Time Mark 409 Data Sheet

MODEL 409
Liquid Level
Controller
Automatic control of liquid level
Solid-state sensing circuit
Adjustable sensitivity
5-Year Unconditional Warranty
DESCRIPTION
The Model 409 is a compact, socket-mount device for level control of conductive liquids. The internal relay is energized when operating power is applied. When the liquid level reaches the probe, the relay de-energizes. When the level drops below the probe, the relay will reset. A fixed, two second time delay prevents oscilla­tion due to wave action. Probe cables may be shielded or unshielded. If the liquid container is made of a non­conductive material, a common electrode is required. Other features include an LED indicator to show the output relay status and an adjustable sensitivity setting. Requires standard 8-pin octal socket (socket number 51X00120-01).
DIMENSIONS
SPECIFICATIONS
Model 409
Operating voltages 24VAC: 20-30VAC, 50-400Hz
120VAC: 90-140VAC, 50-400Hz 230VAC: 200-250VAC, 50-400Hz
Power consumption 2.5W
Transient Protection 2500VRMS for 10ms
Probe voltage (open circuit) 15VRMS
Probe current 5mA maximum
Sensitivity adjust 1K ohms-100K ohms
Contacts SPDT
Contact Rating 10A @ 240VAC resistive
Expected Relay Life Mech: 10,000,000 operations
Elec: 100,000 at rated load
Response Time 2 seconds
Reset Time <1 second
Reset Method Automatic
Time delay accuracy ±5%
Operating Temp -13º to +140º F
Humidity Tolerance 0-97% w/o condensation
Case Material ABS plastic
Weight 6.2 oz. Max.
(dimensions have a tolerance of ±0.06)
© 2013
TIME MARK is a division of
TIME MARK CORPORATION
MODEL 409
Liquid Level Controller
READ ALL INSTRUCTIONS BEFORE INSTALLING, OPERATING OR SERVICING THIS DEVICE.
KEEP THIS DATA SHEET FOR FUTURE REFERENCE.
GENERAL SAFETY
POTENTIALLY HAZARDOUS VOLTAGES ARE PRESENT AT THE TERMINALS OF THE MODEL 409.
ALL ELECTRICAL POWER SHOULD BE REMOVED WHEN CONNECTING OR DISCONNECTING WIRING.
THIS DEVICE SHOULD BE INSTALLED AND SERVICED BY QUALIFIED PERSONNEL.
Installation Instructions
INSTALLATION
Mount the 8-pin socket in a suitable enclosure. A NEMA-1 rated enclosure, designed for socket-mounted relays, is available from Time Mark (part no. 98A498).
Referring to the pin diagram on this page or on the unit connect appropriate AC operating power. Connect the probes as needed, and connect the output relay as appropriate.
ADJUSTMENT
Adjust the sensitivity as needed.
TYPICAL APPLICATION
WARRANTY
This product is warranted to be free from defects in materials and workmanship, and is covered by our exclusive 5-year Unconditional Warranty. Should this device fail to operate for any reason, we will repair it for five years from the date of manufacture. For complete warranty details, see the Terms and Conditions of Sales page in the front section of the Time Mark catalog or contact Time Mark at 1-800-862-2875.
© 2013
TIME MARK is a division of
11/2013
TIME MARK CORPORATION
Loading...