Read this manual and follow its intructions. Signal words such as DANGER, WARNING
and CAUTION will be followed by important safety information that must be carefully reviewed.
Indicates a situation which will result in death, serious injury , and severe property damage if you
do not follow instructions.
Means that you might be seriously injured or killed if you do not follow instructions. Severe
property damage might also occur.
Means that you might be injured if you do not follow instructions. Equipment damage might
also occur.
NOTE
Give you helpful information.
Note: The contents of this manual will not become apart of or modify the warranty
policy , the terms of which are set forth at the end of this manual.
READ SAFETY SIGNS
T o avoid injury , you must read and follow all safety signs.
Keep the safety signs visible and in good shape. Never remove or cover any safety sign.
QUALIFIED OPERATORS ONLY
Only qualified persons are to install, operate, or service this equipment according to all applicable
codes and established safety practices.
A qualified person must:
1)Carefully read the entire instruction manual.
2)Be skilled in the installation, construction or operation of the equipment and aware of
the hazards involved.
3)Be trained and authorized to safely energize, de-energize, clear, ground, lockout and
tag circuits in accordance with established safety practices.
4)Be trained and authorized to perform the service, maintenance or repair of this equipment.
5)Be trained in the proper care and use of protective equipment such as rubber gloves,
hard hat, safety glasses, face shield, flash clothing, etc. in accordance with established practices.
6)Be trained in rendering first aid.
SAFETY
WARNING
SAFETY CODES
T oshiba motor control is designed and built in accordance with the latest applicable provisions of
NEMA and the National Electrical Code. Installations must comply with all applicable state and local
codes, adhere to all applicable National Electric Code (NFP A 70) st andards and instructions provided
in this manual.
HAZARDOUS VOL TAGE will cause severe injury , death, fire, explosion and
property damage.
• Turn off and lock out Primary and Control Circuit Power before servicing.
•Keep all panels and covers securely in place.
•Never Defeat, Modify , or Bypass any Safety Interlocks.
• Qualified Operators only.
Never attempt to install, operate, maintain or dispose of this equipment until
you have first read and understood all of the relevant product warnings and
user directions that are contained in this Instruction Manual.
Use only T oshiba-authorized replacement parts.
This equipment is designed and built in accordance with applicable safety
standards in effect on the date of manufacture. Unauthorized modifications
can result in voiding the warranty, severe injury, death and property
damage. Do not make any modifications to this equipment without
the written approval of Toshiba.
For assistance, address correspondence to:
T oshiba International Corporation
Field Service Department
13131 West Little York Road
Houston, T exas 77041 USA
or call:(713) 466-0277Fax:(713) 466-8773
(800) 231-1412
(800) 527-1204 (Canada)
Please complete the following information for your records and retain with this manual:
Model:___________________________________
Serial Number:_____________________________
Date of Installation:_________________________
Inspected by:______________________________
Reference Number:_________________________
Full horsepower rated contactor included as standard in all Type 12, 3R, 4 & 4X
Chapter 1 - Introduction
This chapter is a brief introduction to the TX Series soft starter and describes
product operation and unit features.
1.1 - General
The TX Series is a high-end digitally programmable solid state reduced voltage soft
starter. This heavy duty starter provides reduced voltage, stepless soft starting of
3-phase AC induction motors, protecting mechanical components from excessive
torque stress and electrical systems from the effects of high motor inrush currents.
The TX Series includes advanced motor and load protection features just like those
found in expensive motor protection relays. These include retentive thermal
memory, dynamic reset capacity, true thermal modeling, separate trip curves for
start and run protection, overload alarm, etc. In the case of the TX Series, these
features are built in as standard features, providing a cost effective and reliable
motor starting and protection scheme for your critical motor applications.
The TX Series features an easy to use interface operator for programming and
status indication. It includes a large tactile feedback keypad, LED status indicators and a 2 line x 20 character backlit display using plain English text readout. In
addition to programming the standard parameters such as starting torque, ramp
time, current limit, dual ramp and decel control, other features like programmable
overload trip curves (NEMA/UL Classes 5 - 30), starts-per-hour, time between
starts and coast down/back spin lockout protection can also be programmed for
your specific application needs.
1.2 Specifications
Type of Load
AC Supply Voltage
HP Ratings
Unit Overload Capacity
(Percent of motor FLA)
Power Circuit
SCR Diode Ratings
(Peak Inverse Voltage)
Phase Insensitivity
Transient Voltage Protection
Cooling
Bypass Contactor
Ambient Condition Design
Three phase AC induction motors or synchronous motors
208 - 600 VAC +
39 - 1250 Amps, 10 - 1125 HP
6 SCRs
1600V
Unit operates with any phase sequence
RC snubber dv/dt networks on each phase
Convection up to 180A, fan assisted 78 - 120A
Fan ventilated 220 - 1250A
enclosed units 120A and above.
