entire stop
Entire stop
Entire stop
Entire stop
Entire stop
Entire stop
Entire stop
Auto-reset (Auto-reset)
31-EN
–31–
Under Ceiling Type
Installation Manual
P22 ALT Outdoor unit fan error Outdoor
P26 ALT
P29 ALT
P31 ALT Other indoor unit error Indoor
Check codes in parentheses ( ) are displayed when connected to an outdoor unit other than the new SDI series.
: Lighting : Flashing : OFF : The air conditioner automatically enters the auto-address setting mode. ALT: When two LEDs are flashing, they flash alternately. SIM: When two LEDs are flashing, they flash in synchronization. Receiving unit display OR: Orange GR: Green
Outdoor unit inverter Idc activated
Outdoor unit position error
Outdoor
Outdoor
Outdoor unit fan motor, outdoor unit P.C. board --- An error (overcurrent, locking, etc.) was detected in the outdoor unit fan drive circuit.
IGBT, outdoor unit P.C. board, inverter wiring, compressor --- Short-circuit protection for compressor drive circuit devices (G-Tr/IGBT) was activated.
Outdoor unit P.C. board, high-pressure switch --­Compressor motor position error was detected.
Another indoor unit in the group is raising an alarm. Entire stop
E03/L07/L03/L08 alarm check locations and error description
Entire stop
Entire stop
Entire stop
Auto-reset
–32–
EN
32-EN
EH99864801
Loading...