TJERNLUND HSJ, 1, 2 POWER VENTERS WITH UC1 CONTROL 8506001 REV B 0206, HS1, HS2 Dimensions

HSJ POWER VENTER SPECIFICATIONS
Performance curves
Static pressure (inches H2O) vs CFM (std. air) at selected flue gas temps. NOTE: TO ARRIVE AT TOTAL SYSTEM STATIC PRESSURE REFER TO CURVE AND ADD .38” TO COMPENSATE FOR VENT HOOD AND WIND RESISTANCE.
MOTOR ELECTRICAL DATA
Volts 115 Hertz 60 RPM 3000 Watts 95 Amps 1.26 Therm. Prot. Yes
MOTOR MECHANICAL DATA
DESCRIPTION
Shaded Pole Yes Open Yes Int. Fan Cooled Yes
BEARINGS
Type Sleeve Material Sintered Iron
UC1 UNIVERSAL CONTROL
Maximum Power Consumption 1/2 Amp @ 120 VAC 50/60 Hz + Venter motor load
Pre-Purge: Options (0,15,30,60 seconds)
Post-Purge: Factory set at 2 minutes Options (0,30 seconds; 1,2,4,8,16 minutes)
Dimensions: 5” x 8” (2’ electrical whip inc.)
SAFETY / INTERLOCK
Fan Proving Switch
5 VDC UC1 board supplied power switched through Fan Prover. UC1 burner / gas valve interlock rated for 1 H.P. @ 120 VAC.
MODELS AND APPLICATION:
HSJ (Gas or Oil)
Used as a means of Side Wall Venting gas or oil appliances which require a Post Purge cycle. Used also to co-vent two gas heaters within combined BTU/hr. input listed below (requires accessory controls). Includes a Fan Proving Switch and the UC1 Universal Control for 24V, 115V or “dry contact” actuation. LED diagnos­tics and Pre / Post-purge options are standard with the UC1.
HSUL-J (Discontinued 8/05) HS115-J & HST-J (Discontinued 7/02)
Replace above models with HSJ.
Note: Tjernlund Products, Inc. reserves the right to make changes to specifications without notification.
ADJUSTMENT ROD
DAMPER
TOLERANCE: ±1/8" UNLESS OTHERWISE NOTED
SHADED POLE MOTOR
3,000 R.P.M.
ADJUSTABLE DAMPER
FAN PROVING PRESSURE SWITCH
4 5/8
3 1/8
9 5/8
4 I.D.
2
4 I.D.
7
9 7/8
1 7/8
1
4 3/4
7 5/8
4 I.D.
5 5/8
7 1/2
2 1/4
5 1/4
FIGURE 2061000-3
1 1/2
FAN PROVER SENSOR
SHIELD
DRIP
1 1/8
-SIDE VIEW- -END VIEW- -PLAN VIEW-
P/N 8506001 REV. B 2/06
500°F
400°F
300°F
70°F
1.00
.80
.60
.20
.40
1601401208060 1004020CFM (std air)
DIA.
VENT BTU / HR
MAXIMUM PIPE LENGTH
OILGAS
23'
--
--
100' 100'
100' 100' 100'
35'
100'
100'
100'
125,000
100,000
75,000
50,000
4"HSJ
500° F400° F300° F
FIREDFIRED
AT STACK TEMPERATURE
(FT)
INPUT
PIPE
MODEL
TJERNLUND PRODUCTS, INC.
1601 Ninth Street • White Bear Lake, MN 55110-6794 PHONE (800) 255-4208 • (651) 426-2993 • FAX (651) 426-9547 Visit our web site • www.tjernlund.com
HS1 POWER VENTER SPECIFICATIONS
Performance curves
Static pressure (inches H2O) vs CFM (std. air) at selected flue gas temps. NOTE: TO ARRIVE AT TOTAL SYSTEM STATIC PRESSURE REFER TO CURVE AND ADD .38” TO COMPENSATE FOR VENT HOOD AND WIND RESISTANCE.
MODELS AND APPLICATION:
HS1 (Gas or Oil)
Used as a means of Side Wall Venting gas or oil appliances which require a Post Purge cycle. Used also to co-vent multiple heaters within combined BTU/hr. input listed below (requires accessory controls). Includes a Fan Proving Switch and the UC1 Universal Control for 24V, 115V or “dry contact” actuation. LED diagnos­tics and Pre / Post-purge options are standard with the UC1.
HSUL-1 (Discontinued 8/05) HS115-1 & HST-1 (Discontinued 7/02)
Replace above models with HS1.
Note: Tjernlund Products, Inc. reserves the right to make changes to specifications without notification.
70°F
300°F 400°F
500°F
1.00
.60
.20
.40
.80
16014010080 1206040CFM (std air) 20
FIGURE 2011038-3
1 1/2
SHIELD
DRIP
TOLERANCE: ±1/8" UNLESS OTHERWISE NOTED
SHADED POLE MOTOR
3,000 R.P.M.
7 5/8
4 I.D.
5 5/8
7 1/2
2 1/4
5 1/4
ADJUSTMENT ROD
DAMPER
4 5/8
3 1/8
1 1/8
10 3/4
2 1/16
4 I.D.
7
4 I.D.
FAN PROVER SENSOR
134 3/4
11
FAN PROVING PRESSURE SWITCH
ADJUSTABLE DAMPER
DIA.
VENT BTU / HR
MAXIMUM PIPE LENGTH
OILGAS
--
--
--
--
--
--
35' 27'
100' 100'
60' 57' 12'
100' 100'
92'
100'
30'
100' 100'
4'
40'
87'
100'
150,000 200,000 250,000 300,000
300,000
250,000
200,000
150,000
6"
4"
HS1
500° F400° F300° F
FIREDFIRED
AT STACK TEMPERATURE
(FT)
INPUT
PIPE
MODEL
-SIDE VIEW- -END VIEW- -PLAN VIEW-
TJERNLUND PRODUCTS, INC.
1601 Ninth Street • White Bear Lake, MN 55110-6794 PHONE (800) 255-4208 • (651) 426-2993 • FAX (651) 426-9547 Visit our web site • www.tjernlund.com
MOTOR ELECTRICAL DATA
Volts 115 Hertz 60 RPM 3000 Watts 95 Amps 1.26 Therm. Prot. Yes
MOTOR MECHANICAL DATA
DESCRIPTION
Shaded Pole Yes Open Yes Int. Fan Cooled Yes
BEARINGS
Type Sleeve Material Sintered Iron
UC1 UNIVERSAL CONTROL
Maximum Power Consumption 1/2 Amp @ 120 VAC 50/60 Hz + Venter motor load
Pre-Purge: Options (0,15,30,60 seconds)
Post-Purge: Factory set at 2 minutes Options (0,30 seconds; 1,2,4,8,16 minutes)
Dimensions: 5” x 8” (2’ electrical whip inc.)
SAFETY / INTERLOCK
Fan Proving Switch
5 VDC UC1 board supplied power switched through Fan Prover. UC1 burner / gas valve interlock rated for 1 H.P. @ 120 VAC.