Tork 7100, 7102, 7120, 7122, 7202L Installation And Operating Instructions Manual

...
TORK MODEL 7100
24 HR. TIME SWITCH
WITH SKIP-A-DAY
SWITCH: SPST CONTACT RATINGS:
40 AMP 120-277VAC 20 AMP INDUCTIVE
120-277VAC SINGLE PHASE 40 AMP TUNGSTEN 120VAC 1000VA (120-277) PILOT DUTY 2HP 120VAC; 5HP 240VAC
TIMING MOTOR: 120VAC 60Hz POWER CONSUMPTION: 3 WATTS MAX.
INSTALLATION AND OPERATING INSTRUCTIONS
TO SET ON AND OFF TIMES:
Light trippers turn ON. Dark tr ippers tur n OFF. Place tripper on dial edge as shown in figure and set point of each tripper to desired operating time. CAUTION: Note if selected time is AM or PM. Hold tripper against dial edge and firmly tighten knurled screw.
Disconnect power at main panel prior to installing or servicing this time switch or the equipment connected to it.
Connect in accordance with national and local electrical codes. Supply Connections: Use gauge specified (AWG # 8-14) suitable for
75 degrees C (167 degrees F)
TORK
®
1 GROVE STREET, MT. VERNON, NY 10550 TEL: 914-664-3542
FAX: 914-664-5052
LI-565(A)
▲▲
L
1X
2
LOAD
M
H
N
TO SET DIAL TO TIME: Turn dial counter-clockwise until correct time is indicated by arrow on nameplate . FOR MANUAL OPERATIONS: Press down lever on right of nameplate to turn ON. Press down lever
on left of nameplate to turn OFF. TO OMIT ON OPERATION: 7 spoke wheel at lower left of 24 hour dial moves ahead once each day,
about 5 hours before the first ON tripper is set to operate. Insert brass knurled screws in appropriate spokes on days when ON operations are to be omitted.
TO SET OMITTING WHEEL TO CORRECT DAY: Hold down OFF lever on left of name­plate. The red stud on this lever is the day-indicator. If the ON tripper has already passed the omitting wheel, turn omitting wheel clockwise until the present day of the week is indi­cated. If ON tripper has not passed omitting wheel, set omitting wheel so preceding day is indicated (24 hour dial turns counter-clockwise).
TO REMOVE MECHANISM FROM CASE: Press lever near case latch to release mainplate and swing the movement out. To replace, inser t mainplate projections in slots opposite latch and swing movement in until it latches.
OFF TIME
(Dark Tripper)
MANUAL
OFF
LEVER
Dial Calibrations
Knurled Screw
O F
TORK
F
ON TIME
(Light Tripper)
TIME
MANUAL
O N
LEVER
ACTUATOR
ON
GREEN
RED
STUD
TORK MODEL 7102
24 HR. TIME SWITCH
WITH SKIP-A-DAY
SWITCH: SPST CONTACT RATINGS:
40 AMP 120-277VAC 40 AMP TUNGSTEN 120VAC
20 AMP INDUCTIVE 1000VA (120-277) PILOT DUTY
120-277VAC SINGLE PHASE 2HP 120VAC; 5HP 240VAC
TIMING MOTOR:
208-277VAC 60Hz
POWER CONSUMPTION:
3 WATTS MAX.
INSTALLATION AND OPERATING INSTRUCTIONS
TO SET ON AND OFF TIMES:
Light trippers turn ON. Dark tr ippers tur n OFF. Place tripper on dial edge as shown in figure and set point of each tripper to desired operating time. CAUTION: Note if selected time is AM or PM. Hold tripper against dial edge and firmly tighten knurled screw.
TO SET DIAL TO TIME: Turn dial counter-clockwise until correct time is indicated by arrow on name­plate.
FOR MANUAL OPERATIONS: Press down lever on right of nameplate to turn ON. Press down lever on left of nameplate to turn OFF.
TO OMIT ON OPERATION: 7 spoke wheel at lower left of 24 hour dial moves ahead once each day, about 5 hours before the first ON tripper is set to operate. Insert brass knurled screws in appropriate spokes on days when ON operations are to be omitted.
TO SET OMITTING WHEEL TO CORRECT DAY: Hold down OFF lever on left of nameplate. The red stud on this lever is the day-indicator. If the ON tripper has already passed the omitting wheel, turn omitting wheel clockwise until the present day of the week is indicated. If ON tripper has not passed omitting wheel, set omit­ting wheel so preceding day is indicated (24 hour dial turns counter-clockwise).
TO REMOVE MECHANISM FROM CASE: Press lever near case latch to release mainplate and swing the movement out. To replace, inser t main-plate projections in slots opposite latch and swing movement in until it latches.
Disconnect power at main panel prior to installing or servicing this time switch or the equipment connected to it.
