Shows the lubricant remaining
in the Timken C-Power LV-Unit
in percent volume.
Setting Mode
Displays the current setting in days,
weeks or months.
Size of Timken C-Power LV-Unit
Displays volume of LV-Unit (250 or 500 cc)
Ice Icon
Indicates either that the temperature
fell below 0° C/ 32° F (icon blinking) or
that the low temperature shutoff (below
-20° C/-4° F) has turned the system off
(icon permanent).
No Function
Setting of C-Power LV-Unit size
is done via menu on the display.
Battery – Set
(Timken C-Power B)
2
On this page, you will find some important information for quick and easy operation and setting of the
Timken C-Power. Before the first installation of the Timken C-Power, and whenever you need detailed
instructions, you should read the complete Operating Manual, which contains information that must
be observed. Make sure to follow the instructions given in the chapter “Safety Notes.”
1. Assembly of the Timken C-Power/Exchange of Timken C-Power
LV-Unit (refer to Chapters 4 and 7)
Mount the drive unit on the mounting plate and secure it at
•
the three pre-drilled holes (see attached template).
Insert a new battery set into the battery compartment (follow
•
directions of the arrows).
Place the LV-Unit inside the cover and remove the plug of the
•
LV-Unit.
Push the LV-Unit into the cover until lubricant comes out of
•
the opening.
Place the LV-Unit with its cover on the drive unit. Make sure
•
that the catch locks and that the teeth of LV-Unit and drive
unit interlock.
Turn the cover clockwise until the bayonet catch locks.
•
2. Determine the Discharge Period (refer to Chapter 6.7)
Refer to the manufacturer’s guidelines about the lubrication point that you want to lubricate
•
to determine the required lubricant amount in cc per one hundred operating hours.
Refer to Chart 3 (Chapter 6.7, Chart 4) and find your required lubrication amount. Based on that, the
•
chart will show you the required C-Power LV-Unit size, the setting of the discharge period, and the setting mode.
You also may refer to our Timken Select program, which can be downloaded from our web page
•
free of charge. It helps you in selecting the correct settings.
3. Setting of LV-Unit Size, Discharge Period, Outlets and PIN (refer to Chapter 6.8)
Hold down the MODE/SAVE button until the set time is displayed.
•
Hold down the MODE/SAVE button again until you reach the current PIN (PIN cannot be changed
•
here/PIN setting at delivery is “00”).
Hold down the MODE/SAVE button again until you reach the other setting menus:
•
LV-Unit, discharge period, outlets and PIN change. Change settings with a short push of
MODE/SAVE or ON/OFF/SELECT.
4. Save Settings (refer to Chapter 6.8)
Keep the MODE/SAVE button pressed until display shows “– –”.
•
5. Starting Timken C-Power (refer to Chapter 6.5)
Hold down the ON/OFF/SELECT button until the “Remaining Volume” appears in the
•
display and the green LED starts blinking.
6. Stopping Timken C-Power (refer to Chapter 6.6)
Keep the ON/OFF/SELECT button pressed until the display shows (“––”).
•
3
QUICK REFERENCE DISTRIBUTION GUIDE
Outlets 1 to 3
With connections
for grease lines.
Housing
Contains drive unit and
distribution system.
Connection Thread
For attaching a lubricator of
the Timken C-Power Line.
Outlets 4 to 6
With connections
for grease lines.
Connector
Used for plugging in
the connecting cable.
Accessories
Plugs (4 pcs.)
For sealing the outlets
that are not used.
Connecting Cable (1 pc.)
Used for power supply and
for communication.
Activation of Outlets on Timken C-Power Multi-Point Lubricator/Timken C-Power Control
Multi-Point Lubricator
Activation/selection of outlets is done on the connected Timken C-Power/Timken C-Power Control. Please
observe operating instructions (refer to Chapter 6.8) of the attached lubrication system since
the following chart does not go into detail. Outlets must be activated by the user before operation (factory
setting = all outlets inactive).
On/Off Outlet 1
or
6 Connections
Straight or angle. For
grease lines.
