Toshiba 48-1250 A User Manual

Page 1
INSTRUCTION MANUAL
INSTALLATION - OPERATION - MAINTENANCE
TX SERIES
Low Voltage Digital Solid State Starter
48 - 1250 A
Issued: 11/04 Manufactured in the USA
Page 2
Page 3
SAFETY
DANGER
WARNING
CAUTION
DANGER
IMPORTANT MESSAGES
Read this manual and follow its intructions. Signal words such as DANGER, WARNING
and CAUTION will be followed by important safety information that must be carefully reviewed. Indicates a situation which will result in death, serious injury , and severe property damage if you
do not follow instructions. Means that you might be seriously injured or killed if you do not follow instructions. Severe
property damage might also occur. Means that you might be injured if you do not follow instructions. Equipment damage might
also occur.
NOTE
Give you helpful information.
Note: The contents of this manual will not become apart of or modify the warranty policy , the terms of which are set forth at the end of this manual.
READ SAFETY SIGNS
T o avoid injury , you must read and follow all safety signs. Keep the safety signs visible and in good shape. Never remove or cover any safety sign.
QUALIFIED OPERATORS ONLY
Only qualified persons are to install, operate, or service this equipment according to all applicable codes and established safety practices.
A qualified person must:
1) Carefully read the entire instruction manual.
2) Be skilled in the installation, construction or operation of the equipment and aware of the hazards involved.
3) Be trained and authorized to safely energize, de-energize, clear, ground, lockout and tag circuits in accordance with established safety practices.
4) Be trained and authorized to perform the service, maintenance or repair of this equip­ment.
5) Be trained in the proper care and use of protective equipment such as rubber gloves, hard hat, safety glasses, face shield, flash clothing, etc. in accordance with estab­lished practices.
6) Be trained in rendering first aid.
Page 4
SAFETY
WARNING
SAFETY CODES
T oshiba motor control is designed and built in accordance with the latest applicable provisions of NEMA and the National Electrical Code. Installations must comply with all applicable state and local codes, adhere to all applicable National Electric Code (NFP A 70) st andards and instructions provided
in this manual.
HAZARDOUS VOL TAGE will cause severe injury , death, fire, explosion and
property damage.
Turn off and lock out Primary and Control Circuit Power before servicing.
Keep all panels and covers securely in place.
Never Defeat, Modify , or Bypass any Safety Interlocks.
Qualified Operators only.
Never attempt to install, operate, maintain or dispose of this equipment until you have first read and understood all of the relevant product warnings and user directions that are contained in this Instruction Manual.
Use only T oshiba-authorized replacement parts.
This equipment is designed and built in accordance with applicable safety standards in effect on the date of manufacture. Unauthorized modifications can result in voiding the warranty, severe injury, death and property damage. Do not make any modifications to this equipment without the written approval of Toshiba.
For assistance, address correspondence to: T oshiba International Corporation
Field Service Department 13131 West Little York Road Houston, T exas 77041 USA
or call: (713) 466-0277 Fax: (713) 466-8773
(800) 231-1412 (800) 527-1204 (Canada)
Please complete the following information for your records and retain with this manual:
Model: ___________________________________ Serial Number: _____________________________ Date of Installation: _________________________ Inspected by: ______________________________ Reference Number: _________________________
© TOSHIBA INTERNA TIONAL CORPORA TION, 2004
Page 5
TX Series
TX Series 48 - 1250A
Digital Solid State Soft Starter 48 - 1250A
Chapter 1: Introduction ...................................................................................................... 1
1.1 General
1.2 Specifications
1.3 Theory of Operation
1.4 General Protection
1.5 Thermal Overload Protection
Installation & Operation Manual
Chapter 2: Installation .......................................................................................................8
2.1 Receiving and Unpacking
2.2 Initial Unit Inspection
2.3 Location
2.4 Mounting & Cleaning
2.5 Power Wire Range and Tightening Torque
2.6 Dimensions
2.7 Power Connections
2.8 Control Connections
2.9 CPU Board Connections
2.10 Communications Board
2.11 RTD Board (Optional)
Chapter 3: Start-Up.......................................................................................................... 16
3.1 Preliminary Start-up Check List
3.2 Introduction
3.3 Acceleration Adjustments
3.4 Deceleration Adjustments
3.5 Sequence of Normal Operation
Chapter 4: User Interface and Menu Navigation.............................................................20
4.1 Keypad/Operator Interface
4.2 Menu Navigation
Chapter 5: Setpoint Programming..................................................................................23
5 .1 Setpoints Page List
5.2 Setpoint Menu
SP.1 Basic Configuration ................................................................................................33
SP.2 Starter Configuration...............................................................................................34
SP.3 Phase & Ground Settings .......................................................................................37
SP.4 Relay Assignment ...................................................................................................40
SP.5 Relay Configuration ...............................................................................................42
SP.6 I/O Configuration ....................................................................................................43
SP.7 Custom Acceleration Curve...................................................................................46
SP.8 Overload Curve Configuration............................................................................... 49
SP .9 R TD Configuration..................................................................................................50
SP.10 Set Password .......................................................................................................52
SP .1 1 Communications ....................................................................................................53
SP.12 System Setpoints ..................................................................................................54
SP.13 Calibration & Service ............................................................................................56
Chapter 6: Metering Pages ..............................................................................................57
6 .1 Metering Page List
Chapter 7: Maintenance and Troubleshooting/Disposal/Storage.................................. 67
7.1 Failure Analysis
7.2 SCR Testing Procedure
7.3 Replacing SCR devices
7.4 Replacing the Main Control Board
7.5 Interconnect Drawing
7.6 Maintenance Program
7.7 Disposal/Storage
Appendix A: Reference Section....................................................................................... 78
Appendix B: Record of Setpoint Adjustments .................................................................81
Warranty Policy .................................................................................................................89
TOSHIBA- 95
Page 6
TX Series 48 - 1250A
TOSHIBA - 96
Page 7
TX Series 48 - 1250A
Full horsepower rated contactor included as standard in all Type 12, 3R, 4 & 4X
Chapter 1 - Introduction
This chapter is a brief introduction to the TX Series soft starter and describes product operation and unit features.
1.1 - General
The TX Series is a high-end digitally programmable solid state reduced voltage soft starter. This heavy duty starter provides reduced voltage, stepless soft starting of 3-phase AC induction motors, protecting mechanical components from excessive torque stress and electrical systems from the effects of high motor inrush currents. The TX Series includes advanced motor and load protection features just like those found in expensive motor protection relays. These include retentive thermal memory, dynamic reset capacity, true thermal modeling, separate trip curves for start and run protection, overload alarm, etc. In the case of the TX Series, these features are built in as standard features, providing a cost effective and reliable motor starting and protection scheme for your critical motor applications.
The TX Series features an easy to use interface operator for programming and status indication. It includes a large tactile feedback keypad, LED status indica­tors and a 2 line x 20 character backlit display using plain English text readout. In addition to programming the standard parameters such as starting torque, ramp time, current limit, dual ramp and decel control, other features like programmable overload trip curves (NEMA/UL Classes 5 - 30), starts-per-hour, time between starts and coast down/back spin lockout protection can also be programmed for your specific application needs.
1.2 Specifications
Type of Load AC Supply Voltage HP Ratings
Unit Overload Capacity (Percent of motor FLA)
Power Circuit SCR Diode Ratings
(Peak Inverse Voltage) Phase Insensitivity
Transient Voltage Protection Cooling
Bypass Contactor
Ambient Condition Design
Three phase AC induction motors or synchronous motors 208 - 600 VAC + 39 - 1250 Amps, 10 - 1125 HP
125% - Continuous 500% - 60 seconds 600% - 30 seconds
6 SCRs 1600V Unit operates with any phase sequence
RC snubber dv/dt networks on each phase Convection up to 180A, fan assisted 78 - 120A
Fan ventilated 220 - 1250A
enclosed units 120A and above.
Chassis units: 0° to 50 °C (32° to 122°F) Enclosed units: 0° to 40°C (32° to 104°F) 5 - 95% relative humidity 0 - 3300 ft. (1000m) above sea level without derating
10%, 50/60 Hz
Control
Auxiliary Contacts
Approvals
2 or 3 wire 120VAC (customer supplied) Optional 240VAC control voltage and CPTs are available
Type/Rating: FORM C (SPDT), rated 5 Amps, 240VAC max. (1200VA) 4 Programmable Relays UL Listed, Canadian UL (cUL)
TOSHIBA- 1
Page 8
TX Series 48 - 1250A
for a successful restart. Starter learns and retains this information by monitoring
1.2 Specifications (continued)
Advanced Motor Protection
Two Stage Electronic Overload Curves
Overload Reset Retentive Th ermal Memory
Dynamic Reset Capacity
Phase Current Imbalance Protection
Over Current Protection (Electronic Shear Pin)
Load Loss Trip Protection
Coast Down (Back Spin) Lockout Timer
Starts-per-hour Lockout Timer
Starting: programmable for Class 5 - 30 or locked rotor time. Run: Programmable for Class 5 - 30 when "At-Speed" is detected.
Manual (default) or automatic Overload circuit retains thermal condition of the motor regardless of control
power status. Unit uses real time clock to adjust for off time. Overload will not reset until thermal capacity available in the motor is enough
previous successful starts. Imbalance Trip Level: 5 - 30% current between any two phases
Imbalance Trip Delay: 1 -20 seconds Trip Level: 100 - 300% of motor FLA while running not starting or OFF
Trip Delay: 1 - 20 seconds Under Current Trip Level: 10 -90 % of motor FLA or OFF
Under Current Trip Delay: 1 - 60 seconds
Coast Down Time Range: 1 - 60 minutes or OFF
Range: 1 - 6 successful starts per hour Time between starts: 1 - 60 minutes between start attempts
Programmable Outputs
Type / Rating Run Indication At Speed Indication
Acceleration Adjustments
Dual Ramp Settings
Deceleration Adjustments
Jog Settings (Function selected via programming input)
Kick Start Settings
Fault Display Lockout Display
Form C (DPDT), Rated 5 amps 240 VAC max, (1200 VA) Start/Stop or Start/End of Decel At Speed/Stop or At Speed/End of Decel Programmable Ramp Types: Voltage or Current Ramp (VR or CR)
Starting Torque: 0 - 100% of line voltage (VR) or 0 - 600% of motor FLA (CR) Ramp Time: 1 to 120 seconds Current Limit: 200 - 600% (VR or CR)
4 Options: VR1+VR2; VR1+CR2; CR1+CR2; CR1+VR2 Dual Ramp Control: Ramp 1 = Default Ramp 2 = selectable via dry contact input
Begin Decel Level: 0 - 100% of line voltage Stop Level: 0 to 1% less than Begin Decel Level Decel Time: 1 - 60 seconds Programmable to decel or coast to stop upon overload trip
Voltage Jog: 5 - 100% or OFF Time of Voltage Jog: 1 - 20 seconds Current Jog: 100 - 500%
Kick Voltage: 10 - 100% or OFF Kick Time: 0.1 - 2 seconds
Shorted SCR, Phase Loss, Shunt Trip, Phase Imbalance Trip, Overload, Overtemp, Overcurrent, Short Circuit, Load Loss, Undervoltage or Any Trip
Coast Down Time, Starts Per Hour, Time Between Starts, and Any Lockout
TOSHIBA - 2
Page 9
TX Series 48 - 1250A
1.2 Specifications (continued)
Event History
Up to 60 Events
Motor Load Current Data Thermal Data
Start Data RTD Data
Voltage Metering
Protocol Signal Network Functionality
LCD Readout Keypad Status Indicators Remote Mount Capability
Data includes cause of event, time, date, and current for each phase and ground fault current at time of event
Metering Functions
Percent of FLA A, B, C Phase Current, Avg Current, Ground Fault Remaining thermal register; thermal capacity to start Avg Start Time, Avg Start Current, Measured Capacity to start, time since last
start Temperature readings from up to 12 RTDs (6 stators) KW, KVAR, PF, KWH
Serial Communications
Modbus RTU RS-485 or RS-422 Up to 247 devices per mode Full operation, status view, and programming via communications port
Operator Interface
Alpha numeric LCD display 8 function keys with tactile feedback 8 LEDs include Power, Run, Alarm, Trip, Aux Relays Up to 1000 feet from chassis (use twisted, shielded wire)
Clock and Memory
Operating Memory Factory Default Sto rage Customer Settings and Status Real Time Clock
DRAM loaded from EPROM and EEPROM at initialization Flash EPROM, field replaceable Non-volatile EEPROM, no battery backup necessary Lithium ion battery for clock memory only
TOSHIBA- 3
Page 10
TX Series 48 - 1250A
1.3 - Theory of Operation
The power of the TX Series is in the CPU, a microprocessor based protection and control system for the motor and starter assembly. The CPU uses Phase Angle Firing of the SCRs to apply a reduced voltage to the motor, and then slowly and gently increases torque through control of the voltage and current until the motor accelerates to full speed. This starting method lowers the starting current of the motor, reducing electrical stresses on the power system and motor. It also reduces peak starting torque stresses on both the motor and load mechanical components, promoting longer service life and less downtime.
Acceleration: The TX Series comes standard with several methods of accelerating the motor so that it can be programmed to match almost any industrial AC motor application.
The factory default setting applies a Voltage Ramp with Current Limit as this has been proven the most reliable starting method for the vast majority of applications. Using this starting method, the Initial Torque setting applies just enough voltage to the motor to cause the motor shaft to begin to turn. This voltage is then gradually increased over time (as per the Ramp Time setting) until one of three things happen: the motor accelerates to full speed, the Ramp Time expires or a Current Limit setting is reached.
If the motor accelerates to full speed before the ramp time setting has expired, an automatic Anti-Oscillation feature will override the remaining ramp time and full voltage will be applied. This will prevent any surging or pulsation in the motor torque, which might otherwise occur due to the load not being fully coupled to the motor when operating at reduced voltage and torque levels.
If the motor has not reached full speed at the end of the ramp time setting, the current limit setting will proportionally control the maximum output torque. Feedback sensors in the TX Series provide protection from a stall condition, an overload condition or excessive acceleration time.
The Current Limit feature is provided to accommodate installations where there is limited power available (for example, on-site generator power or utility lines with limited capacity). The torque is increased until the motor current reaches the preset Current Limit point and it is then held at that level. Current Limit overrides the ramp time setting so if the motor has not accelerated to full speed under the Current Limit setting, the current remains limited for as long as it takes the motor to accelerate to full speed.
When the motor reaches full speed and the current drops to running levels, the TX Series detects an At-Speed condition and will close the Bypass Contactor (if provided). The Bypass Contactor serves to shunt power around the SCR stack assemblies to prevent heat build-up NEMA 12, 3R, 4 and 4X enclosed units due to the slight voltage drop across the SCRs. At this point, the TX Series has the motor operat- ing at full voltage, just as any other starter would.
TOSHIBA - 4
Page 11
TX Series 48 - 1250A
Other starting methods available in the TX Series are:
· Current Ramp: uses a closed current feedback PID loop to provide a linear torque increase up to a Maximum Current level.
· Constant Current: current is immediately increased to the Current Limit point and held there until the motor reaches full speed.
· Custom Curve: gives the user the ability to plot torque and time points on a graph. The soft starter will then accelerate the motor following these points.
· Tachometer Feedback Ramp: uses a closed loop speed follower method monitoring a tachometer input signal from the motor or load shaft. (PENDING)
Deceleration: the TX Series provides the user with the option of having the load coast to a stop or controlling the deceleration by slowly reducing the voltage to the motor upon initiating a stop command. The Decel feature is the oppo- site of DC injection braking in that the motor will actually take longer to come to a stop than if allowed to coast to a stop. The most common applica­tion for the Decel feature is pumping applications where a controlled stop prevents water hammer and mechanical damage to the system.
1.4 General Protection
Operation of the TX Series can be divided into 4 modes; Ready, Start, Run and Stop. The CPU provides motor and load protection in all four modes. Additional details on each protection feature can be found in later chapters.
Ready Mode: In this mode, control and line power are applied and the starter is ready for a start command. Protection during this mode includes the monitor­ing of current for leakage through multiple shorted SCRs. Other protection features in effect are:
· Starter Temperature
· Shorted SCR
· Phase Reversal (if enabled)
· Line Frequency Trip Window
· External Input Faults
Note: The “Programming Mode” can only be entered from the Ready Mode. During programming, all protection features and start command are disabled.
Start Mode: These additional protection functions are enabled when the soft starter receives a valid Start command:
· Phase Reversal (if enabled)
· Start Curve
· Acceleration Timer
· Phase Imbalance
· Short Circuit / Load Pre-check (Toe-in-the-Water)
· Ground Fault
· External Input Faults
· Accumulated Starting FLA Units (I2t Protection)
· Overload Protection
· Thermal Capacity
Note: Shorted SCR and Shunt Trip protection are no longer in effect once the soft starter goes into the Start Mode.
TOSHIBA- 5
Page 12
TX Series 48 - 1250A
Run Mode: The soft starter enters the Run Mode when it reaches full output voltage FLA plus service factor) for a predetermined period of time. During the Run Mode these additional protection features are enabled:
· Running Overload Curve
· Phase Loss
· Under Current / Load Loss
· Over Current / Electronic Shear Pin
· External Input Faults Stop Mode: Once a Stop command has been given, the TX Series protec-
tion features change depending on which Stop Mode is selected.
· Decel Mode: retains all protection features of the Run Mode. At the end of
· Coast-T o-Stop Mode: power is immediately removed from the motor and the
· Coast-Down / Back Spin Timer
· Starts-per-Hour
· Time Between Starts
· External Input Faults
and the motor current drops below the FLA setting (motor nameplate
Decel, the motor will be stopped and the protection features change as indicated below.
soft starter returns to the Ready Mode. Additional protection features activated when the stop command is given include:
1.5 Thermal Overload Protection
The TX Series plays an important role in the protection of your motor in that it monitors the motor for excessive thermal conditions due to starting, running or even ambient conditions. The TX Series has a Dynamic Thermal Register system in the CPU that provides a mathematical representation of the thermal state of the motor. This thermal state information is kept in memory and is monitored for excesses in both value and rate of change. Input is derived from current imbalances and (optional) RTD measurements making it dynamic to all processes involving the motor. The TX Series monitors these conditions separately during Start and Run modes to provide proper thermal overload protection at all times.
Start Mode overload protection is selectable using one of three methods:
· Basic Protection: I2t data is accumulated and plotted based on an Overload Curve selected in programming. This is programmed per NEMA Class 5-30 standard curves and is based on the Locked Rotor Current (from the motor nameplate) as programmed into the soft starter.
· Measured Start Capacity: the user enters a measured amount of thermal capacity from a pre-selected successful start as a setpoint to the Thermal Register for the soft starter to follow.
· Learned Curve Protection: the user sets the soft starter to the “LEARN” mode and starts the motor under normal starting conditions. The CPU then samples and records 100 data points during the start curve, analyzes them and creates a graphical representation in memory. The soft starter is then switched to Curve Follow protection mode and monitors motor performance against this curve. This feature is especially useful in initial commissioning tests to record a base line performance sample (in this case, it is not necessarily used for motor protection).
TOSHIBA - 6
Page 13
TX Series 48 - 1250A
Run Mode overload protection is initiated when the TX Series determines that the motor is At-Speed. Overload Protection is initiated when the motor RMS current rises above a “pick-up point” (as determined by the motor nameplate FLA and service factor). Run mode protection is provided by the CPU monitoring the Dynamic Thermal Register. Data for the Dynamic Thermal Register is accumulated from I trip occurs when the register reaches 100% as determined by the selected Overload Protection Curve (NEMA Class 5-30 standard curves) and is based on the programmed Locked Rotor Current indicated on the motor nameplate. The Dynamic Thermal Register is altered, or “biased”, by the following condi­tions:
· Current Imbalance: will bias the register higher to add protection from additional motor heating during a current imbalance condition.
· Normal Cooling: provided when the motor current drops below the pick-up point or the motor is off line. The cooling rate is lower for motors that are off­line (such as after a trip) since cooling fans are also inoperative.
· RTD Input: (requires the optional RTD monitor card): will bias the register in either direction based on real-time input of the motor, bearing and even ambient temperature conditions.
2
t calculations and cooling rates. A
· Dynamic Reset is another feature that adds reliability and consistency to the performance of the TX Series soft starter. If a motor overload condition occurs and the soft starter trips, it cannot be reset until sufficient cool down time has elapsed. This cool down time is determined by the thermal state of the motor when it tripped (i.e. hot motors cool more quickly due to additional convection). The cool down time is also biased by RTD measurements when used.
Retentive Thermal Memory provides continuous overload protection and real time reset even if power is lost. Upon restoration of power, the TX Series will read the Real Time Clock and restore the thermal register to what it should be given the elapsed time.
· Learned Reset Capacity is a feature that is unique to the TX Series. By sampling the amount of thermal capacity used in the previous three successful starts, the TX Series will not allow a reset until a sufficient amount of thermal capacity has been regained in the motor. This prevents nuisance tripping and insures that unsuccessful start attempts (which would otherwise use up the starts-per-hour capacity of the motor) are not allowed.
TOSHIBA- 7
Page 14
TX Series 48 - 1250A
WARNING
Chapter 2 - Installation
2.1 Receiving and Unpacking
Upon receipt of the unit:
• Carefully unpack the unit and inspect it for any shipping damage. Report any damage immediately and file a claim with the freight carrier within 15 days of receipt.
• Verify that the model number on your unit matches your purchase order.
• Confirm that the ratings label on the unit matches or is greater than the motor’s HP and current rating.
2.2 Initial Unit Inspection
• Make a complete visual check of the unit for damage which may have occurred during shipping and handling. Do not attempt to continue installation or start up the unit if it is damaged.
• Check for loose mechanical assemblies or broken wires which may have occurred during transportation or handling. Loose electrical connections will increase resistance and cause the unit to function improperly.
• Prior to beginning the installation, verify that the motor and TX unit are rated for the proper amperage and voltage.
2.3 Location
The proper location of the unit is an important factor in achieving the unit’s specified performance and normal operation lifetime. The unit should always be installed in an area where the following conditions exist:
• Ambient Operating Temperature: 0° C to 50° C (32° F to 122° F) (Optional space heaters can be provided for operation in ambient temperature to -20° C.)
• Protected from rain and moisture.
• Humidity: 5% to 95% non-condensing.
• Free from metallic particles, conductive dust and corrosive gas.
• Free from excess vibration (below 0.5G)
• Open panel units must be mounted in the appropriate type of enclosure. Enclosure size and type must be suitable to dissipate heat generated by the soft starter. Contact factory for assistance in sizing the enclosure.
Do not service equipment with voltage applied! The unit can be the source of fatal electrical shocks! To avoid shock hazard, disconnect main power and control power before working on the unit. Warning labels must be attached to terminals, enclosure and control panel to meet local codes.
2.4 Mounting and Cleaning
When drilling or punching holes in the enclosure, cover the electrical assembly to prevent metal filings from becoming lodged in areas which can cause clearance reduction or actually short out electronics. After work is completed, thoroughly clean the area and reinspect the unit for foreign material. Make sure there is sufficient clearance (six inches) all around the unit for cooling, wiring and maintenance purposes. To maximize effective air flow and cooling, the unit must be installed with its heat sink ribs oriented vertically and running parallel to the mounting surface.
TOSHIBA - 8
Page 15
TX Series 48 - 1250A
Model
W ire
WARNING
Remove all sources of power before cleaning the unit!
