Toshiba 1400 Series, 1400 Plus Series Operation Manual

Page 1
UNINTERRUPTIBLE POWER SYSTEM
SINGLE PHASE - .6/.8/1.0/1.2/1.5/2 KVA
SINGLE PHASE - .5/.75/1.0/1.5 KVA PLUS
and
MANUFACTURED IN THE U.S.A.
OPERATION MANUAL
February, 1993 Part #37725
Page 2
WARRENTY CARD
INSERT
iii
Page 3
WARRENTY CARD
INSERT
iv
Page 4
TOSHIBA
INTRODUCTION
Thank you for purchasing the 1400/1400 Plus Series UPS. This Series features the very latest state of the art microprocessor technology and also uses IGBT transistors for fast, high power and low noise PWM (pulse width modulation) switching. Also, the Plus Series features a low impedence output transformer to provide isolation even during bypass operation.
It is the intent of this manual to provide a guide for installing, operating, and maintaining the UPS. Please read this manual thoroughly before installation and operation. All warnings and precautions should be observed for both personal safety and for proper equipment performance and longevity.
Important safety instructions are found on page viii. These safety instructions should be read and saved for future reference.
The manual is divided into major sections of interest. All of the initial inspection, storage, installation and operating precautions can be found in Sections 1 and 2 while Section 3 concentrates on the theory of operation and applications.
Section 4 contains the equipment standard specifications and Section 5 outlines the operating modes, protective features, battery recharging, battery low voltage tolerances, alarm and panel indicator functions.
Sections 6 and 7 are devoted to troubleshooting procedures, preventative maintenance techniques and periodic parts replacement. A fuse rating chart is also shown.
Section 8 shows front, rear, and side panel layout views with dimensional data. Labels, connector and switch placement, and shipping weights are also shown.
Section 9 shows the control interface pin configurations. And finally, we hope that you find this manual informative and easy to understand, and once
again thank you for the purchase of this product.
TOSHIBA INTERNATIONAL CORPORATION
Copyright 1993/February
©
v
Page 5
TOSHIBA
CONTENTS
SECTION PAGE
Warranty Card.........................................................................................iii-iv
Introduction............................................................................................... v
Contents................................................................................................. vi-vii
Important Safety Instructions .................................................................viii
1.0 Inspection/Storage ..................................................................................1-1
1.1 Inspection of the new UPS equipment ..............................................1-1
1.2 Storage of UPS equipment..............................................................1-1
2.0 Precautions..............................................................................................2-1
2.1 Installation Precautions ....................................................................2-1
2.2 Prestart Precautions ........................................................................2-1
2.3 Operating Precautions.....................................................................2-1
3.0 Product Description ................................................................................3-1
3.1 Theory of Operation .........................................................................3-1
3.2 Application and Use ........................................................................3-1
3.3 Power Backup .................................................................................3- 1
3.4 Power Conditioning .........................................................................3-1
4.0 Specifications ..........................................................................................4-1
4.1 Standard Series Specifications .......................................................4-1
4.2 Plus Series Specifications (w/output isolation transformer) ..............4-3
5.0 Operating the UPS...................................................................................5-1
5.1 Operation Modes.............................................................................5-1
5.1.1 AC Input Mode (normal operation)...........................................5-1
5.1.2 Battery Backup Mode .............................................................5-2
5.1.3 Circuit Bypass Mode...............................................................5-3
5.2 System Protection Features ............................................................5-4
5.3 Front Panel Indicator LED Functions...............................................5-5
5.4 Battery Backup Time .......................................................................5-5
5.5 Battery Recharging..........................................................................5-6
5.6 Battery Low Voltage Tolerances ......................................................5- 7
5.7 Audible Alarm Functions..................................................................5-7
vi
Page 6
TOSHIBA
CONTENTS (Cont'd)
SECTION PAGE
6.0 Troubleshooting Procedures .................................................................6-1
6.1 AC Line Indicator LED Not Lighting .................................................6-1
6.2 Inverter Indicator LED Not Lighting ...................................................6-2
6.3 Fault Indicator LED Lights................................................................6-3
6.4 AC Output Voltage Not Available .....................................................6-4
7.0 Preventive Maintenance/Parts Replacement.........................................7- 1
7.1 Preventive Maintenance...................................................................7-1
7.2 Parts Replacement..........................................................................7-1
7.3 Input/Output Fuse Rating Chart ........................................................7-1
8.0 External Dimensions/Shipping Weights/Panel Layout.........................8-1
8.1 External Dimensions for 500 through 1200 VA Model ......................8-1
8.2 External Dimensions for 1500 through 2000 VA Model ....................8-2
8.3 Panel Layout....................................................................................8-3
8.4 Shipping Weights ............................................................................8-3
9.0 Control Interface ......................................................................................9-1
9.1 Interface for 500 through 1200 VA Models .......................................9-1
9.2 Interface for 1500 and 2000 VA Models...........................................9-1
vii
Page 7
TOSHIBA
IMPORTANT SAFETY INSTRUCTIONS
SAVE THESE INSTRUCTIONS- This manual cont ains important instructions
for models UC0A1A005C6T, UC0A1A006C6, UC0A1A007C6T, UC0AIA008C6, UC0A1A010C6, UC0A1A010C6T, UC0A1A012C6, UC0A1A015C6, UC0A1A015C6T, and UC0A1A020C6 that should
be followed during the installation and maintenance of the UPS and it's batteries.