1
Outlet 1 active
1
2
2
4
On/Off Outlet 2
or
Outlet 2 active
(if desired, remaining outlets can
be turned On/Off the same way)
On this page, you will find some important information for quick and easy operation and setting of your Timken
C-Power Distributor Block. Before the Timken C-Power Distributor Block is used, prior to the assembly of the
distributor with a lubricator of the Timken C-Power range and whenever you need detailed information, you
should read the complete Operating Instructions, which contain information that must be observed. Make sure
to follow the instructions given in the chapter “Safety Instructions.“
Additionally, you have to observe the Operating Instructions of the connected lubricator.
1. Assembly of Timken C-Power (refer to Chapters 4.1 and 4.2)
Screw connections into the outlets that you want to activate and seal the other outlets with plugs.
•
2. Connect Timken C-Power to the Lubricator (refer to Chapter 4.2)
Connect the lubricant tubes (Ø 8 x 1.5, inner-Ø 5mm, admissible total length per pipe up to 5 m) to the
•
connecting pieces of the distributor and lay them between the distributor and the lubrication point.
Connect the lubricator with the distributor using the enclosed connecting cable. For this, the
•
lubrication system must be switched off.
3. Determine Discharge Period (refer to Chapter 6.7)
Determine the required lubricant volume (cc) per one hundred operating hours while taking into
•
account the number of open outlets. For this, you have to multiply the lubricant volume with the
number of open outlets.
You have to take into account that this distributor is able to supply an equal amount of lubricant to up
•
to six lubrication points.
Determine the required discharge volume using the Operating Instructions of the lubricator. Depending
•
on the size of the Timken C-Power LV-Unit, you can then determine the setting of the discharge period
and the setting mode.
You also may refer to our Timken Select program. It helps you in selecting the correct settings.
•
4. Setting and Starting the Complete Lubrication System (refer to Chapter 6.5)
Set discharge period or Impulse mode, size of Timken C-Power LV-Unit, outlets, PIN (refer to
•
Timken C-Power Multi-Point Lubricator/Timken C-Power Control Multi-Point Lubricator operating
instructions, Chapter 6.8, of each lubricator).
Keep the ON/OFF/SELECT button of the Timken C-Power Multi-Point Lubricator pressed until the
•
display no longer shows “––” (for Off).
An automatic initialization is carried out by the lubrication system and the display shows the counting
•
of the outlets.
After the initialization is complete, the display of the lubricator shows the remaining volume and the
•
lubrication system starts to operate.
5
TABLE OF CONTENTS
The Timken C-Power mulTi-PoinT lubriCaTor SySTem
QuiCk referenCe Guide
This operating manual is intended for the safe operation of the Timken C-Power Multi-Point Lubricator.
•
It contains safety instructions that must be adhered to.
Everyone who works on or with the lubricator must have access to this operating manual during their
•
shift. They also must pay attention to all relevant instructions and notices.
The operating manual must always be kept complete and in easy to read condition.
•
Terms Used
Timken C-Power Multi-Point Lubricator
•
In the following text, the Timken C-Power Multi-Point Lubricator will either be called lubricator or
by its name, Timken C-Power Multi-Point Lubricator.
Lubrication Canister
•
In the following text, the “Canister” will be called Timken C-Power LV-Unit. The user can order the
Timken C-Power LV-Unit with different lubricants and in size 250 cc and 500 cc.
Usage of Safety Instructions
All safety instructions in this operating manual are standardized.
Danger Signs
This sign warns you of any danger to people’s health or to subjects.
Tips
This sign alerts you to application tips that will help you in doing certain tasks quicker and safer.
1.1 Delivery/Content
Timken C-Power Multi-Point Lubricator will be delivered according to customer specifications in
•
regard to type of grease and size of Timken C-Power LV-Unit. The user must only assemble it and
adjust the desired settings.
Mounting device and screws included.
•
Operating instructions and EC Conformity Declaration included. Upon delivery, make sure to check if
•
the delivered goods correspond to your order. Timken will not accept liability for subsequent claims of
any shortcomings.
Please immediately forward any claims:
•
• of noticeable transport damage: directly to the forwarder.
