Time Mark 422 Data Sheet

C
L
3.88"
3.0"
0.44"
3.03" Holes are symetrical
about center line.
0.203" 4 PL.
5.5"
6.06"
0.55"
2.63"
0.28"
MOTOR
4-20mA
OUTPUT
REVERSE WIRES TO CT IF MOTOR FAILS TO RUN FOR MORE THAN THE INITIAL 2 SECOND PERIOD.
MODEL 276A-xx
L1
L2
MANUAL
RESTART
120VAC COIL
TIME MARK is a division of
MODEL 422
Submersible
Pump Controller
Monitors True Motor Power (volts x current x power factor)
Detects Motor Overload or Underload
Operates on 120 or 240VAC,
Single-phase or 3-phase
Built-in Trip and Restart Delay Options
SPECIFICATIONS
DESCRIPTION
The Model 422 Submersible Pump Controller detects an overload or underload condition on all types of running pump motors: suction pumps, submersible pumps, etc.
This Monitor detects the actual power used (voltage x current x power factor) and is more sensitive than simple current monitors. The 422 can be used with single phase pumps or, using the Model 276C current transducer, with 3-phase pumps. Matching CT’s allow the Model 422 to be used with most pump motor sizes.
Optional trip and restart delays are provided.
TYPICAL APPLICATION -single-phase monitoring
Model 422
Input Voltage Range 100-130VAC or 200-250VAC
Frequency 50/60Hz
Power Consumption
Nominal Current
Minimum Current
Current Adjustment 0 - 5 amps x PF
Current Output 4-20mA for chart recorders
Repeat Accuracy 1% (fixed conditions)
Output SPDT 10A at 240VAC resistive
Expected Relay Life Mech: 10 million operations
Trip Delay
Restart Delay
Indicators Red LED: Overload or Underload; tripped
Transient Protection 2500V for 10ms
Operating Temp - 2to 131º F
Humidity Tolerance 97% w/o condensation
Enclosure Material ABS plastic
Weight 1 lb.
Agency Approvals UL Listed to US and Canadian safety
0.5 VA max.
2.5 amps
0.25 amps
Elec: 100,000 operations at rated load
OFF or 0.3 to 180 seconds
OFF or 0.1 to 4 hours
Yellow LED: Restart timing
standards CSA Certified
DIMENSIONS
Page 1 of 8 11/2011
© 2011 TIME MARK CORPORATION
TIME MARK is a division of
MODEL 422
READ ALL INSTRUCTIONS BEFORE INSTALLING, OPERATING OR SERVICING THIS DEVICE.
Submersible Pump Controller
KEEP THIS DATA SHEET FOR FUTURE REFERENCE.
APPLICATION GUIDE
GENERAL
This application guide is written for equipment designers, maintenance personnel, electrical contractors, etc.
It is intended to aid in the installation of the Model 422 Submersible Pump Controller into pump protection systems. The notes and diagrams deal with methods of protecting motors in the event of an underload condition or an overload condition.
THEORY
The need for a system to detect an underload condition other than by the simple monitoring of current becomes clear when examining the following waveforms.
In a purely resistive circuit, as in Figure 1, the current (amps) is directly proportional to the power (watts) being consumed. To find the power, multiply the voltage across the load times the current through the load. The result is in watts (V x A = W).
In Figure 2, When the load is not resistive, but inductive as it is with a motor, the formula is no longer correct. The inaccuracy occurs because the current and the voltage waveforms are not in phase.
The current waveform lags the voltage waveform by as much as
90 degrees in a completely unloaded condition, or as little as 5 or 10 degrees in a fully loaded condition.
The current, as measured with an ammeter, may only vary a slight amount as the motor changes from a fully loaded condition to a completely unloaded condition. This makes it difficult to detect an unloaded condition by simply monitoring current alone.
To obtain an accurate picture of real power consumption of any inductive device, such as a motor, the formula V x A x Cosø = W is used.
The Cosø is a multiplication factor derived from the number of degrees of lag between the current and voltage waveforms.
This is called the “power factor” (or “PF”). The power factor is the natural cosine of the degrees of lag:
Degrees
of lag
0 1.000 50 0.643
5 0.996 55 0.574
10 0.985 60 0.500
15 0.966 65 0.423
20 0.940 70 0.342
25 0.906 75 0.259
30 0.866 80 0.174
35 0.819 85 0.087
40 0.766 90 0.000
45 0.707
Power Factor
Degrees
of lag
Power Factor
Figure 1. RESISTIVE
LOAD
With a purely resistive load, the current and voltage waveforms are occurring simultaneously.
