Toshiba Carrier RAV-SP180KRT-UL, RAV-SP240KRT-UL Installation Manual

Toshiba
AIR CONDITIONER (SPLIT TYPE)
Indoor Unit
Model name:
High-Wall Type
RAV-SP180KRT-UL RAV-SP240KRT-UL
Installation Manual
English
Manuel d’installation 43
Français
+001111052201_00Ta.book Page 1 Friday, November 20, 2009 11:45 AM
–1–
Toshiba
High-Wall Type
Installation Manual
Contents
1 ACCESSORY PARTS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
2 PRECAUTIONS FOR SAFETY . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
3 SELECTION OF INSTALLATION PLACE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
4 INSTALLATION OF INDOOR UNIT . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
5 CUTTING A HOLE AND MOUNTING INSTALLATION PLATE. . . . . . . . . . . . . . . 8
6 PIPING AND DRAIN HOSE INSTALLATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
7 INDOOR UNIT FIXING. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
8 DRAINAGE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
9 REFRIGERANT PIPING . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
10 ELECTRIC WORK. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
11 APPLICABLE CONTROLS. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
12 TEST RUN . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
13 TROUBLE SHOOTING . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
Please read this Installation Manual carefully before installing the Air Conditioner.
• This Manual describes the installation method of the outdoor unit.
• For installation of the indoor unit, refer to the Installation Manual attached to the indoor unit.
ADOPTION OF NEW REFRIGERANT
This Air Conditioner uses R410A an environmentally friendly refrigerant.
1-EN
+001111052201_00Ta.book Page 1 Friday, November 20, 2009 11:45 AM
High-Wall Type
Installation Manual
–2–
Toshiba
EN
1 ACCESSORY PARTS
Accessory parts
<Others>
Part name Q’ty Shape
Installation plate 1
Wireless remote controller 1
Battery 2
Remote control holder 1
Mounting screw Ø0.16” (4 mm) × 1.0” (25 mm) 6
Pan head wood screw Ø1/8” (3.1 mm) × 0.6” (16 mm) 2
Screw Ø0.16” (4 mm) × 0.4” (10 mm) 2
Heat insulator 1
Name
Owner’s manual
Installation manual
2-EN
+001111052201_00Ta.book Page 2 Friday, November 20, 2009 11:45 AM
High-Wall Type
Installation Manual
–3–
Toshiba
2 PRECAUTIONS FOR SAFETY
Installing, starting up, and servicing air--conditioning equipment can be hazardous due to system pressures, electrical components, and equipment location (roofs, elevated structure s , etc.). Only trained, qualified installers and service mechanics should install, start-up, and service this equipment. Untrained personnel can perform basic maintenance functions such as cleaning coils. All other operations should be performed by trained service personnel. When working on the equipment, observe precautions in the literature and on tags, stickers, and labels attached to the equipment. Follow all safety codes.Wear safety glasses and work gloves. Keep quenching cloth and fire extinguisher nearby when brazing. Use care in handling, rigging, and setting bulky equipment. Read these instructions thoroughly and follow all warnings or cautions included in literature and attached to the unit. Consult local building codes and National Electrical Code (NEC) for special requirements. Recognize safety information. This is the safety-alert symbol . When you see this symbol on the unit and in instructions or manuals, be alert to the potential for personal injury.Understand these signal words: DANGER, WARNING, and CAUTION. These words are used with the safety--alert symbol. DANGER identifies the most serious hazards which will result in severe personal injury or death. WARNING signifies hazards which could result in personal injury or death. CAUTION is used to identify unsafe practices which may result in minor personal injury or product and property damage. NOTE is used to highlight suggestions which will result in enhanced installation, reliability, or operation.
WARNING
Ask an authorized dealer or qualified installation professional to install (including moving)/
maintain the air conditioner.
Inappropriate installation may result in water leakage, electric shock or fire.
Be sure to connect ground wire. (grounding work) Incomplete grounding cause an electric shock. Do not connect ground wires to gas pipes, water pipes, lightning rods or ground wires for telephone wires.
Turn off the circuit breaker and leakage breaker before attempting any electrical work. Make sure all circuit breaker and leakage breaker are off. Failure to do so may cause electric shock.
Install the refrigerant pipe securely during the installation work before operating the air
conditioner.
If the air conditioner is operated with the valve open and without the refrigerant pipe, the compressor sucks air and the refrigeration cycle is over pressurized, which may cause a burst or injury.
When moving the air conditioner for the installation into another place, be very careful not to
enter any gaseous matter other than the specified refrigerant into the refr igeration cycle.
If air or any other gas is mixed in the refrigerant, the gas pressure in the refrigeration cycle becomes abnormally high and it resultingly causes pipe burst and injuries on persons.
Perform installation work properly according to the Installation Manual. Inappropriate installation may result in water leakage, electric shock or fire.
When the air conditioner is installed in a small room, provide appropriate measures to ensure
that the concentration of refrigerant leakage occur in the room does not exceed the critical level.
Install the air conditioner securely in a location where the base can sustain the weight adequately.
Perform the specified installation work to guard against an earthquake. If the air conditioner is not installed appropriately, accidents may occur due to the falling unit.
If refrigerant gas has leaked during the installation work, ventilate the room immediately. If the leaked refrigerant gas comes in contact with fire, noxious gas may generate.
After the installation work, confirm that refrigerant gas does not leak. If refrigerant gas leaks into the room and flows near a fire source, such as a cooking range, noxious gas might generate.
3-EN
+001111052201_00Ta.book Page 3 Friday, November 20, 2009 11:45 AM
High-Wall Type
Installation Manual
–4–
Toshiba
EN
Electrical work must be performed by a qualified electrician in accordance with the Installation Manual. Make sure the air conditioner uses an exclusive power supply.
An insufficient power supply capacity or inappropriate installation may cause fire.
Use the specified wires for wiring conn ect the terminals securely fix.
To prevent external forces applied to the terminals from affecting the terminals.
Conform to the regulations of the local electric company when wiring the power supply. Inappropriate grounding may cause electric shock.