• of noticeable faults, shortcomings or defects: directly to your Timken distributor.
1.2 Storage
When the lubricators are not immediately installed, you must ensure appropriate storage
conditions in dry, dust-free places with a temperature of +20° C ±5° C (+68° F ±9° F).
Please make sure that the cover disc (2) with plug (3) on Timken C-Power/ Timken
C-Power Control Multi-Point Lubricator drive units (1) is never removed for a longer period since this will cause the internal support battery to empty prematurely.
Remove the cover disc only right before you intend to use the lubricator.
Extended storage periods without cover disc/plug or without a Timken
C-Power LV-Unit should be avoided.
Make sure that Timken C-Power LV-Units and battery sets are not stored
longer than one year.
Fig. 1.
7
1.3 Markings
The lubricator is clearly marked with a label (serial number) on the drive system and a label
•
on the Timken C-Power LV-Unit.
CE mark on the drive unit and the Timken C-Power LV-Unit.
•
Manufacturer:
•
Timken
Hammelburger Straße 21
97717 Euerdorf, Germany
This equipment is suitable for use in Class I, Division 2, Groups A, B, C and D or non-hazardous locations only.
WARNING–EXPLOSIVE HAZARD–substitution of components may impair suitability for Class I, Division 2.
1.4 Intended Usage
• Immediately supplies all lubrication points with lubricant, at a pressure build-up of maximum 25 bar
(360 psi.), permanently, precisely and independent of temperature.
• Can be used for all lubrication points of sliding and roller bearings, drive and transport chains,
sliding guideways, open gears and seals.
• Should only be connected to/used with original lubrication tubes from Timken.
• Is intended for use on machinery and equipment.
• Is only to be used for the ordered purpose and purposes confirmed by Timken.
• Is only to be used for operating conditions recommended in this operating manual.
• Is only to be used with settings and variations recommended in this operating manual.
The Timken C-Power Multi-Point Lubricator
•
Any other usage, setting, addition and/or variation is considered inappropriate.
1.5 Legal Requirements
Liability
•
• The information, data and tips stated in this operating manual were up-to-data as of the printing date.
No claims for already delivered Timken C-Power Multi-Point Lubricators can be made based on the
information, pictures and descriptions
• Timken cannot be held liable for damages and malfunctions caused by:
- inappropriate usage;
- unauthorized alterations to the drive system or the Timken C-Power LV-Unit;
- inappropriate operations on or with the lubricator;
- incorrect operation and settings of the lubricator;
- incorrect settings of time and size of the lubricator;
- ignoring the operating manual.
Warranty
•
•Warranty terms and conditions: see terms and conditions of sale and delivery pertaining to Timken.
•Lodge any warranty claims with your local supplier immediately after the defect or error has
been identified.
•The warranty expires in all instances where no liability claims can be enforced.
8
2. SAFETY INSTRUCTIONS
2.1 Persons Responsible for Safety
The operator or his safety officer must warrant:
•
• that all the relevant regulations, instructions and laws are adhered to;
• that only qualified personnel will work with and on the lubricator;
• that unauthorized personnel are not allowed to work with and on the lubricator;
• that the safety regulations are adhered to when mounting the lubricator or during maintenance.
2.2 General Safety Instructions
We are not laying claim to completeness in regards to these safety instructions. Please contact
•
Timken Customer Service if you have any questions or problems.
At the time of delivery the lubricator is in line with state-of-the-art technology and in principle is
•
considered to be safe to operate.
Dangers emanate from the lubricator for persons, the lubricator itself and for other material assets of
•
the operator if:
•unqualified personnel operate the lubricator;
•the lubricator is used inappropriately and for operations for which it was not intended;
•the lubricator setting/variation is incorrect;
•the lubricator is opened by force while in operation;
•the lubricator is not mounted with the Timken mounting device;
•the tube connection to the lubrication point was not carried out and attached correctly;
Operate the lubricator only when it is in perfect condition.
•
Retrofitting, changing or reconstructing the lubricator is prohibited. Timken must be consulted first.
