Timeguard TPT88 User Manual

UNDERFLOOR HEATING
CONTROLLER
Cat. No TPT88
INSTALLATION & OPERATING INSTRUCTIONS
1
Continuously OFF indicator
Normal operating (timed) mode
Probe failure indicator
Output to underfl oor heating ON
Periods of comfort temperature
Programme overview display
Continuous
control of
comfort
temperature
Temperature display - shows under-fl oor temperature
(except when Comfort and Economy temperatures are being set)
Day indicator (day 1 = Monday)
Programme
number
Introduction
The TPT88 is a combined temperature and time controller for electric underfl oor heating. It is rated at 16A (3.68kW). The unit controls to a fully adjustable comfort temperature during programmed ON times and to a fully adjustable economy temperature during OFF times. It does this by using the signal from an underfl oor probe (included). Both the economy and comfort temperatures can be set to a minimum of 7°C to give frost protection.
The large LCD display can be back lit if required at the press of a button. The display reverts to normal 15 seconds after the button is fi rst pressed.
24 hour time
display (also
indicated
copy in
Programming
mode)
Push to
illuminate
display
Fig. 1
Connections
The TPT88 must be used with the temperature probe provided. Connections are made to the unit according to the following diagram.
2
Siting
The TPT88 should not be installed in a wet area such as a bathroom or shower area. Further instructions are given in the Thermolay Cable and Mat instruction leafl et.
Installation
The installation should be carried out by a competent person following the latest I.E.E. wiring and local authority regulations in the UK or the relevant wiring and local authority regulations in other countries.
The TPT88 underfl oor heating controller is designed to fi t onto either a BS4662 recessed single box or a BS5733 surface mount single box. The minimum box depth required is 32mm. The ideal mounting height is at eye level for the shortest person who is likely to need to programme the unit. For details of the installation of the temperature probe and heating cable or mat see the Thermolay instruction leafl et.
Fig. 2
Fig. 3 Fig. 4
Switch OFF the mains to the controller. Remove the front of the thermostat by using a small screwdriver in the slot as shown in Figure 3.
Cut the cable tails of the temperature probe and heating mat or cables to length and strip sleeving and insulation as required. Identify the wires and locate according to fi gure 2. Supply cable with a minimum of
2
2.5mm
must be used. Tighten the screw terminals onto the wires and
form the cables. Offer the back plate up to the wall box forming the cables as required,
fi nally locating and tightening up the fi xing screws supplied as shown
3
in Figure 4. Snap the front of the thermostat back into position on the back plate. To test the unit is operating set the temperature to 30ºC as described
in the section “Timed override for Two Hours“. After a few seconds the Heating ON indicator will show.
Wait for a one hour for a wood underfl oor or up to 5 hours for an uninsulated concrete fl oor (the warm-up time for uninsulated concrete will be substantially reduced when the moisture has been driven out of the concrete during the fi rst few heating cycles) and feel if the fl oor starts to warm. If it does not, check the connections and carry out the checks on the mat or cable installation instructions.
Earthing
The TPT88 itself does not require to be earthed. The screen around the fl ying lead (cold cable) from the Thermolay mat must be earthed to the box terminal. This also applies to the screen at each end of the Thermolay cablee, both of which must be earthed in the same way.
Loading...
+ 8 hidden pages