Toptech TT-N-721 True Comfort III, T721 True Comfort III Installation Manual

INSTALLATION MANUAL
This manual covers TopTech models:
TT-N-721 and T721
Thermostat Applications Guide
noitpircseD
Gas or Oil Heat
Electric Furnace
Heat Pump (No Aux. or Emergency Heat)
Heat Pump (with Aux. or Emergency Heat)
Multi-stage Systems
Heat Only Systems
Heat Only Systems - Floor or Wall Furnaces
Cool Only Systems
Millivolt
Table of Contents
Installation Tips Thermostat Quick Reference Subbase Installation Wiring Technician Setup Technician Setup Menu Mounting and Battery Installation Set Time Specifications and Contact
No
No
Yes
Yes
No
No
No
No
No
Page
2 3 4 5 6 7 8 9
10
Power Type
Battery Power Hardwire (Common Wire) Hardwire (Common Wire) with Battery Backup
A trained, experienced technician must install this product.
Carefully read these instructions. You could damage this product or cause a hazardous condition if you fail to follow these instructions.
Need Help?
Una versión española de este manual puede ser descargada en www.pro1iaq.com
® U.S. Registered Trademark. Patents pending. Copyright © 2006 Pro1 IAQ, Inc. All rights reserved.
Rev. 0850
1
Wall locations
The thermostat should be installed approximately 4 to 5 feet above the floor. Select an area with average temperature and good air circulation.
INSTALLATION TIPS
NO NO YES
NO
Do not install thermostat in locations:
• Close to hot or cold air ducts
• That are in direct sunlight
• With an outside wall behind the thermostat
• In areas that do not require conditioning
• Where there are dead spots or drafts (in corners or behind doors)
• Where there might be concealed chimneys or pipes
PRO1 Tip
Pick an installation location that is easy for the user to access. The temperature of the location should be representative of the building.
2
Getting to know your thermostat
2
1
7
Displays the user selectable setpoint
LCD
1
Days of the week and time
6
Button options
temperature.
System operation indicators: The COOL, HEAT or FA N icon will display when the COOL, HEAT or FAN is on.
NOTE: The compressor delay feature is active if these icons are flashing. The compressor will not turn on until the 5 minute delay has elapsed.
3 4
2
Glow in the Dark Light Button
Fan Switch
3
System Switch
4
Easy Change Battery Door
5
Setpoint Buttons
6
User Buttons
7
Low Battery Indicator:
5
Indicates the current room temperature.
+1 will appear in the display when the auxiliary heat is active.
Replace batteries when indicator is shown.
Important:
The low battery indicator is displayed when the AA battery power is low. If the user fails to replace the battery within 21 days, the thermostat display will only show the low battery indicator as a final warning before the thermostat becomes inoperable.
3
SUBBASE INSTALLATION
Caution: Electrical Hazard
Failure to disconnect the power before beginning to install this product can cause electrical shock or equipment damage.
For vertical mount put one screw top and one screw bottom.
For horizontal mount put one screw left and one screw right.
Mercury Notice:
All of Pro1’s products are mercury free. However, if the product you are replacing contains mercury, dispose of it properly. Your local waste management authority can give you instructions on recycling and proper disposal.
Vertical mount
Horizontal mount
O
W2
UP
C
B
E
R
Horizontal mount
G Y
Vertical mount
4
WIRING
Caution: Electrical Hazard
Failure to disconnect the power before beginning to install this product can cause electrical shock or equipment damage.
Wiring
1.
If you are replacing a thermostat, make note of the terminal connections on the thermostat that is being replaced. In some cases the wiring connections will not be color coded. For example, the green wire may not be connected to the G terminal.
2.
Loosen the terminal block screws. Insert wires then retighten terminal block screws.
3.
Place nonflammable insulation into wall opening to prevent drafts.
Warning:
All components of the control system and the thermostat installation must conform to Class II circuits per the NEC Code.
Note:
application. Always consult the original equipment manufacturer for proper installation instructions.
This cross reference represents typical systems and is not necessarily representative of your particular
5
Terminal Designations
TECHNICIAN SETUP
Auxiliary heat relay - Stage 2
W2
Compressor relay - Stage 1
Y
Fan relay
G
Heat pump changeover valve
O
energized in cooling
Transformer power
R
Common wire from
C
system transformer
Heat pump changeover valve
B
energized in heating
Emergency heat relay
E
Note:
In many systems with no emergency heat relay a jumper can be installed between E and W2.
Fahrenheit/Celsius Display
Select F or C with the jumper pin on the back of the thermostat. F is for Fahrenheit and C is for Celsius.
12 or 24 Hour Time
Reset button
12 or 24 hour (military time) can be selected with the jumper pin.
Important:
The RESET button must be pressed after changing any switch or jumper pin setting. Batteries must be installed for this operation.
Select F or C with the jumper pin
12 or 24 hour jumper pin
6
Technician Setup Menu
This thermostat has a technician setup menu for easy installer configuration. To setup the thermostat for your particular application:
Press MENU button
1.