•
Only original tube connections and connectors from Timken can be used on or with the lubrication
•
system since these will withstand high pressures of up to 25 bar (360psi).
Ambient media, especially chemically aggressive substances, can attack seals and plastic.
•
2.3 Safety Information for Timken C-Power Multi-Point Lubricator
Safety During Installation and Maintenance
•
• Ensure that all workstations and traffic routes are clean and safe.
• Ensure that the relevant regulations and guidelines are adhered to when the installation or
maintenance work is carried out in places where danger of falling exists.
• Ensure that the relevant safety and operating instructions are observed when the lubricators are
installed or serviced on machines or in factories (i.e. to stop the machine).
• Avoid contact of lubricant with eyes, skin and clothing.
• Avoid swallowing lubricant.
• Prevent lubricant from getting into soil or sewer system.
• Observe lubricant safety data sheets.
• Lubricant on traffic ways will increase the danger of slipping. Therefore, immediately clean lubricant
from floors with special cleaner.
• Only use original Timken C-Power LV-Units from Timken.
• Avoid contact of battery substances with eyes, skin and clothing.
• Avoid swallowing any leaking battery substances.
• Observe safety data sheets for batteries.
• Do not expose batteries to extreme heat and do not throw into open fire.
• Do not recharge batteries.
• Ensure that regulations for waste disposal of batteries are observed.
• Only use original battery sets from Timken.
Safety When Handling the Timken C-Power LV-Unit
•
Safety when Handling Batteries.
•
9
3. TECHNICAL DATA FOR DRIVE UNIT
Table 1.
Table 2.
Volume of t he C-Pow er LV-Uni t 25 0 cc50 0 cc
Leng th (L) 210 mm 26 0 mm
Diame ter (D) 92 mm92 mm
Weigh t, empt y 1.3 0 kg1.3 7 mm
Weigh t, fill ed with SF0 4 1.5 3 kg1.82 mm
Discharged volume per lubricatio n impulse 0. 5 cc
60˚
50˚
40˚
30˚
20˚
10˚
0˚
Temperature Degrees Celsius
-10˚
-20˚
The dashed standard grease and dotted low temperature lines show the maximum values allowed.
Discharge period 1 day to 24 mont hs1 day t o 12 months
Applicat ion temperature-20° C t o +60 ° C/-4° F to +14 0° F
Maximum p ressure b uildup25 bar/3 60 psi
Maximum t ube length (inner-Ø 5 mm) 5m
Lubrican ts
Power supplyBat tery set C- Power B (3 V alka line mangan ese, not r echargeabl e)
Connecti on threadG 3/ 8 outside – G 1 /8 inside
Protect ion class
Diagram showing dependency of application
temperature and tube length (inner-ø 5 mm) for Timken
standard grease and low-temperature grease
012345
Tube Length in Meters
Application area
for standard grease
Application area
for low temperature grease
C-Power 2 50 C-Power 5 00
Comb ination of these
maximum-values can o nly be
reali zed by tem peratures of
≥2 0° C/68° F. At lower
temperat ures, th e applicat ion
Greas es up to ra ted
consi stency N LGI 2
Protect ion class I P 54 D L
UL Ce rtification and listing informat ion
Out of specification range
No warranty!
is limite d according
to the diagram below.
140˚
120˚
100˚
80˚
60˚
40˚
20˚
0˚
Temperature Degrees Fahrenheit
10
If your application is out of the specification range shown in this diagram, please contact your local
distributor. Timken cannot be held liable for these applications.
Example:
1. The application temperature is +5° C/+41° F. What is the maximum tube length allowed for
standard grease?
Correct Answer: 3 m maximum tube length for standard grease, 5 m maximum tube length for low
temperature grease (arrow 1 meets the dashed line of the standard grease range at 3 m)
2. You want to use a 4 m tube. Up to what temperature can the system be used? Correct Answer: +10° C/50° F with standard grease -5° C/23° F with low-temperature grease (arrow 3
meets the dotted line of low-temperature grease at the -5° C mark; and the dashed line of the standard
grease at the +10° C mark)
Loading...
+ 22 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.