In dirty or contaminated atmospheres the unit should be cleaned on a regular basis to ensure proper cooling. Do not use any chemicals to clean the unit. T o remove surface dust use 80 to 100 psi, clean, dry compressed air only . A three inch, high quality , dry paint brush is helpful to loosen up the dust prior to using compressed air on the unit.
2.5 Power Terminal Wire Range and Tightening Torque
kW
230V 400V
Ran ge
Torque
lbs/in
Model
Number
Max
Am p s
Max HP
208V 230V 480V 600V
TX005 TX006 TX007 TX008 TX009 TX010 TX011 TX012 TX013 TX014 TX015 TX016 TX017
48 10 15 30 40 11 22 #18 - #4 20
78 20 25 50 60 22 37 #14 - #2 50 120 30 40 75 100 30 55 180 50 60 125 150 55 90 220 60 75 150 200 110 288 75 100 200 250 75 132 414 125 150 300 350 200 476 - - 350 400 132 250 550 150 200 400 500 160 718 200 250 500 600 200 315
1006 300 350 700 800 400 1150 350 400 800 900 1250 450 500 1000 1125
Note: All wiring must be sized according to NEC standards
2.6 Dimensions
TX DIME NSIONS
Enclosure
PANEL
(OPEN
CHASSIS
TYPE)
Number
TX005 to TX007
TX008 TX009 to TX010 TX011 to TX013 TX014 to TX015 TX016 to TX017
Overall Dimensions Mounting Dimensions ABCDEF
16.5 10 10 15.9 9 0.28 20 20.1 12 18.5 17.5 0.44 27 20.1 11.2 25.5 17.5 0.44
29.5 20.1 11.5 25.5 17.5 0.44 45 33 12.8 43.3 31.3 0.44 33 33 15.2 31.2 31.2 0.44
#6 - 250 kc m il 3 25
(2) #6 - 600 kcm i l 375
(2) #2 - 600 kcm i l 375
(3) #2 - 600 kcm i l 375
(4) #2 - 600 kcm i l 375
B
F
C
D
E
TOSHIBA- 9
Page 16
TX Series 48 - 1250A
WARNING
2.7 Power Connections
Connect appropriate power lines to the unit input terminals marked L1, L2, L3. Avoid routing power wires near the control board. Connect the motor leads to the unit terminals marked T1, T2, T3. Refer to NEC standards for wire length and sizing. Never interchange input and output connections to the unit. This could cause excessive voltage in the control logic circuit and may damage the unit.
TX Series Unit
Never connect power factor correction capacitors on the load side of the unit. The SCRs will be seriously damaged if capacitors are located on the load side.
The unit must be tested with a motor or other test load connected to the load side of the unit. (A load bank can be used if a motor is not available). Note that line voltage will appear across the output terminals if there is no motor or load connected to the unit. In areas where lightning is a significant problem, station-type air gap lightning arrestors should be considered and utilized on the input power source.
2.7.1 Grounding
Connect the ground cable to the ground terminal as labeled on the unit. Refer to the National Electrical Code for the proper ground wire sizing and be sure that the ground connector is connected to earth ground.
2.8 Control Connections
Separate 120Vac supply is required (240Vac for 380V and 415V applications). The control voltage should be connected to pins 1 and 6 of TB4 on the power board. This control voltage must be customer supplied, unless an optional control power transformer (See chart) has been supplied with the unit.
Recommended Transformer Sizes
TX Model
Panel NEMA Type 1 NEMA Type 12/3R/4
TX008 50 VA 100 VA 250 VA* TX009 50 VA 100 VA 500 VA* TX010 250 VA 250 VA 500 VA*
TX011 to TX013 250 VA 250 VA 750 VA*
Power Connections
TB4
Control
Power
Source
Unit comes standard with 120Vac control. Order 240Vac control as an option if required.
Control
Power
Return
2.8.1 Three-Wire Connection
TX014 500 VA 500 VA 1 KVA*
TX015 to TX016 500 VA 750 VA 1.5 KVA*
TX017 500 VA 750 VA 1.5 KVA*
* Transformer size is adequate to power built-in bypass contactors on these models.
Recommended Transformer Sizes for Control Power
Note:
1. If power is used for additional accessory items (Lights, fans, etc.) contact factory for sizing.
For standard 3-wire control connect 120V ac (or 240Vac for 415V and 380V applications) to pins 1 and 6 of TB4. Connect N.C. (normally closed) stop button between pins 3 and 4 of TB4. Connect N.O. (normally open) start button between pins 4 and 5 of terminal block TB4.
TOSHIBA - 10
Three-Wire Connection
Page 17
TX Series 48 - 1250A
WARNING
2.8.2 Two-Wire Connection
An alternate connection for unattended operation replaces start/stop push buttons by connecting a maintained contact closure between pins 3 and 5 on TB4. When the maintained contact is used for start/stop it is necessary to set the overload setpoint to the manual reset position. This will prevent the motor from restarting if the thermal overload trips and then cools off.
Two-Wire Connection
When two-wire connection method is used, the start circuit must be interlocked to prevent automatic restart when either of the two protective devices (overload or thermostat) reset. Thermostats always automatically reset on cool down.
2.8.3 Programmable Relays/Relay Contacts
All the relay contacts are FORM C (Com, N.O., N.C.). Toshiba recommends fusing all contacts with external fuses. The TX has four programmable relays on TB3 on the power board. The relays are rated for 240Vac, 5 A and 1200 VA. These relays can respond to either a fault condition or an up-to-speed condition. In the TX all tripping functions have been assigned to the TRIP (AUX1) relay, and all alarm (warning) condition has been configured to the ALARM (AUX2) relay. AUX 3 is factory programmed for a SHUNT TRIP indication and can be connected to a shunt trip coil on an incoming circuit breaker or open an input isolation contactor. AUX4 is the AT SPEED contact. When the motor has reached the end of its acceleration ramp, the TX will wait until the AT SPEED programmed time delay has expired. Then, the relay will energize until a stop command has been received. The AT SPEED contact can be used to operate a bypass contactor (used for shorting the load current around the SCRs. To change AUX3 or AUX4 functions, see Setpoint Page 4.
Relay Contacts on Power Board
Rated 240Vac, 5A, 1200VA
TOSHIBA- 11
Page 18
TX Series 48 - 1250A
2.8.4 Power Board
2.8.4a Power Board Connections
TB4
Three-Wire Control Connection
TB4
Two-Wire Control Connection
Relay Contacts on Power Board
Rated 240Vac, 5A, 1200VA
TOSHIBA - 12
Page 19
TX Series 48 - 1250A
2.9 CPU Board Connections
There are eight digital inputs on the CPU board. Four of the inputs are user programmable. There are also two analog outputs, a tachometer feedback input.
20
20
TB1
Tach Input
1 2 43 5 6 7 8 9
Analog Output #1
4 - 20 mA
Analog Output #2
4 - 20 mA
Contact factory for remote
reset connections
Input
TB2
1 2 43 5 6 7 8
Program Enable
Factory wired. Do not change
TB3
External Input #1
1 2 43 5 6 7 8
External Input #2
Dual Ramp
Thermostat
-
+
+ -
+ -
+ -
Note: Install program jumper to enable setpoint programming. Jumper must be removed after programming or for prolonged storage to preserve settings.
TOSHIBA- 13
-
+
+-
+
­+-
Page 20
TX Series 48 - 1250A
2.10 Communications Board
Full (RS422) or half (RS485) duplex Modbus communications port is available at TB1 on the communications board. No field wiring connections are required for TB2.
(RS485)
Note: Remove for last unit in modbus string
2.10.1 Communication Board Connections
REAR
VIEW
(RS422)
TB1 TB2
RS485 Connections
(Customer Connections)
TOSHIBA - 14
RS422 Connections
(Factory Only)
Page 21
TX Series 48 - 1250A
2.1 1 Optional RTD Board
RTD1
Compensation
Signal
Power
RTD
Typical RTD
Installation
Shield
RTD2
RTD3
RTD4
RTD5
RTD6
RTD7
RTD8
RTD9
RTD10
RTD11
RTD12
TOSHIBA- 15
Page 22
TX Series 48 - 1250A
WARNING
Chapter 3 - Start-up
THE TX UNIT DEALS WITH POTENTIALLY LETHAL VOL T AGE LEVELS. YOU MUST BE CERT AIN THA T PERSONNEL ARE THOROUGHL Y TRAINED IN THE APPLICABLE SAFETY PRECAUTIONS BEFORE PROCEEDING WITH THIS SECTION!
3.1 Preliminary Start-Up Check List
Please make the following checks before applying power to the unit:
Supply voltage matches the rated supply voltage of the unit.
Horsepower and current ratings of the motor and unit match or the unit has a higher rating.
Initial ramp time and torque adjustments have been checked.
Power lines are attached to the unit input terminals marked L1, L2 and L3.
Motor leads are connected to the lower terminals marked T1, T2 and T3.
Appropriate control power is applied and/or control connections have been made.
The motor’s FLA has been programmed.
The thermal overload parameters are properly set.
The motor area and equipment are clear of people and parts before start-up.
3.2 Introduction
It is best to operate the motor at its full load starting condition to achieve the proper time, torque and ramp settings. Initial settings are set to accommo­date most motor conditions. TRY INITIAL SETTINGS FIRST. See Setpoints Page 2 to make any adjustments.
3.3 Acceleration Adjustments
The unit is set at the factory with typical starting characteristics that perform well in most applications. When the system is ready to start, try the initial unit settings. If the motor does not come up to speed, increase the current limit setting. If the motor does not start to turn as soon as desired, raise the starting voltage adjustment. Adjustment description and procedures are described as follows (See section 4.5.2 for additional Accel settings):
3.3.1 Starting Voltage
Factory Setting = 20% of line voltage Range = 0% - 100% of line voltage
Starting voltage adjustment changes the initial starting voltage level to the motor.
3.3.2 Ramp Time
Factory Setting = 10 sec. Range = 0 - 120 sec.
Ramp time adjustment changes the amount of time it takes to reach the current limit point or full voltage if the current limit point was not reached.
3.3.3 Current Limit
Factory Setting = 350% of unit FLA Range = 200% - 600% of unit FLA
The current limit adjustment is factory set for 350% of the unit’s rating. The range of adjustment is 200% to 600%. The main function of current limit is to cap the peak current. It may also be used to extend the ramp­ing time if required. The interaction between the voltage ramp and the current limit will allow the soft start to ramp the motor until the maximum current is reached and the current limit will hold the current at that level.
TOSHIBA - 16
Page 23
TX Series 48 - 1250A
The current limit must be set high enough to allow the motor to reach full speed. The factory setting of 350% is a good starting point. Do not set the current limit too low on variable starting
loads. This could cause the motor to stall and eventually cause the overload protection to trip.
3.4 Deceleration Adjustments (Pump Control)
Decel extends the stopping time on loads that would otherwise stop too quickly if allowed to coast to stop. Decel control provides smooth deceleration until the load comes to a stop. Three adjustments optimize the deceleration curve to meet the most demanding require­ments. Try factory settings before adjusting.
Deceleration Applications The unit is shipped from the factory with the decel feature disabled. Apply power and adjust the soft start before enabling or
modifying the deceleration adjustments. Both acceleration and deceleration adjustments should be made under normal load conditions.
The deceleration feature provides a slow decrease in the output voltage, accomplishing a gentle decrease in motor torque during the stopping mode. This is the OPPOSITE OF BRAKING in that it will take longer to come to a stop than if the starter were just turned off. The primary use of this function is to reduce the sudden changes in pressure that are associated with “Water Hammer” and slamming of check valves with centrifugal pumps. Decel control in pump applications is often referred to as Pump Control.
In a pump system, liquid is being pushed uphill. The force exerted by gravity on the column of liquid as it goes up hill is called the “Head Pressure” in the system. The pump is sized to provide enough Output Pressure to overcome the Head Pressure and move the fluid up the pipe. When the pump is turned off, the Output Pressure rapidly drops to zero and the Head Pressure takes over to send the fluid back down the hill. A “Check Valve” is used somewhere in the system to prevent this (if necessary) by only allowing the liquid to flow in one direction. The kinetic energy in that moving fluid is suddenly trapped when the valve slams closed. Since fluids can’t compress, that energy is transformed into a “Shock Wave” that travels through the piping system looking for an outlet in which it dissipates. The sound of that shock wave is referred to as “Water Hammer”. The energy in that shock wave can be extremely damaging to pipes, fittings, flanges, seals and mounting systems. By using the Soft Stop/Deceleration feature of the TX, the pump output torque is gradually and gently reduced, which slowly reduces the pressure in the pipe. When the Output Pressure is just slightly lower than the Head Pressure, the flow slowly reverses and closes the Check Valve. By this time there is very little energy left in the moving fluid and the Shock Wave is avoided. When the output voltage to the motor is low enough to no longer be needed, the TX will end the Decel cycle and turn itself off.
TOSHIBA- 17
Page 24
TX Series 48 - 1250A
WARNING
Another common application for decel control is on material handling convey­ors as a means to prevent sudden stops that may cause products to fall over or to bump into one another. In overhead crane applications, soft stopping of the Bridge or Trolley can prevent loads from beginning to over swing on sudden stops.
3.4.1 Start Deceleration Voltage
Factory Setting = 60% of line voltage Range = 0% - 100% of line voltage
The step down voltage adjustment eliminates the dead band in the deceleration mode that is experienced while the voltage drops to a level where the motor deceleration is responsive to decreased voltage. This feature allows for an instantaneous drop in voltage when deceleration is initiated.
3.4.2 Stop Deceleration Voltage
Factory Setting = 20% of line voltage Range = 0% - 100% of line voltage
The stop voltage level setpoint is where the deceleration voltage drops to zero.
3.4.3 Deceleration Time
Factory Setting = 5 sec. Range = 0 - 60 sec.
The deceleration ramp time adjusts the time it takes to reach the stop voltage level set point. The unit should be restarted and stopped to verify that the desired deceleration time has been achieved.
DO NOT EXCEED THE MOTOR MANUF ACTURER’S RECOMMENDED NUMBER OF ST ARTS PER HOUR. WHEN CALCULA TING THE NUMBER OF ST ARTS PER HOUR, A DECEL CURVE SHOULD BE COUNTED AS A START CUR VE. FOR EXAMPLE: RECOMMENDED NUMBER OF ST ARTS PER HOUR = 6, ALLOW ABLE ST ARTS WITH DECEL CYCLE PER HOUR = 3.
TOSHIBA - 18
Page 25
TX Series 48 - 1250A
3.5 Sequence of Normal Operation
Apply control power and check that the “Power” LED comes on. (Display 1)
Apply three phase power to the unit. The motor should run only when the start command is applied.
Apply the start command. (Display 2). The RUN LED will be lit. (Display 3) The AUX3 LEDs will be lit. If the motor does not enter run mode in the set time, a trip will occur.
The POWER, RUN, AUX3 LEDs will be lit, indicating that the contact has energized. IA, IB, IC will display the current setting for Phase A, Phase B, and Phase C and the G/F indicates ground fault. (Display 4)
When the motor reaches full speed, the “AUX4” LED (At Speed) will be lit.
If the motor decelerates, or stops, during the acceleration period, hit the stop button immediately and open the disconnect line. If the unit does not follow this operational sequence, please refer to the Troubleshooting Chapter.
It is best to operate the motor at its full load starting condition to achieve the proper time, torque and ramp settings. Initial settings are set to accommodate most motor conditions. TRY INITIAL SETTINGS FIRST. See Setpoint Page 2 to make any adjustments.
Initial Voltage
Soft Start Curve
Current Limit
Acceleration Time
MOTOR STOPPED
1.
READY TO START
MOTOR STARTING
2.
00 X FLA
OVERLOAD ALARM
3.
TIME TO TRIP: XXX SECS.
IA: _ _ _ IB: _ _ _
4.
IC: _ _ _ G/F: _ _ _
If decel is enabled, the following parameters for Deceleration Time, Start Decel Voltage (see SP2) and Stop Decel Voltage (see SP2) must also be pro­grammed.
TOSHIBA- 19
Page 26
TX Series 48 - 1250A
n
e
Chapter 4 - User Interface & Menu Navigation
This chapter explains the keypad operator interface, the LCD descriptions and the programming features
4.1 Keypad/Operator Interface
The TX Series user keypad/keypad operator interface consists of:
• 2 row by 20 characters Liquid Crystal Display (LCD)
• 12 LEDs
• 8 pushbuttons
Note: The TX Series is menu driven and there are three levels of programming. The programming for two of these levels is password protected. Level two requires a three digit password and level three requires a four digit password.
Button
MENU
RESET
ENTER
HELP
UP ARROW
RIGHT ARROW
DOWN ARROW
Toggle between the menu selection for metering and setpoint pages.
Will clear the trip indicator and release the trip relay.
In the edit mode, press the ENTER pushbutton so the unit will accept the new programming information. Whe not in the edit mode, the ENTER pushbutton will toggle through the event in dicator list (such as alarms or trips)
Provides general help information about a specific setpoint or action.
Will scroll up through the setpoint and metering menu page. It will scroll to the top of the setpoint page or a section. In edit mode it wil l increase a setpoint in an incremental step or toggle through the available options in the setpoint.
In the main menu the RIGHT ARROW button provides access to the setpoint page. For setpoint pages with multiple columns, the RIGHT ARROW will scroll the setpoint page to the right. When in edit mode it will shift one character to the right.
Will scroll down through the setpoint pages and down through the setpoints. In edit mode, it will decrement through values and toggle available options in the setpoint.
Keypad Operator Interface
Will move to the left through setpoint pages with multipl columns. When in edit mode it will become the backspace key and will shift one character to the left.
Indicates unit/motor is running Lights in conjunction with AUX 2 to indicate event or
warn of possible critical condition. Lights in conjunction with AUX 1 to indicate a critical
condition has occurred. Auxilary relays
LED
LEFT ARROW
Power Indicates control power is present
Run
Alarm
Trip
AUX 1-4
Note: The directional arrow buttons are sensitive. In edit mode, if the buttons
are held for a long period, the scrolling speed will increase.
TOSHIBA - 20
Page 27
TX Series 48 - 1250A
4.2 Menu Navigation
PAGE 1 BASIC CONFIGURATION
LEVEL 1
PAGE 2 STARTER CONFIGURATION
PAGE 3 PHASE & GROUND SETTINGS
PAGE 4 RELAY ASSIGNMENT
LEVEL 2
PAGE 5 RELAY CONFIGURATION
MENU
(1)
Notes:
1. The MENU keys allow you to toggle the screens between the Setpoint Menu and the Metering Menu. Simply use the arrow keys to get to the different screens within each menu. Example: To access Setpoint Page 3: PHASE & GROUND SETTINGS, press the MENU key once and the DOWN ARROW two times.
2. Levels 1, 2 and 3 indicate password protection levels for these setpoint pages.
LEVEL 3
PAGE 6 USER I/O CONFIGURATION
PAGE 7 CUSTOM ACCELERATION CURVE
PAGE 8 OVERLOAD CURVE CONFIGURATION
PAGE 9 RTD CONFIGURATION
PAGE 10 SECURITY SET PASSWORD
PAGE 11 COMMUNICATIONS
PAGE 12 SYSTEM SETPOINTS
FACTORY
LEVEL
PAGE 13 CALIBRATION & SERVICE
TOSHIBA- 21
Page 28
TX Series 48 - 1250A
4.2.1 Password Access
Screens in Level 1 of the setpoint menu can be changed without password access because they list basic motor information. Screens in Levels 2 and 3 require passwords because they provide more in-depth protection and control of the TX Series unit. The password in Levels 2 and 3 can be changed by the user.
NOTE: Setpoints can only be changed when the motor is in Stop/
Ready Mode! The TX will not allow a start if it is still in the Edit Mode. When the unit is in the Edit Mode, a “*” is in the top right corner of the display .
4.2.2 Changing Setpoints
Example 1: Changing Motor FLA
A. Press MENU button to display Setpoint Page 1, Basic Configuration B. Press the RIGHT ARROW you will view the screen Motor Full Load
Amps.
C. Press the ENTER button for edit mode. Note the asterisk (*) in the
top right corner of the LCD screen that indicates Edit Mode. D. To change the value, select the UP ARROW or DOWN ARROW. E . To accept the new value, press the ENTER button. The unit will
accept the changes and will leave the edit mode. Note the * is no
longer in the top right corner of the LCD Display.
MENU
PAGE 1 BASIC CONFIGURATION
MOTOR FULL LOAD AMPS : 140 AMPS
ENTER
2x
ENTER
MOTOR FULL LOAD AMP : 142 AMPS
MOTOR FULL LOAD AMP* : 142 AMPS
TOSHIBA - 22
Page 29
TX Series 48 - 1250A
50 - 100% of Unit Max Curr ent Rati ng (Model
Chapter 5 - Setpoint Programming
The TX Series has twelve programmable setpoint pages which define the motor data, ramp curves, protection, I/O configuration and communications. In Section 5.1, the setpoint pages are outlined in chart form. In Section 5.2 the setpoint pages are illustrated and defined for easy navigation and programming. Note: Setpoints can only be changed when the starter is in the Ready Mode. Also the soft start will not start when it is in programming mode.
5.1 Setpoints Page List
The following charts list each Setpoint Page and the programmable functions within that page. The applicable section of the manual is also referenced.
