Titan TOCS01 User Manual

1
TOCS01
SURFACE MOUNT 360°
MICROSENSITIVE
OCCUPANCY DETECTOR
Main Body Lens
INTRODUCTION
The use of occupancy detectors in commercial and industrial applications can significantly reduce energy usage reducing both energy costs and helping the environment.
The TOCS01 360 degrees MICROSENSITIVE surface mount OCCUPANCY DETECTOR uses passive infrared sensors (PIR) which react to changes in temperature emitted by the slight motion of persons or objects passing through its detection area. The PIR sensor automatically operates the connected load when an area is occupied. After a preset time on non-activation (when an area is vacated) the load will be switched off. In addition the built in photocell takes natural light (daylight) into account when determining its activation.
Note : Read this entire manual before you start to install the system.
SAFETY PRECAUTIONS
Do not install when it may be possible for water
to access the fitting.
Be sure to switch off power source before
installing.
Make sure that the power wiring comes from
circuit with an external miniature circuit breaker not higher than 16A for the short circuit protection or a suitable fuse.
IMPORTANT
Some local building codes may require installation of this product by a qualified electrician.
Check your local codes as they apply to your situation. If the house wiring is of aluminum, consult with an electrician about proper wiring methods.
Before proceeding with the installation, TURN OFF THE POWER TO THE LIGHTING CIRCUIT AT THE CIRCUIT BREAKER OR FUSE BOX TO AVOID ELECTRICAL SHOCK.
CHOOSING A MOUNTING LOCATION
Avoid aiming the motion sensor at heating vents,
air conditioners or objects which may change temperature rapidly.
Do not allow sunlight to fall directly on the front of
unit.
FIGURE 1
INSTALLATION
The unit has a sensing angle of 360°. It detects micro movement within a 7m diameter (sitting zone) and can detect general movement up to 10m diameter at a mounting height of 2.5 meters. (FIGURE 2)
.
FIGURE 2
2
SCHEMATIC
FIGURE 3
WIRING INSTRUCTION
(1) Switch off the power source or wall switch.
(2) Strip approximately 6-8mm insulating part of the
wires from the power cord.
(3) Connect the BROWN wire (Live wire) of power
cord to the terminal block "L" mark.
Connect the BLUE wire (Neutral wire) of power
cord to the terminal block “N” mark.
Connect the RED wire of lamp wire to the
terminal block "LS" mark. (FIGURE 4)
FIGURE 4
(4) Fit the main body to the wall box of the ceiling
and secure it with two fixing screws provided. (FIGURE 5)
FIGURE 5
The product is also designed to fit a standard UK spec pattress box.
SETTING THE LIGHTING SYSTEM
(1) TEST MODE
Turn the Lux control and the Time control
counter-clockwise to the edge-the TEST position. (FIGURE 6)
FIGURE 6
Turn the power supply or wall switch on, the light
will turn on immediately and wait for about 1 minute to warm up the unit. After warming-up time is expired and the light goes off, you may make a walk test and the light will turn on. This confirms that the wiring was done properly and that the light is working.
Walk through the coverage area. The light will
turn on for about 5 seconds when motion is
detected and turn off shortly after the area is fully
vacated.
(2) SETTINGS
TIME ADJUSTMENT The TIME adjustment controls how long the light will stay on after motion has been detected.
Adjust the TIME Control Knob clockwise to increase the turn-off time (40 minutes maximum) or counter-clockwise to decrease the turn-off time (5 seconds minimum). (FIGURE 7)
FIGURE 7
LUX ADJUSTMENT The LUX adjustment determines at what light level the light will start operating when you set the sensor to the AUTO mode.
L N
AC POWER
Brown Blue Red
Loading
about 5 sec about 40min
OPTIONAL
Loading...
+ 1 hidden pages