For the refrigerant pump-down work (collection of refrigerant from the pipe to the compressor),
stop the compressor before disconnecting the refrigerant pipe .
If the refrigerant pipe is disconnected while the compressor is working with the valve open, the compressor sucks air and the refrigeration cycle is over pressurized, which may cause a burst or injury.
CAUTION
THIS AIR CONDITIONER ADOPTS THE NEW HFC REFRIGERANT (R410A) WHICH DOES NOT DESTROY OZONE LAYER.
• The characteristics of R410A refrigerant are; easy to absorb water, oxidizing membrane or oil, and its pressure is approx. 1.6 times higher than that of refrigerant R22. Accompanied with the new refrigerant, refrigerating oil has also been changed. Therefore, during installation work, be sure that water, dust, former refrigerant, or refrigerating oil does not enter the refrigerating cycle.
• To prevent charging an incorrect refrigerant and refrigerating oil, the sizes of connecting sections of charging port of the main unit and installation tools are changed from those for the conventional refrigerant.
• Accordingly the exclusive tools are required for the new refrigerant (R410A).
• For connecting pipes, use new and clean piping designed for R410A, and please care so that water or dust does not enter.
The installation fuse must be used for the power supply line of this conditioner.
Tighten the flare nut with a torque wrench in the specified manner. Excessive tightening of the flare nut may cause a crack in the flare nut after a long period, which may result in refrigerant leakage.
Wear heavy gloves and a long sleeve shirt during the installation work to avoid injury.
4-EN
+001111052201_00Ta.book Page 4 Friday, November 20, 2009 11:45 AM
High-Wall Type
Installation Manual
–5–
Toshiba
3 SELECTION OF INSTALLATION PLACE
WARNING
Install the air conditioner at enough strong place to withstand the weight of the unit. If the strength is not enough, the unit may fall down resulting in injury.
CAUTION
Do not install the air conditioner in a location subject to a risk of exposure to a combustible gas. If a combustible gas leaks and stays around the unit, a fire may occur.
Upon approval of the customer, install the air conditioner in a place that satisfies the following conditions.
• Place where the unit can be installed horizontally.
• Place where a sufficient servicing space can be ensured for safety maintenance and check.
• Place where drained water will not cause any problem.
Avoid installing in the following places.
• Place exposed to air with high salt content (seaside area), or place exposed to large quantities of sulfide gas (hot spring). (Should the unit be used in these places, special protective measures are needed.)
• A restaurant kitchen where a lot of oil is used or place near machines in a factory (Oil adhering to the heat exchanger and resin part (cross flow fan) in the indoor unit may reduce the performance, generate mist or dew drop, or deform or damage resin parts.)
• Place where organic solvent is used nearby.
• Place close to a machine generating high frequency.
• Place where the discharged air blows directly into the window of the neighbour house. (Outdoor unit)
• Place where noise of the outdoor unit is easily transmitted. (When install the outdoor unit on the boundary with the neighbour, pay due attention to the level of noise.)
• Place with poor ventilation.
• Do not use the air conditioner for special purposes such as preserving food, precision instruments, or art objects, or where breeding animals or growing plants are kept. (This may degrade the quality of preserved materials.)
• Place where any of high-frequency appliances (including inverter devices, private power generators, medical equipment, and communication equipment) and inverter-type fluorescent light is installed. (A malfunction of the air conditioner, abnormal control, or problems due to noise to such appliances/ equipment may occur.)
• When the wireless remote controller is used in a room equipped with an inverter-type fluorescent light or at a place exposed to direct sunlight, signals from the remote controller may not be received correctly.
• Place near a door or window exposed to humid outside air (Dew dropping may form.).
• Place where special spray is used frequently.
5-EN
+001111052201_00Ta.book Page 5 Friday, November 20, 2009 11:45 AM
High-Wall Type
Installation Manual
–6–
Toshiba
EN
Installation diagram of Indoor and outdoor units
Installation space
The indoor unit shall be installed so that its top surface comes at a height of 6’7” (2 m) or more. Also it must be avoided to put anything on top of the indoor unit.
*1 Provide a space as shown for service clearance for the cross flow fan.
Installation place
• A place which provides the spaces around the indoor unit as shown in the above diagram.
• A place where there is no obstacle near the air inlet and outlet.
• A place that allows easy installation of the piping to the outdoor unit.
• A place which allows the front panel to be opened.
CAUTION
• Direct sunlight to the indoor unit’ s wireless receiver should be avoided.
• The microprocessor in the indoor unit should not be too close to RF (Radio Frequency) noise sources. (For details, see the owner’ s manual.)
A
CL
For the rear left and left piping
Wall
Insert the cushion between the indoor unit and wall, and tilt the indoor unit for better operation.
Do not allow the drain hose to get slack.
Cut the piping hole sloped slightly.
Make sure to run the drain hose sloped downward.
The auxiliary piping can be connected to the left, rear left, rear right, right, bottom right or bottom left.
Right
Rear right
Bottom right
Bottom left
Rear left
2.0” (50 mm) or more
6
.
7
(
1
7
0
m
m
)
o
r
m
o
r
e
3
3
.
5
(
8
5
0
m
m
)
o
r
m
o
r
e
Hook
Installation plate
Hook
Connecting pipe
A
i
r
f
i
l
t
e
r
(
A
tt
a
c
h
t
o
t
h
e
f
r
o
n
t
p
a
n
e
l
.
)
Remote controller holder
Pan head wood screw
Batteries
Wireless remote controller
Before installing the wireless remote controller
1.Remove the battery cover.
2.Insert 2 new batteries (R03 [AAA] type) following the (+) and (–) positions.
Wireless remote controller
Cover
Batteries
Heat insulator
*
1
Left
* CAUTION Connecting pipe cannot be connected to the right side of the indoor unit when conduit pipe is used. When connecting pipe is connected on the left or bottom of the indoor unit, connect the conduit pipe on other side.
6-EN
+001111052201_00Ta.book Page 6 Friday, November 20, 2009 11:45 AM
High-Wall Type
Installation Manual
–7–
Toshiba
Wireless remote controller
• A place where there are no obstacles such as a curtain that may block the signal from the indoor unit.