5.1.1 Basic Configuration (Setpoint Page 1)
Setpoint
Page
Security
Level
Description
Factory Setting
Default
Range Section
Motor Full Load Amps (FLA) Model dependent Service Factor 1.15 1.00 – 1.3 SP1.2
Overload Class 10 O/L Class 5-30 SP1.3
Page 1
Basic Configuration
Level 1
NEMA Design B A-F SP1.4 Insulation Class B A, B, C, E, F, H, K, N, S SP1.5 Line Voltage 480 208 to 600V SP1.6
No Passowrd Required
Line Frequency 60 50 or 60 HZ SP1.7
5.1.2 Starter Configuration (Setpoint Page 2)
Setpoint
Page
Page 2
Starter Configuration
Security
Level
Level 1
Description
Start Control Mode Start Ramp 1
Jog Voltage Off 5-75%, Off Start Ramp #1 Type Voltage Current, Voltage, Off Initial Voltage #1 20% 0-100% Ramp Time #1 10 sec 0-120 sec Current Limit #1 350% FLA 200-600 % Initial Current #1 200% FLA 0-300% Ramp Time #1 10 sec 0-120 sec Maximum Curre nt #1 350% FLA 200-600 % Start Ramp #2 Type Off Current, Voltage, Off Initial Voltage #2 60% 0-100 % Ramp Time #2 10 sec 0-120 sec Current Limit #2 350 % FLA 200-600 % Initial Current #2 200% FLA 0-600 % Ramp Time #2 10 sec 0-120 sec Maximum Curre nt #2 350% FLA 200-600 %
No Passowrd Required
Kick Start Type Off Voltage or Off Kick Start Voltage 65% 10-100 % Kick Start Time 0.50 sec 0.10-2.00 Deceleration Disabled Enabled or Disabled Start Deceleration Voltage 60% 0-100 % Stop Decel eration Voltage 30% 0-59 % Deceleration Time 5 sec 1-60 sec Timed Output Time Off 1-1000 sec, Off Run Delay Time 1 Sec 1-30 sec, Off At Speed Delay Time 1 Sec 1-30 sec, Off Bypass Pull-in Current 100% FLA 90 - 300%
Factory Setting
Default
and Service Factor dependent)
Range Section
Jog, Start Ramp 1, Start Ramp 2, Custom Accel Curve, Start Disabled, Dual Ramp
SP1.1
SP2.1
SP2.2
SP2.3
SP2.4
SP2.5
SP2.6
SP2.7 SP2.8 SP2.9
SP2.10
TOSHIBA- 23
Page 30
TX Series 48 - 1250A
Page
Level
Default
5.1.3 Phase and Ground Settings (Setpoint Page 3)
Setpoint
Page 3
Phase and Ground Settings
Security
Level 2
Password Protecti on
Description
Imbalance Alarm Level 15% FLA 5-30 %, Off Imbalance Alarm Delay 1.5 sec 1.0-20.0 sec Imbalance Trip Level 20% 5-30 %, Off Imbalance Trip Delay 2.0 sec 1.0-20.0 sec Undercurrent Alarm Level Off 10-90 %, Off Undercurrent Alarm Delay 2.0 sec 1.0-60.0 sec Overcurrent Alarm Leve l Off 100-300 %, Off Overcurrent Alarm Delay 2.0 sec 1.0-20.0 sec Overcurrent Trip Lev e l Off 100-300 %, Off Overcurrent Trip Delay 2.0 sec 1.0-20.0 sec Phase Loss Trip Disabled Enabled or Disabled Phase Loss Trip Delay 0.1 sec 0-20.0 sec Phase Rotation Detection Enabled Enabled Only Phase Rotation ABC ABC Ground Fault Alarm Level Off 5-90 %, Off Ground Fault Alarm Delay 0.1 sec 0.1-20.0 sec Ground Fault Loset Trip Level Off 5-90 %, Off Ground Fault Loset Tr ip Delay 0.5 sec 0.1-20 sec Ground Fault Hiset Trip Lev el Off 5-90 %, Off Ground Fault Hiset Trip Delay 0.008 sec 0.008-0.250 sec Overvoltage Alarm Level Off 5 -30%, Off Overvoltage Alarm Delay 1.0 sec 1.0-30.0 sec Overvoltage Trip Level Off 5-30%, Off Overvoltage Trip Delay 2.0 sec 1.0-30.0 sec Undervoltage Alarm Level Off 5-30%, Off Undervoltage Alarm Delay 1.0 sec 1.0-30.0 sec Undervoltage Trip Level Off 5-30%, Off Undervoltage Trip Delay 2.0 sec 1.0-30.0 sec Line Frequency Trip Window Disabled 0-6 Hz, Disabled Line Frequency Trip Delay 1.0 sec 1.0-20.0 sec P/F Lead P/F Alarm Off 0.1-1.00, Off P/F Lead Alarm Delay 1.0 sec 1-120 sec P/F Lead P/F Trip Off .01-1.00, Off P/F Lead Trip Delay 1.0 sec 1-120 sec P/F Lag P/F Alarm Off .01-1.00, Off P/F Lag Alarm Delay 1.0 sec 1-120 sec P/F Lag P/F Trip Off .01-1.00, Off P/F Lag Trip Delay 1.0 sec 1-120 sec Power Demand Period 10 min 1 - 60 min KW Demand Alarm Pickup Off KW Off, 1-100000 KVA Demand Alarm Pickup Off KVA Off, 1-100000 KVAR Demand Alarm Pickup Off KVAR Off, 1-100000 Amps Demand Alarm Pickup Off Amps Off, 1-100000
Factory Setting
Range Section
SP3.1
SP3.2
SP3.3
SP3.4
SP3.5
SP3.6
SP3.7
SP3.8
SP3.9
SP3.10
SP3.11
SP3.12
SP3.13
SP3.14
SP3.15
SP3.16
SP3.17
SP3.18
SP3.19
SP3.20
TOSHIBA - 24
Page 31
TX Series 48 - 1250A
5.1.4 Relay Assignments (Setpoint Page 4)
Setpoint
Page
Page 4
Security
Level
O/L Trip Trip Only None None I/B Trip Trip None None S/C Trip Trip Only None None Overcurrent Trip Trip None None Stator RTD Trip Trip None None Non-stator RTD Trip Trip None None G/F Hi Set Trip Trip None None G/F Lo Set Trip Trip None None Phase Loss Trip Trip None None Accel. Time Trip Trip Only None None Start Curve Trip Trip Only None None Over Frequency Trip Trip None None Under Frequency Trip Trip None None I*I*T Start Curve Trip None None Learned Start Curve Trip None None Phase Reversal Trip None None Overvoltage Trip Trip None None Undervoltage Trip Trip None None Power Factor Trip Trip None None Tach Accel Trip Trip None None Inhibits Trip Trip None None Shunt Trip AUX3 None None Bypass Discrepancy None None None External Input #1 None None None
Level 2
Relay Assignments
External Input #2 None None None Dual Ramp None None None Thermostat Trip None None
Password Protecti on
O/L Warning Alarm None None Overcurrent Alarm Alarm None None Ground Fault Alarm Alarm None None Under Current Alarm Alarm None None Motor Running None None None I/B Alarm Alarm None None Stator RTD Alarm Alarm None None Non-Stator RTD Alarm Alarm None None RTD Failure Alarm Alarm None None Self Test Fail Trip None None Thermal Register Alarm None None U/V Alarm Alarm None None O/V Alarm Alarm None None Power Factor Al arm Alarm None None KW Demand Alarm Alarm None None KVA Demand Alarm Alarm None None KVAR Demand Alarm Alarm None None Amps Demand Alarm Alarm None None Timed Output None None None Run Delay Time None None None At Speed AUX4 None None
Description
Factory Setting
1st 2nd 3rd
Range Section
None Trip(AUX1) Alarm(AUX2) AUX3 AUX4
SP4.1
TOSHIBA- 25
Page 32
TX Series 48 - 1250A
5.1.5 Relay Configuration (Setpoint Page 5)
Setpoint
Page
Page 5
Relay Configuration
Security
Level
Level 2
Password Protection
Description
Trip (AUX1) Fail-Safe No Yes or No SP5.1 Trip (AUX1) Relay Latched Yes Yes or No SP5.2 Alarm (AUX2) Fail-Safe No Yes or No SP5.1 Alarm (AUX2) Relay Latched No Yes or No SP5.2 AUX3 Relay Fail-Safe No Yes or No SP5.1 AUX3 Relay Latched No Yes or No SP5.2 AUX4 Relay Fail-Safe No Yes or No SP5.1 AUX4 Relay Latched No Yes or No SP5.2
Factory Setting
Default
Range Section
TOSHIBA - 26
Page 33
TX Series 48 - 1250A
Off, RPM 0-3600, Hottest Non-Stator RTD 0-
5.1.6 User I/O Configuration (Setpoint Page 6)
Setpoint
Page
Page 6
User I/O Configuration
Security
Level
Lavel 2
Description
Tachometer Scale Selection Disabled Enabled or Disabled Manual Tach Scale 4.0 mA: 0 RPM 0 - 3600 Manual Tach Scale 20.0 mA: 2000 RPM 0 - 3600 Tach Accel Trip Mode Select Disabled Underspeed, Overspeed or Disabled Tach Ramp Time 20 sec 1 - 120 Tach Underspeed Trip PT 1650 RPM 0-3600 Tach Overspeed Trip PT 1850 RPM 0 - 3600 Tach Accel Trip Delay 1 sec 1 - 60
Analog Output #1 RMS Current
Analog Output #1 4mA: 0 0-65535 Analog Output #1 20mA: 250 0-65535 Analog Output #2 % Motor Load Same As Analog Input #1 Analog Output #2 4mA: 0 0-1000% Analog Output #2 20mA: 1000 0-1000% User Programmable External
Inputs External Input #1 Disabled Enabled or Disabled
Passowrd Protect i on
Name Ext. Input #1 User Defined, up to 15 Characters External Input #1 NO Normally Open or Closed External Input #1 0 sec 0-60 sec External Input #2 Disabled Enabled or Disabled Name Ext. Input #2 User Defined, up to 15 Characters External Input #2 Type NO Normally Open or Closed External Input #2 Time Delay 0 sec 0-60 sec Dual Ramp Dual Ramp Enabled or Disabled or Dual Ramp Name Ext. Input #3 Dual Ramp User Defined, up to 15 Characters Dual Ramp Type NO Normally Open or Closed Dual Ramp Time Delay 0 sec 0-60 sec Thermostat E nabled Enabled or Disabled Name Ext. Input #4 Thermostat User Defined, up to 15 Characters Thermostat Type NC Normally Open or Closed Thermostat Time Delay 1 sec 0-60 sec
Factory Setting
Default
Range Section
200°C, Hottest Stator RTD 0 - 200°C, RMS Current 0 - 7500 A, % Motor Load 0 - 600%, kw 0 - 30000kw.
SP6.1
SP6.2
SP6.3
SP6.4
SP6.5
TOSHIBA- 27
Page 34
TX Series 48 - 1250A
5.1.7 Custom Acceleration Curve (Setpoint Page 7)
Setpoint
Page
Page 7
Custom Acceleration Curve
Security
Level
Level 3
Password Protecti on
Description
Custom Accel Curve Disabled Disabled, Curve A, B, or C Custom Curve A Curve A Voltage Level 1 25% 0-100% Curve A Ramp Time 1 2 sec 1-60 sec Curve A Voltage Level 2 30% 0-100% Curve A Ramp Time 2 2 sec 1-60 sec Curve A Voltage Level 3 37% 0-100% Curve A Ramp Time 3 2 sec 1-60 sec Curve A Voltage Level 4 45% 0-100% Curve A Ramp Time 4 2 sec 1-60 sec Curve A Voltage Level 5 55% 0-100% Curve A Ramp Time 5 2 sec 1-60 sec Curve A Voltage Level 6 67% 0-100% Curve A Ramp Time 6 2 sec 1-60 sec Curve A Voltage Level 7 82% 0-100% Curve A Ramp Time 7 2 sec 1-60 sec Curve A Voltage Level 8 100% 0-100% Curve A Ramp Time 8 2 sec 1-60 sec Curve A Current Limit 350% FLA 200-600%
Custom Curve B
Custom Curve C
Factory Setting
Default
Range Section
Same Programmable Data Points and Ranges as Custom Curve A
Same Programmable Data Points and Ranges as Custom Curve A
SP7.1
5.1.8 Overload Curve Configuration (Setpoint Page 8)
Setpoint
Page
Page 8
Overload Curve Configuration
Security
Level
Level 3
Password Protecti on
Description
Basic Run Overload Curve Run Curve Locked Rotor Time O/L Class 1-30 sec, O/L Class Run Locked Rotor Current 600% FLA 400-800% Coast Down Timer Disabled 1-60 Min, Disabled Basic Start Overload Curve Start Curve Locked Rotor Time O/L Class 1-30 sec, O/L Class Start Locked Rotor Current 600% FLA 400-800% Accelera tion Time Limit 30 sec 1-300 sec, Disabled Number of Starts Per Hour Disabled 1-6, Disabled Time Between Start s Ti me Disabled 1-6 0 Mi n, D isab le d Area Under Curve Protection Disabled Enabled or Disabled Max I*I*T Start 368 FLA 1-2500 FLA*FLA*sec Current Over Curve Disabled Disabled, Learn, Enabled Learned Start Curve Bias 10% 5-40% Time for Sampling 30 sec 1-300 sec
Factory Setting
Default
Range Section
SP8.1
SP8.2
SP8.3
SP8.4
TOSHIBA - 28
Page 35
TX Series 48 - 1250A
5.1.9 RTD Option Configuration (Setpoint Page 9)
Setpoint
Page
Page 9
RTD Configuration
Security
Level
Level 3
Description
Use NEMA Temp for RTD Values Disabled Enabled or Disabled SP9.1 # of RTD Used for Stator 4 0-6 SP9.2
RTD Voting Disabled Enabled or Disabled SP9.3
Stator Phase A1 Type Off
RTD #1 Description S tator A1 User defined, Up to 15 Characters Stator Phase A1 Alarm Level Off 0-240C (32-464F), Off Stator Phase A1 Trip Level Off 0-240C (32-464F), Off Stator Phase A2 Type Off Same as Stator Phase A1 RTD #2 Description S tator A2 User defined, Up to 15 Characters Stator Phase A2 Alarm Off 0-240C (32-464F), Off Stator Phase A2 Trip Level Off 0-240C (32-464F), Off Stator Phase B1 Type Off Same as Stator Phase A1 RTD #3 Description S tator B1 User defined, Up to 15 Characters Stator Phase B1 Alarm Level Off 0-240C (32-464F), Off Stator Phase B1 Trip Level Off 0-240C (32-464F), Off Stator Phase B2 Type Off Same as Stator Phase A1 RTD #4 Description S tator B2 User defined, Up to 15 Characters Stator Phase B2 Alarm Level Off 0-240C (32-464F), Off Stator Phase B2 Trip Level Off 0-240C (32-464F), Off Stator Phase C1 Type Off Same as Stator Phase A1 RTD #5 Description Stator C1 User defined, Up to 15 Characters
Password Protecti on
Stator Phase C1 Alarm Level Off 0-240C (32-464F), Off Stator Phase C1 Trip Level Off 0-240C (32-464F), Off Stator Phase C2 Type Off Same as Stator Phase A1 RTD #6 Description Stator C2 User defined, Up to 15 Characters Stator Phase C2 Alarm Level Off 0-240C (32-464F), Off Stator Phase C2 Trip Level Off 0-240C (32-464F), Off End Bearing Type Off Same as Stator A1 RTD #7 Description End Bearing User defined, Up to 15 Characters End Bearing Alarm Level Off 0-240C (32-464F), Off End Bearing Trip Level Off 0-240C (32-464F), Off Shaft Bearing Type Off Same as Stator Phase A1 RTD #8 Description Shaft Bearing User defined, Up to 15 Characters Shaft Bearing Alarm Level Off 0-240C (32-464F), Off Shaft Bearing Trip Level Off 0-240C (32-464F), Off RTD #9 Type Off Same as Stator Phase A1 RTD #9 Description User defined User defined, Up to 15 Characters RTD #9 Alarm Level Off 0-240C (32-464F), Off RTD #9 Trip Level Off 0-240C (32-464F), Off
Factory Setting
Default
Range Section
120 OHM NI, 100 OHM NI, 100 OHM PT, 10 OHM CU
SP9.4
TOSHIBA- 29
Page 36
TX Series 48 - 1250A
5.1.9 RTD Option Configuration Page 9 Cont’d
Setpoint
Page
Page 9
5.1.10 Security Set Password Page 10
Setpoint
Page
Page
RTD Configuration
10
Security
Level
Level 3
Password Protection
Security
Level
3
Level
Description
RTD #10 Type Off Same as Stator Phase A1 RTD #10 Description User defined User defined, Up to 15 Characters RTD #10 Alarm Level Off 0-240C (32-464F), Off RTD #10 Trip Level Off 0-240C (32-464F), Off RTD #11 Type Off Same as Stator Phase A1 RTD #11 Description User defined User defined, Up to 15 Characters RTD #11 Alarm Level Off 0-240C (32-464F), Off RTD #11 Trip Level Off 0-240C (32-464F), Off RTD #12 Type Off Same as Stator Phase A1 RTD #12 Description User defined User defined, Up to 15 Characters RTD #12 Alarm Level Off 0-240C (32-464F), Off RTD #12 Trip Level Off 0-240C (32-464F), Off
Description
Set Level 2 Password 100 000 – 999 Three Digits SP10.1 Set Level 3 Password 1000 0000 – 9999 Four Digits SP10.2
Factory Setting
Default
Factory Setting
Default
Range Section
Range Section
SP9.4
5.1.1 1 Communications Page 1 1
Setpoint
Page
Page 11
Communiications
Security
Level
Level 3
Password Protection
Description
Set Front Baud Rate 9.6 KB/sec 2.4, 4.8, 9.6, 19.2, 38.4 KB/sec SP11.1 Set Modbus Baud Rate 9.6 KB/sec 2.4, 4.8, 9.6, 19.2, 38.4 KB/sec SP11.2 Modbus Address Number 247 1 – 247 SP11.3 Set Access Code 1 1 – 999 SP11.4 Set Link Baud Rate 38.4 KB/sec 2.4, 4.8, 9.6, 19.2, 38.4 KB/sec SP11.5
Remote Start/Stop Disabled Enabled or Disabled SP11.6
Factory Setting
Default
Range Section
TOSHIBA - 30
Page 37
TX Series 48 - 1250A
Model #
5.1.12 System (Setpoint Page 12)
Setpoint
Page
Page 12
Security
Level
Default Display Screen Metering Data Page # 1 Enter Metering Page (1-4)
Metering Data Screen # 1
Alarms RTD Failure Alarm Disabled Enabled or Disabled Thermal Regi ster Alarm 90% Off, 40-95% Thermal Alarm Delay 10 sec 1-20 sec Thermal Register Setup Info Cold Stall Time O/L Class O/L Class (5-30) or 4-40 second time delay Hot Stall Time ½ O/L Class ½ O/L Class, 4-40 sec
Level 3
Stopped Cool Down Time 30 Min 10-300 Min
System Setpoints
Runing Cool Down Time 15 Min 10-300 Min
Password Protecti on
Relay Measured Cool Rates Disabled Enabled or Disabled Thermal Regis ter Minimum 15% 10-5 0% Motor Design Ambient Temp 40C 10-90C
Description
Factory Setting
Default
Range Section
Enter Metering Screen Page 1(1-10) Page 2 (1-11) Page 3 (1 - 29) Page 4 (1 - 6)
SP12.1
SP12.2
SP12.3
Motor Design Run Temperature 80% Max 50-100% of Motor Stator Max Temp
Motor Stator Max Temp INS CLS INS CLS, 10-240 C I/B Input to Thermal Register Enabled Enabled Only Use Calculated K or Assign 7 1-50, On
Press Enter to Clr Thermal Register SP12.4
5.1.13 Calibration and Service (Setpoint Page 13)
Setpoint
Page
Page 13
Calibration & Service
Security
Level
FACTORY USE ONLY
Description
Set Date and Time (DDMMYY:HHMM)
Enter Date (DDMMYYYY)
Enter Time (HH:MM)
Firmware REV. # Press Ent er to Access Fac tory
Settings
FACTORY SET; ##/##/## ##:##
FACTORY SET; ##/##/####
FACTORY SET; ##:##
FACTORY SET; ###### ######
Factory Setting
Default
Range Section
D=1-31, M=1-12, Y=1970-2069
H=00-23, M=0-59
Display Only, Cannot be changed SP13.2
Available to Qualified Factory Personnel SP13.3
SP13.1
TOSHIBA- 31
Page 38
TX Series 48 - 1250A
5.2 Setpoint Menu
PAGE 1 BASIC CONFIGURATION
LEVEL 1
PAGE 2 STARTER CONFIGURATION
PAGE 3 PHASE & GROUND SETTINGS
PAGE 4 RELAY ASSIGNMENT
LEVEL 2
PAGE 5 RELAY CONFIGURATION
MENU
(1)
Note:
1. Push MENU key to toggle the screens between Setpoint Menu and Metering Menu.
2. Follow the arrow keys to get to different screens. Example: For Page 3 PHASE & GROUND SETTINGS, press the MENU key and the DOWN ARROW two times.
LEVEL 3
PAGE 6 USER I/O CONFIGURATION
PAGE 7 CUSTOM ACCELERATION CURVE
PAGE 8 OVERLOAD CURVE CONFIGURATION
PAGE 9 RTD CONFIGURATION
PAGE 10 SECURITY SET PASSWORD
PAGE 11 COMMUNICATIONS
PAGE 12 SYSTEM SETPOINTS
FACTORY
LEVEL
PAGE 13 CALIBRATION & SERVICE
TOSHIBA - 32
Page 39
TX Series 48 - 1250A
SP.1 Basic Configuration (Setpoint Page 1)
In Setpoint Page 1, the TX is looking for the following basic nameplate data of the motor.
SP1.1 Motor Full Load Amps: Allows the user to enter the
motor’s FLA rating. Range of adjustment is 50 - 100% (less programmed service factor).
SP1.2 Service Factor: Sets the pickup point on the overload
curve as defined by the programmed motor full load current. Ex: If the motor FLA is 100 and the service factor is 1.15, the TX overload pickup point will be 115 Amps.
SP1.3 Overload Class: Choose the motor protection overload
class, range from 5-30. Ex: Overload Class 10 will trip in 10 seconds at six times FLA.
MENU
PAGE 1 BASIC CONFIGURATION
MOTOR FULL LOAD AMPS : 200 AMPS
Range: 50 - 100% of Unit
MAX CURRENT AMPS Increments of 1
SERVICE FACTOR : 1.15 X FLA
Range: 1.00 - 1.3
Increments of 0.01
OVERLOAD CLASS: 10
Range: 5 - 30
Increments of 5
NEMA DESIGN: B
Range: A - F
INSULATION CLASS: B
Range: A - S
LINE VOLTAGE INPUT: 480 VOLTS
Range: 208 - 600
SP1.4 NEMA design: The motor design maximum allowed slip (Select from
Class A through F).
SP1.5 Insulation Class: The motor insulation temperature class (Select A,
B, C, E, F, H, K, N or S).
SP1.6 Line Voltage Inut: Applied system nominal voltage.
LINE FREQUENCY HZ: 60
Range: 50 or 60
SP1.7 Line Frequency: The user may choose either 50 Hz or 60 Hz.
TOSHIBA- 33
Page 40
TX Series 48 - 1250A
SP.2 Starter Configuration (Setpoint Page 2)
MENU
(Hit DOWN ARROW one time)
PAGE 2 STARTER CONFIGURATION
START CONTROL MODE : START RAMP 1
JOG, START RAMP 1, START RAMP 2, DUAL RAMP, CUSTOM ACCEL CURVE,START DISABLED
JOG VOLTAGE : OFF
Range: 5 - 75% or Off
Increments 5
START RAMP #1 TYPE : VOLTAGE
Options: Voltage, Current
or Off
START RAMP #2 TYPE : OFF
Options: Voltage, Current
or Off
If
VOLTAGE
selected
these
screens
will appear.
If
VO LTAGE
selected
these
screens
will appear.
INITIAL VOLTAGE #1: 20%
Range: 0 - 100%
Increments of 1
RAMP TIME #1: 10 SEC.
Range: 0 - 120 SEC.
Increments of 1
CURRENT LIMIT #1: 350% FLA
Range: 200 - 600%
Increments of 10
INITIAL VOLTAGE #2: 60%
Range: 0 - 100%
Increments of 1
RAMP TIME #2: 10 SEC.
Range: 0 - 120 SEC.
Increments of 1
If
CURRENT
selected
these
screens
will appear.
If
CURRENT
selected
these
screens
will appear.
INITIAL CURRENT #1: 200% FLA
Range: 0 - 300%
Increments of 1
RAMP TIME #1: 10 SEC.
Range: 0 - 120 SEC
Increments of 1
MAXIMUM CURRENT #1: 350% FLA
Range: 200-600%
Increments of 10
INITIAL CURRENT #2: 200% FLA
Range: 0 - 300%
Increments of 1
RAMP TIME #2: 10 SEC.
Range: 0 - 120 SEC
Increments of 1
KICK START TYPE: OFF
Range: Voltage or Off
DECELERATION : DISABLED
Range: Enabled or Disabled
TIMED OUTPUT TIME: OFF
Range: 1 - 1000 sec, OFF
Increments of 1
RUN DELAY TIME: 1 SEC.
Range: 0 - 30 sec, OFF
Increments of 1
AT SPEED DELAY TIME: 1 SEC.
Range: 0 - 30 sec, OFF
Increments of 1
BYPASS PULL-IN CURRENT: 100% FLA
Range: 90 - 300%
Increments of 1
TOSHIBA - 34
CURRENT LIMIT #2: 350% FLA
Range: 200 - 600%
Increments of 10
KICK START VOLTAGE : 65%
Range: 10 - 100%
Increments of 5
KICK START TIME : 0.50 SEC.