Connect in accordance with national and local electrical codes. Supply Connections: Use gauge specified (AWG # 8-14) suitable for
75 degrees C (167 degrees F)
TORK
®
1 GROVE STREET, MT. VERNON, NY 10550 TEL: 914-664-3542
FAX: 914-664-5052
LI-589(A)
M
▲▲
L
1X
2
H
LOAD
N
OFF TIME
(Dark Tripper)
MANUAL
OFF
LEVER
Dial Calibrations
Knurled Screw
O F
TORK
F
(Light Tripper)
TIME
MANUAL
O N
ON TIME
ON
LEVER
GREEN
RED
STUD
ACTUATOR
TORK MODEL 7120
24 HR. TIME SWITCH
WITH SKIP-A-DAY
SWITCH: SPDT CONTACT RATINGS:
40 AMP 120-277VAC 40 AMP TUNGSTEN 120VAC 20 AMP INDUCTIVE
120-277VAC SINGLE PHASE 1000VA (120-277) PILOT DUTY 2HP 120VAC; 5HP 240VAC
TIMING MOTOR: 120VAC 60Hz POWER CONSUMPTION:
3 WATTS MAX.
INSTALLATION AND OPERATING INSTRUCTIONS
TO SET ON AND OFF TIMES:
Light trippers turn ON. Dark tr ippers tur n OFF. Place tripper on dial edge as shown in figure and set point of each tripper to desired operating time. CAUTION: Note if selected time is AM or PM. Hold tripper against dial edge and firmly tighten knurled screw.
TO SET DIAL TO TIME: Turn dial counter-clockwise until correct time is indicated by arrow on name­plate.
FOR MANUAL OPERATIONS: Press down lever on right of nameplate to turn ON. Press down lever on left of nameplate to turn OFF.
TO OMIT ON OPERATION: 7 spoke wheel at lower left of 24 hour dial moves ahead once each day, about 5 hours before the first ON tripper is set to operate. Insert brass knurled screws in appropriate spokes on days when ON operations are to be omitted.
TO SET OMITTING WHEEL TO CORRECT DAY: Hold down OFF lever on left of nameplate. The red stud on this lever is the day-indicator. If the ON tripper has already passed the omitting wheel, turn omitting wheel clockwise until the present day of the week is indicated. If ON tripper has not passed omitting wheel, set omit­ting wheel so preceding day is indicated (24 hour dial turns counter-clockwise).
TO REMOVE MECHANISM FROM CASE: Press lever near case latch to release mainplate and swing the movement out. To replace, inser t main-plate projections in slots opposite latch and swing movement in until it latches.
Disconnect power at main panel prior to installing or servicing this time switch or the equipment connected to it.
Connect in accordance with national and local electrical codes. Supply Connections: Use gauge specified (AWG # 8-14) suitable for
75 degrees C (167 degrees F)
TORK
®
1 GROVE STREET, MT. VERNON, NY 10550 TEL: 914-664-3542
FAX: 914-664-5052
LI-594(A)
H
N
M
▲ ▼
L 1 X 2
LOAD
A
LOAD
B
H
N
OFF TIME
(Dark Tripper)
MANUAL
OFF
LEVER
Dial Calibrations
Knurled Screw
O F
TORK
F
ON TIME
(Light Tripper)
TIME
MANUAL
O N
LEVER
ACTUATOR
ON
GREEN
RED
STUD
TORK MODEL 7122
24 HR. TIME SWITCH
WITH SKIP-A-DAY
SWITCH: SPDT CONTACT RATINGS:
40 AMP 120-277VAC 20 AMP INDUCTIVE
120-277VAC SINGLE PHASE 40 AMP TUNGSTEN 120VAC 1000VA (120-277) PILOT DUTY 2HP 120VAC; 5HP 240VAC
TIMING MOTOR:
208-277VAC 60Hz
POWER CONSUMPTION:
3 WATTS MAX.
INSTALLATION AND OPERATING INSTRUCTIONS
TO SET ON AND OFF TIMES:
Light trippers turn ON. Dark tr ippers tur n OFF. Place tripper on dial edge as shown in figure and set point of each tripper to desired operating time. CAUTION: Note if selected time is AM or PM. Hold tripper against dial edge and firmly tighten knurled screw.
TO SET DIAL TO TIME: Turn dial counter-clockwise until correct time is indicated by arrow on name­plate.
FOR MANUAL OPERATIONS: Press down lever on right of nameplate to turn ON. Press down lever on left of nameplate to turn OFF.
TO OMIT ON OPERATION: 7 spoke wheel at lower left of 24 hour dial moves ahead once each day, about 5 hours before the first ON tripper is set to operate. Insert brass knurled screws in appropriate spokes on days when ON operations are to be omitted.
TO SET OMITTING WHEEL TO CORRECT DAY: Hold down OFF lever on left of nameplate. The red stud on this lever is the day-indicator. If the ON tripper has already passed the omitting wheel, turn omitting wheel clockwise until the present day of the week is indicated. If ON tripper has not passed omitting wheel, set omit­ting wheel so preceding day is indicated (24 hour dial turns counter-clockwise).
TO REMOVE MECHANISM FROM CASE: Press lever near case latch to release mainplate and swing the movement out. To replace, inser t main-plate projections in slots opposite latch and swing movement in until it latches.
Disconnect power at main panel prior to installing or servicing this time switch or the equipment connected to it.
Connect in accordance with national and local electrical codes. Supply Connections: Use gauge specified (AWG # 8-14) suitable for
75 degrees C (167 degrees F)
TORK
®
1 GROVE STREET, MT. VERNON, NY 10550 TEL: 914-664-3542
FAX: 914-664-5052
LI-595(A)
Typical for 240VAC supply.
M
L1 X2
H
H
LOAD
A
LOAD
B
H
H
OFF TIME
(Dark Tripper)
MANUAL
OFF
LEVER
Dial Calibrations
Knurled Screw
O F
TORK
F
ON TIME
(Light Tripper)
TIME
MANUAL
O N
LEVER
ON
GREEN
RED
STUD
ACTUATOR