• Do not install the remote controller in a place exposed to direct sunlight or close to a heating source, such as a stove.
• Keep the remote controller at least 3’3” (1 m) apart from the nearest TV set or stereo equipment. (This is necessary to prevent image disturb-bounces or noise interference.)
• The location of the remote controller should be determined as shown below.
4 INSTALLATION OF INDOOR UNIT
WARNING
Install the air conditioner certainly to sufficiently withstand the weight. If the strength is insufficient, the unit may fall down resulting in human injury. Perform a specified installation work to guard against strong wind or earthquake. An incomplete installation can cause accidents by the units falling and dropping.
REQUIREMENT
Strictly comply with the following rules to prevent damage of the indoor units and human injury.
• Do not put a heavy article on the indoor unit. (Even units are packaged)
• Carry in the indoor unit as it is packaged if possible. If carrying in the indoor unit unpacked by necessity, be sure to use buffering cloth, etc. to not damage the unit.
• To move the indoor unit, do not apply force to the refrigerant pipe, drain pan, foamed parts, or resin parts, etc.
• Carry the package by two or more persons, and do not bundle it with plastic band at positions other than specified.
Be careful to the following items when installing the unit.
• Considering air discharge direction, select an installation place where discharge air can circulate evenly in a room. Avoid to install the unit at place with “NO GOOD” mark in the right figure.
(Side view) (Top view)
Remote controller
Reception range
*: Axial distance
Indoor unit
Remote controller
* 23’ (7 m)
Indoor unit
1
6
5
(
5
m
)
16’5” (5
m)
2
3
(
7
m
)
75
°
4
5
°
4
5
°
Reception range
Good installation place Cooled well all over.
Bad installation place
: Not cooled well.
Screen
OK NO GOOD
7-EN
+001111052201_00Ta.book Page 7 Friday, November 20, 2009 11:45 AM
High-Wall Type
Installation Manual
–8–
Toshiba
EN
5 CUTTING A HOLE AND MOUNTING INSTALLATION
PLATE
Cutting a hole
In case of installing the refrigerant pipes from the rear:
1. Decide the hole position for piping at 7.1”
(180 mm) from the arrow mark (Ö) on the installation plate and drill a hole at a slight downward slant toward outdoor side. Pipe hole; dia.2.6” (65 mm): SP180 type Pipe hole; dia.3.1” (80 mm): SP240 type
NOTE
• When drilling a wall that contains a metal lath, wire lath or metal plate, be sure to use a pipe hole brim ring sold separately.
Mounting the installation plate
When the installation plate is
directly mounted on the wall
1. Securely fit the installation plate onto the wall by screwing it in the upper and lower parts to hook up the indoor unit.
2. To mount the installation plate on a concrete wall with anchor bolts, utilize the anchor bolt holes as illustrated in the above figure.
3. Install the installation plate horizontally in the wall.
CAUTION
When installing the installation plate with a mounting screw, do not use the anchor bolt hole. Otherwise the unit may fall down and result in personal injury and property damage.
80 65
1111012101
80 65
1111012101
0.9” (23 mm)
The centre of the pipe hole is above the arrow
7.1” (180 mm)
Pipe hole
dia. 2.6” (65 mm): SP180 type dia. 3.1” (80 mm): SP240 type
dia.2.6"
(65 mm)
5.2" (132 mm)
6.7" (170 mm)
1.6" (40 mm)
2.0" (50 mm)
6.7" (170 mm)
0.9" (23 mm)
3.3"(85 mm)
Anchor bolt holes
Hook
Hook
Pipe hole
Indoor unit
Thread
Weight
Mounting Screw
Installation plate
Pipe hole (dia. 2.6” (65 mm)) dia. 3.1” (80 mm))
Hook
6’7” (2 m) or more from floor
Be sure that the installation plate is fix to the wall with screws to make the indoor unit fit to the wall.
8-EN
+001111052201_00Ta.book Page 8 Friday, November 20, 2009 11:45 AM
High-Wall Type
Installation Manual
–9–
Toshiba
CAUTION
Failure to firmly install the unit may result in personal injury and property damage if the unit falls.
• In case of block, brick, concrete or similar type walls, make 0.2” (5 mm) dia. holes in the wall.
• Insert clip anchors for appropriate mounting screws.
NOTE
• Secure four corners and lower parts of the installation plate with 6 mounting screws to install it.
Projection
0.6” (15 mm) or less
Clip anchor (local parts)
Mounting screw
0.16” (4 mm) × 1.0” (25 mm)
Anchor bolt
0.2” (5 mm) dia. hole
OK NO
GOOD
NO
GOOD
9-EN
+001111052201_00Ta.book Page 9 Friday, November 20, 2009 11:45 AM
High-Wall Type
Installation Manual
–10–
Toshiba
EN
6 PIPING AND DRAIN HOSE INSTALLATION
Piping and drain hose forming
* Apply heat-insulation for both refrigerant pipe and drain hose surely so that no dew generates inside of
the equipment. (Use polyethylene foam for insulating material.)
1. Remove the front panel
The front panel must be removed for piping connections in the left, bottom left, and rear left directions.
• Open the air inlet grille upward.
• Remove the four screws securing the front panel.
• Slightly open the lower part of the front panel, and then pull the upper part of the front panel toward you to remove it from the rear plate.
2. Die-cutting front panel slit
Cut out the slit on the leftward or right side of the front panel for the left or right connection and the slit on the bottom left or right side of the front panel for the bottom left or right connection with a pair of nippers.
3. Changing drain hose
For leftward connection, bottom-leftward connection and rear leftward conne ction's piping, it is necessary to change the drain hose and drain cap. Without changing the drain hose position, the indoor unit will not fit to the wall.
How to remove the drain hose
• The drain hose can be removed by removing the screw securing the drain hose and then pulling out the drain hose.
• When removing the drain hose, be car eful of any sharp edges of steel plate. The edges can injuries.
• To install the drain hose, insert the drain hose firmly until the connection part contacts with heat insulator, and the secure it with original screw.