Chassis units: 0° to 50 °C (32° to 122°F)
Enclosed units: 0° to 40°C (32° to 104°F)
5 - 95% relative humidity
0 - 3300 ft. (1000m) above sea level without derating
10%, 50/60 Hz
Control
Auxiliary Contacts
Approvals
2 or 3 wire 120VAC (customer supplied)
Optional 240VAC control voltage and CPTs are available
Type/Rating: FORM C (SPDT), rated 5 Amps, 240VAC max. (1200VA)
4 Programmable Relays
UL Listed, Canadian UL (cUL)
TOSHIBA- 1
TX Series 48 - 1250A
for a successful restart. Starter learns and retains this information by monitoring
1.2 Specifications (continued)
Advanced Motor Protection
Two Stage Electronic
Overload Curves
Overload Reset
Retentive Th ermal Memory
Dynamic Reset Capacity
Phase Current Imbalance
Protection
Over Current Protection
(Electronic Shear Pin)
Load Loss Trip Protection
Coast Down (Back Spin)
Lockout Timer
Starts-per-hour Lockout Timer
Starting: programmable for Class 5 - 30 or locked rotor time.
Run: Programmable for Class 5 - 30 when "At-Speed" is detected.
Manual (default) or automatic
Overload circuit retains thermal condition of the motor regardless of control
power status. Unit uses real time clock to adjust for off time.
Overload will not reset until thermal capacity available in the motor is enough
previous successful starts.
Imbalance Trip Level: 5 - 30% current between any two phases
Imbalance Trip Delay: 1 -20 seconds
Trip Level: 100 - 300% of motor FLA while running not starting or OFF
Trip Delay: 1 - 20 seconds
Under Current Trip Level: 10 -90 % of motor FLA or OFF
Under Current Trip Delay: 1 - 60 seconds
Coast Down Time Range: 1 - 60 minutes or OFF
Range: 1 - 6 successful starts per hour
Time between starts: 1 - 60 minutes between start attempts
Programmable Outputs
Type / Rating
Run Indication
At Speed Indication
Acceleration Adjustments
Dual Ramp Settings
Deceleration Adjustments
Jog Settings
(Function selected via
programming input)
Kick Start Settings
Fault Display
Lockout Display
Form C (DPDT), Rated 5 amps 240 VAC max, (1200 VA)
Start/Stop or Start/End of Decel
At Speed/Stop or At Speed/End of Decel
Programmable Ramp Types: Voltage or Current Ramp (VR or CR)
Starting Torque: 0 - 100% of line voltage (VR) or 0 - 600% of motor FLA (CR)
Ramp Time: 1 to 120 seconds
Current Limit: 200 - 600% (VR or CR)
Begin Decel Level: 0 - 100% of line voltage
Stop Level: 0 to 1% less than Begin Decel Level
Decel Time: 1 - 60 seconds
Programmable to decel or coast to stop upon overload trip
Voltage Jog: 5 - 100% or OFF
Time of Voltage Jog: 1 - 20 seconds
Current Jog: 100 - 500%
Kick Voltage: 10 - 100% or OFF
Kick Time: 0.1 - 2 seconds
Shorted SCR, Phase Loss, Shunt Trip, Phase Imbalance Trip, Overload,
Overtemp, Overcurrent, Short Circuit, Load Loss, Undervoltage or Any Trip
Coast Down Time, Starts Per Hour, Time Between Starts, and Any Lockout
TOSHIBA - 2
TX Series 48 - 1250A
1.2 Specifications (continued)
Event History
Up to 60 Events
Motor Load
Current Data
Thermal Data
Start Data
RTD Data
Voltage Metering
Protocol
Signal
Network
Functionality
LCD Readout
Keypad
Status Indicators
Remote Mount Capability
Data includes cause of event, time, date, and current for each phase and
ground fault current at time of event
Metering Functions
Percent of FLA
A, B, C Phase Current, Avg Current, Ground Fault
Remaining thermal register; thermal capacity to start
Avg Start Time, Avg Start Current, Measured Capacity to start, time since last
start
Temperature readings from up to 12 RTDs (6 stators)
KW, KVAR, PF, KWH
Serial Communications
Modbus RTU
RS-485 or RS-422
Up to 247 devices per mode
Full operation, status view, and programming via communications port
Operator Interface
Alpha numeric LCD display
8 function keys with tactile feedback
8 LEDs include Power, Run, Alarm, Trip, Aux Relays
Up to 1000 feet from chassis (use twisted, shielded wire)
Clock and Memory
Operating Memory
Factory Default Sto rage
Customer Settings and Status
Real Time Clock
DRAM loaded from EPROM and EEPROM at initialization
Flash EPROM, field replaceable
Non-volatile EEPROM, no battery backup necessary
Lithium ion battery for clock memory only
TOSHIBA- 3
TX Series 48 - 1250A
1.3 - Theory of Operation
The power of the TX Series is in the CPU, a microprocessor based
protection and control system for the motor and starter assembly.
The CPU uses Phase Angle Firing of the SCRs to apply a reduced
voltage to the motor, and then slowly and gently increases torque
through control of the voltage and current until the motor accelerates
to full speed. This starting method lowers the starting current of the
motor, reducing electrical stresses on the power system and motor.
It also reduces peak starting torque stresses on both the motor and
load mechanical components, promoting longer service life and less
downtime.
Acceleration: The TX Series comes standard with several methods of
accelerating the motor so that it can be programmed to match almost
any industrial AC motor application.
The factory default setting applies a Voltage Ramp with Current Limit
as this has been proven the most reliable starting method for the vast
majority of applications. Using this starting method, the Initial Torque
setting applies just enough voltage to the motor to cause the motor shaft
to begin to turn. This voltage is then gradually increased over time (as
per the Ramp Time setting) until one of three things happen: the motor
accelerates to full speed, the Ramp Time expires or a Current Limit
setting is reached.
