Toro 12, 36, 24, 48 User Manual

Intelli-Sense
User’s Guide
Professional Controllers
12-, 24-, 36-, and 48-Station Models
TIS-PRO
The Toro Company Technical Support
(877) 345-8676
WeatherTRAK
®
ET Everywhere Subscription & Technical Support
(800) 362-8774
Table of Contents
Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
Chapter 1 - Getting Started . . . . . . . . . . . . . . . . . 3
Controller Hardware Overview . . . . . . . . . . . . . . . . . . . . . . . . 4
Control Module Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Chapter 2 - Controller Setup. . . . . . . . . . . . . . . . . 9
Adjust Display Contrast . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Set Controller Date and Time . . . . . . . . . . . . . . . . . . . . . . . . . 10
Select Time Zone . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Select Auto Daylight Savings Option. . . . . . . . . . . . . . . . . . . . 11
Set Maximum Active Station Count. . . . . . . . . . . . . . . . . . . . . 12
Select Stack or Overlap Option . . . . . . . . . . . . . . . . . . . . . . . . 13
Select Master Valve/Pump Start Option . . . . . . . . . . . . . . . . . 14
Assign Pump Start Outpt. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Select Run Time Valve Test Option . . . . . . . . . . . . . . . . . . . . 15
Set Maximum Backup ET . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
Chapter 3 - Set Program Schedule . . . . . . . . . . . . . 17
Select Program . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
Set Program Start Times and Water Windows . . . . . . . . . . . . 18
Set High ET Start / Water Window . . . . . . . . . . . . . . . . . . . . . 19
Set Program Water Day Mode . . . . . . . . . . . . . . . . . . . . . . . . 20
Chapter 4 - Station Data Setup . . . . . . . . . . . . . . 23
Station Setup Mode: Automated by WeatherTRAK . . . . . . 24
Select Station . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
Select Station Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
Select Program . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
Select Water Window Option . . . . . . . . . . . . . . . . . . . . . . . . . 25
Select Usable Rainfall . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
Select Sprinkler Type . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
Set Precipitation Rate . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
Set Sprinkler Efficiency . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
iii
IV
Chapter 4 (continued)
Select Soil Type . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
Select Plant Type . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
Set Root Depth . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
Set Microclimate . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
Select Slope Factor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
Select Sprinkler Location. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
Completing Station Setup . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
Station Setup Modes: User Defined. . . . . . . . . . . . . . . . . . . 32
Select Station . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
Select Station Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
Select Program . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
Select Water Window Option . . . . . . . . . . . . . . . . . . . . . . . . . 33
Select Usable Rainfall . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34
Set Station Runtime. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34
Select Number of Cycles. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
Set Soak Time. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
Set Reference ET Value . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36
Set Reference Month . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36
Chapter 5 - Support Functions. . . . . . . . . . . . . . . . . 37
Using the Review Function. . . . . . . . . . . . . . . . . . . . . . . . . . 38
Review Station Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38
Review Flow Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39
Using the Copy Function . . . . . . . . . . . . . . . . . . . . . . . . . . . 40
Restoring Station Default Settings . . . . . . . . . . . . . . . . . . . . . 41
Restoring Program Settings . . . . . . . . . . . . . . . . . . . . . . . . . . 42
Restoring Setup Default Settings . . . . . . . . . . . . . . . . . . . . . . 43
Copy Station Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43
Using the % Adjust Function . . . . . . . . . . . . . . . . . . . . . . . . 44
% Adjust by Water Amount . . . . . . . . . . . . . . . . . . . . . . . . . . . 44
% Adjust by Day Frequency/ Max. Allowable Depletion . . . . . 45
Using the Alerts Function. . . . . . . . . . . . . . . . . . . . . . . . . . . 46
Using the Flow Monitor Function. . . . . . . . . . . . . . . . . . . . . 47
Set Station Exclusion . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 48
Edit Flow Sensor K Value and Offset . . . . . . . . . . . . . . . . . . . 49
Set Threshold and Delay Values. . . . . . . . . . . . . . . . . . . . . . . 50
Setting the High Flow Threshold . . . . . . . . . . . . . . . . . . . . . . . 50
Setting the No Flow Threshold . . . . . . . . . . . . . . . . . . . . . . . . 51
Setting the Leak Detection Threshold . . . . . . . . . . . . . . . . . . . 52
Using the Reports Function . . . . . . . . . . . . . . . . . . . . . . . . . 53
Weekly Stations Report. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 53
Monthly Station Report . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 53
Flow Report . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 54
Using the ET Function . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 57
Edit Custom Plant Kc Value . . . . . . . . . . . . . . . . . . . . . . . . . . 57
Edit Custom Turf Kc Value . . . . . . . . . . . . . . . . . . . . . . . . . . . 58
Set Weekly ET. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 58
Using the Help / ET Function . . . . . . . . . . . . . . . . . . . . . . . . 59
Rain Service . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 60
View Group Number . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 60
Days Since Last ET. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 60
Current Depletion . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 61
Run Valve Test . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 61
Using the Manual Watering Function . . . . . . . . . . . . . . . . . 62
Manually Operate Specific Stations . . . . . . . . . . . . . . . . . . . . 62
Manually Operate All Stations . . . . . . . . . . . . . . . . . . . . . . . . . 63
The Run Function . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 64
The Off Function . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 64
Using the Maintenance Timeout Function 55
Using the Rain Pause Function . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . .
