5.8 Using the back box as a template mark the position for the holes.
Note the back box must be mounted in the correct orientation,
following the ‘TOP’ marking inside the back box. If the mounting
position desired is uneven use a sheet of marine ply as a base plate
and fit the back box.
5.9 Drill the wall using a 4mm Ø drill bit making sure not to infringe
or compromise any gas, water pipes or cables. Insert the rawl
plugs into the holes.
5.10 The drain feature must be drilled out using a 5mm drill bit if the top
or side entry conduit is used. Opening this drain hole will reduce
the IP rating of the product. Only the lower drain feature on the
back box must be opened.
5.11 Select the required entry point by unscrewing the appropriate
seal located on all four sides of the back box. If conduit is not
going to be used, a waterproof cable with suitable rated 20mm
glands will be required to maintain the overall IP rating. If the
bottom entry conduit is used, there must be adequate drainage
from the lowest point of the conduit.
5.12 Secure the back box to the wall using suitable screws for the rawl
plugs installed. Ensure that the back box is correctly orientated
following the ‘TOP’ marking which is labelled inside.
5.13 Pass through the 230V AC 50Hz mains supply cable and secure
the cables tightly to their respective terminals, ensuring that all
bare conductors are sleeved and that correct polarity is observed.
Note that if metal conduit is used the earth continuity between
the conduits must be maintained.
5.14 Once the mains supply is connected to the correct terminals,
mount the face plate to the four mounting holes on the back box.
Tighten until secured.