Toshiba 1800 User Manual

UNINTERRUPTIBLE POWER SYSTEMS
1800 Series
User Manual 1800 Series Uninterruptible Power Systems (UPS)
6!
© Copyright 2007 Toshiba International Corporation All rights reserved.
PRODUCT USE AND WARRANTY
RESTRICTIONS
The Toshiba products listed in this document are intended for usage in general
electronics applications (computer, personal equipment, ofce equipment,
measuring equipment, industrial robotics, domestic appliances, etc.). These Toshiba products are neither intended nor warranted for usage in equipment that either requires extraordinarily high quality and/or reliability, or a malfunction or failure of which may cause loss of human life or bodily injury (“Unintended Usage”). Unintended Usage include atomic energy control instruments,
airplane or spaceship instruments, transportation instruments, trafc signal
instruments, combustion control instruments, medical instruments, all types of safety devices, etc. Unintended Usage of Toshiba products listed in this document shall be made at the customer’s own risk.
NOTICE
PLEASE INFORM TOSHIBA INTERNATIONAL CORPORATION
OR AUTHORIZED REPRESENTATIVE IN CASE OF
INCONSISTENCIES, OMISSIONS, OR QUESTIONS.
The instructions contained in this manual are not intended to cover all of the details or variations in equipment, or to provide for every possible contingency concerning installation, operation, or maintenance. Should further information
be required or if problems arise which are not covered sufciently contact your Toshiba sales ofce.
The contents of this instruction manual shall not become a part of or modify any prior or existing agreement, commitment, or relationship. The sales contract contains the entire obligation of Toshiba International Corporation’s Uninterruptible Supply Systems Division. The warranty contained in the contract between the parties is the sole warranty of Toshiba International Corporation’s UPS Division and any statements contained herein DO NOT create new warranties or modify the existing warranty.
Any electrical or mechanical modications to this equipment without prior
written consent of Toshiba International Corporation will void all warranties
and may void the UL/CUL listing. Unauthorized modications can also result
in personal injury, death, or destruction of the equipment.
3
QUALIFIED PERSONNEL ONLY
Qualied Personnel are those who have the skills and knowledge
relating to the construction, installation, operation, and maintenance of the electrical equipment and have received safety training on the hazards involved (Refer to the latest edition of NFPA 70E for additional safety requirements).
UNINTERRUPTIBLE POWER SYSTEM (UPS)
Please complete the following information and retain for your records.
Unless otherwise specied, the warranty period for the UPS or UPS part is 36
months from the shipment date (see Toshiba International Corporation Bill of Lading for shipping date).
Unless otherwise specied, the warranty period for a UPS battery is 24 months
from the shipment date (see Toshiba International Corporation Bill of Lading for shipping date).
JOB NUMBER
MODEL NUMBER
SERIAL NUMBER
APPLICATION
SHIPMENT DATE
INSTALLATION DATE
INSPECTED BY
4
SEPT 2007 59752-000
TOSHIBA’S CUSTOMER SUPPORT CENTER
Contact the Toshiba Customer Support Center for assistance with application information or for any problems that you may experience with your Uninterruptible Power System (UPS).
Toshiba Customer Support Center
8 a.m. to 5 p.m. (CST) - Monday through Friday Email - toshibaups@tic.toshiba.com
Tel 713-466-0277 Fax 713-896-5212 USA Toll Free 877-867-8773 Canada 877-867-8773 Mexico 01-800-527-1204
You may also contact Toshiba by writing to:
Toshiba International Corporation
13131 West Little York Road Houston, Texas 77041-9990
Attn: UPS Product Manager
For further information on Toshiba’s products and services, please visit our website at:
www.toshiba.com/ind/
© Copyright 2007 Toshiba International Corporation All rights reserved. Printed in the U.S.A.
5

TABLE OF CONTENTS

Product Use and Warranty Restrictions ...............................................3
General Safety Instructions ...............................................................8
Important Safety Instructions ............................................................9
INSTRUCTIONS IMPORTANTES CONCERNANT LA SÉCURITÉ ....10
Product Description ...........................................................................11
Inspection/Installation ........................................................................13
Inspection of the New UPS Equipment .............................................13
Unpacking Instructions ......................................................................13
After Unpacking .................................................................................13
Installation Precautions .....................................................................13
Operating Precautions .....................................................................14
Layout ...............................................................................................15
External Dimensions .........................................................................16
Wiring the Unit ..................................................................................16
UPS Power Connections ...................................................................16
Operating the UPS ..............................................................................19
Display Panel Layout ........................................................................19
Starting the UPS System ..................................................................20
Stopping the UPS ..............................................................................20
Battery Backup Time .........................................................................24
Battery Recharge Time .....................................................................24
Battery Check Function .....................................................................25
The Function Control Button .............................................................25
Communication Interface ..................................................................26
Remote Contacts (IBM AS/400) ........................................................26
RS-232C ...........................................................................................27
Option Card Slot ................................................................................28
Troubleshooting .................................................................................28
Warning/Fault Modes ........................................................................28
Storage of UPS Equipment ................................................................35
General Guidelines ...........................................................................35
Disposal ............................................................................................36
6
Preventive and Scheduled Maintenance/Parts Replacement.........37
Preventive Maintenance ....................................................................37
Parts Replacement ............................................................................37
Appendix A: Specications ..............................................................38
Appendix B: System Overload .........................................................40
Appendix C: Parallel Operation........................................................41
Appendix D: Bypass Undervoltage / Overvoltage ..........................42
Appendix E: 1800 Model/Wire Size specications .........................43
Limited Warranty Policy ....................................................................44
7

