A B C D E F G H I J
1
2
3
4
5
6
7
AC Input
208/120V
3Ph/4W
60Hz
AC Input
208/120V
3Ph/4W
60Hz
SW1
SW1
3-Breaker Maintenance Bypass Switch
Fuse
Contactor
Contactor Fuse Contactor
MCCB
HF Noise
Filter
Battery Cabinet(s) or Rack(s) with DC breaker
15 kVA UPS #2 Cabinet
Maintenance Bypass
Static Switch Bypass
Converter
3-Breaker Maintenance Bypass Switch
Fuse
Contactor
15 kVA UPS #1 Cabinet
Maintenance Bypass
Static Switch Bypass
SYNC
Inverter
DC Chopper/
Charger
72B
ST
SW2
2
1
Fuse
Make-Before-Break
SW3
3
HF Noise
Filter
4
+
-
5
SW2
6
7
8
AC Input
208/120V
MCCB
3Ph/4W
60Hz
9
10
NOTES
1) This drawing is for illustration purposes only and is subject to change without notice. TIC
is not responsible for any errors or omissions.
Battery Cabinet(s) or Rack(s) with DC breaker
SYNC
Contactor Fuse Contactor
HF Noise
Filter
DRAWN BY
DATE 08/15/05
Approved by
DATE 08/15/05
Converter
JE
JIS
TOSHIBA INTERNATIONAL CORPORTION AND SHALL NOT
Inverter
DC Chopper/
Charger
72B
ST
TOSHIBA
INTERNATIONAL CORPORATION
Houston Texas, USA
THIS MATERIAL IS THE EXCLUSIVE PROPERTY OF
BE REPRODUCED, USED, OR DISCLOSED TO OTHERS
UNLESS PRIOR WRITTEN AUTHORIZATION IS OBTAINED.
Fuse
HF Noise
Filter
Make-Before-Break
SW3
AC Output
208V,
3Ph/4W,
60Hz
15kVA
8
.8 PF
9
+
-
TITLE
Isolated Redundant System, Shown with
DRAWING NO. REV.
One-Line Drawing
4200FA XT UPS, 15 kVA Capacity
3-Breaker External Bypass Switch
T42F3F150FAMXN
10
1.3