55
Appendix A - Troubleshooting Guide . . . . . . . . . 65
Appendix B - Glossary of Terms . . . . . . . . . . . . 69
Appendix C - Installation Procedures. . . . . . . . . 71
Selecting the Installation Site . . . . . . . . . . . . . . . . . . . . . . . . . 71
Mounting the Controller . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 72
Connecting the Power Wires. . . . . . . . . . . . . . . . . . . . . . . . . . 73
Connecting an Earth Ground Source . . . . . . . . . . . . . . . . . . . 73
Connecting the Station Wires (includes Pump Relay). . . . . . . 74
Toro Rain Sensor Connection . . . . . . . . . . . . . . . . . . . . . . . . . 76
Flow Sensor Connection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 77
Toro TMR-1 Handheld Remote Connection . . . . . . . . . . . . . . 78
Fuse Replacement. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 79
Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 79
Warranty Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 81
FCC Compliance Information . . . . . . . . . . . . . . . . . . . . . . . . 82
vi
Notes:
Introduction
Congratulations on selectingToro, the proven leader in smart irrigation. Twenty public agency studies and thousands of customers make it clear— the Toro Intelli-Sense Commercial controllers with WeatherTRAK technology are #1 in saving water, protecting landscapes, reducing runoff, and satisfying
customers. The Toro Intelli-Sense Professional controller series, available in 12, 24, 36 and 48 station-count models, dynamically adjust irrigation based on current ET (evapotranspiration) conditions, received each day via radio transmission from the WeatherTRAK ET Everywhere®subscription service.
Some Key Features of the TIS-PRO Controllers
Reliable Toro-built irrigation controller.
WeatherTRAK’s exclusive irrigation scheduleing software.
The flexibility of 12, 24, 36 and 48 station-counts models
to meet a wide variety of irrigation system needs.
• Four independent irrigation programs
• Integrated flow management and reporting utilities with flow sensing and leak detection at station and system
• User alerts relating to flow, valves, communications, scheduling and more.
• Station-specific programming of watering days, run times, start times and cycle/soak periods.
• Automatic syringe irrigation for high ET-rate conditions.
• Toro Handheld Remote and Rain/Freeze Sensor ready.
• Large, easy-to-read liquid crystal display.
• Built-in surge protection.
• Non-volatile memory.
• Weather and vandal-resistant heavy-gauge steel cabinet.
• Weather-proof external antenna.
level.
How the ET Everywhere Service Works
2 - Proven scientific modeling techniques are then used to
calculate and validate specific ET data down to one square kilometer.
3 - The ET data is uploaded to a communications satellite
where it received nightly by the intelli-Sense controller to automatically recalculate station-specific irrigation parameters for the next scheduled watering day.
32
1
1 - The WeatherTRAK ET Everywhere service collects data
from over 25,000 monitoring stations including the National Oceanic and Atmospheric Administration (NOAA) network, state and county networks, and private weather stations.
Important: The ET Everywhere subsciption service is
!
not included with the purchase of the Intelli-Sense controller. For service subscription information, contact WeatherTRAK customer service at 1-800-362-8774 during normal business hours.