If the motor accelerates to full speed before the ramp time setting has
expired, an automatic Anti-Oscillation feature will override the remaining
ramp time and full voltage will be applied. This will prevent any surging
or pulsation in the motor torque, which might otherwise occur due to the
load not being fully coupled to the motor when operating at reduced
voltage and torque levels.
If the motor has not reached full speed at the end of the ramp time
setting, the current limit setting will proportionally control the maximum
output torque. Feedback sensors in the TX Series provide protection
from a stall condition, an overload condition or excessive acceleration
time.
The Current Limit feature is provided to accommodate installations
where there is limited power available (for example, on-site generator
power or utility lines with limited capacity). The torque is increased
until the motor current reaches the preset Current Limit point and it is
then held at that level. Current Limit overrides the ramp time setting
so if the motor has not accelerated to full speed under the Current
Limit setting, the current remains limited for as long as it takes the
motor to accelerate to full speed.
When the motor reaches full speed and the current drops to running
levels, the TX Series detects an At-Speed condition and will close the
Bypass Contactor (if provided). The Bypass Contactor serves to shunt
power around the SCR stack assemblies to prevent heat build-up
NEMA 12, 3R, 4 and 4X enclosed units due to the slight voltage drop
across the SCRs. At this point, the TX Series has the motor operat-
ing at full voltage, just as any other starter would.
TOSHIBA - 4
TX Series 48 - 1250A
Other starting methods available in the TX Series are:
· Current Ramp: uses a closed current feedback PID loop to provide a linear
torque increase up to a Maximum Current level.
· Constant Current: current is immediately increased to the Current Limit point
and held there until the motor reaches full speed.
· Custom Curve: gives the user the ability to plot torque and time points on a
graph. The soft starter will then accelerate the motor following these points.
· Tachometer Feedback Ramp: uses a closed loop speed follower method
monitoring a tachometer input signal from the motor or load shaft. (PENDING)
Deceleration: the TX Series provides the user with the option of having the
load coast to a stop or controlling the deceleration by slowly reducing the voltage
to the motor upon initiating a stop command. The Decel feature is the oppo-site of DC injection braking in that the motor will actually take longer to
come to a stop than if allowed to coast to a stop. The most common application for the Decel feature is pumping applications where a controlled stop
prevents water hammer and mechanical damage to the system.
1.4 General Protection
Operation of the TX Series can be divided into 4 modes; Ready, Start, Run and
Stop. The CPU provides motor and load protection in all four modes. Additional
details on each protection feature can be found in later chapters.
Ready Mode: In this mode, control and line power are applied and the starter is
ready for a start command. Protection during this mode includes the monitoring of current for leakage through multiple shorted SCRs. Other protection
features in effect are:
· Starter Temperature
· Shorted SCR
· Phase Reversal (if enabled)
· Line Frequency Trip Window
· External Input Faults
Note: The “Programming Mode” can only be entered from the Ready Mode.
During programming, all protection features and start command are disabled.
Start Mode: These additional protection functions are enabled when the soft
starter receives a valid Start command:
· Phase Reversal (if enabled)
· Start Curve
· Acceleration Timer
· Phase Imbalance
· Short Circuit / Load Pre-check (Toe-in-the-Water)
· Ground Fault
· External Input Faults
· Accumulated Starting FLA Units (I2t Protection)
· Overload Protection
· Thermal Capacity
Note: Shorted SCR and Shunt Trip protection are no longer in effect once the
soft starter goes into the Start Mode.
TOSHIBA- 5
TX Series 48 - 1250A
Run Mode: The soft starter enters the Run Mode when it reaches full output
voltage
FLA plus service factor) for a predetermined period of time. During the Run
Mode these additional protection features are enabled:
· Running Overload Curve
· Phase Loss
· Under Current / Load Loss
· Over Current / Electronic Shear Pin
· External Input Faults
Stop Mode: Once a Stop command has been given, the TX Series protec-
tion features change depending on which Stop Mode is selected.
· Decel Mode: retains all protection features of the Run Mode. At the end of
· Coast-T o-Stop Mode: power is immediately removed from the motor and the
· Coast-Down / Back Spin Timer
· Starts-per-Hour
· Time Between Starts
· External Input Faults
and the motor current drops below the FLA setting (motor nameplate
Decel, the motor will be stopped and the protection features change as
indicated below.
soft starter returns to the Ready Mode. Additional protection features activated
when the stop command is given include:
1.5 Thermal Overload Protection
The TX Series plays an important role in the protection of your motor in that it
monitors the motor for excessive thermal conditions due to starting, running or even
ambient conditions. The TX Series has a Dynamic Thermal Register system in
the CPU that provides a mathematical representation of the thermal state of the
motor. This thermal state information is kept in memory and is monitored for
excesses in both value and rate of change. Input is derived from current
imbalances and (optional) RTD measurements making it dynamic to all processes
involving the motor. The TX Series monitors these conditions separately during
Start and Run modes to provide proper thermal overload protection at all times.
Start Mode overload protection is selectable using one of three methods:
· Basic Protection: I2t data is accumulated and plotted based on an Overload
Curve selected in programming. This is programmed per NEMA Class 5-30
standard curves and is based on the Locked Rotor Current (from the motor
nameplate) as programmed into the soft starter.
· Measured Start Capacity: the user enters a measured amount of thermal
capacity from a pre-selected successful start as a setpoint to the Thermal
Register for the soft starter to follow.
