These instructions should be read carefully and retained for further reference
and maintenance.
2. Safety
• Before installation or maintenance, ensure the mains supply to the
thermostat is switched off and the circuit supply fuses are removed
or the circuit breaker turned off.
• It is recommended that a qualified electrician is consulted or used for the
installation of this thermostat and install in accordance with the current
IEE wiring and Building Regulations.
• Check that the total load on the circuit including when this thermostat is
fitted does not exceed the rating of the circuit cable, fuse or circuit breaker.
• To clean use a clean dry cloth only. Do not use any liquid cleaners.
3. Technical Specifications
• 230V AC 50 Hz
• This thermostat is of Class ll Construction and must not be earthed
1
• Switch Rating: 3(1)A
• Switch Type: Single pole, voltage free changeover
• Connection Type: 2 wire
• Installation Type: Surface mount with wall plate
• Micro Disconnection: Type 1.B control action
• Operating Temperature Range: 0°C to +40°C
• Set Temperature Range: 10°C to 30°C
• Temperature Swing Adjuster: +/- 0.5°C or 1.0°C set by DIP switch
• Frost Protection Mode: 5°C
• Night Set Back Mode: Lowers set temperature by
• PID Adjustment: ON or OFF set by DIP switch
contacts
4°C for 1-9 hours
Page 3
• Boiler Type Adjustment: 3CYC = Gas, 6CYC = Oil, set by DIP switch
• Illumination: Blue LED illuminated on setting for button
surrounds and display
• Batteries: 2x 1.5V AA
• CE Compliant
• Dimensions (H x W x D): 90 x 95 x 30mm
TRT033N Front View
Digital room temperature display
(illuminated on setting)
10°C to 30°C
23
set temperature
range
The heating symbol
will show when heat
is demanded
Night set-back (reduces temperature
by 4°C, 1-9 hours recall) and frost
protection setting mode
+/- setting
buttons
(illuminated
on setting)
Flip down cover for display battery
compartment and reset button –
uses 2x 1.5V AA batteries supplied
Page 4
4. Siting
• The TRT033N must be sited where it will not be influenced
by heat sources, for example above a radiator or a television or
a refrigerator/freezer or in direct sunlight or subjected to draughts.
• The product requires air circulation, so do not position above
or below shelving or other wall mounted obstacles.
• It should be mounted approximately 1.5 metres above floor level.
5. Installation
5.1 Ensure the mains supply is switched off and the circuit supply fuses
are removed or the circuit breaker turned off.
5.2 Remove the wall plate from the unit, by undoing the retaining screws,
and pivoting the bottom of the unit outwards. The TRT033N body
can then be lifted off.
5.3 Mark the position of the mounting holes on the wall using the wall plate
as a template. Drill out the mounting holes taking care to avoid any
joists, electrical cables or water/gas pipes that may be hidden beneath
the surface. Insert the rawl plugs into the holes.
5.4 Pass the 230V 50Hz mains supply and load cables through the opening
3
of the wall plate. Allow sufficient excess cable to wire up the unit, but
not too much to make it difficult to close the unit to the wall plate.
5.5 Fix the wall plate to the wall using the correct mounting screws for the
rawl plugs installed. The retaining screws which secure the unit to the
wall plate should be at the bottom.
5.6 Terminate the cables into the terminal block ensuring correct polarity
is observed and that all bare conductors are sleeved (See section 6.
Connection Diagram). Make sure that the curved washer grips
the conductor.
5.7 To insert batteries into the unit, first lower hinged flip down cover
and carefully lever the battery holder cover off. Insert the 2x AA
batteries supplied into the battery holder maintaining the correct polarity,
as shown in the base of the battery holder. Re-position the battery holder
cover and click into place.
Page 5
5.8 To reinstall the unit onto the wall plate, first ensure the wall plate
retaining screws are loosened enough to clear the TRT033N body,
then engage the top of the TRT033N onto the wall plate retaining tabs,
and push firmly downwards and then upwards. There will be some
resistance from the terminals.
5.9 Once in place, secure with the retaining screws making sure
not to over tighten.
