Time Mark 2780 Data Sheet

3.25"
1.95"
1.95"
MODEL 2780
TIME MARK is a division of
AC Current Transducer
High accuracy, low cost
Isolated input and output
Socket-mounted, solid-state design
0 - 10VDC Output
Five year unconditional warranty
SPECIFICATIONS
DESCRIPTION
The Model 2780 AC Current Transducer is designed to accept an AC current input, and provide a proportional DC voltage output. A linear transformer input is coupled to a solid-state output amplifier. The Model 2780 is powered by a 115VAC or 230VAC source, and is socket-mounted for ease of use.
Model 2780 Current Transducers can be used with computer and programmable controls to provide:
- Motor and power control
- Supervisory data acquisition
- Load monitoring
- Feedback control
- Energy management
DIMENSIONS
MODEL 2780-115 2780-230
Supply voltage 115VAC @ 50/60Hz 230VAC @ 50/60Hz
Input current 0-5 amps
Input frequencies 25-400Hz
Input burden 0.5VA at 120VAC 60Hz
Output @ rated input 0 - 10VDC
Maximum load 500 ohms
Output accuracy 2% at 77°F
Output ripple 1% max at nominal frequency
Response time 800ms from 0-99%
Overload withstand 2 times rated output-continuous
Dielectric withstand voltage (isolation)
Operating temperature -20° to +131°F
Humidity tolerance 0-97% w/o condensation
Enclosure material ABS plastic
Mounting 8-pin socket (*order separately)
Weight 9.5 oz.
Agency Approvals UL Recognized-US/Canada
*Order 8-pin socket number 51X120
10 times rated input-1 second
1500 VRMS input, output, case
11/2011
© 2011 TIME MARK CORPORATION
MODEL 2780
TIME MARK is a division of
AC Current Transducer
READ ALL INSTRUCTIONS BEFORE INSTALLING, OPERATING OR SERVICING THIS DEVICE.
KEEP THIS DATA SHEET FOR FUTURE REFERENCE.
GENERAL SAFETY
POTENTIALLY HAZARDOUS VOLTAGES ARE PRESENT AT THE TERMINALS OF THE MODEL 2780.
ALL ELECTRICAL POWER SHOULD BE REMOVED WHEN CONNECTING OR DISCONNECTING WIRING.
THIS DEVICE SHOULD BE INSTALLED AND SERVICED BY QUALIFIED PERSONNEL.
Installation Instructions
INSTALLATION
The Model 2780 AC Current Transducer requires an 8
-pin mounting socket, such as the Time Mark Model 51X120.
The base connecting diagram on the unit shows the pin connection numbers for the AC power, the AC Current input, and the DC Voltage Out.
Connect the appropriate wiring to the socket as required (See the Typical Application diagram).
PIN DRAWING
NOTE: When installing the Model 2780 Transducer in areas of high humidity or contamination, it is recommended that the base area and all exposed metal parts of the socket be coated liberally with a good quality silicone grease, such as Dow Corning DC-4 or DC-4X. Insert the unit into the socket and wipe off excess grease around the base. This will prevent the entrance of moisture and other contaminates into the base and socket areas.
TYPICAL APPLICATION
TROUBLESHOOTING
Should the Model 2780 AC Current Transducer fail to operate properly, check that all voltage is present, and is of the correct voltage level. Check all fuses and verify that all wiring connections are correct. If problems persist, contact your local Time Mark Distributor, or the factory for assistance, Monday- Friday, 8 a.m. to 5 p.m. CST.
WARRANTY
This product is warranted to be free from defects in materials and workmanship, and is covered by our exclusive 5-year Unconditional Warranty. Should this device fail to operate for any reason, we will repair it for five years from the date of manufacture. For complete warranty details, see the Terms and Conditions of Sales page in the front section of the Time Mark catalog or contact Time Mark at 1-800-862-2875.