- The maximum ambient temperature in which this UPS unit should be operated or stored is 104 deg F (40 deg C).
- The nominal battery voltage range is indicated in Section 5.6 on page 5-7.
- Servicing of the batteries should only be performed by a qualified Toshiba Representative who is knowledgeable of batteries and the required precautions. Keep unauthorized personnel away from
batteries.
- When replacing batteries, use the same number and type of one of the following sealed, lead-acid batteries:
Model Capacity Manufacturer Type Quantity
500 VA Panasonic LCR 12V6.5BP 3
600 VA Panasonic LCR 12V6.5BP 3
750 VA Panasonic LCR 12V6.5BP 4
800 VA Panasonic LCR 12V6.5BP 4
1000 VA Panasonic LCR 12V6.5BP 5
1200 VA Panasonic LCR 12V6.5BP 6
1500 VA Panasonic LCR 12V6.5BP 6
2000 VA Panasonic LCR 12V6.5BP 8
- CAUTION- Do not dispose of the batteries in a fire. The batteries may explode.
- CAUTION- Do not open or mutilate the batteries. Released electrolyte is harmful to the eyes
and skin and could also be toxic.
Panasonic LCR 12V7.2P 3
Yuasa NP7 - 12 3
Panasonic LCR 12V7.2P 3
Yuasa NP7 - 12 3
Panasonic LCR 12V7.2P 4
Yuasa NP7 - 12 4
Panasonic LCR 12V7.2P 4
Yuasa NP7 - 12 4
Panasonic LCR 12V7.2P 5
Yuasa NP7 - 12 5
Panasonic LCR 12V7.2P 6
Yuasa NP7 - 12 6
Panasonic LCR 12V7.2P 6
Yuasa NP7 - 12 6
Panasonic LCR 12V7.2P 8
Yuasa NP7 - 12 8
- CAUTION- A battery can present a risk of electrical shock and high short circuit current. The
following precautions should be observed when working on the batteries:
1) Verify that the UPS is off and that the power cord is disconnected from the power source.
2) Remove watches, rings or other metal objects.
3) Use tools with insulated handles to prevent inadvertent shorts.
4) Wear rubber gloves and boots.
5) Do not lay tools or metal parts on top of batteries.
6) Determine if the battery is inadvertently grounded. If inadvertently grounded, remove source of ground. Contact with any part of a grounded battery can result in electrical shock. The likelihood of such shock will be reduced if such grounds are removed during installation and maintenance.
viii
Page 8
1.0 Inspection/Storage
1.1 Inspection of the new UPS equipment
Upon receipt of the UPS, a careful inspection for shipping damage should be made.
After Uncrating:
1) Check the unit for loose, broken, bent or otherwise damaged parts. If damage has occurred during shipment, keep all original crating and packing materials for return to shipping agent. Warranty will not apply to units which are damaged during shipment.
2) Check to see that the rated capacity and the model number specified on the nameplate conform to the order specifications.
1.2 Storage of UPS equipment.
If the UPS equipment is to be subject to long or short term storage the following guidelines should be used.
Avoid:
1) Storage in sites subject to extreme changes in temperature or high humidity.
2) Storage in sites subject to exposure of high levels of dust or metal particles
3) Storage on inclined floor surfaces or in sites subject to excessive vibration.
TOSHIBA
Before storing:
1) Charge the units batteries.
2) Place the UPS ON/OFF switch in the OFF position.
Storing:
1) Store within a temperature range of -20 to 40 deg C (-4 to 104 deg F).
2) For best results, store the UPS in the original shipping container and place on a wood or metal pallet.
3) The optimum storage temperature is 21 deg C (70 deg F). Higher ambient temperatures cause UPS batteries to need recharging more frequently.
After storing:
1) If stored in an ambient temperature under 20 deg C (68 deg F); recharge the batteries every 9 months.
2) If stored in an ambient temperature of 20 to 30 deg C (68 to 86 deg F); recharge the batteries every 6 months.
3) If stored in an ambient temperature of 30 to 40 deg C (86 to 104 deg F); recharge the batteries every 3 months.
1 - 1
Page 9
TOSHIBA
2.0 Precautions
2.1 Installation Precautions
1) Install the unit in a well ventilated location; allow at least 10 cm (4 inches) on
2) Install the unit in a stable, level, and upright position which is free of vibration.
3) Install the unit in an environment where the ambient temperature is
4) Do not install the UPS in areas that are subject to high humidity.
5) Do not allow direct sunlight to shine on the unit.
6) Do not install the UPS in areas which are subject to contamination such as
7) Avoid installation near sources of electrical noise and always make sure that
all sides for air ventilation and for maintenance.
between 0 to 40 deg C (32 to 104 deg F).
high levels of airborne dust, metal particles, or inflammable gas.
the unit ground is intact to prevent electrical shock and to help reduce electrical noise.
8) Do not install where water or any foreign object may get inside the UPS.
9) This UPS generates and can radiate radio-frequency energy during operation. Although RFI noise filters are installed inside the unit there is no guarantee that the UPS will not influence some sensitive devices which are operating close by. If such interference is experienced, the UPS should be installed farther away from the effected equipment and/or powered from a different source than that of the affected equipment.
2.2 Prestart Precautions
1) Before connecting the UPS to a power source; move the ON/OFF switch, on the front panel (See Section 8.1), to the OFF position.
