Misuse of this equipment can result in property damage or human injury.
Because controlled system applications vary widely, you should satisfy yourself
as to the acceptability of this equipment for your intended purpose.
In no event will Toshiba Corporation be responsible or liable for either indirect
or consequential damage or injury that may result from the use of this equipment.
No patent liability is assumed by Toshiba Corporation with respect to use of
information, illustrations, circuits, equipment or examples of application in this
publication.
Toshiba Corporation reserves the right to make changes and improvements to this
publication and/or related products at any time without notice. No obligation shall be
incurred other than as noted in this publication.
This publication is copyrighted and contains proprietary material. No part of this book
may be reproduced, stored in a retrieval system, or transmitted, in any form or by any
means ¾ electrical, mechanical, photocopying, recording, or otherwise ¾ without
obtaining prior written permission from Toshiba Corporation.
The Programmable Cont r oller PROSEC T1 and T1S (hereafter called T1/T1S) complies with the
requirements of t he EMC Directive 89/336/EEC and Low Voltage Directive 72/23/EEC under the
condition of use according to the instructions described in this manual.
The contents of the conformity are shown below.
Application of EMC :89/336/EEC (as amended by 91/263/EEC and 92/31/EEC)
Council DirectiveLVD :72/23/EEC (as amended by 93/68/EEC)
Manufacture’s Name:Toshiba Corporation, Fuchu Works
Address:1, Toshiba-Cho
EMC
Radiated Interference:EN 55011 Group 1 Class A
Mains Interference:EN 55011 Group 1 Class A
Radiated Susceptibility:ENV50140
Conducted RFI Susceptibility:ENV50141, IEC100-4-6.
Electrostatic Discharge:IEC1000-4-2
Electrical Fast Transient:IEC1000-4-4
LVD:EN61131-2:19953.10Dielectric Properties
4.Mechanical Requirements
Supplementary information:
(1) Included Handy Programmer THP911A*S.
(2) Included each type of associated input/output unit in a typical configuration.
(3) Product must be installed in accordance with manufacturers instructions
This manual is prepared for users of Toshiba’s Programmable Controller T1/T1S.
Read this manual thoroughly before using the T1/T1S. Also, keep this manual and related manuals
so that you can read them anytime while the T1/T1S is in operation.
General Information
1. The T1/T1S has been designed and manufactured for use in an industr ial environment.
However, the T1/T1S is not intended to be used for systems which may endanger human
life. Consult Toshiba if you intend t o use the T1/T1S for a special applicat ion, such as
transportation machines, medical apparat us, aviation and space systems, nuclear
controls, submarine systems, etc.
2. The T1/T1S has been manufactured under strict quality control. However, to keep safety
of overall automated system, fail-safe systems should be considered outside the T1/T1S.
3. In installation, wiring, operation and maintenance of the T1/T1S, it is assumed that the
users have general knowledge of industrial elect r ic cont r ol system s.
If this product is handled or operat ed im pr operly, electrical shock, fire or dam age to this
product could result.
4. This manual has been written for users who are f am iliar with Prog rammable Controllers
and industrial control equipment. Cont act Toshiba if you have any questions about this
manual.
5. Sample programs and circuits described in this manual are provided for explaining the
operations and applications of the T1/T1S. You should test completely if you use them as
a part of your application system.
Hazard Classifications
In this manual, the following two hazard classifications are used to explain the safety
precautions.
!
WARNING
!
CAUTION
Even a precaution is classified as CAUTION, it may cause serious results depending on the
situation. Observe all the safety precautions described on this manual.
Indicates a potentially hazardous situation which, if not avoided, could
result in death or serious injury.
Indicates a potentially hazardous situation which, if not avoided, may
result in minor or moderate injur y. I t m ay also be used to aler t
1. Excess temperature, humidity, vibration, shock s, or dusty and corrosive gas
environment can cause electrical shock, fire or malfunction. Install and use the T1/T1S
and related equipment in the environment described in this manual.
2. Improper installation directions or insufficient installation can cause fir e or t he units to
drop. Install the T1/T 1S and r elated equipment in accordance with the instructions
described in this manual.
3. Turn off power before installing or removing any units, modules, r acks or terminal
blocks. Failure to do so can cause electrical shock or dam age to the T1/T1S and
related equipment.
6F3B0250
4. Entering wire scraps or other foreign debris into to the T1/T 1S and r elated equipment
can cause fire or malfunction. Pay att ention to prevent entering them into the T1/T1S
and related equipment during inst allat ion and wiring.
5. Turn off power immediat ely if the T1/T1S or related eq uipm ent is emitting smoke or
odor. Operation under such situation can cause fire or electrical shock. Also
unauthorized repairing will cause fire or serious accidents. Do not attempt to repair.
Contact Toshiba for repairing.
Wiring:
!
CAUTION
1. Turn off power before wiring to minimize the risk of electrical shock.
2. Exposed conductive parts of wire can cause electrical shock. Use crimp-style terminals
with insulating sheath or insulating tape to cover the conductive parts . Also close t he
terminal covers securely on the terminal blocks when wiring has been completed.
3. Operation without grounding may cause electrical shock or malfunction. Connect the
ground terminal on the T1/T1S to the system ground.
4. Applying excess power voltage to the T1/T1S can cause explosion or fire. Apply power
of the specified rating s descr ibed in t he manual.
5. Improper wiring can cause fire, electr ical shock or malfunction. Obser ve local
regulations on wiring and grounding.
1. Configure emergency stop and safety interlocking circuits out side t he T1/T1S.
Otherwise, malfunction of t he T1/T1S can cause injury or serious accidents.
!
CAUTION
2. Operate the T1/T1S and t he r elated modules with closing the terminal covers. Keep
hands away from terminals while power on, to avoid the risk of electrical shock.
3. When you attempt to perform force outputs, RUN/HALT controls, etc. during operation,
carefully check for safety.
6F3B0250
4. Turn on power to the T1/T1S before turning on power to the loads. Failure to do so may
cause unexpected behavior of the loads.
5. Do not use any modules of the T1/T1S for the purpose other than specified. This can
cause electrical shock or injury.
6. Do not modify the T1/T1S and r elat ed equipment in hardware nor software. This can
cause fire, electrical shock or injury.
7. Configure the external circuit so that the external 24 Vdc power required for t r ansistor
output circuits and power to the loads are switched on/off simultaneously.
Also, turn off power to the loads before turning of f power to the T1/T1S.
8. Install fuses appropriate to t he load cur rent in the external circuits for t he outputs.
Failure to do so can cause fire in case of load over-cur r ent .
9. Check for proper connections on wires, connector s and m odules. Insufficient contact
can cause malfunction or damage to t he T1/T1S and related equipment .
1. Turn off power before removing or replacing units, modules, terminal blocks or wires.
Failure to do so can cause electrical shock or damag e t o the T1/T1S and related
equipment.
2. When you remove both input and out put terminal blocks with wires for maintenance
purpose, pay attention to prevent inserting them upside down.
3. Do not insert your finger into t he expansion rack’s ventilation hole during power on.
This can cause electrical shock.
6F3B0250
4. Do not disassemble the T1/T1S because ther e ar e hazardous voltag e par ts inside.
5. Perform daily checks, periodical checks and cleaning to maintain the system in normal
condition and to prevent unnecessary troubles.
6. Check by referring “T r oubleshooting” section of this manual when operating
improperly. Contact Toshiba for repairing if t he T1/T1S or related eq uipm ent is failed.
Toshiba will not guarantee proper operation nor safety for unauthorized repairing.
7. The contact reliability of t he out put relays will reduce if the switching exceeds the
specified life. Replace the unit or module if exceeded.
The safety label as shown on the right is
attached to the power terminal of the
T1/T1S.
Remove the mount paper before wiring.
Peel off the label fr om the mount paper
and stick it near the power terminals
where it can be readily seen.
Contact Toshiba if the label is damaged.
Safety Precautions
CAUTION
!
Do not touch terminals
while power on.
Hazardous voltage can shock , bur n or c ause death.
Do not touch terminals while power on.
Read related manual thoroughly for safety.
Stick this seal on uni t or near unit.
This manual has been prepared for first-time users of Toshiba’s Programmable Controller
T1 and/or T1S to enable a full under standing of the configuration of the equipment, and to
enable the user to obtain the maximum benefit s of the equipment.
This manual introduces the T1 and T1S, and explains the system configuration,
specifications, installation and wiring for T1/T1S’s basic hardware. This manual provides
the information for designing T1/T1S user program, such as the internal operation, memory
configuration, I/O allocation and programming instructions. Information for maintenance
and troubleshooting are also provided in this manual.
The specifications of the option cards, expansion units, and I/O modules, and how to use
them, are explained in the separate manual. Read the T1/T1S User’s Manual - Expansion
I/O - when using the option cards, expansion units, and/or I/O modules.
The T1/T1S’s computer link function and T1S’s multi-purpose communication functions are
covered by the separate manual. Read the T1/T1S User ’s Manual - Comm unicat ion
Function - for details.
