Time Mark 15 Data Sheet

MODEL 15
TIME MARK is a division of
Reverse Phase
Correction Relay
Senses and automatically corrects
for damaging phase reversal
Low power consumptionUnconditional 5-Year Warranty
DESCRIPTION
Under normal power conditions, incoming A B C voltage is passed straight through the device to the A B C output terminals (4 amps @ 480 VAC resistive maximum). If the unit detects an incoming reverse phase condition (C B A), it will light the reverse phase LED and internally switch 2 of the phases and pass the
If your load is higher than 4 amps @ 480VAC resistive, the Model 15 provides an auxiliary output relay to put in the control circuit of a remote reversing contactor. If phasing is correct, the relay will remain in the static condition (N.C contact will remain closed and N.O. will remain open). If the Model 15 detects a reverse phase input, the auxiliary output relay will energize and the relay contacts will switch (N.C contact will open and N.O. will close). Reversing the phases is done through
the wiring of the reversing contactor.
INSTALLATION
1. Mount the Model 15 in the desired location.
2. Connect the 3 - phase power to the input terminals marked A, B and C.
3. When using a reversing contactor, connect the control circuit to the Aux Output terminals and then to the reversing contactor. (Refer to the Typical Motor
Application wiring diagram for additional information).
SPECIFICATIONS
Model
Nominal voltage (phase to phase)
Operating range Frequency Power consumption Transient protection Repeat accuracy Response time Reset time Reset type Dead Band Output contacts (AUX)
Output contacts (3 Phase) Expected relay life
Operating temperature Humidity tolerance Case material Mounting Weight
15-240 15-480
240VAC 480VAC
± 10%
50 to 60Hz
2W per phase
2500V for 10ms
± 0.1% (fixed conditions)
.05 seconds .05 seconds
Automatic
Approximately 2%
SPDT 10A at 240VAC resistive 3P3T 4A at 480VAC resistive
Mechanical: 10 million operations Electrical: 100,000 at rated load
- 20° to +140° F
0 - 97% w/o condensation
NORYL
Surface Mount
15.9 oz.
11440 Ea s t Pi ne S tr ee t
Tu l sa , Ok lah o ma 7 41 16
05/2017
© 2017 TIME MARK CORPORATION
MODEL 15
TIME MARK is a division of
Reverse Phase Correction Relay
READ ALL INSTRUCTIONS BEFORE INSTALLING, OPERATING OR SERVICING THIS DEVICE.
KEEP THIS DATA SHEET FOR FUTURE REFERENCE.
GENERAL SAFETY
POTENTIALLY HAZARDOUS VOLTAGES ARE PRESENT AT THE TERMINALS OF THE MODEL 15.
ALL ELECTRICAL POWER SHOULD BE REMOVED WHEN CONNECTING OR DISCONNECTING WIRING.
THIS DEVICE SHOULD BE INSTALLED AND SERVICED BY QUALIFIED PERSONNEL.
Installation Instructions
TYPICAL MOTOR APPLICATIONS
DIMENSIONS
TROUBLESHOOTING
Should the relay fail to operate properly, check that all three voltages are present and are of the correct level. Check all fuses and verify that all wiring connections are correct. Should problems persist, contact the factory for
assistance.
WARRANTY
This product is warranted to be free from defects in materials and workmanship, and is
covered by our exclusive 5-year Unconditional
Warranty. Should this device fail to operate for any reason, we will repair it for five years from the date of manufacture. For complete warranty details, see the Terms and Conditions of Sales page in the front section of the Time
Mark catalog or contact Time Mark at 1-800-862-2875.
11440 Ea s t Pi ne S tr ee t
Tu l sa , Ok lah o ma 7 41 16
© 2017 TIME MARK CORPORATION
05/2017
Loading...