Piping
preparation
Die-cutting front panel
slit
Rear right
Rear left
Bottom left
Left
Bottom right
Right
Removing
front panel
Changing
drain hose
3
2
1
Air inlet grille
Front panel
Heat insulator
Drain hose
10-EN
+001111052201_00Ta.book Page 10 Friday, November 20, 2009 11:45 AM
High-Wall Type
Installation Manual
–11–
Toshiba
How to remove the drains cap
Clip the drain cap by needle-nose pliers and pull out.
How to fix the drains cap
1) Insert hexagonal wrench (dia. 0.16” (4 mm)) in a centre head.
2) Firmly insert drains cap.
CAUTION
Firmly insert the drain hose and drain cap; otherwise, water may leak.
In case of right or left piping
• After scribing slits of the front panel with a knife or a marking-off pin, cut them with a pair of nippers or an equivalent tool.
How to remove the drain hose
1) Remove the front panel.
2) Remove the screws of drain hose.
3) Pull out the drain hose.
How to fix the drain hose
1) Put the drain hose.
2) Screw the drain hose to the indoor unit.
3) Install the front panel.
0.16” (4 mm)
No gap
Do not apply lubricating oil (refrigerant machine oil) when inserting the drain cap. Application causes deterioration and drain leakage from the plug.
Insert a hexagon wrench (0.16” (4 mm))
Slit
11-EN
+001111052201_00Ta.book Page 11 Friday, November 20, 2009 11:45 AM
High-Wall Type
Installation Manual
–12–
Toshiba
EN
In case of bottom right or bottom left piping
• After scribing slits of the front panel with a knife or a marking-off pin, cut them with a pair of nippers or an equivalent tool.
Left-hand connection with pi ping
Bend the connecting pipe so that it is laid within 1.7” (43 mm) above the wall surface. If the connecting pipe is laid exceeding 1.7” (43 mm) above the wall surface, the indoor unit may unstably be set on the wall. When bending the connecting pipe, make sure to use a spring bender so as not to crush the pipe.
Bend the connection pipe within a radius of 1.2” (30 mm).
To connect the pipe after installation of the unit (figure)
NOTE
If the pipe is bent incorrectly, the indoor unit may unstably be set on the wall. After passing the connecting pipe through the pipe hole, connect the connecting pipe to the auxiliary pipes and wrap the facing tape around them.
CAUTION
• Carefully arrange pipes so that any pipe does not stick out of the rear plate of the indoor unit.
• Carefully connect the auxiliary pipes and connecting pipes to one another and cut off the insulating tape wound on the connecting pipe to avoid double-taping at the joint, moreover, seal the joint with the vinyl tape, etc.
• Since dew results in a machine trouble, make sure to insulate both the connecting pipes. (Use polyethylene foam as insulating material.)
• When bending a pipe, carefully do it, not to crush it.
Slit
22.4” (570 mm)
Outward form of indoor unit
(To the fore front of flare)
R 1.2” (30 mm) (Use polish polyethylene core or the like for bending pipe.)
G
as side
Liquid side
Use the handle of screwdriver, etc.
16.5” (420 mm)
1.7” (43 mm)
8
0
°
Indoor unit
Auxiliary pipes
Installation plate
12-EN
+001111052201_00Ta.book Page 12 Friday, November 20, 2009 11:45 AM
High-Wall Type
Installation Manual
–13–
Toshiba
7 INDOOR UNIT FIXING
1. Pass the pipe through the hole in the wall, and hook the indoor unit on the installation plate at the upper hooks.
2. Swing the indoor unit to right and left to confirm that it is firmly hooked up on the installation plate.
3. While pressing the indoor unit onto the wall, hook it at the lower part on the installation plate. Pull the indoor unit toward you to confirm that it is firmly hooked up on the installation plate.
• For detaching the indoor unit from the installation
plate, pull the indoor unit toward you while pushing its bottom up at the specified parts.
REQUIREMENT
The lower part of indoor unit may float, due to the condition of piping and you cannot fix it to the installation plate. In that case, use the screws provided to fix the unit and the installation plate.
Especially when the pipes are pulled out from the left side, the unit must be screwed to the installation plate.
8 DRAINAGE
1. Run the drain hose sloped downwards.
NOTE
• Hole should be made at a slight downward slant on the outdoor side.
2. Put water in the drain pan and make sure that the water is drained out of doors.
3. When connecting extension drain hose, insulate the connecting part of extension drain hose with shield pipe.
CAUTION
Arrange the drain pipe for proper drainage from the unit. Improper drainage can result in dew-dropping.
This air conditioner has the structure designed to drain water collected from dew, which forms on the back of the indoor unit, to the drain pan. Therefore, do not store the power cord and other parts at a height above the drain guide.
1
2
Press(unhook)
Hook
Hook here Installation plate
PushPush
screw screw
Do not put the drain hose end in the drainage ditch.
Do not put the drain hose end into water.
Do not rise the drain hose.
Do not form the drain hose into a wavy shape.
2.0” (50 mm) or more
Drain hose
Inside the room
Shield pipe
Extension drain hose
Wall
Drain guide
Space for pipes
13-EN
+001111052201_00Ta.book Page 13 Friday, November 20, 2009 11:45 AM
High-Wall Type
Installation Manual
–14–
Toshiba
EN
9 REFRIGERANT PIPING
Refrigerant Piping
1. Use copper pipe with 0.03” (0.8 mm) or more thickness. (In case pipe size is dia.
5/8” (15.9 mm), with 0.04” (1.0 mm) or more.)
2. Flare nut and flare works are also different from those of the conventional refrigerant. Take out the flare nut attached to the main unit of the air conditioner, and use it.
REQUIREMENT
When the refrigerant pipe is long, provide support brackets at intervals of 8’2” - 9’10” (2.5 - 3 m) to clamp the refrigerant pipe. Otherwise, abnormal sound may be generated.