Figure 2. INDUCTIVE
LOAD
With an inload, the current waveform lags the voltage waveform by 60°.
Page 2 of 8 11/2011
© 2011 TIME MARK CORPORATION
TIME MARK is a division of
2.38"
1.95"
1.63"
Secondary
Space for Primary turn:
0.25" 0.38"x
1.25"
0.43"
.187" dia.
Secondary terminals
(0 - 5 amps)
Loop one leg of AC line thru transformer as shown
MODEL 422
Submersible Pump Controller
APPLICATION GUIDE
Example: TRUE POWER CONSUMED BY AN AC
MOTOR
For this example we will use a 3-horsepower, 230 volt, single phase motor.
Condition 1 represents the motor being used at near full load, while Condition 2 represents a drop in motor load.
Comparing the results of this example, the motor current decreased only 10% with a drop of 61% in the motor load (input power). A drop in pump motor power cannot be accurately measured by only monitoring the current and voltage.
By monitoring the phase relationship and applying the resultant power factor an accurate and selective method of sensing changes in true power consumption can be obtained.
The Model 422 Controller is based on the above principal of detecting the actual power used, and is more sensitive than simple current monitors.
ADDITIONAL FEATURES
As described previously, the Model 422 would fulfill the basic requirements in most pump motor protection control systems. However, there are situations which would require the pump to restart automatically after a preset time.
The Model 422 has an adjustable restart timer for such applications. This timer has a range of 0.1 to 4 hours. If the restart timer is not needed, turn it off with DIP switch 2.
If restart timing is needed for an underload condition only, the overload restart can be turned off with DIP switch 1.
Resetting the Model 422 is accomplished by cycling the power off and back on, pressing the RESET button, or by using the restart timer (DIP switch 2).
Some applications require a trip delay period before shutting down the pump. The Model 422 has a built-in trip delay timer. The timing range is from 0.3 to 180 seconds. The trip delay timer can be turned off with DIP switch 4.
Example: (V x A x Cosø = Watts)
Condition 1
230 volts x 10 amps x 0.985 PF = 2265.5 watts
Condition 2
230 volts x 9 amps x 0.423 PF = 875.6 watts
Refer to the chart under INSTALLATION (pg 4) for all DIP switch settings.
A 4-20mA output is provided for monitoring power consumption. A 4mA output is equal to 0 watts and a 20mA output is equal to 600 watts at 120 V or 1200 watts at 240 V.
This signal can be sent to a strip chart recorder, a process controller, computer, etc.
INPUT CURRENT REQUIREMENTS
The CT input of the Model 422 is the isolated winding of a small current transformer within the unit. Ideally, the current range needed should be between 2 and 3.5 amps for a fully loaded motor.
Polarity of the wires connected to the CT terminals is critical to achieve the correct phase relationship
between the current and voltage waveforms as described earlier.
This is simple to determine after the installation is complete (refer to the ADJUSTMENT PROCEDURE, pg
5).
If the full load motor current is 3.5 amps or less, and the pump motor is a single-phase type, connect one leg of the motor current directly into the Model 422.
Figure 3 shows the Model 276A and Figure 4 shows the Model 276B Current Transformers; available from Time Mark.
Figure 3. MODEL 276A CURRENT TRANSFORMER
Page 3 of 8 11/2011
© 2011 TIME MARK CORPORATION
2.6"
3.6"
.187" dia. typical
4.0"
2.3"
4.6"
TIME MARK is a division of
3.90"
2.00"
0.44"
1.25"
4.50"
3.88"
(2) 0.27" x 0.44" slots
B
C
MODEL 422
APPLICATION GUIDE INSTALLATION INSTUCTIONS
Figure 4. MODEL 276B CURRENT TRANSFORMER
Use the chart below to cross reference your motor horsepower to a Time Mark single-phase or 3-phase current transformer.