· Learned Curve Protection: the user sets the soft starter to the “LEARN” mode
and starts the motor under normal starting conditions. The CPU then
samples and records 100 data points during the start curve, analyzes them
and creates a graphical representation in memory. The soft starter is then
switched to Curve Follow protection mode and monitors motor performance
against this curve. This feature is especially useful in initial commissioning
tests to record a base line performance sample (in this case, it is not
necessarily used for motor protection).
TOSHIBA - 6
TX Series 48 - 1250A
Run Mode overload protection is initiated when the TX Series determines
that the motor is At-Speed. Overload Protection is initiated when the motor
RMS current rises above a “pick-up point” (as determined by the motor
nameplate FLA and service factor). Run mode protection is provided by the
CPU monitoring the Dynamic Thermal Register. Data for the Dynamic
Thermal Register is accumulated from I
trip occurs when the register reaches 100% as determined by the selected
Overload Protection Curve (NEMA Class 5-30 standard curves) and is based
on the programmed Locked Rotor Current indicated on the motor nameplate.
The Dynamic Thermal Register is altered, or “biased”, by the following conditions:
· Current Imbalance: will bias the register higher to add protection from
additional motor heating during a current imbalance condition.
· Normal Cooling: provided when the motor current drops below the pick-up
point or the motor is off line. The cooling rate is lower for motors that are offline (such as after a trip) since cooling fans are also inoperative.
· RTD Input: (requires the optional RTD monitor card): will bias the register in
either direction based on real-time input of the motor, bearing and even
ambient temperature conditions.
2
t calculations and cooling rates. A
· Dynamic Reset is another feature that adds reliability and consistency to the
performance of the TX Series soft starter. If a motor overload condition
occurs and the soft starter trips, it cannot be reset until sufficient cool down
time has elapsed. This cool down time is determined by the thermal state of
the motor when it tripped (i.e. hot motors cool more quickly due to additional
convection). The cool down time is also biased by RTD measurements when
used.
Retentive Thermal Memory provides continuous overload protection and real
time reset even if power is lost. Upon restoration of power, the TX Series will
read the Real Time Clock and restore the thermal register to what it should be
given the elapsed time.
· Learned Reset Capacity is a feature that is unique to the TX Series. By
sampling the amount of thermal capacity used in the previous three successful
starts, the TX Series will not allow a reset until a sufficient amount of
thermal capacity has been regained in the motor. This prevents nuisance
tripping and insures that unsuccessful start attempts (which would otherwise
use up the starts-per-hour capacity of the motor) are not allowed.
TOSHIBA- 7
TX Series 48 - 1250A
WARNING
Chapter 2 - Installation
2.1 Receiving and Unpacking
Upon receipt of the unit:
• Carefully unpack the unit and inspect it for any shipping damage.
Report any damage immediately and file a claim with the freight
carrier within 15 days of receipt.
• Verify that the model number on your unit matches your purchase
order.
• Confirm that the ratings label on the unit matches or is greater than
the motor’s HP and current rating.
2.2 Initial Unit Inspection
• Make a complete visual check of the unit for damage which may have
occurred during shipping and handling. Do not attempt to continue
installation or start up the unit if it is damaged.
• Check for loose mechanical assemblies or broken wires which may
have occurred during transportation or handling. Loose electrical
connections will increase resistance and cause the unit to function
improperly.
• Prior to beginning the installation, verify that the motor and TX unit
are rated for the proper amperage and voltage.
2.3 Location
The proper location of the unit is an important factor in achieving the
unit’s specified performance and normal operation lifetime. The unit
should always be installed in an area where the following conditions
exist:
• Ambient Operating Temperature: 0° C to 50° C (32° F to 122° F)
(Optional space heaters can be provided for operation in ambient
temperature to -20° C.)
• Protected from rain and moisture.
• Humidity: 5% to 95% non-condensing.
• Free from metallic particles, conductive dust and corrosive gas.
• Free from excess vibration (below 0.5G)
• Open panel units must be mounted in the appropriate type of
enclosure. Enclosure size and type must be suitable to dissipate
heat generated by the soft starter. Contact factory for assistance in
sizing the enclosure.
Do not service equipment with voltage applied!
The unit can be the source of fatal electrical
shocks! To avoid shock hazard, disconnect
main power and control power before working
on the unit. Warning labels must be attached
to terminals, enclosure and control panel to
meet local codes.
2.4 Mounting and Cleaning
When drilling or punching holes in the enclosure, cover the electrical
assembly to prevent metal filings from becoming lodged in areas which
can cause clearance reduction or actually short out electronics. After
work is completed, thoroughly clean the area and reinspect the unit for
foreign material. Make sure there is sufficient clearance (six inches)
all around the unit for cooling, wiring and maintenance purposes. To
maximize effective air flow and cooling, the unit must be installed with
its heat sink ribs oriented vertically and running parallel to the mounting
surface.
TOSHIBA - 8
TX Series 48 - 1250A
Model
W ire
WARNING
Remove all sources of power before cleaning the unit!
In dirty or contaminated atmospheres the unit should be cleaned on a regular
basis to ensure proper cooling. Do not use any chemicals to clean the unit. T o
remove surface dust use 80 to 100 psi, clean, dry compressed air only . A three
inch, high quality , dry paint brush is helpful to loosen up the dust prior to using
compressed air on the unit.
2.5 Power Terminal Wire Range and Tightening Torque
Connect appropriate power lines to the unit input terminals marked L1, L2, L3.
