Toshiba 1000 User Manual

Page 1
1000 &1000+ SERIES
UPS USERS MANUAL
Page 2
I
The instructions contained in this manual ar e not intended to cover all of the details or variations in equipment, or to provide for every possible contingency concerning installation, operation, or maintenance. Should further information be required or if problems arise which are not covered sufficiently, contact your local Toshiba sales office or (877) 867-8773 or by e-mail at toshibaups@tic.toshiba.com.
The contents of thi s inst ruction m anual s hall n ot becom e a par t of or modi fy any prior or existing agreement, commitment, or relationship. The sales contract contains the entire obligation of Toshiba International Corporation (TIC) Uninterruptible Power Systems (UPS) Division. The warranty contained in the contract between the parties is the sole warranty of TIC's UPS Division and any statements contained herein do not create new warranties or modify the existing warranty.
Any electrical or mechanical modifications to this equipment without prior written consent of Toshiba International Corporation will void all warranties and may void the UL/CUL listing. Unauthorized modifications can also result in personal injury, death, or destruction of the equipment.
Page 3
II
UNINTERRUPTIBLE POWER SYSTEM
Complete the information below for the UPS received.
Unless otherwise specified on the warranty card, the warranty period for the UPS or UPS part is 36 months from the shipment date (see TIC Bill of Lading).
Unless otherwise specified on the warranty card, the warranty period for a UPS battery is 24 months from the shipment date (see TIC Bill of Lading).
Please complete the following information and retain for your records.
Job Number: ________________________________________________________
Model Number: _____________________________________________________
Serial Number: ______________________________________________________
Application: ________________________________________________________
Shipment Date: ______________________________________________________
Installation Date: ____________________________________________________
Inspected By: _______________________________________________________
January, 2013
Document Number: 57723-010
Page 4
III

Table of Contents

Manual’s Purpose and Scope ................................................................................ V
Contacting Toshiba International Corporation’s Customer Support Center ...... VII
EMC Statements ............................................................................................... VIII
General Safety Instructions .................................................................................. X
Important Safety Instructions ........................................................................... XIII
Instructions Importantes Concernant ...............................................................XVII
Inspection/Storage/Disposal .......................................................................... XVIII
Installation Precautions ..................................................................................... XX
Operating Precautions .....................................................................................XXII
1. Introduction ..................................................................................................... 1
2. System Description ......................................................................................... 1
2.1 General Description ....................................................................................... 2
2.2 Efficiency Optimizer Function ...................................................................... 3
2.3 Auto-Restart .................................................................................................. 4
2.4 Free Run Mode .............................................................................................. 4
2.5 Diagnostic Tests ............................................................................................. 4
2.6 System Configuration .................................................................................... 5
3. Storage ............................................................................................................ 6
4. Shipping .......................................................................................................... 6
5. Installation ....................................................................................................... 8
5.1 Environment .................................................................................................. 8
5.2 UPS Frequency Converter Option ................................................................. 8
5.3 Rear Panel Views ........................................................................................... 9
5.4 Connecting to main supply, loads, and external battery cabinet .................. 13
5.5 Front Panel Settings ..................................................................................... 16
6. Computer and Alarm Connections ................................................................ 18
Page 5
IV
6.1 RS-232 Standard Interface Port ................................................................... 18
6.2 Dry Contact Interface (optional card) .......................................................... 19
6.3 USB Port ..................................................................................................... 20
6.4 EPO Port (emergency power off) ................................................................ 20
6.5 Network Transient Protector ........................................................................ 20
6.6 Load Segments ............................................................................................ 20
7. User’s Guide to Operations ........................................................................... 21
7.1 UPS Startup and Shutdown ......................................................................... 21
7.2 Button Operation ......................................................................................... 21
7.3 Control Panel Functions .............................................................................. 22
7.4 Normal Display ........................................................................................... 23
7.5 UPS Meters Displa y .................................................................................... 24
7.6 UPS Configurations ..................................................................................... 24
7.7 UPS Manual Test ......................................................................................... 26
7.8 Interpreting UPS Messages ......................................................................... 26
7.9 Audible Alarms ............................................................................................ 26
7.10 Silencing an Alarm ...................................................................................... 26
7.11 Troubleshooting ........................................................................................... 27
8. Maintenance .................................................................................................. 28
8.1 Battery Servicing ......................................................................................... 28
9. Technical Specifications ................................................................................ 29
9.1 Power Range 1000-3000 VA (120 V) .......................................................... 29
9.2 Power Range 2400 VA (208/240 V) ............................................................ 30
9.3 Power Range 1000-3000 VA (230 V) .......................................................... 31
9.4 Backup Time at Partial Loads ...................................................................... 34
10. Warranty Information .................................................................................... 35
LIMIT ATIONS AND EXCLUSIONS ................................................................. 36
Page 6
V
Manual’s Purpose and Scope
The purpose of this manual is to provide informatio n on how to safel y install, o perate,
and maintain your TIC power electronics product. This manual includes a section of general safety instructions that describes the warning labels and symbols that are used throughout the manual. Read the manual completely before installing, operating, or performing maintenance on this equipment.
The scope of this manual is to describe the requiremen ts for an On-Line Uninterruptible
Power System (UPS). The UPS will supply a computer grade AC output sine wave which is unaffected by the quality of the AC input. The input voltage is single phase and the output voltage is single phase.
This manual and the accompanying drawings should be considered a permanent part of
the equipment and should be readily available for reference and review. Dimensions shown in the manual are i n metric and/or the En glish equivalent.
TIC reserves the right, without prior notice, to update information, make product
changes, or to discontinue any pr oduct or service identified in this publication.
Page 7
VI
TOSHIBA is a registered trademark of Toshiba Corporation. All other product or trade
references appearing in this manual are registered trademarks of their respective owners.
Toshiba International Corporation (TIC) shall not be liable fo r direct, indirect,
special, or consequential damages resulting from the use of the information contained within this manual.
This manual is copyrighted. No part of this manual may be photocopied or reproduced
in any form without the prior written consent of Toshiba International Corporation.
© Copyright 2013 Toshiba International Corporation. All rights reserved. Printed in the U.S.A.
Page 8
VII

Contacting Toshiba International Corporation’s Customer Support Center

Toshiba International Corporation’s Customer Support Center can be contacted to obtain help in resolvi ng any Uninterr uptible Power System pr oblems that you ma y experience or to provide application information.
The center is open from 8 a.m. to 5 p.m. (CST), Monday through Friday. The Support Center’s toll free number is US (877) 867-8773, Fax (713) 896-5212.
The email address is toshibaups@tic.toshiba.com.
You may also contact Toshiba International Corporation by writing to:
Toshiba International Corporation 13131 West Little York Road Houston, Texas 77041-9990 Attn: 1000 Series UPS Product Mana ger.
For further information on Toshiba International Corporation’s products and services, please visit our website at www.toshiba.com/ind
Page 9
VIII

EMC Statements

FCC Part 15

NOTICE: Pursuant t o section 15 of the FCC rule s each capacity unit has been tested and the 1000, 1500, and 2000 VA units comply with the conditions of a Class B digital device. The product has been established as offering sufficient protection against dangerous interference for installations in a residential area. The 2400 and 3000 VA units comply with FCC Section 15 c onditio ns of a Class A digital devic e. Installation and use of the equipment should comply with the ins tructi ons provide d in or der to av oid interference due to the amount of radio frequency energy that is radiated and generated by the equipment. TIC cannot assure that no interference will occur. Turn the unit on and off to help determine if the radio or television reception is found to be influenced by harmful interference from the equipment. If required, use one of the following measures to minimize the negative effects of interference:
Place the receiving antenna in a separate location or orientation.
Increase the distance between the receiver and the equipment.
Ensure that your equipment and the receiver are on separate circuits.
Contact a technician experienced with radio and TV or a dealer for further
assistance.

ICES-003

This Class A a nd B Interference Causing Equipment meets all requirements of the Canadian Interference Causing Equipment Regulations ICES–003. Cet appareil numérique de la classe A et B respecte toutes les exigences du Reglement sur le matériel brouilleur du Canada.
Page 10
IX

Declaration of Conformity Request

Units labeled with a CE mark comply with the following standards and directives: Harmonic Standards: EN 62040-1 and EN 62040-2. EU Directives: 73/23/EEC, Council Directive on equipment designed for use within certain voltage limits. 2006/95/EC, Amending D irective 93/68/EEC and 73/23/EEC. 89/336/EEC, Council Directive relating to electromagnetic c ompatibility. 2004/108/EC, Amending Directive 92/31/EEC and 89/336/EEC relating to EMC. The EC Declaration of Conformity is available upon request for products with a CE mark.
Page 11
X
Signal Words
DANGER

General Safety Instructions

DO NOT attempt to install, op erate, maintain or dispose of t his equipment until you have read and understood all of the product safety information and directions that are contained in this instruction ma nual.