Figure 5. CURRENT TRANSFORMER CHART
Motor
1 1/2 276A-30 276A-15 276A-10 *
7 1/2 276B-150 276B-60 276A-35 276A-20
100 276B-400 276B-200 125 276B-250 150 276B-300 200 276B-400 250 276B-500 300 276B-600 350 276B-700 400 276B-750 500 276B-1000
Submersible Pump Controller
276B Series
50 - 500 600 - 1200
B = 0.87 C = 1.56” C = 2.06”
Time Mark Model Number
Single-Phase 3-Phase
HP
1/4 276A-10
1/3 276A-15
1/2 276A-15 276A-10 3/4 276A-20 276A-10 * *
1 276A-25 276A-15 276A-10
2 276A-35 276A-20 276A-10 * 3 276B-50 276A-25 276A-15 276A-10 5 276B-80 276A-40 276A-25 276A-15
10 276B-150 276B-75 276A-40 276A-20 15 276B-60 276A-30 20 276B-80 276A-40 25 276B-100 276B-50 30 276B-150 276B-60 40 276B-150 276B-75 50 276B-200 276B-100 60 276B-250 276B-150 75 276B-300 276B-150
120VAC 240VAC 240VAC 480VAC
* *
* *
* Direct connection to Model 276C (see page 8)
* * Direct connection to Model 422
B = 0.87”
*
*
*
3-PHASE INSTALLATION
The basic Model 422 Controller is designed for use with single-phase pump motors. However, it can easily be used in 3-phase applications by installing the current cancelling transformer, Model 276C. The Model 276C (figure 6) monitors two of the three phases, and cancels the effect of the current signal in the third phase, which would otherwise cause a phase shift error in the Model
422.
Figure 6. MODEL 276C
IMPORTANT NOTE:
In 3-phase applications, the current inputs must come from the same phases providing the voltage input. The applications schematics shown on the last page describe the interconnections.
INSTALLATION
Mount the Model 422 in the control panel or in a suitable enclosure. Connect the voltage and current inputs to the appropriate terminals on the Model 422 Monitor.
If the 4-20mA output is used, connect it across a 300 resistive load. Set the four MODE switches on the Model 422 according to the chart below. During the initial setup you may wish to disable all time delays.
DIP SW MODE ON OFF
After the system is completely installed, a simple test and adjustment will insure that the polarity and threshold are correct.
1
2
3
4
Overload Restart Disabled Enabled
Restart Delay Enabled Disabled
Reset Button Enabled Disabled
Trip Delay Enabled Disabled
Page 4 of 8 11/2011
© 2011 TIME MARK CORPORATION
TIME MARK is a division of
MODEL 422
Submersible Pump Controller
READ ALL INSTRUCTIONS BEFORE INSTALLING, OPERATING OR SERVICING THIS DEVICE.
KEEP THIS DATA SHEET FOR FUTURE REFERENCE.
GENERAL SAFETY
POTENTIALLY HAZARDOUS VOLTAGES ARE PRESENT AT THE TERMINALS OF THE MODEL 422.
ALL ELECTRICAL POWER SHOULD BE REMOVED WHEN CONNECTING OR DISCONNECTING WIRING.
THIS DEVICE SHOULD BE INSTALLED AND SERVICED BY QUALIFIED PERSONNEL.
INSTALLATION INSTRUCTIONS
ADJUSTMENT
Connect a temporary jumper across the NO contacts on the Model 422 (this keeps the motor running as the Model 422 trips off and resets).
With the correct voltage applied to the system, the motor should start and run continuously. Make sure the motor is running under its normally loaded condition.
With a clamp-type ammeter, measure the current in one of the wires connected to the CT terminals on the Model
422. A reading between 2 and 3.5 amps should be
measured for best results. This current level can be changed by exchanging the CT with a different ratio.
Turn the UNDER adjustment through its entire range and find the spot where the UNDERLOAD LED just illuminates.
Turn the UNDER adjustment until the LED just goes out. If the UNDERLOAD LED is lit all the time, reverse the two wires connected to the CT terminals and re­adjust.
Repeat this procedure for the OVER adjustment. If the OVERLOAD indicator LED stays on all the time, the current input may be incorrect. Check the CTs for proper sizing.
Set the SECONDS adjustment for the appropriate TRIP delay, and HOURS adjustment for the appropriate RESTART delay, as required for the application.
Remove the jumper from the NO contacts; the motor should continue to run. The adjustment is now complete.
TROUBLESHOOTING
Should the Model 422 Submersible Pump Controller fail to operate, check all connections to the device and its control circuits. Insure that the proper voltage and currents have been applied.
Check all fuses. Should the Model 422 operate improperly, check that the CT is properly sized. Check all DIP switch settings. If problems persist, contact the factory for technical assistance.
