Time Mark 2742 Data Sheet

A
RESET
UNDER
CURRENT
AC B
C
L1 L2 L3
Control Voltage
Lamp
Stop
Start
M
M
O/L's
MODEL 2742
3-Phase Over/Under
Current Monitor
Monitors over or under current Fail-safe design Automatic or manual reset Adjustable trip delay timer For use on motors, pumps, conveyors, etc.
Engineered and Built in the U.S.A.
DESCRIPTION
The Model 2742 3-Phase Over/Under Current Monitor is designed to monitor the current level of a three-phase line or to compare the currents of three single-phase lines.
The Model 2742 is factory-set as an over-current monitor; that
is, if one or more current inputs rises above the trip level, the
internal relay will de-energize. Adding a wire between the
UNDER CURRENT terminals on the case will cause the Model 2742 to sense a decrease of one or more current inputs.
An adjustable trip delay of 0.2 to 20 seconds will prevent nuisance tripping. The current trip point is adjustable from 1 to 5 amps, and matching current transformers are available to extend the current range of the monitor.
The Model 2742 will automatically reset when the current fault is corrected. An external manual reset can be added by installing a normally closed switch between the terminals
marked RESET.
TYPICAL APPLICATION Over-current; auto reset; 5 amps
SPECIFICATIONS
Model 2742-24 2742-115 2742-220
Supply voltage 20-28VAC 100-130VAC 190-250VAC Max supply voltage 30V 140V 260V
Power consumption 1.5 Watts max. Transient protection 2500 VRMS for 10ms Frequency range 50/60 Hz Input current 1-5 amps ±5% Max. input current 40 amps for 2 sec Current range 1-5 amps ± 5% Trip delay 0.2 to 20 sec ± 5%
Dead band 4% max. Contact rating DPDT 10A at 240VAC resistive Expected relay life
Operating temperature - 20º to +131º F Enclosure material ABS plastic Weight 1 lb. 5.9 oz.
Mech: 10 million operations Elec: 100,000 ops at rated load
DIMENSIONS
Shows No Power Applied
11440 Ea s t Pi ne S t re e t
Tu l s a , Ok l a h o m a 7 4 1 1 6
10/2020
© 2020 TIME MARK CORPORATION
C B A
AC
RST
Reset
MANUAL RESET
C
B
A
AC
Jumper
Connection
RST
UNDER-CURRENT SENSING
MODEL 2742
3-Phase Over/Under Current Monitor
READ ALL INSTRUCTIONS BEFORE INSTALLING, OPERATING OR SERVICING THIS DEVICE.
KEEP THIS DATA SHEET FOR FUTURE REFERENCE.
POTENTIALLY HAZARDOUS VOLTAGES ARE PRESENT AT THE TERMINALS OF THE MODEL 2742.
ALL ELECTRICAL POWER SHOULD BE REMOVED WHEN CONNECTING OR DISCONNECTING WIRING.
THIS DEVICE SHOULD BE INSTALLED AND SERVICED BY QUALIFIED PERSONNEL.
INSTALLATION
Mount the Model 2742 in a suitable enclosure.
If the current to be monitored is 5 amps or less, break and connect each wire to the three inputs of the Model 2742 (see TYPICAL APPLICATION on front page). Observe polarity.
If the current to be monitored is greater than 5 amps, install a current transformer on the line. Connect the secondary leads of the CT to the Model 2742 terminals (see TYPICAL APPLICATION on this page). Observe polarity.
Connect the operating supply voltage to the AC input terminals.
Connect the load control wiring to the appropriate terminals. For most motor control applications, use the normally open contact(s), which will close when the current is within the acceptable range. For alarm applications, use the normally
closed contact(s). Refer to the diagram on this page.
If a manual reset is desired, connect a normally closed push
-button across the RESET terminals (see figure 1). If under-
current sensing is desired, add a jumper connection (see
figure 2).
Turn on the supply voltage. The contacts should transfer and neither indicator light should be lit.
ADJUSTMENT PROCEDURE
Set the SECONDS adjustment to the required amount of delay. If the desired current trip level is known, set the CURRENT adjustment to that point. A slight adjustment up or down may be necessary to allow for tolerance inaccuracies.
NOTE: If the manual reset is used, press and hold the reset button during this step. Usually a trip is desired only if
the current changes from the present nominal. To calibrate for this turn the SECONDS adjustment to the maximum delay. Turn the CURRENT adjustment up or down until the FAULT indicator lights. Turn the CURRENT adjustment back, until the FAULT light just goes out. Reset the SECONDS delay to the previous setting.
GENERAL SAFETY
Installation Instructions
TYPICAL APPLICATION Over-current; auto reset; 5 amps
figure 1 figure 2
WARRANTY
This product is warranted to be free from defects in materials and workmanship for one year. Should this device fail to operate, we will repair it for one year from the date of manufacture. For complete warranty details, see the Terms and Conditions of Sales page in the front section of the Time
Mark catalog or contact Time Mark at 1-800-862-2875.
Shows No Power Applied
11440 Ea s t Pi ne S t re e t
Tu l s a , Ok l a h o m a 7 4 1 1 6
10/2020
© 2020 TIME MARK CORPORATION