Safety Alert Symbol / Signal Words

The Safety Alert Symbol indicates that a potential personal injury hazard exists. The symbol is comprised of an equilateral triangle enclosing an exclamatio n mark.
Listed below are the signal words that are used throughout this manual followed by their descriptions and associated symbols. When the words DANGER, WARNING, and CAUTION are used in this manual they will be followed by important safety information that must be carefully adhered to.
1. Danger — The word DANGER in capital letters preceded by the safety alert
symbol indicates that an imminently hazardous situation exists that, if not avoided, will result in death or serious injury to personnel.
Page 12
XI
WARNING
CAUTION / ATTENTION
CAUTION
2. Warning — The word WARNING i n capital letters preceded by the safety alert
symbol indicates that a potent ially hazardous situation e xists that, if not avoided, could result in death or serious injury to personnel.
3. Caution/Attention — The word CAUTION or ATTENTION in capital letters
preceded by the safety alert symbol indicates that a potentially hazardous situation exists that, if not avoided, may resu lt in minor or moderate injury.
4. The word CAUTION without the safety alert symbol indicates a potentially
hazardous situation exists which, if not avoided, may result in equipment and property damage.
Page 13
XII

Special Symbols

Other warning symbols may appear in conjunction with the Danger, Warning, and Caution symbol and are used to specify special hazards. These warnings describe
particular areas where special care and/or procedures are required in order to prevent serious injury and possible death.
1. ELECTRICAL HAZARD SYMBOL – Indicates a hazard that may cause injury
from an electrical shock or burn. The symbol is comprised of an equilateral triangle enclosing a lightning bolt.
2. EXPLOSION HARZARD SYMBOL – Indicates a hazard that may cause injury
from exploding parts. It is comprised of an equilateral triangle enclosing an explosion image.
Page 14
XIII

Important Safety Instructions

This manual contains important instructions that should be followed during the installation, maintenance, and operatio n of the UPS and its b atteries to ass ure safe and proper operation. SAVE THESE INSTRUCTIONS
Disconnect device in the building installation wiring.
Not for use in a computer room as defined in the Standard for the Protection of
Electronic Computer/Data Processing Equipment, ANSI/NFPA 75.
CAUTION - To reduce the risk of fire, the input of the unit is connected only to
a circuit provided with 20 amperes maximum branch circuit overcurrent protection in accordance with the National Electric Code, ANSI/NFPA 70
CAUTION - Disconnect switch for each ungrounded conductor of ac output
shall be provided by others. To reduce the risk of fire, the output of the unit is connected in series with branch circuit overcurrent protection for 20 amperes rating in accordance with the National Electric Code, ANSI/NFPA 70.
CAUTION - RISK OF EXPLOSION IF BATTERY IS REPLACED BY
AN INCORRECT TYPE. DISPOSE OF USED BATTERIES ACCORDING TO THE INSTRUCTIONS.
1. Turn of f , lock ou t, an d tagou t all powe r sou rces before conn ecting th e powe r wi ring
to the equipment or when performi ng maintenance.
2. Hardwire type UPS units are not equipped with an over-current protection device,
nor do they have an output disconnect for the ac output. Therefore, a user-installed circuit breaker should be provided between the UPS output and the load input.
3. The maximum ambient operating temperature is 40° C (104° F).
4. Battery servicing should be performed by a qualified Toshiba Representative only.
5. Unauthorized personnel should not service batteries.
Page 15
XIV
WARNING
CAUTION
6. Contact your nearest Toshiba authorized service center for battery replacement.

Qualified Personnel ONLY!

Qualified Personnel is one that has the skills and knowledge relating to the construction, installation, op eration, and maintenance of the electrical equip ment and has received safety training on the hazards inv olved (Refer to the lat est edition of NFPA 70E for additional safety requirements).

Qualified Personnel shall:

1. Have read the entire operation manual.
2. Be trained and authorized to safely energize, de-energize, ground, loc kout a nd tag
circuits and equipment, and clear faults in accordance with established safety practices.
3. Be trained in the proper care and use of protective equipment such as safety shoes,
rubber gloves, hard hats, safety glasses, face shields, flash clothing, etc., in accordance with established safety practices.
4. Be trained in rendering first aid.
5. Be knowledgeable of batteries and the required handling and maintenance
precautions.
For further information on workplace safety visit www.osha.gov
Misuse of this equipment could result in injury and equipment damage. In no event will Tos hiba C orporat ion be respons ible or l iable for eit her in direc t or consequential damage or injury tha t may result from the misuse of this equipment.
Do not dispose of the batteries in a fire. The batteries may explode.
Page 16
XV
CAUTION
DANGER
WARNING
Do not open or mutilate the batteries. Released electrolyte is harmful to the eyes and skin and could also be toxic.
Disconnect charging source prior to connecting or disconnecting batter y ter mina ls.
A battery can present a risk of electrical shock and high short circuit current.
Page 17
XVI
—Strict adherence to the following precautions is a requirement whe n wor ki n g wit h batteries— Disconnect charging source prior to connecting or disconnecting battery terminals.

To be performed by Qualified Personnel only.

1. Verify that the UPS is off and that the power cord is disconnected from the power
source.
2. Disconnect charging source prior to connecting or disconnecting battery termin als.
3. Remove watches, rings or other metal objects.
4. Use tools with insulated handles to prevent inadvertent shorts.
5. Wear rubber gloves and boots.
6. Do not place tools or any metal parts on top of batteries.
7. Determine if the battery is inadvertently grounded. If inadvertently grounded,
remove source of ground.
Contact with any pa rt of a grounded battery can result in electr ic al shock.
The likelihood of shock will be reduced if such grounds are removed prior to installation or maintenance.
Page 18
XVII
ATTENTION
ATTENTION

Instructions Importantes Concernant

LA SÉCURITÉ CONSERVER CES INSTRUCTIONS

Cette notice contient des instr uctions importantes concernant la séc urité .
Une battery peut présenter un risque de choc électrique, de brûlure par transfert d' énergie.
L' élimination des batteries est règlementèe. Consulter les codes locaux à cet effet.
Page 19
XVIII
CAUTION

Inspection/Storage/Disposal

Inspection

Upon receipt of the UPS, an inspection for shipping damage should be performed. Use caution when removing the unit from the pallet. Refer to labels or documentation attached to packing material.

Uncrating

Check the unit for loose, broken, bent or otherwise damaged parts. If damage has occurred during ship ping, ke ep all original cra ting and packing materials for return to the shipping agent. The warranty does not apply to damage incurred during shipping. Ensure that the rated capacity and the model number specified on the nameplate conform to the order specifications.

Storage

During periods of non-use, the following guidelines are recommended for storage.

Storage Preparation

1. Power up the UPS and allow it to operate with no load for 24 hours to fully charge
the batteries.
2. Stop the unit.
3. Disable the COLD START function prior to storing the unit by following the
instructions in section 4. Shipping, page 6.
4. Ensure the MCCB switch is in the Off position.

Storing Conditions

For best results, store the UPS in the original shipping container and place on a
wood or metal pallet.
Storage temperature — -4 – 104 °F (-20 – 40 °C).
Page 20
XIX
The optimum storage tempera ture is 70 °F (21° C). A higher ambient temperature
will requir e recharging the batteries more freq uently during storage.
Avoid the following storage locations:
Locations that are subject to extreme temperature changes or high humidity.
Locations that are subject to high levels of dust or metal particles.
Locations that are subject to excessive vibration.
Inclined floor surfaces.

Storage Maintenance

If stored at an ambient temperature less t han 68 °F (20 °C), recharge the batteries
every 9 months.
If stored at an ambient temperature of 68 – 86 °F (20 – 30 °C), recharge the
batteries every 6 months.
If stored at an ambient temperature of 86 – 104 °F (30 – 40 °C), recharge the
batteries every 3 months.

Disposal

Please contact your local or state environmental agency for details on disposal of electrical components and packaging in your particular area.
It is illegal to dump lead-acid batteries in landfills or dispose of improperly.
Please help our Earth by contacting the envi ronmental protection ag encies i n y our area, the battery manufacturer, or call Toshiba toll-free at (877) 867-8773 for more information about recycling.
Page 21
XX
CAUTION

Installation Precautions

1. Install the unit in a well-ventilated lo cation; allow at least 4 inc hes (10 cm) on all
sides for air ventilation and for mainte nance.
2. Install the unit in a stable, level and upright position that is free of excessive
vibration.
3. Install the unit where the ambient temperature is within the range specified.
4. Do not install the UPS in areas that are sub ject to high humidity.
5. Do not install the UPS in areas that allo w e xp osure to direct sunlight.
6. Do not install the UPS in areas that allow exposure to hig h levels of airborne dust,
metal particles, or flammable gases.
7. Do not install the UPS in areas near sources of electrical noise. Ensuring a proper
earth ground will reduce the effects of electri cal noise an d will reduce the potential for electrical shock.
8. Do not install the UPS in areas that would allow fluids or any foreign object to get
inside the UPS.
9. The UPS generates and can radiate radio-frequency energy during operation.
Although RFI noise filters are installed inside of the unit, there is no guarantee that the UPS will not influence some sensitive devices that are operating near by . If such interference is experienced, the UPS should be installed farther away from the affected equipment and/or powered from a dif ferent s ource than that of the af f ected equipment.
10. The user should provide output over -current protection for hardwired UPS systems.
11. After ensuring that all power sources are turned off and is olated in accordance w ith
established lockout/tagout procedures, connect the power source wiring of the correct voltage to the input termi nals of the UPS.
Page 22
XXI
CAUTION
12. Connect the output terminals of the UPS to the load (refer to NEC Article 300 –
Wiring Methods and Article 310 – Conductors For General Wiring). Size the branch circuit conductors in accordance with NEC Table 310.16.

