Toshiba 4200FA XT2 User Manual

A B C D E F G H I J
1
2
3
4
5
6
Customer Supply
AC Input
(208-600V),
Bypass
Isolation
Transformer
Y
D
Isolation
Transformer
Y
D
MCCB
High Freq. Filter
Contactor
UPS Cabinet
Maintenance Bypass
Static Switch Bypass
SYNC
Converter
Inverter
DC Chopper/
Charger
Contactor
High Freq. Filter
Transformer
Make-Before-Break
Output
Y
2-Breaker
Maintenance
Bypass
Switch
52C
1
2
3
4
AC Output
Y
52L
(208-600V)
15 kVA,
0.8 PF
5
6
7
8
9
Customer
10
NOTES
1) This drawing is for illustration purposes only and is subject to change without notice. TIC is not responsible for any errors or omissions.
2) A Maximum of 2 transformers can be equipped within the standard UPS cabinet.
3) An output transformer is not equipped in models with 208/120V output.
supplied
wiring
Battery Cabinet(s) or Rack(s) with DC Breaker
72B
Drawn by
EO
DATE 03/25/04
Approved by
JIS
DATE 03/25/04
ST
TOSHIBA
INTERNATIONAL CORPORATION
Houston Texas, USA
THIS MATERIAL IS THE EXCLUSIVE PROPERTY OF
TOSHIBA INTERNATIONAL CORPORATION AND SHALL NOT
BE REPRODUCED, USED, OR DISCLOSED TO OTHERS
UNLESS PRIOR WRITTEN AUTHORIZATION IS OBTAINED.
Customer
supplied
wiring
TITLE
4200FA XT2 UPS, 15 kVA Capacity
shown with External Bypass Transformer and
One-Line Drawing
Single Input Transformer Model,
External 2-Breaker Maintenance Bypass Switch
DRAWING NO. REV.
T42X3X150XAMXN
7
8
9
10
1.2