6F3B0250
Inside This Manual
This manual consists of 10 main sections and an appendix.
Section 1 outlines the T1/T1S configuration. To fully understand the T1/T1S, it is important
to read this section carefully. Sections 2, t o 4 descr ibe the hardware used in designing
external circuits and panels. Sections 5 to 7 are mainly concerned with software. Section 8
explains the T1/T1S’s special I/O functions. Sections 9 and 10 describe the maintenance
procedure for the T1/T1S, to ensure safe operation and long service life.
Related Manuals
The following related manuals are available for T1/T1S. Besides this manual, read t he
following manuals for your better under st anding.
T1/T1S User’s Manual - Basic Hardware and Function -
T1/T1S User’s Manual - Expansion I/O T1/T1S User’s Manual - Communication Function T-Series Handy Programmer (HP911) Operation Manual
T-Series Program Development System (T-PDS) User’s Manual
NOTE
Other than the listed above, some T1 related manuals for special I/O modules
and data transmission modules are available. Contact Toshiba for more
information.
The following is a list of abbreviations and acronyms used in this m anual.
6F3B0250
About This Manual
s
mmmm
ASCII
AWG
BCC
CCW
CPU
CW
EEPROM
H
I/O
LED
LSB
ms
MSB
PWM
RAM
ROM
Vac
Vdc
microsecond
American Standard Code For Infor m at ion I nt erchange
American W ir e Gage
Block Check Code
Counter-Clockwise
Central Processing Unit
Clockwise
Electrically Erasable Programmable Read O nly Memory
hexadecimal (when it appears in front of an alphanumer ic st r ing)
Input/Output
Light Emitting Diode
Least Significant Bit
millisecond
Most Significant Bit
Pulse Width Modulation
Random Access Memory
Read Only Memory
AC voltage
DC voltage
The T1 Series are compact, block style, high-performance programmable controllers
with a range of 16 to 328 input and output points.
The T1 Series are available in two versions, T1 and T1S. T he T1S is an enhanced
version against the standard T1.
The figure below shows the T1 Series line-up. The T1 Series consists of the total 12
types.
T1 Seri esT1T1-16T1-MDR 16
6F3B0250
T1-MAR16
T1-MDR16D
T1-28T1-MDR28
T1-MAR28
T1-MDR28D
T1-40T1-MDR40
T1-MAR40
T1-MDR40D
T1ST1-40ST1-MDR40S
T1-MAR40S
T1-MDR40SD
I/O points:
The T1 Series are available in four models, T1-16, T1-28, T1- 40 and T1-40S. Each
model has the following I/O points.
T1-16T1-28T1-40T1-40S
Input
Output
Expansion
The T1-16 and T1-28 are fixed I/O non-expandable controllers.
The T1-40 and T1-40S, however, provides additional flexibility. They are expandable in
three ways, option cards, expansion rack and expansion unit.
The T1-40/T1-40S can hold two option cards. These are approximately 1/2 the size of a
credit card. Also, the T1-40/ T1-40S can be connected to either one expansion rack or
one expansion unit. The expansion rack (2-slot type or 4-slot type) allows the T140/T1-40S to use most T2 series I/O modules. The expansion unit is a fixed I/O unit. It
has 32 I/O points (16 inputs and 16 outputs).
If two 16 points option cards are inserted and t he 4- slot expansion rack with four 64
points modules is connected to the T1-40/T1-40S, it can control up to 328 points.
Program memory capacity of the T1 is 2 k steps. And that of the T1S is 8 k steps. Whole
the program and a part of data registers are stored in built - in EEPRO M.
T1T1S
Memory
Program capacity
Data capacity
EEPROM back-up
RAM back-up
RAM (for execution) and EEPROM (for back-up)
2 k steps8 k steps
(4 k mode or 8 k mode)
Auxiliary relay: 1024 points
Timer:64 points
Counter:64 points
Data register: 1024 words
Program and leading 512 words
of Data register
Capacitor
(6 hours or more at 25°C)
Auxiliary relay: 4096 points
Timer:256 points
Counter:256 points
Data register: 4096 words
Program and the user specified
range of Data regist er ( 0 to
2048 words)
Capacitor
(168 hours or more at 25°C)
Control functions:
In addition to the basic relay ladder functions, t he T1/T1S provides functions such as
data operations, arithmetic operations, various functions, etc. Furthermore, its high
speed counter functions, pulse output functions and data communication funct ions
allow its application to a wide scope of control systems.
T1T1S
Language
Number of
instructions
Subroutines
Execution speed
Real-time clock/
calendar
Communication
Construction:
The T1/T1S is a compact, easy-handling block style programmable contr oller . The
T1/T1S has all of the features of a block style controller. In addition, the T1-40/T1-40S
has modular expandability. The T1-40/T 1 - 40S pr ovides flexibility into the block style
controller.
Ladder diagram with function block
Basic:17 types
Function: 76 types
16 (nesting not allowed)256 (up to 3 levels of nesting)
RS-232C (programmer por t)RS-232C (programmer por t),
Basic:21 types
Function: 99 types
hours, minutes, seconds)
RS-485 (multi-purpose)
Series compatibility:
Programming instruct ions ar e upward compat ible in the T-Series programmable
controllers. The T1/T1S programs can be used for other models of the T-Ser ies, T2,
T2E, T2N, T3 and T3H. Peripheral tools can also be shared.
The T1-40/T1-40S has two slots for the option card, which is approximately 1/2 the size
of a credit card. The following eight types of the option cards ar e available.
16 points DC input
·
16 points DC output
·
8 DC inputs + 8 DC outputs
·
1 channel analog input (0 to 5 V/0 to 20 mA)
·
1 channel analog input (±10 V)
·
1 channel analog output (0 to 20 mA)
·
1 channel analog output (±10 V)
·
Field network TOSLINE-F10 rem o t e
·
By using the 16 points input and 16 points output cards, t he T1-40/T1-40S can control
up to 72 I/O points without enlarging the mounting space.
Built-in high speed counter:
Two single-phase or one quadrature (2-phase) pulses can be counted. The acceptable
pulse rate is up to 5 kHz. (DC input t ype only)
6F3B0250
Built-in analog setting adjust ers:
Two analog setting adjusters are pr ovided on the T1/T1S. This allows operators to
adjust time or other control par am eters easily using a screwdriver.
High speed processing:
Sophisticated machine control applications require high speed data manipulations. The
T1/T1S is designed to meet these requirements.
1.4 ms per contact
·
4.2 ms per 16-bit transfer
·
The T1/T1S also supports int errupt input function (DC input type only). This allows
immediate operation independent of pr ogram scan.
High performance software:
The T1 offers 17 basic ladder instructions and 76 function instructions. The T1S offers
21 basic ladder instructions and 99 function instructions.
Subroutines, Interrupt functions, Indirect addressing, For /Next loops, Pre-derivative
real PID, etc. are standard on the T1/T1S. These f unct ions allow the T1/T1S to be
applied to the most demanding control applicat ions.
Battery-less operation:
The T1/T1S has a standard built-in EEPROM, permitting operation without need of a
battery. Also, the variable data can be written into and/or r ead from the EEPROM,
providing completely maintenance-free back-up operation.
This function is an important feature for OEMs, because it can eliminate the need for
changing the battery every few years. The cost of the battery is also eliminated.
One point of variable frequency pulses (m ax. 5 kHz) or variable duty pulses can be
output. These functions can be used to drive a stepping motor or to simulate an analog
output. (DC input type only)
Built-in computer link function:
The T1/T1S’s RS-232C prog rammer port can accept the comput er link protocol (data
read/write). This results in easy connection to a hig her level comput er, an operator
interface unit, etc.
The parity setting of the programmer port can be selected either odd or none. The none
parity mode is provided especially for telephone modem connection. Using m odems,
remote programming/monitoring is available.
Real-time control data link network:
By inserting the TOSLINE-F10 rem ote card (option card) into the T1-40/T1-40S, high
speed data link network can be established. In this network, upper T-series PLC model
(T2/T2E/T2N or T3/T3H) works as master and up t o 16 T1-40/T1-40Ss can be
connected as remote. Each T1-40/T1-40S can exchange data with the master through
1 word input and 1 word output. The transmission speed can be selected either 750
kbps or 250 kbps.
T2 Series I/O module interface:
In addition to the option cards, the T1-40/T1-40S has a interface for connecting the T2
Series I/O modules. Up to four modules can be connected to the T1-40/T1-40S. The
following I/O modules are available.
The sampling trace is the function to collect the user specified data every user specified
timing (minimum every scan), and to display the collected data on the programmer
screen in time chart and/or trend graph format. This function is useful for check ing the
input signals changing.
The collecting capacities between T1 and T1S are different as follows.
T1 ..... 1 register - 128 times, or 8 devices - 256 times
By registering your passwords, four levels of pr ot ection is available according to the
security levels required for your application.
