Toro 220G Series, 220 Brass Valves User Manual

Introduction
Built on proven technologies and components, the Toro 220 Series brass valves are tough, have excellent performance and are extremely reliable. A self-flushing, clog-resistant, stainless-steel filter for dirty water conditions assures years of trouble-free performance.
In commercial installations, it is advantageous to install the valves in a valve box. This enables the valve to be located, accessed and maintained easily. The use of clean aggregate in the bottom of the box, and keeping valve box locations away from structures, potential hardscaping features (such as sidewalks) and large planting locations is recommended. Additionally, valve box locations generally should be in shrub beds and at right angles to structure locations. If the valves are installed below grade without a valve box, access to the top of the valve should be provided using a section of 4" PVC pipe and a Toro Valve Cover (Part No. 850-00) installed directly over each valve.
Specifications
Models:
220 Series electric - 1", 1
1
4", 11⁄2", 2", 21⁄2", 3”
220 Series hydraulic - 1", 1
1
2", 2"
Flow range: 1" - 540 GPM1
1
4" - 20—100 GPM
1
1
2" - 20—130 GPM
2" - 30180 GPM2
1
2" - 60—250 GPM
3" - 80350 GPM
Operating pressure:10220 psi maximumPressure-regulating models:
– Outlet: 5-30 psi, ±3 psi (EZR-30)
5-100 psi, ± 3 psi (EZR-100)
– Inlet: 15-220 psi
Minimum inlet/outlet pressure differential: 10 psi
Burst pressure safety rating: 750 psi
Body styles: Globe - 1", 1
1
4", 11⁄2", 2" female threads, NPT and BSP
Angle - 2
1
2", 3" female threads, NPT and BSP
Solenoid: 24 V a.c.Inrush: 0.40 amps, 11.50 VAHolding: 0.20 amps, 5.75 VA
Dimensions:1" 5
3
4" H x 5" W
1
1
4" — 61⁄2" H x 6" W
1
1
2" — 61⁄2" H x 6" W
2" — 7
1
2" H x 5" W
2
1
2" — 83⁄4" H x 81⁄2" W
3" — 8
3
4" H x 81⁄2" W
Ingot brass and stainless-steel construction
Removable, self-flushing, contamination-proof, 120-mesh,
stainless-steel filter screen (electric models)
Manual flow control: adjustable to zero flow
Bleed screw (electric models): bleeds internally downstream
Pressure-regulating models:Precise pressure control with compact EZReg dial designPressure regulates in electric and manual modes,
serviceable under pressure
Schrader-type valve for pressure gauge attachment
220 Series Brass Valve Installation and Operating Instructions
Table 2 — Voltage Requirement (standard solenoid)
Voltage Inlet Pressure
22.5 V a.c. 220 psi
21.1 V a.c. 200 psi
20.2 V a.c. 175 psi
19.1 V a.c. 150 psi
18.2 V a.c. 125 psi
17.1 V a.c. 100 psi
16.1 V a.c. 75 psi
16.0 V a.c. 50 psi
Note: For optimum performance, calculate total friction loss to ensure sufficient downstream pressure. Values shown in psi.
Table 1 Friction Loss Data
GPM Flow
Model 5 10 15 20 30 40 50 60 70 80 100 120 150 170 180 200 250 300 350
Electric
1" 2.0 2.5 1.5 2.5 5.5 7.0
11⁄4" 4.4 4.7 5.1 5.5 5.8 7.2
11⁄2" 3.9 4.2 4.6 4.9 5.2 5.5 7.2
2" 1.0 2.0 2.0 2.5 3.0 3.5 6.0 7.5 10.0 12.0 14.0
21⁄2" 2.0 2.2 2.3 2.4 2.5 3.0 4.0 4.5 5.5 7.0
3" 2.2 2.4 2.5 3.0 4.0 4.5 5.5 6.5 7.0 7.5
Hydraulic
1" <1 <1 1.5 2.5 5.5 7.0
11⁄4" 2.0 2.7 3.7 4.8 6.0 8.0
11⁄2" <1 1.5 2.5 3.0 4.5 5.0 8.0
2" <1 1.0 1.1 1.5 2.5 3.0 5.5 7.0 10.0 11.5 14.5
Installation Guidelines
Note the flow direction arrow in the side of the valve body and install accordingly.