Press and hold TECH SET button for 3
2.
seconds. This 3 second delay is designed so that homeowners do not accidentally access the installer settings.
Tech Setup Steps
TECHNICIAN SETUP MENU
3.
Configure the installer options as desired using the table below.
Use the or keys to change settings and the NEXT STEP or PREV STEP key to move from one option to another. Note: Only press DONE key when you want to exit the Technician Setup options.
Filter
Change
Reminder
This feature will flash “FILT” in the display after the elapsed run time to remind the user to change the filter. A setting of “off” will disable this feature.
LCD Will Show
Adjustment Options
You can adjust the filter change reminder from “off” to 2000 hours of runtime in 50 hour increments.
Factory Default Settings
Off 0 ºF Off On 0.8 ºF 0.8 ºF Off
Room
Temperature
Calibration
This feature allows the installer to change the calibration of the room temperature display. For example, if the thermostat reads 70° and you would like it to read 72° then select +2.
You can adjust the room temperature display to ready -4°F to +4°F above or below the factory calibrated reading.
Minimum
Compressor
On Time
This feature allows the installer to select the minimum run time for the compressor. For example, a setting of 4 will force the compressor to run for at least 4 minutes every time the compressor turns on, regardless of the room temperature.
You can select the minimum compressor run time from “off”, “3”, “4”, or “5” minutes. If 3, 4, or 5 is selected, the compressor will run for at least the selected time before turning off.
Compressor
Short Cycle
Delay
The compressor short cycle delay protects the compressor from “short cycling”. This feature will not allow the compressor to be turned on for 5 minutes after it was last turned off.
Selecting “ON” will not allow the compressor to be turned on for 5 minutes after the last time the compressor was on. Select “off” to remove this delay.
Cooling
Swing
The swing setting, often called “cycle rate”, “differential” or “anticipation” is adjustable. A smaller swing setting will cause more frequent cycles and a larger swing setting will cause fewer cycles.
The cooling swing setting is adjustable from ±0.4°F to ±2°F. For example: A swing setting of
0.5°F will turn the cooling on at approximately 0.5°F above the setpoint and turn the cooling off at approximately
0.5°F below the setpoint.
Heating
Swing
The swing setting, often called “cycle rate”, “differential” or “anticipation” is adjustable. A smaller swing setting will cause more frequent cycles and a larger swing setting will cause fewer cycles.
The heating swing setting is adjustable from ±0.4°F to ±2°F. For example: A swing setting of
0.5°F will turn the heating on at approximately 0.5°F below the setpoint and turn the heating off at approximately
0.5°F above the setpoint.
for Heat Pump
Selectable on or off.
This option should be “ON” for “DUAL FUEL” applications that use a gas furnace for auxiliary heat.
Gas Auxiliary
When on, this feature turns off the Y terminal 45 seconds after the second stage of heat turns on.
PRO1 Tip
The second stage will turn on at 2x the swing setting. The second stage will turn off when 1x the swing is reached. For example, if the swing setting is .8 degrees for heating and the thermostat is set at 70ºF, the first stage will turn on at approximately 69.2ºF. The second stage will turn on at 68.4ºF. The second stage will turn off at 69.2ºF and the first will turn off at 70.8ºF.
7
MOUNT THERMOSTAT & BATTERY INSTALLATION
Mount Thermostat
Align the 4 tabs on the subbase with corresponding slots on the back of the thermostat, then push gently until the thermostat snaps in place.
C
O
B
E
W2
8
Set Time
Follow the steps below to set the day of the week and current time:
1.
Press MENU
2.
Press SET TIME
3.
Day of the week will be flashing. Use the or key to select the current day of the week.
4.
Press NEXT STEP
5.
The current hour is flashing. Use the or key to select the current hour. When using 12-hour time, make sure the correct a.m. or p.m. choice is selected.
6.
Press NEXT STEP
7.
Minutes are now flashing. Use the or key to select current minutes.
8.
Press DONE when completed
SET TIME
9
Specifications
Pro1 IAQ Inc.
1111 S. Glenstone Suite 2-100 Springeld, MO 65804
Toll-free: 1-888-Pro1iaq (776-1427) Toll Number (Outside the USA): 330-821-3600 Web: http://www.pro1iaq.com Hours of Operation: Monday - Friday 9 AM - 6 PM Eastern
SPECIFICATIONS & CONTACT INFORMATION
The display range of temperature The control range of temperature Load rating Display accuracy Swing (cycle rate or differential)
Power source
Operating ambient Operating humidity Dimensions of thermostat
41ºF to 95ºF (5ºC to 35ºC) 44ºF to 90ºF (7ºC to 32ºC) 1 amp per terminal, 1.5 amp maximum all terminals combined ± 1ºF Heating is adjustable from 0.4ºF to 2.0ºF Cooling is adjustable from 0.4ºF to 2.0ºF 18 to 30 VAC, NEC Class II, 50/60 Hz for hardwire (common wire) Battery power from 2 AA Alkaline Energizer batteries 32º to +105º (0º to +41ºC) 90% non-condensing maximum
4.7”W x 4.4”H x 1.1”D
Contact Us
10
Loading...