Level 4: Reading/writing program and writing data are prohibited
Level 3: Reading/writing program are pr ohibit ed
Level 2: Writ ing program is prohibited
Level 1: No protection (changing passwords is available only in this level)
Two points of solid-st at e out put :
Each model of the T1/T1S has two points of solid-state output (transistors for DC input
type and triacs for AC input type). T hese solid- s t at e outputs are suitable for f requent
switching application.
Removable terminal blocks:
The T1-28, T1-40 and T 1- 40S ar e equipped with removable terminal blocks. This
supports the easy maintenance work.
6F3B0250
DIN rail mounting:
The T1/T1S is equipped with brackets for mounting on a standard 35 mm DIN rail. The
T1/T1S can be mounted on a DIN r ail as well as screw mounting.
On-line program changes: (T1S only)
When the T 1S’s memory mode is set to 4 k steps mode, on-line (in RUN mode)
program changes are available. Furthermore, progr am writ ing into the built-in
EEPROM is also available in RUN mode. These functions are usef ul in pr ogram
debugging stage.
Real-time clock/calendar function: (T1S only)
The T1S has the real-time-clock / calendar function (year, month, day, day of the week,
hours, minutes, seconds) that can be used for performing scheduled operations, data
gathering with time stamps, et c. The real-time-clock/calendar data is backed up by
built-in capacitor for power off. The back-up period is mor e than 7 days at 25 °C.
RS-485 multi-purpose communication port: ( T1S only)
The T1S has an RS-485 multi-purpose communication port. Using this port, one of the
following communication modes can be selected.
Computer link mode:
····
Up to 32 T1Ss can be connected to a master comput er . By using this mode,
MMI/SCADA system can be easily configured.
Data link mode:
····
linked together. This direct link is inexpensive, easily configur ed and r equires no
special programming.
Free ASCII mode:
····
received through this port. A ter m inal, pr int er , bar-code reader, or other ser ial
ASCII device can be directly connected.
T-series computer link prot ocol can be used in this mode.
Two PLCs (any combination of T1S, T2E or T2N) can be directly
User defined ASCII messages can be t r ansm it t ed and
The I/O points on the T1-16 and T1-28 are not expandable. The T1-40 and T1-40S,
however, provides I/O expandability by using the option cards, expansion rack and
expansion unit.
The T1-40/T1-40S can hold up to two option cards. Also, the T1-40/T1- 40S can be
connected to either one expansion rack (2-slot or 4- slot) or one expansion unit. By
using the expansion rack, most of the T2 Series I/O modules can be used with the
T1-40/T1-40S.
Available option cards
·
DI116:16 points DC input
DO116: 16 points DC output
DD116: 8 points DC input + 8 points DC output
AD121: 1 channel analog input (0 to 5V or 0 to 20mA)
AD131: 1 channel analog input (-10 to +10V)
DA121: 1 channel analog output (0 to 20mA)
DA131: 1 channel analog output (-10 to +10V)
FR112: TOSLI NE- F10 r emote station
6F3B0250
Available expansion racks
·
BU152: Up to 2 I/O modules can be mounted
BU154: Up to 4 I/O modules can be mounted
Available expansion units
·
T1-EDR32: 16 points DC input + 16 points relay output
T1-EAR32: 16 points AC input + 16 points relay output
Available I/O expansion configuration
·
ModelUnit configurationI/O points
T1-1616 points(8 in / 8 out)
T1-2828 points(14 in / 14 out)
T1-40
or
T1-40S56 points(40 in / 16 out)
T1-16
T1-28
T1-40(S)
T1-40(S)
T1-40(S)
T1-40(S)
T1-40(S)
+
DD116
+
DO116
+
+
DI116
DI116
+
DI116
40 points(24 in / 16 out)
56 points(32 in / 24 out)
56 points(24 in / 32 out)
72 points(56 in / 16 out)
The basic unit is available in four models, the T 1- 16, T1-28, T1-40 and T1- 40S.
And each model is available in three types, depending on the power supply and input
types.
PWRLitInt er nal 5 Vdc power is norm a l.
(Power) (g r een)Not litInternal 5 Vdc power is not nor m al.
RUN(green)BlinkingHOLD mode
FLTLitERRO R mode
(Fault)( r ed)BlinkingHar dware error (programmer cannot be connect ed)
AUX
(Auxiliary) (red)
PWRPWR
RUNRUN
FLTFLT
AUX
LitRUN mode (in oper at ion)
Not litHALT mode or ERRO R mode
Not litNormal
-
Can be controlled by user program. Lit when S320 is
ON and unlit when S320 is OFF. (T1-40/T1-40S)
6F3B0250
Mode control switch:
Controls the operation modes of t he T1/T1S.
H (HALT)When the switch is turned to H (HALT) side, the T1/T1S stops
program execution (HALT mode) . In this position, RUN/HALT
command from the prog rammer is disabled. In case of the T1,
programming is available only in the HALT m ode.
R (RUN)When the switch is turned to R (RUN) side, the T1/T1S starts program
execution. This is the position during normal oper ation.
In this position, RUN/HALT com m and from the progra m m er is also
available.
Analog setting adjusters:
Two analog setting adjusters are provided. The V0 value is stored in SW30 and the V1
value is stored in SW31. The converted value range is 0 to 1000. Refer t o sect ion 8.5
for details of the analog setting function.
Programmer port connector:
Used to connect the programmer cable. The interface is RS-232C. T his por t can also
be used for the computer link funct ion. Ref er to section 1.6 for more inform at ion about
the computer link funct ion.
Used to insert the option cards. Two slots are pr ovided. Refer to separate “T1/ T1S
Use’s Manual - Expansion I/O -” for details of the option cards.
Expansion connector (T1-40/T1-40S):
Used to connect the expansion rack or expansion unit. Refer to separate “T1/T1S Use’s
Manual - Expansion I/O -” for details of the T2 type I/O modules.
RS-485 port (T1-40S only):
Used to connect a computer (SCADA system), operator interface unit, ot her T1S, or
many kinds of serial ASCII devices including Toshiba’s I nverter through RS-485
interface. Refer to section 1.7 for more information about the T1S’s RS-485 m ult ipurpose communication functions.
Mounting holes:
Used to fix the T1/T1S on a mount ing frame by screws. The mounting holes ar e
provided at two opposite corners.
Use two M4 screws for mounting. See section 4.2 for
T1
DIN rail bracket:
The DIN rail bracket is pr ovided at the rear for mounting the T1/T1S on a 35 mm DIN
rail. See section 4.2 for inst alling the unit.
The T1-40/T1-40S can hold up to two option cards for expanding I/O points, etc.
The following eight types of t he opt ion car ds are available.
For details of the option cards, r efer to the separate manual “T1/T1S User’s Manual
Expansion I/O -“.
TypeDescriptionPower supply
DI11616 points input, 24 Vdc - 5 mASupplied from the
DO11616 points output, 24 Vdc - 100 mAbasic unit (5 Vdc)
DD1168 point s input, 24 Vdc - 5 mA
+ 8 points output, 24 Vdc - 100 mA
AD1211 channel analog input, 0 to 5 V / 0 t o 20 m A
AD131
DA1211 channel analog output, 0 to 20 m A
DA131
FR112TOSLINE-F10 remote station,
1 channel analog input, ±10 V
1 channel analog output, ±10 V
1 word input + 1 word output
6F3B0250
-
T1-40
or
T1-40S
NOTE
Option card
The TOSLINE-F10 remote car d ( FR112) can be used with other cards.
However two FR112s cannot be used together.
The T1-40/T1-40S can be connected to either one expansion rack or one expansion
unit.
The following two types of the expansion racks are available. By using the expansion
rack, T2 Series I/O modules can be used with the T1-40/T1-40S.
For details of the expansion rack, refer to the separate manual “T1/T1S User’s Manual
Expansion I/O -“.
-
TypeDescriptionPower supply
BU1522 slots for I/O modulesSupplied from the
BU1544 slots for I/O modulesbasic unit
BU152BU154
6F3B0250
1. System Configuration
NOTE
Expansion connectors
(1) A 0.15 m expansion cable is supplied with the expansion rack.
(2) Internal 5 Vdc power for I/O modules is supplied from the T1-40/T1-40S
basic unit. No power supply module is required on the expansion rack.
(3) Expansion connectors are provided on the both sides. However either one
As listed below, various I/O modules are available for the T1-40/T1-40S, allowing it to
be used for a wide variety of applications. Up to four I/O modules can be used with the
T1-40/T1-40S by connecting the expansion rack .
For details of the I/O modules, refer to the separate manual “T1/T1S User’s Manual
Expansion I/O -“.
AC61Triac out put
AI21Analog input4 channels, 1 to 5 V / 4 to 20 mA, 8-bit resolution
AI224 channels, 1 to 5 V / 4 to 20 mA, 12-bit resolution
AI314 channels, 0 to 10 V, 8-bit resolution
AI32
AO31Analog output2 channels, 1 to 5 V / 4 to 20 mA / 0 t o 10 V,
AO222 channels, 1 t o 5 V / 4 to 20 mA, 12-bit resolution
AO32
PI21Pulse input1 channel (2-phase and zero marker), 5/12 V,
The T1-40/T1-40S can be connected to either one expansion rack or one expansion
unit.