Conductor Routing and Grounding

1. Use separate metal conduits for routing the input power, output power, and control
circuits.
2. Follow the wire size and tighteni ng tor que specifications.
3. Always ground the unit to reduce the potential for electrical shoc k and to help
reduce electrical noise.
4. A separate ground cable should be run inside the conduit with the input power,
output power, and control circuits.
THE METAL OF CONDUIT IS NOT AN ACCEPTABLE GROUND.
Page 23
XXII
CAUTION

Operating Precautions

1. The UPS should not be powered up until the entire operation manual has been read.
2. The voltage of the in put pow er sourc e must be wit hin the range of +10% to -30% of
the rated input voltage. The input frequency must be within the rated input frequency range. Voltages and frequencies outside of the permissible range may activate the internal protection devices.
3. The UPS should not be used with a load that has a rated input that is greater than the
rated output of the UPS.
4. Do not use th e UPS to prov ide pow er t o motor s tha t requ ire hi gh s tart ing cu rrent or
with motors that require a long starting time, such as v acuum cleaners and m achine tools (over sizing the UPS for lock rotor current would be required).
5. Do not insert metal objects or combustible materials in the ventilatio n slots of the
UPS.
6. Do not place, hang, or paste any objects on the exterior surfaces of the UPS.
7. The capacitors of the UPS maintain a residual charge for a while after turning the
UPS off. The required discharge time for each UPS typeform is provided via a cabinet label and a CHARGE LED. W ait for at least the minimum time indicated on the label and ensur e tha t the C HA RGE LED ha s go ne out be fo re o pe ning t he d o o r of the UPS once the UPS power has been turned off.
8. Do not attempt to disassemb le , modify, or repair the UPS. Call yo ur Toshiba sales
representative for repair information.
9. Turn the power on o nly after at taching ALL of the covers.
10. Do Not remove any covers of the UPS when the power is on.
11. If the UPS should emit smoke or an unusual odor or sound, turn the power off
immediately.
Page 24
XXIII
WARNING
CAUTION
MAINTENANCE NOTE
12. The heat sink and other components may become extremely hot to the touch. Allow
the unit to cool before coming in contact with these items.
13. War n i ng s ign s sh ou l d be pla ce d on or near the load as a notification that the load is
being powered by the UPS.
14. Additional warnings and notifications shall be p osted at the equipment installation
location as deemed required by Qualified Personnel.
While operating in the inverter mode, placing the breaker in the OFF position will switch the UPS to the battery backup mode. The output of the UPS will continue uninterrupted to the load. The unit must be in the bypass mode at the ti me that the breaker is placed in the OFF position for the UPS to shutdown power to the load.
After an Emergency Power Off (EPO), do not reset the breaker until the UPS has been fully discharged. The UPS could be damaged if the unit is not fully discharged before the breaker is reset.
The 1000 S eries UPS is not designed for field-level service. All troub leshooting and repairs will be done at the Depot-level.
Page 25
XXIV
Page 26
1

1. Introduction

The information provided in this manual covers single phase 1000 – 6000 VA uninterruptible power system s (UPS). Included in this manual is information on the installation, operation, safety precautions, shipping, and storage of the equipment. Installation must be carried out in accor dance with this man ual. Electrical ins tallatio ns must also follow local legislation and regulations. Only qualified personnel should install this equipment. Failure to comply with the warnings and precautions could prove to be fatal.

2. System Description

The purpose of the UPS is to protect sensitive systems from poor quality utility power, complete loss of power, or other associated problems. System types include computers, workstations, process control systems, telecommunications systems, sales terminals, or other critical instrumentation. Electrical interference may occur causing problems in AC power. Interference may come from lightning, the power company, radio transmissions, or motors. Normal operation of sensitive electrical equipment requires protection against power outages, low or high voltage levels, frequency variations, differential and common-mode noises, and transients. In order to prevent power line problems from reaching critical systems and causing damage to software, hardware or causing equipment to ma lfunc tio n, t he UP S he lps by maintaining a constant voltage, isolating critical load output, and cleaning the utility AC power.
Page 27
2

2.1 General Description

As a double conversion on-line UPS, it is able to supply uninterrupted, clean single-phase power to your critical systems while keeping batteries charged continuously, even if the utility power fails. Other features of the UPS includes
Auto-Restart feature (See detailed explanation on page 4)
Cold Start feature
Programmable Load Shed Receptacle
Intelligent Charger with Rapid Charge in only 4 hours to 90%
Wide Input Voltage Window
Wide Input Frequency Window for Complete Generator Compatibility
Input Power Factor greater than 0.97
Output Power Factor:
1000VA – 0.7 1500VA – 0.7 2000VA – 0.7 2400VA – 0.8 3000VA – 0.7 6000VA – 0.7
Multiple Languages LCD Display
Efficiency Optimizer Function – See detail explanation on page 3
Free Run Mode - See detailed explanation on page 4
Diagnostic Tests - See detailed explanat ion on page 4
Optional Network Interface Card, RemotEye II
Optional Environmental Monitoring Device
Auto-Restart in ON-Line mode after UPS shutdown.
No Cold Starts on first use (safety purpose) (See detailed explanation
on page 6)
Page 28
3
See Figure 1 for systems applicable to the UPS system.
Figure 1. B lock diagram
An input filter reduces transi ents on the main supply.
For maintaining full battery charge, AC power is rectified and regulated in the
rectifier feeding power to the inverter and battery converter.
DC power is converted to AC in the inverter and passes it on to the load.
Power to the load is maintained from the battery during a power failure.
The converter increases voltage for the inverter as required.

2.2 Efficiency Optimizer Function

The Efficiency Optimizer function is a new feature for the UPS that increases the cost effectiveness of the UPS by mini mizing power losses and reduces power consumption. Alternating between bypass and on-line modes is achieved automatically and in accordance with the conditions of the utility power. On-line mode may be used during times of utility power irregularities. The bypass mode should be used when power flow s
Page 29
4
smoothly in order to obtain the greatest efficiency. Irregularities can be detected in less than a second a nd the on-line mode can be reactivated immediately. Switching back to online mode oc curs when the input vo ltage exceeds ±10% (or ±15% selectable), when the input freq ue nc y exceeds ±3Hz, or when no input line is available. Although hi gh efficie ncy is st andard , the defaul t opera tion is the on-line mode. From the LCD display panel, Bypass can be activated as required or O n-line operation can be run permanently if preferred.

2.3 Auto-Restart

In the event tha t a po wer fail ure last s longer than the UPS b ackup ti me, the UP S will shut down. Upon power restoration, the UPS will restart automatically in On-Line mode, which includes output power being restored to the load an d the start of battery recharge.

2.4 Free Run Mode

Free run mode is a mode of oper at i on i n w hic h th e U PS outputs a pre-set frequency (50 or 60 Hz) regardless of the input freque ncy. The UPS operates in free run mode when the inp ut freq ue ncy is outs ide of the sel ecte d inp ut fr eque nc y range . When star ti ng the UPS, the targeted frequency is 50 or 60 Hz ±0.25 Hz.

2.5 Diagnostic Tests

When t he UPS is started, a diagnostic test is executed auto matically that checks the electronics and battery, and reports any problems on the LCD display. The advanced battery management system monitors the performance of the battery and will indicate if battery replacement is required. The battery ma nagement sys tem tests the battery every 30 days of normal mode operation. A battery discharge test is performed and reports any problems on the LCD display. Except during the first 24 hours after startup while the UPS is in charging mode, diagnostic tests can be performed manually from the front panel when requi red.
Page 30
5
batteries
capacity
UPS 1500VA
6 min
4 hours
UPS 2400VA
11 min
4 hours
UPS 6000VA
7 min
4 hours

2.6 System Configuration

The UPS device and the internal backup battery make up the system. Depending on the site and load requirements of the installation, available options may be utilized to create a tailored solution.
Planning a UPS system should include the following considerations:
The total demand of the protected system shall dictate the output power rating (VA).
Allow a margin for future expansion or calculation inaccuracies from measuring power requirements.
Backup time required will determine the battery size needed. If the load is less than
the UPS nominal power rating then the actual backup time will be longer.
Here are the following backup time for each model that is based in a 100% load.
Model
Backup time Internal
UPS 1000VA 7 min 4 hours
UPS 2000VA 6 min 4 hours
UPS 3000VA 5 min 4 hours
The following configuration options are available for enhanced UPS performance:
External Battery Cabinets. (Additional External Battery Cabinets are
available if more back-up time is needed.)
Connectivity options (Remote Contact, SNMP/WEB card).
Recharge time to 90%
Page 31
6

3. Storage

Please adhere to the following instructions if the UPS is not installed when received:
Store the equipment in its original packing and shipping carton.
Store the unit in a temperature of 59 – 77 °F (15 – 25 °C).
Ensure that the equipment is fully protected from wet or damp areas and from moist
air. In order to maintain the vitality of the batteries, ensure that the UPS is recharged every 6 months for at least 8 hours during storage.