The following checklist provides the basic steps required for Intelli-Sense Professional Controller installation, setup, programming and operation.
Install per the provided intallation instructions. (See Installation Instructions beginning on page 69).
Fill out the Intelli-Sense Control System Profile spreadsheet with as much accurate detail as possible. Have the spreadsheet on hand when performing the controller setup and programming procedures.
Program the controller. This manual provides step-by-step instructions for programming the controller based on the infor­mation captured on the System Profile spreadsheet.
Chapter 1
Getting Started
Thoroughly inspect the irrigation system for proper design, installation and operating condition, leaks, as well as broken heads and pipes. The performance of your new controller depends on the integrity of the irrigation system design and installation. You will maximize the performance of your controller when the irrigation system is well maintained.
Activate the WeatherTrak ET Everywhere subscription service. This necessary and important step enables the Intelli-Sense to receive daily ET updates.
Controller Hardware Overview
2
TIS-PRO
1
5
3
1 - Intelli-Sense Control Module - (See page 6 for details.)
2 - Enclosure - Weather- and vandel- resistant heavy-gauge
steel cabinet with locking cover.
3 - Weatherproof External Anatenna - Provides exceptional
reception in most locations.
4 - Hinged Access Panel Fasteners - Thumbscrew fasteners
secure hinged control panel for ease of access without
5 - Rain Sensor Control Switch - Slide switch provides
manual override control of auxiliary rain sensor.
4
tools.
8
7
VC/
VC/
25 26 27 28 29 30 31 32 33 34 35 36
25 26 27 28 29 30 31 32 33 34 35 36
MV/
1 2 3 4 5 6 7 8 9 10 11 12
PUMP
MV/
6
1 2 3 4 5 6 7 8 9 10 11 12
PUMP
37 38 39 40 41 42 43 44 45 46 47 48
COM
COM
VC/
VC/
37 38 39 40 41 42 43 44 45 46 47 48
COM
COM
VC/
VC/
13 14 15 16 17 18 19 20 21 22 23 24
COM
COM
VC/
VC/
13 14 15 16 17 18 19 20 21 22 23 24
COM
COM
9
10
11
13
6 - Control Module Latch - Enables control module
12
to be
easily removed without disturbing controller installation.
7 - Fuse - 2A Slo-Blo fuse provides short-circuit protection
on the 24 VAC output circuit.
8
- Flow and Rain Sensor Connection Terminal Block
Quick release wire terminals for easy, secure connections.
9
- TMR-1 Handheld Remote Connections - Provides
RJ-11 plug receptacle and 24 VAC power source for TMR-1 handheld remote reciever connection.
- Valve Wire Connection Terminal Blocks - Screwless,
10
quick release control wire terminals for easy installation.
11 - Earth-ground Lug -
Heavy-duty ground lug accepts
10 AWG solid-copper wire from earth ground device.
12 - Hot Post - Provides a constant 24 VAC power sou
rce to assist in valve identification for initial installation, system service and troublshooting procedures.
13 - Main Power Connection Terminal Block - Screw
terminals for 120 VAC input power wires.
Control Module Overview
17a
16a
18
14
15
17
16
14 - Function dia l - Turn this dial in either direction to select
controller setup and operational functions:
RUN - The normal position for automatic operation.
Current time/date and controller activity is displayed.
1
SETUP - Select and define specific controller setup
and operating parameters.
SCHEDULE - Set up and adjust start times/water
windows and watering day schedules.
STATION DATA - Select and define specific station
setup and operating parameters.
REVIEW - Review current program information
for each station, and flow sensor setup and data log.
COPY - Transfer station or program information from one station or program to another. Also used
to
reset station, setup and program default settings.
o
ADJUST - Adjust station watering by 5% increase or
decrease of run time and/or watering days.
ALERTS - Display system problems and
operationalconflicts.
FLOW - Set flow meter attributes and operational
partameters.
REPORTS - Access and review station run time
flow data by day, week or month time periods.
and RAIN PAUSE - Suspend automatic watering for a
period of 1 to 14 days.
ET - Display current daily and average weekly ET values. Set custom Kc and weekly ET values.
Access various controller activation
HELP/INFO ­ setup data, operational preferences, and status information.
OFF - Terminate and suspend all watering activity.
MANUAL - Access manual watering operations.