CAUTION
IMPORTANT 4 POINTS FOR PIPING WORK
1. Remove dust and moisture from the inside of the connecting pipes.
2. Tight connection (between pipes and unit)
3. Evacuate the air in the connecting pipes using VACUUM PUMP.
4. Check the gas leakage. (Connected points)
Pipe size
Permissible Piping Length and
Height Difference
They vary according to the outdoor unit. For details, refer to the Installation Manual attached to the outdoor unit.
Flaring
• Cut the pipe with a pipe cutter. Remove burrs completely. Remaining burrs may cause gas leakage.
• Insert a flare nut into the pipe, and flare the pipe. As the flaring sizes of R410A differ from those of refrigerant R22, the flare tools newl y manufactured for R410A are recommended. However, the conventional tools can be used by adjusting projection margin of the copper pipe.
Projection margin in flaring: B (Unit: in (mm))
Rigid (Clutch type)
Flaring dia. meter size: A (Unit: in (mm))
* In case of flaring for R410A with the
conventional flare tool, pull it out approx.
0.02” (0.5 mm) more than that for R22 to adjust to the specified flare size. The copper pipe gauge is useful for adjusting projection margin size.
dia.: in (mm)
RAV-
SP180 type SP240 type
Gas side 1/2” (12.7) 5/8” (15.9)
Liquid side 1/4” (6.4) 3/8” (9.5)
Outer dia. of
copper pipe
R410A tool
used
Conventional
tool used
R410A R410A
1/4” (6.4) , 3/8” (9.5)
0 - 0.02” (0 - 0.5)
0.04” - 0.06” (1.0 - 1.5)
1/2” (12.7) , 5/8” (15.9)
Outer dia. of copper pipe
A
R410A
1/4” (6.4) 0.36” (9.1)
3/8” (9.5) 0.52” (13.2) 1/2” (12.7) 0.65” (16.6) 5/8” (15.9) 0.78” (19.7)
B
+0
-0.02" (-0.4)
A
14-EN
+001111052201_00Ta.book Page 14 Friday, November 20, 2009 11:45 AM
High-Wall Type
Installation Manual
–15–
Toshiba
Tightening connection
CAUTION
• Do not apply excessive torque. Otherwise, the nut may crack depending on the conditions.
Tightening torque of flare pipe connections
Pressure of R410A is higher than that of R22. (Approx. 1.6 times) Therefore, using a torque wrench, tighten the flare pipe connecting sections which connect the indoor and outdoor units of the specified tightening torque. Incorrect connections may cause not only a gas leak, but also a trouble of the refrigeration cycle. Align the centres of the connecting pipes and tighten the flare nut as far as possible with your fingers. Then tighten the nut with a spanner and torque wrench as shown in the figure.
REQUIREMENT
Tightening with an excessive torque may crack the nut depending on installation conditions. Tighten the nut within the specified tightening torque.
Piping with outdoor unit
• Shape of valve differs according to the outdoor unit. For details of installation, refer to the Installation Manual of the outdoor unit.
Heat insulation
Heat insulation for the pipes should be done separately for the liquid side and gas side. Because both of the liquid and gas side pipes become a low temperature during cooling operation, sufficient heat insulation should be done to prevent condensation.
• Heat insulator with a heat resistance of 248 °F (120 °C) or more must be used for the gas side pipe.
• The pipe connection section of the indoor unit must be heat insulated securely and compactly with the attached heat insulator.
Air purge
Using a vacuum pump, perform vacuuming fr om the charge port of valve of the outdoor unit. For details, follow to the Installation Manual attached to the outdoor unit.
• Never use the refrigerant sealed in the outdoor unit for air purge.
REQUIREMENT
For the tools such as charge hose, etc., use those manufactured exclusively for R410A.
Refrigerant amount to be added
For addition of the refrigerant, add refrigerant “R410A” referring to the attached Installation Manual of outdoor unit. Be sure to use a scale to charge the refrigerant of specified amount.
REQUIREMENT
• Charging an excessive or too little amount of refrigerant causes a trouble of the compressor. Be sure to charge the refrigerant of specified amount.
• A personnel who charged the refrigerant should write down the pipe length and the added refrigerant amount in the nameplate attached to the service panel of the outdoor unit. It is necessary to troubleshoot the compressor and refrigeration cycle malfunction.
Unit: ft•lbs (N•m)
Outer dia. of copper pipe Tightening torque
1/4” (6.4 mm) 10 - 13 (14 - 18)
3/8” (9.5 mm) 24 - 31 (33 - 42) 1/2” (12.7 mm) 37 - 46 (50 - 62) 5/8” (15.9 mm) 50 - 60 (68 - 82)
Work using double spanner
Fix with vinyl tape
Heat insulator (attached)
Local side pipe
15-EN
+001111052201_00Ta.book Page 15 Friday, November 20, 2009 11:45 AM
High-Wall Type
Installation Manual
–16–
Toshiba
EN
Open the valve fully
Open the valve of the outdoor unit fully. A 4 mm hexagon wrench is required for opening the valve. For details, refer to the Installation Manual attached to the outdoor unit.
Gas leak check
Check with a leak detector or soap water whether gas leaks or not, from the pipe connecting section or cap of the valve.
REQUIREMENT
Use a leak detector manufactured exclusively for HFC refrigerant (R410A, R134a, etc.).
Wireless remote control A-B
selection
Using 2 wireless remote controllers for the respective air conditioners, when the 2 air conditioners are closely installed.
Wireless remote controller B setup
1. Press button on the indoor unit to turn the air conditioner ON.
2. Point the wireless remote controller at the indoor unit.
3. Push and hold button on the wireless remote controller by the tip of the pencil. “00” will be shown on the display.
4. Press during pushing . “B” will be shown on the display and “00” will be disappear and the air conditioner will turn OFF. The wireless remote controller B is memorized.
NOTE
• Repeat above step to reset wireless remote controller to be A.
• The wireless remote controllers do not display “A”.
• The factory default of the wireless remote controllers is “A”.
CHK
MODE
CHK
PRESET FAN
"B" Display "00" Display
16-EN
+001111052201_00Ta.book Page 16 Friday, November 20, 2009 11:45 AM
High-Wall Type
Installation Manual
–17–
Toshiba
10 ELECTRIC WORK
WARNING
Consult local building codes, NEC (National
Electrical Code) or CEC (Canadian Electrical Code) for special requirements.