4. Shipping

The cold star t function must be disabled before the UPS is shipped. Cold start applies power to the UPS output with no UPS input. This can pose a shock or fire hazard if the output terminals are shorted. Toshiba is not responsible for any resultant fire or damage if the cold start function is not disabled.
Cold Start Disable Procedure (1000/1500/2000/2400/3000/6000 VA):
1. Ensure the UPS is switched OFF.
2. Plug In AC Power.
3. For 1/1.5/2/3/6k VA UPS: Press and hold the Function Ke y while pre ssin g the
“Enter” key 3 times. For 2.4kVA UPS: Press and hold the Function Key while pressing the “Status” key 3 times.
4. After a beep sounds, unplug the AC power cord and wai t for UPS to s hut down
automatically.
** Note: Cold start will be automatically re-enabled when the UPS is plugged into commercial power and switched ON.
Page 32
7
The 1000 Ser ies UPS s hips with an adhesive patch that covers the ON/OFF Button to prevent accidentally pressing the On/Off Button during shipping. Follow the above procedure to disable Cold Start and close the cover to prevent a fire hazard.
Page 33
8

5. Installation

5.1 Environment

To ensure sa fe and proper operation, ensure that the installation conforms to the following specifications.
NOTE: Remove the protective plastic adhesive shipping cover over the Off-On
button before turning the UPS On.
Ensure that the installation location is con sistent with the following:
Avoid extreme temperature and humi dity. Maximal battery life can be attained with
a recommended temperature range of 15 °C to 25 °C.
Protect the equipment from moisture.
Space and ventilation requirements must be met. Ensure there is at least 100mm (4
inch) behind and 50mm (2 inch) on the sides of the UPS for ventilation.
Ensure that the front of the UPS remains clear for user access. The External Battery Cabinets must be installed next to or underneath the UPS.

5.2 UPS Frequency Converter Option

The UPS has an optional software upgrade that allows it to serve as a frequency converter. Installing this software allows the user to set the UPS output to 50 or 60 Hz regardless of the input frequency.
This option can be downloaded from the Toshiba website, www.toshiba.com/ind Follow the home page menu path to : UPS>> Options/Accessories>> 1000 series>> Software>> Frequency Conve rsion.
** Note: Installing the frequency converter software upgrade will disable the bypass function. (This insures that in the event of power loss you are not trying to, for example, run a 50 Hz load with 60 Hz commercial power.)
.
Page 34
9
(230V IEC)
EXTERNAL
BATTERY
BATTERY
(120V NEMA)
(230V IEC)
(120V NEMA)

5.3 Rear Panel Views 1000VA – 1500VA Tower Rear Panel

USB
USB

2000VA – 3000VA Tower Rear Panel

EXTERNAL
Page 35
10

2400VA Tower Rear Panel

Page 36
11
120
0
I/L
I/N
120
88
O/P ISO
0
88 0
120
120
240
0
OPISO
L1 L2 G
X1 X2
N
X3
G
Load MAX 100%
240
0
Terminal Block
120
0
I/L
I
/N
120
88
O/P ISO
0
88 0
120
120
240
0
OPISO
L1 L2
G
X1 X2
N
X3
G
Load MAX 100%
208
0
Terminal Block
120
0
I/L
I/N
120
88
O/P
ISO
0
88
0
120
120
240
0
OPISO
L1 L2
G
X1 X2
N
X3
G
Load MAX 50%
120
0
Terminal Block
120
0
I/L
I
/N
120
88
O/P
ISO
0
88 0
120
120
240
0
OPISO
L1 L2
G
X1 X2
N
X3
G
Load MAX 50%
120
0
Terminal Block

2400VA Power Wiring Options

The 2400VA unit is hardwired Input and Output only. Use the following wiring guidelines.
Note – Use minimum No. 14 AWG or 1.5 mm2, 60°C copper wire and 22 Lb-in Torque force when connecting to Input and Output connection.
1. X1-X3 – 240V – FULL LOAD
2. X2-X3 – 208V – FULL LOAD
3. X1-N or N-X3 – 120V – HALF LOAD
Page 37
12
RM-2U 120V NEMA
RM-2U 120V NEMA
RM-2U 230V IEC
RM-2U 120V NEMA with –P1 Option

1000 – 1500 VA Rack mount (2U) Rear Panel

2000 – 3000 VA Rack mount (2U) Rear Panel

Page 38
13
RM-2U 230V IEC
(Includes Battery Pack, not shown)

6000 VA Rack mount (UPS – 3U, Battery Pack – 3U) Rear Panel

5.4 Connecting to main supply, loads, and external battery cabinet 1000 – 3000 VA (Except 2400VA and 6000VA)

The AC input cable is supplied with all models except the 2400 VA and 6000 VA.
Ensure that the UPS is disconnected from the main supply and loads while
connecting the External Battery Cabinets.
Use the battery cable supplied with the External Battery Cabinet to connect the
External Battery Cabinet to the UPS. If more than one b attery cabinet is required ,
use the supplied cable.
RM-6U 208/240V NEMA
Page 39
14
A familiarity with the UPS parameter settings is required if changi ng the B attery
pack quantity as when us ing the External Batte ry Cabinet s .
Connect the input cable to the UPS and connect the other end to a grounded outlet.
The batteries will charge automatically when connected to the main supply.
The UPS may be used immediately to power a load. However, the maximum
battery back-up time will not be available until the recommended 8-hour minimum
charge time has completed.
If a Site Wiring Fault is displayed, rotate the connector.
After charging the UPS, connect the load to the UPS.
Do not connect any devices to the UPS that may cause overloading of the UPS or
that draws half-wave rectified current, such as hair dryers or vacuum cleaners.
See section 6 Comput er and Alarm Connections if co mputer or alarm (rear panel)
connections are used.
The installation is now complete.
Figure 2 Example of Installation of Plug & Play products.

2400 VA

The 2400 VA UPS input and output power is hardwired to the po wer terminals. The output of the UPS can be adjusted according to which output terminals are selected. See 2400VA Power Wiring Options, page 11.
Page 40
15

6000 VA

The 6000 VA UPS comes in two sections, a Power Module an d th e Battery Pack. Each unit is RM-3U tall. T he input power is hardwired to the UPS power input terminals. The UPS accepts ei ther 208V or 240V input. The UPS autosenses the input voltage and provides the corresponding output voltage (208V or 240V). The UPS provides two L6-30R receptacles.
Ensure that the UPS Main Circuit Breaker is open, and the UPS loads are
disconnected while connecting the External Battery Cabinet/s.
Use the battery cable supplied with the External Battery Cabinet to connect the
External Battery Cabinet to the UP S. If more than o ne b attery cabinet is required,
use the supplied cable. The batteries will charge automatically when connec ted t o
the main suppl y.
NOTE: The UPS may be used immediately to power a load. However, the
maximum battery back-up time will not be available until the recommended 8-hour
minimum charge time has completed.
After charging the UPS, connect the load to the UPS.
Page 41
16
Settings
Options
Default
Remarks
1) O/P VOLT SET
100/110/115/120/127
120 V
120 V (FOR LV series)
2) I/P FREQ SET
setting)
+/- 2%
+/- 7%
+/- 5%
Input Frequency range in
3) I/P BYPASS
setting)
+/- 10%
+10%
Input Voltage range when
4) FREE RUN
ON/OFF
ON If ON, enable UPS runs on
UPS will go to battery mode.
5) HE MODE SET
ON/OFF
OFF
If ON, enable UPS runs in
efficiency.
6) MANUAL
ON/OFF
OFF
If ON, enable UPS switch to

