The Model 404 Liquid Level Sensor operates in conjunction with a Model 403 Controller for bubbler-type duplex pumping systems. The 404 contains an air pressureto-voltage transducer and requires only a small compressor capable of 15 psi (pounds per square inch) to operate
the system down to approximately 35 feet.
The Model 404’s four outputs are designed to replace the
float switch inputs to a Model 403, or to be used with a
Model 448 Output Relay Board. A 4-20mA signal output
provides for other control applications.
A 3-digit LED display continuously shows the liquid level
to a tenth of a foot when the Display Control switch is in
the Liquid Level position. Other settings of the switch allow setting of the liquid level trip points. LED Indicators
illuminate as the levels are exceeded. A test control allows
the trip settings to be checked without actually raising or
lowering the liquid level.
DIMENSIONS
SPECIFICATIONS
MODEL 404-24V 404-115V
Input voltage 20-28VAC 105-130VAC
Input frequency 47-65Hz
Power consumption 2W
Air pressure input 0-15 psi max.
Input air supply fitting Requires 3/16” I.D. tubing
Maximum liquid level
displayed
Calibration accuracy ± 2%
Repeat accuracy
(fixed condition)
Repeat accuracy
(0-60º C)
Dead band 0.1 foot
Switching outputs 4 open-collector transistors rated for regulated
12VDC, 10mA, maximum. Designed as inputs
for the Model 403 Liquid Level Controller or
Model 448 Output Relay Board
Signal outputs 4-20mA output proportional to 0-34.6 feet of water
READ ALL INSTRUCTIONS BEFORE INSTALLING, OPERATING OR SERVICING THIS DEVICE.
KEEP THIS DATA SHEET FOR FUTURE REFERENCE.
POTENTIALLY HAZARDOUS VOLTAGES ARE PRESENT AT THE TERMINALS OF THE MODEL 404.
ALL ELECTRICAL POWER SHOULD BE REMOVED WHEN CONNECTING OR DISCONNECTING WIRING.
DO NOT EXCEED THE OUTPUT OR INPUT RATINGS, AS STATED IN THE SPECIFICATIONS.
PROTECT THE UNIT WITH PROPERLY RATED FUSES.
DO NOT INSTALL IN DAMP OR MOIST AREAS.
THIS DEVICE SHOULD BE INSTALLED AND SERVICED BY QUALIFIED PERSONNEL.
GENERAL SAFETY
Installation Instructions
INSTALLATION
Mount the Sensor in a suitable enclosure. If a Model 448
relay module is being used, mount it in a suitable location near the Sensor.
Referring to the terminal block decal on the sensor and
the illustration on this page, make the following connections
1. Connect a chassis ground to the terminals marked
CHS GND.
2. Connect operating power (24 or 120VAC) to the terminals marked for input voltage.
3. Observing polarity, connect the LOW terminals to the
LOW terminals on the 403. For connections to 448,
refer to connection chart on page 4.
4. Repeat step 3 for the LEAD, LAG, and HIGH terminals.
5. The terminals marked LIQUID LEVEL are the 420mA output. If used, connect these terminals to the
appropriate control circuitry. Observe polarity.
Connect a 3/16” I.D. tubing to the air supply fitting on the
back of the 404. Connect the other end of the tubing to
the air compressor and the tank or well .Apply operating
power and proceed to the adjustment procedure.
A. Display control switch used to select liquid level or
level setting.
B. 3-Digit LED indicator reads depth in feet.
C. Test switch enables simulated level change by
rotating control D.
D. Simulates liquid level change when switch C is
pressed.
E. Indicator LED shows when level is reached (one
per level)
F. Coarse adjustment for setting level trip point (one
per level)
G. Fine adjustment for setting level trip point (one per
level)
ADJUSTMENT
1. The trip points are set using coarse and fine
adjustment pots; the results are shown on the LED
display. To adjust the device, set the display control
knob (A) to LOW and adjust the low level coarse
adjustment (F) to the approximate desired level. A fine
adjustment (G) is located below the coarse adjustment.
The trip level will be shown on the LED display (B).
2. Repeat step 1 for the lead, lag and high level
adjustments.
3. Set the display control knob to the LIQUID LEVEL
position. The Sensor is now ready to operate.
TESTING
For testing purposes a test switch (C) and LO_HI
adjustment (D) are provided. Set the adjustment to LO,
then press and hold the test switch. As the adjustment
is turned clockwise (HI), the LED display will show an
increasing simulated liquid depth. As each level is
reached the appropriate LED indicator (E) will illuminate
and the output should activate (pump will turn on,
output relay will energize, or alarm will sound).
TROUBLESHOOTING
Problem: Erratic and/or unstable operation when
used with 403.
Cause: Signal ground wire between the two units is
not connected.
Solution: Connect signal ground.
Problem: In test position, display reads other than
zero with adjustment fully counterclockwise
Cause: This is a normal condition; fully counterclockwise on the adjustment may be
below zero.
Solution: Turn the adjustment slightly clockwise; the
display should read zero (or higher).
Note: This device is not a field repairable unit. Should the unit not
operate properly during installation or testing, insure that all electrical,
ground, and physical connections are correct. Verify that the proper
voltage is applied and check all fuses. Contact the factory if
everything is correct and the device still fails to operate. Should the
sensor fail during use, contact the factory for instructions on returning
the device for repair.
WARRANTY
This product is warranted to be free from defects in materials
and workmanship for one year. Should this device fail to
operate, we will repair it for one year from the date of
manufacture. For complete warranty details, see the Terms and Conditions of Sales page in the front section of the Time
Mark catalog or contact Time Mark at 1-800-862-2875.