Range: 0.10 - 2.00
Increments of 0.10
START DECELERATION VOLTAGE: 60%
Range: 0 - 100%
Increments of 1
STOP DECELERATION VOLTAGE: 30%
Range: 0 - 59%
Increments of 1
DECELERATION TIME: 5 SEC.
Range: 1 - 60
Increments of 1
MAXIMUM CURRENT #2: 350% FLA
Range: 200-600%
Increments of 10
Page 41
TX Series 48 - 1250A
SP.2 Starter Configuration (Setpoint Page 2)
Provides multiple choices for starting ramps that can be selected for particular loads and applications.
SP2.1 Start Control Mode: Dual Ramp, Custom
Accel Curve, Tach Ramp, Jog Voltage, Start Ramp 1, Start Ramp 2.
• Dual Ramp: The dual ramp mode works in conjunction with External Input #3. This allows the user to switch between the two start ramps without having to reconfigure the start mode. (For details on configuring External Input #3 for DUAL RAMP see Setpoint Page 6.)
• Custom Accel Curve: Allows the user to custom design the acceleration start curve to the application. (See setpoint page 7 for configuration setup.) Note: If Custom Accel Curve has not been enabled in setpoint page 7, the TX will ignore the start control mode and read this setpoint as disabled.
• Tach Ramp: See setpoint page 6 for configuration setup of tachometer input. (Pending)
SP2.2 Jog Voltage: The voltage level necessary to
cause the motor to slowly rotate.
SP2.3 Start Ramp 1 Type: The ramp type can be
setup for either Voltage or Current. If Voltage is selected, initial voltage, ramp time and current limit are adjustable. If Current is selected, initial current, ramp time and maximum current are adjustable.
Start Ramp 1 Type: Voltage
• Voltage Ramping is the
most reliable starting method, because the starter will eventually reach an output voltage high enough to draw full current and develop full torque. This method is useful for applications where the load conditions change frequently and where different levels of torque are required. Typical applications include material handling conveyors, positive displacement pumps and drum mixers. Voltage is increased from a starting point (Initial Torque) to full voltage over an adjustable period of time (Ramp Time). To achieve Voltage Ramping, select VOLTAGE for the START RAMP #1 TYPE setpoint and set CURRENT LIMIT #1 setpoint to 600% (the maximum setting). Since
this is essentially Locked Rotor Current on most motors, there is little or no Current Limit effect on the Ramp profile.
Voltage Ramping with Current Limit is the most used curve and is similar to voltage ramping. However, it adds an adjustable maximum current output. Voltage is increased gradually until the setting of the Maximum Current Limit setpoint is reached. The voltage is held at this level until the motor accelerates to full speed. This may be necessary in applications where the electrical power is limited. Typical applications include portable or emergency generator supplies, utility power near the end of a transmission line and utility starting power demand restrictions. Note: Using Current Limit will override the Ramp Time setting if necessary, so use this feature when acceleration time is not critical. To achieve Voltage Ramping with Current Limit, select VOLTAGE for the START RAMP #1 setpoint and set CURRENT LIMIT #1 setpoint to a desired lower setting, as determined by your application requirements.
Start Ramp 1 Type: Current Current Ramping (Closed Loop Torque
Ramping) is used for smooth linear acceleration of output torque. Output voltage is constantly updated to provide the linear current ramp, and therefore the available torque is maximized at any given speed. This is for applications where rapid changes in torque may result in load damage or equipment changes. Typical applications include overland conveyors if belt stretching occurs; fans and mixers if blade warping is a problem; and material handling systems if stacked products fall over or break.
This feature can be used with or without the
Maximum Current Limit setting. To achieve Current Ramping select CURRENT for START RAMP #1 TYPE setpoint and the MAXIMUM CURRENT #1 setpoint to the desired level.
Current Limit Only: (Current Step) start uses the Current Limit feature exclusively. This method of starting eliminates the soft start voltage/current ramp and instead, maximizes the effective application of motor torque within the limits of the motor. In this mode, setpoint RAMP TIME #1 is set to zero (0), so the output current jumps to the current limit setting immediately. Typically used in with a limited power supply, when starting a difficult load such as a centrifuge or deep well pump, when the motor capacity is barely adequate (stall condition or overloading occurs) or if other starting modes fail. Since ramp times are set to zero (0). START RAMP #1 TYPE is set to
TOSHIBA- 35
Page 42
TX Series 48 - 1250A
either VOLTAGE or CURRENT.
• Initial Torque (Initial Voltage #1 or Initial Current #1): Sets the initial start point of either
the Voltage Ramp or the Current Ramp. Every load requires some amount of torque to start from a standstill. It is inefficient to begin ramping the motor from zero every time, since between zero and the WK2 break-away torque level, no work is being performed. The initial torque level should be set to provide enough torque to start rotating the motor shaft, enabling a soft start and preventing torque shock damage. Setting this start point too high will not damage the starter, but may reduce or eliminate the soft start effect.
• Ramp Time #1: Sets the maximum allowable time for ramping the initial voltage or current (torque) setting to either of the following:
1) the Current Limit setting when the motor is still accelerating, or
2) full output voltage if the Current Limit is set to maximum. Increasing the ramp time softens the start process by gradually increasing the voltage or current. Ideally, the ramp time should be set for the longest amount of time the application will allow (without stalling the motor). Some applications require a short ramp time due to the mechanics of the system. (i.e., centrifugal pumps, because pump problems can occur due to insufficient torque).
SP2.4 Start Ramp 2: The same options and screen
setups as Start Ramp 1. Note: CUSTOM ACCEL CURVE overrides the voltage or current start in Ramps 1 and 2 when selected to be the start control mode.
SP2.5 Kick Start: Used as an initial energy burst in
applications with high friction loads.
• Kick Start Voltage: The initial voltage (as a percent of full voltage value) that is needed to start the motor (i.e. Breakaway or Initial Torque).
Kick Start Time: The time the initial torque boost is applied.
SP2.6 Deceleration: Allows the motor to gradually
come to a soft stop.
• Start Deceleration Voltage: The first part of the deceleration ramp. The TX initially drops to this voltage level upon receiving a STOP command. (Represented as a percent of voltage value.)
• Stop Deceleration Voltage: The drop-off point of the deceleration ramp. (Percent of voltage value.)
• Deceleration Time: Decel ramp time.
• Current Limit: Sets the maximum motor
current the starter will allow during Ramping. As the motor begins to ramp, the Current Limit feature sets a ceiling at which the current draw is held. Current Limit remains in effect until the following occurs:
1) the motor reaches full speed (detected by the At-Speed detection circuit) or
2) the Overload Protection trips on Motor Thermal Overload. Once the motor reaches full speed, the Current Limit feature becomes inactive.
In the Voltage Ramp Profile, the voltage output is increased until it reaches the Current Limit. Ramp time is the maximum amount of time it takes for the voltage to increase until the Current Limit setting takes over. With some load conditions, the Current Limit is reached before the Ramp Time expires.
The Current Ramp profile varies the output voltage to provide a linear increase in current up to the Maximum Current setpoint value. A closed loop feedback of motor current maintains the Current Ramp profile.
SP2.7 Timed Output: Used with an AUX relay. When
enabled, and upon a start command, it energizes the assigned relay for the programmed time. At the end of the programmed time the relay de­energizes. See Setpoint Page 4.
SP2.8 Run Delay Time: Used with an AUX3 relay.
When enabled, and upon a start command, it waits until the programmed time has expired. The relay energizes and remains so until a stop command is received. It de-energizes upon receiving a stop command. See Setpoint Page
4.
SP2.9 At Speed Delay Time: Used with an AUX4 relay,
it waits until after the motor reaches the end of ramp and the programmed delay time has expired. The relay energizes until a stop command has been received. See Setpoint Page
4.
TOSHIBA - 36
Page 43
TX Series 48 - 1250A
MENU
(Hit DOWN ARROW two times)
PAGE 3 PHASE & GROUND SETTINGS
SP.3 Phase & Ground Settings (Setpoint Page 3)
(Security Level: 2)
Note: Proper phase sequence must be observed when
connecting the input power. For example, phase A must lead phase B, which in turn must lead phase C by 120° respectively. If the phase rotation is not correct, a fault light and the LCD display will indicate the problem.
SP3.1 Imbalance Alarm Level: This is an advance
warning of a phase imbalance problem. The problem may not be a fault in the motor, but merely caused by imbalanced voltages.
• Imbalance Alarm Delay: The amount of time the imbalance condition must exist before an alarm occurs.
SP3.2 Imbalance Trip Level: This will trip the motor on
excessive phase imbalance. The trip level should be programmed to a higher value than the alarm level.
IMBALANCE ALARM LEVEL: 15% FLA
Range: 5 - 30%, OFF
Increments of 1
IMBALANCE TRIP LEVEL: 20%FLA
Range: 5 - 30%, OFF
Increments of 1
UNDERCURRENT ALARM LEVEL: OFF
Range: 10 - 90%, OFF
Increments of 1
OVERCURRENT ALARM LEVEL: OFF
Range: 100 - 300%, OFF
Increments of 1
OVERCURRENT TRIP LEVEL: OFF
Range: 100 - 300%, OFF
Increments of 1
PHASE LOSS TRIP : DISABLED
Options: Enabled or Disabled
PHASE ROTATION DETECTION: DISABLED
Options: Enabled or Disabled Options: ABC, ACB
IMBALANCE ALARM DELAY: 1.5 SEC.
Range: 1.0 - 20.0 SEC.
Increments of 0.1
IMBALANCE TRIP DELAY: 2.0 SEC.
Range: 1.0 - 20.0 SEC.
Increments of 0.1
UNDERCURRENT ALARM DELAY: 2.0 SEC.
Range: 1.0 - 60.0 SEC.
Increments of 0.1
OVERCURRENT ALARM DELAY: 2.0 SEC.
Range: 1.0 - 20.0 SEC., OFF
Increments of 0.1
OVERCURRENT TRIP DELAY: 2.0 SEC.
Range: 1.0 - 20.0 SEC.
Increments of 0.1
PHASE LOSS TRIP DELAY: 0.1 SEC.
Range: 0 - 20.0 SEC.
Increments of 0.1
PHASE ROTATION : ABC
• Imbalance Trip Delay: The amount of time the imbalance condition must exist before a trip will occur.
SP3.3 Undercurrent Alarm Level: Typically used to
warn of possible load loss, a coupling breaking or other mechanical problems.
• Undercurrent Alarm Delay: The amount of time the undercurrent condition must exist before an alarm will occur.
SP3.4 Overcurrent Alarm Level: Typically used to
indicate when the motor is overloaded. This feature can be used to either stop the feed to the equipment or warn operators of an overload condition.
• Overcurrent Alarm Delay: The amount of time the overcurrent condition must exist before an alarm will occur.
GROUND FAULT ALARM LEVEL: OFF
Range: 5 - 90%, OFF
Increments of 1
GROUND FAULT LOSET TRIP LEVEL: OFF
Range: 5 - 90%, OFF
Increments of 1
GROUND FAULT HISET TRIP LEVEL: OFF
Range: 5 - 90%, OFF
Increments of 1
OVERVOLTAGE ALARM LEVEL: OFF
Range: 5 - 30%, OFF
Increments of 1
OVERVOLTAGE TRIP LEVEL: OFF
Range: 5 - 30%, OFF
Increments of 1
UNDERVOLTAGE ALARM LEVEL: OFF
Range: 5 - 30%, OFF
Increments of 1
UNDERVOLTAGE TRIP LEVEL: OFF
Range: 5 - 30%, OFF
Increments of 1
GROUND FAULT ALARM DELAY: 0.1 SEC.
Range: 0.5 - 20.0 SEC.
Increments of 0.1
GROUND FAULT LOSET TRIP DELAY: 0.5 SEC
Range: 1.0 - 20.0 SEC., OFF
Increments of 0.1
GROUND FAULT HISET TRIP DELAY: 0.008 SEC.
Range: 0.008 - 0.250 SEC.
Increments of 0.002
OVERVOLTAGE ALARM DELAY: 1.0 SEC.
Range: 1.0 - 30.0 SEC.
Increments of 0.1
OVERVOLTAGE TRIP DELAY: 2.0 SEC.
Range: 1.0 - 30.0 SEC.
Increments of 0.1
UNDERVOLTAGE ALARM DELAY: 1.0 SEC.
Range: 1.0 - 30.0 SEC.
Increments of 0.1
UNDERVOLTAGE TRIP DELAY: 2.0 SEC.
Range: 1.0 - 30.0 SEC.
Increments of 0.1
TOSHIBA- 37
LINE FREQUENCY TRIP WINDOW: DISABLED
Range: 0 - 6, Disabled
Increments of 1
LINE FREQUENCY TRIP DELAY: 1.0 SEC.
Range: 1.0 - 20.0 SEC.
Increments of 0.1
Page 44
TX Series 48 - 1250A
SP.3 Phase & Ground Settings (Setpoint Page 3)
continued
MENU
(Hit DOWN ARROW two times)
PAGE 3 PHASE & GROUND SETTINGS
SP.3 Phase & Ground Settings (Setpoint Page 3)
(Security Level: 2)
SP3.5 Overcurrent Trip Level: Typically used to
indicate the motor is severely overloaded and at which point a trip occurs.
• Overcurrent Trip
Delay: The
amount of time the overcurrent condition must exist before a trip will occur.
SP3.6 Phase Loss Trip: When enabled, the TX will trip
the motor off-line upon a loss of phase power.
• Phase Loss Trip Delay: The amount of time the phase loss condition must exist before a trip will occur.
SP3.7 Phase Rotation Detection: The TX is
continuously monitoring the phase rotation. Upon a start command, a trip will occur if it detects a change in the phase rotation.
POWER FACTOR LEAD P/F ALARM: OFF
Range: .01 - 1.00, OFF
Increments of .01
POWER FACTOR LEAD P/F TRIP: OFF
Range: .01 - 1.00, OFF
Increments of .01
POWER FACTOR LAG P/F ALARM: OFF
Range: .01 - 1.00, OFF
Increments of .01
POWER FACTOR LAG P/F TRIP: OFF
Range: .01 - 1.00, OFF
Increments of .01
POWER DEMAND PERIOD: 10 MINUTES
Range: 1 - 60 Minutes
Increments of 1
KW DEMAND ALARM PICKUP: OFF KW
Range: OFF, 1 - 100000
Increments of 1
KVA DEMAND ALARM PICKUP: OFF KVA
Range: OFF, 1 - 100000
Increments of 1
KVAR DEMAND ALARM PICKUP: OFF KVAR
Range: OFF, 1 - 100000
Increments of 1
P/F LEAD ALARM DELAY: 1 SEC.
Range: 1 - 120 SEC
Increments of 1
P/F LEAD TRIP DELAY: 1.0 SEC.
Range: 1 - 120 SEC.
Increments of 1
P/F LAG ALARM DELAY: 1.0 SEC.
Range: 1 - 120 SEC.
Increments of 1
P/F LAG TRIP DELAY: 1.0 SEC.
Range: 1 - 120 SEC.
Increments of 1
• Phase Rotation: There are two possible phase rotation options: ABC or ACB. This setpoint monitors the wiring to ensure that the phase rotation is correct. To view the present phase rotation, go to Metering Page1, screen number 4.
SP3.8 Ground Fault Alarm: Typically used to warn of
low level ground current leakage
• Ground Fault Alarm Delay: The amount of time that the ground fault condition must exist before an alarm will occur.
SP3.9 Ground Fault Loset Trip Level: Typically used
to trip the motor on a low level of ground current leakage. This setpoint is intended to detect high impedance faults. (Pending)
• Ground Fault Loset Trip Delay: The amount of time that the ground fault condition must exist before a trip will occur.
TOSHIBA - 38
AMPS DEMAND ALARM PICKUP: OFF AMPS
Range: OFF, 1 - 100000
Increments of 1
SP3.10 Ground Fault Hiset Trip Level: Used to trip
the motor (within milliseconds) upon detecting a high level of ground current leakage. This setpoint is intended to detect low impedance faults. (Pending)
• Ground Fault Hiset Trip Delay: The amount of time that the ground fault condition must exist before a trip will occur.
SP3.11 Overvoltage Alarm Level: Typically used to
indicate when the line voltage is too high. This is an alarm level.
• Overvoltage Alarm Delay: The amount of time that the overvoltage condition must exist before a trip will occur.
Page 45
TX Series 48 - 1250A
SP3.12 Overvoltage Trip Level: Typically used to
indicate that the line voltage is too high and at which point a trip occurs
• Overvoltage Trip Delay: The amount of time that the overvoltage condition must exist before a trip will occur.
SP3.13 Undervoltage Alarm Level: Typically used to
indicate when the line voltage is too low. This is an alarm level.
• Undervoltage Alarm Delay: The amount of time that the overvoltage condition must exist before a trip will occur.
SP3.14 Undervoltage Trip Level: Typically used to
indicate that the line voltage is too low and at which point a trip occurs
• Undervoltage Trip Delay: The amount of time that the undervoltage condition must exist before a trip will occur.
SP3.15 Line Frequency Trip Window: The acceptable
amount of drift above or below the line frequency before a trip is generated.
SP3.19 Power Factor Lag Trip: The acceptable
amount of power factor lag before a trip is generated.
• Power Factor Lag Delay: The amount of time that the power factor lag condition must exist beyond the window before a trip will occur.
SP3.20 Power Demand Period: The TX Series
measures the damand of the motor for several parameters (current, kW, kvar, kVA). The demand values of motors assists in energy management programs where processes may be altered or scheduled to reduce overall demand. Demand is calculated by a programmed amount of time where current, kW, kvar and kva samples are taken and then averaged and stored to assess demand.
• Line Frequency Trip Delay: The amount of time that the frequency drift condition must exist beyond the window before a trip will occur.
SP3.16 Power Factor Lead Alarm: Typically used to
indicate a leading power factor.
• Power Factor Lead Alarm Delay: The amount of time that the power factor lead condition must exist beyond the window before a trip will occur.
SP3.17 Power Factor Lead Trip: The acceptable
amount of power factor lead before a trip is generated.
• Power Factor Lead Delay: The amount of time that the power factor lead condition must exist beyond the window before a trip will occur.
SP3.18 Power Factor Lag Alarm: Typically used to
indicate a lagging power factor.
• Power Factor Lag Alarm Delay: The amount of time that the power factor lagging condition must exist beyond the window before a trip will occur.
TOSHIBA- 39
Page 46
TX Series 48 - 1250A
SP.4 Relay Assignment (Setpoint Page 4)
MENU
(Hit DOWN ARROW three times)
PAGE 4 RELAY ASSIGNMENT
O/L TRIP 1ST: TRIP ONLY
Range: TRIP (AUX1),
ALARM (AUX2), AUX3, AUX4
I/B TRIP 1ST: TRIP
S/C TRIP 1ST: TRIP ONLY
OVERCURRENT TRIP 1ST: TRIP
STATOR RTD TRIP 1ST: TRIP
NON-STATOR RTD TRIP 1ST: TRIP
G/F HI SET TRIP 1ST: TRIP
PHASE REVERSAL 1ST: TRIP
OVERVOLTAGE TRIP 1ST: TRIP
UNDERVOLTAGE TRIP 1ST: TRIP
POWER FACTOR TRIP 1ST: TRIP
TACH ACCEL TRIP 1ST: TRIP
INHIBITS TRIP 1ST: TRIP
SHUNT TRIP 1ST: AUX 3
BYPASS DISCREPANCY 1ST: NONE
EXTERNAL INPUT #1 1ST: NONE
I/B ALARM 1ST: ALARM
STATOR RTD ALARM 1ST: ALARM
NON-STATOR RTD ALARM 1ST: ALARM
RTD FAILURE ALARM 1ST: ALARM
SELF-TEST FAIL 1ST: TRIP
THERMAL REGISTER 1ST: ALARM
U/V ALARM 1ST: ALARM
O/V ALARM 1ST: ALARM
G/F LO SET TRIP 1ST: TRIP
PHASE LOSS TRIP 1ST: TRIP
ACCEL. TIME TRIP 1ST: TRIP ONLY
START CURVE TRIP 1ST: TRIP ONLY
OVER FREQUENCY TRIP 1ST: TRIP
UNDER FREQUENCY TRIP 1ST: TRIP
I*I*T START CURVE 1ST: TRIP
EXTERNAL INPUT #2 1ST: NONE
DUAL RAMP 1ST: NONE
THERMOSTAT 1ST: TRIP
O/L WARNING 1ST: ALARM
OVERCURRENT ALARM 1ST: ALARM
GROUND FAULT ALARM 1ST: ALARM
UNDERCURRENT ALARM 1ST: ALARM
POWER FACTOR ALARM 1ST: ALARM
KW DEMAND ALARM 1ST: ALARM
KVA DEMAND ALARM 1ST: ALARM
KVAR DEMAND ALARM 1ST: ALARM
AMPS DEMAND ALARM 1ST: ALARM
TIMED OUTPUT 1ST: NONE
RUN DELAY TIME 1ST: NONE
LEARNED START CURVE 1ST: TRIP
MOTOR RUNNING 1ST: NONE
TOSHIBA - 40
AT SPEED 1ST: AUX4
Page 47
TX Series 48 - 1250A
SP.4 Relay Assignment (Setpoint Page 4) (Security Level: 2)
All of the protection functions of the TX are user programmable to an output relay. The factory will ship with all tripping functions assigned to TRIP (AUX1) relay, and all alarm functions to ALARM (AUX2) relay. Note: AUX1 - 4 are Factory Set and should not be changed.
SP4.1 The following is a list of all the user programmable functions.
Note: The Relay Assignments are factory defaults.
FUNCTIONS RELAY ASSIGNMENT
IMBALANCE TRIP TRIP (AUX1) SHORT CIRCUIT TRIP TRIP (AUX1) OVERCURRENT TRIP TRIP (AUX1) ST ATOR RTD TRIP TRIP (AUX1) NON-ST A TOR R TD TRIP TRIP (AUX1) GROUND FAULT HI SET TRIP TRIP (AUX1) GROUND FAULT LO SET TRIP TRIP (AUX1) PHASE LOSS TRIP TRIP (AUX1) ACCELERATION TIME TRIP (AUX1) START CURVE TRIP TRIP (AUX1) OVER FREQUENCY TRIP TRIP (AUX1) UNDER FREQUENCY TRIP TRIP (AUX1) I*I*T START CURVE TRIP (AUX1) LEARNED START CURVE TRIP (AUX1) PHASE REVERSAL TRIP OVERVOLTAGE TRIP TRIP UNDERVOLTAGE TRIP TRIP POWER FACTOR TRIP TRIP T ACH ACCEL TRIP TRIP INHIBITS TRIP TRIP SHUNT TRIP AUX 3 BYPASS DISCREPANCY NONE EXTERNAL INPUT 1 NONE EXTERNAL INPUT 2 NONE DUAL RAMP NONE THERMOSTAT TRIP (AUX 1) OVERLOAD WARNING ALARM (AUX2) OVERCURRENT ALARM ALARM (AUX2) GROUND FAULT ALARM ALARM (AUX2) UNDERCURRENT ALARM ALARM (AUX2) MOTOR RUNNING NONE IMBALANCE ALARM ALARM (AUX2) STATOR RTD ALARM ALARM (AUX2) NON-STATOR RTD ALARM ALARM (AUX2) RTD FAILURE ALARM ALARM (AUX2) SELF TEST FAIL TRIP (AUX1) THERMAL REGISTER ALARM (AUX2) U/V ALARM ALARM O/V ALARM ALARM POWER FACTOR ALARM ALARM KW DEMAND ALARM ALARM KVA DEMAND ALARM ALARM KVAR DEMAND ALARM ALARM AMPS DEMAND ALARM ALARM TIMED OUTPUT NONE RUN DELAY TIME NONE AT SPEED AUX4
TOSHIBA- 41
Page 48
TX Series 48 - 1250A
SP.5 Relay Configuration (Setpoint Page 5) (Security Level: 2)
In Setpoint Page 5 the user can configure the four output
MENU
(Hit DOWN ARROW four times)
relays as either fail-safe or non fail-safe and latching or non-latching.