GENERAL SAFETY INSTRUCTIONS

Warnings in this manual appear in two different ways:
DANGER WARNINGS The danger warning symbol is an
exclamation mark enclosed in a triangle that precedes the large bold letters spelling
DANGER
CAUTION WARNINGS The caution warning symbol is an
CAUTION
Other warning symbols may appear along with the Danger and Caution symbol and are used to specify special hazards. These warnings describe particular areas where special care and/or procedures are required in order to prevent serious injury and possible death:
the word “DANGER”. The Danger warning symbol is used to indicate situations, locations, and conditions that exist and can cause serious injury or death.
exclamation mark enclosed in a triangle that precedes the large bold letters spelling the word “CAUTION”. The Caution warning symbol is used to indicate situations and conditions that can cause operator injury and/or equipment damage.
ELECTRICAL WARNINGS The electrical warning symbol is a
lightning bolt mark enclosed in a triangle. The electrical warning symbol is used to indicate high voltage locations and conditions that may cause serious injury or death if the proper precautions are not observed.
EXPLOSION WARNINGS The explosion warning symbol is an
explosion mark enclosed in a triangle. The explosion warning symbol is used to indicate locations and conditions where molten, exploding parts may cause serious injury or death if the proper precautions are not observed.
8

IMPORTANT SAFETY INSTRUCTIONS

SAVE THESE INSTRUCTIONS.
This manual contains important instructions for all models of the Toshiba 1800 Series UPS. These instructions should be followed during the installation and maintenance of the UPS and its batteries.
• The maximum ambient temperature in which this UPS unit should
be operated or stored is 104°F (40°C). The maximum ambient temperature in which this UPS should charge batteries is 95°F
(35°C).
• When changing battery packs, be sure to use the proper model unit.
Do not dispose of the batteries in a re.
DANGER
CAUTION
Misuse of this equipment could result in human injury and equipment damage. In no event will Toshiba International Corporation be responsible or liable for either indirect or consequential damage or injury that may result from the use of this equipment.
The batteries inside may explode.
CAUTION
CAUTION
CAUTION
Do not open or mutilate the batteries. Released electrolyte is harmful to the eyes and skin, and could be toxic.
This unit contains sealed lead acid batteries. Lack of preventative maintenance could result in batteries exploding and emitting gasses and/or
ame. Annual preventative maintenance must be
performed by an authorized, trained technician.
Failure to replace the batteries in accordance with the maintenance schedule may cause the batteries to crack, possibly releasing electrolytes from the battery, and resulting in secondary faults such as
odor, smoke and re.
9
INSTRUCTIONS IMPORTANTES
CONCERNANT LA SÉCURITÉ
CONSERVER CES INSTRUCTIONS.
Cette notice contient des instructions importantes concernant la sécurit.
ATTENTION
ATTENTION
ATTENTION
Une batterie peut présenter un risque de choc électrique, de brûlure par transfert d’énergie.
Pour le remplacement, utiliser le même nombre de batteries du modèle suivant.
L’élimination des batteries est réglementée. Consulter les codes locaux à cet effet.
10

PRODUCT DESCRIPTION

Theory of Operation
An uninterruptible power supply, or system, is a device that is installed between commercial power and load equipment. The UPS provides steady AC power
to the load during commercial power uctuations and interruptions.
During normal operation the UPS uses commercial AC power. It also takes in all of the high voltage spikes and transients caused by switching and faults, and all of the common mode and normal mode noise which is associated with
commercial AC power. The UPS converts this input to at DC power. From
this DC power, the UPS generates its own extremely high quality AC output. The result of this process is maximum power conditioning.
If the AC power supplied to the UPS drops below a specied voltage level, the
unit’s batteries automatically begin supplying the power instead of receiving it. This insures that the load connected to the UPS continues to receive power
without interruption. When commercial AC input power becomes available
again, operation returns to normal. The unit’s batteries begin to recharge so they will be ready for the next power interruption.
Application and Use
Toshiba’s 1800 Series of on-line Uninterruptible Power Systems (UPS) provides continuous computer-grade AC power in a compact, high performance,
energy efcient unit. The UPS assures safe and reliable operation of critical ofce equipment, minicomputers, and local area networks. All units feature
an audible alarm which sounds if the battery voltage drops below standard
during use. This is an additional aid to help in retaining the valuable ofce
data banks. All units allow for computer interfacing for remote control and monitoring, and an external battery pack option for extended backup operation.
(See Specications)
Power Backup
During an electrical power failure the batteries of the UPS unit supply DC power to the inverter that supports the load equipment automatically, without interruption. For example, when used to support a computer, a UPS backup assures additional time to complete your activity and save data after a power failure occurs.
11
Power Conditioning
While commercial power is present, the UPS supplies conditioned power to the
load while maintaining the batteries in a charged condition. The UPS protects the connected load against the normal everyday problems associated with heavy use of raw commercial power, including power sags, signal interference, and spikes. This protection keeps power-line problems from reaching your load where it can cause equipment to operate erratically, or damage software or hardware.
12

INSPECTION/INSTALLATION

INSPECTION OF THE NEW UPS EQUIPMENT

Upon receipt of the UPS, a careful inspection for shipping damage should be made.

UNPACKING INSTRUCTIONS

Remove box and foam pack.
1. Unbolt mounting rails from both
2. pallet and unit. Place mounting rails at front of
3.
pallet as shown.
Insert bolts removed from pallet
4.
into holes at top of ramp. Place tie bracket in slots near
5. base of ramp.

AFTER UNPACKING

1) Check the unit for loose, broken, bent or otherwise damaged parts. If
damage has occurred during shipment, keep all original packing materials
for return to shipping agent. Warranty will not apply to units damaged
during shipment.
2) Check to see that the rated capacity and the model number specied on the
nameplate conform to the order specications.

INSTALLATION PRECAUTIONS

CAUTION
13
1) Install the unit in a well ventilated location; allow at least 4 inches (10
cm) on all sides and 8 inches (20 cm) on back for air ventilation and for maintenance.
2) Install the unit in a stable, level, and upright position that is free of
vibration.
3) Install the unit where the ambient temperature is between 32° and 104°F
(0° and 40°C).
4) Do not install the UPS in areas that are subject to high humidity.
5) Do not install the UPS in a location that will cause direct sunlight to shine
on the unit.
6) Do not install the UPS in areas that are subject to contamination such as
high levels of airborne dust, metal particles, or ammable gas.
7) Avoid installation near sources of electrical noise. Always make sure that
the unit earth ground is intact to prevent electrical shock and to help reduce electrical noise.
8) Do not install where water or any foreign object may get inside the UPS.
9) This UPS generates and can radiate radio-frequency energy during
operation. Although RFI noise lters are installed inside the unit there is no guarantee that the UPS will not inuence some sensitive devices which are
operating close by. If such interference is experienced, the UPS should be installed farther away from the affected equipment and/or powered from a different source than that of the affected equipment.

