Toptech TT-N-705, T705 Installation Manual

Page 1
INSTALLATION MANUAL
This manual covers TopTech models:
TT-N-705 and T705
Thermostat Applications Guide
noitpircseD
Gas or Oil Heat
Electric Furnace
Heat Pump (No Aux. or Emergency Heat)
Heat Pump (with Aux. or Emergency Heat)
Multi-stage Systems
Heat Only Systems
Heat Only Systems - Floor or Wall Furnaces
Cool Only Systems
Millivolt
Table of Contents
Installation Tips Thermostat Quick Reference Subbase Installation Wiring Wiring Diagrams Technician Setup Technician Setup Menu Mounting and Battery Installation Programming The Thermostat Programming The Thermostat (cont) Specifications
Una versión española de este manual puede ser descargada en www.pro1iaq.com
Yes
Yes
Yes
No
No
Yes
Yes
Yes
Yes
Page
2 3 4 5 6 7 8
9 10 11 12
Power Type
Battery Power Hardwire (Common Wire) Hardwire (Common Wire) with Battery Backup
A trained, experienced technician must install this product.
Carefully read these instructions. You could damage this product or cause a hazardous condition if you fail to follow these instructions.
Need Help?
® U.S. Registered Trademark. Patents pending. Copyright © 2006 Pro1 IAQ, Inc. All rights reserved.
Rev. 0850
1
Page 2
Wall locations
The thermostat should be installed approximately 4 to 5 feet above the floor. Select an area with average temperature and good air circulation.
INSTALLATION TIPS
NO NO YES
NO
Do not install thermostat in locations:
• Close to hot or cold air ducts
• That are in direct sunlight
• With an outside wall behind the thermostat
• In areas that do not require conditioning
• Where there are dead spots or drafts (in corners or behind doors)
• Where there might be concealed chimneys or pipes
PRO1 Tip
Pick an installation location that is easy for the user to access. The temperature of the location should be representative of the building.
2
Page 3
Getting to know your thermostat
2
1
7
3 4
8
2
Glow in the Dark Light Button
5
LCD
1
Days of the week and time
6
Button options
Indicates the current room temperature.
Programmable Time Period Icons: This thermostat
has 4 programmable time periods per day.
Displays the user selectable setpoint temperature.
Hold is displayed when thermostat program is permanently overridden.
System operation indicators: The COOL, HEAT or FA N icon will display when the COOL, HEAT or FAN is on.
NOTE: The compressor delay feature is active if these icons are flashing. The compressor will not turn on until the 5 minute delay has elapsed.
Low Battery Indicator: Replace batteries when indicator is shown.
Fan Switch
3
System Switch
4
Easy Change Battery Door
5
Setpoint Buttons
6
User Buttons
7
Universal Private Label Badge
8
Important:
The low battery indicator is displayed when the AA battery power is low. If the user fails to replace the battery within 21 days, the thermostat display will only show the low battery indicator as a final warning before the thermostat becomes inoperable.
3
Page 4
SUBBASE INSTALLATION
Caution: Electrical Hazard
Failure to disconnect the power before beginning to install this product can cause electrical shock or equipment damage.
For vertical mount put one screw top and one screw bottom.
For horizontal mount put one screw left and one screw right.
Mercury Notice:
All of Pro1’s products are mercury free. However, if the product you are replacing contains mercury, dispose of it properly. Your local waste management authority can give you instructions on recycling and proper disposal.
Vertical mount
Horizontal mount
UP
C
O
B
W
RH
RC
Horizontal mount
G
Y
Vertical mount
4
Page 5
WIRING
Caution: Electrical Hazard
Failure to disconnect the power before beginning to install this product can cause electrical shock or equipment damage.
Wiring
1.
If you are replacing a thermostat, make note of the terminal connections on the thermostat that is being replaced. In some cases the wiring connections will not be color coded. For example, the green wire may not be connected to the G terminal.
2.
Loosen the terminal block screws. Insert wires then retighten terminal block screws.
3.
Place nonflammable insulation into wall opening to prevent drafts.
Warning:
All components of the control system and the thermostat installation must conform to Class II circuits per the NEC Code.
Terminal Designations
Heat relay
W
Compressor relay
Y
Fan relay
G
Heat pump changeover valve
O
energized in cooling
Transformer power for cooling
RC
PRO1 Tips:
RH & RC terminals
For single transformer systems, leave the jumper wire in place between RH and RC. Remove jumper wire for two transformer systems.
Heat pump systems
If wiring to a heat pump, use a small piece of wire (not supplied) to connect terminals W and Y.
Transformer power for heating
RH
Heat pump changeover valve energized
B
in heating
Common wire from system transformer
C
C terminal
The C (common wire) terminal does not have to be connected when the thermostat is powered by batteries.
Wire specifications
Use shielded or non-shielded 18 - 22 gauge thermostat wire.
5
Page 6
WIRING DIAGRAMS
Power supply
Factory-installed jumper. Remove only when installing on 2-transformer systems.