5.5 Front Panel Settings

Listed below are the default settings of the primary UPS parameters.
(output voltage set)
(input frequency
SET (input bypass
SET
208/220/230/2 40 Vac
+/- 5%
+10% -15% +15% -20%
230 V
-15%
230 V (FOR HV series)
Free Run mode
Bypass mode is on
Asynchronous mode. For example: If input freq 55Hz output freq stays at 60Hz.
If OFF, disable UPS runs on synchronous mode. For example: If input freq 55Hz,
High efficiency mode. The unit will be in bypass mode with 95% or higher efficiency.
If OFF, the unit will be in the online mode with 85%
BYPASS
Bypass mode immediately.
Page 42
17
Settings
Options
Default
Remarks
7) OUTLET
GROUP1/GROUP2
Option 4: 1 On /2 Off
Option 1
This is a load-shed feature.
8)BATTERY TEST
TEST?
Perform battery test
9) SILENCE SET
ON/OFF
OFF
10)BAT CABINET
0: EXT B. PACKS
0
Shown options when battery
11) SITE FAULT
ENABLE/DISABLE
DISABLE
Alarm on main computer
without group.
12) LANGUAGE
ENGLISH
ENGLISH
13) GENERATOR
ON/OFF
OFF
If ON, UPS will work with a
mode.
14) RS232
ENABLE/DISABLE
ENABLE
Option to enable and disable
SETTING
SET
SET
Option 1: 1 On /2 On Option 2: 1 Off /2 On Option 3: 1 Off /2 Off
1: EXT B. PACKS 2: EXT B. PACKS
GERMAN FRENCH SPANISH ITALIAN
immediately
Cabinets are connected
connected at wrong polarity or Installation to main supply
wide range o f voltages and frequencies, without switching back and forth between Line and Battery
CONTROL
Complete the i nst a l la t ion e ntirely befor e c ha nging the defaul t s e t ti ng s or c onne c t ing a load to the UPS.
the RS232 port. USB share the communication line with RS232. Only one option may be used at a time.
Page 43
18
Pin #
Signal
Direction (re UPS)
Functions
2
TxD
Output
TxD Output
3
RxD
Input
RxD / Inverte r Off Input
5
Common
Common
6 Output (Normally Open)
AC Fail (13VDC)
8 Output (Normally Open)
Low Battery (13VDC)
9 Output
8–24 VDC Power

6. Computer and Alarm Connections

At the rear of the UPS is an interface that allows direct communication with a computer system (see Figure 2, Pg. 14). There is a RS232 serial data interface, a USB data interface, and an e merge ncy p ower o ff switc h. The RS232 port and the USB interface cannot be used simultaneously. In addition there is an optional interface slot that allows for the installation of communications cards. It may be used in p ara llel with either the RS232 or USB ports. An SNMP/WEB card is available for the optional interface slot that allows for the RemotEy e II to manage and monitor the system over a network or over the internet.

6.1 RS-232 Standard Interface Port

Only the communica ti on c abl e pr ov i ded with the UPS may be used to connect the UPS to a computer when using the RS232 port of the UPS. Ensure that the operating system of the computer supports RS232 communications. Other advanced power protection solutions, such as S NMP, are available from your dealer. The RS-232 interface uses a 9-pin D-sub connector. The names and functions of the port pins are listed in the following table.
Note: In Bat tery mode, th e UPS will be turned off 2 minutes after 5V is applied to Pin 3 and Pin 5 for more than 5seconds.
DB9 Female Connector Outline
(facing connector)
Table 1 : RS232 Pin Out Signal
Page 44
19
Pin #
Description
I/O Type
7) Charger failure
Remote shutdown
Remove short be t ween Pin 4 & Pin 5: UPS swi tc h back
to Inverter/Run
5
Common
7
Battery low, normally open, active close
output
(Requires 2 seconds
for pin to activate)
(facing connector)

6.2 Dry Contact Interface (optional card)

DB9 Male Connector Outline
1 UPS fail, relay contact, normally open, active close. output 2 Summary alarm, relay contact, normally open, active close.
One of the following signals activate this signal:
1) Output fault
2) Bus fault
3) Over temperature
4) Overload
5) Over Charging
6) Battery test fail
3 GND for secondary 4
Short Pin 4 & Pin 5: Remote Output Shutdown
output
input
6 Bypass active, normally open, active close output
8 No connection input 9 Utility fail, normally open, active close
Note: Vcc Voltage is 9-12 Vdc.
Tabl e 2 : DryContact Pin Out Signal Chart
output
Page 45
20

6.3 USB Port

Connecting t he UPS t o a computer using the USB port of th e computer requires USB compliant hardware, PC operating system support, and a UPS driver. The RS232 serial port canno t be used when u sing the USB po rt. The USB cable is a standard cable and may be purchased separately.

6.4 EPO Port (emergency power off)

A customer-supplied switch located remotely may be used to open the EPO conn ec ti on and force the UPS output receptacles to be switched off. The EPO function shuts down the equipment immediately. An EPO will not provide an orderly shutdown. T he UPS will have to be manually restarted in order to regain power to the outlets. After an Emergency Power Off (EPO), do not reset the breaker until the UPS has been fully discharged. The UP S could be d amage d if t he uni t is not full y di scharged b efo re the breaker is reset.

6.5 Network Transient Protector

The network transient protector, located on the back panel, has both IN and OUT RJ45 10 baseT jacks and will protect a single network connector. Connect the input connector to the jack labeled IN, and the output connector to the jack labeled OUT.

6.6 Load Segments

The sets of receptacles known as load segments provide organized shutdown and startup of the equipment. Less critical equipment can be turned off during power outages saving battery p ower for critical loads. The load group status can be viewed from the LCD display and can be changed if necessary.
Page 46
21

7. User’s Guide to Operations

Normal ongoing UPS operation requires little or no user input. Star tup a nd shutdown requirements of the user are discussed in this section.

7.1 UPS Startup and Shutdown Starting the UPS

Ensure that installation is correct and that the input power cable is connected to a
properly grounded outlet.
Start the UPS by pressing the On/Off button on the front panel.
The UPS will start the inspection of internal functio ns, main s ynchronizatio n, and
inverter startup. A successful completion allows for output power via the outlets.
During the startup inspection the LCD will display Read y On. The LED will light
up when outp ut power has started and the LCD displa y will show Line Mode.
Apply power to the load.

Shutting Down the UPS

Shut off and disconnect the load.
Press and ho ld the UP S On/Off button for five seconds. The alarm will sound and
the UPS will shut down.
The LCD will momentarily display UPS OFF.
Note: In emergency situations the EPO should be used.

7.2 Button Operation

1. “ ” or ON/OFF is the UPS ON/OFF button. (a) Press and hold the ON/ O FF button for at least 3 seconds to t urn on the UP S . (b) When the UPS is operating, press and hold the Load ON /OFF button for at least
3 seconds to turn off the UPS.
Page 47
22
2. “ ” or ENTER is the Enter button. (a) Press and hold the Enter button for at least 2 seconds to read the parameter
settings of the UPS. Pre ss the Enter b utton a gain to cycle through each successive parameter.
(b) Ten seconds of inactivity will return the display to the original status.
3. “ ” or FUNC is the Function but ton. (a) Press and hold the Function button for at least 2 seconds to access the selectable
parameters. Press the Function button again to cycle throu gh each successi ve selectable parameter.
(b) Press the Enter button to view or change the displayed parameter .
(c) Ten seconds of inactivity will return the display to the original stat us.
4. STATUS (2400/6000VA Only) will display the UPS data. (a) Press and hold the Status button for at least 2 seconds to read the parameter
settings of the UPS. Pre ss the Enter b utton a gain to c ycle through each successive parameter.
(b) Ten seconds of inactivity will return the display to the original status.
5. ESCAPE (2400/6000VA Only) – Press Escape to return to the main display
immediately.

7.3 Control Panel Functions

The front panel is composed of five LED indicators, an LCD screen, and a speaker for audible alarms.
Rack-mounted units have international sy mbols stenciled next to the LED indicator s instead of text.
ON/OFF or — is on when the UPS is turned on (gre en).
ON-LINE or — is on when in the Normal or Static Bypass modes. Also
ON-BAT or — is on while operating in the B a ttery mode.
BYPASS or — is on while ope rating in the Bypass mode (yellow).
indicates that there is voltage at the output terminals (green).
Page 48
23
Tower Unit
ON ON-LINE ON-BATT BYPASS FAULT
FUNC ENTER ON/OFF
Rack Unit
FAULT or — is on during active UPS internal errors (red). FAULT is
accompanied by an audible alarm. Press any of the front pa nel buttons to cancel the alarm.
Status of the UPS, measurements, and alarms are all indicated on the LCD screen.
Figure 3 Control panels – 1000/1500/2000/3000VA
Figure 4 Control panel – 2400VA Tower/6000VA Rack Unit

7.4 Normal Display

The UPS sta tus i s s ho wn i n the normal display mode. The UPS Meters display and the Setting display may be accessed by pressing the Return button on Tower Unit and FUNC button on the Rack Unit.
Page 49
24
LCD Message
Description
O/P VOLT= xxx.xV
Shows Output AC V oltage
O/P FREQ= xx.x Hz
Shows Output Frequency
I/P VOL T= xxx.xV
Shows Input AC V oltage
I/P FREQ= xx.x Hz
Shows Input F requency
BAT VOLT= xx.xV
Shows Battery Voltage
O/P LOAD%= xx%
Shows Load % of Max Load
O/P W= xW
Shows Output Watts
O/ P VA = xVA
Shows Output VA
O/P CURR= xA
Shows Output Current
BACKUP TIME= xx min
Shows Estimated Backup Time in Minutes
BAT CHARG= xx%
Shows Approximate Percentage of Battery Capacity
TEMPERATURE= xxC
Shows Approxim ate Ambi ent Tem perature
BAT PACK NUM= x
Shows External Battery Pack Number
RATING = xxxxVA
Shows UPS Rating
CPU VERSION xx.x
Shows CPU Version

7.5 UPS Meters Display

Listed below are the parameters available for viewing from the UPS meters d isplay. Press this button to scroll through the parameters.