OPERATING PRECAUTIONS

CAUTION
1) The UPS should not be powered up until this entire manual has been
reviewed.
2) The input power source voltage and frequency must be within the allowable
range specied in Appendix A. Voltages and frequencies outside of the specied tolerance range may cause internal protection devices to
activate.
14
3) Use a breakered input power souce with high inrush tolerance.
4) The UPS should not be used with a load whose rated input is greater than
the rated UPS output.
5) Do not use the UPS to provide power to motors that require high starting
current or that require a long starting time such as vacuum cleaners and machine tools (unless appropriate sizing is done by a Toshiba applications
engineer, or other qualied personnel).
6) Do not insert metal objects or combustible materials in the unit’s ventilation
slots.
7) Do not place, hang, or paste any objects on the top or on the exterior
surfaces of the UPS.

LAYOUT

Display
Run/Stop Switch 0: Stop 1: Run
Breaker
Remote Contact (male)
RS-232C
(female)
Air
Vents
Option Card Slot
(SNMP/Web Remote Card)
Battery Plug
(48V DC
Input Receptacle
Line cord and Receptacle Options panel
for extended run times
- contact TIC Marketing)
Live (Always-on)
Cooling Fans
- CAUTION -
Receptacle
15

EXTERNAL DIMENSIONS

9.9 in.
28.3 in. Max
23.3 in.

WIRING THE UNIT

Select the wire size appropriate for the 1800 model being installed. (See Ap-
pendix E, 1800 Model/Wire Size Specications.)
All wiring is to be tightened to 13 lb-in(1.5 N•m) of torque

UPS POWER CONNECTIONS

System Protection Features - The schematic shown below depicts the
electrical locations of the protection devices of the UG1G2L024C6TB
typeform UPS.
Input
16
Input
Abnormal
Breaker
Overcurrent
Low Battery
Level
Reactor/ Charger/ Chopper
Overheating
Bypass
Batteries
Inverter
Current Limit
Overload
ISOLATION OUTPUT XFMR
Overvoltage/ Undervoltage
Power Flow
Output
Output
Power Connections - 120 V Input
This illustrates the wiring connections from the power distribution panel (not
part of the UPS) to the UPS terminal block for the 120 V input models of the
1800 Series UPS.
Main UPS Unit
120 V
Source Power
Distribution Panel
UPS Output Voltage
Output Voltage
120 VAC
Terminal
H3-N
L1 1
L2 2
G 3
H1
H2
Breaker
H3
N
G
Terminal Block Details
This is a detailed view of the UPS terminal block for 120V Input referenced in
the connection diagrams above.
120V
5
7 8643
G
GNDGND
1 2
H1
120V
H2 G
H3 N
17
Power Connections - 208/240 V Input
This illustrates the wiring connections from the power distribution panel (not
part of the UPS) to the UPS terminal block for the 208/240 V input model of
the 1800 Series UPS.
UPS Output Voltage
Output Voltage Terminal
240 VAC
208 VAC
120 VAC
H1A - H3
H1A - H2A
H1A-N, H3-N
208/240 V
Source Power
Distribution
Panel
L1 1
L2 2
G 3
11
Low (208V)
12
High (240V)
13
Breaker
H2
H1
Main UPS Unit
Input voltage section (factory setting: Low)
H3
H2A
H1A
4
5
7
N
6
8
G
Terminal Block Details
This is a detailed view of the UPS terminal block for 208/240 V input refer­enced in the connection diagrams above.
213
208/240 VAC
Input cables from distribution panel
Note 1: 208V Input: If AC input power is 208 V rated, terminals 11 and 12 must be shorted by
a jumper wire. DO NOT jumper to terminal 13.
Note 2: 240V Input: If AC input power is 240 V rated, terminals 12 and 13 must be shorted by
a jumper wire. DO NOT jumper to terminal 11.
4
H3 LOW HIGHH1H2
G G
Ground
AC Output cables to loads
18
6
5 8 14131211 15
H2A
240V
120V
N
208V
120V
7
H1A
Ground
COM
208V
Jumper selection see Note 1 & 2
240V

OPERATING THE UPS

DISPLAY PANEL LAYOUT

FUNCTION
CONTROL
BUTTON
ON LINE (green lamp)
Lights green when the UPS’s inverter is supplying power to the load.
AC INPUT (green lamp) Lights green when normal AC input power is being supplied to the UPS unit.
WARNING/FAULT (red lamp) Lights red when the UPS is experiencing an abnormal condition.
BATTERY (red lamp) Lights red to indicate that an abnormal condition exists that is affecting the batteries.
19

STARTING THE UPS SYSTEM

Ensure the input breaker is switched on (Figure, page 15). When the “AC Input” LED is lit switch the RUN/STOP switch to the RUN position (RUN = I, STOP = 0).
When the RUN/STOP switch is in the RUN position both the “AC Input” and
the “On Line” LEDs should be lit. It is advisable to allow time for the batteries to fully charge before any load is connected (see “Battery Recharge Time”, page 24).

