![](/html/75/7515/751537cd3c17560cdbfc6f04df12136dd10c3d659fa9819a5168e7932313fd26/bg1.png)
MODEL 261XBXP (R)
TIME MARK is a division of
Alternating Relay
Solid-State Reliability
Socket-Mounted
Heavy-Duty Contact Ratings
DESCRIPTION
The Model 261XBXP(R) Alternating Relays use the
same solid-state latching and control circuit as all the other
261series models, the enclosure and the connecting base
being the major differences.
This version was designed to replace a long time and
widely used mechanical latching relay offered by another
manufacturer. The modern circuitry used in the Model
261XBXP(R) offers a vast improvement in reliability and
useful life over the mechanical type. The XBXP version of
the relay requires closing the control switch to begin
alternation, and the XBXPR version requires opening the
control switch to begin alternation.
Replacement of the original mechanical alternator with the
Model 261XBXP(R) requires the addition of one wire from
L1 to Pin 5 of the connector, in order to supply continuous
power to the solid-state circuit.
Either of these units is available in two voltage versions for
use with 24 VAC/DC or 120 VAC/DC.
DIMENSIONS
SPECIFICATIONS
MODEL 261XBXP-24
Supply Voltage 24V AC/DC 120V AC/DC
Voltage Range 20 - 28V 90 - 130V
Max Voltage 30V 140V
Supply Current
Control Current
Operating Duty Continuous
Minimum Cycle Time 100ms
Contacts 10A at 240VAC resistive
Expected Relay Life
Operating Temperature -20° to +140° F
Humidity 0 - 97% w/o condensation
Mounting 12-pin socket *
Enclosure Material ABS plastic
Weight
261XBXPR-24
0.05A 0.01A
0.001A
Mech: 10 million operations
Elec: 100,000 at rated load
4.8 oz.
* order 12-pin socket number 51X156
261XBXP-120
261XBXPR-120
12/2012
© 2012 TIME MARK CORPORATION
![](/html/75/7515/751537cd3c17560cdbfc6f04df12136dd10c3d659fa9819a5168e7932313fd26/bg2.png)
MODEL 261XBXP (R)
TIME MARK is a division of
Alternating Relay
READ ALL INSTRUCTIONS BEFORE INSTALLING, OPERATING OR SERVICING THIS DEVICE.
KEEP THIS DATA SHEET FOR FUTURE REFERENCE.
GENERAL SAFETY
POTENTIALLY HAZARDOUS VOLTAGES ARE PRESENT AT THE TERMINALS OF THE MODEL 261XBXP(R).
ALL ELECTRICAL POWER SHOULD BE REMOVED WHEN CONNECTING OR DISCONNECTING WIRING.
THIS DEVICE SHOULD BE INSTALLED AND SERVICED BY QUALIFIED PERSONNEL.
Installation Instructions
INSTALLATION
Connect wiring to the socket as indicated in the
following examples.
The Model 261XBXP(R) Alternating Relay is extremely
versatile and can be used in many other configurations
besides those shown. Any type of switch (float,
pressure, etc.) can be used as the control switch;
however, it must be connected as shown (from L1 to the
control input) or the alternator will not function properly.
NOTE: When installing the Model 261XBXP(R) in areas
of high humidity or contamination, it is recommended
that the base area and all exposed metal parts of the
socket be coated liberally with a good quality silicone
grease, such as Dow Corning DC-4 or DC-4X. Insert
the unit into the socket and wipe off excess grease
around the base. This will prevent the entrance of
moisture and other contaminants into the base and
socket area.
PIN DIAGRAM
TYPICAL APPLICATION
TROUBLESHOOTING
Should the unit fail to operate properly, check to see that
all voltage levels are present and are of the correct level.
Verify that all connections are correct and securely
attached to equipment. Should problems persist, contact
the manufacturer at 800-862-2875 for assistance.
WARRANTY
This product is warranted to be free from defects in
materials and workmanship, and is covered by our
exclusive 5-year Unconditional Warranty. Should this
device fail to operate for any reason, we will repair it for
five years from the date of manufacture. For complete
warranty details, see the Terms and Conditions of Sales
page in the front section of the Time Mark catalog or
contact Time Mark at 1-800-862-2875.
12/2012
© 2012 TIME MARK CORPORATION