Use either O or B terminals for changeover valve.
Use a small piece of wire (not supplied) to connect W and Y terminals.
Set fan operation switch to electric
Optional 24 VAC common connection when thermostat is used in battery power mode.
Typical 1H/1C system: 1 transformer
C
RC
RH
Y C
2
COMPRESSOR
6
R
RELAY
W
G
FAN RELAY
HEAT RELAY
Typical 1H/1C heat pump system
C
L2
RC RH
2
COMPRESSOR
Y C
4
RELAY
6
W G
5
FAN RELAY
L1 (HOT)
1
R
COOL CHANGE
OVER VALVE
HEAT CHANGE
OVER VALVE
L2
L1 (HOT)
1
Typical 1H/1C system: 2 transformer
REMOVE JUMPER
RC RH
Y C
W
G
2
COMPRESSOR
HEAT RELAY
RELAY
6
FAN RELAY
C
L2
L1 (HOT)
1
R
C
L2
L1 (HOT)
1
R
Typical heat-only system
C
RC
2
RH
Y
C
3
O
B
W
G
6
HEAT RELAY
L2
L1 (HOT)
1
R
Typical heat-only system with fan Typical cool-only system
C
RC RH
Y
C
2
R
6
W
G
FAN RELAY
HEAT RELAY
L2
L1 (HOT)
1
RC RH
Y C
W
G
2
6
COMPRESSOR
RELAY
FAN RELAY
C
L2
L1 (HOT)
1
R
6
Page 7
Select F or C with the jumper pin
Reset button
TECHNICIAN SETUP MENU
Gas or Electric Setup
Gas:
For systems that control the fan during a call for heat, put the fan operation switch to the GAS position.
Electric: The thermostat operation
switch should be put in the ELEC position. This setting allows the thermostat to operate the fan when the fan relay is connected to the
G terminal.
Fahrenheit/Celsius Display
Select F or C with the jumper pin on the back of the thermostat. F is for Fahrenheit and C is for Celsius.
12 or 24 hour jumper pin
Important:
The RESET button must be pressed after changing any switch or jumper pin setting. Batteries must be installed for this operation.
12 or 24 Hour Time
12 or 24 hour (military time) can be selected with the jumper pin.
7
Page 8
Technician Setup Menu
This thermostat has a technician setup menu for easy installer configuration. To setup the thermostat for your particular application:
Press MENU button
1.
Press and hold TECH SET button for 3
2.
seconds. This 3 second delay is designed so that homeowners do not accidentally access the installer settings.
TECHNICIAN SETUP MENU
3.
Configure the installer options as desired using the table below.
Use the or keys to change settings and the NEXT STEP or PREV STEP key to move from one option to another. Note: Only press DONE key when you want to exit the Technician Setup options.
Feature
Feature Description
LCD Will Show
Adjustment Options
Filter
Change
Reminder
This feature will flash “FILT” in the display after the elapsed run time to remind the user to change the filter. A setting of “off” will disable this feature.
You can adjust the filter change reminder from “off” to 2000 hours of runtime in 50 hour increments.
Room
Temperature
Calibration
This feature allows the installer to change the calibration of the room temperature display. For example, if the thermostat reads 70° and you would like it to read 72° then select +2.
You can adjust the room temperature display to read -4°F to +4°F above or below the factory calibrated reading.
Minimum
Compressor
On Time
This feature allows the installer to select the minimum run time for the compressor. For example: A setting of 4 will force the compressor to run for at least 4 minutes every time the compressor turns on, regardless of the room temperature.
You can select the minimum compressor run time from “off”, “3”, “4”, or “5” minutes. If 3, 4, or 5 is selected, the compressor will run for at least the selected time before turning off.
Compressor
Short Cycle
Delay
The compressor short cycle delay protects the compressor from “short cycling”. This feature will not allow the compressor to be turned on for 5 minutes after it was last turned off.
Selecting “ON” will not allow the compressor to be turned on for 5 minutes after the last time the compressor was on. Select “off” to remove this delay.
Cooling
Swing
The swing setting, often called “cycle rate”, “differential” or “anticipation” is adjustable. A smaller swing setting will cause more frequent cycles and a larger swing setting will cause fewer cycles.
The cooling swing setting is adjustable from ±0.4°F to ±2°F. For example: A swing setting of
0.5°F will turn the cooling on at approximately 0.5°F above the setpoint and turn the cooling off at approximately
0.5°F below the setpoint.
Heating
Swing
The swing setting, often called “cycle rate”, “differential” or “anticipation” is adjustable. A smaller swing setting will cause more frequent cycles and a larger swing setting will cause fewer cycles.
The heating swing setting is adjustable from ±0.4°F to ±2°F. For example: A swing setting of
0.5°F will turn the heating on at approximately 0.5°F below the setpoint and turn the heating off at approximately
0.5°F above the setpoint.