Avoid routing power wires near the control board. Connect the motor leads to the
unit terminals marked T1, T2, T3. Refer to NEC standards for wire length and sizing.
Never interchange input and output connections to the unit. This could cause
excessive voltage in the control logic circuit and may damage the unit.
TX Series Unit
Never connect power factor correction
capacitors on the load side of the unit.
The SCRs will be seriously damaged if
capacitors are located on the load side.
The unit must be tested with a motor or other test load connected
to the load side of the unit. (A load bank can be used if a motor is
not available). Note that line voltage will appear across the output terminals if
there is no motor or load connected to the unit. In areas where lightning is a
significant problem, station-type air gap lightning arrestors should be considered
and utilized on the input power source.
2.7.1 Grounding
Connect the ground cable to the ground terminal as labeled on the unit. Refer
to the National Electrical Code for the proper ground wire sizing and be sure
that the ground connector is connected to earth ground.
2.8 Control Connections
Separate 120Vac supply is required (240Vac for 380V and 415V
applications). The control voltage should be connected to pins 1 and 6 of
TB4 on the power board. This control voltage must be customer supplied,
unless an optional control power transformer (See chart) has been supplied
with the unit.
Unit comes standard with 120Vac
control. Order 240Vac control as an
option if required.
Control
Power
Return
2.8.1 Three-Wire Connection
TX014500 VA500 VA1 KVA*
TX015 to TX016500 VA750 VA1.5 KVA*
TX017500 VA750 VA1.5 KVA*
* Transformer size is adequate to power built-in bypass contactors on these models.
Recommended Transformer Sizes for Control Power
Note:
1. If power is used for additional accessory items (Lights, fans, etc.)
contact factory for sizing.
For standard 3-wire control connect 120V ac (or 240Vac for 415V and
380V applications) to pins 1 and 6 of TB4. Connect N.C. (normally
closed) stop button between pins 3 and 4 of TB4. Connect N.O.
(normally open) start button between pins 4 and 5 of terminal block
TB4.
TOSHIBA - 10
Three-Wire Connection
TX Series 48 - 1250A
WARNING
2.8.2 Two-Wire Connection
An alternate connection for unattended operation replaces start/stop push
buttons by connecting a maintained contact closure between pins 3 and
5 on TB4. When the maintained contact is used for start/stop it is
necessary to set the overload setpoint to the manual reset position.
This will prevent the motor from restarting if the thermal overload trips
and then cools off.
Two-Wire Connection
When two-wire connection method is used, the start
circuit must be interlocked to prevent automatic
restart when either of the two protective devices
(overload or thermostat) reset. Thermostats always
automatically reset on cool down.
2.8.3 Programmable Relays/Relay Contacts
All the relay contacts are FORM C (Com, N.O., N.C.). Toshiba recommends
fusing all contacts with external fuses. The TX has four programmable relays
on TB3 on the power board. The relays are rated for 240Vac, 5 A and 1200
VA. These relays can respond to either a fault condition or an up-to-speed
condition. In the TX all tripping functions have been assigned to the TRIP
(AUX1) relay, and all alarm (warning) condition has been configured to the
ALARM (AUX2) relay. AUX 3 is factory programmed for a SHUNT TRIP
indication and can be connected to a shunt trip coil on an incoming circuit
breaker or open an input isolation contactor. AUX4 is the AT SPEED contact.
When the motor has reached the end of its acceleration ramp, the TX will
wait until the AT SPEED programmed time delay has expired. Then, the
relay will energize until a stop command has been received. The AT SPEED
contact can be used to operate a bypass contactor (used for shorting the
load current around the SCRs. To change AUX3 or AUX4 functions, see
Setpoint Page 4.
Relay Contacts on Power Board
Rated 240Vac, 5A, 1200VA
TOSHIBA- 11
TX Series 48 - 1250A
2.8.4 Power Board
2.8.4a Power Board Connections
TB4
Three-Wire Control Connection
TB4
Two-Wire Control Connection
Relay Contacts on Power Board
Rated 240Vac, 5A, 1200VA
TOSHIBA - 12
TX Series 48 - 1250A
2.9 CPU Board Connections
There are eight digital inputs on the CPU board. Four of the inputs are user
programmable. There are also two analog outputs, a tachometer feedback
input.
20
20
TB1
Tach Input
124356789
Analog Output #1
4 - 20 mA
Analog Output #2
4 - 20 mA
Contact factory for remote
reset connections
Input
TB2
12435678
Program Enable
Factory wired. Do not change
TB3
External Input #1
12435678
External Input #2
Dual Ramp
Thermostat
-
+
+-
+-
+-
Note: Install program jumper to enable
setpoint programming. Jumper must be
removed after programming or for
prolonged storage to preserve settings.
TOSHIBA- 13
-
+
+-
+
+-
TX Series 48 - 1250A
2.10 Communications Board
Full (RS422) or half (RS485) duplex Modbus communications port is available at TB1
on the communications board. No field wiring connections are required for TB2.
