Liquid Level
Controller
Level simulator control
2 scalable 4-20mA outputs
Output voltage for probe supply
8 adjustable setpoints with relay outputs
LCD level display with zero and span adjustments
DESCRIPTION
The Model 4082 Liquid Level Controller monitors, displays and controls water level up to 34.6 feet, in a tank or reservoir.
The Model 4082 operates from the 4-20mA input signal provided by either the Time Mark Model 450 or Model 456-15 Pressure Transducer. This 4-20mA signal represents the water level to be controlled, where 4mA equals zero feet, and 20mA equals 34.6 feet. A liquid crystal display (LCD) is provided to show the water level during normal operation, and the setpoint values during calibration.
There are eight user-adjustable trip setpoints. As the water level rises above each trip point setting, the front panel LED for that level illuminates, and the corresponding output relay energizes.
Two 4-20mA outputs, which track the 4-20mA input, are also provided. These signal outputs can be re-scaled to different ranges of level by the user. A test control, that simulates an input signal, is available on the front panel. The test control is useful for checking the trip setpoints, and overall system operation.
DIMENSIONS
SPECIFICATIONS
MODEL 4082
Input voltage 120VAC, ± 10% 50/60Hz
Power consumption 6W maximum
Signal input
Signal input load
Dead band 1% of full scale
Repeat accuracy ± 1% of scaled maximum (fixed conditions)
Display type 3-1/2 digit liquid crystal display
Display range
Display resolution 1 decimal place (factory set; user-adjustable)
Contacts 8 SPDT
Contact rating 10A at 240VAC resistive
Signal output Output is factory set to track the 4-20mA input.
Signal output load
Probe supply voltage 24VDC regulated
Trip levels 8 setpoints, user-adjustable
Operating temperature +14º to +122º F
Humidity tolerance 0-97% w/o condensation
Enclosure material front panel - 16 gauge steel
Termination removable terminal strips
Weight
Agency Approvals UL Recognized (U.S. & Canadian)
4-20mA (optional 0-5v), 2 or 3 wire
250 maximum
00.0 to 34.6 w/4-20mA input
(factory set; user-adjustable)
4A at 120VAC inductive
zero and span adjustments are provided:
as little as a 2mA change can cause a full swing of the output
300 maximum
rear panel - 20 gauge steel
5.5 pounds
Page 1 of 6 11/2011
© 2011 TIME MARK CORPORATION
C
E
D
G
A
H
F
E
D
C
TIME MARK
CORPORATION
INPUT LEVEL
SETPOINT 1 SETPOINT 2 SETPOINT 3 SETPOINT 4
INPUT LEVEL
INPUT LEVEL SETPOINT 8 SETPOINT 7 SETPOINT 6 SETPOINT 5 INPUT LEVEL
PUSH
MIN
1
5
ZERO
ZERO
SPAN
SPAN
ZERO
SPAN
SETPOINTS
SETPOINTS
DISPLAY SELECT
M ODEL 40 82
LIQUID LEVEL CONTROLLER
4-20ma
OUTPUT
AUX 4-20 ma
OUTPUT
LIQUID LEVEL (
FEET
)
2
6
3
7
4
8
LEVEL
SIMULATOR
MAX
MADE I N
USA
B
TIME MARK is a division of
1 2 3 4 5 6 7 8
MODEL 4082
Liquid Level Controller
READ ALL INSTRUCTIONS BEFORE INSTALLING, OPERATING OR SERVICING THIS DEVICE.
KEEP THIS DATA SHEET FOR FUTURE REFERENCE.
POTENTIALLY HAZARDOUS VOLTAGES ARE PRESENT AT THE TERMINALS OF THE MODEL 4082.
ALL ELECTRICAL POWER SHOULD BE REMOVED WHEN CONNECTING OR DISCONNECTING WIRING.
DO NOT EXCEED THE OUTPUT OR INPUT RATINGS, AS STATED IN THE SPECIFICATIONS.
PROTECT THE UNIT WITH PROPERLY RATED FUSES.
DO NOT INSTALL IN DAMP OR MOIST AREAS.
THIS DEVICE SHOULD BE INSTALLED AND SERVICED BY QUALIFIED PERSONNEL.
GENERAL SAFETY
Installation Instructions
Front Panel Controls
figure 1
TYPICAL APPLICATION
3-1/2 DIGIT LCD INDICATOR - SHOWS LIQUID LEVEL IN FEET
A
ZERO AND SPAN ADJUSTMENTS FOR THE DISPLAY
B
ZERO AND SPAN ADJUSTMENTS FOR 4-20MA OUTPUT
C
SIGNAL
INDICATOR LEDs - SHOW WHEN SETPOINT IS REACHED
D
(ONE PER SETPOINT)
SETPOINT ADJUSTMENT POTENTIOMETERS
E
DISPLAY SELECT SWITCH - USED TO DISPLAY LIQUID LEVEL
F
OR TRIP POINT SETTINGS
PUSH BUTTON - ENABLES SIMULATED LEVEL CHANGE
G
SIMULATES LIQUID LEVEL CHANGE (WITH OR WITHOUT
H
INPUT SIGNAL) WHEN BUTTON G IS PRESSED. THE 4-20MA OUTPUT IS ALSO AFFECTED.
Warranty
This product is warranted to be free from defects in materials and workmanship for one year. Should this device fail to operate, we will repair it for one year from the date of manufacture. For complete warranty details, see the Terms and Conditions of Sales page in the front section of the Time Mark catalog or contact Time Mark at 1-800-862-2875.