7.6 UPS Configurations

1) Parameter settings may be viewed from the UPS Settings display.
2) To enter the configuration mode, pres s and hol d the Function button for one sec ond.
The first configuration parameter will be shown on the LCD disp la y.
3) Press the Fu nction button again to s croll through the rema ining parameters.
Page 50
25
4) Press the Enter button to select a displayed parameter.
5) Press the Function button to scr oll through the op tions for the selected pa rameter.
Press the Enter button to select the setting.
6) If prompted to save the select ion, press the E nter button to either confirm or save
the selection. See the table on page 16 for a complete listing of the user-settable parameters.
7) If ther e is no u ser inp ut fo r te n sec ond s, t he U PS will exit the c onfi gura ti on mo de
and return to normal mode displaying Line mode.
Page 51
26

7.7 UPS Manual Test

Manual UPS and B attery tests may be performed fr om the UP S configura tion screen. Tests may be performed when the battery is not being charged. To run the battery test scroll to the “Manual Bat Test” parameter press the Enter button twice. ** Note: In order for t he U PS t o ope rate n orm ally , Ma nual Bypass shou ld alw ays be set to OFF because the load will not be protected by the unit when Manual Bypass is ON. *** Note: Turn off the UPS and ke ep the A C po wer on to use the Gene rator funct ion. (go to normal mode for \Generator\OFF).

7.8 Interpreting UPS Messages

Troubleshooting procedures described here provide instructions to b e used to isolate UPS malfunctions. Start the troubleshooting procedure in the event of a control p a nel a la rm.

7.9 Audi b le Al a r m s

While operating on battery power (O N BAT LED is on) the UPS will beep once at
5-second intervals.
While operating on battery power and the batter y power is low (ON BAT LED is
flashing) the UPS will beep twice at 5-second intervals.
In the event of an internal fault with an active alarm (ALARM LED is on), the UPS
will provide a co nstant audible alarm a nd display an err or message on t he LCD display.
While operating in the Bypass mode (BYPASS LED is on) the UPS will not beep.

7.10 Silencing an Alarm

With the exception of a LOW BATTER Y A larm , p ressing any of the front panel buttons will turn off the alarm. Select Silent Alarm Mode to disable all audible alarms.
Page 52
27
Output Overload
Two Beeps/sec
The UPS is overloaded (in
Remove loads from the UPS; least to
Over-Charge
Constant Beep
Overcharged Batteries.
Turn off loads. Turn off UPS. Call service @ 1-877-867-8773
Low Battery
2 Beeps/5 sec
UPS operating on Battery Power and w ill shut down
voltage.
The unit will restart
On-Battery
1 Beep/5 sec
UPS operating on Battery Power.
Save your data and perfor m a controlled shutdown.
Charger Failure
Constant Beep
Failed Charger.
Call service @ 1-877-867-8773
Over-Temperature
Constant Beep
High ambient
Ensure that the UPS fans and
mbient temp. is < 40° C. If
1-877-867-8773
Output Short
Constant Beep
Output short circuit.
Call service @ 1-877-867-8773
High output Voltag e
Constant Beep
High output voltage.
Call service @ 1-877-867-8773
Low Output Volta g e
Constant Beep
Low output voltage.
Call service @ 1-877-867-8773
Bus Fault
2 Beeps/sec
High internal DC bus Voltage.
Turn off loads. Turn off UPS. Call service @ 1-877-867-8773
Site Wiring Fault
1 Beep/sec
Voltage detected between
UPS main connector has wrong
n supply without
the Site wiring alarm.
Wrong AC Line backed

7.11 Troubleshooting

Displayed on LCD Audible Alarm Alarm Description What You Should Do
Line Mode). More power required than the UPS can provide. The UPS operates in bypass.
most critical. If this solves the problem, the UPS will return to normal operation.
Battery Test No Beeps Battery test active. No action needed.
User Notification only.
Automatically when acceptable
soon due to low battery
Temperature.
power returns.
vents are not blocked, and that the a problem persists call service @
Line Abnormal 1 Beep/sec
neutral and ground.
up during auto restart.
polarity. Rotate the connector (Schuko-electric contact). UPS installed to mai ground. See section 5.5 for informati on on how to disa bl e
Page 53
28
Manufacturer
Type
Rating
REW45-12FR
12 Vdc, 8.0 Ah

8. Maintenance

With a minimal amount of maintenance you can expect years of satisfactory operation from the UPS unit. The most critical issues for the reliability of the UPS are environmental issues. Ensure that the temperature and humidity are always in accordance with the specifications and keep the area around the unit clean and dust free. The typical battery lifetime is 4 years when operated at 77° (25 °C). Check the back-up time capability of the UPS/batter y at 6 to 12 month intervals to ensure adequate support for the application.

8.1 Battery Servicing

Servicing of batteries should be performed or supervised by personnel knowledgeable about batteries and the required precautions. See IMPORTANT SAFETY INSTRUCTIONS – Qualified Personnel.
CAUTION – When replacing batteries, replace with the same type and number of batteries.
Battery Type: Lead-Acid Type Battery Rating: Total DC 72V, 9 6 Ah. (6 Pcs Battery/SET, 2 SET) Replacement batteries available:
TAIWAN YUASA BATTERY CO LTD (MH28947)
REW45-12 12 Vdc, 8.0 Ah
Page 54
29
Tower
US 120V Model
UT1A1A010C6
UT1A1A015C6
UT1A1A020C6
UT1A1A030C6
Rack­mount (2U)
US 120V Model
UT1A1A010C6R KB2
UT1A1A015C6R KB2
UT1A1A020C6R KB2
UT1A1A030C6R KB2
Input
Voltage
120 VAC (80 – 144 V)
Volta ge Range
+20% to -33%
Frequency
50 / 60 Hz auto sensing
Power Factor
Greater than 0.97
Topology
True on-line Double conversion Input PF correction
Output
Voltage
120 VAC
Capacity (VA)
1000 VA
1500 VA
2000 VA
3000 VA
Capacity (W)
700 W
1050 W
1400 W
2100 W
Frequency
50 / 60 Hz auto sensing *
Wave Form
Sine wave, zero transfer time
Load Power Factor
0.70
Efficiency AC/DC/AC
Greater than 86%
Greater than
85%
Rated Current
8.3 A
12.5 A
16.6 A
25 A
Overload
125% for 1 min 150% for 10 sec
125% for 1 min
sec
Crest Factor
3.0 at full load
2.5 at full load
Battery
DC Voltage (Tower & 2U)
36 V / 12 V
9 AH x 3
72V / 12 V
9 AH x 6
Backup Time (Tower & 2U)
7 min
(full lo a d )
6 min
(full load)
6 min
(full lo a d )
5 min
(full lo a d )
Interface
RS-232 and USB standard RemotEye II® and EMD option
Physical
Dimensions (Tower)
16.5”L x 6.0”W x 9.4”H
16.7"L x 8.9"W x 14.2"H
Dimensions (2U)
16.7”L x 16.9”W x 3.5”H
25.0"L x 16.9"W x 3.5"H
Weight (Tower/2U)
35.6 lbs /
37.6 lbs
37.4 lbs /
37.6 lbs
68.4 lbs /
69.5 lbs
72.6 lbs /
71.5 lbs
Line Cord
5-15P
5-20P
L5-30P
Receptacles (Tower/2U)
NEMA 5 - 15 P (6 / 6)
Tower - NEMA 5-20 P (12)
2U - NEMA 5-15 P (4)
Environ-ment
Operating Temperature
32 – 104°F (0 – 40°C)
Altitude
11500 ft (3500 m) above sea level
Warranty
Three years on electronics
details.)