2.3 Operating Precautions
1) The UPS should not be powered up until the entire operation manual has been reviewed.
2) The input power source voltage must be within +10% to -30% of the rated input voltage. The input frequency must be within the rated input frequency range. Voltages and frequencies outside of the permissible tolerance range may cause internal protection devices to activate.
3) The UPS should not be used with a load whose rated input is greater than the rated UPS output.
4) Do not use the UPS to provide power to motors that require high starting current or a long starting time such as vacuum cleaners and machine tools.
5) Do not insert metal objects or combustible materials in the unit's ventilation slots.
6) Do not place, hang, or paste any objects on the top or on the exterior surfaces of the UPS.
2 - 1
Page 10
3.0 Product Description
3.1 Theory of Operation
An uninterruptible power supply is a system that is installed between the commercial power and the load equipment. It is used during short-term blackouts or brownouts. The UPS provides steady ac output power during these commercial power interruptions. This power is provided for a long enough time so that the load can be shutdown in an orderly fashion. This prevents loss of data and possible damage to both hardware and software.
During normal operation the UPS uses commercial ac power. In addition, it also takes in all of the high voltage spikes and transients caused by switching and faults, and all of the common mode and normal mode noise which is associated with commercial ac power. The UPS converts it all to flat dc power. From this dc power, the UPS charges its batteries and generates its own extremely high quality ac waveform output. The result of this process is maximum power conditioning.
If the ac power supplied to the UPS drops below a specified voltage level, the unit's batteries automatically begin supplying power instead of receiving it. This insures that the loads connected to the UPS continue to receive power with no interruption. When ac input power becomes available again, operation returns to normal. The unit's batteries begin to recharge so they will be ready for the next power interruption.
TOSHIBA
3.2 Application and Use
Toshiba's 1400 Series of on-line uninterruptible power supply (UPS) systems provide continuous computer-grade ac power in a compact, high performance, and energy efficient unit. The UPS unit assures safe and reliable operation of critical office equipment. This can range from word processors and personal computers to mini­computers and local area networks. All units feature an audible alarm which sounds if the battery voltage drops below standard during use. This is an additional aid to help in retaining the valuable office data banks. All units allow for computer interfacing and and an external battery pack option (see specifications).
3.3 Power Backup
When an electrical power failure occurs, the UPS unit's internal maintenance-free batteries automatically supply back-up power to the load without interruption. For example, when used to support a computer, the UPS back-up assures enough additional time to complete the activity and store data. This allows an orderly shutdown after a power failure has occurred.
3.4 Power Conditioning
When commercial power is present, the UPS supplies conditioned power to the load while maintaining its batteries in a charged condition. The UPS protects against the normal everyday problems associated with heavy use of raw commercial ac power, including power sags, surges, signal interference, and spikes. This protection keeps power-line problems from reaching the loads where they can cause equipment to operate erratically, hard-disk crashes, or cause damage to hardware and software.
3 - 1
Page 11
TOSHIBA
4.0 Specifications
4.1 Standard Series Specifications
MODEL NUMBER UC0A1A006C6 UC0A1A008C6 UC0A1A010C6
CAPACITY 600 VA (0.42 kW) 800 VA (0.56 kW) 1000 VA (0.7 kW)
Input Input voltage Single phase, 120 Vac, +10% to -30%
Input frequency 45 to 65 Hz
Input capacity 660 VA 880 VA 1100 VA
Input power factor Approximate unity (0.98 to 1.0)
Battery Battery rated voltage 36 Vdc 48 Vdc 60 Vdc
Battery backup time when fully charged 8 mins. at full load (*) 8 mins. at full load (*) 10 mins. at full load (*)
with 0.7 power factor and 77° F (25° C) 24 mins. at half load (*) 24 mins. at half load (*) 30 mins. at half load (*)
Recharge time Maximum 10 hrs to 100% (***)
Type of batteries Sealed lead-acid
Output Output voltage Single-phase, 120 volts
Output voltage regulation Less than +/- 3%, steady state
Output frequency 50/60 Hz +/- 0.1% in free-running mode (line sync range +/- 1.0%)
Output voltage waveform Computer-grade sine wave with less than 3.0% total harmonic
distortion with linear load
Rated load power factor 0.7 lagging (0.6 to 1.0)
Voltage transient characteristic +/- 10% under 100% load step change
Rated output current (rms) 5.0A 6.6A 8.3A
Maximum peak output current (peak) 15.0A 19.8A 25.0A
Inverter overload capacity 150% for 60 seconds
Crest factor 3
Environment Operating temperature 32 to 104° F (0 to 40° C), optimal at 77° F (25° C)
Storage temperature -4 to 104° F (-20 to 40° C)
Operating humidity 30 to 90%, no condensation
Altitude(**) Less than 3000 ft (1000 m) above sea level
External dimensions 7.06W x 20.44D x 14.63H in (179W x 519D x 371H mm)
Weight 60 lb (27.2 kg) 66 lb (29.9 kg) 70 lb (31.8 kg)
Acoustical noise 45 dB at max. output, measured 3.3 ft (1 m) from front panel
Efficiency (ac-dc-ac) 89% 89% 89%
Switches Bypass switch Automatic bypass is provided when the run switch is in the off
position, if a fault occurs, or if an overload occurs
Transfer switch Mechanical switch provided (transfer time: approx. 4 mS)
Interface Novell (TM) local area DB9 connector (dry contact)
network Signals:(1)ac input present (NC) [ jumper selectable to (NO) ]
(2)low battery (NO)
Options Software for unattended
computer shutdown Contact Toshiba for details on this option
RS232 ASCII interface board Contact Toshiba for details on this option
External battery pack Contact Toshiba for details on this option
(*) Battery backup time may vary depending on the operating conditions and ambient temperature at the installation site. (**) At 6000 ft (2000 m) above sea level, output capacity should be derated by 3%. (***) An initial charge time of 24 hrs. is necessary to obtain proper battery performance level before unit is placed in operation.