Using the specified wires, ensure to
connect the wires, and fix wires securely so that the external tension to the wires do not affect the connecting part of the terminals.
Incomplete connection or fixation may cause a fire, etc.
Be sure to connect ground wire. (grounding
work)
Incomplete grounding cause an electric shock. Do not connect ground wires to gas pipes, water pipes, lightning rods or ground wires for telephone wires.
Appliance shall be installed in accordance
with national wiring regulations.
Capacity shortage of circuit breaker and leakage breaker or incomplete installation may cause an electric shock or a fire.
CAUTION
• If incorrect/incomplete wiring is carried out, it will cause an electrical fire or smoke.
• Be sure to install circuit breaker and leakage breaker that are not tripped by shock waves. If circuit breaker and leakage breaker are not installed, an electric shock may be caused.
• Be sure to use the cord clamps attached to the product.
• Do not damage or scratch the conductive core and inner insulator of Indoor/Outdoor connecting wire when peeling them.
• Use the power cord and Inter-connecting wire of specified thickness, type, and protective devices required.
• Never connect 208/230 V wired remote controller/central control wiring blocks ( ,
, , , etc.) for control wiring.
(Otherwise, the system will fail.)
REQUIREMENT
• For Indoor/Outdoor connecting wire, strictly conform to the Local Regulation in each country.
• For wiring of power supply of the outdoor units, follow the Installation Manual of each outdoor unit.
• Perform the electric wiring so that it does not come to contact with the high-temperature part of the pipe. The coating may melt resulting in an accident.
• Connect the wires to the terminal blocks and fix the wires with the cord clamp as no force applys to the wires.
• Run the refrigerant piping line and control wiring line in the same line.
• Do not turn on the circuit breaker and leakage breaker of the indoor unit until vacuuming of the refrigerant pipes completes.
*1: Length of the Indoor/Outdoor unit connecting wires.
CAUTION
Use the same size wire for the outdoor unit power cable and connecting wire between the indoor unit and the outdoor unit when the outdoor unit is RAV-SP180AT2 (2HP).
NOTE
• Use copper supply wires.
• Use UL wires rated 600 V for the Indoor/ Outdoor unit connecting wires.
• Use UL wires rated 300 V for the remote controller wires.
3
4
A B
Wire Quantity x size
Indoor unit - Outdoor unit *
1
3 x AWG12 (polar) Ground 1 x AWG12 or thicker Remote controller 2 x AWG20 (non-polar)
RAV- SP180AT2 (2HP) SP240AT2 (3HP)
Wire length 50 m or less 70 m or less
17-EN
+001111052201_00Ta.book Page 17 Friday, November 20, 2009 11:45 AM
High-Wall Type
Installation Manual
–18–
Toshiba
EN
Wiring Connection
REQUIREMENT
• Be sure to connect the wires matching the terminal numbers. Incorrect connection causes a trouble.
• The low-voltage circuit is provided for the wired remote controller. (Do not connect the high-voltage circuit)
When using the supplied wireless remote
controller
1. Remove the air inlet grille. Open the air inlet grille upward and pull it toward you.
2. Remove the front panel.
3. Remove the terminal cover.
4. Remove the conduit cover.
5. Attach a conduit to the conduit cover with a lock nut.
6. Take the Indoor/Outdoor connecting wire (3 x AWG12) and the ground wire (1 x AWG12) out of the cable slot on the rear panel so that it protrudes about 11.0” (280 mm) from the conduit cover.
7. Insert the Indoor/Outdoor connecting wire (3 x AWG12 (polar)) fully into the terminal block and secure it tightly with screws. Tightening torque: 0.9 ft•lbs (1.2 N•m) Secure the ground wire (1 x AWG12) with the ground screw.
8. Clamp the Indoor/Outdoor connecting wire and the ground wire with the cord clamp.
L
1
L
2
S
L1
L2
S
Terminal block for indoor/outdoor connecting
Screw
Cord clamp
Terminal Cover
Screw
Ground screw
Conduit cover
Conduit hole (dia. 7/8” (22.2 mm))
Screw
S L
2
L1
Indoor/Outdoor connecting wire
Ground wire
0.4” (10 mm)
0.8” (20 mm)
<Stripping length of the Indoor/Outdoor connecting wire>
Conduit cover
11.0” (280 mm)
Connecting wire
L1 L2 S
Terminal block for indoor/ outdoor connecting
Ground screw
Ground wire
Cord clamp
Indoor/Outdoor connecting wire
18-EN
+001111052201_00Ta.book Page 18 Friday, November 20, 2009 11:45 AM
High-Wall Type
Installation Manual
–19–
Toshiba
9. Attach the conduit cover.
10.Attach the terminal cover, the front panel and the air inlet grille to the indoor unit.
CAUTION
• Be sure to refer to the wiring diagram attached inside the front panel.
• Check local electrical cords and also any specific wiring instructions and limitations.
• Beware of the metal plate edge when working on the unit. The edge can be sharp and may cut your hand.
• Firmly tighten the screws of the terminal block.
Keep the wire length as shown in figure below when it is connected to the terminal block.
Wiring Diagram
When using optional wired remote controller
1. Remove the air inlet grille. Open the air inlet grille upward and pull it toward you.
2. Remove the front panel.
3. Remove the terminal cover and the clamp base.
4. Insert the wired remote controller wire fully into the wired remote controller/central control terminal block,
and , and
secure it tightly with screws.
• Strip off the wire approx. 0.4” (9 mm) to
connect.