STOPPING THE UPS

There are two ways to turn off the UPS: switching from online to bypass mode, or completely shutting down.
OPTION 1
The rst option is to place the UPS into bypass mode. Bypass mode means
that if there is AC power available, the UPS will route power directly from the input source to the connected loads without any conditioning. The UPS inverter is off during this state, but the attached loads do not lose power during the transition. To place the UPS into bypass mode, switch the RUN/STOP switch to the STOP position. This mode is most often used manually during maintenance operation or automatically upon the occurrence of an internal UPS fault. (For more information concerning bypass mode see Appendix D:
Bypass Undervoltage / Overvoltage).
OPTION 2
The other option is to turn the UPS off completely. This means that in addition to the UPS’s inverter shutting down, all power will be stopped to any equipment attached to the UPS. To shut the UPS down completely, switch the RUN/STOP switch to the STOP position. Then switch the input breaker off (Figure, page 15). Once the input breaker has been switched off, all the LEDs should turn off.
If the RUN/STOP switch is in the RUN position when the input breaker is switched off, the unit will switch to battery backup mode. The unit will continue to run for as long as the available battery reserves can support the connected loads.
20
Initial Mode Resultant Mode after:
Switch to Bypass Trip Manual Breaker
Run Bypass Backup
Backup Shutdown Backup
Bypass --- Shutdown
21
Notes
Alarm State
Alarm is off.
LED State
On Line On
AC Input On
20% to 100% On
*see Note 1,
page 23.
The unit will return to normal
operation mode when AC
power is restored.
Alarm will
sound for 1
second at
10 second
On Line On
Battery On
Backup On
20% to 100% On
intervals.
*see Note 2,
page 23
Battery backup is not available.
Alarm is off.
AC Input On
20% to 100% On
*see Note 1,
page 23.
UPS Display Status and Operating Condition
22
Display State
Operation Mode
Normal
Battery Backup
Bypass
Notes
Parallel operation occurs when
input power is present but
inadequate to fully power the
connected load. The batteries
are used to supplement the AC
input power. The UPS will re-
turn to normal operation when
full input power returns.
Alarm State
Alarm will
sound for 1
second at
10 second
intervals.
LED State
On Line On
AC Input On
Battery On
20% to 100% On
*see Note 1.
Display State
UPS Display Status and Operating Condition (cont.)
Operation Mode
Parallel
Operation
All other display conditions constitute either a warning or a fault condition. These conditions are explained in the section titled
“Troubleshooting” (page 28) in the charts on Warnings and Faults.
Note 1: The level meter, which consists of the LEDs labeled 20% through 150%, will light according to the current amount of
load connected. As the load exceeds one level, the next level will begin to blink, increasing the blink rate as the load increases
until that full percentage is reached. For example, if the unit is loaded to 40% of maximum output power the 20% and 40%
LEDs will be lit. If another small load is added increasing the load to 45% the 60% LED will begin to blink. If a little bit more
load is added so that the total load becomes 50% the 60% LED will blink faster. This will continue until enough load is added to
equal 60% of the maximum output power at which time the 60% LED will stop blinking and light continuously.
Note 2: The level meter described in Note 1 above also displays the remaining battery time when the unit is in backup mode.
If the batteries are fully charged when the unit switches to backup mode the 20% through 100% LEDs will light. As the batter-
ies begin to discharge, the LEDs starting from the top will blink rapidly then slowly and will then turn off as the battery time runs
down. For example if the unit has been running on battery power and there is 90% battery capacity remaining the 20% through
80% LEDs will be lit and the 100% LED will be blinking.
23

BATTERY BACKUP TIME

The exact amount of backup time provided will vary depending on the UPS model being used, number of batteries, condition of the batteries and other factors. However, the chart below gives the times that can be expected from the standard units with batteries in good condition. For longer runtime options contact your Toshiba sales representative or the Toshiba marketing department
at 877-867-8773 or by e-mail at toshibaups@tic.toshiba.com.
TABLE 1 - BACKUP TIME AS A % OF RATED LOAD*
UPS Model 100% 75% 50% 25%
1500 VA** 13 min 22 min 35 min 65 min
2000 VA** 10 min 17 min 25 min 53 min
2400 VA 7 min 12 min 20 min 44 min
* Times given are approximate and will vary depending on the age of the batteries, the battery
temperature, the number of previous discharges and the type of load.
** Products are under development, specication may change.

BATTERY RECHARGE TIME

The following table gives estimates of the time required to recharge the UPS’s batteries. The recharge time may vary depending on the battery temperature, the age of the batteries, and other factors.
24
TABLE 2 - BATTERY RECHARGE TIME*
Unit Batteries
1500 VA 3 ½ hours
2000 VA 3 ½ hours
2400 VA 3 ½ hours
* Recharge times are to 90% full capacity.

BATTERY CHECK FUNCTION

During startup the UPS will perform an automatic ‘Battery Check’ to detect whether a problem exists in the battery circuit. If the batteries pass the test, the unit will start normal operation. If a problem is detected during the test the
“Warning/Fault” LED will activate. Other LED’s may also activate. If this occurs
please refer to the “Troubleshooting” section on page 28 for a description of the problem and possible solutions. It is important to note that when the UPS has detected bad batteries, the battery backup mode is disabled. The unit will continue to operate and provide clean power; however, since there is no battery power available, the unit cannot provide backup power if input power is lost.

THE FUNCTION CONTROL BUTTON

The function control button is located on the display panel (see “Display Panel Layout”, page 19). This button is used to perform different UPS operations,
including initiating a self test, and silencing the alarm. A brief description of each function follows:
1) Self-Test. In order to perform a self-test the UPS must be operating in the
normal mode (see “UPS Display Status and Operating Condition”, page 22). To initiate the self-test simply press and hold the Function Control button until the audible alarm sounds. The self-test also performs the same battery check described above.
2) Alarm Silence. The alarm silence feature is used to stop the audible alarm
from sounding. Any time the audible alarm is sounding, quickly pressing and releasing (in less than 1 sec.) the Function Control button will silence the alarm.
25

COMMUNICATION INTERFACE

REMOTE CONTACTS (IBM AS/400)

The remote contacts interface is a standard feature. It is provided through solid state relays with contacts through a DB9 male connector located on the back of the UPS. The following chart shows the signals and the connector pinout.
Pin Signal Function Logic In the UPS
1 Fault Signal Closed when fault
detected
2 UPS stop com-
mon
3 UPS stop signal
input
4 Normal input
power supply
5 Signal common Common signal return
6 Bypass operation Closed during bypass
7 Battery voltage
low
8 UPS operation Closed during inverter
9 Power failure
signal
Backup stop when the level changes from
Low (-3 to -15 V) to High (+3 to +15 V)
Closed with normal supply power
operation
Closed at voltage drop
operation
Closed at power failure
1
2
3
4
5
6
7
8
9
DB9 Male Connector Outline (facing connector)
26
Voltage Current
48 VDC peak 100 mA peak
30 VAC rms
(42 VAC peak)
70 mA rms
(100 mA peak)