4 - 1
Page 12
4.0 Specifications
4.1 Standard Series Specifications (Cont'd)
MODEL NUMBER UC0A1A012C6 UC0A1A015C6 UC0A1A020C6
CAPACITY 1200 VA (0.84 kW) 1500 VA (1.05 kW) 2000 VA (1.4 kW)
Input Input voltage Single phase, 120 Vac, +10% to -30%
Input frequency 45 to 65 Hz
Input capacity 1320 VA 1650 VA 2200 VA
Input power factor Approximate unity (0.98 to 1.0)
Battery Battery rated voltage 72 Vdc 72 Vdc 96 Vdc
Battery backup time when fully charged 11 mins. at full load (*) 9 mins. at full load (*) 11 mins. at full load (*) with 0.7 power factor and 77° F (25° C) 33 mins. at half load (*) 27 mins. at half load (*) 33 mins. at half load (*)
Recharge time Maximum 10 hrs to 100% (***)
Type of batteries Sealed lead-acid
Output Output voltage Single-phase, 120 volts
Output voltage regulation Less than +/- 3%, steady state
Output frequency 50/60 Hz +/- 0.1% in free-running mode (line sync range +/- 1.0%)
Output voltage waveform Computer-grade sine wave with less than 3.0% total harmonic
distortion with linear load
Rated load power factor 0.7 lagging (0.6 to 1.0)
Voltage transient characteristic +/- 10% under 100% load step change
Rated output current (rms) 10.0A 12.5A 16.6A
TOSHIBA
Maximum peak output current (peak) 30.0A 37.5A 50.0A
Inverter overload capacity 150% for 60 seconds
Crest factor 3
Environment Operating temperature 32 to 104° F (0 to 40° C), optimal at 77° F (25° C)
Storage temperature -4 to 104° F (-20 to 40° C)
Operating humidity 30 to 90%, no condensation
Altitude(**) Less than 3000 ft (1000 m) above sea level
External dimensions (1.2 KVA) 7.06W x 20.44D x 14.63H in (179W x 519D x 371H mm)
External dimensions (1.5 - 2 KVA) 7.06W x 23.16D x 14.63H in (179W x 588D x 371H mm)
Weight 76 lb (34.5 kg) 96 lb (43.6 kg) 106 lb (48.2 kg)
Acoustical noise 45 dB at max. output, measured 3.3 ft (1 m) from front panel
Efficiency (ac-dc-ac) 89% 89% 89%
Switches Bypass switch Automatic bypass is provided when the run switch is in the off
position, if a fault occurs, or if an overload occurs
Transfer switch Mechanical switch provided (transfer time: approx. 4 mS)
Interface IBM (TM) AS/400 DB9 connector (dry contact)
(****) Signals:(1)ac input present (NO) (3)inverter on (NO)
Options Software for unattended
computer shutdown Contact Toshiba for details on this option
RS232 ASCII interface board Contact Toshiba for details on this option
External battery pack Contact Toshiba for details on this option
(2)low battery (NO) (4)bypass active (NO)
(*) Battery backup time may vary depending on the operating conditions and ambient temperature at the installation site. (**) At 6000 ft (2000 m) above sea level, output capacity should be derated by 3%. (***) An initial charge time of 24 hrs. is necessary to obtain proper battery performance level before unit is placed in operation. (****) IBM (TM) AS/400 interface is used on 1500 and 2000 VA units only. The 1200VA unit uses Novell (TM) local area network (see page 4-1).