• Non polarity, 2 core wire is used for wiring
of the wired remote controller. (2 x AWG20)
Indoor/Outdoor connecting wire
Conduit cover
11.0” (280 mm)
0.08” (2 mm) or less
Indoor/Outdoor unit connecting wire
L
1
L
1
L
2
L
2
S
S
208/230-1-60
Outdoor unit
High voltage
Indoor unit
L1
L2
S
L
1
L
2
S
L
1
L
2
S
Terminal block for Indoor/Outdoor connecting
Terminal block
Clamp base
Screw
Terminal Cover
Screw
A B
AU4U3 B
L1 L2 S
Terminal block for wired remote controller/ central control wiring
Wired remote controller wire
Cord clamp
Hole for indoor/ outdoor connecting wires and ground wire
Hole for remote controller wires
19-EN
+001111052201_00Ta.book Page 19 Friday, November 20, 2009 11:45 AM
High-Wall Type
Installation Manual
–20–
Toshiba
EN
5. Clamp the wired remote controller wire with the cord clamp.
6. Install the clamp base with a screw.
7. Remove the conduit cover.
8. Attach a conduit to the conduit cover with a lock nut.
9. Take the Indoor/Outdoor connecting wire (3 x AWG12 (polar)) and the ground wire (1 x AWG12) out of the cable slot on the rear panel so that it protrudes about 11.0” (280 mm) from the conduit cover.
10.Insert the Indoor/Outdoor connecting wire (3 x AWG12 (polar)) fully into the terminal block and secure it tightly with screws. Tightening torque: 0.12 kgf•m (1.2 N•m) Secure the ground wire (1 x AWG12) with the ground screw.
11.Clamp the Indoor/Outdoor connecting wire with the cord clamp.
12.Attach the conduit cover.
13.Attach the terminal cover, the front panel and the air inlet grille to the indoor unit.
CAUTION
• Be sure to refer to the wiring diagram attached inside the front panel.
• Check local electrical cords and also any specific wiring instructions and limitations.
• Do not catch the wired remote controller wire when installing the clamp base
• Beware of the metal plate edge when working on the unit. The edge can be sharp and may cut your hand.
• Firmly tighten the screws of the terminal block.
Keep the wire length as shown in figure below when it is connected to the terminal block.
Insert remote controller wires
Conduit Cover
Conduit hole (dia. 7/8” (22.2 mm))
Conduit hole (dia. 7/8” (22.2 mm))
Conduit cover
Indoor/Outdoor connecting wire
Conduit cover
11.0” (280 mm)
L1 L2 S
Terminal block for indoor/ outdoor connecting
Ground screw
Ground wire
Cord clamp
Indoor/Outdoor connecting wire
0.08” (2 mm) or less
Indoor/Outdoor unit connecting wire
20-EN
+001111052201_00Ta.book Page 20 Friday, November 20, 2009 11:45 AM
High-Wall Type
Installation Manual
–21–
Toshiba
Wiring Diagram
A B
A B
Terminal block for remote controller wiring of indoor unit
Remote controller wire (Field supply)
Terminal block
Remote controller unit
AB
L
1
L
1
L
2
L
2
S
S
208/230-1-60
Outdoor unit
High voltage
Low voltage
Remote controller
Indoor unit
21-EN
+001111052201_00Ta.book Page 21 Friday, November 20, 2009 11:45 AM
High-Wall Type
Installation Manual
–22–
Toshiba
EN
11 APPLICABLE CONTROLS
A wired remote controller is necessary for this function. This function cannot be ope rate with a wirele ss remote controller.
REQUIREMENT
• When you use this air conditioner for the first time, it takes approx. 5 minutes until the remote controller becomes available after power-on. This is normal.
<When power is turned on for the first time after installation>
It takes approx. 5 minutes until the remote controller becomes available.
<When power is turned on for the second (or later) time>
It takes approx. 1 minute until the remote controller becomes available.
• Normal settings were made as factory default. Change the indoor unit settings as required.
• Use the wired remote controller to change the settings.
Changing of settings of for
applicable controls
Basic procedure for changing sett ings
Change the settings while the air conditioner is not working. (Be sure to stop the air conditioner before making settings.)
Procedure 1
Push button and temp. setup button simultaneously for at least 4 seconds. After a while, the display flashes as shown in the figure. Confirm that the CODE No. is [01].
• If the CODE No. is not [01], push button to erase the display content, and repeat the procedure from the beginning. (No operation of the remote controller is accepted for a while after button is pushed.)
* The settings cannot be changed using the
wireless remote controller, sub remote controller, or remote-controller less system (for central remote controller only). Therefore, install the wired remote controller to change the settings.
Approx. 5 minutes
Power on
“SETTING” flashes
“SETTING” goes out
Remote controller is available
Approx. 1 minutes
Power on
“SETTING” flashes
“SETTING” goes out
Remote controller is available
1
6
1 3
2
5
4
(* Display content varies with
the indoor unit model.)
22-EN
+001111052201_00Ta.book Page 22 Friday, November 20, 2009 11:45 AM
High-Wall Type
Installation Manual
–23–
Toshiba
Procedure 2
Each time you push button, indoor unit numbers in the control group change cyclically. Select the indoor unit you want to change settings for. The fan of the selected unit runs and the louvers start swinging. You can confirm the indoor unit for which you want to change settings.
Procedure 3
Using temp. setup / buttons, specify CODE No. [ ].
Procedure 4
Using timer time / buttons, select SET DATA [ ].
Procedure 5
Push button. When the display changes from flashing to lit, the setup is completed.
• To change settings of another indoor unit, repeat from Procedure
2.
• To change other settings of the selected indoor unit, repeat from Procedure 3. Use button to clear the settings. To make settings after button was pushed, repeat from Procedure
2.
Procedure 6
When settings have been completed, push button to determine the settings. When button is pushed, “SETTING” flashes and then the display content disappears and the air conditioner enters the normal stop mode. (While “SETTING” is flashing, no operation of the remote controller is accepted.)
Change of lighting time of filter
sign
According to the installation condition, the lighting time of the filter sign (Notification of filter cleaning) can be changed. Follow to the basic operation procedure (1 2 3 4 5 6).
• For the CODE No. in Procedure 3, specify [01].
• For the [SET DATA] in Procedure
4, select the
SET DATA of filter sign lighting time from the following table.
To secure better effect of heating
When it is difficult to obtain satisfactory heating due to installation place of the indoor unit or structure of the room, the detection temperature of heating can be raised. Also use a circulator, etc. to circulate heat air near the ceiling. Follow to the basic operation procedure (1 2 3 4 5 6).