RS-232C

RS-232C serial communication interface is a standard feature that can be
used by authorized service personnel. It is provided through a DB9 female connector located on the back of the UPS (see “Layout “, page 15). This interface allows communication between the UPS and a personal computer. The chart below shows the signals and the connector pinout.
Pin I/O Symbol Description In the UPS
1 This pin not used
2 Input RXD Receive Data
3 Output TXD Transmit Data
4 Output DTR* Data Terminal Ready
5 - GND Signal ground
6 Input DSR* Data Set Ready
7 Output RTS** Request to Send
8 Input CTS** Clear to Send
9 This pin not used
(*) (**) These pins are tied together internally in the UPS. Signals DTR, DSR, RTS, and CTS are not used.
N/C RXD
TXD
GND
N/C
1 2
3 4
5
6
7
8
9
DB9 Female Connector Outline
(facing connector)
27

OPTION CARD SLOT

The option card slot is a standard feature. An optional network adapter card such as RemoteEye®II slides into the slot located on the back of the electronics module (Figure, page 15). This optional interface allows the UPS to be monitored across the network or from any point on the Internet.
The RemoteEye®II is an optional network card that allows the UPS to be managed remotely using the common SNMP/web network protocols. For
more information contact Toshiba’s UPS Marketing Department at (800) 231­1412 or by e-mail at toshibaups@tic.toshiba.com.

TROUBLESHOOTING

Warnings and Faults are those abnormal conditions that can occur and could
cause the unit to stop normal operation. These conditions are detected by
the protective circuitry in the unit. The UPS “Warning/Fault” lamp will light red
when a warning or fault occurs.
“Troubleshooting” involves monitoring the LED’s on the front panel and then interpreting the readout by using the warning and fault mode display charts that follow. Only the state of the LED’s listed in the chart should be considered. Other LED’s might be active; nevertheless, only those listed under the column “LED state” should be considered when diagnosing a warning, or fault.

WARNING/FAULT MODES

All warnings will cause the red “Warning/Fault” LED to ash. All faults will cause the red “Warning/Fault” LED to light continuously.
Some warnings and most faults will cause the UPS to transfer to bypass mode. In many cases, after the condition that caused the fault is corrected the unit will automatically transfer back to normal mode. For those cases where the unit does not transfer back automatically contact your Toshiba UPS service
representative at 1-877-867-8773 (outside the U.S. call 713-466-0277).
28
Description and Resolution
The batteries have less than 30%
power remaining. The warning will
continue until either the batteries
become completely exhausted or
AC input power is restored.
Alarm State
Alarm will
sound for
1-second at
5- second
intervals.
LED State
Warning/Fault Flash
Backup Flash
An output current limit warning is
typically a sign of misapplication.
The load may not be appropri-
ate for UPS support. For further
explanation contact your Toshiba
UPS service representative at 1-
877-867-8773 (outside the U.S. call
713-466-0277).
The temperature of the UPS operating
environment is too high. Causes of
this condition include allowing the room
Alarm will
sound for
1/2- sec-
ond at
1-second
intervals.
Warning/Fault Flash
80% Flash
Alarm will
sound for
1-second at
Warning/Fault Flash
100% Flash
temperature to exceed 104°F (40°C), a
blocked vent, or direct sunlight on the
unit. The unit will transfer to bypass
mode until the temperature is reduced.
If temperature is not reduced after an
allowable time, the unit will shut down.
15- second
intervals.
Display StateWarning
Warning
Low Battery
Current Limit
(Over
Current)
Ambient
Over Heat
29
Description and Resolution
This warning can be caused by
the same conditions listed for
Ambient Overheat. Another pos-
sible cause would be a problem
with the battery module, which
could prevent the unit from provid-
ing backup power.
Alarm State
Alarm will
sound for
1-second at
15- second
intervals.
LED State
Warning/Fault Flash
Battery Flash
This warning will occur if the input
voltage drops below the minimum
allowable voltage. If the unit was
online when the warning occurred it
will transfer to battery backup. If the
unit was in bypass the output will be
turned off. The unit will reinitialize the
startup sequence if input power returns
to within specied limits.
This warning will occur if the input volt-
age exceeds the maximum allowable
Alarm will
sound for
1/2-second
at 10-second
intervals.
Warning/Fault Flash
20% Flash
Alarm will
sound for
Warning/Fault Flash
40% Flash
voltage. If the unit was online when
the warning occurred it will transfer
to battery backup. If the unit was in
bypass the output will be turned off.
The unit will return to normal operation
if input power returns to within speci-
ed limits.
two 1/2-sec-
ond beeps
at 10-second
intervals.
Display State
Warning (cont.)
Warning
Battery Over
30
Heat
Input Under
Voltage
(see Note 1,
page 31)
Input Over
Voltage
(see Note 1,
page 31)
Description and Resolution
The input frequency is outside
specied limits. If the unit was online
when the warning occurred it will
transfer to battery backup. After the
backup the output will shutdown. If
the unit was in bypass the output will
be turned off. The unit will return to
normal operation if input frequency
returns to within specied limits.
Alarm State
Alarm will
sound for 3
1/2-second
beeps at
10-second
intervals.
LED State
Warning/Fault Flash
60% Flash
The connected load exceeds the
UPS power rating. Reduce the
load attached to the UPS. The unit
will automatically return to normal
when the load is reduced within the
allowable time limit. If the load is
not reduced, the output will be shut
down. (Details see Appendix B.)
Alarm will
sound for 1
second at
15-second
intervals.
Warning/Fault Flash
150% Flash
Display State
Warnings (cont.)
Warning
Input
Frequency
Regulation
(see Note 1)
Output
Overload
= Flashing LED = LED lit continuously
Note 1: If any of these warnings occur while the UPS is in online mode it will immediately transfer to backup mode. In this case
the percentage LED’s will be used to show the battery power status. To identify the cause of the warning listen to the number of
consecutive beeps. One beep indicates an input undervoltage, two beeps means input overvoltage, three beeps is a frequency
problem.
31
Description and Resolution
Battery pack is not connected or
needs replacement as soon as pos-
sible. Failure to replace the battery
pack could result in danger to the
user and failure of the system to
provide backup power.
Alarm State
Alarm will
sound for
1/2-second
at 1/2-sec-
ond inter-
vals.
LED State
Warning/Fault On
Battery On
The battery power of the unit has
been exhausted. The unit output
will shutdown. Batteries must
charge before backup power will
be available. For charging times
Continuous
alarm
Warning/Fault On
Backup On
see page 24.
This fault indicates an internal
problem with the UPS. Con-
tact your Toshiba UPS service
Alarm will
sound for
1/2-second
Warning/Fault On
20% On
representative at 1-877-867-8773
(outside the U.S. call 713-466-
0277).
at 1/2-sec-
ond inter-
vals.
Faults
32
Display State
Fault
Replace
Battery
Battery
Shutdown
DC Bus
Over Current
Description and Resolution
These faults indicate an
internal problem with the
UPS. Contact your Toshiba
UPS service representative at
1-877-867-8773 (outside the
U.S. call 713-466-0277).
Alarm State
LED State
Warning/Fault On
40% On
Display StateFault
Warning/Fault On
Alarm will
60% On
sound for
1/2-second
at 1/2-sec-
ond intervals.
Warning/Fault On
80% On
Faults (cont.)
DC Bus
Over
Voltage
DC Bus
Voltage
Imbalance
Output
Under
Voltage
33
Description and Resolution
This fault indicates an internal
problem with the UPS. Con-
tact your Toshiba UPS service
representative at 1-877-867-
8773 (outside the U.S. call
713-466-0277).
If the system Overheat Fault is
triggered under normal mode, the
unit will transfer to bypass. The
unit will shut down after a certain
amount of time in bypass. This
fault indicates an internal problem
with the UPS. Contact your
Toshiba UPS service representa-
tive at 1-877-867-8773 (outside
the U.S. call 713-466-0277).
Alarm State
LED State
Warning/Fault On
100% On
Display StateFault
Alarm will
sound for
1/2-second
at
1/2-second
intervals.
Warning/Fault On
150% On
Faults (cont.)
Output
34
Over Voltage
System
Over Heat
= Flashing LED = LED lit continuously