4 - 2
Page 13
TOSHIBA
4.0 Specifications
4.2 Plus Series Specifications (w/output isolation transformer)
MODEL NUMBER UC0A1A005C6T UC0A1A007C6T UC0A1A010C6T
CAPACITY 500 VA (0.35 kW) 750 VA (0.53 kW) 1000 VA (0.7 kW)
Input Input voltage Single phase, 120 Vac, +10% to -30%
Input frequency 45 to 65 Hz
Input capacity 550 VA 830 VA 1100 VA
Input power factor Approximate unity (0.98 to 1.0)
Battery Battery rated voltage 36 Vdc 48 Vdc 60 Vdc
Battery backup time when fully charged 10 mins. at full load (*) 10 mins. at full load (*) 10 mins. at full load (*) with 0.7 power factor and 77° F (25° C) 30 mins. at half load (*) 30 mins. at half load (*) 30 mins. at half load (*)
Recharge time Maximum 10 hrs to 100% (***)
Type of batteries Sealed lead-acid
Output Output voltage Single-phase, 120 volts
Output voltage regulation Less than +/- 3%, steady state
Output frequency 50/60 Hz +/- 0.1% in free-running mode (line sync range +/- 1.0%)
Output voltage waveform Computer-grade sine wave with less than 3.0% total harmonic
distortion with linear load
Common mode Less than 0.5V peak
Normal mode Less than 10V peak
Rated load power factor 0.7 lagging (0.6 to 1.0)
Voltage transient characteristic +/- 10% under 100% load step change
Rated output current (rms) 4.2A 6.3A 8.3A
Maximum peak output current (peak) 12.6A 18.9A 24.9A
Inverter overload capacity 150% for 60 seconds
Crest factor 3
Environment Operating temperature 32 to 104° F (0 to 40° C), optimal at 77° F (25° C)
Storage temperature -4 to 104° F (-20 to 40° C)
Operating humidity 30 to 90%, no condensation
Altitude(**) Less than 3000 ft (1000 m) above sea level
External dimensions 7.06W x 20.44D x 14.63H in (179W x 519D x 371H mm)
Weight 80 lb (36.4 kg) 85 lb (38.6 kg) 92 lb (41.8 kg)
Acoustical noise 45 dB at max. output, measured 3.3 ft (1 m) from front panel
Efficiency (ac-dc-ac) 89% 89% 89%
Switches Bypass switch Automatic bypass is provided when the run switch is in the off
position, if a fault occurs, or if an overload occurs
Transfer switch Mechanical switch provided (transfer time: approx. 4 mS)
Interface Novell (TM) local area DB9 connector (dry contact)
network Signals:(1)ac input present (NC) [ jumper selectable to (NO) ]
(2)low battery (NO)
Options Software for unattended
computer shutdown Contact Toshiba for details on this option
RS232 ASCII interface board Contact Toshiba for details on this option
External battery pack Contact Toshiba for details on this option
(*) Battery backup time may vary depending on the operating conditions and ambient temperature at the installation site. (**) At 6000 ft (2000 m) above sea level, output capacity should be derated by 3%. (***) An initial charge time of 24 hrs. is necessary to obtain proper battery performance level before unit is placed in operation.
4 - 3
Page 14
4.0 Specifications
4.2 Plus Series Specifications (w/output isolation transformer) (Cont'd)
MODEL NUMBER UC0A1A015C6T
CAPACITY 1500 VA (1.05 kW)
Input Input voltage Single phase, 120 Vac, +10% to -30%
Input frequency 45 to 65 Hz
Input capacity 1650 VA
Input power factor Approximate unity (0.98 to 1.0)
Battery Battery rated voltage 72 Vdc
Battery backup time when fully charged 10 mins. at full load (*) with 0.7 power factor and 77° F (25° C) 30 mins. at half load (*)
Recharge time Maximum 10 hrs to 100% (***)
Type of batteries Sealed lead-acid
Output Output voltage Single-phase, 120 volts
Output voltage regulation Less than +/- 3%, steady state
Output frequency 50/60 Hz +/- 0.1% in free-running mode (line sync range +/- 1.0%)
Output voltage waveform Computer-grade sine wave with less than 3.0% total harmonic
distortion with linear load
Common mode Less than 0.5V peak
Normal mode Less than 10V peak
Rated load power factor 0.7 lagging (0.6 to 1.0)
Voltage transient characteristic +/- 10% under 100% load step change
Rated output current (rms) 12.5A
TOSHIBA
Maximum peak output current (peak) 37.5A
Inverter overload capacity 150% for 60 seconds
Crest factor 3
Environment Operating temperature 32 to 104° F (0 to 40° C), optimal at 77° F (25° C)
Storage temperature -4 to 104° F (-20 to 40° C)
Operating humidity 30 to 90%, no condensation
Altitude(**) Less than 3000 ft (1000 m) above sea level
External dimensions 7.06W x 23.16D x 14.63H in (179W x 588D x 371H mm)
Weight 117 lb (53.2 kg)
Acoustical noise 45 dB at max. output, measured 3.3 ft (1 m) from front panel
Efficiency (ac-dc-ac) 89%
Switches Bypass switch Automatic bypass is provided when the run switch is in the off
position, if a fault occurs, or if an overload occurs
Transfer switch Mechanical switch provided (transfer time: approx. 4 mS)
Interface IBM (TM) AS/400 DB9 connector (dry contact)
Signals:(1)ac input present (NO) (3)inverter on (NO)
(2)low battery (NO) (4)bypass active (NO)
Options Software for unattended
computer shutdown Contact Toshiba for details on this option
RS232 ASCII interface board Contact Toshiba for details on this option
External battery pack Contact Toshiba for details on this option
(*) Battery backup time may vary depending on the operating conditions and ambient temperature at the installation site. (**) At 6000 ft (2000 m) above sea level, output capacity should be derated by 3%. (***) An initial charge time of 24 hrs. is necessary to obtain proper battery performance level before unit is placed in operation.
4 - 4
Page 15
TOSHIBA
5.0 Operating the UPS
5.1 Operation Modes
5.1.1 AC Input Mode (normal operation)
Bypass circuit
5-15P
Power input plug
Power input plug
Circuit breaker
receptacles (rear panel)
Fuse
UPS batteries
Power flow in AC input mode for 500, 600, 750, 800, 1000, and 1200 VA Models
Bypass circuit
UPS main circuit
UPS main
circuit
Output Xfmr (Plus Series)
+
= power flow
_
Fuse
UPS
5-15R
UPS receptacles (rear panel)
5-20P
UPS batteries = power flow
Power flow in AC input mode for 1500 and 2000 VA Models
Both of the above illustrations show circuit power flow in the ac input mode. The UPS unit's rectifier, included in a boost chopper circuit, converts ac input power to dc power. This dc power runs the unit's transistor inverter and charges the batteries. The boost chopper circuit maintains a constant voltage, with current limiting, for charging the batteries and assures proper sine waveform generation for the output current. The unit's batteries are maintained in a constantly charged state when the UPS is in the normal operation mode.