The following two types of the expansion units are available. Each expansion unit has
32 points I/O (16 inputs and 16 outputs).
For details of the expansion unit, refer to the separate manual “T1/T1S User’s Manual
Expansion I/O -“.
TypeDescriptionPower supply
T1-EDR32Input:16 points, 24 Vdc - 7 mASupplied from the
Output: 16 points, relay, 240 Vac/24 Vdc (max.) -
T1-EAR32Input :16 points, 100 to 120 Vac - 7 mA
Output: 16 points, relay, 240 Vac/24 Vdc (max.) -
2 A/point (max.)
2 A/point (max.)
6F3B0250
1. System Configuration
basic unit (5Vdc)
-
NOTE
(1) A 0.5 m expansion cable is supplied with the expansion unit.
(2) Internal 5 Vdc power for expansion unit is supplied from the T1-40/T1-40S
(3) 24 Vdc power for output relay coils is required externally.
(4) DIN r ail br acket is provided.
ItemTypeDescription
Programmer port
connector
Option cardPT15SCable side connector for DI116,Soldering type
I/O connectorPT15FDO116, or DD116Flat cable type
Expansion cableCS1R2For connecting the expansion rack , 0. 15 m length,
Empty slot cover
6F3B0250
PT16SFor RS-232C computer link, with 2 m cable
(spare parts)
CS1R5BFor connecting the expansion unit, 0.5m length,
The interface of t he T1/T1S’s programm er por t is RS-232C. Normally this port is used
to connect the programmer . However, this por t can also be used for the computer link
function.
The computer link is a data comm unicat ion function between computer or operator
interface unit and the T1/ T1S. The data in the T1/T1S can be read and written by
creating simple communication prog r am on the computer. The computer link protocol
of the T1/T1S is published in “ T1/T1S User’s Manual - Communication Function -”.
ItemSpecifications
InterfaceConforms to RS-232C
Transmission systemHalf-duplex
SynchronizationStar t - stop system (asynchronous)
Transmission speed9600 bps (fixed)
Transmission distance15 m max.
Framin
ProtocolT-series computer link (ASCII)
Transmission delay option0 t o 300 m s
Start bit:
Data bits:
Parity:
Stop bit:
1 bit
8 bits (fixed)
Odd or none
1 bit (fixed)
Programmer (binary)
6F3B0250
1. System Configuration
By using the multi-drop adapter (CU111), multiple T1/T1Ss can be connected on an
RS-485 line. The T-series PLC programming software (T-PDS) can also be used in this
configuration.
Operator Interface
RS-232CRS-485 (1 km max.)
T1T1
NOTE
In case of the T1, ther e ar e functional limitations as follows.
·
·
C
U
Multi-drop configuration is available with version 1.10 or lat e r .
Programmer connection in t he m u lt i-drop configuration, none parity and
Master Com puter
C
U
T1
C
U
Max. 32 T1s
T1
transmission delay options are available with version 1.20 or later.
The T1S has an RS-485 muiti-purpose comm unication port. This port can work
independent of the programmer port.
By using this communication port, one of t he following three communication modes is
available, computer link mode, data link m ode and free ASCII mode.
For details of these funct ions, refer to the separate manual “T1/T1S User’s Manual
Communication Function -”.
ItemComputer linkFree ASCIIData link
InterfaceConforms to RS-458 (4-wire or 2-wire)
Transmission systemHalf-duplex
SynchronizationStart-stop system (asynchronous)
Transmission codeASCII/binar
Transmission speed300, 600, 1200, 2400, 4800, 9600, or
Transmission distance1 km max.
Framin
ProtocolT-series
Link configuration1-to-NN/A1-to-1
Transmission dela
option
ASCIIBinar
19200 bps (fixed)
19200 bps
Start bit:1 bit
Data bits:7 or 8 bits
Parity:Odd, even, or none
Stop bit:1 or 2 bits
User defined
computer link
(ASCII),
Programmer
(binary)
0 to 300 msN/AN/A
ASCII messages
Special
Special
6F3B0250
-
Computer link mode
T-series computer link prot ocol can be used in this mode. A maximum of 32 T1Ss can
be connected to a master computer.
By using this mode, all the T1S’s data can be accessed by a master com put er.
The T-series PLC programming software (T-PDS) can also be used in t his
configuration.
Two PLCs (any combination of T1S, T 2 E or T2N) can be directly linked together. This
direct link is inexpensive, easily configured and requires no special programming. Data
registers D0000 to D0031 are used for the data transfer.
T1S
T1T1
RS-485 (1 km max.)
Station No. 1
D0000
D0015
D0016
D0031
T1S
Station No. 2
D0000
D0015
D0016
D0031
Free ASCII mode
User defined ASCII messages can be t r ansmitted and received through this port.
A terminal, printer, bar- code reader, or other serial ASCII device can be directly
connected. This mode also allows the T1S to communicat e with other PLCs ( T1, T2E,
T2N, etc.), Toshiba’s I nvert ers (such as VF-S7/A5, G3), Toshiba’s motor protection
relay (S2E21), or others.
TOSLINE-F10 is a high speed data transm ission system suit ed for small points I/O
distribution system. By inserting the T O SLI NE- F10 r em ote card (FR112) into the T140/T1-40S, the T1-40/ T1-40S can work as a remote station of the TOSLINE-F10
network. On this network, the T1-40/T1-40S sends 1 word data to the mast er station
and receives 1 word data from the master stat ion.
ItemTOSLINE-F10 system specifications
TopologyBus (terminated at both ends)
Transmission distance
(without repeater)
Transmission speed750 kbps250 kbps
Scan transmission
capacity
Scan cycle7 ms / 32 words12 ms/32 words
Error checkingCRC check
6F3B0250
High speed modeLong distance mode
500 m max. (total)1 km max. (tot al)
512 points (32 words) max.
NOTE
(1) Ref er to the separate “T1 User’s Manual - Option Card and I/O
Module -“ for details of the TOSLINE-F10 remote card (FR112) .
(2) Ref er to the separate TOSLINE-F10 User’s Manual for details of overall
TOSLINE-F10 system.
Typical data link configuration
The figure below shows the typical data link configuration.
The following peripheral tools are available for the T1/T1S.
T-Series Program Development System (T-PDS)
The T-Series Program Development System ( T-PDS) is a software which runs on any
IBM-PC compatible personal computers such as Toshiba’s Notebook com puters. The
same T-PDS software supports on-line/off-line prog r am m ing, debugging and program
documentation for all the T-Series programmable controllers T1/T1S, T2/T2E/T2N and
T3/T3H.
User-friendly program editor includes cut & paste, address search & replace,
·
program block move/copy, etc.
Group programming - part program development by multiple desig ner s and
·
merging them into a complete program - enhance the software productivity.
Powerful monitoring, I/O force and data set functions fully support your program
·
debugging.
Documentation of programs with commentary makes your maintenance work easy.
·
Remote monitoring/prog r amming via modem (radio/phone) is possible.
·
6F3B0250
1. System Configuration
The table below shows the T-PDS versions that support the T1/ T1S.
TypePart numberVersions available for
T1T1S
T-PDS for WindowsTMW33E1SSVer 1.0 or later
T-PDS for MS-DOSTMM33I1SSVer 1.61 or later
*1)
*1)
Ver 1.2 or later
Ver 2.1 or later
*1) The T1S can be used with these versions. However, in this case, t her e are the
following functional limitat ions.
The program size setting is only available as 2 k. It is set to 4 k mode in the T1S.
·
Some of the added instructions (MAVE, DFL, HT OA, ATOH) may not be
·
edited/monitored. (depending on t he version)
NOTE
The connection cable for the T1 Series is different from that for upper T-Series
PLCs. These cables are supplied separately.
Connection cable for T1/T1S . . . Type: CJ105, 5 m length
Connection cable for T2/T3 ¼. Type: CJ905, 5 m length
The HP911A is a hand-held programmer, that can be used to program the T1/T1S
using ladder diagram. I t s por t abilit y makes it ideal for maint enance use at r e m ot e
locations.
The HP911A has the following features.
The HP911A supports ladder diagram pr ogramming of T- Series programmable
·
controllers T1/T1S, T2/T2E/T2N and T3.
Built-in EEPROM allows program copy between T-Series controller s .
·
Two display modes are available,
·
- Normal: 5 lines and 12 columns
- Zoom: Full device description
On-line data set and I/O force are useful for system checking.
·
Backlit LCD display allows operation in dim light.
·
6F3B0250
There are two types of the Handy Programm er (HP911) depending on the cable
included with.
TypePart numberCable included withVersions available for T1/T1S
HP911A
HP911
The T1S can be used with the HP911(A). However, there are the following functional
limitations.
The program size setting is only available as 2 k. I t is set to 4 k mode in the T1S.
