Toshiba 1700 Series UPS
Option Module Connection Guide
IMPORTANT SAFETY INSTRUCTIONS
SAVE THESE INSTRUCTIONS. This sheet contains important instructions for Toshiba 1700 Series Transformer Modules.
These instructions should be followed during the installation of the transformer module.
The ambient temperature range in which this unit should be operated or stored is 32°F to 104 °F (0°C to 40 °C).
This module should not be opened under any circumstances. There are no user servicable parts inside. For service
contact your local Toshiba representative, or contact the Toshiba UPS marketing department toll-free at (800) 231-
1412.
When adding transformer modules, be sure to use the proper model unit.
CAUTION
Inspection/Installation
After Unpacking:
1) Check the unit for loose, broken, bent or otherwise damaged parts. If damage has occurred during shipment, keep all
original packing materials for return to shipping agent. Warranty will not apply to units damaged during shipment.
2) Check to see that the rated capacity and the model number specified on the nameplate conform to the order
specifications.
Installation Precautions
This transformer module is intended for use with a Toshiba 1700 Series UPS. Any electrical or mechanical
modifications to this equipment, without prior written consent of Toshiba International Corporation will void all
warranties and may void UL/CUL listing. Unauthorized modifications also can result in personal injury, death, or
destruction of the equipment. When installing this transformer module follow all installation instructions and precautions
as listed in the 1700 Series user manual.
Module Layout
Misuse of this equipment could result in human injury and equipment damage. In no event will
Toshiba Corporation be responsible or liable for either indirect or consequential damage or injury that
may result from the use of this equipment.
Specifications
Model Number
Capacity
Input voltage
Input
frequency
Input
Input capacity
Input power
factor
Output
voltage
024-6AA 024-6EE
2400VA
(1.68kW)
Single phase
120VAC
2400VA 2400VA
Approximately unity (0.95 to 1.0)
Single phase
120VAC
UF1-IO-
2400VA
(1.68kW)
Single phase
230VAC
45 to 65 Hz
Single phase
230VAC
Output
voltage
Within +/- 3%, steady state
regulation
Figure 1
Output
frequency
Output
Rated load
power factor
Rated output
current (rms)
50/60 Hz (+/- 0.5% in free running
mode, line sync range +/-1%)
0.7
20A 10A
55611-001
UPS Connections
Standard Unit with 120V Isolation Module
Figure 2 shows the standard unit, consisting of one
electronics module and one battery module, with the
addition of the 120V isolation transformer module.
Standard Unit with 230V IO Module
Figure 3 shows the standard unit, consisting of one
electronics module and one battery module, with the
addition on the 230V transformer module.
Figure 2 : 120V Isolation Transformer Module Configuration Figure 3: 230V Transformer Module Configuration
The modules do not have to be stacked for the unit to
operate; however, if the modules are to be stacked
please refer to the 1700 Series user manual for
instructions on interlocking modules.
To connect the modules electrically follow these steps:
1. The power cord from the electronics module must be
plugged into the output receptacle on the back of the
option module (see figure 1).
2. The input power cord from the option module must
be plugged into a power source (see figure 1).
The battery power cord must also be plugged into the
electronics module for the system to provide backup
power (refer to the 1700 Series user manual or the
battery module installation instructions for instructions on
connecting the battery module).
Note: No more than three modules should be stacked
in any configuration. If the option module is being used
with a system that has an expansion battery module at
least one module must be placed beside the others.
Stacking four modules could result in a tipping hazard.
The modules do not have to be stacked for the unit to
operate; however, if the modules are to be stacked
please refer to the 1700 Series user manual for
instructions on interlocking modules.
To connect the modules electrically follow these steps:
1. Plug the output power cord from the transformer
module into one of the output receptacles on the
back of the electronics module (in the case of the
2.4kVA model the cord can only be plugged into the
20A outlet, see figure 1).
2. Next, plug the power cord from the electronics
module into the output receptacle on the back of the
transformer module (see figure 1).
3. The input power cord from the transformer module
must be plugged into a power source (see figure 1).
The battery power cord must also be plugged into the
electronics module for the system to provide backup
power (refer to the 1700 Series user manual or the
battery module installation instructions for instructions on
connecting the battery module). The unused
receptacles on the back of the electronics module are
still active, but they are providing 120V power, not 230V.
All 230V power must be drawn from the output
receptacles on the back of the option module.