The valve can be installed at any angle without affecting operation.
Electric valves only:
Use direct-burial irrigation control wire for connection from the controller to valves.
Leaving a wire expansion loop at each valve location on long-run wire lengths is recommended.
Waterproof wire splice connectors are absolutely essential for proper electric control system operation. Follow the
installation instructions provided with the connectors for optimum waterproof splice protection.
Hydraulic valves only:
Note:
The normally open hydraulic valve is particularly appropriate for dirty-water applications such as effluent water use. With these valves, the main-flow water supply is not utilized as a source for closing the valve. The pressure within the diaphragm chamber on a normally open valve is supplied separately through a filtered water source from the controller.
To enable proper valve operation, the filtered water supplied to the controller and valves must be obtained from the high­est source of pressure within the irrigation system. In other words, the water pressure in the control tubing from the con­troller to the valves must be greater than or equal to the main-flow water pressure on the inlet side of the valve
The recommended maximum control tubing run is 1000'. Exceeding this distance may cause erratic valve operation.
Prior to connecting the control tube to the valve fitting, the tube must be pre-filled and completely free of all debris and
trapped air. A flushing adapter (model 995-02) enables the tubing to be easily attached to a standard water hose end for this procedure.
Leaving an expansion loop at each valve location is recommended.
Hydraulic valve control tubing should be rated for a maximum continuous working pressure of 220 psi with
1
4" O.D. and 1⁄8"
I.D. Toro polyethylene control tubing and fittings are recommended for this type of installation. See Table 3 below.
Valve Operation and Adjustment
Flow Control
The flow control is used to reduce the flow and pressure to the valve outlet. By turning the control handle clockwise, the flow will gradually be reduced to zero.
For valve models
without EZReg, adjust the flow control as necessary for optimum sprinkler performance.
For valve models
with EZReg, the flow control should remain in the fully open position. Use only for emergency shut off.
Manual Bleed Knob (electric valves only)
The manual bleed knob is used to manually operate the valve. Turning the knob counterclockwise 2–3 turns allows water to bleed downstream from the diaphragm chamber, relieving pressure from the top of the diaphragm which allows the valve to open. Turning the bleed knob clockwise until finger tight, shuts off the discharge enabling pressure to build within the diaphragm chamber, causing the valve to close.
Pressure Regulation (electric valves with EZReg only) An accurate, adjustable dial coupled with a forward-flow valve design allows the 220 series valve with EZReg to regulate
downstream water pressure with precision. It can regulate accurately down to 5 GPM flow (1" model) and only requires 10 psi differential pressure to operate. The EZReg will operate during electrical and manual valve operation.
To adjust, remove the cover from the regulator dial. Turn the dial until the pointer is on the desired downstream pressure: 5–30 psi (EZR-30) or 5–100 psi (EZR-100).
Note: Due to the micro-adjustment feature of the EZReg, the dial requires several complete revolutions to move the pointer from the minimum to the maximum adjustment settings.
Operate the valve (electrically or manually). Check the flow control to confirm that it is in the fully open position. Adjust the regulator dial if necessary for optimum sprinkler operation.
To confirm the downstream pressure using a pressure gauge, remove the cap from the Schrader-type valve located directly below the EZReg. Attach a Toro pressure gauge (Model 995-51) to the Schrader-type valve for a direct reading. Adjust EZReg dial as necessary for the desired pressure.
Note: The valve will remain operational if removal of the EZReg assembly is required.
Table 3 1/4" Control Tubing and Accessories
(2000' Coil, 1⁄4" x 1⁄8" Hard Reel)
Model 900-11 - Blue on Black color code Model 900-12 - Yellow on Black color code Model 900-13 - Pink on Black color code Model 900-14 - White on Black color code
Model 900-21 - Adapter, compression to poly 1⁄4" to 1⁄4" Model 900-24 - Adapter, 1⁄8" Male NPT to 1⁄4" poly Model 900-30 - Metal Coupler, 1⁄4" to 1⁄4" Model 900-40 - Retainer, 1⁄4" Model 900-50 - Metal Tee 1⁄4" x 1⁄4" x 1⁄4" Model 900-70 - Tubing Plug, 1⁄4"
© 2003 The Toro Company, Irrigation Division An ISO 9000-certified Company Form Number 373-0027 Rev. B
Loading...