·
Some of the added instructions (MAVE, DFL, HT OA, ATOH) cannot be
·
edited/monitored.
NOTE
THP911A*S
THP911**S
A 2 m connection cable for the T1/T1S (Type: CJ102) is supplied with the
HP911A. The cable for the T2/T3 is available separately. (Type: CJ902, 2 m
length)
2 m cable for T1/T1SVer 1.1 or later
2 m cable for the upper
The program storag e m odule (RM102) is an
external memory for storing the T1/T1S
program. By using the RM102, program saving
from the T1/T 1S to the RM102, and program
loading from the RM102 to the T1/ T1S can be
done without need of a programmer.
Because the RM102 has an EEPROM,
maintenance-free progr am storage and quick
saving/loading are available.
Multi-drop adapter (CU111)
The T1/T1S’s RS-232C programmer port
supports the computer link function.
When two or more T1/T1Ss are connected with
a master computer, the multi-drop adapter
(CU111) can be used. (One-to-N configuration)
The CU111 is an RS-232C/RS-485 converter
specially designed for the T1/T1S’s
programmer port.
Control methodStored program, cyclic scan system
Scan systemFloating scan or constant scan (10 - 200 ms, 10 ms units)
I/O updateBatch I/O refresh (direct I/O instruction available)
Program memoryRAM (capacitor back-up) and EEPROM (no back-up battery required)
RAM memory backup
Program capacity2 k steps8 k steps
Programmin
language
InstructionsBasic ladder instructions: 17
Execution speed
Program types1 main program
UserI/O register 512 points/32 words (X/XW, Y/YW)
dataAuxiliary
NoYes,
High speed counter (2 single or 1 quadrature),
Interrupt input (2 points),
Adjustable analo
Pulse output (CW+CCW or pulse+direction),
PWM output
1 port RS-232C (programmer port)
- for Pro
-
-
Sampling trace
(8 devices - 256 times or 1 re
-
-
rammer or Computer link connection
register (2 points),
ister - 128 times)
2. Specifications
(±30 s/month)
1 port RS-485
- Pro
- Computer link
- Data link
- Free ASCII
TOSLINE-F10 remote
(by option card)
Samplin
(8 devices and
3 re
times)
On-line
pro
On-line
EEPROM write
6F3B0250
rammer
trace
ister - 256
rammin
NOTE
(1) T he input specification of the T1- 16 ( AC power type) is dry contact input,
which supplies the power for input signals (24 Vdc) fr om the unit.
Other types are DC input, which requires external power for input signals.
(2) Hig h speed count er, interrupt input, pulse output and PWM output are
available in the DC input types.
(3) Hig h speed count er and interrupt input cannot be used simultaneously.
(4) Pulse output and PWM output cannot be used simultaneously.
Number of input
points
Rated input voltage Supplied from
Rated input current 7 mA (at 24 Vdc)7 mA (at 100 Vac)
ON levelContact close
OFF levelContact open
ON delay time0 to 15 ms
OFF delay time0 to 15 ms
Input signal display LED display for all points, lit at ON, internal logic side
External connection Terminal block (fixed), M3.5
Withstand voltage1500 Vac, 1 minute (between internal and external circuits)
Internal circuit
25 ms or less + user setting
30 ms or less + user setting
LED
0
0
6F3B0250
LED
7
13
-
+
7
C
24 Vdc
(AC power type only)
*1: The input current direction (source or sink) of the dry contact input can be selected by the
internal jumper plug. (Factory setting = current source) Refer to section 3.1.
3 side: current flows from input terminal to (-) terminal (current source)
1 side: current flows from (+) terminal to input terminal (current sink)
*2: The jumper plug of the DC power supply type must be set to 1 side.
*3: The input ON/OFF delay time of the DC input type can be changed by user. The setting range is
0 to 15 ms. (Default value = 10 ms) Refer to section 8.2.
*4: The input ON/OFF delay time of the AC input can be extended by user. The extension setting
range is 0 to 15 ms. (Default value = 10 ms) Resulting the default delay times are 35 ms (ON
delay) and 40 ms (OFF delay). Refer to section 8.2.
Output typeRelay contact,
Number of output points 6 points
Rated load voltage240 Vac/24 Vdc (max.) 24 Vdc100 - 240 Vac
Range of load voltageMax. 264 Vac/125Vdc 20.0 - 28.0 V24 - 264 Vac
Maximum load current2 A/point (resistive),
ON resistance
Voltage drop at ON
Leakage current at OFF None0.1 mA or less1 mA or less
Minimum load5 Vdc, 10 mA
ON delay time10 ms or less0.1 ms or less1 ms or less
OFF delay time10 ms or less0.1 ms or less1 ms + 1/2 cycle or
Input signal displayLED display for all points, lit at ON, internal logic side
Min. ON voltage15 Vdc80 Vac
Max. OFF voltage5 Vdc30 Vac
ON delay time0 to 15 ms (X00 - X07)
OFF delay time0 to 15 ms (X00 - X07)
Input signal displayLED display for all points, lit at ON, internal logic side
External connectionRemovable terminal block, M3.5
Withstand voltage1500 Vac, 1 minute (between internal and external circuits)
Internal circuit
ItemSpecifications
DC input typeAC input type
AC input
current source/sink
50/60 Hz
*1
10 ms or less (X08 - X0D)
*1
10 ms (X08 - X0D)
LED
25 ms or less + user settin
(X00 - X07)
25 ms or less (X08 - X0D)
30 ms or less + user settin
(X00 - X07)
30 ms or less (X08 - X0D)
6F3B0250
*2
*2
LED
0
D
C
*1: The input ON/OFF delay time of the leading 8 points of the DC input can be changed by user.
The setting range is 0 to 15 ms. (Default value = 10 ms) Refer to section 8.2.
*2: The input ON/OFF delay time of the leading 8 points of the AC input can be extended by user.
The extension setting range is 0 to 15 ms. (Default value = 10 ms) Resulting the default delay
times of these points are 35 ms (ON delay) and 40 ms (OFF delay). Refer to section 8.2.
Output typeRelay contact,
Number of output points 12 points
Rated load voltage240 Vac/24 Vdc (max.) 24 Vdc100 - 240 Vac
Range of load voltageMax. 264 Vac/125Vdc 20.0 - 28.0 V24 - 264 Vac
Maximum load current2 A/point (resistive),
ON resistance
Voltage drop at ON
Leakage current at OFF None0.1 mA or less1 mA or less
Minimum load5 Vdc, 10 mA
ON delay time10 ms or less0.1 ms or less1 ms or less
OFF delay time10 ms or less0.1 ms or less1 ms + 1/2 cycle or
Output signal displayLED display for all points, lit at ON, internal logic side
Min. ON voltage15 Vdc80 Vac
Max. OFF voltage5 Vdc30 Vac
ON delay time0 to 15 ms (X00 - X07)
OFF delay time0 to 15 ms (X00 - X07)
Input signal displayLED display for all points, lit at ON, internal logic side
External connectionRemovable terminal block, M3.5
Withstand voltage1500 Vac, 1 minute (between internal and external circuits)
Internal circuit
ItemSpecifications
DC input typeAC input type
AC input
current source/sink
50/60 Hz
*1
10 ms (X08 - X17)
*1
10 ms (X08 - X17)
LED
25 ms or less + user settin
(X00 - X07)
25 ms or less (X08 - X17)
30 ms or less + user settin
(X00 - X07)
30 ms or less (X08 - X17)
6F3B0250
*2
*2
LED
0
17
C
*1: The input ON/OFF delay time of the leading 8 points of the DC input can be changed by user.
The setting range is 0 to 15 ms. (Default value = 10 ms) Refer to section 8.2.
*2: The input ON/OFF delay time of the leading 8 points of the AC input can be extended by user.
The extension setting range is 0 to 15 ms. (Default value = 10 ms) Resulting the default delay
times of these points are 35 ms (ON delay) and 40 ms (OFF delay). Refer to section 8.2.
Output typeRelay contact,
Number of output points 14 points
Rated load voltage240 Vac/24 Vdc (max.) 24 Vdc100 - 240 Vac
Range of load voltageMax. 264 Vac/125Vdc 20.0 - 28.0 V24 - 264 Vac
Maximum load current2 A/point (resistive),
ON resistance
Voltage drop at ON
Leakage current at OFF None0.1 mA or less1 mA or less
Minimum load5 Vdc, 10 mA
ON delay time10 ms or less0.1 ms or less1 ms or less
OFF delay time10 ms or less0.1 ms or less1 ms + 1/2 cycle or
Input signal displayLED display for all points, lit at ON, internal logic side
(1) Current sour ce / sink selection on the T1-16 dry contact input
The input current flow direction (sour ce or sink) of the T1-16 dr y contact input can be
selected by setting the jumper plug on t he T1-16 printed circuit board as shown below.
The factory setting is current source. Refer to sect ion 2. 4. 1 for specifications and signal
connections.
The tool for opening the
cover is attached on the
back of the T1-16.
