1. General Information
These instructions should be read carefully and retained for further
reference and maintenance.
2. Safety
• Before installation or maintenance, ensure the mains supply to the
alarm system is switched off and the circuit supply fuses are removed
or the circuit breaker turned off. Remove all power sources when
wiring any part of the system.
• It is recommended that a qualified electrician is consulted or used
for the installation of this alarm system and install in accordance
with the current IEE wiring and Building Regulations.
• Check that the total load on the circuit including when this alarm
system is fitted does not exceed the rating of the circuit cable,
fuse or circuit breaker.
• None of the units in the system should be subject to dripping or
splashing liquids.
• To clean use a clean dry cloth only. Do not use and liquid cleaners.
3. Technical Specifications
• Control Unit Supply Voltage: 230V AC 50Hz
• Zone Components Supply Voltage: SELV (24V)
• This Control Unit is of class I Construction and must be earthed
• The individual components are class III and must not be earthed
• Maximum pull force on Pull Cord: 200N
• Pull Cord Length: 2m (including 2 red bangles)
• Reset button marking: Visually and with Braille
• Intensity of sounders:
Control Unit: 80dB at 30cm (continuous)
Over-Door Unit: 80dB at 30cm (continuous)
• LED Indicators:
Control Unit: Green ‘Power ON’, Blue ‘Alarm’
Over-Door Light: Blue illuminates during alarm only
Reset Unit: Blue illuminates during alarm only
Pull Cord Unit: Blue illuminates during alarm only
Angular Coverage of Indicator: 180° on Over-Door Unit