15 -
Copy button – The Copy button is used in various
operations including copying and transferring station and program data, restoring default settings and reviewing various setup, station, and flow data.
16 - Lower Line knob - This knob is used to select and/or
adjust data viewed on the lower line of the display
(16a).
17 - Upper Line knob - This knob is used to select setup and
program control options shown on the upper line of the display (17a ).
18 - Information Line - The third line of the display provides
supplemental information including the Alert prompt.
Notes
Chapter 2
Controller Setup
The SETUP function menu consists of 10 screens listed in the following order:
Adjust Display Contrast
Set Controller Clock
• Set Time Zone
• Set Auto Daylight Savings option
• Set Maximum Active Stations
• Select Stack or Overlap option
• Set Master Valve Type/Pump Start option
• Select Runtime Valve Test
• Set Maximum Backup ET
About Controller Input
As you begin the controller setup procedures, you will find that virtually all user-defined input is accomplished in the same manner using the Function dial, Upper Line knob, and Lower Line knob. For example, when you turn the Function dial to the SETUP position, the first screen in the Setup menu will be displayed. In this case, Adjust Display Contrast will be displayed on the upper line and the default contrast value of 224 will be displayed on the lower line.
ADJUST DISPLAY CONTRAST
224
The contrast value is underscorred and flashing, indicating that it is selected and can be changed or edited by turning the Lower
Line knob. The information displayed on the screen when the Upper Line knob or Function dial is turned in either direction,
enters the information into the controller memory.
Set Controller Clock
1. With the Function dial in the SETUP position, turn the Upper Line knob to select the following display:
DATE (YEAR) Feb 24 2008
2. Turn the Lower Line knob to set the current year.
3. Turn the Upper Line knob right to select the next menu item,
Date (Month).
DATE (MONTH) Feb 24 2008
4. Turn the Lower Line knob to set the current month.
5. Turn the Upper Line knob right to select
6. Turn the Lower Line knob to set the current day.
7. Turn the Upper Line knob right to select
8. Turn the Lower Line knob to set the current hour (am or pm).
9. Turn the Upper Line knob right to select
10. Turn the Lower Line knob to set the current minute.
Note: Leave the Function dial in the SETUP position to continue selecting and setting the remaining Setup menu items.
10
Date (Day).
Time (Hour).
Time (Minute).
Set Time Zone
1. Within the Setup menu, turn the Upper Line knob to view the following display:
TIME ZONE Pacific
2. Turn the Lower Line knob to select your time zone from the following choices:
Pacific (default setting)
Alaska
Hawaii
Atlantic
Eastern
Central
Mountain
Select Auto Daylight Savings Option
1. W
ithin the Setup menu , turn the Upper Line knob to view the
following display:
AUTO DAYLIGHT SAVINGS Yes
2.
The default selection is Yes which enables the controller to automatically compensate for Daylight Savings time. To disable
this option, turn the Lower Line knob to display No.
11
1.
2.
Within the Setup menu, turn the Upper Line knob to view the following display:
Note: The active station count entered in this step will also determine the number of stations that can be accessed within the Programming , Review and Copy function procedures.
MAX ACTIVE STATIONS 01 (User Defined)
Set Maximum Active Station Count
The actual number of stations being used for irrigation must be entered to enable accurate automatic scheduleing.
12
To change the number of active stations, turn the Lower Line knob.
STA CONFIG FOUND ACIVE
36 36 36
Note: To review the current station configuration, press the Copy button when SETUP function is selected.
Important: The Intelli-Sense Professional controller firmware
!
provides for the scheduling of 48 stations regardless of controller output configuration. If the actual number of active stations is not set accurately and/or set according to controller output configura­tion, alert errors and reuced controller performace will result. For example, setting the active station count higher than actual will result in an alert error or will add unnecessary time to the Water Window. Setting the station count lower than actual will cause some stations to be skipped.
Note: The abbreviated display information indicates the following:
STA CONFIG = Controller model configuration of 36 or 48 stations FOUND = Actual number of stations recognized by controller ACTIVE = Maximum active station count selected.
1. Within the Setup menu, turn the Upper Line knob to view the following display:
STACK OR OVERLAP Stack
Select Stack or Overlap Option
When the Stacking option is selected, the controller will be constrained to operate one station at a time. The Water Window
start time and duration selected for Automatic Schedule A will
also be assigned to Automatic Schedule B, C and D.