Remove the tool from the
unit.
Configure emergency stop and safety interlocking circuits out side t he
T1/T1S. Otherwise, malfunction of the T1/T 1S can cause injury or serious
accidents.
!
CAUTION
(1) T ur n off power before
opening the cover.
(2) T ake care not to touch
any electrical parts on
the board. Static
electricity can cause
damage.
(3) Use a pair of tweezers
to change the jumper
plug setting.
Put the tool on the side of
the unit so that the marks
The following conditions guarantee corr ect reading of the ON/O FF state of the input
signal:
Input ON time: ON delay time + the time for one scan
Input OFF time: OFF delay time + the tim e for one scan
The ON and OFF times of the input signals must be longer than these inter vals.
(3) Increasing t he contact current
The reliability of some contacts cannot be guaranteed by the specified input current. In
this case, install an external bleeder resistor to incr ease t he contact current.
Bleeder resistor
V
R
I
V
R
I
1
T1
input
I
2
circuit
=
II
-
Wattage
1
2
V
>´
3
R
6F3B0250
Note) The above solution cannot be applied to the T1-16 dr y contact input .
(4) Connecting tr ansistor output device
An example of connecting a transistor out put device to T1/T1S’s input circuit is shown
below.
For NPN open collector
·
n
n
T1
input
V
circuit
C
V
T1-16 dry contact inputT1-28, T1-40 and T1-40S DC input
(current source)
For PNP open collector
·
+
V
C
T1
input
n
n
circuit
V
T1
input
circuit
T1
input
circuit
T1-16 dry contact inputT1-28, T1-40 and T1-40S DC input
When a switch with an LED or an AC output sensor is used, the input sometimes cannot
recognize that the switch is off due t o t he current leakage. In t his case, install a bleeder
resistor to reduce input impedance.
LED
Bleeder resistor
6F3B0250
Bleeder resistor
R
V
DC input typeAC input type
Select a bleeder resistor according to t he following criteria:
(a) T he voltag e between the input terminals must be lower than the OFF voltage
when the sensor is switched off.
(b) T he cur r ent must be within the allowable range when the sensor is switched on.
(c) Calculate the wattage of the bleeder r esist or by mult iplying the current when the
sensor is switched on times three.
Note) The above solution cannot be applied to the T1-16 dr y contact input .
(6) Countermeasur es against induced current
With ac input signals, if the external cable is long or if a multi-core cable is used, an
induced current can flow from the char ged wire to the open wire, in proportion to the
capacities of the cables. In this case, sometimes the voltage reaches the level of the ON
input even though the contact is open, causing t he input to malfunction for no apparent
reason.
The usual practice when this happens is to reduce input impedance. Install a resistor or a
resistor and capacitor between the input and common terminals, or use shielded cables.
Such precautions are necessary when dealing with a large number of ac input signals.
Configure emergency stop and safety interlocking circuits outside the T1/T1S.
Otherwise, malfunction of t he T1/T1S can cause injury or serious accidents
1. Turn on power to the T1/T1S befor e t ur ning on power to the loads. Failure
to do so may cause unexpected behavior of the loads.
2. Configure the external circuit so that t he exter nal 24 Vdc power required
for the transistor output circuits and power to the loads are switched on/off
simultaneously. Also, turn off power to the loads before turning off power to
the T1/T1S.
3. Inst all fuses appropriate to the load current in the external circuits for the
outputs. Failure to do so can cause fire in case of load over-current.
(1) 2 points of solid- s t at e output
The leading 2 points of output (Y020 and Y021) are solid-state outputs, transistors on the
DC input types and triacs on the AC input types.
These solid-state outputs are suited for frequent switching applicat ions.
Note that the specifications of the solid-state outputs and other out puts (relays) are
different.
(2) Switching life of output relays
Expected relay life is more than 100,000 electrical cycles at rated maximum voltage and
current, and more than 20 million mechanical cycles. The expected contact life (electrical
cycles) is shown on the table below.
The output circuit of t he T1/T1S does not contain protective f uses. Fuses rated for the
output should be provided by the user.
6F3B0250
T1
output
circuit
Fuse appropriate to
the common current
(4) Output surge protection
Where an inductive load is connected t o t he output, a relatively high energy transient
voltage will be generated when the relay turns OFF. To prevent the problems caused by
this surge, install a surge absor ber in par allel t o the inductive load.
T1
output
circuit
Surge absorber:
Flywheel diode (for DC output)
·
Load
Load
PS
Load
PS
Surge absorber
Inverse withstand voltage: At least three times t hat of the power supply
Forward current: Larger than t he load cur rent
Varistor (for AC output)
·
The voltage rating is 1.2 times t he maximum (peak) voltage of t he power supply
CR snubber (for DC or AC output )
·
R: 0.5 to 1 W per volt coil voltage
C: 0.5 to 1 mF per ampere of coil current (non-polarity capacitor)
Do not install the T1/T1S in t he following locations:
·
·
·
·
·
·
·
·
Observe the following precautions when installing enclosures in which the T1/T1S will be
installed:
·
·
·
Excess temperature, humidity, vibration, shocks, or dusty and corrosive gas
environment can cause electrical shock, fir e or m alfunction.
Install and use the T1/T1S and relat ed equipment in the environment
described in this section.
Where the ambient temperature drops below 0 °C or exceeds 55 °C.
Where the relative humidity drops below 20 % or exceeds 90 %.
Where there is condensation due to sudden temperature chang es.
In locations subject to vibration that exceeds tolerance.
In locations subject to shock that exceeds toler ance.
Where there are corrosive or flammable gases.
In locations subject to dust, machining debr is or other particles.
In locations exposed to direct sunlight.
Provide the maximum possible distance from high-voltage or high-power panels. This
distance must be at least 200 mm.
If installing the enclosures in t he vicinity of high-frequency equipment , be sure to
correctly ground the enclosures.
When sharing the channel base with other panels, check for leakage current from the
other panels or equipment.
1. Improper installation directions or insufficient installation can cause fire
or the units to drop. Install the T1/T1S and relat ed equipment in
accordance with the instructions described in this section.
2. Turn off power before installing or removing any units, modules, rack s
or terminal blocks. Failure to do so can cause elect r ical shock or
damage to the T1/T1S and related equipment.
3. Enter ing wire scraps or ot her foreign debris into to the T1/T1S and
related equipment can cause fire or malfunction. Pay attention to prevent
entering them into the T 1 and r elat ed equipment during installation and
wiring.
NOTE
The T1/T1S basic unit and the expansion unit come equipped with a bracket at
the rear for mount ing on a 35 mm DIN rail. However, no DIN rail br acket is
provided on the expansion rack.
Because the T1/T1S is not dust-pr oof, install it in a dust-proof enclosure.
Do not install the unit directly above equipment that generates a large amount of heat,
such as a heater, transform er , or large-capacity resistor.
Do not install the unit within 200 mm of a high-voltage or high-power cables.
Allow at least 70 mm on all sides of the unit for ventilation.
For safely during maintenance and operation, install the unit as far as possible fr om
high-voltage or power equipment. Alternatively, keep the unit separate using a metal
plate or similar separator.
If a high-fr equency equipment is installed in the enclosure tog et her with the T1/T1S,
special attention is required f or grounding. See section 4.4.
Be sure to install the unit vertically with keeping the power term inals upside. Do not
install the unit horizontally or upside-down for safet y reason.
Use M4 size screws to mount the T1/T1S.
(Recommended torque: 1.47 N×m = 15 kgf×cm)
Upward
IN
PROSEC
TOSHIBA
T1
MDR40
OUT
Mount the T1 on a vertical panel.
All other mounting positions are not
acceptable.
The terminal arrangement of each T1 Series model are shown below.
The terminal screw size is M3.5. Use crimp-style terminals of 7 mm width or less useable
for M3.5.
The terminal blocks of the T1-16 are not removable (fixed). On the other hand, the
terminal blocks of the T1-28, T1-40 and T1-40S are removable. However, be sure to turn
off power before rem oving or r eplacing the terminal blocks.
NOTE
1. Turn off power before wiring to m inim ize the risk of electrical shock.
2. Exposed conductive parts of wire can cause electrical shock. Use
crimp-style terminals with insulating sheath or insulating t ape to cover
the conductive parts. Also close the terminal covers securely on the
terminal blocks when wiring has been completed.
3. Turn off power before rem oving or replacing units, modules, term inal
blocks or wires. Failure to do so can cause electrical shock or dam age
to the T1/T1S and related equipment.
For input and output signal connections, refer to sections 2.4 and 3.
T1-16
·
T1-MDR16 ... AC power supply, Dry contact input type
The applicable wire size is 0.3 mm2 (22 AWG) to 1.25 mm2 (16 AWG ) . The table below
shows the recommended wire size.
Type of signalRecommended wire size
Power1.25 mm2 (16 AWG )
Grounding1.25 mm2 (16 AWG )
I/O signals0.3 mm2 (22 AWG) to 0.75 mm2 (18 AWG )
4.4 Grounding
6F3B0250
!