PAGE 5 RELAY CONFIGURATION
SP5.1 When a relay has been configured as fail-safe
and power is applied, the relay will be energized. The relay will then de-energize when an event occurs or if the power fails. NOTE: The relays in the TX will not prevent a start sequence unless they are wired in as interlocks. If power is lost, the motor power is also lost.
SP5.2 A relay configured as non-latching will reset
itself when the cause of the trip event is not continuous. The TRIP (AUX1) relay should
always be programmed for latching, because this trip should require a visual inspection of the motor and starter before issuing a manual reset to release the relay after a trip has been stored.
TRIP (AUX1) RELAY FAIL-SAFE: NO
Options: Yes or No
ALARM (AUX2) RELAY FAIL-SAFE: NO
AUX 3 RELAY FAIL-SAFE: NO
AUX4 RELAY FAIL-SAFE: NO
TRIP (AUX1) RELAY LATCHED: YES
ALARM (AUX2) RELAY LATCHED: NO
AUX3 RELAY LATCHED: NO
AUX4 RELAY LATCHED: NO
TOSHIBA - 42
Page 49
TX Series 48 - 1250A
SP.6 User I/O Configuration (Setpoint Page 6) (Security Level: 2)
ENABLED
PAGE 6 USER I/O CONFIGURATION
TACHOMETER SCALE SELECTION: DISABLED
Options: ENABLED or
DISABLED
TACH ACCEL TRIP MODE SELECT: DISABLED
MANUAL TACH SCALE
4.0 mA: 0 RPM
Range: 0-3600
Increments of 5
MANUAL TACH SCALE
20.0 mA: 2000 RPM
Range: 0-3600
Increments of 5
TACH RAMP TIME : 20 SEC
Range: 1 - 120 SEC.,
Disabled Increments of 1
TACH UNDERSPEED TRIP PT: 1650 RPM
Range: 0 - 3600
Increments of 5
TACH OVERSPEED TRIP PT: 1850 RPM
Range: 0 - 3600
Increments of 5
Options: UNDERSPEED, OVERSPEED or DISABLED
ANALOG OUTPUT #1 :RMS CURRENT
Range:
Analog Output RPM 0 - 3600 Hottest Bearing 0 - 200°C Hottest Stator RTD 0 - 200°C RMS Current 0 - 6500A % Motor Load 0 - 1000% KW 0-30000 KW
OFF Increments of 1
ANALOG OUTPUT #2 :% MOTOR LOAD
Range: See Analog Output #1
Increments of 1
USER PROGRAMMABLE EXTERNAL INPUTS
Range
Continued...
TACH ACCEL TRIP DELAY: 1 SEC
Range: 1 - 60
Increments of 1
ANALOG OUTPUT #1 4ma: 0
Range: 0-65535
Increments of 1
ANALOG OUTPUT #2 4mA: 0
Range: 0-1000%
Increments of 1
ANALOG OUTPUT #1 20mA: 250
Range: 0-65535
Increments of 1
ANALOG OUTPUT #2 20mA: 1000
Range: 0-1000%
Increments of 1
TOSHIBA- 43
Page 50
TX Series 48 - 1250A
SP.6 User I/O Configuration (Setpoint Page 6) (Security Level: 2)
The TX can be configured to accept a tachometer feedback signal through the 4-20mA input and has two options available for scaling the tachometer input. Note: At the time of this printing, SP6.1 - SP6.4 are pending.
SP6.1 The first screen of setpoint page 6 is
TACHOMETER SCALE SELECTION. When this is set to AUTO, the display prompts the user to program the TX to sense when the motor speed is zero. It will prompt again when the motor speed is at maximum RPM. Once these inputs are given, the TX automatically scales the range of the tachometer feedback to give a linear RPM ramp. When this is set to MANUAL, the user will need to input the tachometer scale of the 4-20mA input range.
• Press Enter if Motor Speed = 0 RPM: This setpoint will be displayed when the user has selected Auto Scaling Mode. The TX is prompting the user to program when the motor speed is at zero. This will be the lowest value on the scale.
• Press Enter if Motor Speed = MAX RPM: The TX is now prompting the user to program the unit when the motor is at maximum speed. This will be the highest value on the scale.
SP6.5 The TX provides two 4-20mA analog outputs.
Each analog output is independent of the other and can be assigned to monitor different functions. The available output ranges are RPM, Hottest Non-Stator (Bearing) RTD, Hottest Stator RTD, RMS current, or % Motor Load.
• Analog Output #1 – Select a function from the available five options to be transmitted from the 4-20mA output. Note: If selecting RPM, the Tachometer feedback input signal must be present in order for the TX to give proper output. If selecting RTD, the RTD option must be installed and an RTD input signal must be present for a proper output to be given from the analog output.
• Analog Output #1 4 mA: Enter a value that the 4mA level will represent for the selected function; typically this value should be 0.
• Analog Output #1 20 mA: Enter a value that the 20mA level will represent for the selected function.
SP6.6 Analog Output #2 – All of the setpoints and
setup screens for Analog Output #2 are the same as those for Analog Output #1.
• Press Enter to Scale: This is a prompt to the user that the unit has recorded the values of the tachometer input based on input from the user and is now ready to automatically scale the range of the tachometer input.
• Manual Tach Scale 4.0 mA: The unit is looking for an RPM value to assign to the lowest point on the scale. This value should represent the motor at zero speed.
• Manual Tach Scale 20.0 mA: The unit is looking for an RPM value to assign to the highest point on the scale. This value should represent the motor at full speed.
SP6.2 Feedback Ramp Time: This is the duration of
the tachometer ramp time.
SP6.3 T ach Accel Trip: The maximum allowed
percentage of slip per NEMA design of the motor.
SP6.4 T ach Accel Trip Delay: The duration of time that
the Tach Accel trip condition must persist before a trip is generated.
TOSHIBA - 44
Page 51
TX Series 48 - 1250A
SP.6 User I/O Configuration (Setpoint Page 6) (Security Level: 2)
USER PROGRAMMABLE EXTERNAL INPUTS (Continued)
EXTERNAL INPUT #1 SELECT: DISABLED
Options: Enabled or Disabled See text for directions
EXTERNAL INPUT #2 SELECT: DISABLED
Options: Enabled or Disabled See text for directions
DUAL RAMP SELECT: DUAL RAMP
Options: Enabled, Disabled or
Dual Ramp
THERMOSTAT SELECT: ENABLED
Options: Enabled, Disabled or
Thermostat
NAME EXT. INPUT #1
NAME EXT INPUT #2
NAME EXT INPUT #3 DUAL RAMP
See text for directions
NAME EXT INPUT #4 THERMOSTAT
See text for directions
SP6.7 User Programmable External Inputs: The TX
provides up to 4 digital external inputs which are individually programmable. A description name can be assigned to each individual input for easy identification.
• External Input #1: If used, this setpoint must be enabled.
• Name Ext. Input #1: The user can assign a description name to the input to easily identify the cause of external trip or alarm. Up to 15 characters including spaces can be used to assign the name.
• External Input #1 Type: The external input can be set as either a normally open or normally closed contact.
• External Input #1 Time Delay: Upon a change in contact setting, the unit will wait the programmed amount of time before generating an output. If no delay is needed, then input 0 seconds. The TX will post an event upon seeing a change in state.
• External Input #2: The setup screens and setpoints for External Input #2 includes the option of programming the unit for Under Voltage Phase Rotation.
EXTERNAL INPUT #1 TYPE: NORMALLY CLOSED
Options: Normally Open or
Normally Closed
EXTERNAL INPUT #2 TYPE: NORMALLY CLOSED
Options: Normally Open or
Normally Closed
DUAL RAMP TYPE: NORMALLY CLOSED
Options: Normally Open or
Normally Closed
THERMOSTAT TYPE: NORMALLY CLOSED
Options: Normally Open or
Normally Closed
EXTERNAL INPUT #1 TIME DELAY: 0 SEC.
Range: 0 - 60 SEC
Increments of 1
EXTERNAL INPUT #2 TIME DELAY: 0 SEC.
Range: 0 - 60 SEC.
Increments of 1
DUAL RAMP TIME DELAY: 0 SEC.
Range: 0 - 60 SEC
Increments of 1
THERMOSTAT TIME DELAY: 0 SEC.
Range: 0 - 60 SEC.
Increments of 1
• External Input #3: The setup screens and setpoints for External Input #3 includes the option of being configured for Dual Ramp. In Dual Ramp mode, the initial contact setting is the same as the START RAMP #1. Upon a change in input contact state, the TX will switch over to START RAMP #2 and use that setting for start control mode. Note: The start RAMP types should only be switched while the motor is stopped. In Setpoint Page 4 Relay Assignments, do not assign any output relay to this function. The TX will ship with External input #3 programmed for dual ramp. If it is not needed, disable the dual ramp.
• External Input #4 – These input screens are for the thermostat input and can be enabled or disabled. Note: Toshiba recommends that this
function remain enabled. If the thermostat indicates an over temperature condition, the TX will trip the motor.
TOSHIBA- 45
Page 52
TX Series 48 - 1250A
SP.7 Custom Acceleration Curve (Setpoint Page 7) (Security Level: 3)
MENU
(Hit DOWN ARROW six times)
PAGE 7 CUSTOM ACCELERATION CURVE
SP7.1 Setpoint Page 7 allows the user to custom
design the acceleration curve (start curve) to the specific application. The user can custom design up to three different curves in the TX. Only one curve can be active (enabled) at a time. Each of the three curves allow for eight voltage plotting points, with corresponding ramp times and a current limit setting. Note: Each successive voltage level must be programmed to a voltage level equal to or greater than the previous level. All eight levels of voltages must be programmed and the eighth level has been preset at 100%.
If Custom Accel Curve has been set to curve A, B or C on this page, the TX will override the Start Control Mode selected in Setpoint Page 2, (even if Start Control Mode in Setpoint Page 2 has not been set to Custom Accel Curve). Note: Setpoint Page 7 has a security level 3 requirement.
CUSTOM ACCEL CURVE : DISABLED
Range: DISABLED,
CURVE A, B or C
CUSTOM CURVE A
CURVE A VOLTAGE LEVEL 1: 25%
Range: 0 - 100%
Increments of 1
CURVE A RAMP TIME 1: 2 SEC
Range: 1 - 60 SEC
Increments of 1
CURVE A VOLTAGE LEVEL 2: 30%
Range: 0 - 100%
Increments of 1
CURVE A RAMP TIME 2: 2 SEC.
Range: 1 - 60 SEC
Increments of 1
CURVE A VOLTAGE LEVEL 3: 37%
Range: 0 - 100%
Increments of 1
CURVE A RAMP TIME 3: 2 SEC.
Range: 1 - 60 SEC
Increments of 1
CURVE A VOLTAGE LEVEL 4: 45%
Range: 0 - 100%
Increments of 1
TOSHIBA - 46
CURVE A RAMP TIME 4: 2 SEC.
Range: 1 - 60 SEC
Increments of 1
CURVE A VOLTAGE LEVEL 5: 55%
Range: 0 - 100%
Increments of 1
CURVE A RAMP TIME 5: 2 SEC.
Range: 1 - 60 SEC
Increments of 1
CURVE A VOLTAGE LEVEL 6: 67%
Range: 0 - 100%
Increments of 1
CURVE A RAMP TIME 6: 2 SEC.
Range: 1 - 60 SEC
Increments of 1
CURVE A VOLTAGE LEVEL 7: 82%
Range: 0 - 100%
Increments of 1
CURVE A RAMP TIME 7: 2 SEC.
Range: 1 - 60 SEC
Increments of 1
Page 53
TX Series 48 - 1250A
SP.7 Custom Acceleration Curve (Setpoint Page 7) (Security Level: 3)
CUSTOM CURVE A
CUSTOM CURVE B
CURVE A VOLTAGE LEVEL 8: 100%
Range: 0 - 100%
Increments of 1
CURVE A RAMP TIME 8: 2 SEC
Range: 1 - 60 SEC
Increments of 1
CURVE A CURRENT LIMIT: 350% FLA
Range: 200 - 600%
Increments of 10
CURVE B VOLTAGE LEVEL 1: 25%
Range: 0 - 100%
Increments of 1
CURVE B RAMP TIME 1: 2 SEC.
Range: 1 - 60 SEC
Increments of 1
CURVE B VOLTAGE LEVEL 2: 30%
Range: 0 - 100%
Increments of 1
CURVE B RAMP TIME 2: 2 SEC.
Range: 1 - 60 SEC
Increments of 1
CURVE B VOLTAGE LEVEL 3: 37%
Range: 0 - 100%
Increments of 1
CURVE B RAMP TIME 3: 2 SEC.
Range: 1 - 60 SEC
Increments of 1
CURVE B VOLTAGE LEVEL 4: 45%
Range: 0 - 100%
Increments of 1
CURVE B RAMP TIME 4: 2 SEC.
Range: 1 - 60 SEC
Increments of 1
CURVE B VOLTAGE LEVEL 5: 55%
Range: 0 - 100%
Increments of 1
CURVE B RAMP TIME 5: 2 SEC.
Range: 1 - 60 SEC
Increments of 1
CURVE B VOLTAGE LEVEL 6: 67%
Range: 0 - 100%
Increments of 1
CURVE B RAMP TIME 6: 2 SEC.
Range: 1 - 60 SEC
Increments of 1
TOSHIBA- 47
CUSTOM CURVE B
CUSTOM CURVE C
CURVE B VOLTAGE LEVEL 7: 82%
Range: 0 - 100%
Increments of 1
CURVE B RAMP TIME 7: 2 SEC.
Range: 1 - 60 SEC
Increments of 1
CURVE B VOLTAGE LEVEL 8: 100%
Range: 0 - 100%
Increments of 1
CURVE B RAMP TIME 8: 2 SEC
Range: 1 - 60 SEC
Increments of 1
CURVE B CURRENT LIMIT: 350% FLA
Range: 200 - 600%
Increments of 10
CURVE C VOLTAGE LEVEL 1: 25%
Range: 0 - 100%
Increments of 1
CURVE C RAMP TIME 1: 2 SEC.
Range: 1 - 60 SEC
Increments of 1
CURVE C VOLTAGE LEVEL 2: 30%
Range: 0 - 100%
Increments of 1
CURVE C RAMP TIME 2: 2 SEC.
Range: 1 - 60 SEC
Increments of 1
CURVE C VOLTAGE LEVEL 3: 37%
Range: 0 - 100%
Increments of 1
CURVE C RAMP TIME 3: 2 SEC.
Range: 1 - 60 SEC
Increments of 1
CURVE C VOLTAGE LEVEL 4: 45%
Range: 0 - 100%
Increments of 1
CURVE C RAMP TIME 4: 2 SEC.
Range:1 - 60 SEC
Increments of 1
CURVE C VOLTAGE LEVEL 5: 55%
Range: 0 - 100%
Increments of 1
CURVE C RAMP TIME 5: 2 SEC.
Range: 1 - 60 SEC
Increments of 1
Page 54
TX Series 48 - 1250A
SP.7 Custom Acceleration Curve (Setpoint Page 7) (Security Level: 3)
SP7.1 Setpoint Page 7 allows the user to custom
design the acceleration curve (start curve) to the specific application. The user can custom design up to three different curves in the TX. Only one curve can be active (enabled) at a time. Each of the three curves has eight voltage levels, with corresponding ramp times and a current limit setting. Note: Each successive voltage level must be programmed to a voltage level equal to or greater than the previous level. All eight levels of voltages must be programmed and the eighth level has been preset at 100%.
If Custom Accel Curve has been set to curve A, B or C on this page, the TX will override the Start Control Mode selected in Setpoint Page 2, (even if Start Control Mode in Setpoint Page 2 has not been set to Custom Accel Curve). Note: Setpoint Page 7 has a security level 3 requirement.
CUSTOM CURVE C
CURVE C VOLTAGE LEVEL 6: 67%
Range: 0 - 100%
Increments of 1
CURVE C RAMP TIME 6: 2 SEC.
Range: 1 - 60 SEC
Increments of 1
CURVE C VOLTAGE LEVEL 7: 82%
Range: 0 - 100%
Increments of 1
CURVE C RAMP TIME 7: 2 SEC.
Range: 1 - 60 SEC
Increments of 1
CURVE C VOLTAGE LEVEL 8: 100%
Range: 0 - 100%
Increments of 1
CURVE C RAMP TIME 8: 2 SEC.
Range: 1 - 60 SEC
Increments of 1
CURVE C CURRENT LIMIT: 350% FLA
Range: 200 - 600%
Increments of 10
TOSHIBA - 48
Page 55
TX Series 48 - 1250A
SP.8 Overload Curve Configuration (Setpoint Page 8) (Security Level: 3)
MENU
(Hit DOWN ARROW seven times)
PAGE 8 OVERLOAD CURVE CONFIGURATION
BASIC RUN OVERLOAD CURVE
Configures the unit’s start and run protection mode. The unit has independent start and run curve protection and the settings can be based on the OL Class or set by the motor’s locked rotor current and time.
BASIC START OVERLOAD CURVE
SP8.1 Basic Run Overload Curve
• Run Curve Locked Rotor
Time: Set the locked rotor
time to the OL Class default chosen in Setpoint Page 1 or set the time in seconds. This is the time the locked rotor condition exists before a trip occurs.
• Run Locked Rotor Current: The current the motor draws with full voltage on the windings and no rotor movement (as a percent of motor FLA). Refer to the nameplate data or contact the motor manufacturer.
AREA UNDER CURVE PROTECTION: DISABLED
Range: ENABLED or DISABLED
• Coast Down Timer: If enabled, this prevents the motor from restarting for the programmed amount of time,
CURRENT OVER CURVE: DISABLED
Options: DISABLED, LEARN
or ENABLED
after a stop command is given.
SP8.2 Basic Start Overload Curve
• Start Curve Locked Rotor Time: The locked rotor
time can be set to the OL Class default chosen in Setpoint Page 1 or to a specific time. The overload condition must exist for the programmed amount of time before a trip occurs.
• Start Locked Rotor Current: The current the motor draws with full voltage on the windings and no motor movement (as a percent of motor FLA). Refer to the motor nameplate data or contact the motor manufacturer. See Appendix A.
• Acceleration Time Limit: If the motor does not enter run mode (reach at speed) within the preset time, the unit trips on acceleration time limit.
• Number of Starts per hour: If enabled, this limits the maximum number of starts permitted per hour. This setpoint allows a maximum of 6 starts per hour. Contact motor manufacturer.
• Time Between Starts: If enabled, the TX prevents another start attempt until the programmed time has expired.
TOSHIBA- 49
RUN CURVE LOCKED ROTOR TIME: O/L CLASS
Range: 1 - 30 SEC, O/L CLASS
COAST DOWN TIMER TIME: DISABLED
Range:1 - 60 MIN, DISABLED
Increments of 1
START CURVE LOCKED ROTOR TIME: O/L CLASS
Range:1 - 30 SEC, O/L CLASS
Increments of 1
ACCELERATION TIME LIMIT: 30 SEC
Range:1 - 300 SEC, DISABLED
Increments of 1
NUMBER OF STARTS PER HOUR: DISABLED
Range: 1 - 6, DISABLED
Increments of 1
TIME BETWEEN STARTS TIME: DISABLED
Range:1 - 60 MIN, DISABLED
Increments of 1
MAX I*I*T START : 368 FLA*FLA*SEC
Range:1 - 2500, FLA*Time (Sec)
Increments of 1
LEARNED START CURVE BIAS: 10%
Range: 5 - 40%
Increments of 1
RUN LOCKED ROTOR CURRENT: 600% FLA
Range: 400 - 800%
Increments of 1
START LOCKED ROTOR CURRENT: 600% FLA
Range: 400 - 800%
Increments of 10
TIME FOR SAMPLING : 30 SEC
Range: 1 - 300 SEC
Increments of 1
SP8.3 Area Under Curve Protection: If enabled,
this secondary start protection uses both the basic start protection and the area under the curve protection.
2
• Max I*I*T Start: The maximum I
T allowed during start. If the I2T to start exceeds this number then the TX will generate a trip.
SP8.4 Current Over Curve: Learns the motor’s
starting characteristics and protects the motor based upon the learned curve. It is useful when commissioning a new motor.
• Learn: The unit reads the motor’s starting characteristics. Start the motor and allow it to come to full speed. The start feedback enables the motor protection based on the learned start curve.
• Learned Start Curve Basis: The maximum allowed deviation above or below the start curve before a trip is generated.
• Time for Sampling: The time the TX continues to sample the start curve characteristic during learn the mode.
Page 56
TX Series 48 - 1250A
SP.9 RTD Configuration (Setpoint Page 9) (Security Level: 3)
Please note, this is supplied as an option. Contact factory for more information.
Optional
TOSHIBA - 50
Page 57
TX Series 48 - 1250A
SP.9 RTD Configuration (Setpoint Page 9) (Security Level: 3)
The TX is available with an optional RTD card that provides 12 programmable RTDs which are individually programmable for type. The available types are 100 ohm platinum, 100 ohm nickel, 120 ohm nickel and 10 ohm copper. Each RTD can be identified with a description name of up to 15 characters (including spacing). Also, each individual RTD has it own alarm and trip level.
SP9.1 Use NEMA Temp for RTD Value: When this
setpoint is enabled, the TX will use the NEMA design insulation class to limit the maximum allowed range of the alarm and trip level. The maximum allowed temperature range is 240° C or (464°F).
SP9.2 # Of RTD’S Used for Stator: Up to six RTDs can
be assigned to monitor the stator of the motor.
SP9.3 RTD Voting: When this is enabled, the TX will
not post a trip until 2 RTD’s have exceeded the trip level. This prevents nuisance RTD tripping.
SP9.4 All 12 RTDs are configured in the following
manner. The first column is the RTD type, the second column is the RTD description, the third column is the alarm level, and the fourth column is the trip level. The first six RTDs have been pre-programmed with a description name for the STATOR, with two RTDs per phase. RTDs #1 & #2 have been named STATOR PHASE A1 and A2 respectively. RTDs #3&4 are named STATOR PHASE B1 and B2, RTDs #5&6 are named STATOR PHASE C1 and C2. If other description names are required, press the right arrow button from the RTD Type screen to go the RTD description screen. If no alarm or trip level is required these setpoints can be turned off.
TOSHIBA- 51
Page 58
TX Series 48 - 1250A
SP.10 Set Password (Setpoint Page 10) (Security Level: 3)
The TX has three levels of user programmable setpoint screens. Level one setpoints do not require a password because the data contained in level one is basic nameplate data and starter control. Level two setpoint screens require a three-digit password to configure the protection schemes. Level three setpoint screens require a four-digit password to access the full range of protection and starter schemes.
SP10.1 Set Level 2 Password: This level uses a 3-digit
password. The default level 2 password is 100.
SP10.2 Set Level 3 Password: Level three uses a 4-digit
password. The default level 3 password is 1000.