(RS485)
Note: Remove for last unit in modbus string
2.10.1 Communication Board Connections
REAR
VIEW
(RS422)
TB1TB2
RS485 Connections
(Customer Connections)
TOSHIBA - 14
RS422 Connections
(Factory Only)
TX Series 48 - 1250A
2.1 1 Optional RTD Board
RTD1
Compensation
Signal
Power
RTD
Typical RTD
Installation
Shield
RTD2
RTD3
RTD4
RTD5
RTD6
RTD7
RTD8
RTD9
RTD10
RTD11
RTD12
TOSHIBA- 15
TX Series 48 - 1250A
WARNING
Chapter 3 - Start-up
THE TX UNIT DEALS WITH POTENTIALLY LETHAL
VOL T AGE LEVELS. YOU MUST BE CERT AIN THA T
PERSONNEL ARE THOROUGHL Y TRAINED IN THE
APPLICABLE SAFETY PRECAUTIONS BEFORE
PROCEEDING WITH THIS SECTION!
3.1 Preliminary Start-Up Check List
Please make the following checks before applying power to the unit:
•Supply voltage matches the rated supply voltage of the unit.
•Horsepower and current ratings of the motor and unit match or the unit has a
higher rating.
•Initial ramp time and torque adjustments have been checked.
•Power lines are attached to the unit input terminals marked L1, L2 and L3.
•Motor leads are connected to the lower terminals marked T1, T2 and T3.
•Appropriate control power is applied and/or control connections have been
made.
•The motor’s FLA has been programmed.
•The thermal overload parameters are properly set.
•The motor area and equipment are clear of people and parts before start-up.
3.2 Introduction
It is best to operate the motor at its full load starting condition to achieve the
proper time, torque and ramp settings. Initial settings are set to accommodate most motor conditions. TRY INITIAL SETTINGS FIRST. See Setpoints
Page 2 to make any adjustments.
3.3 Acceleration Adjustments
The unit is set at the factory with typical starting characteristics that perform well
in most applications. When the system is ready to start, try the initial unit
settings. If the motor does not come up to speed, increase the current limit
setting. If the motor does not start to turn as soon as desired, raise the
starting voltage adjustment. Adjustment description and procedures are
described as follows (See section 4.5.2 for additional Accel settings):
3.3.1 Starting Voltage
Factory Setting = 20% of line voltage
Range = 0% - 100% of line voltage
Starting voltage adjustment changes the initial starting voltage level to the
motor.
3.3.2 Ramp Time
Factory Setting = 10 sec.
Range = 0 - 120 sec.
Ramp time adjustment changes the amount of time it takes to reach the
current limit point or full voltage if the current limit point was not reached.
3.3.3 Current Limit
Factory Setting = 350% of unit FLA
Range = 200% - 600% of unit FLA
The current limit adjustment is factory set for 350% of the unit’s rating.
The range of adjustment is 200% to 600%. The main function of current
limit is to cap the peak current. It may also be used to extend the ramping time if required. The interaction between the voltage ramp and the
current limit will allow the soft start to ramp the motor until the maximum
current is reached and the current limit will hold the current at that level.
TOSHIBA - 16
TX Series 48 - 1250A
The current limit must be set high enough to allow the motor to
reach full speed. The factory setting of 350% is a good starting
point. Do not set the current limit too low on variable starting
loads. This could cause the motor to stall and eventually
cause the overload protection to trip.
3.4 Deceleration Adjustments (Pump Control)
Decel extends the stopping time on loads that would otherwise stop
too quickly if allowed to coast to stop. Decel control provides smooth
deceleration until the load comes to a stop. Three adjustments
optimize the deceleration curve to meet the most demanding requirements. Try factory settings before adjusting.
Deceleration Applications
The unit is shipped from the factory with the decel feature
disabled. Apply power and adjust the soft start before enabling or
modifying the deceleration adjustments. Both acceleration and deceleration
adjustments should be made under normal load conditions.
The deceleration feature provides a slow decrease in the output voltage,
accomplishing a gentle decrease in motor torque during the stopping mode.
This is the OPPOSITE OF BRAKING in that it will take longer to
come to a stop than if the starter were just turned off. The primary use
of this function is to reduce the sudden changes in pressure that are
associated with “Water Hammer” and slamming of check valves with
centrifugal pumps. Decel control in pump applications is often referred
to as Pump Control.
In a pump system, liquid is being pushed uphill. The force exerted by
gravity on the column of liquid as it goes up hill is called the “Head
Pressure” in the system. The pump is sized to provide enough Output
Pressure to overcome the Head Pressure and move the fluid up the
pipe. When the pump is turned off, the Output Pressure rapidly drops
to zero and the Head Pressure takes over to send the fluid back down
the hill. A “Check Valve” is used somewhere in the system to prevent
this (if necessary) by only allowing the liquid to flow in one direction.
The kinetic energy in that moving fluid is suddenly trapped when the
valve slams closed. Since fluids can’t compress, that energy is
transformed into a “Shock Wave” that travels through the piping
system looking for an outlet in which it dissipates. The sound of that
shock wave is referred to as “Water Hammer”. The energy in that
shock wave can be extremely damaging to pipes, fittings, flanges,
seals and mounting systems.
By using the Soft Stop/Deceleration feature of the TX, the pump output
torque is gradually and gently reduced, which slowly reduces the
pressure in the pipe. When the Output Pressure is just slightly lower
than the Head Pressure, the flow slowly reverses and closes the
Check Valve. By this time there is very little energy left in the moving
fluid and the Shock Wave is avoided. When the output voltage to the
motor is low enough to no longer be needed, the TX will end the Decel
cycle and turn itself off.
TOSHIBA- 17
TX Series 48 - 1250A
WARNING
Another common application for decel control is on material handling conveyors as a means to prevent sudden stops that may cause products to fall over
or to bump into one another. In overhead crane applications, soft stopping of
the Bridge or Trolley can prevent loads from beginning to over swing on
sudden stops.