Output Xfmr (Plus Series)
+
_
5-15R
5 - 1
Page 16
5.0 Operating the UPS
5.1 Operation Modes (Cont'd)
5.1.2 Battery Backup Mode
Power input
plug
Fuse
5-15P
UPS batteries
Bypass circuit
UPS main
circuit
+
_
Output Xfmr (Plus Series)
TOSHIBA
UPS
receptacles (rear panel)
5-15R
= power flow
Power input plug
5-20P
Circuit breaker
Power flow in battery backup mode for 500, 600, 750, 800, 1000, and 1200 VA Models
Bypass circuit
UPS receptacles (rear panel)
FuseUPS main circuit
Output Xfmr (Plus Series)
+
UPS batteries
-
Power flow in battery backup mode for 1500 and 2000 VA Models
= power flow
5-15R
The above illustrations show power flow during the battery backup mode. When commercial ac power failures occur, the UPS's batteries instantly begin
supplying dc voltage to the UPS's main inverter circuit. This circuit changes (inverts) the dc power into ac power. The ac power is available at the unit's output receptacles. This back-up process will continue until the UPS's battery voltage drops below a specific minimum level. When this occurs, the batteries will stop supplying power to the load. This minimum level is the rated minimum voltage (Vmin). The rated battery voltage chart on page 5-6 (See Section 5.4 for battery backup time) shows (Vmin).
5 - 2
Page 17
TOSHIBA
5.0 Operating the UPS
5.1 Operation Modes (Cont'd)
5.1.3 Circuit-bypass Mode
Power input
plug
Fuse
Bypass circuit
UPS
receptacles (rear panel)
UPS main circuit
Power input plug
5-20P
5-15P
Circuit breaker
Output Xfmr
(Plus Series)
+
UPS batteries
_
Power flow in circuit-bypass mode for 500, 600, 750, 800, 1000, and 1200 VA Models
Bypass circuit
UPS main circuit
Output Xfmr (Plus Series)
Fuse
5-15R
= power flow
UPS receptacles (rear panel)
5-15R
UPS batteries
Power flow in circuit-bypass mode for 1500 and 2000 VA Models
If the UPS unit is overloaded or develops an internal fault, the power flow is automatically switched from the unit's main circuit to the bypass circuit mode. Power flow through the bypass is shown in the above illustrations. This change­over occurs automatically in approximately 4 milliseconds. The switching period is not long enough to cause interruptions to occur in most UPS equipment loads.
After repairing the cause of the inverter shutdown, the energy flow must be transferred manually from the UPS's bypass circuit back to the inverter circuit. This is done by toggling the ON/OFF switch (on the unit's front panel) first to OFF and then back to ON. This action resets (clears) the fault.
+
_
= power flow
5 - 3
Page 18
5.0 Operating the UPS
5.2 System Protection Features
The schematic shown below depicts the electrical locations of the protection devices on the 500, 600, 750, 800, 1000, and 1200 VA UPS models.
TOSHIBA
Power input plug
Power input plug
5-15P
Bypass
Input abnormal
Fuse
Battery
IGBT
+
-
Low battery level
IGBT
Over­current
Capacitor
Capacitor
IGBT
IGBT
Current limit Overload
Overvoltage Undervoltage
Overheating
The next schematic shown below depicts the electrical locations of the protection devices on the 1500 and 2000 VA UPS models.
Bypass
Input abnormal
Circuit breaker
IGBT
Over­current
Capacitor
IGBT
Current limit Overload
UPS receptacles (rear panel)
Fuse
5-15R
UPS receptacles (rear panel)
5-20P
Battery
+
­Low battery
level
IGBT
Capacitor
IGBT
Overvoltage Undervoltage
Overheating
5-15R
Notes:
1) The UPS's RECT/CHOPPER and INVERTER, although separate electrical circuits, are physically located on the same heat sink. This is applicable to all models.
2) The two UPS rear panel output receptacles are supplied from the UPS inverter section through separate 15A output fuses (applies to the 1500 and 2000 VA model only). Thus, an overload on one of the receptacle sets can cause a loss of power to it while the other receptacle set remains active. If all of the UPS indicator lights appear normal and power is not available at one of the receptacle sets, check the associated output fuse.
5 - 4
Page 19
TOSHIBA
5.0 Operating the UPS
5.2 System Protection Features (Cont'd)
The following table lists explanations for the protection features for the 500, 600, 750, 800, 1000, 1200, 1500, and 2000 VA UPS units.