MENU
(Hit DOWN ARROW nine times)
PAGE 10 SECURITY SET PASSWORD
SET LEVEL 2 PASSWORD: 100
Range: 000 - 999
SET LEVEL 3 PASSWORD: 1000
Range: 0000 - 9999
TOSHIBA - 52
Page 59
TX Series 48 - 1250A
SP.11 Communications (Setpoint Page 11) (Security Level: 3)
SP11.1 Set Front Baud Rate: Configures the RS232
communications baud rate.
SP11.2 Set Modbus Baud Rate: Configures the modbus
communications baud rate.
SP11.3 Modbus Address Number: Assigns a Modbus
address to the TX relay.
SP11.4 Set Access Code: Assigns an access code to
the Modbus addressing.
SP11.5 Set Link Baud Rate: Configures the RS422
communications baud rate between the keypad operator and the CPU board. (For applications with remote keypad only.)
MENU
(Hit DOWN ARROW ten times)
PAGE 11 COMMUNICATIONS
SET FRONT BAUD RATE: 9.6 KB/SEC
Range: 2.4, 4.8, 9.6, 19.2
38.4 KB/SEC
SET MODBUS BAUD RATE: 9.6 KB/SEC
Range: 2.4, 4.8, 9.6, 19.2
38.4 KB/SEC
MODBUS ADDRESS NUMBER: 247
Range: 1 - 247
Increments of 1
SET ACCESS CODE CODE: 1
Range: 1 - 999
Increments of 1
SET LINK BAUD RATE: 38.4 KB/SEC
Range: 2.4, 4.8, 9.6, 19.2
38.4 KB/SEC
REMOTE START/STOP: DISABLED
Option: Enabled or Disabled
TOSHIBA- 53
Page 60
TX Series 48 - 1250A
SP.12 System Setpoints (Setpoint Page 12) (Security Level: 3)
MENU
(Hit DOWN ARROW eleven times)
PAGE 12 SYSTEM SETPOINTS
DEFAULT DISPLAY SCREEN
ALARMS
THERMAL REGISTER SETUP INFORMATION
METERING DATA PAGE #: 1
Enter Metering Page (1 - 4) Number for display
RTD FAILURE ALARM ALARM: DISABLED
Enabled or Disabled
THERMAL REGISTER ALARM: 90%
Range: Off, 40 - 95%
Increments of 1
COLD STALL TIME : O/L CLASS
Range: O/L CLASS,
4 - 40 SEC Increments of 1
HOT STALL TIME : 1/2 O/L CLASS
Range: 1/2 O/L CLASS,
4 - 40 SEC Increments of 1
STOPPED COOL DOWN TIME: 30 MIN
Range: 10 - 300 MIN
Increments of 1
RUNNING COOL DOWN TIME: 15 MIN
Range: 10 - 300 MIN
Increments of 1
METERING DATA SCREEN #: 1
Enter Metering Screen Number for display
THERMAL ALARM DELAY: 10 SEC.
Range: 1 - 20 SEC.
Increments of 1
RELAY MEASURED COOL RATES: DISABLED
Range: ENABLED or
DISABLED
THERMAL REGISTER MINIMUM: 15%
Range: 10 - 50%, OFF
Increments of 1
MOTOR DESIGN AMBIENT TEMPERATURE: 40 C
Range: 10 - 90 C
Increments of 1
MOTOR DESIGN RUN TEMPERATURE: 80% MAX
Range: 50 - 100% of Motor Stator Max Temp. Increments of 1%
MOTOR STATOR MAX TEMPERATURE: INS CLS
Range: Insulation Class
10 - 240 C Increments of 1
I/B INPUT TO THERMAL REGISTER: ENABLED
Options: ENABLED or
DISABLED
USE CALCULATED K OR ASSIGN: 7
Range: 1 - 50, ON
PRESS ENTER TO CLR THERMAL REGISTER
TOSHIBA - 54
Page 61
TX Series 48 - 1250A
SP.12 System Setpoints (Setpoint Page 12) (Security Level: 3)
SP12.1 Default Display Screen: This setpoint group
allows the user to choose the default screen the TX displays while the motor is running. Select the metering page number (1-3), then select the metering screen number. The range varies depending on the selected page. To display a default screen, program the following two setpoints:
• Metering Data Page#: Range is Page 1 - 3.
• Metering Data Screen#: If Page 1 is selected
as the default page, then Screens 1- 10 are available. If Page 2 Screens 1-29 are available. If Page 3 is selected then Screens 1-6 are available. (See Metering Menu, MP.1, for screen number assignment.)
SP12.2 Alarms: Configures the RTD failure alarm
(when RTD option is included) and the thermal register alarm.
• RTD Failure Alarm: If enabled, and an RTD shorts or open, an alarm occurs. (Only if RTD option is installed).
• Thermal Register Alarm: Sets a level in the thermal register to generate an alarm when the Thermal Register Capacity Used has exceeded this level.
• Thermal Alarm Delay: The amount of time that the Thermal Register Used must exceed the setpoint before an alarm condition will occur.
SP12.3 Thermal Register Setup Information: This
setpoint group will configure the thermal register and indicate to the TX which inputs to use when thermal modeling.
• Cold Stall Time: Enter the time from the motor manufacturer’s specification sheet or use the time defined by the OL Class. This setpoint is used to define the thermal capacity of the motor.
• Hot Stall Time: Enter the amount of time specified by the motor manufacturer or use half of the time defined by the OL Class.
• Stopped Cool Down Time: The time the motor requires to cool down after it has stopped. Use only the data provided by the motor manufacturer. This setpoint is used to configure the cooling rate of the thermal register.
• Running Cool Down Time: The amount of time the motor requires for cooling down while running. Use only the data provided by the motor manufacturer.
• Relay Measured Cool Rates: When the RTD option is supplied, the TX can be configured to use the measured cool rates from the RTDs instead of the programmed settings. This setpoint should only be enabled when the RTD option is present.
• Thermal Register Minimum: Sets the value in the thermal register which represents a motor running at the nameplate current (with no overheating or negative sequence currents present).
Motor Design Ambient Temperature: Use the data from the motor manufacturer’s specifications. When RTD option is supplied, this setpoint will be the base point for the RTD biasing of the Thermal Register.
• Motor Design Run Temperature: Use the data from the motor manufacturer’s specifications. This setpoint defines the operating temperature rise of the motor at full load amps or 100% load.
• Motor Stator Max Temperature: This represents the maximum temperature the stator insulation will withstand. The user may choose to use the temperature setting of the insulation class (selected in Setpoint Page 1) or enter a specific maximum temperature. This value should not exceed the stator’s insulation temperature. This maximum temperature represents 100% thermal capacity.
• I/B Input to Thermal Register: When enabled it allows the TX to use the line current imbalance information to bias the Thermal Register.
• User Calculated K or Assign: When the setpoint is set to ON the TX will calculate the k constant factor for biasing the thermal register, or the user may choose to assign the k value.
SP12.4 Press Enter to CLR Thermal Register: Allows
the level three password user to clear the thermal register for emergency restarts.
TOSHIBA- 55
Page 62
TX Series 48 - 1250A
SP.13 Calibration & Service (Setpoint Page 13) (Security Level: Factory Use Only)
MENU
(Hit DOWN ARROW twelve times)
PAGE 13 CALIBRATION & SERVICE
SET DATE AND TIME ##/##/## ##:##
MODEL #: ###### FIRMWARE REV. #: ######
PRESS ENTER TO ACCESS FACTORY SETTINGS
SP.13 Calibration & Service (Setpoint Page 13)
Certain screens are displayed for user information only, such as: Current date and time, Model number and Firmware revision number. Setpoint changes in this page will only be accessible to factory personnel.
SP13.1 Set Date and Time: Displays the date and time.
• Enter Date (DDMMYYYY): Allows the factory
personnel to program the date for the TX in the format shown.
• Enter Time (hh:mm): Allows the factory personnel to program the time for the TX.
ENTER DATE (DDMMYYYY) :##/##/####
Range: D = 1 - 31, M = 1-12,
Y = 1970 - 2069
Increments of 1
ENTER TIME (hh:mm) :##:##
Range: H = 00 - 23, M = 0 - 59
Increments of 1
SP13.2 Model & Firmware #: Displays the model number
and firmware revision in the TX.
SP13.3 Press Enter to Access Factory Settings: Available
to qualified personnel.
TOSHIBA - 56
Page 63
TX Series 48 - 1250A
Page
Chapter 6 - Metering Pages
The TX Series offers performance metering which gives the user the ability to view information about the motor and the TX unit.
6.1 Metering Page List
The following charts list each Metering Page and the functions within that page. The applicable section of the manual is also referenced.
6.1.1 Metering Menu & Data (Metering Page 1)
Metering
Page
Page 1
Metering Menu & Data
Phase A, B, C and Ground Fault 1 Average current of the % of imbalance and the motor's RPM 2 Motor load as a percentage of motor FLA 3 Line frequency and present phase order 4 Percentage of remaining Thermal Register 5 Thermal capacity required to start the motor 6 Average time required to start 7 Average current during start 8 Measured I Amount of time required to start the motor during the last successful start 10
2
T required to start the motor
Description of Display Screen
9
6.1.2 Metering (Metering Page 2)
Metering
Page
Phase A, B, C and Power Factor 1 Phase A, B, C and Ground Fault 2 Displays KW and KVA 3 Displays KVAR and Power Factor 4 Displays Peak ON and KW Demand 5
Page 2
Displays Peak ON and KVA Demand 6
Metering
Displays Peak ON and KVAR Demand 7 Displays Peak ON and Amps Demand 8 Clears Demand values 9 Displays Megawatt hours used 10 Press enter to clear statistics on MWH values 11
6.1.3 RTD Values (Metering Page 3)
Metering
Hottest stator RTD (#1 - 6) 1 Hottest non-stator RTD (#7 - 12) Temperature of start phase A1 in °C and °F 3 Maximum temperature for RTD #1 4
Page 3
Same as Screens 3 - 4 5 - 26
RTD Values
Clear the maximum temperature register (Level 3 password required) 27 Measured run cool time in minutes Measured stopped cool time in minutes
Description of Display Screen
Description of Display Screen
2
28 29
TOSHIBA- 57
Page 64
TX Series 48 - 1250A
Page
Page
Page
6.1.4 Status (Metering Page 4)
Metering
Current status 1 Amount of time remaining before an overload trip occurs 2 Amount of time remaining from a thermal inhibit signal 3 Coast down time remaining 4
Status
Page 4
Amount of time remaining before a start command can be given 5 Excessive number of starts per hour 6
6.1.5 Event Recorder (Metering Page 5)
Metering
Displays the event with date and time (Up to 60 events) 1 Displays Phase A, B, C and t he Ground Fault at the time of the trip
Event
Page 5
Recorder
Displays Vab, Vbc, Vca and Power Factor at the time of trip
6.1.6 Last Trip (Metering Page 6)
Metering
Page
Cause of last trip 1 Measured phase current 2 Measured voltage and power factor 3
Page 6
Imbalance percentage, the frequency and the kW 4
Last Trip
Hottest stator RTD temperature 5 Hottest non-stator RTD temperature 6
6.1.7 Statistics (Metering Page 7)
Metering
Displays the total Megawatt hours 1 Accumulated total running hours 2 Clear the total running hour count Total number of trips
Number of start and run overload trips since the last statistical data clearing
Number of frequency trips and imbalance trips Overcurrent trips Stator and non-stator RTD trips 8 Ground fault hiset and loset trips 9 Acceleration time trips 10 Start under curve trips 11 Start over curve trips
Page 7
I2T start curve trips
Statistics
Learned start curve trips 14 Fail shunt trip trips 15 Phase loss trip trips 16 Tach accel trip trips 17 Undervoltage and Overvoltage trips 18 Power Factor trips 19 Phase reversal trips 20 Ext Inp #1 21 Ext Inp #2 22 Ext Inp #3 23 Ext Inp #4 24 Press enter to clear statistics 25
Description of Display Screen
Description of Display Screen
1A 1B
Description of Display Screen
Description of Display Screen
3 4
5 6
7
12 13
TOSHIBA - 58
Page 65
TX Series 48 - 1250A
6.2 Metering Menu
(1) Push MENU key to toggle the screens between Setpoint Menu and Metering Menu and follow the arrow keys to get to different screens.
MENU
METERING PAGE 1 CURRENT METERED DATA
METERING PAGE 2 VOLTAGE & POWER DATA
METERING PAGE 3 RTD VALUES
METERING PAGE 4 STAT US
METERING PAGE 5 EVENT RECORDER
METERING PAGE 6 LAST TRIP
METERING PAGE 7 STATISTICS
TOSHIBA- 59
Page 66
TX Series 48 - 1250A
MP.1 Metering Menu & Data (Metering Page 1)
Displays the basic current metering data:
Screen 1: Phase A, B, C and ground fault current. Screen 2: Displays the average current of the % of
imbalance and the motor’s RPM (available with tachometer input)
Screen 3: Displays the motor load in percent of motor
FLA.
Screen 4: Displays the line frequency and the present
Phase Order.
MENU
METERING PAGE 1 CURRENT METERED DATA IC: ###### G/F: #####
IA: ###### IB: ######
I (AVG): ####
I/B: ## % RPM: ####
Screen 1
Screen 2
Screen 5: Displays the percent of the remainingthermal
register. In order for the motor to successfully start, the percentage must begreater than the thermal capacity required for a successful start.
Screen 6: Displays the thermal capacity required to
successfully start the motor.
Screen 7: Displays the average time required to start. Screen 8: Displays the average current during start. Screen 9: Displays the measured I
2
T required to start
the motor.
Screen 10: Displays the amount of time required to start
the motor during the last successful start.
MOTOR LOAD % OF FLA
FLA: ### %
LINE FREQUENCY:: ##.##
PHASE ORDER: ###
THERMAL REGISTER
REMAINING: ### %
THERMAL CAPACITY TO START: ### %
AVERAGE START TIME TIME: ##.# SECS
AVG START CURENT
: ###### AMPS
Screen 3
Screen 4
Screen 5
Screen 6
Screen 7
Screen 8
TOSHIBA - 60
I*I*T TO START I*I*T: #######
LAST START
TIME: ##.# SEC
Screen 9
Screen 10
Page 67
TX Series 48 - 1250A
MP.2 Metering (Metering Page 2)
Displays the TX Series statistical voltage metering information.
MENU
Screen 1: Displays Phase A, B, C and Power Factor.
Note: P/F: N/A Motor stopped
P/F: LG #.## (Lagging) P/F: LD #.## (Leading)
Screen 2: Displays Phase A, B, C and Ground Fault
Current.
Screen 3: Displays KW and KVA. Screen 4: Displays KVAR and Power Factor. Screen 5: Displays Peak On and KW demand. Screen 6: Displays Peak On and KVA demand. Screen 7: Displays Peak On and KVAR demand.
Note: P/F: N/A Motor stopped
P/F: LG #.## (Lagging) P/F: LD #.## (Leading)
Screen 8: Displays Peak On and Ampsdemand. Screen 9: Clears Demand Values. Screen 10: Displays the Megawatts used per hour.
METERING PAGE 2 VOLTAGE & POWER DATA
Screen 1
Vab: ### Vbc: ### Vca: ### P/F: ## #.##
Screen 2
IA: ##### IB: #####
IC: ##### G/F:###.#
Screen 3
kW: ##### kVA: #####
Screen 4
kVAR: #####
P/F: ## #.##
Screen 5
PEAK ON: ##/## ##:## kW: #####
Screen 6
PEAK ON: kVA: #####
Screen 7
PEAK ON: kVAR: #####
Screen 8
PEAK ON: AMPS: #####
##/## ##:##
##/## ##:##
##/## ##:##
Screen 11: Press Enter to clear statistics on MWH
values.
Screen 9
PRESS ENTER TO CLEAR
DEMAND VALUES
Screen 10
MWH USED
: #####
Screen 11
PRESS ENTER TO CLEAR MWH VALUES
TOSHIBA- 61
Page 68
TX Series 48 - 1250A
METERING PAGE 3 RTD VALUES
MP.3 RTD Values (Metering Page 3)
Displays the RTD information (when RTD option is supplied)
Screen 1: Displays the hottest stator RTD (#1 - 6
depending upon number of RTDs used for stator).
Screen 2: Displays the hottest non-stator RTD (#7-12 if
#1-6 is used for stator).
Screen 3: Displays the temperature of stator phase A1
in °C and °F.
Screen 4: Displays the maximum temperature for RTD
#1 since the last command to clear the thermal register.
Screen 5 - 26: Same as Screens 3 - 4 Screen 27: Allows the user to clear the maximum
temperature register upon entering the setpoint level 3 password.
Screen 28: Displays the measured run cool time in
minutes.
Screen 29: Displays the measured stopped cool time in
minutes.
HOTTEST STATOR RTD#: # @ ### C
Screen 2
HOTTEST NON-STATOR RTD#: # @ ### C
Screen 3
STATOR PHASE A1 RTD #1: ### C = ### F
Screen 5
STATOR PHASE A2 RTD #2: ### C = ### F
Screen 7
STATOR PHASE B1 RTD #3: ### C = ### F
Screen 9
STATOR PHASE B2 RTD #4: ### C = ### F
Screen 11
STATOR PHASE C1 RTD #5: ### C = ### F
Screen 13
STATOR PHASE C2 RTD #6: ### C = ### F
Screen 15
END BEARING RTD #7: ### C = ### F
Screen 17
SHAFT BEARING RTD #8: ### C = ### F
Screen 4
MAX TEMP SINCE CLEAR RTD #1: ### C
Screen 6
MAX TEMP SINCE CLEAR RTD #2: ### C
Screen 8
MAX TEMP SINCE CLEAR RTD #3: ### C
Screen 10
MAX TEMP SINCE CLEAR RTD #4: ### C
Screen 12
MAX TEMP SINCE CLEAR RTD #5: ### C
Screen 14
MAX TEMP SINCE CLEAR RTD #6: ### C
Screen 16
MAX TEMP SINCE CLEAR RTD #7: ### C
Screen 18
MAX TEMP SINCE CLEAR RTD #8: ### C
TOSHIBA - 62
Screen 19
RTD #9 RTD #9: ### C = ### F
Screen 21
RTD #10 RTD #10: ### C = ### F
Screen 23
RTD #11 RTD #11: ### C = ### F
Screen 25
RTD #12 RTD #12: ### C = ### F
Screen 27
PRESS ENTER TO CLEAR MAX TEMP REGS
Screen 28
MEASURED RUN COOL TIME: ### MIN
Screen 29
MEASURED STOPPED COOL TIME: ### MIN
Screen 20
MAX TEMP SINCE CLEAR RTD #9: ### C
Screen 22
MAX TEMP SINCE CLEAR RTD #10: ### C
Screen 24
MAX TEMP SINCE CLEAR RTD #11: ### C
Screen 26
MAX TEMP SINCE CLEAR RTD #12: ### C
Page 69
TX Series 48 - 1250A
MP.4 Status (Metering Page 4)
Displays the present status of the TX Series soft start.
MENU
Screen 1: Displays the present state of the unit as
follows:
Screen 2: Displays the amount of time remaining
before an overload trip will occur.
Screen 1 Note: CURRENT STATUS Screens include:
1. MOTOR STOPPED READY TO START
2. MOTOR STARTING MULT. OF FLA
3. MOTOR RUNNING AT ###.## X FLA
4. LAST TRIP CAUSE NONE (or trip cause)
5. PROGRAMMING SETPOINTS
6. MOTOR STATUS UNKNOWN STATE ### (displays relay state upon error)
Screen 3: Displays the amount of time remaining from
a thermal inhibit. The inhibit time comes from the amount of thermal register remaining versus the amount of thermal capacity required to start.
METERING PAGE 4 STATUS
Screen 1 (See note at left)
(CURRENT STATUS)
Screen 2
O/L TRIP LEFT TO TRIP: ###### SEC
Screen 3
THERM INH TIME LEFT : #### MIN
Screen 4
COAST DOWN TIMER TIME LEFT: #:## MIN
Screen 5
TIME BETWEEN STARTS TIME: #:## MIN
Screen 6
STARTS PER HOUR TIME ## ## ## ## ## ## ##
Screen 4: Displays the coast down time remaining
(Backspin time). The time remaining depends upon the user setting in Setpoint Page 8, Coast Down Time.
Screen 5: Displays the amount of time remaining before
a start command can be given.
Screen 6: If the number of starts per hour has
exceeded the setting.
TOSHIBA- 63
Page 70
TX Series 48 - 1250A
MP.5 Event Recorder - 60 Events (Metering Page 5)
MENU
Screen 1 Screen 1a
METERING PAGE 5 Event Recorder (60 event)
1st Event
2nd Event
59th Event
60th Event
:<cause of event> :##/##/## ##:##
:<cause of event> :##/##/## ##:##
:<cause of event> :##/##/## ##:##
:<cause of event> :##/##/## ##:##
All events will be viewed from oldest event in buffer to most recent event.
The events are listed from oldest to most recent.
Screen 1: Displays the event (i.e., Imbalance Trip) with the
date and time it occurred.
IA: ###### IB: ###### IC: ###### G/F: ####
IA: ###### IB: ###### IC: ###### G/F: ####
IA: ###### IB: ###### IC: ###### G/F: ####
IA: ###### IB: ###### IC: ###### G/F: ####
Screen 1b
Vab: ###### Vbc: ###### Vca: ###### P/F: ####
Vab: ###### Vbc: ###### Vca: ###### P/F: ####
Vab: ###### Vbc: ###### Vca: ###### P/F: ####
Vab: ###### Vbc: ###### Vca: ###### P/F: ####
Screen 1a: Displays the current at Phase A, B, C and the
ground fault at the time of the trip.
Screen 1b: Displays the Vab, Vbc, Vca and power factor at
the time of trip.
TOSHIBA - 64
Page 71
TX Series 48 - 1250A
MP.6 Last Trip (Metering Page 6)
Displays the information regarding the last trip.
MENU
Screen 1: Displays the cause of the last trip. Screen 2: Displays the measured phase current at the
time of the trip.
Screen 3: Displays the Vab, Vbc, Vca and power
factor at the time of trip.
Screen 4: Displays the imbalance percentage, the
frequency and the kW at the time of the trip.
Screen 5: Displays the hottest stator RTD temperature
(when RTD option present) at time of the trip.
Screen 6: Displays the hottest non-stator RTD
temperature (when RTD option present) at the time of the trip.
METERING PAGE 6 LAST TRIP
Screen 1
(cause of trip) (value at time of trip)
Screen 2
Ia: #### Ib: #### Ic: #### G/F: ####.#
Screen 3
Vab: ###### Vbc: ###### Vca: ###### P/F: ######
Screen 4
I/B: ## % Hz: ##.# KW: ########
Screen 5
HOTTEST STATOR RTD# # @ ### C
Screen 6
HOTTEST NON-STATOR RTD# # @ ### C
TOSHIBA- 65
Page 72
TX Series 48 - 1250A
MENU
METERING PAGE 7 STATISTICS
MP.7 Statistics (Metering Page 7)
Displays the TX Series statistical trip information.
Screen 1: Displays the total of megawatt hours. Screen 2: Displays the accumulated total running
hours.
Screen 3: Clears the total running hour count. Screen 4: Displays the total number of trips since the
last clearing the statistical data and the total number of short circuit trips.
Screen 5: Displays the numbers of start overload and
run overload trips since the last clearing of the statistical data.
Screen 6: Displays the number of frequency trips and
Imbalance trips.
Screen 7: Displays the number of overcurrent trips Screen 8: Displays the number of Stator and non-Stator
RTD Trips
Screen 9: Displays the number of Ground Fault Hi and
Lo Set trips
Screen 10: Displays the number of acceleration time
trips.