9. Technical Specifi cations

9.1 Power Range 1000-3000 VA (120 V)

Capacity
Output frequency can hard set at 50 or 60 Hz by installing an optional software upgrade. This upgrade enables the user
to select a fixed output frequency and simultaneously d isables the b ypass mo de.
Standards - Safety:UL-1778, Emissions: FCC Part 15 Class B (1000-2000 VA) FCC Part 15 Class A (3000 VA)
130% for 10
Two years full replacement on battery (See Toshiba warranty policy for full
Page 55
30
Tower
US 208/240 Model
UT1G2L024C6T
Input
Voltage
208 or 240 VAC (161 – 276 V)
Volta ge Range
+15% to -34%
Frequency
50 / 60 Hz auto sensing
Power Factor
Greater than 0.97
Topology
True on-line Double conversion Input PF correction
Output
Voltage
120/208/240 VAC
Capacity (VA)
2400 VA
Capacity (W)
1920 W
Frequency
50 / 60 (45-65) Hz auto sensing *
Wave Form
Sine wave, zero transfer time
Load Power Factor
0.8
Efficiency AC/DC/AC
Greater than 87%
Rated Current
10 A @ 240V
Overload Capacity
125% for 1 min 130% for 10 sec
Crest Factor
3.0 at full load
Battery
DC Voltage
72V / 12 V (9 AH x 6)
Backup Time
11 min (full load)
Interface
RS-232 and USB standard RemotEye II® and EMD option
Physical
Dimensions
23.2”L x 10.1”W x 27.6”H
Weight
154.3 lbs
Line Cord
None (Hardwired)
Receptacles
None (Hardwired)
Environmen t
Operating Temperature
32 – 104°F (0 – 40°C)
Altitude
3300 ft (1000 m) above sea level
Warranty
Three years on electronics
full details.)

9.2 Power Range 2400 VA (208/240 V)

Two years full replacement on battery (See Toshiba warranty policy for
Output frequency can hard set at 50 or 60 Hz by installing an optional software upgrade. This upgrade en ables the u ser
to select a fixed output frequency and simultaneously d isables the bypass mode. Standards – FCC Part 15 Class A (2-3kVA), UL 1778, ICES-0003 Safety – EN 62040-1, Emissions: E N 62040-2, Immunity: EN 62040-2 Categor y C2
Page 56
31
1000 Series 6kVA Specification
Specification
Rackmount
US 208/240V
UT1G1G060C6RKB3 + UT1-BR-0607
True on-line, Double conversion, IGBT Power Factor Correction Input
Certifications
CE
Input
Voltage (V)
Single Phase - 208/240Vin
Capacity (VA)
6kVA Frequency
45-65 Hz auto sensing
Frequency Synchronization
± 3Hz
Power Factor
Greater than 0.97
Current THD
Less than 15%
Cold Start (0 to 100% load)
Defaul t Outp u t Frequency 60 Hz
Earth leakage (max.)
2mA (UPS only)
Bypass
Voltage (V)
+10/-15% of nominal (default)
+10/-10% of no mi n a l
+15/-20% of nominal
Set by display panel
Output
Voltage
208V or 240V
Voltage Regulat ions
± 3% Capacity (W)
4.2kW
Frequency
50 / 60 Hz auto sensing
Battery Mode/Free Run Mode
± 0.25 Hz
Wave Form
Sine wave, zero transfer time
Load Power Factor
0.7 PF Efficiency AC/DC/AC
Greater than 89% at Nominal Voltage
High Efficiency Mode Efficiency
Greater than 92%
Rated Current (based on 240V)
25.0 Inverter Overload Capacity
125% for 1 min, 150% for 10 sec
Crest Factor
3.0 at full load
0%100%0%; ± 15 % max.
20%100%20%; ± 9 % max.
Volta ge Transient Recovery (R type Load)
On-line Transfer Time – Inverter to Bypass and Bypass to Inverter
High Eff icienc y Tr a nsfer Ti me –
Inverter
Short Circuit Protection
Electronic overload and short circuit.
Voltage Total Harmonic Distortion (Full Linear Load)
Voltage Total Harmonic Distortion (Full N on-Linear Load)
Steady State Output Voltage Regulation
Common Mode Noise
less than 0.5 Vrms
Leakage Current
.5mA
Surge Protec tion
MOV 260 Jules on Output

9.3 Power Range 6000 VA (208/240 V)

General
Topology
Volta ge Transient Response (battery mode with R type load)
Return to nominal voltage within 30 ms
Less than 4m sec
Inverter to Bypass and Bypass to
Less than 4m sec transfer time
Less than 3 % THD
Less than 5 % THD
No-load to Full-load +/- 2% at full battery.
Page 57
32
Battery
Acceptable manufacturer
Yuasa Taiwan only
Type / Rating
9AH/12V Valve Regulated Lead Acid, Flame Retardant
Back-up Time at Full Load (at 25 degree C) (min)
Battery Bus Voltage (VDC)
240 Number of Batteries
20 Recharge
4 hours to 90% for all ratings
Battery Mode Voltage Regulation
±3% RMS for entire battery voltage range and 0 to 100% load
Battery Leakage
100 mA maximum
Battery Test
Automatic and Manual
Replaceable Batteries
Not Hot-Swappable
Battery Protection
Fuse Pre-alarm Level
2 minutes
1.67 VPC, ± 3% of battery voltage at FL with level automatically raised for lighter loading
Overcharge Protection
2.50 VPC, ± 3% of ba ttery voltage
Maintains proper float voltage per battery specification over a
C)
2.25 minimum, 2.275 nominal, 2.30V maximum voltage of batter y voltage
Protection against Batteries Deep Discharge
Environment
Operating Temperature
0 - 40oC (32 - 104oF)
Storage Temperat u re
-20 - 40oC (-4 - 104oF)
Operating Humidity
30-90% (No Condensation)
Altitude
11500 ft (3500 m) above sea level
Acoustical Noise
50dB( A) ma x i mum at 1 mete r fr o m F ront Panel
Heat Generation (BTU/Hour)
2234BTU/Hour
Mechanical
Dime nsions ( Rack mount) LxWxH
16.8 in. x23.5 in. x10.5 in. (427 mm x 597mm x 267m m)
Weight (Rackmount)
148lbs (67.1 kg)
Line Cord
Terminal Block with L6-30P (option to remove the L6-30P)
Receptacles
(2) L6-30R
Enclosure of unit made f r om sheet metal meets NEMA 1 and UL Type 1 Standard
Paint System
Black Color
Front Panel
1000 Series Panel
Connectors/Options
EPO
Battery Connectors
Option card Slot (Network and Dry Contact)
Buzzer Volume
Mute/Unmute
Warranty
Three years on electronics
Two years full replacement on battery (See Toshiba warranty policy for full details.)
Battery Level @ Shutdown
Temperature Compensated Charger
Voltage Level
7 minutes
temperature range of 10 to 40 degree C (2.3V/cell at 25 degree C with a temperature coefficient of minus 5 milliv olts per degree
Output frequency can hard set at 50 or 60 Hz by installing an optional software upgrade. This upgrade en ables the u ser
to select a fixed output frequency and simultaneously d isables the b ypass mo de. Standards – FCC Part 15 Class A (2-3kVA), UL 1778, ICES-0003 Safety – EN 62040-1, Emissions : EN 6204 0-2, I mmunit y: EN 62040-2 C ategory C2
Enclosure
Page 58
33
Tower
International 230V Model
UT1E1E010C6
UT1E1E015C6
UT1E1E020C6
UT1E1E030C6
Rack­mount (2U)
International 230V Model
UT1E1E010C6 RKB2
UT1E1E015C6 RKB2
UT1E1E020C6 RKB2
UT1E1E030C6RKB 2
Input
Voltage (International)
230 VAC (161 – 276 V)
Voltage Range (International)
+20% to -30%
Frequency
50 / 60 Hz auto sensing
Power Factor
Greater than 0.97
Topology
True on-line, Double conversion Input PF correction
Output
Voltage (International)
230 VAC
Capacity (VA)
1000 VA
1500 VA
2000 VA
3000 VA
Capacity (W)
700 W
1050 W
1400 W
2100 W
Frequency
50 / 60 Hz auto sensing*
Wave Form
Sine wave, zero transfer time
Load Power Factor
0.7
Efficiency AC/DC/AC
Greater than 86%
Greater than 85%
Rated Current (International)
4.3 A
6.5 A
13 A
13 A
Overload Capacity
125% for 1 min., 150% for 10 sec.
125% for 1 min., 130% for 10 sec.
Crest Factor
3.0 at full load
2.5 at full load
Battery
DC Voltage (Tower & 2U)
36 V / 12 V
9 AH x 3
72V / 12 V
9 AH x 6
Backup Time (Tower & 2U)
7 min
(full lo a d )
6 min
(full lo a d )
5 min
(full lo a d )
5 min
(full lo a d )
Interface
RS-232 and USB standard RemotEye II® and EMD option
Physical
Dimensions (Tower)
16.5”L x 6.0”W x 9.4”H
16.7" L x 8.9" W x 14.2" H
16.7" L x 8.9" W x
14.2" H
Dimensions (2U)
16.7”L x 16.9”W x 3.5”H
25.0"L x 16.9"W
x 3.5"H"
25.0"L x 16.9"W x
3.5"H"
Weight (Tower/2U)
35.6 lbs /
37.6 lbs
37.4 lbs /
37.6 lbs
68.4 lbs /
69.5 lbs
72.6 lbs / 71.5 lbs
Line Cord (International)
IEC 320
Receptacles
International
IEC 320 (4 / 4)
IEC 320 (8 / 4)
IEC 320 (8 / 4)
Environ­ment
Operating Temperature
32 – 104°F (0 – 40°C)
Altitude
11,500 ft (3500 m) above sea level
Warranty
Three years on electronics