When the Overlap option is selected, the constraint is removed, allowing multiple programs to run simultaneously. When Overlap is selected, Start time and Water Window options are available in all schedules.
!
Important: Prior to selecting the Overlap option, confirm that the irrigation system hydraulic capacity and the controller’s maximum current draw capacity (2.0A) will not be exceeded if four stations and master valve circuit are operated concurrently.
!
Important: When the STACK option is selected within the Setup menu, the start time and water window parameters defined for Program A will apply to all progams, and can not be edited by individual program.
If the OVERLAP option is selected, separate start time and water window parameters can be defined for each program.
The Stack option is seleted by default. To select theOverlap option,
2. turn the Lower Line knob to display Overlap.
13
1. Within the Setup menu, turn the Upper Line knob to view the following display:
2. Turn the Lower Line knob to select the preferred option.
Note: If a pump station is in use but no master valve is required, use the Normally Closed/Pump On option.
MASTER VALVE/PUMP START Normally Closed/Pump On
ASSIGN PUMP START OUTPUT NOT ASSIGNED
Set Master Valve/Pump Start Option
The controller features a dedicated master valve/pump start output as a standard feature. The master valve is used to isolate the mainline or a portion of the mainline when programmed as part of flow monitoring. It enables the controller to troubleshoot and isolate pipe malfunctions or other problems. Three choices provided are:
• Normally Closed/Pump On (default)
• Normally Open/Pump Off
• None
Assign Pump Start Output
The controller allows the user to assign a pump start to a station output, effectively decreasing the controller station count by 1. The assigned station will be active with all stations. This feature is typically used in combination with a normally-open (NO) type master valve to enable the pump to operate while the NO master valve remains de-engerized (open).
1. Within the setup Menu, turn the Upper Line knob to view the following display:
2. Turn the Lower Line knob to select the station number to be desig­nated as the pump start output.
14
Set Maximum Backup ET
1. Within the Setup menu, turn the Upper Line knob to view the following display:
Turn the Lower Line knob to adjust the decimal number value.
MAX BACKUP ET Part 1
2.00
The Maximum Backup ET value is a failsafe measure used by the controller to calculate daily watering requirments in the event that current ET Everywhere data is not recieved for an extended period.
2.
The Maximum Backup ET default value of 2.00 is automatically entered to help compensate for seasonal weather changes.
The whole number of the Maximum Backup ET value is selected
by default. To adjust the value from 1 – 3, turn the Lower Line knob.
Note: The Maximum Backup ET is adjustable from 0.50 – 3.99. The whole number is only adjustable to 0 when the decimal number value is .50 or higher.
4.
Turn the Upper Line knob right one stop to select the decimal number.
3.
Set Runtime Valve Test Option
The controller features a Valve Test feature that will test each station for a short-circuit condition each time it is activated. If a fault is detected, an Alert will be posted, enabling identification and repairs to be made.
1. Within the Setup menu, turn the Upper Line knob to view the following display:
RUNTIME VALVE TEST No (Check Fuse Often)
2. Turn the Lower Line knob to select Yes or No as preferred.
15
Notes
16
Chapter 3
Set Program Schedule
1. Turn the Function dial SCHEDULE to view the following display:
Program A is selected by default. The current watering day schedule, start time and water window information is shown for Program A.
SELECT PROGRAM A (Optm S12:00am W16:00)
The Intelli-Sense Professional Controller enables four independent program schedules (A, B, C and D) to be defined by one or two start times with associated water window and a specific watering day schedule. Each station is then assigned to one of the programs in the Station Data function.
Important: When the STACK option is selected within the
!
Setup menu, the start time and water window parameters defined for Program A will apply to all progams, and can not be edited by individual program.
If the OVERLAP option is selected, separate start time and water window parameters can be defined for each program.
Select Program
Note: The abbreviated display information indicates the following: Optm = Watering day schedule is Optimized by WeatherTRAK S12:00am = Start Time is 12:00 a.m. W16:00 = Water window duration is 16 hours.
2. To change the program selection, turn the Lower Line knob to select program B, C or D.
17
Set Program Start Start Time and Water Window
1. Within the Schedule menu, turn the Upper Line knob to select the following display:
SET STARTS/WINDOWS PRG A Skip (Button to View)
Note: To review the current start time/water window settings, press the Copy button. The abbreviated information will be displayed as shown in the example below.