STORAGE OF UPS EQUIPMENT

GENERAL GUIDELINES

If the UPS equipment is to be stored; the following guidelines should be used.
Avoid:
1) Storage in sites subject to extreme changes in temperature or high humidity.
2) Storage in sites subject to exposure of high levels of dust or metal particles.
3) Storage on inclined oor surfaces or in sites subject to excessive
vibration.
Before Storing:
1) Allow UPS to be operated for 4 hours to ensure that the batteries
are fully charged.
2) Stop the unit (see “Stopping the UPS” on page 21).
3) Place the unit’s Input Breaker switch in the “off” position (see “Layout”, page 15).
Storing:
1) Store within a temperature range of -4° to 104°F (-20° to 40° C).
If the UPS is stored at a temperature outside of the allowable operating range, allow time for the unit to reach equilibrium with the ambient temperature before starting the UPS.
2) For best results, store the UPS in the original shipping container and place on a wood or metal pallet.
3) The optimum storage temperature is 70°F (21° C). Higher ambient
temperatures cause UPS batteries to need recharging more frequently.
35
Recharging requirements during storage:
Recharging the batteries requires that the UPS has AC input power available. The UPS can be in either the online or bypass mode. (See
“Starting the UPS System”, page 20, and “Battery Recharge Time”, page 24).
1) If stored in an ambient temperature less than 68°F (20°C), recharge
the batteries every 9 months.
2) If stored in an ambient temperature of 68° to 86°F (20° to 30°C), recharge the batteries every 6 months.
3) If stored in an ambient temperature of 86° to 104°F (30° to 40°C), recharge the batteries every 3 months.

DISPOSAL

Please contact your local environmental agency for details on disposal of electrical components and packaging in your particular area. It is illegal to dump lead-acid batteries in landlls or dispose of improperly. Please help our Earth by contacting the environmental protection agencies in your
area, the battery manufacturer, or call Toshiba toll-free at 877-867-8773 for
more information about recycling.
36
PREVENTIVE AND SCHEDULED
MAINTENANCE/PARTS REPLACEMENT

PREVENTIVE MAINTENANCE

Toshiba’s 1800 Series of UPS’ have been designed to provide years of trouble­free operation requiring a minimum of preventive maintenance.
The best preventive measure is to keep the area around the unit, particularly the air inlet vents, clean and free of moisture and dust accumulations. If the atmosphere of the installation site is very dusty, use a vacuum cleaner to periodically remove dust accumulations from the exterior of the unit, especially around ventilation openings. Schedule authorized Toshiba service centers to perform internal parts inspections annually, or call a Toshiba UPS service
representative at 1-877-867-8773 (outside the U.S. call 713-466-0277).
Note: Disconnect AC source before servicing
CAUTION
Proper maintenance of the battery system of this unit is essential to the safety and reliability of the UPS system.

PARTS REPLACEMENT

The following list shows intervals for periodic maintenance and replacement of certain UPS parts.
1) Batteries: Replacement should be done once every 3 to 5 years at a
minimum.
2) Cooling Fans: Replace once every 3 to 4 years. (Fan replacement must
be done by Toshiba authorized service personnel).
3) Battery Fuses: Replace the battery fuses every 7 years.
37

