Time Mark 269 Data Sheet

R
LISTED
MODEL 269
TIME MARK is a division of
Over & Under
3-Phase Monitor
Monitors for High Voltage, Low Voltage, Phase Loss & Phase Reversal
4 Voltage Ranges
Automatic Reset
5 Year Unconditional Warranty
DESCRIPTION
The Model 269 Over & Under 3-Phase Monitor continu­ously monitors 3-phase lines for high voltage, low voltage, phase loss or phase reversal. This device features a solid­state voltage and phase angle sensing circuit, which drives a SPDT output relay.
The Model 269 is independent of the system load, and may be used on any horsepower motor. When phase sequence is correct, and the voltage remains between the upper and lower trip points, the output relay remains energized. When a fault condition is sensed, the output relay drops out.
The Model 269 does not require a neutral connection, and can be used on Wye or Delta systems. Each of the four voltage versions can be adjusted over a wide range. An adjustable trip delay (1-10 seconds) prevents nuisance tripping. OVER and UNDER voltage failure indicators aid in calibration and system troubleshooting.
DIMENSIONS
SPECIFICATIONS
Model A269 B269 C269 EX269
Nominal AC Voltage (phase to phase)
Adj Range - Upper
- Lower
Frequency 60Hz 50Hz
Power Consumption
Transient Protection 2500VRMS for 10ms
Repeat Accuracy
Response Time Adjustable from 1-10 seconds ±5%
Reset Time
Reset Type Automatic
Dead Band Approximately 2%
Output Contacts SPDT 10A at 240VAC resistive
Expected Relay Life Mech: 10 million operations
Operating Temp - 2to +130º F Humidity Tolerance 0-97% w/o condensation Enclosure Material ABS Plastic Mounting Surface Weight 9 oz. Agency Approval UL Listed & CSA Certified
120VAC 208/240VAC 480VAC 380VAC
110 - 145V
80 - 115V
1.5W
Elec: 100,000 operations at rated load
210 - 280V 170 - 240V
3W 6W 6W
± 0.1% of set point (fixed conditions)
400 - 540V 380 - 460V
0.25 seconds
350 - 450V 300 - 400V
11/2011
© 2011 TIME MARK CORPORATION
MODEL 269
Motor
A B C
M
Start
Stop
Optional Alarm Indicator
Control Voltage
M
M
M
M
O/L's
Model 269
L1
L2
L3
TIME MARK is a division of
Over & Under 3-Phase Monitor
READ ALL INSTRUCTIONS BEFORE INSTALLING, OPERATING OR SERVICING THIS DEVICE.
KEEP THIS DATA SHEET FOR FUTURE REFERENCE.
GENERAL SAFETY
POTENTIALLY HAZARDOUS VOLTAGES ARE PRESENT AT THE TERMINALS OF THE MODEL 269 .
ALL ELECTRICAL POWER SHOULD BE REMOVED WHEN CONNECTING OR DISCONNECTING WIRING.
THIS DEVICE SHOULD BE INSTALLED AND SERVICED BY QUALIFIED PERSONNEL.
Installation Instructions
WARNING
THE MODEL 269 IS NOT TO BE USED IN APPLICATIONS WHERE VOLTAGES TO BE MONITORED OR SWITCHED WILL EXCEED VOLTAGE SPECIFICATIONS FOR THE PARTICULAR UNIT. SEE ‘ADJUST-MENT RANGE’ IN THE TABLE ON THE REVERSE SIDE OF THIS DATA SHEET.
INSTALLATION
Connect 3-phase wiring to the terminals marked A, B and C.
Connect the control wires to the terminals with the relay contact markings. The markings shown are in a TRIPPED condition.
Apply power. If the indicator lights are ON, and the contacts do not transfer when power is applied, check that all three phases are present and of the correct voltage. If all phases are correct, rotate the UNDER VOLTS adjustment fully counter-clockwise, and the OVER VOLTS adjustment fully clockwise.
If the contacts still do not transfer, remove power from the unit, and reverse two of the three input wires. Re-apply power. The contacts should then transfer (LED-off).
ADJUSTMENT
Turn the DELAY SECONDS trip delay adjustment counter­clockwise.
Rotate the UNDER VOLTS adjustment slowly clockwise until the contacts transfer to a tripped condition (LED-on).
Slowly turn the UNDER VOLTS adjustment back counter­clockwise until the contacts reset to the normal condition (LED-off).
Rotate the OVER VOLTS adjustment counter-clockwise until the contacts trip (LED-on).
Slowly turn the OVER VOLTS adjustment back clockwise until the contacts reset to the normal condition (LED-off).
These settings will be correct for most installations.
Set the SECONDS delay adjustment to the desired amount of trip delay. This delay will help prevent nuisance tripping.
Should nuisance tripping still occur, turn the OVER VOLTS, and UNDER VOLTS adjustments slightly farther.
NOTE: In eliminating nuisance tripping, the voltage ad­justments should be rotated in very small increments, until the true nuisance trips no longer occur.
TYPICAL APPLICATION
Shows No Power Applied
TROUBLESHOOTING
Should the Model 269 fail to operate properly, check that all three voltages are present, and are of the correct level. Check all fuses, and verify that all wiring connections are correct. Should problems persist, contact your local Time Mark Distributor, or the factory for further assistance.
WARRANTY
This product is warranted to be free from defects in materials and workmanship, and is covered by our exclusive 5-year Unconditional Warranty. Should this device fail to operate for any reason, we will repair it for five years from the date of manufacture. For complete warranty details, see the Terms and Conditions of Sales page in the front section of the Time Mark catalog or contact Time Mark at 1-800-862-2875.
11/2011
© 2011 TIME MARK CORPORATION