• For the CODE No. in Procedure 3, specify [06].
• For the SET DATA in Procedure 4, select the
SET DATA of shift value of detection temperature to be set up from the table below.
Setup data Filter sign lighting time
0000 None 0001 150H (Factory default) 0002 2500H 0003 5000H 0004 10000H
Setup data Detection temp shift value
0000 No shift 0001 + 1.8 °F (+1 °C) 0002 + 3.6 °F (+2 °C)
0003
+ 5.4 °F (+3 °C)
(Factory default)
0004 + 7.2 °F (+4 °C) 0005 + 9 °F (+5 °C) 0006 + 10.8 °F (+6 °C)
23-EN
+001111052201_00Ta.book Page 23 Friday, November 20, 2009 11:45 AM
High-Wall Type
Installation Manual
–24–
Toshiba
EN
How to set up power saving
mode
1. Push button for at least four seconds
when the air conditioner is not working.
flashes.
Indicates CODE No. “C2.”
2. Select an indoor unit to be set by pushing
(left side of the button). Each time you push the button, unit numbers change as follows:
3. Adjust the power save setting by pushing TIME buttons. Each push of the button changes the power level by 1% within the range from 100% to 50%.
* Factory default is 75%.
4. Determine the setting by pushing button.
5. Push button to complete the setting.
Remote controller switch
monitoring function
This function is available to call the service monitor mode from the remote controller during a test run to acquire temperatures of sensors of the remote controller, indoor unit, and outdoor unit.
1. Push and buttons simultaneously for
at least 4 seconds to call the service monitor mode. The service monitor indicator lights up and the header indoor unit number is displayed first. CODE No. is also displayed.
2. Pushing TEMP. buttons, select the number of sensor, etc. (CODE No.) to be monitored. (See the following table.)
3. Pushing
(left side of the button),
select an indoor unit to be monitored. The sensor temperatures of indoor units and their outdoor unit in the control group are displayed.
4. Push
button to return to the normal
display.
UNIT No.
1-1
UNIT No.
1-2
UNIT No.
1-3
UNIT No.
1-4
Setting of power level in power saving mode
Indoor unit data
CODE No. Data name
01 Room temperature (remote controller) 02 Indoor unit intake air temperature (TA)
03
Indoor unit heat exchanger (coil)
temperature (TCJ)
04
Indoor unit heat exchanger (coil)
temperature (TC)
F3
Indoor unit fan cumulative operating hours
(x1 h)
F8 Indoor unit discharge air temperature
13
4
2
24-EN
+001111052201_00Ta.book Page 24 Friday, November 20, 2009 11:45 AM
High-Wall Type
Installation Manual
–25–
Toshiba
Group control
Group control is not available with the supplied wireless remote controller. Use the optional wired remote controller.
In case of group control for system of multiple units
One remote controller can control maximum 8 indoor units as a group.
In case of group control in single system
• For wiring procedure and wiring method of the
individual line (Identical refrigerant line) system, follow to “Electric work”.
• Wiring between lines is performed in the
following procedure. Connect the terminal block (A/B) of the indoor unit connected with a remote controller to the terminal blocks (A/B) of the indoor units of other indoor units by wiring the inter-unit wire of the remote controller.
• When the circuit breaker and leakage breaker
are turned on, the automatic address setup starts and which indicates that address is being set up flashes on the display part. During setup of automatic address, the remote controller operation is not accepted.
Required time up to the finish of automatic addressing is approx. 5 minutes.
NOTE
In some cases, it is necessary to change the address manually after setup of the automatic address according to the system configuration of the group control.
Outdoor unit data
CODE No. Data name
60
Outdoor unit heat exchanger (coil)
temperature (TE)
61 Outside air temperature (TO) 62
Compressor discharge air temperature
(TD)
63 Compressor intake air temperature (TS) 64 65 Heat sink temperature (THS)
6A Operating current (x1/10) F1
Compressor cumulative operating hours
(x100h)
Outdoor unit
Outdoor unit
Outdoor unit
Outdoor unit Outdoor unit
Indoor unit
Indoor unit
Indoor unit Indoor unit Indoor unit
Remote
Controller
(Max. 8 units)
Finish address setup by power-ON
25-EN
+001111052201_00Ta.book Page 25 Friday, November 20, 2009 11:45 AM
High-Wall Type
Installation Manual
–26–
Toshiba
EN
Manual address setup procedure
(Procedure example 1)
While the operation stops, change the setup. (Be sure to stop the operation of the unit.)
Procedure 1
Push simultaneously + + buttons for 4 seconds or more. After a while, the display part flashes as shown below. Check the displayed CODE No. is [10].
• When the CODE No. is other than [10], push
button to erase the display and repeat procedure from the first step. (After pushing button, operation of the remote controller is not accepted for approx. 1 minute.) (For a group control, No. of the firstly displayed indoor unit becomes the header unit.)
Procedure 2
Every pushing button, the indoor UNIT No. in the group control is displayed in order. Select the indoor unit of which setup is changed. In this time, the position of the indoor unit of which setup is changed can be confirmed because fan and louver of the selected indoor unit operate.
Procedure 3
1. Using temp. setup / buttons, specify CODE No. [12]. (CODE No. [12]: Line address)
2. Using timer time / buttons, change the line address from [3] to [2].
3. Push button. In this time, the setup finishes when the display changes from flashing to lighting.
Procedure 4
1. Using temp. setup / buttons, specify CODE No. [13]. (CODE No. [13]: Indoor address)
2. Using timer time / buttons, change the indoor address from [3] to [2].
3. Push button. In this time, the setup finishes when the display changes from flashing to lighting.
2,61
7
3
-1,
4
-1,
5
-1,
7
3
-3,
4
-3,
3
-2,
4
-2,
5
-2
5
-3,
(* Display changes according to
the model No. of indoor unit.)
Indoor UNIT No. before setup change is displayed.
Indoor UNIT No. before setup change is displayed.
26-EN
+001111052201_00Ta.book Page 26 Friday, November 20, 2009 11:45 AM
Loading...
+ 61 hidden pages