3.4.1 Start Deceleration Voltage
Factory Setting = 60% of line voltage
Range = 0% - 100% of line voltage
The step down voltage adjustment eliminates the dead band in the
deceleration mode that is experienced while the voltage drops to a level
where the motor deceleration is responsive to decreased voltage. This
feature allows for an instantaneous drop in voltage when deceleration is
initiated.
3.4.2 Stop Deceleration Voltage
Factory Setting = 20% of line voltage
Range = 0% - 100% of line voltage
The stop voltage level setpoint is where the deceleration voltage drops
to zero.
3.4.3 Deceleration Time
Factory Setting = 5 sec.
Range = 0 - 60 sec.
The deceleration ramp time adjusts the time it takes to reach the stop
voltage level set point. The unit should be restarted and stopped to verify
that the desired deceleration time has been achieved.
DO NOT EXCEED THE MOTOR MANUF ACTURER’S
RECOMMENDED NUMBER OF ST ARTS PER HOUR.
WHEN CALCULA TING THE NUMBER OF ST ARTS PER
HOUR, A DECEL CURVE SHOULD BE COUNTED AS A
START CUR VE. FOR EXAMPLE: RECOMMENDED
NUMBER OF ST ARTS PER HOUR = 6, ALLOW ABLE
ST ARTS WITH DECEL CYCLE PER HOUR = 3.
TOSHIBA - 18
TX Series 48 - 1250A
3.5 Sequence of Normal Operation
•Apply control power and check that the “Power” LED comes on.
(Display 1)
•Apply three phase power to the unit. The motor should run only when the
start command is applied.
•Apply the start command. (Display 2). The RUN LED will be lit. (Display 3)
The AUX3 LEDs will be lit. If the motor does not enter run mode in the set
time, a trip will occur.
•The POWER, RUN, AUX3 LEDs will be lit, indicating that the contact has
energized. IA, IB, IC will display the current setting for Phase A, Phase B,
and Phase C and the G/F indicates ground fault. (Display 4)
•When the motor reaches full speed, the “AUX4” LED (At Speed) will be lit.
•If the motor decelerates, or stops, during the acceleration period, hit the
stop button immediately and open the disconnect line. If the unit does not
follow this operational sequence, please refer to the Troubleshooting
Chapter.
It is best to operate the motor at its full load starting condition to achieve the
proper time, torque and ramp settings. Initial settings are set to accommodate
most motor conditions. TRY INITIAL SETTINGS FIRST. See Setpoint Page 2
to make any adjustments.
•Initial Voltage
•Soft Start Curve
•Current Limit
•Acceleration Time
MOTOR STOPPED
1.
READY TO START
MOTOR STARTING
2.
00 X FLA
OVERLOAD ALARM
3.
TIME TO TRIP: XXX SECS.
IA: _ _ _ IB: _ _ _
4.
IC: _ _ _ G/F: _ _ _
If decel is enabled, the following parameters for Deceleration Time, Start Decel
Voltage (see SP2) and Stop Decel Voltage (see SP2) must also be programmed.
TOSHIBA- 19
TX Series 48 - 1250A
n
e
Chapter 4 - User Interface & Menu Navigation
This chapter explains the keypad operator interface, the LCD descriptions and the
programming features
4.1 Keypad/Operator Interface
The TX Series user keypad/keypad operator interface consists of:
• 2 row by 20 characters Liquid Crystal Display (LCD)
• 12 LEDs
• 8 pushbuttons
Note: The TX Series is menu driven and there are three levels of programming.
The programming for two of these levels is password protected. Level two requires
a three digit password and level three requires a four digit password.
Button
MENU
RESET
ENTER
HELP
UP ARROW
RIGHT ARROW
DOWN ARROW
Toggle between the menu selection for metering and
setpoint pages.
Will clear the trip indicator and release the trip relay.
In the edit mode, press the ENTER pushbutton so the
unit will accept the new programming information. Whe
not in the edit mode, the ENTER pushbutton will toggle
through the event in dicator list (such as alarms or trips)
Provides general help information about a specific
setpoint or action.
Will scroll up through the setpoint and metering menu
page. It will scroll to the top of the setpoint page or a
section. In edit mode it wil l increase a setpoint in an
incremental step or toggle through the available options
in the setpoint.
In the main menu the RIGHT ARROW button provides
access to the setpoint page. For setpoint pages with
multiple columns, the RIGHT ARROW will scroll the
setpoint page to the right. When in edit mode it will shift
one character to the right.
Will scroll down through the setpoint pages and down
through the setpoints. In edit mode, it will decrement
through values and toggle available options in the
setpoint.
Keypad Operator Interface
Will move to the left through setpoint pages with multipl
columns. When in edit mode it will become the
backspace key and will shift one character to the left.
Indicates unit/motor is running
Lights in conjunction with AUX 2 to indicate event or
warn of possible critical condition.
Lights in conjunction with AUX 1 to indicate a critical
condition has occurred.
Auxilary relays
LED
LEFT ARROW
PowerIndicates control power is present
Run
Alarm
Trip
AUX 1-4
Note: The directional arrow buttons are sensitive. In edit mode, if the buttons
are held for a long period, the scrolling speed will increase.
