Time Mark 261XBXP Data Sheet

3.55"
1.75"
2.44"
MODEL 261XBXP (R)
TIME MARK is a division of
Alternating Relay
Solid-State Reliability
Socket-Mounted
Heavy-Duty Contact Ratings
DESCRIPTION
The Model 261XBXP(R) Alternating Relays use the same solid-state latching and control circuit as all the other 261series models, the enclosure and the connecting base being the major differences.
This version was designed to replace a long time and widely used mechanical latching relay offered by another manufacturer. The modern circuitry used in the Model 261XBXP(R) offers a vast improvement in reliability and useful life over the mechanical type. The XBXP version of the relay requires closing the control switch to begin alternation, and the XBXPR version requires opening the control switch to begin alternation.
Replacement of the original mechanical alternator with the Model 261XBXP(R) requires the addition of one wire from L1 to Pin 5 of the connector, in order to supply continuous power to the solid-state circuit.
Either of these units is available in two voltage versions for use with 24 VAC/DC or 120 VAC/DC.
DIMENSIONS
SPECIFICATIONS
MODEL 261XBXP-24
Supply Voltage 24V AC/DC 120V AC/DC
Voltage Range 20 - 28V 90 - 130V
Supply Current
Control Current
Operating Duty Continuous
Minimum Cycle Time 100ms
Contacts 10A at 240VAC resistive
Expected Relay Life
Operating Temperature -20° to +140° F
Humidity 0 - 97% w/o condensation
Mounting 12-pin socket *
Enclosure Material ABS plastic
Weight
261XBXPR-24
0.05A 0.01A
0.001A
Mech: 10 million operations
Elec: 100,000 at rated load
4.8 oz.
* order 12-pin socket number 51X156
261XBXP-120
261XBXPR-120
12/2012
© 2012 TIME MARK CORPORATION
2
L1
L2
L2
L2
L2
L2
L1
L2
5
CONTROL SWITCH
L1
MODEL 261XBXP (R)
TIME MARK is a division of
Alternating Relay
READ ALL INSTRUCTIONS BEFORE INSTALLING, OPERATING OR SERVICING THIS DEVICE.
KEEP THIS DATA SHEET FOR FUTURE REFERENCE.
GENERAL SAFETY
POTENTIALLY HAZARDOUS VOLTAGES ARE PRESENT AT THE TERMINALS OF THE MODEL 261XBXP(R).
ALL ELECTRICAL POWER SHOULD BE REMOVED WHEN CONNECTING OR DISCONNECTING WIRING.
THIS DEVICE SHOULD BE INSTALLED AND SERVICED BY QUALIFIED PERSONNEL.
Installation Instructions
INSTALLATION
Connect wiring to the socket as indicated in the following examples.
The Model 261XBXP(R) Alternating Relay is extremely versatile and can be used in many other configurations besides those shown. Any type of switch (float, pressure, etc.) can be used as the control switch; however, it must be connected as shown (from L1 to the control input) or the alternator will not function properly.
NOTE: When installing the Model 261XBXP(R) in areas of high humidity or contamination, it is recommended that the base area and all exposed metal parts of the socket be coated liberally with a good quality silicone grease, such as Dow Corning DC-4 or DC-4X. Insert the unit into the socket and wipe off excess grease around the base. This will prevent the entrance of moisture and other contaminants into the base and socket area.
PIN DIAGRAM
TYPICAL APPLICATION
TROUBLESHOOTING
Should the unit fail to operate properly, check to see that all voltage levels are present and are of the correct level. Verify that all connections are correct and securely attached to equipment. Should problems persist, contact the manufacturer at 800-862-2875 for assistance.
WARRANTY
This product is warranted to be free from defects in materials and workmanship, and is covered by our exclusive 5-year Unconditional Warranty. Should this device fail to operate for any reason, we will repair it for five years from the date of manufacture. For complete warranty details, see the Terms and Conditions of Sales page in the front section of the Time Mark catalog or contact Time Mark at 1-800-862-2875.
12/2012
© 2012 TIME MARK CORPORATION
Loading...