Toner Cable CAT6S-G User Manual

CAT6S-G
Category 6 UTP Indoor Cable
969 Horsham Road lHorsham, Pennsylvania 19044 USA l Phone: 215-675-2053 Fax: 215-675-7543 linfo@tonercable.com
Packaged in a 1000’ dispenser carton, the cable is ideal for any data cabling installation that doesn’t require plenum cables.
Ordering Information
Model Description
CAT6S-G CAT6 UTP Indoor Cable, Grey Jacket
Specifications Subject To Change Without Notice Rev 12-12 ©Toner Cable Equipment, Inc.
969 Horsham Road lHorsham, Pennsylvania 19044 USA l Phone: 215-675-2053 Fax: 215-675-7543 linfo@tonercable.com
Specifications
CAT6S-G
Category 6 UTP Indoor Cable
Applications
Telephony Voice Wiring, Network T Base 10 / 100 / 1000, UL Subject 444, EIA / TIA568 & ISO / IEC 11801
Construction
Center Conductor: 4 pairs 0.0226” (23 AWG) bare copper
Dielectric: 0.0403” PE
Separator Cross: PE
Outer Jacket: 0.248” PVC
Electrical Characteristics at 20°C
Conductor Resistance (Max): 98.6 Ω / km
Insulation Resistance (Min): 5000 MΩ / km
Capacitance: < 55 pF / m
Impedance: 100 Ω (±15%)
Transport & Storage
Temperature: 0 +50°C
Operating Temperature: -20 to +65°C
Performance Characteristics
Frequency Attenuation / 100m NEXT PS-NEXT ELFEXT PS-ELFEXT Return Loss
(MAX) (MIN)
1 MHz 1.9 dB 72 dB 69 dB 68 dB 65 dB 20 dB
10 MHz 5.9 dB 65 dB 62 dB 53 dB 50 dB 23 dB
16 MHz 7.5 dB 61 dB 58 dB 48 dB 45 dB 26 dB
25 MHz 9.3 dB 55 dB 52 dB 45 dB 42 dB 25 dB
40 MHz 12.1 dB 53 dB 50 dB 42 dB 39 dB 23 dB
60 MHz 14.8 dB 52 dB 49 dB 35 dB 32 dB 22 dB
100 MHz 19.3 dB 50 dB 47 dB 31 dB 28 dB 22 dB
150 MHz 23.6 dB 43 dB 40 dB 28 dB 25 dB 19 dB
200 MHz 27.5 dB 40 dB 37 dB 24 dB 21 dB 18 dB
250 MHz 30.6 dB 38 dB 35 dB 21 dB 18 dB 18 dB
• PVC - Polyvinylchloride • AWG - American Wire Gauge • AL / PE - Aluminum / Polyethylene
Loading...