Time Mark 272 Data Sheet

3.0"
5.5"
3.88"
.19 dia. typ.
6.06"
2.08"
.62"
MODEL 272
MAX CURRENT - MIN CURRENTMAX CURRENTMAX CURRENT
MAX CURRENTMAX CURRENTMAX CURRENT
100 = %
TIME MARK is a division of
3-Phase Current
Unbalance Detector
Adjustable Trip Delay
Adjustable Unbalance Percentage
Automatic Reset
DESCRIPTION
The Model 272 3-Phase Current Unbalance Detector monitors 3-phase lines to detect an unbalanced current. It can also monitor three separate single phase lines for equal current levels.
The percentage of unbalance is adjustable from 2% to 25% by adjusting a front panel control. An unbalance greater than this setting energizes the relay. The formula for an unbalance is:
An adjustable trip delay of 0.5 to 10 seconds is also provided. For optimum performance, operating currents should be kept in the 1 to 5 amps range. However, zero current on each phase is considered to be a balanced condition.
Continuous currents, up to 10 amps per phase, will not damage the unit, nor will current surges up to 40 amps for 2 seconds. The contacts are automatically reset when the unbalanced condition is corrected.
A supply voltage of 24 or 120VAC is required for this unit.
SPECIFICATIONS
Model 272-24 272-120
Input Voltage 24VAC 115VAC
Input Voltage Range 20-28VAC 100-130VAC
Power Consumption
VA Burden
Frequency Range 50 - 400Hz
Current Range 1 - 5 amps AC
Max. Input Current 40 amps for 2 seconds
Unbalance Adjustment 2% to 25%
Trip Delay
Contact Rating SPDT 10A at 240VAC resistive
Expected Relay Life Mech: 10 million operations
Elec: 100,000 at rated load Transient Protection 2500V for 10ms
Operating Temperature - 2to +131° F
Humidity Tolerance 0-97% w/o condensation
Enclosure Material ABS plastic
Weight
1.5W
0.5 to 10 seconds ± 20%
1 lb. 1.5 oz.
DIMENSIONS
11/2011
© 2011 TIME MARK CORPORATION
Control voltage
Start
Stop
AC
A B C
Motor
O/L's
MODEL 272
TIME MARK is a division of
3-Phase Current Unbalance Detector
READ ALL INSTRUCTIONS BEFORE INSTALLING, OPERATING OR SERVICING THIS DEVICE.
KEEP THIS DATA SHEET FOR FUTURE REFERENCE.
GENERAL SAFETY
POTENTIALLY HAZARDOUS VOLTAGES ARE PRESENT AT THE TERMINALS OF THE MODEL 272.
ALL ELECTRICAL POWER SHOULD BE REMOVED WHEN CONNECTING OR DISCONNECTING WIRING.
THIS DEVICE SHOULD BE INSTALLED AND SERVICED BY QUALIFIED PERSONNEL.
Installation Instructions
INSTALLATION
Mount the Model 272 in a suitable enclosure.
Connect AC operating power to the appropriate terminals.
Connect the normally closed (N.C.) relay contacts to the load control wiring.
Connect the 3-phase currents or CT outputs to the current input terminals marked A B C.
Set the PERCENT UNBALANCE and TRIP DELAY adjustments to the desired levels, and apply operating power.
TROUBLESHOOTING
Should the monitor fail to operate properly, check that all three currents are present and are of the correct level. Check all fuses and verify that all wiring connections are correct. Should problems persist, contact the factory at 800-862-2875 for assistance.
WARRANTY
This product is warranted to be free from defects in materials and workmanship for one year. Should this device fail to operate, we will repair it for one year from the date of manufacture. For complete warranty details, see the Terms and Conditions of Sales page in the front section of the Time Mark catalog or contact Time Mark at 1-800-862-2875.
TYPICAL APPLICATION
Shows No Power Applied
11/2011
© 2011 TIME MARK CORPORATION