CAUTION
The optimum method for grounding electronic equipment is to ground it separ at ely fr om
other high-power systems, and to ground m or e than one units of electronic equipment
with a single-point ground.
Although the T1/T1S has noise immunity to be used in industrial operating conditions,
grounding is important for safety and reliability.
Check the grounding against the following criteria.
1. The T1/T1S must not become a path for a ground current. A high-frequency current is
2. Equalize the ground potentials when the expansion rack or unit is connected. Ground
3. Do not connect t he ground of the T1/T1S to that of high- power systems.
4. Do not use a ground that has an unstable impedance, such as painted screws, or
1. Turn off power before wiring to m inim ize the risk of electrical shock.
2. Oper at ion without grounding may cause electrical shock or malfunction.
Connect the ground terminal on the T 1/T1S to the system ground.
particularly harmful.
the T1/T1S and the expansion rack or unit at a single point.
ground subject to vibration.
The grounding marked terminal (see below) is provided on the T1/T1S basic unit and the
expansion unit for grounding purpose.
Wire the power source t o t he T1/T1S power supply terminals.
Power source
Power conditions:
·
1. Turn off power before wiring to m inim ize the risk of electrical shock.
2. Applying excess power voltage to the T1/T1S can cause explosion or fire.
Apply power of the specified ratings described below.
Line filter
Insulation
transformer
T1
AC power supply typeDC power supply type
Rated voltage100 to 240 Vac, +10/-15 %24 Vdc, +20/-15 %
Frequency
Power consumption30 VA or less (T1-16/T1-28)
Retentive power
interruption
1.25 mm
·
The power cable should be separated from other cables.
·
2
(16 AWG) twisted-pair cable should be used for the power cable.
50/60 Hz, ±5 %
38 VA or less (T1-40)
45 VA or less (T1-40S)
Continuous operation for less than 10 ms
12 W or less (T1-16/T1-28)
18 W or less (T1-40)
18 W or less (T1-40S)
-
T1/T1S User’s Manual
78
Page 81
Connections of the power supply terminals are shown below.
1. Turn off power before wiring to m inim ize the risk of electrical shock.
2. Exposed conductive parts of wire can cause electrical shock. Use
crimp-style terminals with insulating sheath or insulating tape to cover the
conductive parts. Also close the terminal covers securely on the terminal
blocks when wiring has been completed.
3. Turn off power before rem oving or replacing units, modules, term inal
blocks or wires. Failure to do so can cause electrical shock or damage to
the T1/T1S and related equipment.
Refer to sections 2.4 and 3 for instructions on how to properly wire the I/O terminals.
0.75 mm
Separate the I/O signal cables from high-power cables by at least 200 mm.
If expansion rack or unit is used, separate the expansion cable from the power and I/O
signal cables by or unit at least 50 mm.
It is recommended to separate the input signal cables from output signal cables.
2
(18 AWG) to 0.3 mm2 (22 AWG) wires are recommended for I/O signals.
The T1/T1S has three basic operation modes, the RUN mode, the HALT m ode and t he
ERROR mode. The T1/T1S also has the HOLD and RUN-F modes mainly for system
checking.
6F3B0250
RUN:
HALT:
ERROR:
The RUN mode is a normal control-oper ation mode.
In this mode, the T1/T 1S reads external signals, executes the user program
stored in the RAM, and outputs signals to the external devices according to the
user program. It is in the RUN mode that the T1/T1S performs scans the user
program logic, which is the basic operation of a PLC.
In case of the T1S, program changes and EEPROM write are possible while
the T1S is in the RUN mode. Ref er to section 6.9.
On the other hand, in case of the standard T1, program changes and
EEPROM write are not possible in the RUN mode.
The HALT mode is a programm ing mode.
In this mode, user program execution is st opped and all out puts are switched
off.
Program loading into t he T1/T1S is possible only in the HALT mode.
For the standard T1, prog r am changes and EEPROM write are possible only
when the T1 is in the HALT mode.
The ERROR mode is a shut-down mode as a result of self-diagnosis.
The T1/T1S enters the ERROR mode if internal t r ouble is det ected by selfdiagnosis. In this mode, prog r am execution is st opped and all outputs are
switched off. The cause of the shut-down can be confirmed by connecting the
programming tool.
To exit from the ERRO R m ode, execute t he Error Reset command from the
programming tool, or cycle power off and then on again.
HOLD:
RUN-F:
T1/T1S User’s Manual
82
The HOLD mode is provided mainly for checking the external I/O signals.
In this mode, user program execution is st opped, with input and out put
updating is executed. It is therefore possible to suspend program execution
while holding the output state. Moreover, a desired output state can be
established by setting any data by using the programm ing tool.
The RUN-F mode is a forced RUN m ode pr ovided for program check ing.
This mode is effective when using the expansion I/Os.
Deferent from the normal RUN mode, the RUN-F mode allows operation even
if the registered option cards, expansion unit and/or I/O modules are not
actually mounted.
The operation modes are switched by the mode control switch provided on the T1/ T1S
and the mode control commands issued fr om t he pr ogramming tool.
The mode transition conditions are shown below.
(Power ON)
’
HOLD
RUN
‘
Œ
Ž
•
Ž
•
HALT
•
’
Œ
•
Ž
•
•
‘
’
“
‘
RUN-F
ERROR
Mode control switch is in R (RUN) side.
Mode control switch is in H (HALT) side.
Mode control switch is turned to H (HALT) side, or HALT command is issued from
the programming tool.
Mode control switch is turned to R (RUN) side, or RUN comm and is issued from
the programming tool.
Force RUN (RUN-F) command is issued from the programm ing tool.
HOLD command is issued from the pr ogramming tool.
HOLD Cancel command is issued from the pr ogramming tool.
Error Reset command is issued from the programming t ool.
(dotted line) Error is detected by self-diagnosis.
Ž
“
NOTE
The commands from the pr ogramming tool are available when the mode
control switch is in R (RUN) side.
The T1/T1S is equipped with a built-in EEPROM and a RAM as standard feat ur es.
The user program is stored in the EEPROM so that the user program can be maintained
without the need of a battery. A part of the Data register can also be stor ed in t he
EEPROM.
The table below shows the contents stored in the built-in EEPROM.
User programEntire program (2 k steps) and
System information
User dataLeading 512 words of Data
register (fixed).
D0000 - D0511
Other data
T1T1S
Entire program (8 k steps) and
System information
User specified number of Data
register starting with address
0. It is set by SW55.
D0000 - Dnnnn
(up to 2048 words)
-
SW36 - SW38:
Programmer port settings
SW55:
Number of Data register to
be saved in the EEPROM
SW56 - SW57:
RS-485 port settings
6F3B0250
The user program and the data stored in the EEPROM is transferred to the RAM when
power is turned on. Subsequent program execution is done based on the RAM contents.
Program editing is also performed on the RAM contents.
Therefore, if the program is modified, i t i s necessary t o i ssue t he EEPRO M Wri t e
command from the programming tool. Otherwise, the modified program is overwritten by original EEPROM contents when the power is turned off and on agai n.
In case of the T1S, Special register SW55 is used to specify the number of Data registers
to be stored in the EEPROM. The allowable setting value is 0 to 2048.
The table below shows the correspondence between the SW55 value and Data registers
saved in the EEPROM.
6F3B0250
SW55 sett ing
value
0None
1D0000 only
2D0000 to D0001
3D0000 to D0002
::
2047D0000 t o D2046
2048D0000 t o D2027Default value
OthersD0000 to D2027Regarded as 2048
When the EEPROM Write command is executed, the T1S checks the value of SW55 and
saves the Data registers into the EEPROM depending on the SW55 value. The value of
SW55 itself is also saved in the EEPROM.
At the initial load or the EEPROM Read command is executed, the T1S checks the value
for SW55 in the EEPROM and transfers the corr esponding number of data to the Dat a
registers of the RAM.
NOTE
(1) T he EEPROM has the life limit for writing. It is 100,000 times. Pay
(2) I n t he T1S, if the EEPROM Write command is executed in RUN mode,
(3) T he dat a in the EEPROM (D0000 to D0511 or D0000 to D2047) can also
(4) T he SW55 sett ing is available only for the T1S.
Range of Data register s saved in
EEPROM
attention not to exceed the limit. If the number of execution of EEPROM
Write command exceeds 100,000 times, EEPROM alarm flag (S007)
comes ON.
only the user program is written into the EEPROM.
be read or written by using the program inst ruction (FUN236 XFER
The flowchart below shows the basic internal operations perform ed by the T1/T1S from
the time power is turned on through prog r am execution. As the diagram shows,
executing a program consists of continuous scanning operations. One scan is a cycle
starting with the self-diagnosis and ending with the completion of peripheral support.
Performs checking and init ialization of the system ROM, the system RAM and the
peripheral LSIs.
Initial load:
Transfers the user pr ogram and user data from the EEPROM to the RAM. (Refer to
section 5.2)
Register/device initialization:
Initializes registers and devices as shown below.