Screen 11: Displays the number of start curve trips Screen 12: Displays the number of I Screen 13: Displays the number of learned start curve
trips.
Screen 14: Displays the number of fail shunt trips. Screen 15: Displays the number of phase loss trips. Screen 16: Displays the number of tachometer
acceleration trips.
Screen 17: Displays the number of undervoltage and
overvoltage trips.
Screen 18: Displays the number of power factor trips. Screen 19: Displays the number of phase reversal trips. Screen 20: Displays the number of external input #1
trips.
Screen 21: Displays the number of external input #2
trips.
Screen 22: Displays the number of external input #3
trips.
Screen 23: Displays the number of external input #4
trips.
Screen 24: Requires a Security Level 2 password to
clear the statistics.
2
T start curve trips
Screen 1
MWH TOTAL
: ###
Screen 2
RUNNING HOURS TOTAL TIME: ## ## HOURS
Screen 4
TOTAL TRIPS: ###
S/C TRIPS: ###
Screen 5
START O/L TRIPS: ### RUN O/L TRIPS: ###
Screen 6
FREQUENCY TRIPS: ###
I/B TRIPS: ###
Screen 7
OVERCURRENT TRIPS: ###
Screen 8
STATOR TRIPS: ### NON-STATOR TRIPS: ###
Screen 9
G/F HISET TRIPS: ### G/F LOSET TRIPS: ###
Screen 10
ACCELERATION TIME TRIPS: ###
Screen 11
START CURVE
TRIPS: ###
Screen 12
I*I*T START CURVE TRIPS: ###
Screen 13
LEARNED START CURVE TRIPS: ###
Screen 14
FAIL SHUNT TRIP TRIPS: ###
Screen 15
PHASE LOSS TRIP TRIPS: ###
Screen 3
PRESS ENTER TO CLEAR RUN HOURS
Screen 17
U/V TRIPS: ### O/V TRIPS: ###
Screen 18
POWER FACTOR TRIPS: ###
Screen 19
PHASE REVERSAL TRIPS: ###
Screen 20
EXT INP #1: ###
Screen 21
EXT INP #2: ###
Screen 22
EXT INP #3: ###
Screen 23
EXT INP #4: ###
Screen 24
PRESS ENTER TO CLEAR STATISTICS
LEVEL 2 Password required
Screen 16
TOSHIBA - 66
TACH ACCEL TRIP TRIPS: ###
Page 73
TX Series 48 - 1250A
Short circuit or grou nd fault
,
Loss of 1or more phas es of
Chapter 7 - Maintenance and Troubleshooting
The TX Series is designed to be a maintenance-free product. However, as with all electronic equipment, the unit should be checked periodically for dirt, moisture or industrial contaminants. These can cause high voltage arc-over , carbon tracking or prevent proper cooling of the SCR heat sinks. All bolt s should be checked annually for proper tightness using an accurate torque wrench .
Note: If the unit is installed in a contaminated environment and forced air cooling is used, blower filters must be checked and cleaned regularly to insure proper air flow and cooling of the enclosure.
7.1 - Failure Analysis
When a fault occurs, the LCD will display the fault error and the listed LED and AUX Relay will be lit. Please clear all faults before attempting to restart the unit. Note: If the problem persists after the required programming changes have
been made, and all corrective action has been taken, please contact the factory for assistance.
Problem CPU LCD Display LED
Short Circuit Trip
Single Phase Trip
Thermostat trips
during run
SHORT CIRCUIT TRIP
SINGLE PHASE TRIP
(Check LCD display for
possible fault indicators)
EXTERNAL TRIP ON
THERMOSTAT
Aux
Relay
Trip
Trip
Trip AUX1
AUX1
AUX1
Possibl e Cause Solutions
in motor/cabling
Phase Loss Repai r cause of ph a s e l oss
Branch circuit protection
not correctly sized
Faulty main circuit board
Faulty SCRs
Single phase incom i ng
power
Faulty SCRs
Fan(s) not functioning
(If supplied)
Heatsink coated with dirt
Overcurrent on unit
Environment temperature
over 122° F (ambient
temperature for chas sis
units) or over 104°F
(ambient temperat ure for
enclosed version
Locate and remove short or ground
Verify correct sizing of branch circuit protection
Remove power and replace main circuit board.
Remove power and test SCR(s). Refer to Section 7.1.1 for the SCR test ing procedure
Correct problem with incomi ng power
Remove power and test SCR(s). Refer to Section 7.1.1 for the SCR test ing procedure
If fans have power, remove power and replace fan(s). If fan s do not have power find cause of power loss and repair.
Remove power and clean hea ts i nk with high pressure air (80 - 100 psi max clean and dry air)
Verify that running current do es not exceed unit rating
Place unit in environmen t t em perature less than 122°F for panel version or less than 104°F for enclosed version.
Phase Loss
PHASE LOSS
Trip AUX1
TOSHIBA- 67
Bypass failed to close Check bypass co ntactor and wiring
power from utility or
generated power
Blown power fuses Check for short circuits
Check power source
Page 74
TX Series 48 - 1250A
.
Problem CPU LCD Display LED
Overload
Stall prevention
Under Current
Trip
Self-test Failure
Line Frequency
Trip
OVERLOAD TRIP Trip AUX1
ACCEL TIME TRIP
UNDER CURRENT TRIP
SELF-TEST FAILURE
OVER OR UNDER
FREQUENCY TRIP
Aux
Relay
Trip AUX1
Trip
Trip
AUX1
AUX1
Trip AUX1
Possibl e Cause Solutions
Improper programming
Possible load damage or
jammed load
Improper setting for motor
load condition
Damaged load Check for load failure
Improper programming or
unloaded motor
Failed CPU or Main Firing
Board
Vibration Check internal wiring connections
Generator Power Problem
or grid change
Improper programming Check program setpoints
Check motor na m ep l ate versus programme d parameters
Check motor currents
Verify current limit setting
Check setpoint settings Check load
Contact factory
Troubleshoot and repair generator Contact utilities company Main board failure
Three phase power removed from Main Board
Any Ground Fault
Trip (Pending)
Motor stopped
during run
Control circuit fuses blow after control power is
applied.
GROUND FAULT
HI-SET OR LO-SET
(Pending)
Check for fault indication Trip AUX1
None None None
Trip
AUX1
Any wire going to ground (I.e. stator ground, motor ground, soft start ground)
High vibration or loose
connections
Warning:
condition is clear ed on the load before attempting to resta rt the m ot or
This is a serious fault condition. Ensure that the fault
Load shorted/ ground ed/
faulted
Faulty main circuit board Replace the main circuit board
Short in c ontrol circuit
Wrong c ont rol voltage
Check with meggar or Hi-pot motor leads and motor
Check internal conne ct ions
Remove power and repair.
Remove power, locate and rem ove this short
Apply the correct voltage t o t he control circuit
TOSHIBA - 68
Page 75
TX Series 48 - 1250A
6
Problem CPU LCD Display LED
M o t o r will not st a r t
An y fault ind ic ation
message
Trip
Aux
Relay
AUX1
Possible Cause Solutions
No control voltage applied
to control board
Control power transformer
failu re or CP T fuse failure
Start circuit wired
incorrectly
No start command Apply the start command
No 3 phase line voltage Apply 3 phase line voltage to the unit
Shorted SC R in starter
Faulty control logic
Failure of main circuit
board
Fa u lty moto r
Apply control voltage to TB1 pins 1 and on the power board
Remove power and replace the power transformer or the CPT fuse
Remove power and correct the start circuit wiring
Remove power and test SCR(s). Refer to Section to 7.1.1 for the SCR testing procedure
Remove power and repair the control logic .
Replace the main circuit board
Ch e ck the motor and the motor connections
Motor vibrates/
Motor growls
while starting or
extremely unbalanced motor currents run mode
IMBALANCE TRIP
IMBALANCE ALARM
Trip
Alarm
AUX1 AUX2
Faulty SCR s
Faulty gate/cathode on
SCRs
Faulty main circuit board Replace the main circuit board
Faulty motor/wiring Troubleshoot and repair/replace wiring
Faulty main circuit board Replace the main circuit board
Remove power and perform the SCR device checks
Remove power and test SCR(s). Refer to Section 7.1.1 for the SCR testing procedure
TOSHIBA- 69
Page 76
TX Series 48 - 1250A
WARNING
7.2 SCR Testing Procedure
Failure to remove both line and control power before starting this procedure may cause personal injury or death.
Remove both line power and control power from the unit and lock out. Disconnect any two motor load leads and any two line leads. Disconnect the SCR connections to main control board J5, J6 and J7. Refer the Chapter 6 for the main control board layout. Note the type of color coding of the wires connected to J5, J6 and J7. Toshiba uses two possible configurations. Both configurations have 4 wires going to each plug. The first configuration consists of 4 wires color coded black, yellow, grey and white. The second configuration consists of 4 wires color coded red, white, red, white.
The testing procedure for SCRs is comprised of two separate tests. The first one tests the anode to cathode integrity of the SCR by performing the following ohm checks:
The second tests the gate to cathode integrity of the SCR. The chart below indicates good versus bad readings.
Note: If any of the above readings are out of specifications, replace the faulty SCR.
Note: The best way to test an SCR is with an SCR Tester and look for leakage current less than the manufacturer specified values.
TOSHIBA - 70
Page 77
TX Series 48 - 1250A
WARNING
7.3 Replacing SCR Devices
Two types of SCRs are used in the TX Series depending on the horsepower/ amperage rating of the unit. Isolated SCRs are used in smaller units and “hockey puck” type SCRs are used in larger units. (Refer to Chapter 9 for the main control board layout.)
7.3.1 Changing an Isolated SCR
• Remove both line and control power from unit, tag and lock out. Failure to remove both line and control power
before starting this procedure may cause personal injury or death.
• Label the location of wires connected to the SCR.
• Remove the mounting screws, lugs and associated wiring from the
existing SCR.
• Make sure the surface to which the power module mounts is clean
and free from dirt, nicks and scratches.
• Apply thermal grease uniformly along the mounting surface of the
SCR. Spread the grease thinly (3 mil thick) to completely cover the base of the power module and minimize air pockets. The grease must be free of contamination.
• Replace the screws and tighten down firmly. All mounting screws
should be 44 lb/in. Units with a maximum amperage rating of up to
48A, should use 26 lbs/in busbar and power lugs. Units with a maximum amperage of 78A - 120A should use 44 lbs/in busbar and power lugs.
• Reconnect all busbars, lugs and wires. Check to make sure the gate and cathode are wired correctly . Use the following chart to verify the wiring of J5, J6 and J7:
• After verifying that all wiring is correctly connected, test the SCR.
TOSHIBA- 71
Page 78
TX Series 48 - 1250A
WARNING
7.3.2 Changing a Hockey Puck T ype SCR
Remove both line and control power from unit, tag and lock out.
Failure to remove both line and control power before starting this procedure may cause personal injury or death.
Toshiba uses two types of clamps with gauges for reading the amount of force on the device. The first type of force gauge uses a spin washer. When the proper force is applied, the washer will be free to spin. The second type of gauge uses a step indicator on the end of the lever. Before proceeding, note the type of clamp used and, if the clamp has a step indicator, document the position of the indicator before removing the clamp to facilitate proper mounting of the new SCR device.
Label the location of the wires connected to the SCR.
Remove any lugs, snubbers, printed circuit boards (refer to section X) and associated wiring that may get in the way of reaching the faulty SCR. Document the location and wiring of all parts before removing them to facilitate the reinstallation of the devices later .
Document the position of the indicator on the SCR clamp. Then remove the top clamp holding the SCR stack together. Remove the top heatsink. Use extreme caution when handling the heat sink so it does not become dented or damaged.
Remove the faulty SCR device, noting the direction in which the SCR is oriented. The new SCR puck must be inserted in the same direction.
Make sure the SCR mounting surface, tools, and hands are clean and free from dirt, nicks, and scratches. Do not sand or scrape SCR mounting surface. If necessary, super fine Scotch Brite p ads can be used to clean the heatsink before installing the new SCR.
Apply a thin (3 mil thick) layer of thermal grease uniformly along both sides of the SCR. Spread the grease to cover the entire surface
of both sides of the SCR in a manner that minimizes air pockets.
The grease must be free of contamination.
Locate the centering pin in the bottom and top of the heatsink and center it in the SCR hole (making sure that the SCR is pointed in the
same direction as the SCR that was removed in step 6). Locate the
centering pin in the top heatsink and center it in the SCR hole.
Caution: If center pin is not placed correctly it will damage the SCR and the heat sink. Hand tighten the clamps evenly so
that the same number of threads appear at both ends of the U­clamp. Tighten the clamp 1/4 turn at a time alternating sides of the U-clamp until the correct force is reached. Check the gauge or spin washer every time the clamp nuts are tightened 1/4 turn to ensure that the SCR is not over torqued. The gauge reading should be similar
to the initial reading taken in step 2. If the clamp uses the spin
washer gauge, verify that the washer spins freely after clamping.
TOSHIBA - 72
Page 79
TX Series 48 - 1250A
Once proper force is reached make sure that the SCR pucks are securely held between the heatsinks and aligned evenly .
Replace any lugs, MOVs, snubbers, power straps, printed circuit boards and associated wiring that was removed in step 4. Use the following chart to verify wiring of J5, J6 and J7:
After verifying that all wiring is correctly connected, test the SCR and then test the unit.
7.4 Replacing the Main Control Board
The printed circuit board is not intended to be field repaired. If the board is faulty , the entire board should be replaced using the following procedure:
(See Chapter 6 for the main control board layout.)
• Remove three phase power and control power from the unit and lock out.
• Remove plugs and tag plugs with connector numbers.
• Remove control wires from terminals and tag wires with terminal numbers.
• Note the settings of all jumpers.
• Remove the mounting screws.
• Remove the old printed circuit board.
• Mount the new printed circuit board.
• Install the mounting screws.
• Set the jumpers to the same position as on the old board.
• Install the control wires onto correct terminals per tag sequence.
• Install the plugs.
• Apply power to the unit and program all parameters to values in old board.
• Test
TOSHIBA- 73
Page 80
TX Series 48 - 1250A
7.5 - Interconnect Drawing
Connections for Residual Ground
CON2
CON1
AUX1 (Fault)
AUX2 (Alarm)
AUX3
AUX4
TOSHIBA - 74
Page 81
TX Series 48 - 1250A
2 or 4 wire Modbus
Communication & Keypad Board
Unit #2
2 or 4 wire Modbus TB1
Note: J1 can alternately be connected to remote power supply
Unit #3
2 or 4 wire Modbus TB1
PC Stations
2 or 4 wire Modbus
Tach Input (+)
Tach Input (-)
Analog Output #2 (+)
Analog Output #1 (+)
Analog Output #1 (-)
Analog Output #2 (-)
Cal. Input (+)
Cal. Input (-)
Program Enable Input (+)
Program Enable Input (-)
Thermal Reg. Dump (+)
Thermal Reg. Dump (-)
Fault Reset Input (+)
Fault Reset Input (-)
User Input #1 (+)
User Input #1 (-)
User Input #2 (+)
User Input #3 (+)
User Input #3 (-)
User Input #2 (-)
User Input #4 (+)
User Input #4 (-)
Thermostat
Computer with RS232 Communication Port
RTD Board
TOSHIBA- 75
Page 82
TX Series 48 - 1250A
WARNING
7.6 MAINTENANCE PROGRAM
In order to ensure continued reliable and safe operation of the equipment, a program of periodic maintenance must be established. Operating and environmental conditions will usually dictate the frequency of inspection required. NFP A Publication 70B “Electrical Equipment Maintenance” may be used as a guide for setting up the maintenance program.
DANGER
WARNING
Contact with energized components can cause severe injury, death and property damage. T urn off and lock-out primary and control circuit power
before servicing.
Improper maintenance can cause severe injury, death and property damage. Only qualified and authorized persons are to install, operate or service this
equipment.
Grease is conductive. Do not allow grease or any other substances to contaminate insulating materials. Contaminated insulators can allow a short-circuit or ground fault to occur.
NOTE: Refer to the SAFETY section of this manual for important information.
MAINTENANCE RECORD
Keep a permanent record of all maintenance work. At a minimum, this record should include information on:
1) Items inspected
2) Reports of any testing
3) Equipment condition
4) Corrective actions or adjustments
5) Date of work
6) Comments
WARNING
The degree of detail of the record will depend somewhat on the operating conditions.
SERVICING EQUIPMENT
For your safety , turn off and lock out main and control circuit power before servicing the starter. Cert ain minimum safety procedures must be followed:
1) Only qualified personnel should attempt this service.
2) Never perform service on or next to exposed components energized with line voltage.
Failure to adhere to these safety procedures can result in severe injury, death and property damage.
TOSHIBA - 76
Page 83
TX Series 48 - 1250A
7.7 DISPOSAL/STORAGE
DISPOSAL
Contact your state environmental agency for details on disposal of electrical components and packaging in your particular area.
STORAGE
If the starter is to be stored for any length of time prior to installation, the following precautions should be taken:
1) The original packing should be restored, if possible.
2) Do not subject the equipment to moisture or sun rays. S tore in cool, clean, and dry location.
3) Place a dust cover over the starter packaging to protect against dirt and moisture.
4) S tore in an upright position.
INSPECTION DURING STORAGE
Routine scheduled inspection is necessary if storage is for an extended period. The unit should be checked for condensation, moisture, corrosion, and vermin.
Prior to installation, the starter should be carefully examined for evidence of physical damage, corrosion, or other deterioration.
The MAINTENANCE section of this manual describes various types of inspections recommended for this starter during the operation period.
TOSHIBA- 77
Page 84
TX Series 48 - 1250A
SYNCHRONOUS TYPEINDUCTION T YPE
Appendix A - Reference Section
T ypical Full Load Current for 3 Phase Motors
SQUIRREL CAGE AND WOUND ROTOR UNITY POWER FACTOR*
(AMPERES)(AMPERES)
HP 115V 200V 208V 230V 460V 575V 2300V 230V 460V 575V 2300V
0.5 4.4 2.5 2.4 2.2 1 .1 0.9
0.75 6.4 3.7 3.5 3.2 1.6 1.3 1 8.4 4.8 4.6 4.2 2.1 1.7
1.5 12 6.9 6.6 6 3 2.4 2 13.6 7.8 7.5 6.8 3.4 2.7 3 11 10.6 9.6 4.8 3.9 5 17.5 16.7 15.2 7.6 6.1
7.5 25.3 24.2 22 11 9
10 32.2 30.8 28 14 11 15 48.3 46.2 42 21 17 20 62.1 59.4 54 27 22 25 78.274.8683427 532621 30 92 88 80 40 32 63 32 26 40 120 114 104 52 41 83 41 33 50 150 143 130 65 52 104 52 42 60 177 169 154 77 62 16 123 61 49 12
75 221 211 192 96 77 20 155 78 62 15 100 285 273 248 124 99 26 202 101 81 20 125 359 343 312 156 125 31 253 126 101 25 150 414 396 360 180 144 37 302 151 121 30 200 552 528 480 240 192 49 400 201 161 40 250 302 242 60 300 361 289 72 350 414 336 83 400 477 382 95 450 515 412 103 500 590 472 118
* For 90 and 80 percent power factor, the figures shall be multiplied by 1.1 and 1.25, respectively.
T ypical Maximum Allowable S tart and Stops per hour
ALLOWABLE STARTS AND STARTING INTERVALS
DESIGN A AND B MOTORS
HP
1 151.275305.838341533
1.5 12.9 1.8 76 25.7 8.6 38 29.1 23 34 2 11.5 2.4 77 23 11 39 26.1 30 35 3 9.9 3.5 80 19.8 17 40 22.4 44 36 5 8.1 5.7 83 16.3 27 42 18.4 71 37
7.5 7 8.3 88 13.9 39 44 15.8 104 39
10 6.2 11 92 12.5 51 46 14.2 137 41 15 5.4 16 100 10.7 75 50 12.1 200 44 20 4.8 21 110 9.6 99 55 10.9 262 48 25 4.4 26 115 8.8 122 58 10 324 51 30 4.1 31 120 8.2 144 60 9.3 384 53 40 3.7 4 130 7.4 189 65 8.4 503 57 50 3.4 49 145 6.8 232 72 7.7 620 64 60 3.2 58 170 6.3 275 85 7.2 735 75
75 2.9 71 180 5.8 338 90 6.6 904 79 100 2.6 92 220 5.2 441 110 5.9 1181 97 125 2.4 113 275 4.8 542 140 5.4 1452 120 150 2.2 133 320 4.5 640 160 5.1 1719 140 200 2 172 600 4 831 300 4.5 2238 265 250 1.8 210 1000 3.7 1017 500 4.2 2744 440
2 POLE 4 POLE 6 POLE
ABCABCABC
TOSHIBA - 78
Page 85
TX Series 48 - 1250A
MAXIMUM LOCKED-ROTOR CURRENTS
T ypical Maximum Locked Rotor Current
NEMA B, C & D
THREE PHASE SQUIRREL CAGE MOTORS
NEMA DESIGNS B, C & D
HP
0.5 232010 8
0.75 29 25 12 10 1 34301512
1.5 46402016 2 57502520 3 74643226 5 106 92 46 37
7.5 146 127 63 51
10 186 162 81 65 15 267 232 116 93 20 333 290 145 116 25 420 365 182 146 30 500 435 217 174 40 667 542 290 232 50 834 725 362 290 60 1000 870 435 348 87 50
75 1250 1085 542 434 108 62 100 1665 1450 725 580 145 83 125 2085 1815 907 726 181 104 150 2500 2170 1085 868 217 125 200 335 2900 1450 1160 290 167 250 4200 3650 1825 1460 365 210 300 5060 4400 2200 1760 440 253 350 5860 5100 2550 2040 510 293 400 6670 5800 2900 2320 580 333 450 7470 6500 3250 2600 650 374 500 8340 7250 3625 2900 725 417
200V 230V 460V 575V 2300V 4000V
RATED VOLTAGE
NEMA E
THREE-PHASE SQUIRREL CAGE MOTORS
NEMA DESIGN E
HP
0.5 232010 8
0.75 29 25 13 10 1 35301512
1.5 46402016 2 58502520 3 84733729 5 1140 122 61 49
7.5 210 183 92 73
10 259 225 113 90 15 388 337 169 135 20 516 449 225 180 25 646 562 281 225 30 775 674 337 270 40 948 824 412 330 50 1185 1030 515 412 60 1421 1236 618 494 124 71
75 1777 1545 773 618 155 89 100 2154 1873 937 749 187 108 125 2692 2341 1171 936 234 135 150 3230 2809 1405 1124 281 162 200 4307 3745 1873 1498 375 215 250 5391 4688 2344 1875 469 270 300 6461 5618 2809 2247 562 323 350 7537 6554 3277 2622 655 377 400 8614 7427 3745 2996 749 431 450 9691 8427 4214 3371 843 485 500 10767 9363 4682 3745 936 538
200V 230V 460V 575V 2300V 4000V
RATED VOLTAGE (AMPS)
TOSHIBA- 79
Page 86
TX Series 48 - 1250A
Cooling Consideration for Maintaining Ambient Temperature
RATED CURRENT HEAT GENERATED MINIMUM CFM MINIMUM EXP. S.S.
UNITS = AMPS UNITS = WATTS UNITS = CFM UNITS = SQ.FT.