TOSHIBA - 20
TX Series 48 - 1250A
4.2 Menu Navigation
PAGE 1 BASIC
CONFIGURATION
LEVEL 1
PAGE 2 STARTER
CONFIGURATION
PAGE 3 PHASE &
GROUND SETTINGS
PAGE 4 RELAY
ASSIGNMENT
LEVEL 2
PAGE 5 RELAY
CONFIGURATION
MENU
(1)
Notes:
1. The MENU keys allow you to toggle the screens between the Setpoint Menu and
the Metering Menu. Simply use the arrow keys to get to the different screens
within each menu.
Example: To access Setpoint Page 3: PHASE & GROUND SETTINGS, press
the MENU key once and the DOWN ARROW two times.
2. Levels 1, 2 and 3 indicate password protection levels for these setpoint pages.
LEVEL 3
PAGE 6 USER I/O
CONFIGURATION
PAGE 7 CUSTOM
ACCELERATION CURVE
PAGE 8 OVERLOAD
CURVE CONFIGURATION
PAGE 9 RTD
CONFIGURATION
PAGE 10 SECURITY
SET PASSWORD
PAGE 11
COMMUNICATIONS
PAGE 12 SYSTEM
SETPOINTS
FACTORY
LEVEL
PAGE 13 CALIBRATION
& SERVICE
TOSHIBA- 21
TX Series 48 - 1250A
4.2.1 Password Access
Screens in Level 1 of the setpoint menu can be changed without password
access because they list basic motor information. Screens in Levels 2
and 3 require passwords because they provide more in-depth protection
and control of the TX Series unit. The password in Levels 2 and 3 can be
changed by the user.
NOTE: Setpoints can only be changed when the motor is in Stop/
Ready Mode! The TX will not allow a start if it is still in the
Edit Mode. When the unit is in the Edit Mode, a “*” is in the
top right corner of the display .
4.2.2 Changing Setpoints
Example 1: Changing Motor FLA
A. Press MENU button to display Setpoint Page 1, Basic Configuration
B. Press the RIGHT ARROW you will view the screen Motor Full Load
Amps.
C. Press the ENTER button for edit mode. Note the asterisk (*) in the
top right corner of the LCD screen that indicates Edit Mode.
D. To change the value, select the UP ARROW or DOWN ARROW.
E . To accept the new value, press the ENTER button. The unit will
accept the changes and will leave the edit mode. Note the * is no
longer in the top right corner of the LCD Display.
MENU
PAGE 1 BASIC
CONFIGURATION
MOTOR FULL LOAD AMPS
: 140 AMPS
ENTER
2x
ENTER
MOTOR FULL LOAD AMP
: 142 AMPS
MOTOR FULL LOAD AMP*
: 142 AMPS
TOSHIBA - 22
TX Series 48 - 1250A
50 - 100% of Unit Max Curr ent Rati ng (Model
Chapter 5 - Setpoint Programming
The TX Series has twelve programmable setpoint pages which define the motor
data, ramp curves, protection, I/O configuration and communications. In Section 5.1,
the setpoint pages are outlined in chart form. In Section 5.2 the setpoint pages are
illustrated and defined for easy navigation and programming. Note: Setpoints can
only be changed when the starter is in the Ready Mode. Also the soft start will not
start when it is in programming mode.
5.1 Setpoints Page List
The following charts list each Setpoint Page and the programmable functions within
that page. The applicable section of the manual is also referenced.
5.1.1 Basic Configuration (Setpoint Page 1)
Setpoint
Page
Security
Level
Description
Factory Setting
Default
RangeSection
Motor Full Load Amps (FLA)Model dependent
Service Factor1.151.00 – 1.3SP1.2
Overload Class10O/L Class 5-30 SP1.3
Page 1
Basic Configuration
Level 1
NEMA DesignBA-FSP1.4
Insulation ClassBA, B, C, E, F, H, K, N, SSP1.5
Line Voltage480208 to 600VSP1.6
No Passowrd Required
Line Frequency6050 or 60 HZSP1.7
5.1.2 Starter Configuration (Setpoint Page 2)
Setpoint
Page
Page 2
Starter Configuration
Security
Level
Level 1
Description
Start Control ModeStart Ramp 1
Jog VoltageOff5-75%, Off
Start Ramp #1 TypeVoltageCurrent, Voltage, Off
Initial Voltage #120%0-100%
Ramp Time #110 sec0-120 sec
Current Limit #1350% FLA200-600 %
Initial Current #1200% FLA0-300%
Ramp Time #110 sec0-120 sec
Maximum Curre nt #1350% FLA200-600 %
Start Ramp #2 TypeOffCurrent, Voltage, Off
Initial Voltage #260%0-100 %
Ramp Time #210 sec0-120 sec
Current Limit #2350 % FLA200-600 %
Initial Current #2200% FLA0-600 %
Ramp Time #210 sec0-120 sec
Maximum Curre nt #2350% FLA200-600 %
No Passowrd Required
Kick Start TypeOffVoltage or Off
Kick Start Voltage65%10-100 %
Kick Start Time0.50 sec0.10-2.00
Deceleration DisabledEnabled or Disabled
Start Deceleration Voltage60%0-100 %
Stop Decel eration Voltage30%0-59 %
Deceleration Time5 sec1-60 sec
Timed Output TimeOff1-1000 sec, Off
Run Delay Time1 Sec1-30 sec, Off
At Speed Delay Time1 Sec1-30 sec, Off
Bypass Pull-in Current100% FLA90 - 300%