OPERATION
When AC voltage is first applied, the output transfers for approximately two seconds, completing the motor control circuit and allowing the motor to come up to speed.
If the power being used is within acceptable limits the contacts remain energized and the motor continues to run. If the power drops or rises outside the limits, the contacts will open.
WARRANTY
This product is warranted to be free from defects in materials and workmanship for one year. Should this device fail to operate, we will repair it for one year from the date of manufacture. For complete warranty details, see the Terms and Conditions of Sales page in the front section of the Time Mark catalog or contact Time Mark at 1-800-862-2875.
Page 5 of 8 11/2011
© 2011 TIME MARK CORPORATION
MOTOR
4-20mA
OUTPUT
REVERSE WIRES TO CT IF MOTOR FAILS TO RUN FOR MORE THAN THE INITIAL 2 SECOND PERIOD.
MODEL 276A-xx
L1
L2
MANUAL
RESTART
120VAC COIL
MOTOR
4-20mA OUTPUT
REVERSE WIRES TO CT IF MOTOR FAILS TO RUN FOR MORE THAN THE INITIAL 2 SECOND PERIOD.
MODEL 276B-xx
L1
L2
MANUAL
RESTART
240VAC COIL
TIME MARK is a division of
MODEL 422
Submersible Pump Controller
TYPICAL APPLICATIONS
SINGLE-PHASE, 120V, <3 HP
SINGLE-PHASE, 240V, 7.5 HP
Shows No Power Applied
Shows No Power Applied
Page 6 of 8 11/2011
© 2011 TIME MARK CORPORATION
4-20mA OUTPUT
REVERSE WIRES TO CT IF MOTOR FAILS TO RUN FOR MORE THAN THE INITIAL 2 SECOND PERIOD.
M
O
D
E
L
2
7
6
C
L1
L2
MANUAL
RESTART
240VAC COIL
OBSERVE POLARITY
AS SHOWN
USE MODEL 276A-xx
MOTOR
L3
TIME MARK is a division of
MOTOR
4-20mA OUTPUT
REVERSE WIRES TO CT IF MOTOR FAILS TO RUN FOR MORE THAN THE INITIAL 2 SECOND PERIOD.
L1
L2
MANUAL
RESTART
240VAC COIL
MODEL 276A-xx
MODEL 422
Submersible Pump Controller
TYPICAL APPLICATIONS
SINGLE-PHASE, 240V, 1/2 TO 5 HP
3-PHASE, 240V, 1 TO 10 HP
Shows No Power Applied
Shows No Power Applied
Page 7 of 8 11/2011
© 2011 TIME MARK CORPORATION
4-20mA OUTPUT
REVERSE WIRES TO CT IF MOTOR FAILS TO RUN FOR MORE THAN THE INITIAL 2 SECOND PERIOD.
M
O
D
E
L
2
7
6
C
MANUAL
RESTART
120VAC COIL
MOTOR
OBSERVE POLARITY
AS SHOWN
USE MODEL 276B-xx
120VAC
480VAC
T
I
M
E
M
A
R
K
3
-
P
H
A
S
E
M
O
N
I
T
O
R
L1
L3
L2
4-20mA OUTPUT
REVERSE WIRES TO CT IF MOTOR FAILS TO RUN FOR MORE THAN THE INITIAL 2 SECOND PERIOD.
M
O
D
E
L
2
7
6
C
L1
L2
MANUAL
RESTART
240VAC COIL
OBSERVE POLARITY
AS SHOWN
MOTOR
L3
TIME MARK is a division of
MODEL 422
Submersible Pump Controller
TYPICAL APPLICATIONS
Over/Under Load & Phase Loss Protection
3-PHASE, 240V, <1 HP
THE INFORMATION PRESENTED IN THIS GUIDE IS CORRECT TO THE BEST OF OUR KNOWLEDGE. HOWEVER, TIME MARK CORPORATION DOES NOT WARRANT THE APPLICATIONS AS OUTLINED NOR MAKE ANY OFFERS THAT THE CIRCUITS ARE FREE FROM PATENT INFRINGEMENT. TIME MARK CORPORATION RESERVES THE RIGHT TO CHANGE OR ALTER SPECIFICATIONS AT ANY TIME.
Shows No Power Applied
Shows No Power Applied
Page 8 of 8 11/2011
© 2011 TIME MARK CORPORATION
Loading...