UPS Protection Features
Item Overcurrent Over- Under- Overload Overheat
(OC) (OV) (UV) (OL) (OH)
Setting level Chopper OC: 140% 120% of rated 85% of rated 150% for 1 90 deg. C or
DC OC: 200% of the voltage (avg.) voltage min. of rated 194 deg. F main transistor's output current rating (instantaneous)
Cause Transistor fault (short Control Excessive load Overload; Fan failure;
circuit; load inrush malfunction connected to short circuit at high ambient current; control UPS output; load temperature malfunction control
Ope ratio n Transfer to bypass; Transfer to Transfer to Transfer to Transfer to mode after stop chopper, INV bypass; stop bypass; stop bypass; stop bypass; stop fault chopper, INV chopper, INV chopper, INV chopper, INV
Audible alarm None None None Yes None Visible alarm Fault light Fault light Fault light Fault light Fault light
5.3 Front Panel Indicator LED Functions
1.) AC LINE: This green LED lights when normal ac input power is being supplied to the UPS unit.
voltage voltage
malfunction
2.) INVERTER: This green LED lights when the inverter output voltage is normal.
3.) FAULT: This red LED lights when an overcurrent, overvoltage, overload, or overheating problem is detected. Operation of the unit's inverter is inhibited until the fault is corrected and the system is reset. Refer to Section 5.2 "System Protection Features" for details.
5.4 Battery Backup Time
The UPS unit's batteries provide about 10 minutes of back-up time for the 500 through 1200 VA capacity units and about 8 minutes of back-up time for the 1500 through 2000 VA capacity units. These times are valid when the unit is operating under full load. When the units are operating at half load, the batteries can power the load equipment about 3 times longer. The exact length of these times will depend on the UPS model used, condition of the batteries, amount of load, temperature and other variables. See battery backup time in the standard specifications Sections 4.1 and 4.2.
5 - 5
Page 20
5.0 Operating the UPS (Cont'd)
5.5 Battery Recharging
The graph below shows the typical voltage requirements for recharging the UPS unit's batteries.
TOSHIBA
Current
0.4 amp (A)
Voltage
Charging current
Vmax.
Vmin.
0
The recharge process usually consists of three periods. During the first period, the current is maintained at approximately 0.4 amperes. In the second period, the constant­voltage control starts and the current gradually decreases as the batteries continue to charge. In the third period, a slight current flows into the batteries to keep them fully charged. After a complete discharge, a full recharge usually requires 24 hours (90% recharge in 8 hours) for the 500 through 750 VA models and 30 hours (90% recharge in 8 hours) for the 800 through 2000 VA models.
Discharge shut-off point
0
Period 1
Time
Period 2 Period 3
Battery charge voltage
Fully charged
The chart depicted below shows the rated maximum and minimum battery voltages, and the charge current for each of the sizes.
Model Vmax. Vmin. Charge
600 VA 41.4 29.2 0.4 (A)
800 VA 55.2 38.9 0.4 (A) 1000 VA 69.0 98.6 0.4 (A) 1200 VA 82.8 58.3 0.4 (A) 1500 VA 82.8 58.3 0.4 (A) 2000 VA 110.4 77.8 0.4 (A)
500 VA Plus 41.4 29.2 0.4 (A)
750 VA Plus 55.2 38.9 0.4 (A) 1000 VA Plus 69.0 48.6 0.4 (A) 1500 VA Plus 82.8 58.3 0.4 (A)
Rated battery voltages
5 - 6
Page 21
TOSHIBA
5.0 Operating the UPS
5.6 Battery Low Voltage Tolerances
Excessive discharge will cause the UPS unit's battery voltage to drop. The chart shown below lists the voltage level at which each UPS unit's low-voltage alarm will sound and also at what level the low-voltage condition will cause the unit to automatically shut down.
UPS Capacity 600 800 1000 1200 1500 2000 500+ 750+ 1000+ 1500+
in VA
Nominal voltage 36 48 60 72 72 96 36 48 60 72
in Vdc
Alarm voltage 31.7 42.3 52.8 63.4 63.4 84.5 31.7 42.3 52.8 63.4
in Vdc
Shutdown voltage 29.7 38.9 48.6 58.3 58.3 77.8 29.2 38.9 48.6 58.3
in Vdc
5.7 Audible Alarm Functions
Audible alarms will sound when the UPS unit is in the battery backup mode, has low battery voltage, or is in an overload condition. The chart shown below depicts the audible alarm pattern for each condition. Time units are shown in seconds.
Condition Audible Pattern
UPS in battery backup mode (battery voltage: 100% - 88%)
UPS low battery voltage (voltage less than 88%)
Overload
5 S70 S
1 S1 S
0.3 S 0.3 S
5 - 7
Page 22
6.0 Troubleshooting Procedures
6.1 AC Line Indicator LED Not Lighting
6.1
TOSHIBA
Is the input
power plug securely Tighten the input plug.
connected?
YES
Is the AC input Reset input circuit breaker
circuit breaker or fuse or
open ? Replace the AC input fuse.
NO
Is the input voltage Connect to input voltage
above or below specified source within correct tolerance.
limits?
NO
NO
YES
YES
Contact your Toshiba
service representative. Continue normal operations.
Caution:
All UPS units contain hazardous voltages that have the potential to burn and shock. These voltages exist even if main power is disconnected. Only qualified personnel should perform troubleshooting or repair work on UPS units.
NO
Is the AC Line LED lit?
YES
6 - 1
Page 23
TOSHIBA
6.0 Troubleshooting Procedures
6.2 Inverter Indicator LED Not Lighting
6.2
Is the AC
line LED indicator
lit?
YES
Is the fault
LED indicator
lit?
NO
NO
YES
Go to
6.1
Go to
6.3
Is the On/Off Move the On/Off switch
switch in the ON to the ON position
position?
YES
Contact your Toshiba
service representative.
