Time Mark 2642 Data Sheet

MODEL 2642
TIME MARK is a division of
4.5"
4.8"
4.0"
4.5"
3.5"
2.25"
2.25"
3.13"
3-Phase Monitor
Detects Phase Loss, Low Voltage and Phase Reversal
Adjustable Trip Delay
Automatic or Manual Reset
DPDT Output Contacts
DESCRIPTION
The Model 2642 3-Phase Monitor protects electrical equipment by sensing phase loss, low voltage and reverse phase conditions. This device uses a combination of voltage and phase angle sensing, and will detect a phase loss even when regenerated voltages are present.
The Model 2642 is fail-safe; the output contacts will transfer when correct power is applied, and trip out on any fault condition or complete loss of power. Each of five voltage versions can be adjusted throughout a wide operating range. An adjustable trip delay timer prevents nuisance tripping caused by momentary voltage dips.
The DPDT output contacts allow the Model 2642 to be used in control circuits and alarm circuits. The auto­matic reset can be converted to a manual reset by adding a normally closed switch.
DIMENSIONS
SPECIFICATIONS
MODEL A2642 B2642 C2642 D2642 EX2642
Nominal AC Voltage (phase to phase)
Adjustment Range 85-125V 160-260V 380-500V 450-600V 300-400V
Frequency 60Hz 60Hz 60Hz 60Hz 50Hz
Transient Protection 2500 VRMS for 10ms
Repeat Accuracy
Response Time
Reset Time
Dead Band Approximately 2%
Output Contacts DPDT 10 amps at 240VAC resistive
Expected Relay Life Mech: 10 million operations
Operating Temp - 2to +131° F
Humidity Tolerance 0 - 97% w/o condensation
Enclosure Material ABS plastic
Mounting Surface
Weight 12 oz.
Agency Approvals UL Recognized; CSA Certified
120VAC 208/240VAC 480VAC 575VAC 380VAC
0.25W 0.5W 1.5W 2.5W
Elec: 100,000 operations at rated load
1.5W
± 0.5% of setpoint (fixed conditions)
Adjustable 0.2 to 10 seconds ±5%
0.15 seconds
11/2011
© 2011 TIME MARK CORPORATION
Alarm (optional)
M M
Motor
M
L1 L2 L3
Control
Voltage
Alarm
Circuit
O/L
M
A BC
Model 2642
RESET
Manual Reset (omit for auto reset)
Shown with no power applied
MODEL 2642
TIME MARK is a division of
3-Phase Monitor
READ ALL INSTRUCTIONS BEFORE INSTALLING, OPERATING OR SERVICING THIS DEVICE.
KEEP THIS DATA SHEET FOR FUTURE REFERENCE.
GENERAL SAFETY
POTENTIALLY HAZARDOUS VOLTAGES ARE PRESENT AT THE TERMINALS OF THE MODEL 2642.
ALL ELECTRICAL POWER SHOULD BE REMOVED WHEN CONNECTING OR DISCONNECTING WIRING.
THIS DEVICE SHOULD BE INSTALLED AND SERVICED BY QUALIFIED PERSONNEL.
Installation Instructions
INSTALLATION
Turn both adjustment control potentiometers fully counter­clockwise.
Connect the 3-phase wires to the terminals marked A, B and C.
Connect the control wires to one set of the terminals with the relay contact markings. The contact markings on the unit are the failed or tripped condition of the contacts. The second set of output terminals can be used in an alarm circuit or in the control circuit of a second load. Refer to the TYPICAL APPLICATION drawing.
As provided, the Model 2642 has an Automatic Reset. If you prefer a Manual Reset, install a normally-closed push button across the terminals marked RESET. The Manual Reset leads should be kept as short as possible.
Apply power. If the contacts do not transfer when power is applied (TRIPPED indicator off; NORMAL indicator on), check that all three phases are present and of the correct voltage.
If all phases are correct, remove power from the unit, reverse any two of the A, B or C terminal wires (phase rotation is reversed), and re-apply power. The contacts should then transfer.
ADJUSTMENT
NOTE: When adjusting the Model 2642 you may wish to jumper the control circuit contacts (& disconnect the alarm contacts, if used) to prevent the unit from cycling the load.
Rotate the VOLTAGE ADJUST pot clock-wise until the unit trips (NORMAL indicator off, TRIP indicator on).
Slowly turn the VOLTAGE ADJUST pot counter-clockwise until the unit resets (TRIP indicator off; NORMAL indicator on).
Set the TRIP DELAY adjustment to the desired amount of delay to prevent nuisance trips.
These adjustment settings will be correct for most applications. Should nuisance trips occur, even with the TRIP DELAY set, turn the VOLTAGE ADJUST pot slightly farther counter-clockwise. Any adjustments should be made in very small increments.
TYPICAL APPLICATION
Shows No Power Applied
WARRANTY
This product is warranted to be free from defects in materials and workmanship, and is covered by our exclusive 5-year Unconditional Warranty. Should this device fail to operate for any reason, we will repair it for five years from the date of manufacture. For complete warranty details, see the Terms and Conditions of Sales page in the front section of the Time Mark catalog or contact Time Mark at 1-800-862-2875.
11/2011
© 2011 TIME MARK CORPORATION
Loading...