TRT033N Wall Plate
Alternate mounting holes
Retaining tabs
4
Wall plate retaining screws
Loop terminal
Mounting
holes
Page 6
COM
230V AC
50Hz
MAINS
SUPPLY
6. Connection Diagram
Connect the 230V 50Hz mains supply and load cables to the terminal block
which are marked as follows;
• Note: Check boiler
instructions before
connecting.
NCNO
Switch Live from NO
(normally open contact
for heating) to bolier
5
230V 50Hz Mains Supply
Live Supply (Brown or Red) to L
A ‘Loop Terminal’ is provided should a 3 core cable
be used
Load (Boiler)
Switch Live (Brown or Red) to NO
BOILER
Supply
Neutral
Supply
Live
Page 7
7. DIP Switch Settings
• The temperature swing can be adjusted between 0.5°C and 1.0°C by
selecting the desired DIP switch position found on the rear of the unit.
We suggest using 0.5°C position unless the boiler turns ON and OFF
too rapidly. Press the reset button after changing.
• The PID ‘Proportional-Integral-Derivative’ can also be selected ON or OFF
using the DIP switches on the rear of the unit. We suggest setting this to
the ON position. As the room temperature approaches the set temperature,
the thermostat will intermittently turn the heating ON and OFF, to help
prevent temperature over-shoot. Press the reset button after changing.
• The boiler type can be set to either 3CYC (Gas) or 6CYC (Oil), using the
DIP switches on the rear of the unit. Press the reset button after changing.
TRT033N Rear of Unit
DIP switch for PID settingDIP switch for
6
boiler type setting
DIP switch for temperature
swing adjustment setting
Page 8
8. Operation
• Restore mains to the unit after making sure to check all system wiring
is complete, and after you have selected the desired DIP switch settings.
• Press the reset button located beneath the flip down cover on the front
of the unit, all of the characters will briefly appear on the display,
followed by the current room temperature.
• The default set temperature is 22°C.
7
Adjusting Set Temperature
• Use the +/- setting buttons to change the set temperature.
• The set temperature will flash while the change is being made.
• The set temperature change will be made in 0.5 degree increments,
and the +/- button surround and display light will illuminate upon setting.
• The set temperature and illumination will time out 5 seconds after the last
button press, saving your settings, and the display will revert to show the
current room temperature.
Page 9
• When the room temperature is below the set temperature, the heating
symbol will appear on the display to indicate output.
Heating symbol will show when
heat is demanded.
Frost Protection Mode
• Use the +/- setting buttons to change the set temperature.
• The display will show 1 hour flashing.
8
• Use the +/- buttons to set the desired hours, the button surround
will illuminate.
Page 10
• When the correct number of hours is selected, the display will time out
3 seconds after the last button is pressed. The display will then alternate
every 2.5 seconds between the number of hours of night set back
remaining, and the current room temperature. The Night set back
bed symbol will flash continuously whilst active.
The night set back bed symbol will
continuously flash when night set back
is active.
• Press the frost/night set back button once again to cancel.
Battery Low Indicator
9
• When the batteries are low, the battery low indicator comes on.
Battery low indicator will appear
when the batteries are low.
Page 11
3 Year Guarantee
In the unlikely event of this product becoming faulty due to defective
material or manufacture within 3 years of the date of purchase, please
return it to your supplier in the first year with proof of purchase and it
will be replaced free of charge. For the second and third years or any
difficulty in the first year telephone the helpline on 020 8450 0515.
Note: A proof of purchase is required in all cases. For all eligible
replacements (where agreed by Timeguard) the customer is responsible
for all shipping/postage charges outside of the UK. All shipping costs
are to be paid in advance before a replacement is sent out.
10
Page 12
If you experience problems, do not immediately
Telephone the Timeguard Customer Helpline;
return the unit to the store.
HELPLINE
020 8450 0515
or email helpline@timeguard.com
Qualified Customer Support Co-ordinators will be on-line
to assist in resolving your query.
For a product brochure please contact:
Timeguard Limited.
Victory Park, 400 Edgware Road,
London NW2 6ND
Sales Office: 020 8452 1112
or email csc@timeguard.com
www.timeguard.com
Zerofour – January 2018
67.058.600 (Issue 1)
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.