Register/deviceInitialization
External input (X/XW)Forced inputs are ret ained. Others are cleared to 0.
External output (Y/YW)Forced coil devices are retained. Others are cleared to 0.
Auxiliary device/register
(R/RW)
Special device/register
(S/SW)
Timer device/register
(T./T)
Counter device/register
(C./C)
Data register (D)User specified retentive registers ar e r etained. Others are
Index register (I, J, K)Cleared to 0.
6F3B0250
User specified retentive register s and forced coil devices
are retained. Others are cleared t o 0.
Special setting data are retained. O t her s are cleared to 0.
User specified retentive register s ar e r et ained. Others are
cleared to 0.
User specified retentive register s ar e r et ained. Others are
cleared to 0.
cleared to 0.
NOTE
(1) When the data stor ed in t he EEPRO M (Data registers) are used, these
registers should be specified as retent ive. O therwise, these data are
transferred fr om EEPROM to RAM, but then cleared to 0 at the
initialization.
(2) T he dat a in t he retentive registers are stored in RAM and backed up by
built-in capacitor. The back-up period is 6 hours or more at 25 °C (T1), or
168 hours or more at 25 °C (T1S).
The T1/T1S checks t he validity of t he retentive data at the power-up
initialization, and if they are not valid, sets the special device (S00F) to ON.
Therefore, it is recommended to check the status of S00F in the user
program and to initialize the retentive registers if S00F is O N.
(3) T he r et entive registers can be set by the programm ing tool for RW, T, C
and D registers. The reg ist er s from address 0 to the designat ed addr ess
for each type are set as retentive reg ist er s. Refer to the separate manual
for the programm ing tool for setting t he retentive registers.
(4) T he input force and the forced coil are functions for progr am debugging.
Checks the proper operation of the T1/T1S itself. If an error has detected and cannot be
recovered by re-tries, the T1/ T1S moves into ERROR mode. For the self-diagnosis
items, refer to sect ion 10. 2.
Mode control:
Checks the mode control switch status and the m ode cont r ol r equest commands from
the programming tool.
The scan mode - floating scan or fixed-time scan - is also controlled hear.
NOTE
The floating scan:
When one scan is finished, immediately starts the next scan. The scan time is
shortest, but may vary depending on the program execution status.
Scan timeScan timeScan time
The fixed-time scan:
The scan operation is started every user-specified time. The time setting range
is 10 to 200 ms (10 ms units). If an actual scan needs longer time than t he
setting time, it works as the floating scan.
Scan time (50 ms fixed)Scan time (50 ms fixed)
(idling)(idling)
Program check:
At the beginning of the RUN mode, the user progra m is com p iled and it s validity is
checked.
I/O update:
Reads the external input signals into the external input devices/registers (X/XW), and
sends the data of the external output devices/registers (Y/YW) to the external output
circuits. Then the outputs ( r elays, etc. ) changes the states and latches until the next I/O
update timing.
The states of the forced input devices are not updated by this operation.
Timer update:
Updates the timer registers which are activated in the user pr ogram, and the timing
devices (S040 to S047).
Executes the programmed instructions from the beginning t o t he END instruction.
This is the essential function of t he T1/T1S.
In this section, only the main program execution is mentioned. For other program types,
such as timer interrupt, etc., refer to section 6.5.
Peripheral support:
Supports the communications with the program m ing tool or an external devices
connected by the computer link funct ion. The time for this operat ion is lim it ed within
approx. 2 ms in the floating scan mode, and within allowable idling time in the fixed-time
scan mode.
In case of the T1S, if the special relay S158 is set to ON, the peripheral support priority
mode is selected. In the peripheral support pr iority mode, the peripheral support time is
not limited. As the result, t he com m unicat ion r esponse is im pr oved although the scan
time becomes long at the time.
The T1/T1S program consists of bit-based instructions that handle ON/OFF information,
such as contact and coil instructions, and regist er - based ( 16-bit) instructions, such as
those for data transfer and arithmetic operations.
Devices are used to store the ON/OFF infor m at ion of contacts and coils, and register s
are used to store 16-bit data.
Devices are divided into six types:
XExternal input devices
YExternal out put devices
RAuxiliary relay devices
SSpecial devices
T.Timer devices
C.Counter devices
6F3B0250
Registers are divided into eight types:
XWExternal input registers
YWExternal output registers
RWAuxiliary relay registers
SWSpecial registers
TTimer registers
CCounter r egisters
DData r egisters
I, J, K Index registers
Device and register numbers
X devices share the same memory area as XW registers. Device X014, for example,
represents the number 4 bit in the X W01 regist er .
Bit position / Number
(MSB)(LSB)
FEDCBA9876543210
XW011
X014
Thus, "X014 is ON" means that bit number 4 of XW01 is 1.
Y, R, and S devices work in a similar manner.
(1) 1 word = 16 bits
(2) T he available data range in each register is -32768 to 32767 (H8000 to
H7FFF) except for the timer and the count er registers.
The data range of the timer register is 0 to 32767. T hat of the counter
register is 0 to 65535.
(3) Double-word (32 bits) data is available in two consecutive registers.
In this case, lower address register stores the lower 16 bits data.
(MSB) F 0 F0 (LSB)
D0100D0101
UpperLower
16 bits16 bits
In this manual, a double-word register is expressed by using ‘×’.
For example, D0101×D0100.
These devices (X) indicate the ON/OFF states of external input signals through the input
circuits. External input devices can be used many times in a program .
External output devices (Y)
The external output devices (Y) store the ON/OFF signals that drive the external devices
through the output circuits . They can be used for coils in a program.
External input registers (XW)
These (XW) are 16-bit register s for storing values which are received from the input
circuits.
External output registers (YW)
These 16-bit registers (YW) are used for storing values which are sent to the output
circuits.
Auxiliary relay devices and registers (R/RW)
The auxiliary relay devices (R) are used to store intermediate results of sequences. The
auxiliary relay registers (RW) are used to store temporary results of function instructions.
The data in R/RW cannot be output directly to the output circuits. It is necessary to move
the data to Y/YW.
It is possible to make these reg ist er s r etentive so that they retain data in the event of a
power failure. See section 5.3.
Timer devices and registers (T./T)
The timer registers (T) are used for storing the elapsed time of timer inst r uctions, the
on-delay (TON), off-delay (TOF) and single- s hot ( SS) timers.
0.01 s base timers and 0.1 s base timers are pr ovided.
Time baseT1T 1S
0.01 sT000 to T031T000 to T063
0.1 sT032 to T063T064 to T255
The timer devices (T.) works as the output of the timer instr uctions.
It is possible to specify the T reg ist er s as r etentive to retain their data in the event of a
power failure. See section 5.3.
The counter registers (C) are used for storing the count value of the counter (CNT) and
the up-down counter (U/D) instructions.
The counter devices (C.) works as the output of the counter instructions.
It is possible to specify the C register s as r etentive to retain their data in the event of a
power failure. See section 5.3.
Data registers (D)
Functionally the data registers (D) are the same as auxiliary relay registers (RW) except
that the D registers cannot be used as devices.
A part of the data reg isters are saved in the built-in EEPROM as fixed data and
transferred into t he RAM at the initial load. See section 5.2.
Range of the data regist er s saved in the EEPRO M:
T1T1S
D0000 to D0511User specified range
6F3B0250
starting with D0000
(up to 2048 words)
It is possible to specify the D register s as r etentive to retain their data in the event of a
power failure. See section 5.3.
Index registers (I, J, and K)
These index registers are used for indir ect addressing for a reg ister.
For example, if the value of I is 100 in the following register expression, it designat es
D0100. For details, refer t o sect ion 6.2.
The special devices (S) and special registers (SW) are used for special pur poses. See
list below.
Device/
ister
re
S0000: Initialization4: HOLD mode
S001T1/T1S operation mode1: HALT mode6: ERROR mode
S0022: RUN mode
S0033: RUN-F mode
S004CPU error (down)ON at error state (related to SW01)
S005I/O error (down)ON at error state (related to SW02)
S006Program error (down)ON at error state (related to SW03)
S007EEPROM alarm (alarm)ON when EEPROM write exceeds 100,000 times
S008Fixed-time scan time-over
(alarm)
S009
S00AClock/calendar error
(alarm)
S00B
S00C
S00DTL-F10 error (alarm)ON when TOSLINE-F10 transmission error occurs
S00E
S00FRetentive data invalid
(alarm)
NOTE
(1) These devices are set by the T1/T1S operating system. These devices are
NameFunction
ON when actual scan time is longer than the setting time
as fixed-time scan
-
-
-
-
Reserved
ON when clock/calendar data is illegal (T1S only)
Reserved
Reserved
Reserved
ON when retentive data in RAM are invalid
read only for user.
(2) Devices mark ed as (down) are set in the ERROR mode. Therefore these
devices cannot be used in the user program.
(3) Devices marked as (alarm) are set in the normal operation mode. These