START 1 S12:00am W16:00 Off
Start 1 = 12:00 a.m., water window is 16 hours in duration, and Start Time 2 is turned off.
2. Skip is selected by default. To edit the selected program, turn the Lower Line knob to select Edit.
SET STARTS/WINDOWS PRG A Edit (Button to View)
3. Turn the Upper Line knob to select the following display:
1st Start/Window PRG A Start 12:00am Win 16:00 (Button to View)
4. The start time hour is underlined and flashing, indicating that it
can be edited. Turn the Lower Line knob to set the start time hour, or turn the Upper Line knob right to select next element of the screen to be edited.
18
Repeat the editing procedure used to enter the 1st start time andwater window.
8.
(Button to View)
5. Turn the Upper Line knob right to select water window duration.
1st Start/Window PRG A Start 12:00am Win 16:00
(Button to View)
2nd Start/Window PRG A Start 07:00pm Win 05:00
Note: Water window is the duration of time allotted for all stations, assigned to the program to complete their programmed watering cycle(s). The water window duration is adjustable from 1 hour to 23 hours and 59 minutes. The controller provides the water window end time by factoring the selected start time and duration.
6. Turn the Lower Line knob to adjust number of hours, or turn the Upper Line knob right to select minutes and edit as preferred.
Note: A second program start time/water window is provided for automatic syringe watering where compensation for higher than normal ET is desired. Labeled High ET start, the controller automatically reduces the total station watering amount during this syringe operation to 25% of normal.
To prevent operational conflicts due to overlapping watering cycles, the following setup criteria must be considered:
• The 2nd start time cannot occur within the 1st start time cycle
• The combined water window duration cannot exceed 23 hours and 59 minutes.
If an Overlap condition alert is posted, the source of the conflict must be resolved. If not corrected, the 2nd start time will default to the Off mode. Press the Copy button to compare settings. Also refer to the Alerts function on page 44 for additional information.
7. Turn the Upper Line knob right to select the 2nd Start Type screen. The High ET start time option is Off by defualt. To program, turn the Upper Line knob right to display the following setup screen.
19
Set Program Water Day Mode
Each program can be assigned to unique water day schedule using one of the following options:
• Optimized by WeatherTRAK - Water day schedule selected automatically by the Intelli-Sense scheduling engine.
• Odd/Even - Odd or Even numbered calendar days.
• Interval - Water days set by frequency ranging from 1 to 30 days.
• Days of Week - Specific days of the week (same all months)
• Days of Week by Month - Specific days of the week for each month.
• Off - Turn program off.
1. With the Function dial in the SCHEDULE position, turn the Upper Line dial to view the following display:
WATER DAY MODE PRG A
Optimized by WeatherTRAK
2. Optimized by WeatherTRAK is selected by default. To use this mode, continue at step 3. To use an alternate mode, continue at the appropriate following section.
3. Turn the that enables a weekday to be excluded from operation.
4. Turn the Lower Line
Odd/Even
1. Turn the Lower Line knob to select Odd/Even.
Upper Line knob to select the Day Exclusion feature
knob to display the day name or None.
WATER DAY MODE PRG A
Odd/Even
2. Turn the Upper Line knob to display Odd.
3. Turn the Lower Line
20
knob to select Even.
Interval
1. Turn the Lower Line knob to select Interval.
WATER DAY INTERVAL PGM A
01 (Everyday)
2. The default Interval is 01 which schedules every day as active. To select an Interval from 0230, turn the Lower Line knob.
:etoN The current day is the first active day of the Interval schedule. For example, if today is Saturday and a 02 interval (water every-other-day) is set, today will be active. The next active watering day will be Monday.
Days of Week
1. Turn the Lower Line knob to select Days of Week.
WATER DAY MODE PGM A
Days of Week
2.3.Turn the Upper Line knob to view the following display:
OK TO WATER ON PGM A
S M T W T F S
By default, every day is an active watering day. To remove days from the schedule, turn the Upper Line knob to select the day indicator, then turn the Lower Line knob to replace the indicator with a dash (as shown in the following example).
OK TO WATER ON PGM A
S M - W T - S
21
Loading...
+ 61 hidden pages