APPENDIX A: SPECIFICATIONS

Model Number
Rated Capacity
Input voltage Single phase 120VAC, +10% to -40%
Input transformer Isolation Transformer Auto Transformer
Input
Input frequency 50/60 Hz +/- 3 Hz
Input capacity
Input power factor Approximately unity (0.95 to 1.0)
Input voltage Single phase 120VAC, +10% to -10%
Output voltage Single phase 120VAC
Bypass
Overload rating 125% for 10 minutes, 150% for 5 minutes
Output voltage Single phase 120 VAC
Output transformer None Isolation Transformer
Output voltage regulation Within +/- 3%, steady state
Rated output current (rms) 12.5A 16.6A 20A 9.5A
Maximun output current (peak)
Output
Inverter overload capacity 125% for 60 seconds, 150% for 30 seconds
Crest factor 2.5 at full load
Output frequency 50/60 Hz (+/- 0.5% in free running mode, line sync range +/-1Hz)
Output voltage waveform Computer-grade sine wave with less than 3.0% total harmonic distortion with linear load
Rated load power factor 0.7
Effeciency (AC-DC-AC) 80% 80% 80% 79%
5
UG1A1A015C6TB 1UG1A1A020C6TB1UG1A1A024C6TB1UG1G2L024C6TB
1500VA (1.05KW) 2000VA (1.4KW) 2400VA (1.68KW) 2300VA (1.61KW)
2
(72VAC to 132 VAC)
3
1750VA 2250VA 2650VA 2600VA
4
31.25Apk 41.5Apk 50Apk 23.75Apk
208/240VAC, +10%
(125 VAC to 229VAC)
208/240 VAC +/- 10%
Single phase
to -40%1
Single phase
Single phase
208/240/120 VAC
Single phase
240/208 /120 VAC
4
Note 1: Currently under development, unit specications may be changed.
Note 2: Below 79% input voltage unit may begin parallel operation; supplementing input power with
Note 3: If input frequency is below 50 Hz, the input Voltage must not exceed 103% of rated input
Note 4: In BYPASS mode if the Input voltage is below 90% or above 110%, the UPS output will be
Note 5: The input capacity is computed to include peak battery charging power.
38
battery power. The point at which parallel operation begins is load dependent (for a detailed explanation of Parallel Operation see Appendix C: Parallel Operation).
Voltage.
turned off. (See Appendix D: Bypass Under Voltage/Over Voltage)
Model Number UG1A1A015C6TB1UG1A1A020C6TB1UG1A1A024C6TB1UG1G2L024C6TB
Battery rated voltage 48 Vdc
Estimated Battery backup time (fully charged, 0.7 load
power factor, 77°F (25°C)
Battery
Type 12V, ame retardant, valve regulated lead acid
Conguration 2 strings in parallel, 4 batteries per string
External Dimensions
(HxWxD)
Net Weight (unpacked,
Physical
unpalleted)
Operating temperature 32° to 104°F (0° to 40°C), optimal at 77°F (25°C)
Storage temperature -4 to 104°F (-20 to 40°C)
Operating Humidity 30 to 90%, non-condensing
Altitude Up to 3000 ft (1000m) above sea level
Evvironmental
Acoustical noise 55 dB at max. output, measured 3.3ft (1m) from front panel
Note 1: Currently under development, unit specications may be changed.
13 minutes
(at full load)
-- -- -- 23.3 x 9.9 x 28.3 (in.)
-- -- -- 181 lbs. (82 kg)
10 minutes
(at full load)
7 minutes
(at full load)
39

APPENDIX B: SYSTEM OVERLOAD

The 1800 Series UPS is capable of supporting short duration overloads.
Online Mode:
When operating in the On Line mode if the output load goes above the rated
load, the unit may start beeping indicating output overload. Output overload­ing of 125% of the rated output current can be supported for 1 minute, and
150% for 30 seconds. If the overload continues and does not drop to the
nominal rated load, the unit will eventually transfer to bypass mode.
Bypass Mode: If the output load is reduced below the output power rating, the unit will return to normal. If the unit transfers to bypass due to output overload twice in 10 minutes, the “return to normal” function is disabled and will never return to online mode until the alarm is reset by cycling (turning off then on) the input cir­cuit breaker. If the unit is in bypass mode and the output load is not reduced, the unit will eventually go to shutdown.
40

APPENDIX C: PARALLEL OPERATION

The 1800 Series UPS offers a standard feature that allows the unit to operate with very low input voltage without de-rating the output power. If the input voltage drops below a certain point the unit will switch to parallel mode. Parallel mode means that the unit is using the available input voltage and supplementing with battery power. Because battery power is being used, the time the unit can operate in parallel mode is limited. However, the time will be longer than that available when the unit is operating on battery power alone.
The point when the UPS will enter parallel mode will vary depending on the output load. The following graph illustrates the UPS’ transition from battery
to line power as the line voltage increases from 40% to 100% of normal.
Transition curves are shown for 75% and 100% output load.
120
100
80
60
Input Power (%)
40
20
0
Parallell Running: Input Power vs. Input Voltage
AC Input
100% Load
75% Load
Battery
85705540
Input Voltage (%)
As shown in the graph, the lower the output load, the lower the input voltage can go before parallel mode is activated. However, the minimum input voltage
will always remain at 60% (72 VAC for a 120 VAC system).
41
APPENDIX D: BYPASS UNDERVOLTAGE /
OVERVOLTAGE
When the 1800 Series UPS is in bypass mode the undervoltage and overvoltage
limits are restricted to +/-10% of the rated input voltage. If the input voltage is outside of this voltage window the UPS output will be turned off. There is a 5% hysteresis associated with both the upper and lower limits. This means that once output has been turned off the input voltage will have to be within ±5% of the rated input voltage before the startup sequence will re-initialize.
When the UPS is started, if the RUN/STOP switch is in the STOP (bypass)
position the unit will start in the on-line mode for 1 second before switching to bypass mode. If the input voltage is out of range the UPS will turn off the output after 1 second rather than switching to bypass.
42
APPENDIX E: 1800 MODEL/WIRE SIZE
SPECIFICATIONS
Model Number AC Input, AC Output, Ground,
and Selection Jumper Wire
UG1A1A015C6TB 12 AWG
UG1A1A020C6TB 10 AWG
UG1A1A024C6TB 10 AWG
UG1G2L024C6TB 14 AWG
Note: Tightening torque for all wires is 13 lb-in (1.5 N•m)
43
TOSHIBA INTERNATIONAL CORPORATION

