TOSHIBA 4200FA UPS
Installation Planning Guide for 15-80kVA UPS
Standard System: 208/120V Input, 208/120V Output
General Mechanical Information
Dimensions
UPS kVA/ kW Rating
(W x D x H)
Inches Lbs. kBtu/Hr
15 kVA/12 kW 20 x 36.25 x 59.85 900 5.7
25 kVA/ 20 kW 20 x 36.25 x 59.85 910 7.6
30 kVA/ 24 kW 20 x 36.25 x 59.85 915 9.1
50 kVA/ 40 kW 35.59 x 38.19 x 59.39 2,548 17.7
80 kVA/ 64 kW 44 x 31 x 74 1,560 40.0
Primary AC Input (208/120V 3-Phase / 4-Wire)
Maximum Input Power
Demand
kVA PF Amps Amps AWG or kcmil at 75º C Temp. Rating Feet
15 >0.97 45.7 60 AT (1) x 8 / (1) x 6 380
25 >0.97 76.3 90 AT (1) x 4 / (1) x 2 380
30 >0.97 92.4 125 AT (1) x 3 / (1) x 1 380
50 >0.97 152.6 200 AT (1) x 1/0 / (1) 4/0 380
80 >0.97 244.3 300 AT (1) x 300 / (1) x 500 380
Suggested External
Overcurrent Protection
Optional Alternate AC Input (208/120V 3-Phase / 4-Wire)
Maximum Input Power
Demand
kVA PF Amps Amps AWG at 75º C Temp. Rating Feet
15 >0.97 41.6 60 AT (1) x 8 / (1) x 6 380
25 >0.97 69.4 90 AT (1) x 4 / (1) x 2 380
30 >0.97 83.3 110 AT (1) x 3 / (1) x 1 380
50 >0.97 138.8 175 AT (1) x 1/0 / (1) 4/0 380
80 >0.97 222.1 300 AT (1) x 4/0 / (1) x 400 380
Suggested External
Overcurrent Protection
Battery Input (288VDC Nominal)
Battery Capacity Required
for Full Load Output
kWB Amps DC Amps AWG or kcmil at 75º C Temp. Rating Feet
15 13.33 61.7 90 AT (1) x 6 70
25 22.22 102.8 125 AT (1) x 2 70
30 26.67 123.0 175 AT (1) x 1 70
50 44.44 205.7 225 AT (1) x 4/0 70
80 71.11 329.2 400 AT (2) x 3/0 70
Maximum Discharge
at Full Load Output
Suggested External
Overcurrent Protection
Weight Approximate Full-Load Heat Loss
Suggested Minimum Feeder
Wire Size Per Phase / Neutral
Suggested Minimum Feeder
Wire Size Per Phase / Neutral
Suggested Minimum Feeder
Wire Size Per Phase
Suggested Maximum Feeder Length
For Min. Wire Size in Steel Conduit
Suggested Maximum Feeder Length
For Min. Wire Size in Steel Conduit
Suggested Maximum Feeder Length
For Min. Wire Size in Steel Conduit
AC Output (208/120V 3-Phase / 4-Wire)
Rated Output Power
kVA PF Amps Amps AWG or kcmil at 75º C Temp. Rating Feet
Suggested External
Overcurrent Protection
15 0.8 41.6 60 AT (1) x 8 / (1) x 6 380
25 0.8 69.4 90 AT (1) x 4 / (1) x 2 380
30 0.8 83.3 110 AT (1) x 3 / (1) x 1 380
50 0.8 138.8 175 AT (1) x 1/0 / (1) 4/0 380
80 0.8 222.1 300 AT (1) x 4/0 / (1) x 400 380
Suggested Minimum Feeder
Wire Size Per Phase / Neutral
Suggested Maximum Feeder Length
For Min. Wire Size in Steel Conduit
Rev. 1.03 Page 1 of 2 4200FA-IPG-208v
TOSHIBA 4200FA UPS
Installation Planning Guide for 15-80kVA UPS
Standard System: 208/120V Input, 208/120V Output
Important Notes:
1. Maximum Current required at Primary AC Input based on full load output and maximum
battery charging current.
2. Output load conductors are to be installed in separate conduit from input conductors.
3. Control wires and power wires are to be installed in separate conduits.
4. Recommended AC input and output overcurrent protection based on continuous full load
current per NEC.
5. Wiring shall comply with all applicable national and local electrical codes.
6. Grounding conductors to be sized per NEC Article 250-122. Neutral conductors to be sized
per NEC Article 310.15.
- Primary AC Input: 3φ, 4-wire + ground.
- AC Output: 3φ, 4-wire + ground.
- DC Input: 2-wire (Positive/Negative) + ground.
7. Nominal battery voltage based on the use of VRLA type batteries (2.0 volts / cell nominal).
8. Maximum battery discharge current based on lowest permissible discharge voltage of 1.6
VPC.
9. DC wires should be sized to allow not more than a 2-volt drop at maximum discharge
current.
10. Weights include internal batteries.
11. Sizing calculations based on the following assumptions:
- Not more than 3 current-carrying conductors installed in steel conduit in ambient temperature of 30
degrees C.
- Temperature rating of conductors and terminals: 90 deg. C.
- Feeder distance calculations based on NEC Tables 8 and 9 data, allowing for 2% AC voltage drop.
- Reference: 2002 NEC Handbook. Consult latest edition of applicable national and local codes for
possible variations.
12. Ratings of wires and overcurrent devices are suggested minimums. Consult with a
registered Professional Engineer within your local area for proper size selections.