NO
6 - 2
Is the inverter
LED indicator
lit?
YES
Continue normal operations.
NO
Go to
6.3
Page 24
6.0 Troubleshooting Procedures
6.3 Fault Indicator LED Lights
6.3
Move On/Off switch
to the OFF position.
Disconnect the equipment
load from the UPS unit.
TOSHIBA
Move the On/Off switch
to the ON position.
Is AC LINE
LED lit?
YES
Is the INVERTER
LED lit?
YES
Is the FAULT
LED lit?
NO
NO
NO
Go to
6.1
Go to
6.2
1. Try the start-up procedure again after connecting the equipment load.
2. Reduce the load if an overload has occurred.
Contact your Toshiba
service representative.
YES
6 - 3
Page 25
TOSHIBA
6.0 Troubleshooting Procedures
6.4 AC Output Voltage Not Present
6.4
Is the AC
line LED indicator
lit?
YES
Is the inverter LED indicator
lit?
YES
Is the fault
LED indicator
lit?
NO
NO
NO
YES Go to
Go to
6.1
Go to
6.2
6.3
Is the UPS unit Replace the output fuses.
a 1500 or 2000 VA (See note 2 page 5-4)
model?
NO
Contact your Toshiba
service representative.
NO
YES
Is AC output
voltage present?
YES
Continue normal operations.
6 - 4
Page 26
7.0 Preventive Maintenance/Parts Replacement
7.1 Preventive Maintenance
Toshiba's 1400 Series of uninterruptible power systems have been designed to provide years of trouble-free operation requiring a minimum of preventive maintenance.
The best preventive measure that the UPS user can take is to keep the area around the unit, particularly the air inlet vents, clean and free of moisture and dust accumulations. If the atmosphere of the installation site is very dusty, use a vacuum cleaner to periodically remove dust accumulations from the system.
7.2 Parts Replacement
The following list shows recommended intervals for periodic replacement of certain UPS parts.
1) Batteries: In order to maintain system reliability, the UPS unit's batteries should be replaced once every 3 to 5 years. To ensure reliable operation, all of the batteries should be replaced at the same time.
2) Aluminum electrolytic capacitors: Replace once every 5 years.
3) Fuses: Replace once every 7 years (see output fuse rating chart below).
TOSHIBA
4) Cooling fan: Replace once every 3 years.
7.3 Input/Output Fuse Rating Chart
The following chart shows the recommended fuses for all UPS sizes.
Model Amp rating Fuse model no.
600 VA 15.0A LittleFuse 314015
800 VA 15.0A LittleFuse 314015 1000 VA 15.0A LittleFuse 314015 1200 VA 15.0A LittleFuse 314015 1500 VA 15.0A LittleFuse 314015 2000 VA 15.0A LittleFuse 314015
500 VA Plus 6.25A Bussman MDL-6.25
750 VA Plus 8.0A Bussman MDL-8 1000 VA Plus 10.0A Bussman MDA-10 1500 VA Plus 15.0A Bussman MDA-10
Fuse rating
7 - 1
Page 27
TOSHIBA
8.0 External Dimensions/Shipping Weights/Panel Layout
8.1 External Dimensions for 500 through 1200 VA Models
7.06
On/Off switch
Air vents
RS-232 C (optional)
14.63 DB-9 connector
Output receptacles
Air vents
Front View Rear View
20.44
Fuse
Input power cable
Dimensions are in inches
Side View
8 - 1
Page 28
8.0 External Dimensions/Shipping Weights/Panel Layout
8.2 External Dimensions for 1500 and 2000 VA Model
7.06
On/Off switch
Air vents
RS-232 C (optional)
14.63 DB-9 connector
Fuse
Output receptacles
Air vents
TOSHIBA
Fuse
Breaker
Input power cable
Front View Rear View
23.16
Dimensions are in inches
Side View
8 - 2
Page 29
TOSHIBA
8.0 External Dimensions/Panel Layout/Shipping Weights
8.3 Panel Layout
8.4 Shipping Weights
UPS Shipping Weight
Model Pounds Kilograms
600 VA 60 27.2
800 VA 66 29.9 1000 VA 70 31.8 1200 VA 76 34.5 1500 VA 96 43.6 2000 VA 106 48.2
500 VA Plus 80 36.4
750 VA Plus 85 38.6 1000 VA Plus 92 41.8 1500 VA Plus 117 53.2
8 - 3
Page 30
9.0 Control Interface
9.1 Interface for 500 through 1200 VA Models
TOSHIBA
1
UTILITY FAILURE
9.2 Interface for 1500 and 2000 VA Models
9876
35
COMMON
LOW BATTERY
5
DB9 FEMALE CONNECTOR NOVELL TYPE INTERFACE
UTILITY FAIL (NC)
-Jumper Selectable to ( NO) LOW BATTERY (NO)
DB9 MALE CONNECTOR AS/400 TYPE INTERFACE
UTILITY FAILURE
LOW BATTERY
ON UPS
COMMON
ON BYPASS
ALL SIGNALS (NO)
9 - 1
Page 31
TOSHIBA INTERNATIONAL CORPORATION
I
NDUSTRIAL DIVISION 13131 West Little York Rd., Houston Texas 77041 Tel: [800] 231-1412 Fax: [713] 466-8773 Telex: 762078
World Wide Web http://www.tic.toshiba.com
Printed in U.S.A.
Loading...