Factory Default Settings
Off 0 ºF Off On 0.5 ºF 0.4 ºF
PRO1 Tip
Temperature swing, sometimes called differetial or cycle rate, can be customized for this individual application. For most applications choose a swing setting that is as long as possible without making the occupants uncomfortable.
8
Page 9
MOUNT THERMOSTAT & BATTERY INSTALLATION
Mount Thermostat
Align the 4 tabs on the subbase with corresponding slots on the back of the thermostat, then push gently until the thermostat snaps in place.
9
Page 10
PROGRAMMING THE THERMOSTAT
Set Time
Follow the steps below to set the day of the week and current time:
1.
Press MENU
2.
Press SET TIME
3.
Day of the week will be flashing. Use the or key to select the current day of the week.
4.
Press NEXT STEP
5.
The current hour is flashing. Use the or key to select the current hour. When using 12-hour time, make sure the correct a.m. or p.m. choice is selected.
6.
Press NEXT STEP
7.
Minutes are now flashing. Use the or key to select current minutes.
8.
Press DONE when completed
Programming
All programmable Pro1 thermostats are shipped with an energy saving pre-program. You can customize this default program by following the steps below.
Your thermostat can be programmed to have all the weekdays the same, a separate program for Saturday, and a separate program for Sunday. There are four time periods for each program (WAKE, LEAVE, RETURN, SLEEP).
Factory Default Program
Day of the
Week
Weekday
Saturday
Setpoint
TimeEvents
Temperature
(Heat)
Wake 6 a.m. 70° F (21° C) 75° F (24° C)
Leave 8 a.m. 62° F (17° C) 83° F (28° C)
Return 6 p.m. 70° F (21° C) 75° F (24° C)
Sleep 10 p.m. 62° F (17° C) 78° F (26° C)
Wake 8 a.m. 70° F (21° C) 75° F (24° C)
Leave 10 a.m. 62° F (17° C) 83° F (28° C)
Setpoint
Temperature
(Cool)
Return 6 p.m. 70° F (21° C) 75° F (24° C)
Sleep 11 p.m. 62° F (17° C) 78° F (26° C)
Sunday
Wake 8 a.m. 70° F (21° C) 75° F (24° C)
Leave 10 a.m. 62° F (17° C) 83° F (28° C)
Return 6 p.m. 70° F (21° C) 75° F (24° C)
Sleep 11 p.m. 62° F (17° C) 78° F (26° C)
10
Page 11
PROGRAMMING THE THERMOSTAT
You can use the table below to plan your customized program schedule.
Programming Table
Day of the
Week
Weekday
Saturday
Sunday
Wake
Leave
Return
Sleep
Wake
Leave
Return
Sleep
Wake
Leave
Return
Setpoint
TimeEvents
Temperature
(Heat)
Setpoint
Temperature
(Cool)
Sleep
Set Program Schedule
To customize your program schedule, follow these steps
Weekday: Saturday:
1.
Select HEAT or COOL from the system switch. Note: You have to program heat and cool each
separately.
2.
Press MENU
3.
Press SET SCHED. Note: Monday-Friday is displayed and the WAKE icon is shown. You are now program­ming the wake time period for the weekday setting.
4.
Time is flashing. Use the or key to make your time selection for the weekday WAKE time period.
5.
Press NEXT STEP
6.
The setpoint temperature is flashing. Use the or key to make your setpoint selection for the weekday wake period.
7.
Press NEXT STEP
9.
Repeat steps 4 through 7 for Saturday WAKE time period, for Saturday LEAVE time period, for Saturday RETURN time period, and for Saturday SLEEP time period.
Sunday:
10.
Repeat steps 4 through 7 for Sunday WAKE time period, for Sunday LEAVE time period, for Sunday RETURN time period, and for Sunday SLEEP time period.
8.
Repeat steps 4 through 7 for weekday LEAVE time period, for weekday RETURN time period, and for weekday SLEEP time period.
11
Page 12
Specifications
Pro1 IAQ Inc.
1111 S. Glenstone Suite 2-100 Springeld, MO 65804
Toll-free: 1-888-Pro1iaq (776-1427) Toll Number (Outside the USA): 330-821-3600 Web: http://www.pro1iaq.com Hours of Operation: Monday - Friday 9 AM - 6 PM Eastern
SPECIFICATIONS & CONTACT INFORMATION
The display range of temperature The control range of temperature Load rating Display accuracy Swing (cycle rate or differential)
Power source
Operating ambient Operating humidity Dimensions of thermostat
41ºF to 95ºF (5ºC to 35ºC) 44ºF to 90ºF (7ºC to 32ºC) 1 amp per terminal, 1.5 amp maximum all terminals combined ± 1ºF Heating is adjustable from 0.4ºF to 2.0ºF Cooling is adjustable from 0.4ºF to 2.0ºF 18 to 30 VAC, NEC Class II, 50/60 Hz for hardwire (common wire) Battery power from 2 AA Alkaline Energizer batteries 32º to +105º (0º to +41ºC) 90% non-condensing maximum
4.7”W x 4.4”H x 1.1”D
12
Loading...