48 216 38 54
78 351 62 88 120 540 95 135 180 810 143 203 220 990 174 248 288 1296 228 324 414 1863 328 466 476 2138 376 534 550 2475 436 619 718 3231 569 808
1006 4527 797 1132 1150 5175 911 1294 1250 5625 990 1406
TOSHIBA - 80
Page 87
TX Series 48 - 1250A
50 - 100% of Unit Max Current Rating (Model
Appendix B - Record of Setpoint Adjustment s
Setpoint
Page
Page 1
Basic Configuration
Setpoint
Page
Page 2
Starter Configuration
Security
Level
Level 1
No Passowrd Required
Security
Level
Level 1
No Passowrd Required
Description
Motor Full Load Amps (FLA) Model dependent Service Factor 1.15 1.00 – 1.3
Overload Class 10 O/L Class 5-30 NEMA Design B A-F Insulation Class B A, B, C, E, F, H, K, N, S Line Voltage 480 208 to 600 Line Frequency 60 50 or 60 HZ
Description
Start Control Mode Start Ramp 1
Jog Voltage Off 5-75%, Off Start Ramp #1 Type Voltage Current, Voltage, Off Initial Voltage #1 20% 0-100% Ramp Time #1 10 sec 0-120 sec Current Limit #1 350% FLA 200-600 % Initial Current #1 200% FLA 0-300% Ramp Time #1 10 sec 0-120 sec Maximum Current #1 350% FLA 200-600 % Start Ramp #2 Type Off Current, Voltage, Off Initial Voltage #2 60% 0-100 % Ramp Time #2 10 sec 0-120 sec Current Limit #2 350 % FLA 200-600 % Initial Current #2 200% FLA 0-600 % Ramp Time #2 10 sec 0-120 sec Maximum Current #2 350% FLA 200-600 % Kick Start Type Off Voltage or Off Kick Start Voltage 65% 10-100 % Kick Start Time 0.50 sec 0.10-2.00 Deceleration Disabled Enabled or Disabled Start Deceleration Voltage 60% 0-100 % Stop Deceleration Voltage 30% 0-59 % Deceleration Time 5 sec 1-60 sec Timed Output Time Off 1-1000 sec, Off Run Delay Time 1 Sec 1-30 sec, Off At Speed Delay Time 1 Sec 1-30 sec, Off Bypass Pull-in Current 100% FLA 90 - 300%
Factory Setting
Default
Factory Setting
Default
Range Setting
and Service Factor dependent)
Range Setting
Jog, Start Ramp 1, Start Ramp 2, Custom Accel Curve, Start Disabled, Dual Ramp
TOSHIBA- 81
Page 88
TX Series 48 - 1250A
Page
Level
Default
Setpoint
Page 3
Phase and Ground Settings
Security
Level 2
Password Protecti on
Description
Imbalance Alarm Level 15% FLA 5-30 %, Off Imbalance Alarm Delay 1.5 sec 1.0-20.0 sec Imbalance Trip Level 20% 5-30 %, Off Imbalance Trip Delay 2.0 sec 1.0-20.0 sec Undercurre nt Alarm Level Of f 10-90 %, Off Undercurrent Alarm Delay 2.0 sec 1.0-60.0 sec Overcurrent Alarm Level Off 100-300 %, Off Overcurrent Alarm Delay 2.0 sec 1.0-20.0 sec Overcurrent Trip Level Off 100-300 %, Off Overcurrent Trip Delay 2.0 sec 1.0-20.0 sec Phase Loss Trip Disabled Enabled or Disabled Phase Loss Trip Delay 0.1 sec 0-20.0 sec Phase Rotation Detection Enabled Enabled Only Phase Rotation ABC ABC Ground Fault Alarm Level Off 5-90 %, Off Ground Fault Alarm Delay 0.1 sec 0.1-20.0 sec Ground Fault Loset Trip Level Off 5-90 %, Off Ground Fault Loset Trip Delay 0.5 sec 0.1-20 sec Ground Fault Hiset Trip Level Off 5-90 %, Off Ground Fault Hiset Trip Delay 0.008 sec 0.008-0.250 sec Overvoltage Alarm Level Off 5 -30%, Off Overvoltage Al ar m Delay 1.0 sec 1.0-30.0 sec Overvoltage Trip Level Off 5-30%, Off Overvoltage Tr i p Del ay 2.0 sec 1.0-30.0 sec Undervoltage Alarm Level Off 5-30%, Off Undervoltage Alarm Delay 1 .0 sec 1.0-30.0 sec Undervoltage Trip Level Off 5-30%, Off Undervoltage Trip Delay 2.0 sec 1.0-30.0 sec Line Frequency Tr ip Window Disabled 0-6 Hz, Disabled Line Frequency Trip Delay 1.0 sec 1.0-20.0 sec P/F Lead P/F Alarm Off 0.1-1.00, Off P/F Lead Alarm Delay 1.0 sec 1-120 sec P/F Lead P/F Trip Off .01-1.00, Off P/F Lead Trip Delay 1.0 sec 1-120 sec P/F Lag P/F Alarm Off .01-1.00, Off P/F Lag Alarm Delay 1.0 sec 1-120 sec P/F Lag P/F Trip Off .01-1.00, Off P/F Lag Trip Delay 1.0 sec 1-120 sec Power Demand Period 10 min 1 - 60 min KW Demand Alarm Pickup Off KW Off, 1-100000 KVA Demand Alarm Pickup Off KVA Off, 1-100000 KVAR Demand Alarm Pickup Off KVAR Off, 1-100000 Amps Demand Alarm Pickup Off Amps Off, 1-100000
Factory Setting
Range Setting
TOSHIBA - 82
Page 89
TX Series 48 - 1250A
Setpoint
Page
Page 4
Relay Assignments
Security
Level
Level 2
Password Protecti on
Description
O/L Trip Trip Only None None I/B Trip Trip None None S/C Trip Trip Only None None Overcurrent Trip Trip None None Stator RTD Trip Trip None None Bearing RTD Trip Trip None None G/F Hi Set Trip Trip None None G/F Lo Set Trip Trip None None Phase Loss Trip Trip None None Accel. Time Trip Trip O n ly Non e None Start Curve Trip Trip Only None None Over Frequency T rip Trip None None Under Frequency Trip Trip None None I*I*T Start Curve Trip None None Learned Start Curve Trip None None Phase Reversal Trip None None Overvoltage Trip Trip None None Undervoltage Trip Trip None None Power Factor Trip Trip None None Tach Accel Trip Trip None None Inhibits Trip Trip None None Shunt Trip AUX 3 None None Bypass Discrepancy None None None External Input #1 None None None External Input #2 None None None Dual Ramp None None None Thermostat Trip None None O/L Warning Alarm None None Overcurrent Alarm Alarm None None Ground Fault Alarm Alarm None None Under Current Alarm Alarm None None Motor Running None None None I/B Alarm Alarm None None Stator RTD Alarm Alarm None None Non-Stator RTD Alarm Alarm None None RTD Failure Alarm Alarm None None Self Test Fail Trip None None Thermal Register Alarm None None U/V Alarm Alarm None None O/V Alarm Alarm None None Power Factor Alarm Alarm None None KW Demand Alarm Alarm None None KVA Demand Alarm Alarm None None KVAR Demand Alarm Alarm None None Amps Demand Alarm Alarm None None Timed Output None None None Run Delay Time None None None At Speed AUX4 None None
Factory Setting
1st 2nd 3rd
Range Set ting
None Trip(AUX1) Alarm(AUX2) AUX3 AUX4
TOSHIBA- 83
Page 90
TX Series 48 - 1250A
Off, RPM 0-3600, Hottest Non-Stator RTD 0-
Setpoint
Page
Page 5
Setpoint
Page
Page 6
User I/O Configuration
Relay Configuration
Security
Level
Level 2
Security
Level
Lavel 2
Passowrd Protect i on
Description
Trip (AUX1) Fail-Safe No Yes or No Trip (AUX1) Relay Latched Yes Yes or No Alarm (AUX2) Fail-Safe No Yes or No Alarm (AUX2) Relay Latched No Yes or No AUX3 Relay Fail-Safe No Yes or No AUX3 Relay Latched No Yes or No
Password Protection
AUX4 Relay Fail-Safe No Yes or No AUX4 Relay Latched No Yes or No
Description
Tachometer Scale Selection Disabled Enabled or Disabled Manual Tach Scale 4.0 mA: 0 RPM 0 - 3600 Manual Tach Scale 20.0 mA: 2000 RPM 0 - 3600 Tach Accel Trip Mode Select Disabled Underspeed, Overspeed or Disabled Tach Ramp Time 20 sec 1 - 120 Tach Underspeed Trip PT 1650 RPM 0-3600 Tach Overspeed Trip PT 1850 RPM 0 - 3600 Tach Accel Trip Delay 1 sec 1 - 60
Analog Output #1 RMS Current
Analog Output #1 4mA: 0 0-65535 Analog Output #1 20mA: 250 0-65535 Analog Output #2 % Motor Load Same As Analog Input #1 Analog Output #2 4mA: 0 0-1000% Analog Output #2 20mA: 1000 0-1000% User Programmable External
Inputs External Input #1 Disabled Enabled or Disabled Name Ext. Input #1 User Defined, up to 15 Characters External Input #1 NO Normally Open or Closed External Input #1 0 sec 0-60 sec External Input #2 Disabled Enabled or Disabled Name Ext. Input #2 User Defined, up to 15 Characters External Input #2 Type NO Normally Open or Closed External Input #2 Time Delay 0 sec 0-60 sec Dual Ramp Dual Ramp Enabled or Disabled or Dual Ramp Name Ext. Input #3 Dual Ramp User Defined, up to 15 Characters Dual Ramp Type NO Normally Open or Closed Dual Ramp Time Delay 0 sec 0-60 sec Thermostat Enabled Enabled or Disabled Name Ext. Input #4 Thermostat User Defined, up to 15 Characters Thermostat Type NC Normally Open or Closed Thermostat Time Delay 1 sec 0-60 sec
Factory Setting
Default
Factory Setting
Default
Range Setting
Range Setting
200°C, Hottest Stator RTD 0 - 200°C, RMS Current 0 - 7500 A, % Motor Load 0 - 600 %.
TOSHIBA - 84
Page 91
TX Series 48 - 1250A
Setpoint
Page
Page 7
Custom Acceleration Curve
Setpoint
Page
Page 8
Overload Curve Configuration
Security
Level
Level 3
Password Protecti on
Security
Level
Level 3
Password Protecti on
Description
Custom Accel Curve Disabled Disabled, Curve A, B, or C Custom Curve A Curve A Voltage Level 1 25% 0-100% Curve A Ramp Time 1 2 sec 1-60 sec Curve A Voltage Level 2 30% 0-100% Curve A Ramp Time 2 2 sec 1-60 sec Curve A Voltage Level 3 37% 0-100% Curve A Ramp Time 3 2 sec 1-60 sec Curve A Voltage Level 4 45% 0-100% Curve A Ramp Time 4 2 sec 1-60 sec Curve A Voltage Level 5 55% 0-100% Curve A Ramp Time 5 2 sec 1-60 sec Curve A Voltage Level 6 67% 0-100% Curve A Ramp Time 6 2 sec 1-60 sec Curve A Voltage Level 7 82% 0-100% Curve A Ramp Time 7 2 sec 1-60 sec Curve A Voltage Level 8 100% 0-100% Curve A Ramp Time 8 2 sec 1-60 sec Curve A Current Limit 350% FLA 200-600%
Custom Curve B
Custom Curve C
Description
Basic Run Ov erload Curve Run Curve Locked Rotor Time O/L Class 1-30 sec, O/L Class Run Locked Rotor Current 600% FLA 400-800% Coast Down Timer Disabled 1-60 Min, Disabled Basic Start Overload Curve Start Curve Locked Rotor Time O/L Class 1-30 sec, O/L Class Start Locked Rotor Current 600% FLA 400-800% Acceleration Time Limit 30 sec 1-300 sec, Disabled Number of Starts Per Hour Disabled 1-6, Disabled Time Between Starts Time Disabled 1-60 Min, Disabled Area Under Curve Protection Disabled Enabled or Disabled Max I*I*T Start 368 FLA 1-2500 FLA*FLA*sec Current Over Curve Disabled Disabled, Learn, Enabled Learned Start Curve Bias 10% 5-40% Time for Sampling 30 sec 1-300 sec
Factory Setting
Default
Factory Setting
Default
Range Setting
Same Programmable Data Points and Ranges as Custom Curve A
Same Programmable Data Points and Ranges as Custom Curve A
Range Setting
TOSHIBA- 85
Page 92
TX Series 48 - 1250A
Setpoint
Page
Page 9
RTD Configuration
Security
Level
Level 3
Password Protecti on
Description
Use NEMA Temp for RTD Values Disabled Enabled or Disabled # of RTD Used for Stator 4 0-6
RTD Voting Disabled Enabled or Disabled
Stator Phase A1 Type Off
RTD #1 Description Stator A1 User defined, Up to 15 Characters Stator Phase A1 Alarm Level Off 0-240C (32-464F), Off Stator Phase A1 Trip Level Off 0-240C (32-464F), Off Stator Phase A2 Type Off Same as Stator Phase A1 RTD #2 Description Stator A2 User defined, Up to 15 Characters Stator Phase A2 Alarm Off 0-240C (32-464F), Off Stator Phase A2 Trip Level Off 0-240C (32-464F), Off Stator Phase B1 Type Off Same as Stator Phase A1 RTD #3 Description Stator B1 User defined, Up to 15 Characters Stator Phase B1 Alarm Level Off 0-240C (32-464F), Off Stator Phase B1 Trip Level Off 0-240C (32-464F), Off Stator Phase B2 Type Off Same as Stator Phase A1 RTD #4 Description Stator B2 User defined, Up to 15 Characters Stator Phase B2 Alarm Level Off 0-240C (32-464F), Off Stator Phase B2 Trip Level Off 0-240C (32-464F), Off Stator Phase C1 Type Off Same as Stator Phase A1 RTD #5 Description Stator C1 User defined, Up to 15 Characters Stator Phase C1 Alarm Level Off 0-240C (32-464F), Off Stator Phase C1 Trip Level Off 0-240C (32-464F), Off Stator Phase C2 Type Off Same as Stator Phase A1 RTD #6 Description Stator C2 User defined, Up to 15 Characters Stator Phase C2 Alarm Level Off 0-240C (32-464F), Off Stator Phase C2 Trip Level Off 0-240C (32-464F), Off End Bearing Type Off Same as Stator A1 RTD #7 Description End Bearing User defined, Up to 15 Characters End Bearing Alarm Level Off 0-240C (32-464F), Off End Bearing Trip Level Off 0-240C (32-464F), Off Shaft Bearing Type Off Same as Stator Phase A1 RTD #8 Description Shaft Bearing User defined, Up to 15 Characters Shaft Bearing Alarm Level Off 0-240C (32-464F), Off Shaft Bearing Trip Level Off 0-240C (32-464F), Off RTD #9 Type Off Same as Stator Phase A1 RTD #9 Description User defined User defined, Up to 15 Characters RTD #9 Alarm Level Off 0-240C (32-464F), Off RTD #9 Trip Level Off 0-240C (32-464F), Off
Factory Setting
Default
Range Setting
120 OHM NI, 100 OHM NI, 100 OHM PT, 10 OHM CU
TOSHIBA - 86
Page 93
TX Series 48 - 1250A
Setpoint
Page
Page 9
RTD Configuration
Setpoint
Page
10
Page
Security
Level
Level 3
Password Protection
Security
Level
3
Level
Description
RTD #10 Type Off Same as Stator Phase A1 RTD #10 Description User defined User defined, Up to 15 Characters RTD #10 Alarm Level Off 0-240C (32-464F), Off RTD #10 Trip Level Off 0-240C (32-464F), Off RTD #11 Type Off Same as Stator Phase A1 RTD #11 Description User defined User defined, Up to 15 Characters RTD #11 Alarm Level Off 0-240C (32-464F), Off RTD #11 Trip Level Off 0-240C (32-464F), Off RTD #12 Type Off Same as Stator Phase A1 RTD #12 Description User defined User defined, Up to 15 Characters RTD #12 Alarm Level Off 0-240C (32-464F), Off RTD #12 Trip Level Off 0-240C (32-464F), Off
Description
Set Level 2 Password 100 000 – 999 Three Digits Set Level 3 Password 1000 0000 – 9999 Four Digits
Factory Setting
Default
Factory Setting
Default
Range Setting
Range Setting
Setpoint
Page
Page 11
Communiications
Security
Level
Level 3
Password Protecti on
Description
Set Front Baud Rate 9.6 KB/sec 2.4, 4.8, 9.6, 19.2, 38.4 KB/sec Set Modbus Baud Rate 9.6 KB/sec 2.4, 4.8, 9.6, 19.2, 38.4 KB/sec Modbus Address Number 247 1 – 247 Set Access Code 1 1 – 999
Set Link Baud Rate 38.4 KB/sec 2.4, 4.8, 9.6, 19.2, 38.4 KB/sec Remote Start/Stop Disabled Enabled or Disabled
Factory Setting
Default
Range Setting
TOSHIBA- 87
Page 94
TX Series 48 - 1250A
Model #
Setpoint
Page
Page 12
System Setpoints
Security
Level
Level 3
Password Protecti on
Description
Default Display Screen Metering Data Page # 1 Enter Metering Page (1-4)
Metering Data Screen # 1
Alarms RTD Failure Alarm Disabled Enabled or Disabled Thermal Register Alarm 90% Off, 40-95% Thermal Alarm Delay 10 sec 1-20 sec Thermal Register Setup Info Cold Stall Time O/L Class O/L Class (5-30) or 4-40 second time delay Hot Stall Time ½ O/L Class ½ O/L Class, 4-40 sec Stopped Cool Down Time 30 Min 10-300 Min Runing Cool Down Time 15 Min 10-300 Mi n Relay Measured Cool Rates Disabled Enabled or Disabled Thermal Register Minimum 15% 10-50% Motor Design Ambient Temp 40C 10-90C
Motor Design Run Temperature 80% Max 50-100% of Motor Stator Max Temp
Motor Stator Max Temp INS CLS INS CLS, 10-240 C I/B Input to Thermal Register Enabled Enabled Only Use Calculated K or Assign 7 1-50, On
Factory Setting
Default
Enter Metering Screen Page 1(1-10) Page 2 (1-11) Page 3 (1 - 29) Page 4 (1 - 6)
Range Setting
Setpoint
Page
Page 13
Calibration & Service
Security
Level
FACTORY USE ONLY
Press Enter to Clr Thermal Register
Description
Set Date and Time (DDMMYY:HHMM)
Enter Date (DDMMYYYY)
Enter Time (HH:MM)
Firmware REV. # Press Enter to Access Factory
Settings
Factory Setting
Default
FACTORY SET; ##/##/## ##:##
FACTORY SET; ##/##/####
FACTORY SET; ##:##
FACTORY SET; ###### ######
Range Setting
D=1-31, M=1-12, Y =19 70- 20 69
H=00-23, M=0-59
Display Only, Cannot be changed
Available to Qualified Factory Personnel
TOSHIBA - 88
Page 95
TX Series 48 - 1250A
Toshiba International Corporation ("Company") warrants that all equipment and parts described h
E
E
S
(
D
P
L
P
S
(
D
P
R
P
The Company will, at its optio n, repair or re place such equip ment or part whic h is defective u nder
t
e
C
d
(
d
within the limits of rated c apacity and norm al usage and in ac cordance with t his manual, and (4) if
r
all
e
rt
will be delivered, free of charge, to the purchaser F.O.B. the Company's warehouse or, at the
C
r.
T
y,
i
n
c T
E
T
S
O
E
C
T
W
L
A
S
I
E
C
S
H
S,
I
T
T
.
The total liability of the Company, Tos hiba Corporation an d their suppliers and subcontractors for
a
t),
o
in
this manual or the performance or breach of any contract for the sale or supply of such equipment
and parts, or from t he des ign, man ufactur e, sa le, delivery, resal e, ins tallati on, tec hnical direct ion or
s
e
o
in
any event exceed th e price allocable to the equipment, part or service which gives claim, loss or
d
ity
without fault, or otherwise, shall the Company, Toshiba Corporation or their suppliers or
subcontractors be liab le for special or consequen tial damages, includ ing, without limitation , loss or
p
l,
cost of substitute equ ip me nt or parts, facilities or s ervic es, d ow n-time costs, labor costs or cl ai ms of
c
Warranty Policy
erein will be free from defects in materials and workmanship. THIS WARRANTY WILL EXPIR
IGHTEEN (18) MONTHS AFTER THE DATE ON WHICH SUCH EQUIPMENT AND PART
EXCLUDING REPAIRED OR REPLACEMENT EQUIPMENT AND PARTS FURNISHE
URSUANT TO THIS WARRANTY) ARE SHIPPED BY THE COMPANY TO THE INITIA URCHASER OR TWELVE (12) MONTHS AFTER SUCH EQUIPMENT AND PART
EXCLUDING REPAIRED OR REPLACEMENT EQUIPMENT AND PARTS FURNISHE
URSUANT TO THIS WARRANTY) ARE FIRST PLACED IN OPERATION, WHICHEVE
ERIOD FIRST EXPIRES.
he terms of the foregoing warra nty, fr ee of charge ; prov ided th e p urch aser (1) pr ompt ly notifi es th
ompany in writing of such defect, and (2) furnishes the Company satisfactory proof thereof, an
3) establishes that the equipment or part has been properly installed, maintained and operate equested by the Company, returns the defective equipment or part to the Company and pays
xpenses incurred in connec tion with such return. The repaired or repl acement equ ipment or pa
ompany's option, F.O . B. a Com pa ny aut hor iz e d service shop, not loaded on truck or other carrie
he purchaser will pay the costs applicable to the equipment or part following such deliver
ncluding, without limitation, all handling, transportation, assembly, insurance, testing and inspectio
harges.
HE FOREGOING OBLIGATION TO REPAIR OR REPLACE EQUIPMENT PARTS SHALL B HE SOLE AND EXCLUSIVE REMEDY OF THE PURCHASER, ITS CUSTOMERS AND USER
F THE EQUIPMENT AND PARTS FOR BREACH OF THE FOREGOING WARRANTY. TH OMPANY WILL HAVE NO OBLIGATIONS TO DISASSEMBLE ANY EQUIPMENT OR PAR
HICH IS DEFECTIVE WITHIN THE TERMS OF THE ABOVE WARRANTY OR TO INSTAL
NY REPAIRED OR REPLACEMENT PART OR EQUIPMENT OR TO PAY ANY COST
NCURRED IN CONNECTION WITH ANY SUCH DISASSEMBLY OR INSTALLATION. TH
OMPANY, TOSHIBA CORPORATION AND THEIR SUPPLIERS AND SUBCONTRACTOR EREBY DISCLAIM ALL OTHER EXPRESS, STATUTORY AND IMPLIED WARRANTIE
NCLUDING, WITHOUT LIMITATION, ALL EQUIPMENT AND PARTS FURNISHED PURSUAN
O THE FOREGOING WARRANTY AND ALL IMPLIED WARRANTIES OF MERCHANTABILITY
ny loss, damage or claim, w hether in c ontact, tort ( including negligenc e and lia bility with out faul r otherwise, arising out of, connected with or resulting from the equipmen t and parts des cribed
upervision of inst allation, inspec tion, testing, r epair, replaceme nt, operation, maintenance or us f any such equipment or part or any servic e re latin g ther eto furn ish ed by t he Com pany shal l not
amage. In no event, whether as a breach of contract or warranty, alleged negligence, liabil
rofits or revenue, loss of equipment described herein or any associated equipment, cost of capita ustomers of the purchaser for such damages.
TOSHIBA- 89
Page 96
Loading...