LIMITED WARRANTY POLICY

(48 contiguous U.S. States, Canada, Mexico)
(UNINTERRUPTIBLE POWER SUPPLIES-UPS)
TOSHIBA INTERNATIONAL CORPORATION (“TIC”) warrants that the 1800 Series Uninterruptible Power Systems (“UPS”) and Uninterruptible Power System Battery (“BATTERY”) (external battery cabinet) sold by TIC to the end user (“User”) shall be free of defects in material and workmanship.
Series Capacity
1800 1.5, 2.0, 2.4 kVA 36 months No, Depot 24 months No, Depot M-F, 8am-5pm CT
UPS Unit Battery
Warranty1On-Site2Warranty1On-Site
Toshiba Dispatch
2
Note 1: The warranty period begins from the shipment date. The shipment
date is determined by the date on the TIC Bill of Lading.
Note 2: For the 1800 Series the warranty applies if the unit is sent and
returned (paid for) by the user to/from the Toshiba plant or a Toshiba designated Authorized Service Center.
Note 3: Toshiba Service dispatch is available during normal business hours.
24/7 (24 hour per day/7 days per week) service coverage programs
are available and can be purchased through TIC’s Service Depart­ment. TIC also encourages users to review TIC’s UPS Preventative and Scheduled Maintenance/Parts Programs for Premium coverage.
If any UPS, part of UPS, and/or BATTERY fails to conform or is defective then TIC will repair or replace it at TIC’s option.
LIMITATIONS AND EXCLUSIONS
This limited warranty shall not cover the UPS, UPS part, or BATTERY during their respective warranty periods, if the following storage, maintenance, installation, operating conditions are not met throughout the warranty periods (5 conditions below):
VALVE REGULATED LEAD ACID (VRLA) BATTERIES FOR TOSHIBA UPS
1. Temperature
REQUIRED OPERATING CONDITIONS
Annual Average
Temperature per cell
Temperature 25 °C
(77 °F)
< 32 °C (89 °F) for
more than 30 days
3
44
VALVE REGULATED LEAD ACID (VRLA) BATTERIES FOR TOSHIBA UPS
2. Maximum number of full charge/dis­charge cycles
INSTALLATION AND MAINTENANCE CONDITIONS
Discharge Time Maximum Number of
Cycles
(24 months)
30 min. 69
15 min. 86
10 min. 110
5 min. 130
3. Storage While UPS is in transit or storage it must al­ways be in suitable temperature (see Condi- tion 1).
4. External Batteries Parallel battery string applications must be approved by TIC in writing.
5. Idle Batteries User must recharge the batteries if not in use
(charged) for more than 6 months.
1. This Warranty does not cover damage or defect caused by misuse, improper
application, wrong or inadequate electrical current/voltage/frequency, inadequate connections, inadequate water or drain services, user negligence, repair by non-Toshiba designated personnel, accident during shipment, tampering, alterations, a change in UPS and/or BATTERY location or application, exposure to the elements, acts of God, theft, sabotage, installation contrary to
TIC’s recommendations or specications (Published Operation Manuals), also
if serial numbers have been altered, defaced, or removed.
2. Repair or replacement of a defective UPS, UPS part, and/or BATTERY does not extend the respective original warranty period. All defective UPS, UPS parts, and/or BATTERIES shall be the property of TIC upon replacement.
3. This warranty shall constitute the sole and exclusive remedy of all purchasers
and users of the UPS, UPS part, and/or BATTERY. TIC’s responsibility for UPS, UPS Parts, and/or BATTERY shall not exceed one times the net UPS and/or BATTERY purchase price. TIC HEREBY EXPRESSLY DISCLAIMS
ALL OTHER EXPRESS, STATUTORY AND IMPLIED WARRANTIES, INCLUDING WITHOUT LIMITATION, THE IMPLIED WARRANTIES OF MERCHANTABILITY AND FITNESS FOR A PARTICULAR PURPOSE.
PROCEDURE
User must contact TIC via e-mail upsservice@tic.toshiba.com, or phone
1-877-867-8773 (outside the U.S. call 713-466-0277), no later than 90
days after User’s discovery of occurrence or defect in UPS, UPS part,
45
and/or BATTERY but in no event after the expiration of the respective warranty period. Subject to the limitations of this policy and product type, TIC service or TIC service representative shall repair/replace the UPS/part warranted here­under, without charge for material, labor. If TIC determines that the requested repair is not covered under this limited warranty policy, then TIC shall advise customer and quote cost of repair. Repair charges shall be based on service parts price and prevailing service charges at the time of repair.
If the case in process is a BATTERY (stand-alone and/or cabinet) TIC will use its published Battery Diagnostic Document to evaluate warranty applicability. First, TIC will make sure that the storage, maintenance, installation, and oper­ating conditions were met; then the BATTERY capacity will be tested in accor-
dance with the “performance test” guidelines IEEE Std 450. If the BATTERY
fails to deliver 70% of its rated capacity it shall be deemed defective and be
replaced. Either oat or cyclic service will be used to determine the warranty
credit (as per published Battery Diagnostic Document). The typical credit ap­plied will be as in the following table:
CREDIT FOR REPLACEMENT BATTERY WHEN APPROVED WARRANTY
Time from Shipment UPS Batteries Cost to Customer
(Months) % Credit % List Price
0-24 100 0
25-30 55 45
31-36 45 55
37-42 35 65
43-48 25 75
49-54 15 85
55-60 5 95
MODIFICATIONS
No representative, salesperson, agent, distributor, or employee of TIC is
authorized to modify any of the terms of this warranty, unless modications are made in writing and signed by an authorized TIC ofcer.
THIS WARRANTY REPRESENTS THE ENTIRE AGREEMENT BETWEEN TIC AND USER WITH RESPECT TO THE SUBJECT MATTER HEREIN
AND SUPERSEDES ALL PRIOR OR CONTEMPORANEOUS ORAL OR
WRITTEN COMMUNICATIONS, REPRESENTATIONS, UNDERSTANDINGS
OR AGREEMENTS RELATING TO THIS SUBJECT.
46
NOTES
47
NOTES
48
NOTES
49
NOTES
50
INDUSTRIAL DIVISION
13131 West Little York road, Houston, TX 77041 Tel. 713-466-0277 Fax 713-466-8773 US 800-231-1412 Canada 800-872-2192 Mexico 01/800-527-1204
www.toshiba.com/ind
Copyright 9/2007
Loading...