9.4 Power Range 1000-3000 VA (230 V)

Output frequency can hard set at 50 or 60 Hz by inst alling an optional software upgrade. This upgrade enables the user to select a fixed output frequency a nd simul taneo usly disables the bypass mode. Standards - Safety: EN 62040-1, Emissions: EN 62040-2, Immunity: EN 62040-2 Category C1 (1000-2000VA), EN 62040-2 Category C2 (2000-3000VA
(Tower/2U)
Two years full replacement on battery (See Toshiba warranty policy for full detail s.)
Page 59
34
Load
10%
20%
30%
40%
50%
60%
70%
80%
90%
100%
1000 VA Backup (min)
150
56
38
30
23
19
15
12
10 7 1500 VA Backup (min)
80
37
21
19
18
15
13
11 8 6
2000 VA Backup (min)
150
68
38
26
19
14
11 9 7 6 2400 VA Backup (min)
200
76
53
42
33
28
22
18
15
11
3000 VA Backup (min)
80
40
25
19
15
12 9 8 6 5
6000 VA Backup (min)
45
36
29
22
18
15
13
11 9 7

9.5 Backup Time at Partial Loads

Below is the estimated backup time at various fractions of full load for each 1000 Series model. This table assumes the batteries are fresh and begin with a .full initial charge
Ta ble 9.1 – Backup Time vs. Partial Load
Page 60
35
UPS Unit
Battery
Toshiba
(5)
UPS
Warranty (1)
On-Site
(2)
Battery
Warranty (3)
1, 1.5, 2, 2.4,
3, 6
36 months from
shipment
No,
Depot
24 months from
shipment
Series UPS the warranty applies if the units are sent and returned (paid for) by the user
Shipment date is determined by date on the TIC Bill of Lading * 24 month full replacement, 36 month
Programs for Premium coverage.

10. War ranty Information

TOSHIBA INTE R NATIONAL CORPORATION
LIMITED W ARRANTY POLICY
(48 contiguous U.S. States, Canada & Mexico)
(UNINTERRUPTIBLE POWER SYSTEM)
TOSHIBA INTERNATIONAL CORPORATION (“TIC”) warrants that any Uninterruptible Power System (“UPS”) and Uninterruptible Power System Battery (“BATTERY”) (internal UPS battery and/or extern al battery cabinet) sold by TIC to an end user (“User”) shall be free of defects in material and workmanship. This warranty applies to all UPS seri es in table below:
UPS
Series
Unit kVA
On-Site (4)
Dispatch
1000
Note (1) Shipment date is determined by date on the TIC Bill of Lading.
Note (2) For 1000 to/from the Toshiba Plant or a Toshiba designated Authorized Service Center.
Note (3)
pro-rated warranty (5 yr total)
Note (4) For 1000 Series UPS the warranty applies if the unit s a re se nt an d re tur ne d ( pa id f or ) by the us er to/ fr om the Toshiba Plant or a Toshiba Designated Authorized Service Center .
Note (5) Toshiba Service dispatch available at normal business hours. Contacting Toshiba is possible 24 hours 7 days a week. User can purchase 24x7 dispatch programs offered th rough TIC’s Servi ce Depart ment. TIC also encourages users to review TIC’s UPS Preventative and Scheduled Maintenance/Parts
If any UPS, UPS parts, and/or BATTERY f a il to conform or is defective the n TIC, at its opt io n, will repair o r replace it at the premises of the User (On-Site), The warranty period for a UPS or a UPS part is 12-36 months from shipmen t exc ept for cases st ated i n table a bove. Th e warranty period for the BATTERY is 24 months from shipment except for cases stated in the table a bove
.
No, Depot Depot Only
Page 61
36
Valve Regul ated L ead A cid (V RL A ) Batte ries for To shiba U PS Re quire d O perati ng, Installation, and
Maintenance C o n di tions
Annual Average Temperature is to be 77°F (25 °C) with no greater temperature of 89 °F (32 °C) for more than 30 days
Maximum Number of Cycles (24 Months)***
Discharge Time
Battery > 9 AHr
Battery < 9 AHr
30 min
20
69
15 min
25
86
10 min
32
110
5 min
38
130
*** > 9AHr Typically extended runtimes < 9AHr Typically Single Phase Systems.
While UPS is in Transit or in storage, it must always be in a suitable temperature (as stated above)
4. External Battery
Parallel battery string applications must be approved by TIC in writing
User must rec harge the batteries if not in use (charged ) for more than 6 months
Credit for Replacement Battery When Approved Warranty
Time from Shipments
UPS Batteries
Cost to Customer
Months
% Credit
% List Price
0-24
100 0 25-30
55
45
31-36
45
55
37-42
35
65
43-48
25
75
49-54
15
85
55-60 5 95

LIMITATIONS AND EXCLUSIONS

1. This limited warranty shall not cover the UPS, UPS parts, or BATTERY during their
respective warranty periods, if the following storage, maintenance, installation, operati ng conditions are not met throughout the warranty periods (5 conditions below):
1. Temperature
2. Maximum # of Full Charge/Discharge Cycles
3. Storage
5. Idle Batteries
2. Thi s Warranty does not cover d amage or defect caused by misuse, improper app lication, wrong or
inadequate electrical current/voltage/frequency, inadequate connections, inadequate water or drain services, user negligence, repair by non-Toshiba designated personnel, accident during shipment, tamperin g, alterations, a chan ge in UPS and/or BATTERY locati on or application, exposure to the elements, act s of God, f orce nature, theft, sabotage, installation contrary to TIC's recommendations or specifications (Published Operation Manuals), also if serial numbers have been altered, defaced, or removed.
Page 62
37
3. Repair or rep l acement of a defective UPS, UPS part, and/or BATTER Y does not extend the respective
original warrant y period. All defecti ve UPS, UPS parts, and/ or BATTERIES shall b e the property of TIC upon replacement.
4. Thi s warranty sha ll constitut e the sole and exclu sive remed y of all purch asers and user s of the UPS,
UPS part, and/or BATTERY. TIC’s responsibility for UPS, UPS Parts, and/or BATTERY shall not exceed one times the net UPS and/or BATTERY purchase price. TIC HEREBY EXPRESSLY
DISCLAIMS ALL OTHER EXPRESS, STATUTORY AND IMPLIED WARRANTIES, INCLUDING WITHOUT LIMITATION, THE IMPLIED WARRANTIES OF MERCHANTABILITY AND FITNESS FOR A PARTI CULAR PURPOSE.
User must contact TIC via e-mail upsservice@tic.toshiba.com days after User’s discovery of occurrence or defect in UPS, UPS part, and/or BATTERY but in no event after the expiratio n of the r espe ctive war ranty per iod. S ubject to the l imitat ions o f th is po licy and prod uct ty pe, TIC service or T IC servi ce rep res ent ati ve sh all r epa ir/ replac e th e UPS/ pa rt warra nted hereu nd er, wit hou t cha rge for material, labor (on-site except in cases presented herein). If TIC determines that the requested repair is not covered under this limited warranty policy, then TIC shall advise customer and quote cost of repair. Repair charges shall be based on service parts price and pr evailing service charges at the time of repair.
If the case in process is a BATTERY (stand-alone and /or cabinet) TIC will use its published Battery Diagnostic Document to evaluate warranty applicability. First, TIC will make sure that the storage, maintenance, installation, and operating conditions were met; then the BATTERY capacity will be tested in accordance wit h th e “perf orm an c e t est ” gu id eli n es IEEE STD 45 0 . If th e BATTE R Y fai ls t o deli ver 70 % of its rated capa cit y it sh all b e deemed d efect ive a nd be rep lac ed. Eith er floa t or cyc lic servi ce wi ll be u sed to determine the w ar ranty cre dit ( as pe r p ublis hed Batter y D iagnosti c Doc umen t). T he ty pical c redi t appl ied w ill be as in the t able above.
No representative, salesperson, agent, distribu tor, or employee of TIC is auth orized to modify any of the terms of this warranty, unless modifications are made in writing and signed by an authorized TIC officer.
THIS WARRANTY REPRESENTS THE ENTIRE AGREEMENT BETWEEN TIC AND USER WITH RESPECT TO THE SUBJECT MATTER HEREIN AND SUPERSEDES ALL PRIOR OR CONTEMPORANEOUS ORAL OR WRITTEN COMMUNICATIONS, REPRESENTATIONS, UNDERSTANDINGS OR AGREEMENTS RELATING TO THIS SUBJECT.
PROCEDURE
, or phone 1-800-231-1412, no later than 90
MODIFICATIONS
End User:
Model Number:
Serial Number:
Startup Date: Warranty End Date:
Page 63
38
Page 64
13131 W. Little York Road • Houston, TX 77041 Tel: 713-466-0277 US: 800-231-1412
www.toshiba.com/ups
Loading...